Hager JK11254D Installation Instructions

JK11254D Invicta 3
Instruction leaflet for fitting a 4 pole direct connection kit
Locate and clip the 4 x KR125U (A) connectors onto the DIN rail (B). Fit phase and neutral links as shown. Fit neutral and phase links to busbar at fixing points (C). Ensure these connections are tightened to 5Nm. Connect the incoming cables at fixing points (D), ensuring these connections are tightened to
3.5Nm Remove the left side cutout from the main incomer shroud (E) and fit to the pan assembly with the fixing points (F)
(A)
(C) 5Nm
(D)
3.5Nm
(B)
8mm
(E)
(F)
JK11254D Invicta 3
Direct connection kit
Qty Description
1 Terminal shield
4 KRN199 connection terminals
4 Links
3 M5 carp nuts
1 M6 carp nuts
Hager Ltd
Hortonwood 50 Telford Shropshire TF7 7FT
National Sales Hotline 01952 675612 National Tech Support helpline 01952 675689 Website: www.hagergroup.co.uk Email us @: info@hager.co.uk