Overlap
* The light measurement accuracy (Lux) is
affected by the environment (furniture, ground,
walls...). If necessary, the level has to be adjusted by potentiometer or remote control.
Instances of lighting levels
Remote control for settings
The installer remote control EEK001
can be used to set the following
features if the potentiometer is set on
"auto test" :
- Lux levels ( )
- Time ( )
- Absence/presence detection
- Power up behaviour
Override remote control
The user remote control EEK002 allows
operators to :
- Switch on/off the light (short press),
()
- Dim up/down the light (long press
>0,5s.).
- to control scenes
, , ,
A short push recalls a luminosity level and
a long push (5s.) memorizes a new level.
Position of
potentiometer
Lux value
approximate *
Application
auto test preset
(≈ 400Lux)
1 200 Corridor
>1 ... 2 < > 200 ... 400 <
2 400 Offices
>2 ... On < > 400 ... 1000 <
On 1000 Offices
Product description and operating
principles
Occupancy sensors EEK are presence
detectors designed to detect low level
movements (e.g. person sitting at a desk).
Different models are available :
- without lead : EEK520B for stand alone and
BESA box mounting,
- with pre-wired lead (3m) : EEK523W for use
with the KDCS marshalling boxes.
- with pre-wired lead (3m or 5m) and
klik.system plug to be interfaced with the
KLMB marshalling boxes : EEK52.P.
Detection is by means of a pyro-electric sensor
located under the detection lens.
The occupancy sensor measures the
brightness in the room on a continuous basis
and compares it to the level preset on the
potentiometer 1 (or by means of the remote
control EEK001).
Settings
The Lux threshold and time out period can be
set with the potentiometers or by using the
installer remote control (EEK001).
Test Mode - Walk test
This mode makes it possible to validate the
detection area. To select this mode, set the
potentiometer
1 to the position "auto test".
The green or red LED behind the lens is on for
2 seconds after detection.
The red LED indicates that the light level
measured is lower than current setting.
If the green LED is on, the light level measured
is higher than current setting.
There is a time out of 2 minutes which is
reactivated after each detection.
The output is also switched during 2s. after
each detection.
It is also possible to use the remote control
EEK001 to set the detector in test mode.
Functional modes
The detector has 2 different modes.
- Presence detection (automatic).
- Absence detection (semi-automatic)
The power up and cell operation can be set for
each mode.
Presence detection (automatic mode)
In this mode the light is controlled by motion in
the detection area and ambient light levels.
If presence is detected whilst the light levels are
below the required Lux level, the sensor is
activated and regulates the light whilst there is still
occupancy and for the time out period afterwards.
Once the sensor has deactivated the lights, it will
require new occupancy whilst the ambient light
levels are below the required Lux level to activate
the lights again.
This mode can be changed via the IR remote
control EEK001 (default mode is presence
detection : automatic).
Absence detection (semi automatic mode)
The sensor needs to be activated by a normally
open retractive switch or a user remote control
EEK002 input.
Once the sensor is activated, it will regulate the
lights whilst there is still occupancy and for the
time out period afterwards.
Once the sensor has deactivated the lights, it will
require another input from the wallswitch or the
remote control to switch the lights on.
Power Up
A parameter of the detector allows the choice of
state for the lighting after power up (mains return).
During warm up phase, the green or red LED blinks.
In the Power up ON state, the lighting will automatically be energised when mains power is initially
supplied or returned to the sensor.
In the Power up OFF state, the lighting will not
be energised and the sensor will not operate
during warm up period.
This parameter is modified using the installer
remote control EEK001.
States :
• ON : The light is immediately switched on for 30s.
after power up.
In case of detection, the light (in automatic mode)
remains on during the time delay; otherwise the
light is switched off.
• OFF : The detector switches to the selected mode
after warm up.
DALI/ DSI recognition
The green LED blinks for this period if a DALI load
is recognised.
The red LED blinks continuously in case of DALI
bus error (unplugged wiring, ...) or DSI load.
Lighting regulation modes
In association with Digital Regulating Ballasts
(DALI and DSI), these products offer lighting
control functions.
The used protocol is automatically recognised.
Adjustment potentiometers are used to select
the operating mode of the occupancy sensor.
• Mode 1 : regulation active in auto mode
• Mode 2 : regulation active with local set point
• Mode 3 : regulation not active.
Mode 1 : regulation active in automatic mode
After detection, the DALI/DSI output controls
the lighting level according to the value set,
using the pushbutton input or the remote
control. This value is memorised as the new
setpoint.
The default set point is 400 lux.
The output is controlled for the time set by the
potentiometer
2.
Mode 2 : regulation active with local set point
(potentiometer).
After detection, the DALI output controls the
lighting level according to the value set by the
potentiometer
1 or the remote control.
This level can be temporarily adjusted via a
pushbutton. The light level is fixed.
The output is controlled for the time set by the
potentiometer 2.
Mode 3 : regulation inactive.
During presence detection, the detector
controls its output at a preset level (100%
by default), which can be modified by a
pushbutton. The new instructions are saved.
The output is controlled for the length of time
set by the potentiometer
2 or the remote
control.
At the end of this time delay, the output is set
to a minimum level for 15 min. and is then
switched off.
Use of override input
A connected remplacer par normally open
retractive switch can be used to
modify the state of the output.
Short presses override the state of output for
the time period set by the potentiometer
2.
Long presses are used to modify the level of
dimming or the level of brightness (according
to the mode).
Action Settings Potentiometer
Use Auto settings
(factory) or set by
the remote control
to switch the light
automatically for a
defined time.
Auto Settings
Put the Lux potentiometer on “auto test”.
The settings are predefined :
Lux = 400,
time = 20 min,
: test mode for 2 min.
Remote control settings EEK001
(manual settings inhibited).