hager TRE530, TRE531, TRE510, EE855, TRE511 User Instructions

...
6LE003093A
TRE51., TRE53.
z
Motion Detectors
solar 220°
User instructions
¨
Description
Detection zone
Installation
Adjustments
Shutters
Angle fixing support
Optimal installation height is 2.5m. The detection zone shall remain free of obstacle.
m 8 m 16
m 2,5
m 0,5
m 16
m 4
LED A LED B
Delay (lighting time)
Brightness
level
Sensitivity (change of range)
1
2
Wall fixing plate
Adjustment potentiometers
Directional detection head
Vertical adjustment
DETECTORS 220° TRE510 White TRE511 Anthracite TRE530 White TRE531 Anthracite
ACCESSORY FOR
ANGLE FIXING EE855 White EE856 Anthracite 52125 White 52126 Anthracite
6LE003093A1
V2.6.0
RFTP
230V~
Bus
30 V
Button J
cfgcfg
cfg
LED C
Button J
Warning :
This device is to be installed only by a professional electrician fitter according to local applicable installation standards.
Test and validation of detection zone
Set potentiometer 2 to Test mode. The Test mode is available for 3 minutes time and does not take brightness level into account. Each detected movement turns LED A on for 2 seconds. The associated receiver is not under control. After 3 minutes without detection, the product is set back to auto mode. Limitation of detection zone : You can limit the detection zone using the shutters supplied or by inclining the head.
O
The test mode is available only once the product has been configured.
Mounting
Projection or ceiling mount :
- Fix the wall plate using the supplied screws.
- Clip the detector onto the wall plate
- Tighten the screws to close. For angle mounting, the wall fixing plate is
fitted between the accessory and the detector.
Precautions for installation
For optimum detection conditions, please fol­low these recommendations :
- Keep the detector protected from bad weather, as it is sensitive to these conditions.
- Maintain 1m distance between the light source and the detector and keep the detec­tor out of the light source.
Product Description and working principles
This detector allows remote control of one or more receivers for a given time when a movement is detected in its detection zone. This product can be used in two types of configuration: one detector controls one/seve­ral receiver(s); several transmitters control the receiver(s).
Operation
The receiver(s) is(are) under control as soon as the brightness level as set by potentiometer
2
is considered too low and a movement is adetected. Upon detection, the time delay is restarted.
If LED A flashes quickly during configuration, the position of potentiometer 1 is not compa­tible with the selected function. Product factory reset is recommended before any new configuration.
Factory return
Keep push-button J depressed until LED cfg (flashes (>10s), and then release it. LED cfg is turned o when factory return is completed. After factory return, wait 15s before starting configuration.
Action Adjustments Potentiometer
Use Auto (factory) settings to set automatic lighting turn-on for a given time. Only available when a detector’s time delay is set.
Auto Settings
Put the Lux potentiometer on “auto test”.
The settings are predefined : Lux = , (operating at night only) time = 3 min,
sensitivity = max
Turn automatic lighting on for a given time. Only available when a detector’s time delay is set.
Installer settings
Test and confirm detection zone.
Test mode
Move the potentiometer
2
to “auto test”.
Adjust sensitivity. Allows setting the range
to avoid disturbance.
Configuration (button J )
These detectors can be configured in 3 dierent ways :
quicklink
: tool-free configuration (using product pushbuttons and LEDs), see User's Instructions 6T7952 supplied with the product.
• TX100/B V2.5.0 or above : description of product functions available from the Manufacturer.
• ETS3 or via TR131 : database and description of application software available from the Manufacturer.
Configuration by TX100 or ETS
Set the product in configuration mode by pressing
J button once during the teaching session of
TX100 or for addressing with TR131 in ETS.
O
Product factory return is required to change the configuration mode.
Correct Disposal of This product (Waste Electrical & Electronic
Equipment).
(Applicable in the European Union and other European countries with separate collection systems).
This marking shown on the product or its literature indicates that it hould not be disposed with other household wasted at the end of its working life. To prevent possible harm to the environment or human health from uncontrolled waste disposal, please separate this from other types of wastes and recycle it responsibly to promote the sustainable reuse of material resources.
Household users should contact either the retailer where they purchased this product, or their local government oce, for details of where and how they can take this item for environmentally safe recycling.
Business users should contact their supplier and check the terms and conditions of the purchase contract. This product should not be mixed with other commercial wastes of disposal.
Usable throughout Europe å and in Switzerland
Hager Controls hereby declares that the TRE51., TRE53.
device complies with the essential requirements and other relevant provisions of Directive 2014/53/EU.
The CE declaration is available on the: