Hager JF406B, JF408B Installation Instructions

Installation instructions Notice d’instructions Bedienungsanleitung Instrucciones de uso Instruções Bruksanvisning Gebruiksaanwijzing
Invicta 3 Panelboard
ZD0740 issue 3a
All product(s) must be installed by a suitably competent electrician giving consideration to their intended use and in accordance with the current edition of BS 7671 (IET Wiring Regulations).
The Electricity at Work regulations and the Health and Safety at Work Act shall be complied with.
Only equipment and arrangements specified in Hager’s technical documentation / catalogue shall be used
Install in the vertical plane only.
Notice: To prevent potential overheating from loose connections the installer shall
check connections are tightened to the torque levels stated in these instructions prior to energising this board. This check should include factory made connections which may have loosened in transit.
Page 1
ZD0740 issue 3a
Fixing points with central keyhole
Page 2
400A Incomer kits contain:
3 x Phase extension links
3 x spreader links
6 x Phase link Allen fixing bolts and washers (M10)
4 x Long fixing screws
1 x MCCB/ MCS
Terminal covers
Ensure terminal shrouds are removed before fitting.
JF4 3 Pole 400A MCCB/MCS incomer kit
ZD0740 issue 3a
1
2
Connect the extension links to the busbar with the 3 x M10 coach bolts. Hand tighten at this stage. Now tighten the MCCB fixing screws to secure the MCCB to the pan assembly.
Once the MCCB is in place tighten all M10 electrical connections to 22Nm Fit the terminal shrouds
17 mm A/F
8 mm HEX
Fit the MCCB to the pan assembly with fixing screws provided
Fit the extension links (A) to the MCCB with the Allen fixings
Fit the spreader links to the bottom of the |MCCB (B) with the fixings provided