Hager JK11004S, JK11254S Installation Instructions

In
struction leaflet for fitting
incomer
Invicta 3 JK11004S / JK11254S
Locate the incomer switch (A) onto the left side of the DIN rail (B), and fit the L1, L2 and L3 incomer links. Ensure that the links teeth are within the top terminal of the incomer switch. Ensure the cranked neutral link (C) is inserted into the left most termination on the incomer switch and use the M6 carp nut to secure to the neutral cross link. Use the M5 carp nuts for the phase connections
C
E (5Nm)
D (3.5 Nm)
8mm
Ensure that all terminal connections on incomer switch (D) connections are tightened to 3.5Nm. . Ensure the connections on the busbar links (E) are tightened to 5Nm (3 x Phase and neutral) After terminating incoming cables fix the main incomer shroud (F) to the clip in fixing points (G). Remove additional breakout left of the shroud to ensure the switch protrudes through the main incomer shroud.
A
A
F
B
G
G
JK11004S/ JK11254S Invicta 3
Incomer isolator kit
Qty Description
1 Terminal shield
1 SB499 100A 4P modular switch and DIN rail
4 Incomer L1, L2, L3 & N (to fit M6 stud link
3 M5 carp nuts
1 M6 carp nut
Hager Ltd
Hortonwood 50 Telford Shropshire TF7 7FT
National Sales Hotline 01952 675612 National Tech Support helpline 01952 675689
Website: www.hagergroup.co.uk Email us @: info@hager.co.uk
ZDO681 issue 7