Hager EG203 User Manual

prog
new
On
2
4
1
812
60
ok
ok
menu
+
A B
1
2
34
L N
1357
2468
6LE002460A
EG203, EG203B
Major characteristics
• Product delivered with current time and date set.
• Automatic change of winter / summer time .
• Programming key .
- for permanent waivers,
- for program copy or save.
• Programming for day or group of days.
• 56 program steps On, Off.
• Permanent overrides On or Off ( permanent light on).
• Temporary overrides On or Off ( flashing).
• Display bar graph of daily profile for both channels.
• Keyboard locking possible .
• Programmable with power off.
Resetting the program
The program can be totally deleted by pressing the following three keys simultaneously:
menu, ok, , the time and date are retained.
Reboot
Pressing the -, +, ok, menu keys simultaneously reboots the product.
EG005
Programming: prog new
Programming may be done for each day or for a group of days. In this case instructions arecommon to several days. Days: 1 = Monday, 2 = Tuesday, 3 = Wednesday
..... 7 = Sunday.
¢
z
channels electronic
2 time switch weekly cycle
echnical specifications
T
Electrical characteristics
• Supply voltage: 230 V~ +10%/-15% 50/60Hz
240 V~ +/-6% 50/60Hz
• Frequency: 50/60 Hz
• Power consumption: max. 6 VA à 50 Hz
• Output: 2 changeover volt free contacts
• Maximum load
AC1: µ16A 230 V~ Cos φ = 0,6: µ10A 230 V~ Incandescent lighting: 2300 W Halogen lighting 230 V~: 2300 W Compensated fluorescent tubes // (max. 45 µF): 400 W Non compensated fluorescent tubes, compensated in series: 1000 W Compact fluorescent lamps: 500 W
• Minimum current.
AC1: 100 mA 230 V~
• Galvanic insulation between power supply
and output: < 4 kV
• Rated impulse voltage: 4 kV
• Upstream circuit breaker: 16 A
• Size: 20 (17,5 mm x 2)
• Max. altitude: < 2000m
• Voltage and current declared for the needs of
EMC emissions tests: 230 V~ / 0,5 A
Independent panel-mounted (DIN rail) control device
1. Select the prog mode using menu, then ok.
2. Select the channel (A or B) using + ou -, then ok. The number of remaining program steps appears for a short time.
3. Choose the day(s) using + or -. Validate with ok.
4. ok flashes. Use ok to validate the group of days - or makes it possible to reset the group of days if necessary
5. Using + or -, select the state of the instruction: On, or Off . Validate with ok.
6. Enter the time of switch-on using + or -. Validate with ok.
7. Enter minutes with + or -. Validate with ok.
Functional characteristics
• Programming capacity: 56 pas
• Minimum time between 2 steps: 1 minute
• Running accuracy: ± 1,5 sec. / 24h
• Operating reserve lithium battery provides 5 years of backup.
• The product is set into standby state (display switched-off) after 1 minute withpower off. It switches back into auto mode as soon as power is back or when pressing any key.
• Protection degree: IP 20
• Action type: 1B
• Degree of pollution: 2
Program the other instructions of the group of days by repeating operations 3 to 7.
The day or the group of days may be modified at the during step 3 by pressing the +, - or .
At the end of programming return to auto modeusing the menu button. To set the program of the other channel, return to prog new mode and proceed according to steps 2 to 7. In this mode it is also possible to add an instruction to the program set up. Proceed as described above.
• Software structure: class A
Keys:
1 menu : selection of operating mode
auto : mode of running according to
prog new for programming mode. prog modif to modify an existing program.
: checking of the program. : modification of time, date and
selection of the winter / summer time change mode .
2 + and - : navigation or setting of values.
A : in auto, mode, selection of overrides, B or waivers
3 ok : to validate flashing information
on display.
4 : to return to the previous step.
You may return into auto mode at any moment using menu. If no action is taken for 1 minute, the switch returns into auto mode.
Environment
• Operating temperature: -5 °C to +45 °C
• Storage temperature: -20 °C to +70 °C
Connection
• Flexible capacity: 1 to 6 mm
• Rigid capacity: 1,5 to 10 mm
Connection diagram:
2 2
Display
To check the daily profile set up without the risk of modification or deletion: Select the mode using menu and press ok. Select the channel (A or B) using + or - and ok. The first step of Monday is displayed as well as the daily profile.
Two options available for display:
1. Pressing repeatedly + or -: lets you shift days. In this case only the first daily step is displayed as well as the daily profile.
2. Pressing ok: all steps of each day appear one after the other.
Modification or clearing of a program step : prog modif
Select the prog mode with menu and press ok. Select the channel (A or B) using + or - and ok. Select the modif mode with + or -. Validate with ok.
The number of remaining program steps appears for a short time. The first step of the first day or group of days appears. Repeatedly pressing the ok key displays all programmed steps one at a time.
Any flashing field (state, hour, minutes) may be modified using + ou -, then validated with ok.
When the cursor is positioned on ok located behind the group of days, you may display successively the days or the groups of days and switch directly to the one that has to be modified using + or -. To remove a program step: select the state of the channel (On or Off ), press simultaneously + and -.
Key
As soon as the key appears on the switch appear on the screen.
Two types of operation:
A. Permanent override:
Insert the key into the switch. After 10 seconds the program contained in the key will be executed without clearing the program contained in the time switch. As soon as the key is removed the program of the time switch is again valid.
B. Copy (load) / Save (save):
The key makes it possible to save a program contained in the time switch. It is also possible to copy the contents of the key into the clock.
1. Insert the key and wait for 2 seconds.
2. Using menu select the mode: save to save a program contained in the time switch, load to load the program of the key into the time switch,
to check the program contained in the key.
3. Validate the selection with ok.
4. For save and load reconfirm with ok.
The following error messages may appear on the screen:
• no prog: the key is empty, it does not contain any
program.
• Error: the key is that of a one-channel switch.
In these two cases:
• Only the save is possible.
• The error message remains on display as long as
the key is present, but in this case the program of the time switch is executed.
Setting time and day Winter / summer time change
Select the mode with menu then ok. Modify the day, month, year, the hour and the
minutes using + or - and ok. The time switch next suggests the winter / summer
time changes . Select the type of change desired using + or - . Validate with ok.
The type of change depends on the geographical zone.
Types available:
Start of time
Type
change Summer
Last Sunday
Euro
of March
*
Second Sunday in
USA
March
First Sunday in
AUS
October
Date freely
USER
programmed
No change No change
No
type according defect
*
Start of time change Winter
Last Sunday of October
First Sunday in November
First Sunday in April Australia
Date freely programmed
Zone of application
European Union
North America
The change always takes place between 2:00 and 3:00 a.m.
When the USER type is selected:
1. Enter the day then the month of the date of change of the summer time (+ 1hour) with + or ­and ok.
2. Enter the day then the month of the date of change of the winter time (- 1hour) with + or ­and ok.
The time switch will check which days of which weeks correspond to these dates and will apply changes to the same periods for the following years independently of the date.
Clear appears on the screen. Validate with ok.
Override
Pressing repeatedly A or B If the state of the output is On :
t
s
1
pressure: temporary waiver. Off and
flash. The next program step will let you return to the automatic
d
n
2
pressure: permanent override. On and
mode.
are permanent. This override
d
r
3
pressure: permanent override. Off and
must be cancelled manually.
are permanent. This override
h
t
4
pressure: return to the automatic mode.
must be cancelled manually.
Locking
To prevent all undesirable actions, the keyboard of the time switch may be locked using a key EG004. Unlocking is done in the same way.
Correct Disposal of This product (Waste Electrical & Electronic Equipment).
(Applicable in the European Union and other European countries with separate collection sys-
tems).
This marking shown on the product or its literature indicates that it hould not be disposed with other household wasted at the end of its working life. To prevent possible harm to the envi­ronment or human health from uncontrolled waste disposal, please separate this from other types of wastes and recycle it responsibly to promote the sustainable reuse of material resources. Household users should contact either the retailer where they purchased this product, or their local government office, for details of where and how they can take this item for environ­mentally safe recycling. Business users should contact their supplier and check the terms and conditions of the purchase contract. This product should not be mixed with other commercial wastes of disposal.
Usable in all Europe
This device must be installed only by a qualified electrician according to the installation standards in force in the country.
z
Warranty
A warranty period of 24 months is offered on hager products, from date of manufacture, relating to any material of manufacturing defect. If any product is found to be defective it must be returned via the installer and supplier (wholesaler). The warranty is withdrawn if:
- after inspection by hager quality control dept the device is found to have been installed in a manner which is contrary to IEE wiring regulations and accepted practice within the industry at the time of installation.
- The procedure for the return of goods has not been followed. Explanation of defect must be included when returning goods.
NOT APPLICABLE FOR AUSTRALIA
and in Switzerland
å
Hager Controls S.A.S., 33 rue Saint-Nicolas, B.P. 10140, 67703 SAVERNE CEDEX, France - www.hager.com
4 6LE002460A3
Hager 09.16
Loading...