Example of
Klik 7 pin
a page title
IR commissioning remote control (EEK001)
Use
The remote control allows the user to set or
modify presence detector settings. When the
potentiometer is on auto test it allows single
and multiple settings.
The SET key is used to send the IR messages
to the occupancy sensors. Multiple settings
can be stored in Memo 1 and Memo 2 and
re-called to set several devices.
Single setting
Example: reset
Multiple settings
Dene the parameters to be changed and
press SET to send.
The acknowledgment
LED blinks during
the sending of the IR
message.
Settings available
Key Meaning Indication Function
Presence Green LED on Presence on (automation mode)
Absence Red LED on Absence on (semi automatic mode)
Power Up Green LED on The light is automatically switched on for 30
Reset LED on To return to factory settings (Lux = 400, time
Test LED on To validate the detection area
Technical specification
Power supply:1x 3V CR2032
Shelf life of battery: 2½ years
Protection index: IP 30
Red LED on During warm up phase, the light output is off
Example: for 25 minutes and corridor use,
press 20’, 5’ and corridor.
In the case of 2 opposite states the green LED
denotes ON and red LED denotes OFF (except
Presence / Absence).
When no function is selected all LED’s are OFF.
seconds after power up
= 20 min, presence on, power up off and cell
active)
+
+++
Time LED on To set the time
Day level
1000 Lux
Learn LED on To learn the current Lux level
Corridor
200 Lux
Ofce
400 Lux
Lux + LED on To increase the Lux level (+100)
Lux - LED on To decrease the Lux level (-100)
Active cell Green LED on The light is continuously measured
Passive cell RED LED on The sensor will not switch the light off even if
Memo and set Key Meaning Indication Function
Press LED is on until a setting is changed To load/unload Memo 1
Long press LED is on for 5s, then will blink until
Press LED is on until a setting is changed To load/unload Memo 2
Long press LED is on for 5s, then will blink until
Short press (<5s) LED ashes To send an IR message of the current setting
Long press (>5s but <10s)
only available if no setting
active
LED on To set the value to 1000 Lux
LED on To set the value to 200 Lux
LED on To set the value to 400 Lux
released. After release, the LED goes
off in case of setting change
released. After release, the LED goes
off in case of setting change
LED blinks until release press To toggle automatic mode on DALI/DSI
It is possible to add times together e.g. press
2’ and 5’ for a time value of 7’
the ambient luminosity is sufcient
To save the current setting as Memo 1
To save the current setting as Memo 2
9.34
General Catalogue • klik • Technical