Hager ECR180D User guide

Page 1
z i y
Technical data Technische data Dati tecnici
z i y
Data in compliance with EN 50470-1, EN 50470-3, IEC 62053-21 and
IEC62053-23
General characteristics Algemene karakteristieken Caratteristiche generali
Housing DIN 43880 Behuizing DIN 43880 Involucro DIN 43880 DIN Mounting EN 60715 Montage EN 60715 Montaggio EN 60715 DIN rail 35 mm Depth Diepte Profondità mm 60 Weight Gewicht Peso g 175
Operating features Bedieningsfuncties Funzionalità operative
Connection to single-phase network - number of wires Verbinding naar eenfasig netwerk - aantal draden Connessione alla rete monofase - numero di li Storage of energy values and
conguration
Tariff for active and reactive energy Tarief voor reële en reactieve energie Tariffa per energia attiva e reattiva - T1 … T2 230V - T1 … T8 Modbus
Internal ash non volatile memory Opslag van energiewaarden en
Approval (according to EN 50470-1, EN 50470-3) Goedkeuring (volgens EN 50470-1, EN 50470-3) Omologazione (secondo EN 50470-1, EN 50470-3)
6LE005251Ad
Reference Voltage (Un) Referentiespanning (Un) Tensione di riferimento (Un) VAC 230 Reference Current (Iref) Referentie stroom (Iref) Corrente di riferimento (Iref) A 5 Minimum Current (Imin) Minimumstroom (Imin) Corrente minima (Imin) A 0.25 Maximum Current (Imax) Maximale stroom (Imax) Corrente massima (Imax) A 80 Starting Current (Ist) Startstroom (Ist) Corrente di avviamento (Ist) A 0.015
ECR180D
Sealable terminal cover Dimension Verzegelbare
schroefklemafdekkap Coprimorsetto sigillabile Dimensione
Afmetingen
Reference Frequency (fn) Referentie frequentie (fn) Frequenza di riferimento (fn) Hz 50 Number of phases / number of wires Aantal fasen / aantal draden Numero di fasi / numero di li - 1 / 2
Certied Measures Gecerticeerde maatregelen Misure certicate kWh
Accuracy Nauwkeurigheid Precisione
- Active Energies (accord. to EN 50470-3) - Reële energie (conform EN 50470-3) - Energia attiva (secondo EN 50470-3) classe B / 1
- Active Powers (accord. to IEC 62053-21 and IEC 61557-12) - Reëel vermogen (conform IEC 62053-21 en IEC 61557-12) - Potenza attiva (secondo IEC 62053-21 e IEC 61557-12)
- Reactive Energies (accord. to IEC 62053-23) - Reactive Energieën (conform IEC 62053-23) - Energia reattiva (secondo IEC 62053-23) classe 2
- Reactive Powers (accord. to IEC 62053-21) - Reactief vermogen (conform IEC 62053-21) - Potenza reattiva (secondo IEC 62053-21)
Supply Voltage and Power Consumption Voedingsspanning en Energieverbruik Tensione di alimentazione e potenza assorbita
36
Operating Supply Voltage range Bedrfsspanningbereik Intervallo tensione di alimentazione V 92 … 276 Maximum Power Consumption (Voltage circuit) Maximaal energieverbruik (Spanningscircuit) Potenza massima assorbita (circuito voltmetrico) VA / W ≤2 / ≤1 Maximum VA burden (Current circuit) @ Imax Maximale VA last (stroom circuit) @ Imax Massimo assorbimento VA (circuito amperometrico) @ Imax VA ≤1
Voltage Input Waveform Meetspanningsvorm Forma d'onda tensione di ingresso - AC Voltage impedance Impedantie spanningsingang Impedenza circuito voltmetrico 1 Current impedance Impedantie stroomingang Impedenza circuito amperometrico ≤20
Overload capability Overbelastingscapaciteit Capacità di sovraccarico
Voltage continuous Spanning doorlopend Tensione continuo VAC 276
92
45
Current continuous Stroom doorlopend Corrente continuo A 80
temporary (1 s) tdelk (1 s) temporaneo (1 s) VAC 300
temporary (10 ms) tdelk (10 ms) temporaneo (10 ms) A 2400
Measuring Features Meetfuncties Funzioni di misura
Voltage range Spanningsbereik Intervallo di tensione VAC 92 … 276 Current range Stroombereik Intervallo di corrente A 0.015 … 80
7
44
Frequency range Frequentiebereik Intervallo di frequenza Hz 45 … 65 Measured Quantities Gemeten hoeveelheden Quantità misurate - V, A, kWh, kvarh, PF, Hz, kW, kvar
Display features Display functies Caratteristiche del display
Display type LCD with backlight Display type LCD met achtergrondverlichting Tipo di
60
Active Energy 7 digits + 2 decimal digits Reële Energie 7 cfers + 2 decimalen Energia attiva 7 cifre + 2 cifre decimali kWh 0.01 … 9999999.99 Voltage 3 digits + 2 decimal digits Spanning 3 cfers + 2 decimalen Tensione 3 cifre + 2 cifre decimali V 92.00 … 276.00
Wiring diagram Cable stripping length and terminal screw torque
Aansluitschema Kabelstriplengte en aandraaimomenten van de
aansluitklemmen Schema di collegamento
Lunghezza di sguainatura del cavo e coppia della vite del morsetto
Current 2 digits + 2 decimal digits Stroom 2 cfers + 2 decimalen Corrente 2 cifre + 2 cifre decimali A 0.00 … 80.00 Power factor 1 digit + 3 decimal digits with sign + capac./induc. indic. Powerfactor 1 cfer + 3 decimalen + capaciteit./induc. indic. Fattore di potenza 1 cifra + 3 cifre decimali con segno + indic. capac. /
Frequency 2 digits + 2 decimal digits Frequentie 2 cfers + 2 decimalen Frequenza 2 cifre + 2 cifre decimali Hz 45.00 … 65.00 Active Power 2 digits + 2 decimal digits with sign Reëel vermogen 2 cfers + 2 decimalen met teken Potenza attiva 2 cifre + 2 cifre decimali con segno kW 0.00 … 22.08 Reactive Power 2 digits + 2 decimal digits with sign Reactief vermogen 2 cfers + 2 decimalen met teken Potenza reattiva 2 cifre + 2 cifre decimali con segno kvar 0.00 … 22.08 Running Tariff 1 digit Actueel tarief 1 cfer Tariffa in funzione 1 cifra - T1 … T2 230V - T1 … T8 Modbus Display refresh period Toon verversingsperiode Frequenza di aggiornamento del display s 1
Optical metrological LED Optische metrologische LED LED metrologico ottico
Front mounted red LED (meter constant) proportional to active imp/
Safety Veiligheid Sicurezza
exp Energy
Overvoltage category Overspanningscategorie Categoria di sovratensione - 3 Protective class Beschermingsklasse Classe di protezione classe II AC voltage test (EN 50470-3, 7.2) AC spanningstest (EN 50470-3, 7.2) Test di tensione AC (EN 50470-3, 7.2) kV 4 Degree of pollution Vervuilingsgraad Grado di inquinamento - 2 Operational voltage Nominale spanning Tensione di funzionamento V 300 Impulse voltage test (Uimp) Impulsspanningstest (Uimp) Test di tensione ad impulso (Uimp) 1.2/50 μs-kV 6 Housing material ame resistance UL 94 Behuizing materiaal vlamwerendheid UL 94 Resistenza alla amma del materiale dell'involucro UL 94 classe V0 Safety-sealing between upper and lower housing part Veiligheidsafdichting tussen bovenste en onderste behuizing Sigillo di sicurezza tra la parte superiore e quella inferiore dell'involucro -
IR Connectable Communication Modules IR-koppelbare communicatiemodules Moduli di comunicazione IR collegabili
For communication modules Voor communicatiemodules Per moduli di comunicazione -
Embedded Modbus communication Geïntegreerde communicatie Modbus Comunicazione incorporata Modbus
Physical interface RS-485 - 3 wires Fysieke interface RS-485 - 3 draden Interfaccia sica RS-485 - 3 li - -, +, 0 Baud rate adjustable Baudrate Instelbaar Velocità Baud regolabile bps 1200 … 38400 Parity adjustable: Odd, Even, None Pariteit Instelbaar: Oneven, even, geen Parità regolabile: Dispari, Pari, Nessuno ­Stop Bit adjustable Stop Bit Instelbaar Stop Bit regolabile - 1 , 2 Address adjustable Adres Instelbaar Indirizzo regolabile - 1 … 247 Isolation class SELV Isolatieklasse SELV Classe di isolamento SELV -
MID certied MID gecerticeerd Certicato MID
320/MID
0051M 18
Tariff Tarief Tariffa
Tariff 1 Tarief 1 Tariffa 1 ­Tariff 2 Tarief 2 Tariffa 2 VAC 230 ±20% Input impedance Ingangsimpedantie Impedenza di ingresso 224
Environmental conditions Milieuomstandigheden Condizioni ambientali
Storage temperature range Opslagtemperatuur Temperatura di stoccaggio °C -25 … +70 Operating temperature range Bedrfstemperatuur Temperatura di funzionamento °C -25 … +55 Mechanical environment Mechanische omgeving Ambiente meccanico - M1 Electromagnetic environment Elektromagnetische omgeving Ambiente elettromagnetico - E2 Installation indoor only Installatie alleen binnen Installazione solo all'interno -
Altitude (max.) Hoogte (max.) Altitudine (max.) m ≤2000
Humidity yearly average, without condensation Vochtigheid jaarlks gemiddelde, zonder condensatie Umidità media annuale, senza condensa - ≤75%
on 30 days per year, without condensation op 30 dagen per jaar, zonder condensatie su 30 giorni all'anno, senza condensa - ≤95%
IP rating in built-in condition (front part) IP rating in ingebouwde conditie (voorkant) Grado di protezione IP in condizione di incasso (parte frontale) - IP51(*)
(*) For use in accordance with the MID Directive, the energy meter must be installed in a
distribution board/enclosure for modular products with a minimum protection rating IP30 The IP51 ratings apply to the meter parts exposed in front of (outside of) the cover of the enclosure.
terminal block klemblok morsettiera - IP20
MID safety sealing
MID-verzegeling
Sigillo di sicurezza MID
ECR180D
0.25-5(80)A Cl.B (Cl.1) 230V~50Hz
ECR180D
1000 p/kWh
0.25-5(80)A Cl. B(Cl.1) 230V~50Hz
1000
p/kWh
1 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005251Ad
Gegevens conform EN 50470-1, EN 50470-3, IEC 62053-21 en
IEC62053-23
cong.
Aan voorzde gemonteerde rode LED (meter constant)
(*) Voor gebruik in overeenstemming met de MID-richtln moet de energiemeter
worden gemonteerd in een verdeelkast voor modulaire producten met een minimale beschermingsklasse IP30. De IP51 is van toepassing op het gedeelte van de behuizing van de energiemeter dat door de afdekplaat heen naar buiten steekt..
Intern ash niet-vluchtig geheugen Memorizzazione dei valori di
evenredig met actieve imp / exp Energie
Dati conformi alle norme EN 50470-1, EN 50470-3, IEC 62053-21 e
IEC62053-23
energia e congurazione
visualizzazione
LCD retroilluminato - 7.2 +3.2
Memoria interna non volatile -
indutt.
LED rosso frontale (costante del contatore) proporzionale all'energia imp /
(*) Per l'utilizzo in conformità alla direttiva MID, il contatore di energia deve essere installato
in un quadro di distribuzione per apparecchi modulari con grado di protezione minimo IP30. Il grado di protezione IP51 è relativo a parti del contatore esterne al quadro (frontale dell'apparecchio).
exp. Attiva
2 0
-
2
c
kWh kWh
- -1.000 … 1.000
p/kWh 1000
c
c
c
c
c
c
Page 2
z
6LE005251Ad
ECR180D
Safety instructions
This device must be installed only by a professional electrician tter according to local applicable installation standards. Do not plug in or unplug this product when the power supplying is ON. Its use is only permitted within the limits shown and stated in the installation instructions. The device and the equipement connected can be destroyed by loads exceeding the values stated.
Operating principle
This 4 quadrants Modbus RTU meter measures the active and reactive energy used in an electrical installation. This device can manage 2 tariffs by 230 VAC digital input and up to 8 controlled via communication. Only the total active energy register can be used for billing purposes according to measuring instrument directive (MID).
- Active Energy Class B (according to EN 50470)
- Active Power Class 1 (according to IEC 62053-21 and IEC 61557-12)
- Reactive Energy Class 2 (according to IEC 60253-23)
- Reactive Power Class 2 (according to IEC 62053-21). This device has a LCD backlight and 3 push-button keys to read Energies, V, I, PF, F, P, Q and to congure some parameters. The design and manufacture of this meter comply with Standard EN 50470-3 requirements.
Product presentation
LCD display:
Commands
OK
1000
p/kWh
OK button: is used to conrm a modication of a parameter (or of a digit of a numerical parameter) or to answer to a question
SCROLL button: is used to scroll Menu pages or to modify the whole value or a digit of a parameter
ESCAPE button: is used to escape to main menu from any­where or to skip back to the previous digit of the value under modication
Optical metrological LED
Energy for all tariffs
Tariff
Reactive power inductive/capacitive
Main Energy Register, not resettable
Partial Energy Register, resettable
Units
Energy import (consumption ) Energy export (production
Communication activity status
Energy meter has received a message with the correct address and with the correct checksum, but the meter has answered with an Exception Message in case of Modbus:
- illegal function
- illegal data address
- illegal data value
)
One phase energy meter, direct connection 80 A
with MID declaration of conformity and Modbus RTU communication
MID certication concerns active energy only.
User instructions
EU declaration of conformity:
http://hgr.io/r/ecr180d
Symbols
One phase
Protected by double insulation (Class II)
Backstop: Reversal preventing device
Modbus RTU Communication
Recommendations:
Use HTG485H reference cable specially developed as accessory by Hager.
Important:
It is essential to connect a resistance (reference SMC120R) of 120 Ohms at the 2 ends of the connection.
Modbus protocol:
The Modbus protocol operates on a master/slave structure:
• Reading (Function 3),
• Writing (Function 6 or 16), broadcast option at address 0. The communication method is RTU (Remote Terminal Unit) with hexadecimal.
Modbus table:
Download from: http://hgr.io/r/ecr180d
Error condition:
When partial energy blinks, reset partial energy (maximum partial energy register). When the display shows the message ERROR N02 or
ERROR N03, the meter has got a malfunction and must be replaced.
Power factor Convention according to IEC 62053-23
kW
- +
II I
Q
II I
kvar
kvar
+
-
IV
kW
Active Energy Imported By powering. Software version and checksum
1s
Meter type
Tariff 1 with Partial
register
Active Energy Exported
Tariff 1 with Partial
register
1s
Main page is depending on current power direction
indication
with the corresponding global and
partial energy register display.
Active energy exported
Reactive energy
imported
Reactive energy
exported
OK
Tariff related Energies
OK
Partial Register Reset
OK
Measures reading
OK
Conguration
Serial number
Software version and
checksum
OK
OK
OK
OK
Active Energy Imported
Tariff 2 with Partial
register
Active Energy Exported
Tariff 2 with Partial
register
Reactive Energy
Imported Tariff 1
Reactive Energy
Exported Tariff 1
Reactive Energy
Imported Tariff 2
Reactive Energy
Exported Tariff 2
OK
Modbus Address:
1 ... 247
Baud Rate:
1200-2400-4800-9600
19200-38400
Parity:
none-even-odd
Stop Bit:
1-2
After 2 seconds it goes
back to the Main Page
Active Power
Reactive Power
Apparent Power
Voltage
Current
S
Display test
P
OK
Unidirectional
Bidirectional
Power Factor
OK
Note:
If no button is pushed for at least 20 seconds the display goes back to the Main Page and the backlight is switched off again.
2 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005251Ad
PF ≤0 PF ≥0
Tariffs conguration:
1T
2T input 230 V
8T input Modbus
Frequency
Page 3
Reële energie
geïmporteerd Tarief 1
met gedeeltelk register
Reële energie
geëxporteerd Tarief 1
met gedeeltelk register
Reële energie
geïmporteerd Tarief 2
met gedeeltelk register
Reële energie
geëxporteerd Tarief 2
met gedeeltelk register
6LE005251Ad
i
Eenfase energiemeter, directe stroommeting 80 A
met MID-verklaring van overeenstemming en Modbus RTU-communicatie
MID certicering heeft alleen betrekking op werkelke energie.
Gebruikersinstructies
EU-conformiteitsverklaring:
http://hgr.io/r/ecr180d
Via voeding.
Softwareversie en check
1s
som
Meter type
1s
Hoofdpagina is afhankelk van de huidige
aanduiding van de stroomrichting
het bbehorende algemeen en gedeeltelke
energieregisterscherm.
met
ECR180D
Reactieve energie
Veiligheidsinstructies
Dit apparaat mag alleen worden geïnstalleerd door een professionele installateur in overeenstemming met de geldende installatienormen. Sluit dit product niet aan of koppel het niet los b ingeschakelde spanning. Het gebruik ervan is alleen toegestaan binnen de aangegeven grenzen en vermeld in de installatie-instructies. Het apparaat en het aangesloten apparaat kunnen worden beschadigd door belastingen die de vermelde waarden overschrden.
Werkingsprincipe
Deze 4-kwadranten Modbus RTU-meter meet de reële en reactieve energie die wordt gebruikt in een elektrische installatie. Dit apparaat kan 2 tarieven beheren via de binaire 230 VAC tarief ingang en 8 tarieven via de digitale communicatie interface. Alleen het totale actieve energieregister kan voor factureringsdoeleinden worden gebruikt volgens de meetinstrumentrichtln (MID).
- Reële energieklasse B (volgens EN 50470)
- Reële vermogensklasse 1 (volgens IEC 62053-21 en IEC 61557-12)
- Reactieve energieklasse 2 (volgens IEC 60253-23)
- Reactieve vermogensklasse 2 (volgens IEC 62053-21). Dit apparaat heeft een LCD-achtergrondverlichting en 3 druktoetsen om de meetwaarden, V, I, PF, F, P, Q te lezen en om enkele parameters te congureren. Het ontwerp en de fabricage van deze meter voldoen aan de vereisten van norm EN 50470-3.
Productpresentatie
LCD scherm:
Commando's
Opmerking:
Als er ten minste 20 seconden lang op geen enkele knop wordt gedrukt, keert het display terug naar de hoofdpagina en wordt de achtergrondverlichting weer uitgeschakeld.
OK-knop: wordt gebruikt om een wziging van een parameter
OK
(of een cfer van een numerieke parameter) te bevestigen of om een vraag te beantwoorden
SCROLL-knop: wordt gebruikt om door menupagina's te bladeren of om de hele waarde of een cfer van een parameter te wzigen
ESCAPE-knop: wordt gebruikt om naar het hoofdmenu terug te gaan of om naar het vorige cfer van de gewzigde waarde terug te gaan
1000
Optische metrologische LED
p/kWh
3 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005251Ad
Energie voor alle tarieven
Tarief
Reactief vermogen inductief/capacitief
Hoofdenergieregister, niet opnieuw instelbaar
Gedeeltelk energieregister, opnieuw instelbaar
Eenheden
Energie-import (consumptie ) Energie-export (productie
Status van communicatieactiviteit
Energiemeter een bericht heeft ontvangen met het juiste adres en de juiste controlesom, maar de meter heeft beantwoord met een uitzonderingsbericht in het geval van Modbus:
- illegale functie
- illegaal gegevensadres
- illegale gegevenswaarde
)
Symbolen
Een fase
Beschermd door dubbele isolatie (klasse II)
Backstop: apparaat om achteruitrden te voorkomen
Modbus RTU communicatie
Aanbevelingen:
Gebruik HTG485H-referentiekabels die speciaal zn ontwikkeld als accessoire door Hager.
Belangrk:
Het is noodzakelk om een weerstand (referentie SMC120R) van 120 Ohm aan te sluiten op beide uiteinden van de datacommunicatiekabel.
Modbus-protocol:
Het Modbus-protocol werkt op een master / slave-structuur:
• Lezen (functie 3),
• Schrven (functie 6 of 16), broadcast optie op adres 0. De communicatiemethode is RTU (Remote Terminal Unit) met hexadecimaal.
Modbus-tabel:
Downloaden van: http://hgr.io/r/ecr180d
Foutconditie:
In de situatie dat het woord Partial op het diplay knippert, dan heeft de “partial” teller de maximale waarde overschreden. In dit geval moet je de “partial” teller resetten. In de situatie dat de foutmeldingen ERROR N02 of ERROR N03 op het display verschnen dan is er een defect in de meter. In deze situatie moet de meter worden vervangen.
Powerfactor Conventie volgens IEC 62053-23
kW
- +
II I
kvar
kvar
+
-
II I
PF ≤0 PF ≥0
Reële energie geëxporteerd
Reactieve energie
geïmporteerd
Reactieve energie
geëxporteerd
OK
Tariefgerelateerde
energieën
OK
Gedeeltelk register
resetten
OK
Meetwaarden
OK
OK
Conguratie
OK
Serienummer
OK
kW
Softwareversie en
check som
OK
Q
S
Displaytest
P
OK
IV
OK
geïmporteerd Tarief 1
Reactieve energie
geëxporteerd Tarief 1
Reactieve energie
geïmporteerd Tarief 2
Reactieve energie
geëxporteerd Tarief 2
OK
Modbus-adres:
1 ... 247
Baudrate:
1200-2400-4800-9600
19200-38400
Pariteit:
geen-even-oneven
Stop Bit:
1-2
Unidirectionele
Bidirectionele
Tarieven conguratie:
1T
2T ingang 230 V
8T ingang Modbus
Na 2 seconden gaat
het terug naar de
hoofdpagina
Reëel vermogen
Reactief vermogen
Schnbaar
vermogen
Spanning
Stroom
Powerfactor
Frequentie
Page 4
Energia attiva importata
Tariffa 1 con registro
parziale
Energia attiva esportata
Tariffa 1 con registro
parziale
Energia attiva importata
Tariffa 2 con registro
parziale
Energia attiva esportata
Tariffa 2 con registro
parziale
6LE005251Ad
y
Contatore di energia monofase, inserzione diretta 80 A
con dichiarazione di conformità MID e comunicazione Modbus RTU
La certicazione MID riguarda solo la energia attiva.
Istruzioni per l'utente
Dichiarazione di conformità UE:
http://hgr.io/r/ecr180d
Alimentandolo. Versione
software e checksum
1s
Tipo di contatore
1s
La
pagina principale dipende dall'indicazione
della direzione della potenza impostata
corrispondente display del registro di energia globale
e parziale.
con il
ECR180D
Energia reattiva
Istruzioni per la sicurezza
Questo dispositivo deve essere installato esclusivamente da un elettricista professionista secondo le norme di installazione locali applicabili. Non collegare o scollegare il prodotto quando è alimentato. Il suo utilizzo è consentito solo nei limiti indicati e dichiarati nelle istruzioni di installazione. Il dispositivo e le apparecchiature collegate possono essere danneggiati da carichi che superano i valori indicati.
Principio di funzionamento
Questo misuratore Modbus RTU a 4 quadranti misura l'energia attiva e reattiva utilizzata in un'installazione elettrica. Questo dispositivo può gestire 2 tariffe tramite ingresso digitale da 230 VAC e no a 8 tariffe controllate tramite comunicazione. Solo il registro di energia attiva totale può essere utilizzato per la fatturazione in base alla direttiva dello strumento di misura (MID).
- Classe Energia Attiva B (secondo EN 50470)
- Classe Potenza Attiva 1 (secondo IEC 62053-21 e IEC 61557-12)
- Classe Energia Reattiva 2 (secondo IEC 60253-23)
- Classe Potenza Reattiva 2 (secondo IEC 62053-21). Questo apparecchio è dotato di display LCD retroilluminato e 3 pulsanti per leggere Energia, V, I, PF, F, P, Q e per congurare alcuni parametri. La progettazione e la fabbricazione di questo strumento sono conformi ai requisiti della norma EN 50470-3.
Presentazione del prodotto
Display LCD:
Comandi
Nota:
Se non viene premuto alcun pulsante per almeno 20 secondi, il display torna alla pagina principale e la retroilluminazione viene nuovamente disattivata.
Pulsante OK: consente di confermare una modica di un
OK
parametro (o di una cifra di un parametro numerico) o di rispondere a una domanda
Pulsante SCROLL: consente di scorrere le pagine del menu o di modicare l'intero valore o una cifra di un parametro
Tasto ESCAPE: serve per uscire dal menu principale da qualsiasi posizione o per passare alla cifra precedente del valore in modica
1000
LED metrologico ottico
p/kWh
4 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005251Ad
Energia per tutte le tariffe
Tariffa
Potenza reattiva induttiva/capacitiva
Registro principale dell'Energia, non resettabile
Registro parziale dell'Energia, resettabile
Unità
Energia importata (consumata ) Energia esportata (prodotta
Stato della comunicazione
Il contatore di energia ha ricevuto un messaggio con l'indirizzo corretto e con il checksum corretto ma ha risposto con un messaggio di errore in caso di comunicazione Modbus:
- funzione non valida
- indirizzo dati non valido
- valore dati non valido
Symboli
Monofase
Protetto da doppio isolamento (Classe II)
Backstop: dispositivo anti inversione
Comunicazione Modbus RTU
Raccomandazioni:
Utilizzare i cavi codice HTG485H appositamente sviluppati come accessorio da Hager.
Importante:
È essenziale collegare una resistenza (riferimento SMC120R) da 120 Ohm alle 2 estremità della connessione.
Protocollo Modbus:
Il protocollo Modbus opera su una struttura master / slave:
• Lettura (funzione 3),
• Scrittura (Funzione 6 o 16), opzione di trasmissione all'indirizzo 0. Il metodo di comunicazione è RTU (Remote Terminal Unit) esadecimale.
Piattaforma Modbus:
Scarica da: http://hgr.io/r/ecr180d
Condizione di errore:
Quando l'energia parziale lampeggia, ripristinare l'energia parziale (registro massimo dell'energia parziale). Quando il display mostra il messaggio ERROR N02 o ERROR N03, lo strumento ha un malfunzionamento e deve essere sostituito.
)
Fattore di potenza Convenzione secondo IEC 62053-23
kW
- +
II I
Q
II I
kvar
kvar
+
-
PF ≤0 PF ≥0
IV
kW
Energia attiva esportata
Energia reattiva
importata
Energia reattiva
esportata
OK
Energia legata alle
tariffe
OK
Reset del registro
parziale
OK
Lista misure
OK
OK
Congurazione
OK
Numero di serie
OK
Versione software e
checksum
OK
S
Test di
visualizzazione
P
OK
OK
importata Tariffa 1
Energia reattiva
esportata Tariffa 1
Energia reattiva
importata Tariffa 2
Energia reattiva
esportata Tariffa 2
OK
Indirizzo Modbus:
1 ... 247
Velocità Baud:
1200-2400-4800-9600
19200-38400
Parità:
nessuno-pari-dispari
Stop Bit:
1-2
Unidirezionale
Bidirezionale
Congurazione delle
tariffe:
1T
2T ingresso 230 V
8T ingresso Modbus
Dopo 2 secondi torna alla pagina principale
Potenza attiva
Potenza reattiva
Potenza Apparente
Tensione
Corrente
Fattore di potenza
Frequenza