struction leaflet for fitting
Invicta 3 JK11004S / JK11254S
Locate the incomer switch (A) onto the left side of
the DIN rail (B), and fit the L1, L2 and L3 incomer
links. Ensure that the links teeth are within the top
terminal of the incomer switch.
Ensure the cranked neutral link (C) is inserted into
the left most termination on the incomer switch
and use the M6 carp nut to secure to the neutral
cross link. Use the M5 carp nuts for the phase
connections
C
E (5Nm)
D (3.5 Nm)
8mm
Ensure that all terminal connections on
incomer switch (D) connections are
tightened to 3.5Nm. . Ensure the
connections on the busbar links (E) are
tightened to 5Nm (3 x Phase and neutral)
After terminating incoming cables fix the
main incomer shroud (F) to the clip in fixing
points (G). Remove additional breakout left
of the shroud to ensure the switch protrudes
through the main incomer shroud.
A
A
F
B
G
G

JK11004S/ JK11254S
Invicta 3
Incomer isolator kit
Qty Description
1 Terminal shield
1 SB499 100A 4P modular switch
and DIN rail
4 Incomer L1, L2, L3 & N (to fit M6 stud link
3 M5 carp nuts
1 M6 carp nut
Hager Ltd
Hortonwood 50
Telford
Shropshire
TF7 7FT
National Sales Hotline 01952 675612
National Tech Support helpline 01952 675689
Website: www.hagergroup.co.uk
Email us @: info@hager.co.uk
ZDO681 issue 7