Hager JK104BG, JK106BG, JK108B, JK124B, JK118BG Installation Instructions

...
ZD0675 issue 3ZD0675
Invicta 3
GB
JK1***B JK2***B
Notice d’instructions User instructions Bedienungsanleitung Instrucciones de uso Instruções Bruksanvisning Gebruiksaanwijzing
All product(s) must be installed by a suitably competent electrician giving consideration to their intended use and in accordance with the current edition of BS 7671 (IET Wiring Regulations).
Pozidrive PZ2
2.5
2.5mm
The Electricity at Work regulations and the Health and Safety at Work Act shall be complied with.
Only equipment and arrangements specied in Hager’s technical documentation / catalogue shall be used
Install in the vertical plane only.
Notice: To prevent potential overheating from loose connections the installer shall check connections are tightened to the torque levels stated in these instructions prior to energising this board. This check should include factory made connections which may have loosened in transit.
Pozidrive PZ2
ZD0675 issue 31
Pozidrive
2.5mm
PZ2
Points with central ‘easy t’ xing point
Removal of gland plate
Pozidrive PZ2
Cut tabs and remove insert when using gland larger than 32mm
Drill centre mark provided when tting SWA or conduit
Use product carton / packaging to reduce the swarf when
removing end plate section
Cable protection built into end plate for trunking entry
2 ZD0675 issue 3
L2
8
ISOLATE SUPPLY
BEFORE REMOVING COVER
When tting to trunking, use the endplate
Pozidrive PZ2
2.5mm
cut-out lines as a template for the hole in the trunking
Protected cable whilst drawing into board without need for SRBP / Paxolin laminated sheet
Fitting MCB / RCBO
Pozidrive PZ2
T = Min. 2.8Nm Max. 3.5Nm
1
2
1
2
L2
3
L3
4
L1
10
5
L2
6
L3
11
12
Ability to number outgoing ways
on busbar stack
ISOLATE SUPPLY
BEFORE REMOVING COVER
L1
7
L1
7
8
9
Dedicated label pack for front cover way labelling
1
L2
L1
9
8
7
Lighting
Supply
Sockets
First Floor
Meter kits t directly into the main board.
See overleaf for list of meter kits.
Ability to write on with pencil when installing.
3 ZD0675 issue 3
Interface Characteristics
Rated & operational voltage (Un / Ue)
415V a.c. 50Hz
Rated insulation voltage (Ui)
690V a.c. 50Hz
Rated impulse withstand voltage (U
4kV
Rated current of the Assembly (InA)
JK1xxx 125A JK2xxx 250A
1
or rating of incoming circuit / incomer kit whichever is lower
Rated current of an Outgoing circuit (InC)
MCB 0.5A - 63A (marked rated current on device) RCBO 6A - 50A (marked rated current on device)
Rated conditional short-circuit current of the ASSEMBLY (Icc)
10kA1 with equipment and arrangements specied in Hager’s technical documentation / catalogue.
MCB/RCBO 10kA rating applied as BS EN 61439-3 is intended for use by ordinary persons.
1
Current limitation characteristics specied in Hager’s technical
documentation / catalogue
Protection against electric shock
DBO shall be installed in an electrical system conforming to IEC 60364 / BS 7671
Rated diversity factor (RDF) / Values of assumed loading
4 way = 0.7 6 way - 8 way = 0.6 10 way - 24 way = 0.5
Note: RDF only applies to continuously and simultaneously loaded circuits.
Rated frequency (fn)
50 Hz
Pollution degree
2
Type s o f sys tem e art hin g for w hic h t he AS SEM BLY is d esi gn ed
TNC-S, TN-S and TT when installed in an electrical system conforming to BS 7671
Intended locations
Indoor use only
Stationary ASSEMBLY
Degree of protection
IP3XD with Door Closed IP2XC with Door Open and compliment of outgoing devices and or blanks tted.
Intended use
Distribution boards intended to be operated by ordinary persons (DBO)
Electromagnetic compatibility (EMC) classification
EMC Environment B
External design
Wall-mounte d, surface type, enclosed assembly.
Mechanical impact protection
IK05
The type of construction
Fixed parts
DBO Type
Ty pe B D BO
1
1
imp
)
Warranty
This distribution board is offered with a 24 month warranty against defective material or manufacture. If a warranty claim is necessary, please call the technical support number given at the bottom of the page and we will be pleased to help.
Designation H W D Weight (kg)
JK104B/BG 500 465 132.5 11
JK106B/BG 550 465 132.5 12
JK108B/BG 625 465 132.5 14
JK112B/BG 850 465 132.5 16
JK116B/BG 950 465 132.5 19
JK118B/BG 1100 465 132.5 20
JK124B/BG 1250 465 132.5 22
JK208B/BG 950 465 165.5 14
JK212B/BG 1100 465 165.5 16
JK216B/BG 1250 465 165.5 20
JK218B/BG 1400 465 165.5 21
JK224B/BG 1550 465 165.5 23
JK1 Incomer Kits
Cat ref. No of Poles Description
JK11003S 3 Switch Disconnector 100A
JK11004S 4 Switch Disconnector 100A
JK11253S 3 Switch Disconnector 125A
JK11254S 4 Swtich Disconnector 125A
JK10634C 4 Contactor 63A
JK11004C 4 Contactor 100A
JK11254D 4 125A Direct Connection
JK10634RH 4 RCCB 63A 30mA
JK11004RH 4 RCCB 100A 30mA
JK11004RL 4 RCCB 100A 300mA
JK11004RLD 4 RCCB 100A 300mA (Time Delayed)
JK11004RM 4 RCCB 100A 100mA
JK11004RMD 4 RCCB 100A 100mA (Time Delayed)
JK11254CO 4 Changeover Switch 125A
Meter Kits
Cat ref. Description
JK140MP Digital Multi Function Meter Pack Pulsed
JK140MJ Digital Multi Function Meter Pack Modbus
JK240MP Digital Multi Function Meter Pack Pulsed
JK240MJ Digital Multi Function Meter Pack Modbus
JK107DL 7 Input Data Logger with TCP/IP
JK2 Incomer Kits
Cat ref. No of Poles Description
JK21003S 3 Switch Disconnector 100A
JK21004S 4 Switch Disconnector 100A
JK21253S 3 Switch Disconnector 125A
JK21253MC 3 MCCB 125A
JK21254MC 4 MCCB 125A
JK22503MC 3 MCCB 250A
JK22504MC 4 MCCB 250A
JK22503S 3 Switch Disconnector 250A
JK22504S 4 Switch Disconnector 250A
JK22504D 4 250A Direct Connection
JK21604C 4 Contactor 160A
Accessories
JK250SP 250A Single Phasing Kit
JK01B Single Pole Blank
JK222PK JK1 / JK2 Door Lock Kit
JK1PLATEM Gland Plate + Drill Markings
JK2PLATEM Gland Plate + Drill Markings