Hager ECR300C User guide

Page 1
z i y
Technical data Technische data Dati tecnici
z i y
6LE005422Ad
ECR300C
Sealable terminal cover Dimension Verzegelbare
schroefklemafdekkap Coprimorsetto sigillabile Dimensione
90
7
Wiring diagram Cable stripping length and terminal screw torque
Aansluitschema Kabelstriplengte en aandraaimomenten van de
aansluitklemmen Schema di collegamento
Lunghezza di sguainatura del cavo e coppia della vite del morsetto
MID certied MID gecerticeerd Certicato MID
MID safety sealing
MID-verzegeling
Sigillo di sicurezza MID
Afmetingen
72
44
60
45
Data in compliance with EN 50470-1, EN 50470-3, IEC 62053-21 and
IEC62053-23
General characteristics Algemene karakteristieken Caratteristiche generali
Housing DIN 43880 Behuizing DIN 43880 Involucro DIN 43880 Mounting EN 60715 Montage EN 60715 Montaggio EN 60715 DIN rail 35 mm Depth Diepte Profondità mm 60 Weight Gewicht Peso g 293
Operating features Bedieningsfuncties Funzionalità operative
Connection to three-phase network - number of wires Verbinding naar driefasen netwerk - aantal draden Connessione alla rete trifase - numero di li Storage of energy values and
conguration
Tariff for active and reactive energy Tarief voor reële en reactieve energie Tariffa per energia attiva e reattiva - T1 … T2 230V - T1 … T8 Modbus
Approval (according to EN 50470-1, EN 50470-3) Goedkeuring (volgens EN 50470-1, EN 50470-3) Omologazione (secondo EN 50470-1, EN 50470-3)
Connection Verbinding Connessione - CT /5A - CT /1A Reference Voltage (Un) phase / neutral Referentiespanning (Un) fase /nul Tensione di riferimento (Un) fase / neutro VAC 230
Reference Current (Iref) Referentie stroom (Iref) Corrente di riferimento (Iref) A 1 Minimum Current (Imin) Minimumstroom (Imin) Corrente minima (Imin) A 0.01 Maximum Current (Imax) Maximale stroom (Imax) Corrente massima (Imax) A 6 Starting Current (Ist) Startstroom (Ist) Corrente di avviamento (Ist) A 0.001 External CT max. CT ratio Externe CT max. CT-ratio CT esterno max. Rapporto CT - 6000/5 - 1200/1 Reference Frequency (fn) Referentie frequentie (fn) Frequenza di riferimento (fn) Hz 50 Number of phases / number of wires Aantal fasen / aantal draden Numero di fasi / numero di li - 3 / 4
Certied Measures Gecerticeerde maatregelen Misure certicate
Accuracy Nauwkeurigheid Precisione
- Active Energies (accord. to EN 50470-3) - Reële energie (conform EN 50470-3) - Energia attiva (secondo EN 50470-3)
- Active Powers (accord. to IEC 62053-21 and IEC 61557-12) - Reëel vermogen (conform IEC 62053-21 en IEC 61557-12) - Potenza attiva (secondo IEC 62053-21 e IEC 61557-12)
- Reactive Energies (accord. to IEC 62053-23) - Reactive Energieën (conform IEC 62053-23) - Energia reattiva (secondo IEC 62053-23)
- Reactive Powers (accord. to IEC 62053-21) - Reactief vermogen (conform IEC 62053-21) - Energia reattiva (secondo IEC 62053-21)
Supply Voltage and Power Consumption Voedingsspanning en Energieverbruik Tensione di alimentazione e potenza assorbita
Operating Supply Voltage range Bedrfsspanningbereik Intervallo tensione di alimentazione V 92 … 276 / 160 … 480 Maximum Power Consumption (Voltage circuit) Maximaal energieverbruik (Spanningscircuit) Potenza massima assorbita (circuito voltmetrico) VA / W ≤2 / 0.6 Maximum VA burden (Current circuit) @ Imax Maximale VA last (stroom circuit) @ Imax Massimo assorbimento VA (circuito amperometrico) @ Imax VA ≤0.7
Voltage Input Waveform Meetspanningsvorm Forma d'onda tensione di ingresso - AC Voltage impedance Impedantie spanningsingang Impedenza circuito voltmetrico 1 Current impedance Impedantie stroomingang Impedenza circuito amperometrico ≤20
Overload capability Overbelastingscapaciteit Capacità di sovraccarico
Voltage continuous phase / neutral Spanning doorlopend fase /nul Tensione continuo fase / neutro VAC 276
Current continuous Stroom doorlopend Corrente continuo A 6
Measuring Features Meetfuncties Funzioni di misura
Voltage range phase / neutral Spanningsbereik fase /nul Intervallo di tensione fase / neutro VAC 92 … 276
Current range (secondary winding) Huidig bereik (secundaire wikkeling) Gamma corrente (avvolgimento secondario) A 0.001 … 6
Frequency range Frequentiebereik Intervallo di frequenza Hz 45 … 65 Measured Quantities Gemeten hoeveelheden Quantità misurate - V, A, kWh, kvarh, PF, Hz, kW, kvar
Display features Display functies Caratteristiche del display
Display type LCD with backlight Display type LCD met achtergrondverlichting Tipo di
Active Energy 7 digits + 2 decimal digits / 8+1 Reële Energie 7 cfers + 2 decimalen / 8+1 Energia attiva 7 cifre + 2 cifre decimali / 8+1 kWh 0.01 … 99999999.9 Reactive Energy 7 digits + 2 decimal digits / 8+1 Reactieve energie 7 cfers + 2 decimalen / 8+1 Energia reattiva 7 cifre + 2 cifre decimali / 8+1 kvarh 0.01 … 99999999.9 Voltage 3 digits + 2 decimal digits Spanning 3 cfers + 2 decimalen Tensione 3 cifre + 2 cifre decimali V 92.00 … 276.00 Current 2 digits + 2 decimal digits / 3+1 / 4+0 Stroom 2 cfers + 2 decimalen / 3+1 / 4+0 Corrente 2 cifre + 2 cifre decimali / 3+1 / 4+0 A 0.01 … 6000 Power factor 1 digit + 3 decimal digits with sign + capac./induc. indic. Powerfactor 1 cfer + 3 decimalen + capaciteit./induc. indic. Fattore di potenza 1 cifra + 3 cifre decimali con segno + indic. capac. /
Frequency 2 digits + 2 decimal digits Frequentie 2 cfers + 2 decimalen Frequenza 2 cifre + 2 cifre decimali Hz 45.00 … 65.00 Active Power 2 digits + 2 decimal digits / 3+1 / 4+0 Reëel vermogen 2 cfers + 2 decimalen / 3+1 / 4+0 Potenza attiva 2 cifre + 2 cifre decimali / 3+1 / 4+0 kW 0.00 … 1987 Reactive Power 2 digits + 2 decimal digits / 3+1 / 4+0 Reactief vermogen 2 cfers + 2 decimalen / 3+1 / 4+0 Potenza reattiva 2 cifre + 2 cifre decimali / 3+1 / 4+0 kvar 0.00 … 1987 Apparent Power 2 digits + 2 decimal digits / 3+1 / 4+0 Schnbaar
Running Tariff 1 digit Actueel tarief 1 cfer Tariffa in funzione 1 cifra - T1 … T2 230V - T1 … T8 Modbus Display refresh period Toon verversingsperiode Frequenza di aggiornamento del display s 1
Optical metrological LED Optische metrologische LED LED metrologico ottico
Front mounted red LED (meter constant) proportional to active imp/
Safety Veiligheid Sicurezza
Overvoltage category Overspanningscategorie Categoria di sovratensione - 3 Protective class Beschermingsklasse Classe di protezione classe II AC voltage test (EN 50470-3, 7.2) AC spanningstest (EN 50470-3, 7.2) Test di tensione AC (EN 50470-3, 7.2) kV 4 Degree of pollution Vervuilingsgraad Grado di inquinamento - 2 Operational voltage Nominale spanning Tensione di funzionamento V 300 Impulse voltage test (Uimp) Impulsspanningstest (Uimp) Test di tensione ad impulso (Uimp) 1.2/50 μs-kV 6 Housing material ame resistance UL 94 Behuizing materiaal vlamwerendheid UL 94 Resistenza alla amma del materiale dell'involucro UL 94 classe V0 Safety-sealing between upper and lower housing part Veiligheidsafdichting tussen bovenste en onderste behuizing Sigillo di sicurezza tra la parte superiore e quella inferiore dell'involucro
IR Connectable Communication Modules IR-koppelbare communicatiemodules Moduli di comunicazione IR collegabili
For communication modules Voor communicatiemodules Per moduli di comunicazione
Embedded Modbus communication Geïntegreerde communicatie Modbus Comunicazione incorporata Modbus
Physical interface RS-485 - 3 wires Fysieke interface RS-485 - 3 draden Interfaccia sica RS-485 - 3 li - -, +, 0 Internal termination resistor Interne afsluitweerstand Resistenza di terminazione
Baud rate adjustable Baudrate Instelbaar Velocità Baud regolabile bps 1200 … 38400 Parity adjustable: Odd, Even, None Pariteit Instelbaar: Oneven, even, geen Parità regolabile: Dispari, Pari, Nessuno Stop Bit adjustable Stop Bit Instelbaar Stop Bit regolabile - 1, 2 Address adjustable Adres Instelbaar Indirizzo regolabile - 1 … 247 Isolation class SELV Isolatieklasse SELV Classe di isolamento SELV
Tariff Tarief Tariffa
Tariff 1 Tarief 1 Tariffa 1 Tariff 2 Tarief 2 Tariffa 2 VAC 230 ±20% Input impedance Ingangsimpedantie Impedenza di ingresso 224
Environmental conditions Milieuomstandigheden Condizioni ambientali
Storage temperature range Opslagtemperatuur Temperatura di stoccaggio °C -25 … +70 Operating temperature range Bedrfstemperatuur Temperatura di funzionamento °C -25 … +55 Mechanical environment Electromagnetic environment Elektromagnetische omgeving Ambiente elettromagnetico - E2 Installation indoor only Installatie alleen binnen Installazione solo all'interno
Altitude (max.) Hoogte (max.) Altitudine (max.) m ≤2000
Humidity yearly average, without condensation Vochtigheid jaarlks gemiddelde, zonder condensatie Umidità media annuale, senza condensa - ≤75%
IP rating in built-in condition (front part) IP rating in ingebouwde conditie (voorkant) Grado di protezione IP in condizione di incasso (parte frontale) - IP51(*)
(*) For use in accordance with the MID Directive, the energy meter must be installed in a
distribution board/enclosure for modular products with a minimum protection rating IP30 The IP51 ratings apply to the meter parts exposed in front of (outside of) the cover of the enclosure.
Internal ash non volatile memory Opslag van energiewaarden en
phase / phase fase / fase fase / fase VAC 400
temporary (1 s) phase / neutral tdelk (1 s) fase /nul temporaneo (1 s) fase / neutro VAC 300 continuous phase / phase doorlopend fase / fase continuo fase / fase VAC 480
temporary (1 s) phase / phase tdelk (1 s) fase / fase temporaneo (1 s) fase / fase VAC 800
temporary (0.5 ms) tdelk (0,5 ms) temporaneo (0,5 ms) A 120
phase / phase fase / fase fase / fase VAC 160 … 480
exp Energy
on 30 days per year, without condensation op 30 dagen per jaar, zonder condensatie su 30 giorni all'anno, senza condensa - ≤95%
terminal block klemblok morsettiera - IP20
1 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005422Ad
IEC62053-23
cong.
vermogen
Aan voorzde gemonteerde rode LED (meter constant)
Mechanische omgeving Ambiente meccanico - M1
(*) Voor gebruik in overeenstemming met de MID-richtln moet de energiemeter
worden gemonteerd in een verdeelkast voor modulaire producten met een minimale beschermingsklasse IP30. De IP51 is van toepassing op het gedeelte van de behuizing van de energiemeter dat door de afdekplaat heen naar buiten steekt..
2 cfers + 2 decimalen / 3+1 / 4+0 Potenza Apparente 2 cifre + 2 cifre decimali / 3+1 / 4+0
Intern ash niet-vluchtig geheugen Memorizzazione dei valori di
evenredig met actieve imp / exp Energie
Dati conformi alle norme EN 50470-1, EN 50470-3, IEC 62053-21 e
IEC62053-23
energia e congurazione
visualizzazione
LED rosso frontale (costante del contatore) proporzionale all'energia imp /
interna
(*) Per l'utilizzo in conformità alla direttiva MID, il contatore di energia deve essere installato
in un quadro di distribuzione per apparecchi modulari con grado di protezione minimo IP30. Il grado di protezione IP51 è relativo a parti del contatore esterne al quadro (frontale dell'apparecchio).
LCD retroilluminato
indutt.
Memoria interna non volatile
exp. Attiva
DIN
-
-
kWh
classe B / 1
classe 2
- 7.2 +3.2
- -1.000 … 1.000
kVA 0.00 … 1987
p/kWh 10000
-
-
- 120 Ω
-
-
-
-
4 0
4
c
kWh kWh
c
c
c
c
c
c
Page 2
Active Energy Imported
Tariff 1 with Partial
register
Active Energy Exported
Tariff 1 with Partial
register
z
Three phase energy meter, measure via CT 1 to 6000 A
with MID declaration of conformity
1s
Meter type
By powering. Software version and checksum
and Modbus RTU communication
MID certication concerns active energy only.
User instructions
1s 1s
EU declaration of conformity:
http://hgr.io/r/ecr300c
6LE005422Ad
ECR300C
Safety instructions
This device must be installed only by a professional electrician tter
according to local applicable installation standards. Do not plug in or unplug this product when the power supplying is ON. Its use is only permitted within the limits shown and stated in the installation instructions. The device and the equipement connected can be destroyed by loads exceeding the values stated.
Operating principle
This 4 quadrants Modbus RTU meter measures the active and reactive energy used in an electrical installation. This device can manage 2 tariffs by 230 VAC digital input and up to 8 controlled via communication. Only the total active energy register can be used for billing purposes according to measuring instrument directive (MID).
- Active Energy Class B (according to EN 50470)
- Active Power Class 1 (according to IEC 62053-21 and IEC 61557-12)
- Reactive Energy Class 2 (according to IEC 60253-23)
- Reactive Power Class 2 (according to IEC 62053-21). This device has a LCD backlight and 3 push-button keys to read
Energies, V, I, PF, F, P, Q and to congure some parameters. The design
and manufacture of this meter comply with Standard EN 50470-3 requirements.
Product presentation
LCD display:
Energy for all tariffs
Tariff
Reactive power inductive/capacitive
Phase indicator
Via current transformer (CT)
Secondary transformer current
Main Energy Register, not resettable
Partial Energy Register, resettable
Units
Energy import (consumption ) Energy export (production
Communication activity status
Energy meter has received a message with the correct address and with the correct checksum, but the meter has answered with an Exception Message in case of Modbus:
- illegal function
- illegal data address
- illegal data value
Commands
OK button: is used to conrm a modication of a
parameter (or of a digit of a numerical parameter) or to answer to a question
SCROLL button: is used to scroll Menu pages or to modify the whole value or a digit of a parameter
ESCAPE button: is used to escape to main menu from anywhere or to skip back to the previous digit of the
value under modication
Optical metrological LED
Note:
If no button is pushed for at least 20 seconds the display goes back to the Main Page and the backlight is switched off again.
2 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005422Ad
Symbols
Three phases
Protected by double insulation (Class II)
Backstop: Reversal preventing device
Modbus RTU Communication
Recommendations:
Use HTG485H reference cable specially developed as accessory by Hager.
Important:
It is essential to connect a resistance of 120 Ohms at the 2 ends of the connection.
Modbus protocol:
The Modbus protocol operates on a master/slave structure:
• Reading (Function 3),
• Writing (Function 6 or 16), broadcast option at address 0. The communication method is RTU (Remote Terminal Unit) with hexadecimal.
Modbus table:
Download from: http://hgr.io/r/ecr300c
Error condition:
When partial energy blinks, reset partial energy (maximum partial energy register). When the display shows the message ERROR N02 or ERROR N03, the meter has got a malfunction and must be replaced.
)
Power factor Convention according to IEC 62053-23
kW
- +
II I
Q
II I
kvar
kvar
+
-
PF ≤0 PF ≥0
kW
S
P
IV
Main page is depending on current power direction
indication
with the corresponding global and
partial energy register display.
Active energy imported
Active energy exported
Reactive energy
imported
Reactive energy
exported
Tariff related Energies
Partial Register Reset
Measures reading
Conguration
Serial number
Software version and
checksum
Display test
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
Active Energy Imported
Tariff 2 with Partial
register
Active Energy Exported
Tariff 2 with Partial
register
Reactive Energy
Imported Tariff 1
Reactive Energy
Exported Tariff 1
Reactive Energy
Imported Tariff 2
Reactive Energy
Exported Tariff 2
OK
Primary winding of the
external CTs:
/5A: 5 ...
50 ... 6000
/1A: 1 ... 50 ... 1200
Secondary winding of
the external CTs:
/1 A - /5 A
Modbus Address:
1 ... 247
Baud Rate:
1200-2400-4800-9600
19200-38400
Parity:
even-odd
none-
Stop Bit:
1-2
Unidirectional
Bidirectional
Tariffs conguration:
1T
2T input 230 V
8T input Modbus
In order to read values referred to Secondary side of CTs, push the ESCAPE button for a long time (10 seconds), in the Main Page. For two minutes (120 seconds), the whole set of parameters are displayed with their values referred to Secondary side of CTs, with the CT icon blinking. Also values transmitted through internal bus are referred to Secondary side for 2 minutes
Diagnostic message
The cabling sequence (L1-L2-L3) is wrong. L1, L2 and L3 icons blink. Invert the voltage wires of 2 phases (phase 1
<> phase 2 or phase 2 <> phase 3).
Otherwise, by pressing the "OK" button for at least 5 seconds, the message disappears until the next restart.
10 sec.
After 2 seconds it goes
back to the Main Page
Active Power
Reactive Power
Apparent Power
(L1-N, L2-N, L3-N)
Neutral current
Power factor
Power factor
Power factor
(L1, L2, L3)
(L1, L2, L3)
(L1, L2, L3)
Voltage
Current
(L1, L2, L3)
L1
L2
L3
Frequency
Page 3
Reële energie
geïmporteerd Tarief 1
met gedeeltelk register
Reële energie
geëxporteerd Tarief 1
met gedeeltelk register
i
Driefase energiemeter, meet via CT 1 tot 6000 A
met MID-verklaring van overeenstemming
Softwareversie en check
1s
Meter type
Via voeding.
som
en Modbus RTU-communicatie
MID certicering heeft alleen betrekking op werkelke energie.
Gebruikersinstructies
1s 1s
EU-conformiteitsverklaring:
http://hgr.io/r/ecr300c
6LE005422Ad
ECR300C
Veiligheidsinstructies
Dit apparaat mag alleen worden geïnstalleerd door een professionele installateur in overeenstemming met de geldende installatienormen.
Sluit dit product niet aan of koppel het niet los b ingeschakelde
spanning. Het gebruik ervan is alleen toegestaan binnen de aangegeven grenzen en vermeld in de installatie-instructies. Het apparaat en het aangesloten apparaat kunnen worden beschadigd door belastingen die
de vermelde waarden overschrden.
Werkingsprincipe
Deze 4-kwadranten Modbus RTU-meter meet de reële en reactieve energie die wordt gebruikt in een elektrische installatie. Dit apparaat kan 2 tarieven beheren via de binaire 230 VAC tarief ingang en 8 tarieven via de digitale communicatie interface. Alleen het totale actieve energieregister kan voor factureringsdoeleinden worden gebruikt
volgens de meetinstrumentrichtln (MID).
- Reële energieklasse B (volgens EN 50470)
- Reële vermogensklasse 1 (volgens IEC 62053-21 en IEC 61557-12)
- Reactieve energieklasse 2 (volgens IEC 60253-23)
- Reactieve vermogensklasse 2 (volgens IEC 62053-21). Dit apparaat heeft een LCD-achtergrondverlichting en 3 druktoetsen om de meetwaarden, V, I, PF, F, P, Q te lezen en om enkele parameters te
congureren. Het ontwerp en de fabricage van deze meter voldoen aan
de vereisten van norm EN 50470-3.
Productpresentatie
LCD scherm:
Commando's
Opmerking:
Als er ten minste 20 seconden lang op geen enkele knop wordt gedrukt, keert het display terug naar de hoofdpagina en wordt de achtergrondverlichting weer uitgeschakeld.
3 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005422Ad
OK-knop: wordt gebruikt om een wziging van een parameter (of een cfer van een numerieke parameter) te
bevestigen of om een vraag te beantwoorden
SCROLL-knop: wordt gebruikt om door menupagina's
te bladeren of om de hele waarde of een cfer van een parameter te wzigen
ESCAPE-knop: wordt gebruikt om naar het hoofdmenu
terug te gaan of om naar het vorige cfer van de gewzigde waarde terug te gaan
Optische metrologische LED
Energie voor alle tarieven
Tarief
Reactief vermogen inductief/capacitief
Fase-indicator
Via stroomtransformator (CT)
Secundaire transformatorstroom
Hoofdenergieregister, niet opnieuw instelbaar
Gedeeltelk energieregister,
opnieuw instelbaar
Eenheden
Energie-import (consumptie ) Energie-export (productie
Status van communicatieactiviteit
Energiemeter een bericht heeft ontvangen met het juiste adres en de juiste controlesom, maar de meter heeft beantwoord met een uitzonderingsbericht in het geval van Modbus:
- illegale functie
- illegaal gegevensadres
- illegale gegevenswaarde
)
Symbolen
Drie fasen
Beschermd door dubbele isolatie (klasse II)
Backstop: apparaat om achteruitrden te voorkomen
Modbus RTU communicatie
Aanbevelingen:
Gebruik HTG485H-referentiekabels die speciaal zn ontwikkeld als
accessoire door Hager.
Belangrk:
Het is noodzakelk om een weerstand van 120 Ohm aan te sluiten op
beide uiteinden van de datacommunicatiekabel.
Modbus-protocol:
Het Modbus-protocol werkt op een master / slave-structuur:
• Lezen (functie 3),
• Schrven (functie 6 of 16), broadcast optie op adres 0.
De communicatiemethode is RTU (Remote Terminal Unit) met hexadecimaal.
Modbus-tabel:
Downloaden van: http://hgr.io/r/ecr300c
Foutconditie:
In de situatie dat het woord Partial op het diplay knippert, dan heeft de “partial” teller de maximale waarde overschreden. In dit geval moet je de “partial” teller resetten. In de situatie dat de foutmeldingen ERROR N02 of ERROR N03 op het
display verschnen dan is er een defect in de meter. In deze situatie
moet de meter worden vervangen.
Powerfactor Conventie volgens IEC 62053-23
kW
- +
II I
kvar
kvar
+
-
II I
PF ≤0 PF ≥0
kW
Q
S
P
IV
Hoofdpagina is afhankelk van de huidige
aanduiding van de stroomrichting
het bbehorende algemeen en gedeeltelke
energieregisterscherm.
met
Reële energie
geïmporteerd
Reële energie geëxporteerd
Reactieve energie
geïmporteerd
Reactieve energie
geëxporteerd
Tariefgerelateerde
energieën
Gedeeltelk register
resetten
Meetwaarden
Conguratie
Serienummer
Softwareversie en
check som
Displaytest
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
Reële energie
geïmporteerd Tarief 2
met gedeeltelk register
Reële energie
geëxporteerd Tarief 2
met gedeeltelk register
Reactieve energie
geïmporteerd Tarief 1
Reactieve energie
geëxporteerd Tarief 1
Reactieve energie
geïmporteerd Tarief 2
Reactieve energie
geëxporteerd Tarief 2
OK
Primaire wikkeling van
de externe CT's:
/5A: 5 ...
50 ... 6000
/1A: 1 ... 50 ... 1200
Secundaire wikkeling
van de externe CT's:
/1 A - /5 A
Modbus-adres:
1 ... 247
Baudrate:
1200-2400-4800-9600
19200-38400
Pariteit:
even-oneven
geen-
Stop Bit:
1-2
Unidirectionele
Bidirectionele
Tarieven conguratie:
1T
2T ingang 230 V
8T ingang Modbus
Om de waarden waarnaar de secundaire kant van CT's verwst
te lezen, drukt u lang op de ESCAPE-knop (10 seconden) op de hoofdpagina. Gedurende twee minuten (120 seconden) wordt de hele set parameters weergegeven met hun waarden aan de secundaire kant
van CT's, terwl het CT-pictogram knippert. Ook waarden die worden
verzonden via de interne bus worden gedurende 2 minuten naar de secundaire kant verwezen
Diagnostisch bericht
De bekabelingsvolgorde (L1-L2-L3) is
verkeerd. Pictogrammen L1, L2 en L3 knipperen. Keer de spanningsdraden
van 2 fasen om (fase 1 <> fase 2 of fase 2 <> fase 3). Anders verdwnt het bericht door gedurende ten minste 5
seconden op de knop "OK" te drukken tot de volgende herstart.
10 sec.
Na 2 seconden gaat
het terug naar de
hoofdpagina
Reëel vermogen
Reactief vermogen
(L1-N, L2-N, L3-N)
Nulgeleider stroom
Powerfactor
Powerfactor
Powerfactor
(L1, L2, L3)
(L1, L2, L3)
Schnbaar
vermogen
(L1, L2, L3)
Spanning
Stroom
(L1, L2, L3)
L1
L2
L3
Frequentie
Page 4
Energia attiva importata
Tariffa 1 con registro
parziale
Energia attiva esportata
Tariffa 1 con registro
parziale
y
Contatore di energia trifase, misurare tramite CT 1 a 6000 A
con dichiarazione di conformità MID
Alimentandolo. Versione
software e checksum
1s
Tipo di contatore
e comunicazione Modbus RTU
La certicazione MID riguarda solo la energia attiva.
Istruzioni per l'utente
1s 1s
Dichiarazione di conformità UE:
http://hgr.io/r/ecr300c
6LE005422Ad
ECR300C
Istruzioni per la sicurezza
Questo dispositivo deve essere installato esclusivamente da un elettricista professionista secondo le norme di installazione locali
applicabili. Non collegare o scollegare il prodotto quando è alimentato. Il
suo utilizzo è consentito solo nei limiti indicati e dichiarati nelle istruzioni
di installazione. Il dispositivo e le apparecchiature collegate possono
essere danneggiati da carichi che superano i valori indicati.
Principio di funzionamento
Questo misuratore Modbus RTU a 4 quadranti misura l'energia attiva
e reattiva utilizzata in un'installazione elettrica. Questo dispositivo può
gestire 2 tariffe tramite ingresso digitale da 230 VAC e no a 8 tariffe
controllate tramite comunicazione. Solo il registro di energia attiva totale può essere utilizzato per la fatturazione in base alla direttiva dello
strumento di misura (MID).
- Classe Energia Attiva B (secondo EN 50470)
- Classe Potenza Attiva 1 (secondo IEC 62053-21 e IEC 61557-12)
- Classe Energia Reattiva 2 (secondo IEC 60253-23)
- Classe Potenza Reattiva 2 (secondo IEC 62053-21). Questo apparecchio è dotato di display LCD retroilluminato e 3 pulsanti per leggere Energia, V, I, PF, F, P, Q e per congurare alcuni parametri. La
progettazione e la fabbricazione di questo strumento sono conformi ai
requisiti della norma EN 50470-3.
Presentazione del prodotto
Display LCD:
Energia per tutte le tariffe
Tariffa
Potenza reattiva induttiva/capacitiva
Indicatore di fase
Tramite trasformatore di corrente (CT)
Corrente trasformatore secondaria
Registro principale dell'Energia, non
resettabile
Registro parziale dell'Energia,
resettabile
Unità
Energia importata (consumata ) Energia esportata (prodotta
Stato della comunicazione
Il contatore di energia ha ricevuto un
messaggio con l'indirizzo corretto e con il checksum corretto ma ha risposto con un messaggio di errore
in caso di comunicazione Modbus:
- funzione non valida
- indirizzo dati non valido
- valore dati non valido
Symboli
Tre fasi
Protetto da doppio isolamento (Classe II)
Backstop: dispositivo anti inversione
Comunicazione Modbus RTU
Raccomandazioni:
Utilizzare i cavi codice HTG485H appositamente sviluppati come accessorio da Hager.
Importante:
È essenziale collegare una resistenza da 120 Ohm alle 2 estremità della
connessione.
Protocollo Modbus:
Il protocollo Modbus opera su una struttura master / slave:
• Lettura (funzione 3),
• Scrittura (Funzione 6 o 16), opzione di trasmissione all'indirizzo 0. Il metodo di comunicazione è RTU (Remote Terminal Unit) esadecimale.
Piattaforma Modbus:
Scarica da: http://hgr.io/r/ecr300c
Condizione di errore:
Quando l'energia parziale lampeggia, ripristinare l'energia parziale (registro massimo dell'energia parziale). Quando il display mostra il messaggio ERROR N02 o ERROR N03, lo strumento ha un malfunzionamento e deve essere sostituito.
)
Fattore di potenza Convenzione secondo IEC 62053-23
kW
kW
- +
Comandi
Pulsante OK: consente di confermare una modica di un parametro (o di una cifra di un parametro numerico) o di rispondere a una domanda
Pulsante SCROLL: consente di scorrere le pagine del
menu o di modicare l'intero valore o una cifra di un
parametro
Tasto ESCAPE: serve per uscire dal menu principale da qualsiasi posizione o per passare alla cifra precedente
del valore in modica
LED metrologico ottico
Nota:
Se non viene premuto alcun pulsante per almeno 20 secondi, il display torna alla pagina principale e la retroilluminazione viene nuovamente disattivata.
4 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005422Ad
kvar
kvar
+
-
II I
Q
II I
IV
PF ≤0 PF ≥0
S
P
La
pagina principale dipende dall'indicazione
della direzione della potenza impostata
corrispondente display del registro di energia globale
e parziale.
con il
Energia attiva importata
Energia attiva esportata
Energia reattiva
importata
Energia reattiva
esportata
OK
Energia legata alle
tariffe
OK
Reset del registro
parziale
OK
Lista misure
OK
Congurazione
Numero di serie
Versione software e
checksum
Test di
visualizzazione
OK
OK
OK
OK
OK
OK
OK
OK
Energia attiva importata
Tariffa 2 con registro
parziale
Energia attiva esportata
Tariffa 2 con registro
parziale
Energia reattiva
importata Tariffa 1
Energia reattiva
esportata Tariffa 1
Energia reattiva
importata Tariffa 2
Energia reattiva
esportata Tariffa 2
OK
Avvolgimento primario
dei TA esterni:
/5A: 5 ...
50 ... 6000
/1A: 1 ... 50 ... 1200
Avvolgimento
secondario dei TA
esterni:
/1 A -
/5 A
Indirizzo Modbus:
1 ... 247
Velocità Baud:
1200-2400-4800-9600
19200-38400
Parità:
pari-dispari
nessuno-
Stop Bit:
1-2
Unidirezionale
Bidirezionale
Congurazione delle
tariffe:
1T
2T ingresso 230 V
8T ingresso Modbus
Per leggere i valori riferiti al lato secondario dei CT, premere a lungo il pulsante ESCAPE (10 secondi), nella pagina principale. Per due minuti (120 secondi), l'intera serie di parametri viene visualizzata con i relativi valori riferiti al lato secondario dei CT, con l'icona CT lampeggiante. Anche i valori trasmessi attraverso il bus interno sono riferiti al lato secondario per 2 minuti
Messaggio diagnostico
La sequenza di collegamento (L1­L2-L3) è errata. Le icone L1, L2 e L3 lampeggiano. Invertire i collegamenti
voltmetrici di 2 fasi (fase 1 <> fase 2 o fase 2 <> fase 3). Altrimenti,
premendo il pulsante "OK" per almeno
5 secondi, il messaggio scompare no
al successivo riavvio.
10 sec.
Dopo 2 secondi torna alla pagina principale
Potenza attiva
(L1, L2, L3)
Potenza reattiva
(L1, L2, L3)
Potenza Apparente
(L1, L2, L3)
Tensione
(L1-N, L2-N, L3-N)
Corrente
(L1, L2, L3)
Corrente Neutrale
Fattore di potenza
L1
Fattore di potenza
L2
Fattore di potenza
L3
Frequenza