Hager ECM300C User guide

Page 1
z i y
Technical data Technische data Dati tecnici
z i y
6LE005414Ad
ECM300C
Sealable terminal cover Dimension Verzegelbare
schroefklemafdekkap Coprimorsetto sigillabile Dimensione
90
7
Wiring diagram Cable stripping length and terminal screw torque
Aansluitschema Kabelstriplengte en aandraaimomenten van de
aansluitklemmen Schema di collegamento
Lunghezza di sguainatura del cavo e coppia della vite del morsetto
MID certied MID gecerticeerd Certicato MID
MID safety sealing
MID-verzegeling
Sigillo di sicurezza MID
Afmetingen
72
44
60
45
Data in compliance with EN 50470-1, EN 50470-3, IEC 62053-21 and
IEC62053-23
General characteristics Algemene karakteristieken Caratteristiche generali
Housing DIN 43880 Behuizing DIN 43880 Involucro DIN 43880 Mounting EN 60715 Montage EN 60715 Montaggio EN 60715 DIN rail 35 mm Depth Diepte Profondità mm 60 Weight Gewicht Peso g 293
Operating features Bedieningsfuncties Funzionalità operative
Connection to three-phase network - number of wires Verbinding naar driefasen netwerk - aantal draden Connessione alla rete trifase - numero di li Storage of energy values and
conguration
Tariff for active and reactive energy Tarief voor reële en reactieve energie Tariffa per energia attiva e reattiva - T1 … T2 230V - T1 … T2 M-Bus
Approval (according to EN 50470-1, EN 50470-3) Goedkeuring (volgens EN 50470-1, EN 50470-3) Omologazione (secondo EN 50470-1, EN 50470-3)
Connection Verbinding Connessione - CT /5A - CT /1A Reference Voltage (Un) phase / neutral Referentiespanning (Un) fase /nul Tensione di riferimento (Un) fase / neutro VAC 230
Reference Current (Iref) Referentie stroom (Iref) Corrente di riferimento (Iref) A 1 Minimum Current (Imin) Minimumstroom (Imin) Corrente minima (Imin) A 0.01 Maximum Current (Imax) Maximale stroom (Imax) Corrente massima (Imax) A 6 Starting Current (Ist) Startstroom (Ist) Corrente di avviamento (Ist) A 0.001 External CT max. CT ratio Externe CT max. CT-ratio CT esterno max. Rapporto CT - 6000/5 - 1200/1 Reference Frequency (fn) Referentie frequentie (fn) Frequenza di riferimento (fn) Hz 50 Number of phases / number of wires Aantal fasen / aantal draden Numero di fasi / numero di li - 3 / 4
Certied Measures Gecerticeerde maatregelen Misure certicate
Accuracy Nauwkeurigheid Precisione
- Active Energies (accord. to EN 50470-3) - Reële energie (conform EN 50470-3) - Energia attiva (secondo EN 50470-3)
- Active Powers (accord. to IEC 62053-21 and IEC 61557-12) - Reëel vermogen (conform IEC 62053-21 en IEC 61557-12) - Potenza attiva (secondo IEC 62053-21 e IEC 61557-12)
- Reactive Energies (accord. to IEC 62053-23) - Reactive Energieën (conform IEC 62053-23) - Energia reattiva (secondo IEC 62053-23)
- Reactive Powers (accord. to IEC 62053-21) - Reactief vermogen (conform IEC 62053-21) - Energia reattiva (secondo IEC 62053-21)
Supply Voltage and Power Consumption Voedingsspanning en Energieverbruik Tensione di alimentazione e potenza assorbita
Operating Supply Voltage range Bedrfsspanningbereik Intervallo tensione di alimentazione V 92 … 276 / 160 … 480 Maximum Power Consumption (Voltage circuit) Maximaal energieverbruik (Spanningscircuit) Potenza massima assorbita (circuito voltmetrico) VA / W ≤2 / 0.6 Maximum VA burden (Current circuit) @ Imax Maximale VA last (stroom circuit) @ Imax Massimo assorbimento VA (circuito amperometrico) @ Imax VA ≤0.7
Voltage Input Waveform Meetspanningsvorm Forma d'onda tensione di ingresso - AC Voltage impedance Impedantie spanningsingang Impedenza circuito voltmetrico 1 Current impedance Impedantie stroomingang Impedenza circuito amperometrico ≤20
Overload capability Overbelastingscapaciteit Capacità di sovraccarico
Voltage continuous phase / neutral Spanning doorlopend fase /nul Tensione continuo fase / neutro VAC 276
Current continuous Stroom doorlopend Corrente continuo A 6
Measuring Features Meetfuncties Funzioni di misura
Voltage range phase / neutral Spanningsbereik fase /nul Intervallo di tensione fase / neutro VAC 92 … 276
Current range (secondary winding) Huidig bereik (secundaire wikkeling) Gamma corrente (avvolgimento secondario) A 0.001 … 6
Frequency range Frequentiebereik Intervallo di frequenza Hz 45 … 65 Measured Quantities Gemeten hoeveelheden Quantità misurate - V, A, kWh, kvarh, PF, Hz, kW, kvar
Display features Display functies Caratteristiche del display
Display type LCD with backlight Display type LCD met achtergrondverlichting Tipo di
Active Energy 7 digits + 2 decimal digits / 8+1 Reële Energie 7 cfers + 2 decimalen / 8+1 Energia attiva 7 cifre + 2 cifre decimali / 8+1 kWh 0.01 … 99999999.9 Reactive Energy 7 digits + 2 decimal digits / 8+1 Reactieve energie 7 cfers + 2 decimalen / 8+1 Energia reattiva 7 cifre + 2 cifre decimali / 8+1 kvarh 0.01 … 99999999.9 Voltage 3 digits + 2 decimal digits Spanning 3 cfers + 2 decimalen Tensione 3 cifre + 2 cifre decimali V 92.00 … 276.00 Current 2 digits + 2 decimal digits / 3+1 / 4+0 Stroom 2 cfers + 2 decimalen / 3+1 / 4+0 Corrente 2 cifre + 2 cifre decimali / 3+1 / 4+0 A 0.01 … 6000 Power factor 1 digit + 3 decimal digits with sign + capac./induc. indic. Powerfactor 1 cfer + 3 decimalen + capaciteit./induc. indic. Fattore di potenza 1 cifra + 3 cifre decimali con segno + indic. capac. /
Frequency 2 digits + 2 decimal digits Frequentie 2 cfers + 2 decimalen Frequenza 2 cifre + 2 cifre decimali Hz 45.00 … 65.00 Active Power 2 digits + 2 decimal digits / 3+1 / 4+0 Reëel vermogen 2 cfers + 2 decimalen / 3+1 / 4+0 Potenza attiva 2 cifre + 2 cifre decimali / 3+1 / 4+0 kW 0.00 … 1987 Reactive Power 2 digits + 2 decimal digits / 3+1 / 4+0 Reactief vermogen 2 cfers + 2 decimalen / 3+1 / 4+0 Potenza reattiva 2 cifre + 2 cifre decimali / 3+1 / 4+0 kvar 0.00 … 1987 Apparent Power 2 digits + 2 decimal digits / 3+1 / 4+0 Schnbaar
Running Tariff 1 digit Actueel tarief 1 cfer Tariffa in funzione 1 cifra - T1 … T2 230V - T1 … T2 M-Bus Display refresh period Toon verversingsperiode Frequenza di aggiornamento del display s 1
Optical metrological LED Optische metrologische LED LED metrologico ottico
Front mounted red LED (meter constant) proportional to active imp/
Safety Veiligheid Sicurezza
Overvoltage category Overspanningscategorie Categoria di sovratensione - 3 Protective class Beschermingsklasse Classe di protezione classe II AC voltage test (EN 50470-3, 7.2) AC spanningstest (EN 50470-3, 7.2) Test di tensione AC (EN 50470-3, 7.2) kV 4 Degree of pollution Vervuilingsgraad Grado di inquinamento - 2 Operational voltage Nominale spanning Tensione di funzionamento V 300 Impulse voltage test (Uimp) Impulsspanningstest (Uimp) Test di tensione ad impulso (Uimp) 1.2/50 μs-kV 6 Housing material ame resistance UL 94 Behuizing materiaal vlamwerendheid UL 94 Resistenza alla amma del materiale dell'involucro UL 94 classe V0 Safety-sealing between upper and lower housing part Veiligheidsafdichting tussen bovenste en onderste behuizing Sigillo di sicurezza tra la parte superiore e quella inferiore dell'involucro
IR Connectable Communication Modules IR-koppelbare communicatiemodules Moduli di comunicazione IR collegabili
For communication modules Voor communicatiemodules Per moduli di comunicazione
Embedded M-Bus communication Geïntegreerde communicatie M-Bus Comunicazione incorporata M-Bus
Baud rate adjustable Baudrate Instelbaar Velocità Baud regolabile bps 300 … 9600 Unit load Busbelasting Carico singolo - 1 Address adjustable Adres Instelbaar Indirizzo regolabile - 0 … 250 Isolation class SELV Isolatieklasse SELV Classe di isolamento SELV
Tariff Tarief Tariffa
Tariff 1 Tarief 1 Tariffa 1 Tariff 2 Tarief 2 Tariffa 2 VAC 230 ±20% Input impedance Ingangsimpedantie Impedenza di ingresso 224
Environmental conditions Milieuomstandigheden Condizioni ambientali
Storage temperature range Opslagtemperatuur Temperatura di stoccaggio °C -25 … +70 Operating temperature range Bedrfstemperatuur Temperatura di funzionamento °C -25 … +55 Mechanical environment Mechanische omgeving Ambiente meccanico - M1 Electromagnetic environment Elektromagnetische omgeving Ambiente elettromagnetico - E2 Installation indoor only Installatie alleen binnen Installazione solo all'interno
Altitude (max.) Hoogte (max.) Altitudine (max.) m ≤2000
Humidity yearly average, without condensation Vochtigheid jaarlks gemiddelde, zonder condensatie
IP rating in built-in condition (front part) IP rating in ingebouwde conditie (voorkant) Grado di protezione IP in condizione di incasso (parte frontale) - IP51(*)
(*) For use in accordance with the MID Directive, the energy meter must be installed in a
distribution board/enclosure for modular products with a minimum protection rating IP30 The IP51 ratings apply to the meter parts exposed in front of (outside of) the cover of the enclosure.
Internal ash non volatile memory Opslag van energiewaarden en
phase / phase fase / fase fase / fase VAC 400
temporary (1 s) phase / neutral tdelk (1 s) fase /nul temporaneo (1 s) fase / neutro VAC 300 continuous phase / phase doorlopend fase / fase continuo fase / fase VAC 480
temporary (1 s) phase / phase tdelk (1 s) fase / fase temporaneo (1 s) fase / fase VAC 800
temporary (0.5 ms) tdelk (0,5 ms) temporaneo (0,5 ms) A 120
phase / phase fase / fase fase / fase VAC 160 … 480
exp Energy
on 30 days per year, without condensation op 30 dagen per jaar, zonder condensatie su 30 giorni all'anno, senza condensa - ≤95%
terminal block klemblok morsettiera - IP20
1 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005414Ad
IEC62053-23
cong.
vermogen
Aan voorzde gemonteerde rode LED (meter constant)
(*) Voor gebruik in overeenstemming met de MID-richtln moet de energiemeter
worden gemonteerd in een verdeelkast voor modulaire producten met een minimale beschermingsklasse IP30. De IP51 is van toepassing op het gedeelte van de behuizing van de energiemeter dat door de afdekplaat heen naar buiten steekt..
2 cfers + 2 decimalen / 3+1 / 4+0 Potenza Apparente 2 cifre + 2 cifre decimali / 3+1 / 4+0
Intern ash niet-vluchtig geheugen Memorizzazione dei valori di
evenredig met actieve imp / exp Energie
Dati conformi alle norme EN 50470-1, EN 50470-3, IEC 62053-21 e
IEC62053-23
DIN
energia e congurazione
visualizzazione
LED rosso frontale (costante del contatore) proporzionale all'energia imp /
Umidità media annuale, senza condensa - ≤75%
(*) Per l'utilizzo in conformità alla direttiva MID, il contatore di energia deve essere installato
in un quadro di distribuzione per apparecchi modulari con grado di protezione minimo IP30. Il grado di protezione IP51 è relativo a parti del contatore esterne al quadro (frontale dell'apparecchio).
LCD retroilluminato
indutt.
Memoria interna non volatile
exp. Attiva
-
-
kWh
classe B / 1
classe 2
- 7.2 +3.2
- -1.000 … 1.000
kVA 0.00 … 1987
p/kWh 10000
-
-
-
-
-
4 0
4
c
kWh kWh
c
c
c
c
c
Page 2
Active Energy Imported
Tariff 1 with Partial
register
Active Energy Exported
Tariff 1 with Partial
register
z
Three phase energy meter, measure via CT 1 to 6000 A
with MID declaration of conformity
1s
Meter type
By powering. Software version and checksum
and M-Bus communication
MID certication concerns active energy only.
User instructions
1s 1s
EU declaration of conformity:
http://hgr.io/r/ecm300c
6LE005414Ad
ECM300C
Safety instructions
This device must be installed only by a professional electrician tter
according to local applicable installation standards. Do not plug in or unplug this product when the power supplying is ON. Its use is only permitted within the limits shown and stated in the installation instructions. The device and the equipement connected can be destroyed by loads exceeding the values stated.
Operating principle
This 4 quadrants M-Bus meter measures the active and reactive energy used in an electrical installation. This device can manage 2 tariffs by 230 VAC digital input or 2 controlled via communication. Only the total active energy register can be used for billing purposes according to measuring instrument directive (MID).
- Active Energy Class B (according to EN 50470)
- Active Power Class 1 (according to IEC 62053-21 and IEC 61557-12)
- Reactive Energy Class 2 (according to IEC 60253-23)
- Reactive Power Class 2 (according to IEC 62053-21). This device has a LCD backlight and 3 push-button keys to read
Energies, V, I, PF, F, P, Q and to congure some parameters. The design
and manufacture of this meter comply with Standard EN 50470-3 requirements.
Product presentation
LCD display:
Symbols
Three phases
Protected by double insulation (Class II)
Backstop: Reversal preventing device
Energy for all tariffs
Tariff
Reactive power inductive/capacitive
Phase indicator
Via current transformer (CT)
Secondary transformer current
Main Energy Register, not resettable
Partial Energy Register, resettable
Units
Energy import (consumption ) Energy export (production
Communication activity status
Operating M-Bus Communication
M-Bus MEDIA:
In a standard conguration, a M-Bus connection can be used to link up
to 250* products with a PC or PLC, over a range of 1000 meters**. * depending on the M-Bus master. ** depending on the number of products and the communication speed.
Recommendations:
The use of a JYSTY Nx2x0.8 mm (0.5 mm²) unshielded twisted pair is recommended. If the range of 1000 m and/or the limit of 250 products are exceeded, a repeater will need to be connected. If the 250 limit is exceeded: only use the secondary address.
M-Bus protocol:
The M-Bus protocol operates using a master/slave structure. ECM300C (slave) units are compatible with both primary and secondary addressing
modes. Primary addressing can be congured via the product interface. Secondary addressing uses a xed, unique address shown on the
product. M-Bus ECM300C units also have the «Wildcard addressing» function which allows products to be searched for on the M-Bus network. Option to broadcast to addresses 254 and 255. In addition, M-Bus product units are OMS compatible (Open Metering Systems).
M-Bus table:
Download from: http://hgr.io/r/ecm300c
Error condition:
When partial energy blinks, reset partial energy (maximum partial energy register). When the display shows the message ERROR N02 or ERROR N03, the meter has got a malfunction and must be replaced.
)
Power factor Convention according to IEC 62053-23
kW
kW
- +
Commands
OK button: is used to conrm a modication of a
parameter (or of a digit of a numerical parameter) or to answer to a question
SCROLL button: is used to scroll Menu pages or to modify the whole value or a digit of a parameter
ESCAPE button: is used to escape to main menu from anywhere or to skip back to the previous digit of the
value under modication
Optical metrological LED
Note:
If no button is pushed for at least 20 seconds the display goes back to the Main Page and the backlight is switched off again.
2 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005414Ad
kvar
kvar
+
-
II I
Q
II I
IV
PF ≤0 PF ≥0
S
P
Main page is depending on current power direction
indication
with the corresponding global and
partial energy register display.
Active energy imported
Active energy exported
Reactive energy
imported
Reactive energy
exported
Tariff related Energies
Partial Register Reset
Measures reading
Conguration
Serial number
Software version and
checksum
Display test
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
Active Energy Imported
Tariff 2 with Partial
register
Active Energy Exported
Tariff 2 with Partial
register
Reactive Energy
Imported Tariff 1
Reactive Energy
Exported Tariff 1
Reactive Energy
Imported Tariff 2
Reactive Energy
Exported Tariff 2
OK
Primary winding of the
external CTs:
/5A: 5 ...
50 ... 6000
/1A: 1 ... 50 ... 1200
Secondary winding of
the external CTs:
/1 A - /5 A
Primary Address:
0 ... 250
Baud Rate:
300-600-1200-2400
4800-9600
Secondary Address not
modiable
Unidirectional
Bidirectional
Tariffs conguration:
1T
2T input 230 V
2T input M-Bus
In order to read values referred to Secondary side of CTs, push the ESCAPE button for a long time (10 seconds), in the Main Page. For two minutes (120 seconds), the whole set of parameters are displayed with their values referred to Secondary side of CTs, with the CT icon blinking. Also values transmitted through internal bus are referred to Secondary side for 2 minutes
Diagnostic message
The cabling sequence (L1-L2-L3) is wrong. L1, L2 and L3 icons blink. Invert the voltage wires of 2 phases (phase 1
<> phase 2 or phase 2 <> phase 3).
Otherwise, by pressing the "OK" button for at least 5 seconds, the message disappears until the next restart.
10 sec.
After 2 seconds it goes
back to the Main Page
Active Power
Reactive Power
Apparent Power
(L1-N, L2-N, L3-N)
Neutral current
Power factor
Power factor
Power factor
(L1, L2, L3)
(L1, L2, L3)
(L1, L2, L3)
Voltage
Current
(L1, L2, L3)
L1
L2
L3
Frequency
Page 3
Reële energie
geïmporteerd Tarief 1
met gedeeltelk register
Reële energie
geëxporteerd Tarief 1
met gedeeltelk register
i
Driefase energiemeter, meet via CT 1 tot 6000 A
met MID-verklaring van overeenstemming
Softwareversie en check
1s
Meter type
Via voeding.
som
en M-Bus-communicatie
MID certicering heeft alleen betrekking op werkelke energie.
Gebruikersinstructies
1s 1s
EU-conformiteitsverklaring:
http://hgr.io/r/ecm300c
6LE005414Ad
ECM300C
Veiligheidsinstructies
Dit apparaat mag alleen worden geïnstalleerd door een professionele installateur in overeenstemming met de geldende installatienormen.
Sluit dit product niet aan of koppel het niet los b ingeschakelde
spanning. Het gebruik ervan is alleen toegestaan binnen de aangegeven grenzen en vermeld in de installatie-instructies. Het apparaat en het aangesloten apparaat kunnen worden beschadigd door belastingen die
de vermelde waarden overschrden.
Werkingsprincipe
Deze 4 kwadranten M-Bus-meter meet de reële en reactieve energie die wordt gebruikt in een elektrische installatie. Dit apparaat kan 2 tarieven beheren via de binaire 230 VAC tarief ingang en 2 tarieven via de digitale communicatie interface. Alleen het totale actieve energieregister kan voor factureringsdoeleinden worden gebruikt
volgens de meetinstrumentrichtln (MID).
- Reële energieklasse B (volgens EN 50470)
- Reële vermogensklasse 1 (volgens IEC 62053-21 en IEC 61557-12)
- Reactieve energieklasse 2 (volgens IEC 60253-23)
- Reactieve vermogensklasse 2 (volgens IEC 62053-21). Dit apparaat heeft een LCD-achtergrondverlichting en 3 druktoetsen om de meetwaarden, V, I, PF, F, P, Q te lezen en om enkele parameters te
congureren. Het ontwerp en de fabricage van deze meter voldoen aan
de vereisten van norm EN 50470-3.
Productpresentatie
LCD scherm:
Symbolen
Drie fasen
Beschermd door dubbele isolatie (klasse II)
Backstop: apparaat om achteruitrden te voorkomen
Energie voor alle tarieven
Tarief
Reactief vermogen inductief/capacitief
Fase-indicator
Via stroomtransformator (CT)
Secundaire transformatorstroom
Hoofdenergieregister, niet opnieuw instelbaar
Gedeeltelk energieregister,
opnieuw instelbaar
Eenheden
Energie-import (consumptie ) Energie-export (productie
Status van communicatieactiviteit
)
Operationele M-Bus-communicatie
M-Bus MEDIA:
In een standaardconguratie kan een M-Bus-verbinding worden gebruikt
om tot 250 * producten te verbinden met een pc of PLC, over een bereik van 1000 meter **.
* afhankelk van de M-Bus-master. ** afhankelk van het aantal producten en de communicatiesnelheid.
Aanbevelingen:
Het gebruik van een niet-afgeschermd getwist aderpaar JYSTY Nx2x0,8 mm (0,5 mm²) wordt aanbevolen. Als het bereik van 1000 m en / of de limiet van 250 producten wordt overschreden, moet een repeater worden aangesloten. Als de limiet van 250 wordt overschreden: gebruik alleen het secundaire adres.
M-Bus-protocol:
Het M-Bus-protocol werkt met een master / slave-structuur. ECM300C
(slave) -eenheden zn compatibel met zowel primaire als secundaire
adresseringsmodi. Primaire adressering kan via de productinterface
worden gecongureerd. B secundaire adressering wordt een vast uniek
adres gebruikt dat op het product wordt vermeld. M-Bus ECM300C­enheden hebben ook de functie "Wildcard-adressering" waarmee producten op het M-Bus-netwerk kunnen worden opgezocht. Optie om
uit te zenden naar adressen 254 en 255. Bovendien zn de M-Bus-
producteenheden OMScompatibel (open meetsystemen).
M-Bus-tabel:
Downloaden van: http://hgr.io/r/ecm300c
Foutconditie:
In de situatie dat het woord Partial op het diplay knippert, dan heeft de “partial” teller de maximale waarde overschreden. In dit geval moet je de “partial” teller resetten. In de situatie dat de foutmeldingen ERROR N02 of ERROR N03 op het
display verschnen dan is er een defect in de meter. In deze situatie
moet de meter worden vervangen.
Powerfactor Conventie volgens IEC 62053-23
kW
kW
- +
Commando's
OK-knop: wordt gebruikt om een wziging van een
parameter (of een cfer van een numerieke parameter) te
bevestigen of om een vraag te beantwoorden
SCROLL-knop: wordt gebruikt om door menupagina's
te bladeren of om de hele waarde of een cfer van een parameter te wzigen
ESCAPE-knop: wordt gebruikt om naar het hoofdmenu
terug te gaan of om naar het vorige cfer van de gewzigde waarde terug te gaan
Optische metrologische LED
Opmerking:
Als er ten minste 20 seconden lang op geen enkele knop wordt gedrukt, keert het display terug naar de hoofdpagina en wordt de achtergrondverlichting weer uitgeschakeld.
3 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005414Ad
kvar
kvar
+
-
II I
Q
II I
IV
PF ≤0 PF ≥0
S
P
Hoofdpagina is afhankelk van de huidige
aanduiding van de stroomrichting
het bbehorende algemeen en gedeeltelke
energieregisterscherm.
met
Reële energie
geïmporteerd
Reële energie geëxporteerd
Reactieve energie
geïmporteerd
Reactieve energie
geëxporteerd
Tariefgerelateerde
energieën
Gedeeltelk register
resetten
Meetwaarden
Conguratie
Serienummer
Softwareversie en
check som
Displaytest
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
Reële energie
geïmporteerd Tarief 2
met gedeeltelk register
Reële energie
geëxporteerd Tarief 2
met gedeeltelk register
Reactieve energie
geïmporteerd Tarief 1
Reactieve energie
geëxporteerd Tarief 1
Reactieve energie
geïmporteerd Tarief 2
Reactieve energie
geëxporteerd Tarief 2
OK
Primaire wikkeling van
de externe CT's:
/5A: 5 ...
50 ... 6000
/1A: 1 ... 50 ... 1200
Secundaire wikkeling
van de externe CT's:
/1 A - /5 A
Hoofdadres:
0 ... 250
Baudrate:
300-600-1200-2400
4800-9600
Secundair adres kan niet
worden gewzigd
Unidirectionele
Bidirectionele
Tarieven conguratie:
1T
2T ingang 230 V
2T ingang M-Bus
Om de waarden waarnaar de secundaire kant van CT's verwst
te lezen, drukt u lang op de ESCAPE-knop (10 seconden) op de hoofdpagina. Gedurende twee minuten (120 seconden) wordt de hele set parameters weergegeven met hun waarden aan de secundaire kant
van CT's, terwl het CT-pictogram knippert. Ook waarden die worden
verzonden via de interne bus worden gedurende 2 minuten naar de secundaire kant verwezen
Diagnostisch bericht
De bekabelingsvolgorde (L1-L2-L3) is
verkeerd. Pictogrammen L1, L2 en L3 knipperen. Keer de spanningsdraden
van 2 fasen om (fase 1 <> fase 2 of fase 2 <> fase 3). Anders verdwnt het bericht door gedurende ten minste 5
seconden op de knop "OK" te drukken tot de volgende herstart.
10 sec.
Na 2 seconden gaat
het terug naar de
hoofdpagina
Reëel vermogen
Reactief vermogen
(L1-N, L2-N, L3-N)
Nulgeleider stroom
Powerfactor
Powerfactor
Powerfactor
(L1, L2, L3)
(L1, L2, L3)
Schnbaar
vermogen
(L1, L2, L3)
Spanning
Stroom
(L1, L2, L3)
L1
L2
L3
Frequentie
Page 4
Energia attiva importata
Tariffa 1 con registro
parziale
Energia attiva esportata
Tariffa 1 con registro
parziale
y
Contatore di energia trifase, misurare tramite CT 1 a 6000 A
con dichiarazione di conformità MID
Alimentandolo. Versione
software e checksum
1s
Tipo di contatore
e comunicazione M-Bus
La certicazione MID riguarda solo la energia attiva.
Istruzioni per l'utente
1s 1s
Dichiarazione di conformità UE:
http://hgr.io/r/ecm300c
6LE005414Ad
ECM300C
Istruzioni per la sicurezza
Questo dispositivo deve essere installato esclusivamente da un elettricista professionista secondo le norme di installazione locali
applicabili. Non collegare o scollegare il prodotto quando è alimentato. Il
suo utilizzo è consentito solo nei limiti indicati e dichiarati nelle istruzioni
di installazione. Il dispositivo e le apparecchiature collegate possono
essere danneggiati da carichi che superano i valori indicati.
Principio di funzionamento
Questo misuratore M-Bus a 4 quadranti misura l'energia attiva e reattiva
utilizzata in un'installazione elettrica. Questo dispositivo può gestire 2 tariffe tramite ingresso digitale 230 VAC o 2 tariffe controllate tramite comunicazione. Solo il registro di energia attiva totale può essere utilizzato per la fatturazione in base alla direttiva
dello strumento di misura (MID).
- Classe Energia Attiva B (secondo EN 50470)
- Classe Potenza Attiva 1 (secondo IEC 62053-21 e IEC 61557-12)
- Classe Energia Reattiva 2 (secondo IEC 60253-23)
- Classe Potenza Reattiva 2 (secondo IEC 62053-21). Questo apparecchio è dotato di display LCD retroilluminato e 3 pulsanti per leggere Energia, V, I, PF, F, P, Q e per congurare alcuni parametri. La
progettazione e la fabbricazione di questo strumento sono conformi ai
requisiti della norma EN 50470-3.
Presentazione del prodotto
Display LCD:
Symboli
Tre fasi
Protetto da doppio isolamento (Classe II)
Backstop: dispositivo anti inversione
Energia per tutte le tariffe
Tariffa
Potenza reattiva induttiva/capacitiva
Indicatore di fase
Tramite trasformatore di corrente (CT)
Corrente trasformatore secondaria
Registro principale dell'Energia, non
resettabile
Registro parziale dell'Energia,
resettabile
Unità
Energia importata (consumata ) Energia esportata (prodotta
Stato della comunicazione
Funzionamento della comunicazione M-Bus
M-Bus MEDIA:
In una congurazione standard, è possibile utilizzare una connessione M-Bus per collegare no a 250 * prodotti con un PC o PLC, entro un raggio di 1000 metri **. * a seconda del master M-Bus. ** a seconda del numero di prodotti e della velocità di comunicazione.
Raccomandazioni:
Si consiglia l'uso di un doppino non schermato JYSTY Nx2x0,8 mm
(0,5 mm²). Se viene superato il raggio di 1000 m e / o il limite di 250
prodotti, sarà necessario collegare un ripetitore.
Se il limite 250 viene superato: utilizzare solo l'indirizzo secondario.
Protocollo M-Bus:
Il protocollo M-Bus funziona utilizzando una struttura master / slave. Le unità ECM300C (slave) sono compatibili con entrambe le modalità
di indirizzamento primario e secondario. L'indirizzamento primario può
essere congurato tramite l'interfaccia del prodotto. L'indirizzamento secondario utilizza un indirizzo sso e univoco riportato sul prodotto. Le unità M-Bus ECM300C dispongono anche della funzione «Indirizzamento predenito» che consente la ricerca di prodotti sulla rete M-Bus. Opzione per trasmettere agli indirizzi 254 e 255. Inoltre, i prodotti M-Bus sono compatibili con OMS (Open Metering Systems).
Piattaforma M-Bus:
Scarica da: http://hgr.io/r/ecm300c
Condizione di errore:
Quando l'energia parziale lampeggia, ripristinare l'energia parziale (registro massimo dell'energia parziale). Quando il display mostra il messaggio ERROR N02 o ERROR N03, lo strumento ha un malfunzionamento e deve essere sostituito.
)
Fattore di potenza Convenzione secondo IEC 62053-23
kW
kW
- +
Comandi
Nota:
Se non viene premuto alcun pulsante per almeno 20 secondi, il display torna alla pagina principale e la retroilluminazione viene nuovamente disattivata.
4 Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France - www.hager.com Hager 09.19 OCOM 136679 6LE005414Ad
Pulsante OK: consente di confermare una modica di un parametro (o di una cifra di un parametro numerico) o di rispondere a una domanda
Pulsante SCROLL: consente di scorrere le pagine del
menu o di modicare l'intero valore o una cifra di un
parametro
Tasto ESCAPE: serve per uscire dal menu principale da qualsiasi posizione o per passare alla cifra precedente
del valore in modica
LED metrologico ottico
kvar
kvar
+
-
II I
Q
II I
IV
PF ≤0 PF ≥0
S
P
La
pagina principale dipende dall'indicazione
della direzione della potenza impostata
corrispondente display del registro di energia globale
e parziale.
con il
Energia attiva importata
Energia attiva esportata
Energia reattiva
importata
Energia reattiva
esportata
OK
Energia legata alle
tariffe
OK
Reset del registro
parziale
OK
Lista misure
OK
Congurazione
Numero di serie
Versione software e
checksum
Test di
visualizzazione
OK
OK
OK
OK
OK
OK
OK
Energia attiva importata
Tariffa 2 con registro
parziale
Energia attiva esportata
Tariffa 2 con registro
parziale
Energia reattiva
importata Tariffa 1
Energia reattiva
esportata Tariffa 1
Energia reattiva
importata Tariffa 2
Energia reattiva
esportata Tariffa 2
OK
Avvolgimento primario
dei TA esterni:
/5A: 5 ...
50 ... 6000
/1A: 1 ... 50 ... 1200
Avvolgimento
secondario dei TA
esterni:
/1 A -
/5 A
Indirizzo principale:
0 ... 250
Velocità Baud:
300-600-1200-2400
4800-9600
Indirizzo secondario non
modicabile
Unidirezionale
Bidirezionale
Congurazione delle
tariffe:
1T
2T ingresso 230 V
2T ingresso M-Bus
Per leggere i valori riferiti al lato secondario dei CT, premere a lungo il pulsante ESCAPE (10 secondi), nella pagina principale. Per due minuti (120 secondi), l'intera serie di parametri viene visualizzata con i relativi valori riferiti al lato secondario dei CT, con l'icona CT lampeggiante. Anche i valori trasmessi attraverso il bus interno sono riferiti al lato secondario per 2 minuti
Messaggio diagnostico
La sequenza di collegamento (L1­L2-L3) è errata. Le icone L1, L2 e L3 lampeggiano. Invertire i collegamenti
voltmetrici di 2 fasi (fase 1 <> fase 2 o fase 2 <> fase 3). Altrimenti,
premendo il pulsante "OK" per almeno
5 secondi, il messaggio scompare no
al successivo riavvio.
10 sec.
Dopo 2 secondi torna alla pagina principale
Potenza attiva
(L1, L2, L3)
Potenza reattiva
(L1, L2, L3)
Potenza Apparente
(L1, L2, L3)
Tensione
(L1-N, L2-N, L3-N)
Corrente
(L1, L2, L3)
Corrente Neutrale
Fattore di potenza
L1
Fattore di potenza
L2
Fattore di potenza
L3
Frequenza
Loading...