4 6E 6333.e
Hager 03.2012 OCOM 113567
Programming
Programming may be done for each day or
for a group of days. In this case instructions are
common to several days.
Days : 1 = Monday, 2 = Tuesday, 3 = Wednesday...
7 = Sunday.
Display
Modification or clearing of a program step:
prog modif
EE180: by pressing repeatedly on - for channel A
EE181: by pressing repeatedly on - for channel A
and on + for channel B.
If the state of the output is On:
1
st
press : temporary waiver. Off and flash.
The next program step will let you return
to the automatic mode.
2
nd
press : permanent override. On and are
permanent. This override must be
cancelled manually.
3
rd
press : temporary override 15 minutes. On,
and 15 are permanent. The return to automatic mode will take place after 15 min.
4thpress : temporary override 30 minutes. On, and
and 30 are permanent. The return to
automatic mode will take place after
30 min.
5thpress: temporary override 60 minutes.
On, and and 60 are permanent.
The return to automatic mode will take
place after 60 min.
Override
As soon as the key appears on the switch,
appear on the screen.
Two types of operation :
A. Permanent override :
Insert the key into the switch. After 10 seconds the
program contained in the key will be executed
without clearing the program contained in the time
switch. As soon as the key is removed the program
of the time switch is again valid.
B. Copy (load) / Save (save) :
The key makes it possible to save a program
contained in the time switch.
It is also possible to copy the contents (program +
settings Astro) of the key into the clock.
1. Insert the key and wait for 2 sec.
2. Using menu select the mode:
save to save a program contained in the time
switch,
load to load the program of the key into the
time switch,
to check the program contained in the key.
3. Validate the selection with ok.
4. For save and load reconfirm with ok.
The following error messages may appear on the
screen:
no prog: the key is empty, it does not contain any
program.
Error: incompatible key type.
In these two cases :
⦁ Only the save mode is possible.
⦁ The error message remains on display as long as
the key is present, but in this case the program of
the time switch is executed.
Key
To check the daily profile set up without the risk of
modification or deletion:
Select the mode using menu and press ok.
Select the channel (A or B) using + or - and ok.
The first step of Monday is displayed as well as
the daily profile.
Two options available for display :
1. Select the prog mode using menu, then ok.
2. Select the channel (A or B) using + or -, then ok
(Only applicable to 2-channel clock EE181).
The number of remaining program steps appears
for a short time.
3. If a program already exists,
new will flash, press
ok to validate this new program steps, if not
move to 4.
4. Choose the day(s) using + or -. Validate with ok.
5.
ok flashes. Use ok to validate the group of days.
- or makes it possible to reset the group of
days if necessary
6. Using + or -, select instruction state:
On or Off if your are in automatic astronomical
mode.
On, Off, On or Off if your are in expert
mode.
7. Enter the time of switch-on using + or -.
Validate with ok.
8. Enter minutes with + or -. Validate with ok.
Program the other instructions of the group of
days by repeating operations 3 to 8.
The day or the group of days may be modified at
the during step 3 by pressing the +,- or .
At the end of programming return to auto mode
using the menu button.
To set the program of the other channel, return to
prog mode and proceed according to steps 2 to 8.
In this mode it is also possible to add an instruction to
the program set up.
Proceed as described above.
Select the prog mode with menu and press ok.
Select the channel (A or B) using + or - and ok.
Select the modif mode with + or -. Validate with ok.
The number of remaining program steps appears
for a short time.
The first step of the first day or group of days
appears.
Repeatedly pressing the ok key displays all
programmed steps one at a time.
Any flashing field (state, hour, minute) may be
modified using + or -, then validated with ok.
When the cursor is positioned on ok located
behind the group of days, you may display
successively the days or the groups of days and
switch directly to the one that has to be modified
using + or -.
To remove a program step :
select the state of the channel (On, Off, On or
Off ), press simultaneously + and -.
Clear appears on the screen. Validate with ok.
To prevent all undesirable actions, the
keyboard of the time switch may be locked
using a key EG004.
Unlocking is done in the same way.
Full product reset remains feasible when the
keyboard is locked.
Locking
Technical specifications
Electrical characteristics
⦁ Supply voltage : 230 V AC ± 15%
⦁ Frequency : 50/60 Hz
⦁ Power consumption max. 6 VA to 50 Hz
⦁ Output EE180 : 1 changeover volt free contact
⦁ Output EE181 : 2 changeover volt free contacts
⦁ Maximum load :
AC1 μ16A 250 V~
Cos φ = 0,6 μ10A 250 V~
Incandescent lighting 2300 W
Halogen lighting 230 V 2300 W
Compensated fluorescent tubes //
(max. 45 μF) 400 W
Non compensated fluorescent tubes,
compensated in series 1000 W
Compact fluorescent lamps 500 W
⦁ Minimum current.
AC1
100 mA 250 V~
⦁ Galvanic insulation between power supply
and output < 4 kV
Functional characteristics
⦁ Programming capacity : 56 steps
⦁ Minimum time between 2 steps: 1 minute
⦁ Running accuracy : ± 1,5 sec / 24h
⦁ Astronomical time accuracy : ± 10 minutes
⦁ Operating reserve : lithium battery provides
5 years of backup.
⦁ The product is set in standby mode (display
is off) if power goes off.
It is set back in auto mode when power is
back on. With power off, the screen
display is turned on when striking any key.
After one minute, it is turned off.
⦁ Protection degree: IP 20
The products need to be protected according to
the standards NFC15 100 and/or IEC 60 364-1
Environment
⦁ Operating temperature : -10 °C to +55 °C
⦁ Storage temperature : -20 °C to +60 °C
Connection
⦁ Flexible capacity: 1 to 6 mm
2
⦁ Rigid capacity: 1,5 to 10 mm
2
Connection diagrams:
6. Set the time correction of
sunset time “Set” using + and keys, then validate by ok.
7. Activate the astro mode by selecting On
using + and – then ok to have the product switch
on the control circuit automatically according to
the astronomical parameters.
8. For 2-way clock, select channel
A or B using + or - and validate
with ok.
The symbol on main display
will indicate if the channel is in
astro mode.
Limit of operation in astronomical mode
In this mode the clock is pre-programmed
according to sunrise and sunset hours.
On and Off interrupt steps can be added to
customize the program.
The programming is impossible between Astro Off
and Astro On.