Hager JK11003S, JK11253S Installation Instructions

Locate the incomer switch (A) onto the left side of the DIN rail (B), and fit the L1, L2 and L3 incomer links. Ensure that the links teeth are within the top terminal of the incomer switch. Ensure the caged neutral link (C) is secured to the neutral cross link using the M6 carp nut and tightened to 5Nm. Use the M5 carp nuts for the phase connections and tightened to 5Nm. Ensure that all terminal connections on incomer switch (D) connections are tightened to 3.6Nm.
Ensure the connections on the busbar links (E) are tightened to 5Nm (3 x Phase and neutral) After terminating incoming cables fix the main incomer shroud (F) to the clip in fixing points (G).
Invicta 3 JK11003S / JK11253S
Instruction leaflet for fitting an incomer isolator / switch
F
E (5Nm)
D (3.5 Nm) C
A
G
G B
8mm
JK11003S Invicta 3
Incomer isolator kit
Qty Description
1 Terminal shield
1 100/125A 3P modular switch
3 Incomer links
3 M5 carp nuts
1 Caged terminal & M6 carp nut
Hager Ltd
Hortonwood 50 Telford Shropshire TF1 7FT
National Sales Hotline 01952 675612 National Tech Support helpline 01952 675689
Website: www.hager.co.uk Email us @: info@hager.co.uk
ZD0680 issue 12