z i y
Technical data Technische data Dati tecnici
z
i
y
Data in compliance with EN 50470-1, EN 50470-3,
IEC 62053-21 and IEC62053-23
General characteristics Algemene karakteristieken Caratteristiche generali
Housing DIN 43880 Behuizing DIN 43880 Involucro DIN 43880 DIN
Mounting EN 60715 Montage EN 60715 Montaggio EN 60715 DIN rail 35 mm
Depth Diepte Profondità mm 60
Weight Gewicht Peso g 60
Operating features Bedieningsfuncties Funzionalità operative
6LE005488Ad
Connection to single-phase network - number
Storage of energy values
and conguration
Approval (according to EN 50470-1, EN 50470-3) Goedkeuring (volgens EN 50470-1, EN 50470-3) Omologazione (secondo EN 50470-1, EN 50470-3)
Reference Voltage (Un) Referentiespanning (Un) Tensione di riferimento (Un) VAC 230
of wires
Internal ash non volatile memory Opslag van energiewaarden
Reference Current (Iref) Referentie stroom (Iref) Corrente di riferimento (Iref) A 5
Minimum Current (Imin) Minimumstroom (Imin) Corrente minima (Imin) A 0.25
Maximum Current (Imax) Maximale stroom (Imax) Corrente massima (Imax) A 40
ECR140D
Sealable terminal cover Dimension
Verzegelbare
schroefklemafdekkap
Coprimorsetto sigillabile Dimensione
Afmetingen
18
Starting Current (Ist) Startstroom (Ist) Corrente di avviamento (Ist) A 0.020
Reference Frequency (fn) Referentie frequentie (fn) Frequenza di riferimento (fn) Hz 50
Number of phases / number of wires Aantal fasen / aantal draden Numero di fasi / numero di li - 1 / 2
Certied Measures Gecerticeerde maatregelen Misure certicate kWh
Accuracy Nauwkeurigheid Precisione
- Active Energies (accord. to EN 50470-3) - Reële energie (conform EN 50470-3) - Energia attiva (secondo EN 50470-3) classe B
- Active Powers (accord. to IEC 62053-21 and IEC 61557-12) - Reëel vermogen (conform IEC 62053-21 en IEC 61557-12) - Potenza attiva (secondo IEC 62053-21 e IEC 61557-12) classe 1
Supply Voltage and Power Consumption Voedingsspanning en Energieverbruik Tensione di alimentazione e potenza assorbita
Operating Supply Voltage range Bedrfsspanningbereik Intervallo tensione di alimentazione V 92 … 276
Maximum Power Consumption (Voltage circuit) Maximaal energieverbruik (Spanningscircuit) Potenza massima assorbita (circuito voltmetrico) VA / W ≤2 / ≤1
Maximum VA burden (Current circuit) @ Imax Maximale VA last (stroom circuit) @ Imax Massimo assorbimento VA (circuito amperometrico) @ Imax VA ≤1
Voltage Input Waveform Meetspanningsvorm Forma d'onda tensione di ingresso - AC
Voltage impedance Impedantie spanningsingang Impedenza circuito voltmetrico MΩ 1
Current impedance Impedantie stroomingang Impedenza circuito amperometrico mΩ ≤20
Overload capability Overbelastingscapaciteit Capacità di sovraccarico
92
45
Voltage continuous Spanning doorlopend Tensione continuo VAC 276
temporary (1 s) tdelk (1 s) temporaneo (1 s) VAC 300
Current continuous Stroom doorlopend Corrente continuo A 40
temporary (10 ms) tdelk (10 ms) temporaneo (10 ms) A 1200
Measuring Features Meetfuncties Funzioni di misura
Voltage range Spanningsbereik Intervallo di tensione VAC 92 … 276
Current range Stroombereik Intervallo di corrente A 0.020 … 40
7
44
60
Frequency range Frequentiebereik Intervallo di frequenza Hz 45 … 65
Measured Quantities Gemeten hoeveelheden Quantità misurate - V, A, kWh, PF, Hz, kW
Display features Display functies Caratteristiche del display
Display type LCD Display type LCD Tipo di
Active Energy 5 digits + 2 decimal digits Reële Energie 5 cfers + 2 decimalen Energia attiva 5 cifre + 2 cifre decimali kWh 0.01 … 99999.99
Wiring diagram
Cable stripping length and terminal screw torque
Aansluitschema
Kabelstriplengte en aandraaimomenten van de
aansluitklemmen
Schema di collegamento
Lunghezza di sguainatura del cavo e coppia della
vite del morsetto
Voltage 3 digits + 2 decimal digits Spanning 3 cfers + 2 decimalen Tensione 3 cifre + 2 cifre decimali V 92.00 … 276.00
Current 2 digits + 2 decimal digits Stroom 2 cfers + 2 decimalen Corrente 2 cifre + 2 cifre decimali A 0.00 … 40.00
Power factor 1 digit + 2 decimal digits with sign + capac./
induc. indic.
Frequency 2 digits + 2 decimal digits Frequentie 2 cfers + 2 decimalen Frequenza 2 cifre + 2 cifre decimali Hz 45.00 … 65.00
Active Power 2 digits + 2 decimal digits with sign Reëel vermogen 2 cfers + 2 decimalen met teken Potenza attiva 2 cifre + 2 cifre decimali con segno kW 0.00 … 11.04
Display refresh period Toon verversingsperiode Frequenza di aggiornamento del display s 1
Optical metrological LED Optische metrologische LED LED metrologico ottico
Front mounted red LED (meter
constant)
proportional to active
imp/exp Energy
Safety Veiligheid Sicurezza
Overvoltage category Overspanningscategorie Categoria di sovratensione - 3
Protective class Beschermingsklasse Classe di protezione classe II
AC voltage test (EN 50470-3, 7.2) AC spanningstest (EN 50470-3, 7.2) Test di tensione AC (EN 50470-3, 7.2) kV 4
Degree of pollution Vervuilingsgraad Grado di inquinamento - 2
Operational voltage Nominale spanning Tensione di funzionamento V 300
Impulse voltage test (Uimp) Impulsspanningstest (Uimp) Test di tensione ad impulso (Uimp) 1.2/50 μs-kV 6
Housing material ame resistance UL 94 Behuizing materiaal vlamwerendheid UL 94 Resistenza alla amma del materiale
6 8 10
Ultrasonic safety welding between upper and lower housing
part
Embedded Modbus communication Geïntegreerde communicatie Modbus Comunicazione incorporata Modbus
Physical interface RS-485 - 3 wires Fysieke interface RS-485 - 3 draden Interfaccia sica RS-485 - 3 li - -, +, 0
Baud rate adjustable Baudrate Instelbaar Velocità Baud regolabile bps 1200 … 38400
Parity adjustable: Odd, Even, None Pariteit Instelbaar: Oneven, even, geen Parità regolabile: Dispari, Pari, Nessuno Stop Bit adjustable Stop Bit Instelbaar Stop Bit regolabile - 1, 2
Address adjustable Adres Instelbaar Indirizzo regolabile - 1 … 247
MID certied
MID gecerticeerd
Certicato MID
Isolation class SELV Isolatieklasse SELV Classe di isolamento SELV -
Environmental conditions Milieuomstandigheden Condizioni ambientali
Storage temperature range Opslagtemperatuur Temperatura di stoccaggio °C -25 … +70
Operating temperature range Bedrfstemperatuur Temperatura di funzionamento °C -25 … +55
Mechanical environment Mechanische omgeving Ambiente meccanico - M1
Electromagnetic environment Elektromagnetische omgeving Ambiente elettromagnetico - E2
Installation indoor only Installatie alleen binnen Installazione solo all'interno -
Altitude (max.) Hoogte (max.) Altitudine (max.) m ≤2000
Humidity yearly average, without
condensation
on 30 days per year, without
condensation
IP rating in built-in condition (front part) IP rating in ingebouwde conditie (voorkant) Grado di protezione IP in condizione di incasso (parte
(*) For use in accordance with the MID Directive, the energy meter must be installed in a
distribution board/enclosure for modular products with a minimum protection rating IP30
The IP51 ratings apply to the meter parts exposed in front of (outside of) the cover of the
enclosure.
1 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005488Ad
terminal block klemblok morsettiera - IP20
Gegevens conform EN 50470-1, EN 50470-3, IEC 62053-21
en IEC62053-23
Verbinding naar eenfasig netwerk - aantal
en cong.
Powerfactor 1 cfer + 2 decimalen + capaciteit./induc.
Aan voorzde gemonteerde rode LED
(meter constant)
Ultrasoon veiligheidslassen verbinden bovenste en onderste
behuizingsdelen
indic.
Vochtigheid jaarlks gemiddelde, zonder
(*) Voor gebruik in overeenstemming met de MID-richtln moet de energiemeter
worden gemonteerd in een verdeelkast voor modulaire producten met een minimale
beschermingsklasse IP30. De IP51 is van toepassing op het gedeelte van de behuizing van
de energiemeter dat door de afdekplaat heen naar buiten steekt..
draden
Intern ash niet-vluchtig geheugen Memorizzazione dei valori
evenredig met actieve
imp / exp Energie
condensatie
op 30 dagen per jaar, zonder
condensatie
Dati conformi alle norme EN 50470-1, EN 50470-3, IEC
62053-21 e IEC62053-23
1 0
Connessione alla rete monofase - numero di li
di energia e congurazione
Memoria interna non volatile -
-
2
c
kWh kWh
visualizzazione
Fattore di
potenza
LED rosso frontale (costante del
contatore)
dell'involucro
Saldatura ad ultrasuoni di sicurezza tra la parte superiore e
quella inferiore della custodia
LCD - 7.0 / 5.2
1 cifra + 2 cifre decimali con segno + indic.
capac. / indutt.
proporzionale all'energia
imp / exp. Attiva
- -1.00 … 1.00
p/kWh 5000
UL 94 classe V0
-
c
c
c
c
Umidità media annuale, senza condensa - ≤75%
su 30 giorni all'anno, senza
condensa
frontale)
(*) Per l'utilizzo in conformità alla direttiva MID, il contatore di energia deve essere installato
in un quadro di distribuzione per apparecchi modulari con grado di protezione minimo
IP30. Il grado di protezione IP51 è relativo a parti del contatore esterne al quadro (frontale
dell'apparecchio).
- ≤95%
- IP51(*)

z
6LE005488Ad
ECR140D
Safety instructions
This device must be installed only by a professional electrician tter
according to local applicable installation standards. Do not plug in
or unplug this product when the power supplying is ON. Its use is
only permitted within the limits shown and stated in the installation
instructions. The device and the equipement connected can be destroyed
by loads exceeding the values stated.
One phase energy meter,
direct connection 40 A
with MID declaration of conformity
and Modbus RTU communication
MID certication concerns active energy only.
User instructions
EU declaration of conformity:
http://hgr.io/r/ecr140d
Symbols
One phase
Protected by double insulation (Class II)
Backstop: Reversal preventing device
1 s
Main page is depending on current power direction indication
with the corresponding global and partial energy register
display.
< 1 s
< 1 s
< 1 s
< 1 s
Meter type
Active energy imported
Active energy exported
Active Power
(in this case:
imported
)
Voltage
< 1 s
< 1 s
...
> 3 s
< 1 s
< 1 s
...
> 3 s
Short press to change
value
Short press to change
value
Long press to validate
value
Short press to change
value
Short press to change
value
Long press to validate
value
Operating principle
This Modbus RTU meter measures the active energy used in an
electrical installation. This device can manage up to 8 tariffs controlled
via communication. Only the total active energy register can be used for
billing purposes according to measuring instrument directive (MID).
- Active Energy Class B (according to EN 50470)
- Active Power Class 1 (according to IEC 62053-21 and IEC 61557-12)
This device has a LCD and 1 push-button key to read Energies, V, I, PF, F,
P and to congure some parameters. The design and manufacture of this
meter comply with Standard EN 50470-3 requirements.
Product presentation
LCD display:
Energy register (kWh), not resettable
Energy import (consumption )
Energy export (production
)
Commands
Command button:
Short press: Push briey (<1 sec.) the button and then release
it.
Used to scroll pages or during parameter’s modication.
Long Press: Keep the button pushed for at least 3 seconds.
Used to start and to conrm parameter’s modications.
Optical metrological LED
Note:
If no button is pushed for at least 20 seconds the display goes back to the
Main Page.
Modbus RTU Communication
Recommendations:
Use HTG485H reference cable specially developed as accessory by
Hager.
Important:
It is essential to connect a resistance (reference SMC120R) of 120 Ohms
at the 2 ends of the connection.
Modbus protocol:
The Modbus protocol operates on a master/slave structure:
• Reading (Function 3),
• Writing (Function 6 or 16), broadcast option at address 0.
The communication method is RTU (Remote Terminal Unit) with
hexadecimal.
Modbus table:
Download from: http://hgr.io/r/ecr140d
Error condition:
When the display shows the message ERROR 2 or ERROR 3, the meter
has got a malfunction and must be replaced.
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
1200-2400-4800-9600
< 1 s
Even1 - Even2 - None1
< 1 s
< 1 s
Current
Frequency
Power factor
Modbus Address:
1 ... 247
Baud Rate:
19200-38400
Parity + stop bit:
None2 - Odd1 - Odd2
Serial number
> 3 s
< 1 s
< 1 s
> 3 s
> 3 s
> 3 s
Short press to change
value
Short press to change
value
Long press to validate
value
Long press to modify
current value
- Change: short press
- Validate: long press
Long press to modify
current value
- Change: short press
- Validate: long press
Power factor
Convention according to IEC 62053-23
kW
kW
< 1 s
Software version and
checksum
- +
II I
kvar
kvar
+
-
Q
II I
S
P
IV
PF ≤0 PF ≥0
2 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005488Ad
< 1 s
Display test

i
6LE005488Ad
ECR140D
Veiligheidsinstructies
Dit apparaat mag alleen worden geïnstalleerd door een professionele
installateur in overeenstemming met de geldende installatienormen.
Sluit dit product niet aan of koppel het niet los b ingeschakelde
spanning. Het gebruik ervan is alleen toegestaan binnen de aangegeven
grenzen en vermeld in de installatie-instructies. Het apparaat en het
aangesloten apparaat kunnen worden beschadigd door belastingen die
de vermelde waarden overschrden.
Werkingsprincipe
Deze Modbus RTU-meter meet de actieve energie die wordt gebruikt
in een elektrische installatie. Dit apparaat kan maximaal 8 tarieven
beheren via communicatie. Alleen het totale actieve energieregister
kan voor factureringsdoeleinden worden gebruikt volgens de
meetinstrumentrichtln (MID).
- Reële energieklasse B (volgens EN 50470)
- Reële vermogensklasse 1 (volgens IEC 62053-21 en IEC 61557-12)
Dit apparaat heeft een LCD en 1 druktoets om Energies, V, I, PF, F, P
te lezen en om enkele parameters te congureren. Het ontwerp en
de fabricage van deze meter voldoen aan de vereisten van norm EN
50470-3.
Productpresentatie
LCD scherm:
Energieregister (kWh), niet opnieuw
instelbaar
Commando's
Command knop:
Korte druk: Druk kort (<1 sec.) Op de knop en laat deze dan
los.
Wordt gebruikt om door pagina's te bladeren of tdens de
wziging van de parameter.
Lang indrukken: Houd de knop minstens 3 seconden
ingedrukt.
Wordt gebruikt om de wzigingen van de parameter te starten
en te bevestigen.
Optische metrologische LED
Energie-import (consumptie )
Energie-export (productie
)
Eenfase energiemeter,
directe stroommeting 40 A
met MID-verklaring van overeenstemming
en Modbus RTU-communicatie
MID certicering heeft alleen betrekking op werkelke energie.
Gebruikersinstructies
EU-conformiteitsverklaring:
http://hgr.io/r/ecr140d
Symbolen
Een fase
Beschermd door dubbele isolatie (klasse II)
Backstop: apparaat om achteruitrden te voorkomen
Modbus RTU communicatie
Aanbevelingen:
Gebruik HTG485H-referentiekabels die speciaal zn ontwikkeld als
accessoire door Hager.
Belangrk:
Het is noodzakelk om een weerstand (referentie SMC120R) van 120
Ohm aan te sluiten op beide uiteinden van de datacommunicatiekabel.
Modbus-protocol:
Het Modbus-protocol werkt op een master / slave-structuur:
• Lezen (functie 3),
• Schrven (functie 6 of 16), broadcast optie op adres 0.
De communicatiemethode is RTU (Remote Terminal Unit) met
hexadecimaal.
Modbus-tabel:
Downloaden van: http://hgr.io/r/ecr140d
Foutconditie:
In de situatie dat de foutmeldingen ERROR 2 of ERROR 3 op het display
verschnen dan is er een defect in de meter. In deze situatie moet de
meter worden vervangen.
1 s
Hoofdpagina is afhankelk van de huidige aanduiding van
de stroomrichting
met het bbehorende algemeen en
gedeeltelke energieregisterscherm.
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
Meter type
Reële energie
geïmporteerd
Reële energie
geëxporteerd
Reëel vermogen
(in dit geval:
geïmporteerd
Spanning
Stroom
Frequentie
Powerfactor
Modbus-adres:
1 ... 247
Baudrate:
1200-2400-4800-9600
19200-38400
< 1 s
< 1 s
Pariteit + stopbit:
Even1 - Even2 - Geen1
Geen2 - Vreemd1 - Vreemd2
Serienummer
Druk kort om de waarde
< 1 s
< 1 s
te wzigen
Druk kort om de waarde
te wzigen
...
Lang drukken om de
> 3 s
< 1 s
< 1 s
)
waarde te valideren
Druk kort om de waarde
te wzigen
Druk kort om de waarde
te wzigen
...
Lang drukken om de
> 3 s
< 1 s
< 1 s
> 3 s
> 3 s
> 3 s
> 3 s
waarde te valideren
Druk kort om de waarde
te wzigen
Druk kort om de waarde
te wzigen
Lang drukken om de
waarde te valideren
Lang indrukken om
de huidige waarde te
wzigen
- Verandering: korte druk
- Bevestig: lang
indrukken
Lang indrukken om
de huidige waarde te
wzigen
- Verandering: korte druk
- Bevestig: lang
indrukken
< 1 s
Opmerking:
Als er ten minste 20 seconden lang op geen enkele knop wordt gedrukt,
keert het display terug naar de hoofdpagina.
Powerfactor
Conventie volgens IEC 62053-23
kW
kW
Softwareversie en check
< 1 s
som
- +
II I
kvar
kvar
+
-
Q
II I
S
P
IV
PF ≤0 PF ≥0
3 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005488Ad
< 1 s
Displaytest

y
6LE005488Ad
ECR140D
Istruzioni per la sicurezza
Questo dispositivo deve essere installato esclusivamente da un
elettricista professionista secondo le norme di installazione locali
applicabili. Non collegare o scollegare il prodotto quando è alimentato. Il
suo utilizzo è consentito solo nei limiti indicati e dichiarati nelle istruzioni
di installazione. Il dispositivo e le apparecchiature collegate possono
essere danneggiati da carichi che superano i valori indicati.
Contatore di energia monofase,
inserzione diretta 40 A
con dichiarazione di conformità MID
e comunicazione Modbus RTU
La certicazione MID riguarda solo la energia attiva.
Istruzioni per l'utente
Dichiarazione di conformità UE:
http://hgr.io/r/ecr140d
Symboli
Monofase
Protetto da doppio isolamento (Classe II)
Backstop: dispositivo anti inversione
1 s
La pagina principale dipende dall'indicazione della direzione
della potenza impostata
registro di energia globale e parziale.
con il corrispondente display del
< 1 s
< 1 s
< 1 s
< 1 s
Tipo di contatore
Energia attiva importata
Energia attiva esportata
Potenza attiva
(in questo caso:
importato
)
Tensione
Premere brevemente per
< 1 s
< 1 s
modicare il valore
Premere brevemente per
modicare il valore
...
> 3 s
< 1 s
< 1 s
Premere a lungo per
convalidare il valore
Premere brevemente per
modicare il valore
Premere brevemente per
modicare il valore
...
> 3 s
Premere a lungo per
convalidare il valore
Principio di funzionamento
Questo contatore Modbus RTU misura l'energia attiva utilizzata in
un'installazione elettrica.
Questo dispositivo può gestire no a 8 tariffe controllate tramite
comunicazione. Solo il registro di energia attiva totale può essere
utilizzato per la fatturazione in base alla direttiva dello strumento di
misura (MID).
- Classe Energia Attiva B (secondo EN 50470)
- Classe Potenza Attiva 1 (secondo IEC 62053-21 e IEC 61557-12)
Questo dispositivo ha un display LCD e 1 pulsante per leggere Energia,
V, I, PF, F, P e per congurare alcuni parametri. La progettazione e la
fabbricazione di questo strumento sono conformi ai requisiti della norma
EN 50470-3.
Presentazione del prodotto
Display LCD:
Registro di energia (kWh), non
resettabile
Energia importata (consumata )
Energia esportata (prodotta
)
Comandi
Pulsante di comando:
Breve pressione: Premere brevemente (<1 sec.) Il pulsante e
quindi rilasciarlo.
Utilizzato per scorrere le pagine o durante la modica dei
parametri.
Premere a lungo: Tenere premuto il pulsante per almeno 3
secondi.
Utilizzato per iniziare e confermare le modiche del parametro.
LED metrologico ottico
Comunicazione Modbus RTU
Raccomandazioni:
Utilizzare i cavi codice HTG485H appositamente sviluppati come
accessorio da Hager.
Importante:
È essenziale collegare una resistenza (riferimento SMC120R) da 120
Ohm alle 2 estremità della connessione.
Protocollo Modbus:
Il protocollo Modbus opera su una struttura master / slave:
• Lettura (funzione 3),
• Scrittura (Funzione 6 o 16), opzione di trasmissione all'indirizzo 0.
Il metodo di comunicazione è RTU (Remote Terminal Unit) esadecimale.
Piattaforma Modbus:
Scarica da: http://hgr.io/r/ecr140d
Condizione di errore:
Quando il display mostra il messaggio ERROR 2 o ERROR 3, lo
strumento ha un malfunzionamento e deve essere sostituito.
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
Fattore di potenza
Indirizzo Modbus:
1200-2400-4800-9600
Pari1 - Pari2 - Nessuno1
Nessuno2 - Dispari1 - Dispari2
Corrente
Frequenza
1 ... 247
Velocità Baud:
19200-38400
Parità + stop bit:
Numero di serie
> 3 s
Premere brevemente per
< 1 s
< 1 s
> 3 s
> 3 s
> 3 s
modicare il valore
Premere brevemente per
modicare il valore
Premere a lungo per
convalidare il valore
Premere a lungo per
modicare il valore corrente
- Modicare: breve
- Confermare: premere
Premere a lungo per
modicare il valore corrente
- Modicare: breve
- Confermare: premere
pressione
a lungo
pressione
a lungo
Nota:
Se non viene premuto alcun pulsante per almeno 20 secondi, il display torna
alla pagina principale.
Fattore di potenza
Convenzione secondo IEC 62053-23
kW
kW
< 1 s
< 1 s
Versione software e
checksum
- +
II I
kvar
kvar
+
-
Q
II I
S
P
IV
PF ≤0 PF ≥0
4 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005488Ad
< 1 s
Test di visualizzazione