Haes Excel-EN, Excel-32 Series, XL32-24, XL32-16, TPCA11 Installation, Commissioning & Operating Manual

...
Page 1
Installation, Commissioning &
Operating Manual
EN54 APPROVED 2 - 12 ZONE CONVENTIONAL CONTROL
PANEL
Approved Document UI-XLEN-01 Issue 7.0
810a/04
Software Version 4.0 & Above
Page 2
IMPORTANT NOTE
PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND
OBSERVE ALL ADVICE GIVEN IN IT
THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID
E.S.D
The panel is safe to operate provided it has been installed in compliance with the manufacturer’s instructions
The panel is safe to operate provided it has been installed in compliance with the manufacturer’s instructions
and used in accordance with this manual.
and used in accordance with this manual.
Hazardous voltages are present inside the panel—DO NOT open it unless you are qualifi ed and authorised
Hazardous voltages are present inside the panel—DO NOT open it unless you are qualifi ed and authorised
to do so. There is no need to open the panel’s enclosure except to carry out commissioning, maintenance
to do so. There is no need to open the panel’s enclosure except to carry out commissioning, maintenance
and remedial work. This work must only be carried out by competent service personnel who are fully
and remedial work. This work must only be carried out by competent service personnel who are fully
conversant with the contents of the panel’s installation manual and have the necessary skills for maintaining
conversant with the contents of the panel’s installation manual and have the necessary skills for maintaining
this equipment.
this equipment.
This fi re alarm system requires periodic checks as specifi ed in BS 5839 Part 1 It is the responsibility of the
This fi re alarm system requires periodic checks as specifi ed in BS 5839 Part 1 It is the responsibility of the
system user to ensure it is regularly serviced and maintained in good working order.
system user to ensure it is regularly serviced and maintained in good working order.
Disclaimer
Disclaimer
No responsibility can be accepted by the manufacturer or distributors of this fi re alarm panel for any
No responsibility can be accepted by the manufacturer or distributors of this fi re alarm panel for any
misinterpretation of an instruction or guidance note or for the compliance of the system as a whole. The
misinterpretation of an instruction or guidance note or for the compliance of the system as a whole. The
manufacturer’s policy is one of continuous improvement and we reserve the right to make changes to
manufacturer’s policy is one of continuous improvement and we reserve the right to make changes to
product specifi cations at our discretion and without prior notice. E & O E.
product specifi cations at our discretion and without prior notice. E & O E.
!
IMPORTANT SAFETY NOTES
0832
Haes Systems Ltd, Columbia House, Packet Boat Lane, Cowley Peachey, Uxbridge, UB8 2JP
13
Model Number CPD Number
Excel-EN 2-12 zone conventional panel XLEN-2/4/6/8/12 0832-CPD-2177
European Standard EN54-2 : 1997 + A1 : 2006
Control and indicating equipment for fi re detection and fi re alarm systems for buildings.
Provided Options (with requirements):
Output to fi re alarm devices, dependency types ‘A’, ‘B’ & ‘C’, delays to outputs, test condition
European Standard EN54-4 : 1997 + A1 : 2002 + A2 : 2006
Power supply equipment for fi re detection and fi re alarm systems for buildings.
ATTENTION
Page 3
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
1
CONTENTS
Page
ABOUT THIS PANEL
2
PRODUCT OVERVIEW
2
CABINET DETAILS
3
CIRCUIT BOARDS
4
MAIN PCB TERMINALS
6
ZONE CARD TERMINALS
7
TECHNICAL SPECIFICATION
8
POWER SUPPLY MODULE
9
DESIGN CONSIDERATIONS
10
SYSTEM DESIGN & PLANNING
10
GENERAL CONVENTIONAL WIRIING SCHEMATIC
12
GENERAL TWIN WIRE WIRIING SCHEMATIC
13
INSTALLATION
14
SAFETY
14
ESD PRECAUTIONS
15
GENERAL
15
MOUNTING THE CABINET
15
MAINS CONNECTIONS
16
CONNECTING THE BATTERIES
17
SETUP & PROGRAMMING
18
NETWORK PANELS SETUP
18
TWIN WIRE MODE
20
ZONE INTERFACE FUNCTION
21
LEVEL 3 ENGINEERING MODE
22
LEVEL 3 ENGINEERING OPTIONS INDEX
23
OPERATING
54
PANEL CONTROLS & INDICATIONS
54
DISABLE MODE
56
TEST MODE
57
FAULT DIAGNOSIS
58
FUNCTIONALITY DURING A SYSTEM FAULT
59
SERVICE & MAINTENANCE
60
DUTIES OF THE RESPONSIBLE PERSON
60
ROUTINE MAINTENANCE & TESTING
60
SCHEDULE OF TESTING LOG BOOK
62
FALSE ALARMS, FAULTS & ENGINEER VISIT LOG BOOK
66
USER INSTRUCTIONS
69
Page 4
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
2
ABOUT THIS PANEL
PRODUCT OVERVIEW
Quality, reliability, ease of use and feature rich are attributes that are consistent across the entire range of
Quality, reliability, ease of use and feature rich are attributes that are consistent across the entire range of
Haes fi re alarm control panels. The Haes Excel-EN encompasses all of these attributes to provide the fi re
Haes fi re alarm control panels. The Haes Excel-EN encompasses all of these attributes to provide the fi re
alarm engineer’s panel of choice.
alarm engineer’s panel of choice.
The Excel-EN panel is available from 2 to 12 Conventional and/or Twin Wire (sav-wire) zones.
The Excel-EN panel is available from 2 to 12 Conventional and/or Twin Wire (sav-wire) zones.
For the fi re alarm engineer, the Excel-EN has been designed to minimise labour costs by providing ample
For the fi re alarm engineer, the Excel-EN has been designed to minimise labour costs by providing ample
room for tasks such as wiring and changing batteries. Activation is via key switch or access code, which
room for tasks such as wiring and changing batteries. Activation is via key switch or access code, which
means you should always be able to work on the panel and the one man walk tests will help reduce the
means you should always be able to work on the panel and the one man walk tests will help reduce the
cost of maintaining the fi re alarm system.
cost of maintaining the fi re alarm system.
Simplicity is one of the most important aspects when considering the end user of a fi re alarm panel. The
Simplicity is one of the most important aspects when considering the end user of a fi re alarm panel. The
colour coded buttons and the 3 step silence functionality gives non-technical people the confi dence to
colour coded buttons and the 3 step silence functionality gives non-technical people the confi dence to
correctly manage their fi re alarm system.
correctly manage their fi re alarm system.
All inputs and outputs are fully programmable and there are options to have delays to the outputs. The
All inputs and outputs are fully programmable and there are options to have delays to the outputs. The
programming features of the Excel-EN also include 3 different modes to help reduce false alarms. Local
programming features of the Excel-EN also include 3 different modes to help reduce false alarms. Local
re authorities are demanding this type of functionality to reduce unwanted callouts from alarm receiving
re authorities are demanding this type of functionality to reduce unwanted callouts from alarm receiving
centres
centres
As standard, all Excel-EN panels provide two monitored sounder circuits, Fire & Fault VFCO relays, Fire &
As standard, all Excel-EN panels provide two monitored sounder circuits, Fire & Fault VFCO relays, Fire &
Fault switched negative outputs, class change and an alert input.
Fault switched negative outputs, class change and an alert input.
A fully functional repeater panel is available via a plug in comms PCB.
A fully functional repeater panel is available via a plug in comms PCB.
Excel-EN panels support a large range of conventional detectors including, Apollo, Hochiki & Nittan.
Excel-EN panels support a large range of conventional detectors including, Apollo, Hochiki & Nittan.
The panels are supplied with a 3.0 amp internal power supply module. This module complies with the
The panels are supplied with a 3.0 amp internal power supply module. This module complies with the
requirements of EN54-4 : 1988 and provides temperature compensated battery management charging.
requirements of EN54-4 : 1988 and provides temperature compensated battery management charging.
Excel-EN panels are approved to European standards EN54-2 & 4, Fire Detection and Alarm Systems –
Excel-EN panels are approved to European standards EN54-2 & 4, Fire Detection and Alarm Systems –
Control & Indicating Equipment.
Control & Indicating Equipment.
Quiesecent and alarm current details for standby battery calculations
Base Models Standby Current Alarm Current
XLEN-2 75mA 116mA
XLEN-4 90mA 133mA
Add per Twin Wire circuit N/A 9mA
TPCA04-S 4 zone ext card std 43mA 47mA
TPCA04-H 4 zone ext card, high spec 49mA 87mA
TPCA05 comms card 5.2mA N/A
Page 5
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
3
ABOUT THIS PANEL
CABINET
60mm
85mm
310mm
455mm
300mm
450mm
Fire Detection System
Page 6
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
4
ABOUT THIS PANEL
CIRCUIT BOARDS
Excel-EN panels comprise of two main circuit boards plus optional ancillary boards
PSU
@++-- +-
+-
+- +- +-+- +-
28V 0V
C NC NO C NC NO
FIRE FAULT
FR
FLT
CC
PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
1 2 345
67
ON
1234
ENTER
RESOUND SILENCE RESET
TPCA01-X2/X4 - Master PCB
TPCA03 - LED Display & Controls PCB
Page 7
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
5
ABOUT THIS PANEL
ANCILLARY CIRCUIT BOARDS
+- +-+-+-
ZONE A ZONE B ZONE C ZONE D
1 2 34
ON
D C B A
TWIN
COMS A COMS B 28V+SW -ve OUTPUTS
+-
+-
12345 6
1 2 34
ON
ADDRESS
+- +-+-+-
ZONE A ZONE B ZONE C ZONE D
1 2 34
ON
D C B A
TWIN
+--- +-
OPA OPB AUX SNDR A SNDR B
C
NO
TPCA04-S - Std spec 4 zone extension card
TPCA05 - Comms PCB
TPCA04-H - High spec 4 zone extension card
4 x conventional or Twin Wire zone circuits.
Piggy backs on Main PCB for connection to network & repeater panels
6 programmable switch -ve outputs
4 x conventional or Twin Wire zone circuits.
2 x switched -ve outputs
1 x Aux relay output
2 x monitored sounder circuits
Page 8
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
6
ABOUT THIS PANEL
MAIN PCB TERMINALS
28v output fused @ 500mA
28v input for power supply
Temperature compensation voltage control link
Commmon re VFCO relay
unfused. Max 3A @ 30vdc
Commmon fault VFCO relay
maintained (fail safe)unfused.
Max 3A @ 30vdc
Programmable O/P
Programmable O/P
Alert (pulses sounders)
Precint/class change (activates sounders)
Switched -ve inputs
Switched -ve outputs
Max load 40mA
To 0 volts
Relay Coil
Conventional monitored
sounder circuits, fused @ 500mA
Conventional/Twin Wire
re zone circuits, fused @ 500mA
PSU
@++-- +-
+-
+- +- +-+- +-
28V 0V
C NC NO C NC NO
FIRE FAULT
FR
FLTCCPUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
1 2 345
67
ON
Page 9
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
7
ABOUT THIS PANEL
ZONE CARD TERMINALS
+-
+--- +-
+-+- +-
ZONE A ZONE B ZONE C ZONE D
1 2 34
ON
D C B A
TWIN
OPA OPB AUX SNDR A SNDR B
C
NO
Conventional/Twin Wire
re zone circuits, fused @ 500mA
Relay Coil
Relay Coil
Programmable O/P
Programmable O/P
Programmable relay O/P unfused.
Max 3A @ 30vdc
28v
28v
Switched -ve outputs
Max load 40mA
Conventional monitored
sounder circuits, fused @ 500mA
Drawing shows the high spec version of the zone extension PCB (TPCA04-H).
The std version does not contain the additional outputs or sounder circuits shown at the bottom.
Page 10
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
8
ABOUT THIS PANEL
TECHNICAL SPECIFICATION
Electrical Specifi cation Inputs & Outputs - TPCA01-X2/X4 Main PCB
Terminal capacity 0.5mm2 to 2.5mm2 solid or stranded wire.
PSU @ output Power supply voltage control line. For temperature compensation control.
PSU Input + - 28vdc supply input. Diode protected for
reversal and independent short circuit. Max current 3 amps.
Max input current 3 amps. Input voltage 22vdc to 32vdc.
28v+, 0v- power output 28vdc supply output for fi re alarm
accessory relays etc. Max continuous use = 400mA.
Fused @ 500mA. Fuse = 500mA resettable fuse.
Common fi re relay Fire relay contact. Clean C/O.
Max 3A @ 30vdc.
Unfused
Common fault relay Maintained fault relay contact. Clean C/O
Max 3A @ 30vdc.
Unfused
Outputs; FR, FLT Switched -ve voltage outputs for relay
control.
Overload voltage protected to 52vdc. Current limited 680R. Max load = 40mA
Inputs; CC, PUL Switched -ve inputs, connect to 0v to
trigger. Max input voltage = 28vdc. Non latching, max resistance 100R.
Protected via 10K Ohm impedance, 3v6 zener diode.
SNDR 1 - 2 28vdc polarity reversal monitored
sounder outputs to fi re alarm devices. 4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 28mA, fused @ 500mA. Typical max load 22 devices @ 18mA each per circuit. Ensure 2.4A is not exceeded.
Zone 1 - 4 Fire alarm zone circuits. Conventionally
wired detection circuit or Twin Wire combined detection / sounder circuit. 4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 50mA, fused @ 500mA. Typical max load 22 alarm devices @ 18mA each per circuit. Ensure
2.4A is not exceeded.
Electrical Specifi cation Inputs & Outputs - TPCA04-S/H zone cards
Terminal capacity 0.5mm2 to 2.5mm2 solid or stranded wire.
Zone A - D Fire alarm zone circuits. Conventionally
wired detection circuit or Twin Wire combined detection / sounder circuit. 4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 50mA, fused @ 500mA. Typical max load 22 alarm devices @ 18mA each per circuit. Ensure
2.4A is not exceeded.
Programmable outputs OP A & OP B Switched -ve voltage outputs for relay
control.
Overload voltage protected to 52vdc. Current limited 680R. Max load = 40mA
Programmable relay ouput Fire relay contact. Clean C/O, C & N/O
Max 3A @ 30vdc.
Unfused
SNDR A - B 28vdc polarity reversal monitored
sounder outputs to fi re alarm devices. 4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 28mA, fused @ 500mA. Typical max load 22 devices @ 18mA each per circuit. Ensure 2.4A is not exceeded.
Electrical Specifi cation Inputs & Outputs - TPCA05 comms PCB
Comms A - B RS485 Repeater Comms, fused @ 20mA
28v Supply output Fused @ 500mA
Programmable outputs 1 - 6 Switched -ve outputs Overload voltage protected to 52vdc
Current limited 680R Max load = 40mA
Page 11
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
9
ABOUT THIS PANEL
General Specifi cation
Enclosure Steel IP30. Epoxy powder coated Interpon Radon, silver grey
Cabling Fire resistant screened cable, minimum size 1mm
2
. Max cable length 1Km (20 Ohm). FireBurn, FP200 or equivalent (max capacitance 1uF, max inductance 1 millihenry).
Temperature range -5 deg C to +40 deg C max RH 95%
Number of conventional/Twin Wire detection circuits 2 - 12
Conventional/Twin Wire detector compatibility Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV
POWER SUPPLY MODULE
Power Supply Specifi cation
Mains supply 230vac +10% / -15% 50Hz max current
1.2A
Mains supply fuse 4 Amp (F4A 250V) Not accessible for servicing. Internal to
switch mode power unit
Internal power supply rating 3.0 Amps total including battery charging Maximum load shared between outputs
= 2.4A
Power supply output voltage 21.27 - 29.68vdc Tolerance +/- 0.1%
Maximum continuous load for battery standby (ImaxA)
ImaxA = 610mA ImaxB not specifi ed
Minimum current drawn by panel (example)
4 Zone I min = 90mA
12 Zone I min = 188mA
Maximum ripple 120 mV p-p Supply and charger fault monitored
Min/max battery size and type 2 x 7.0Ah 12volt VRLA
Use Yuasa NP range batteries
Other equivalent batteries may be used but have not been tested for the purposes of EN54 approval.
Battery charging voltage 27.3 vdc nominal at 20 deg C Temperature compensated
Battery charging output current 3.0A PSU 1.34A
Current limited 4.7 Ohms
Battery high impedance fault (Batt Hi Z) Resistance > 1 Ohm 1 hour reporting time
Max current drawn from batteries 3.15 Amps with main power source
disconnected. Battery fuse 3.15A LBC 20mm.
V+
V-
E
N
L
24v +ve output
O/P Voltage adjust
(default setting 27v4 at 20
o
C)
24v -ve output
Earth
Neutral
Live
Mains input
Temperature compensation input
from @ terminal on main PCB
Page 12
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
10
DESIGN CONSIDERATIONS
SYSTEM DESIGN & PLANNING - A few handy tips
What is a detection zone?
In order to direct those responding to a fi re alarm signal, particularly the fi re service, to the area of a fi re, all buildings, other than very small buildings, need to be divided into detection zones. Detection zones need to be small enough for a fi re to be located quickly.
• If the total fl oor area of the building is greater than 300m2, each zone should be restricted to a single storey
If the total fl oor area of the building is less than 300m2 a zone may cover more than a single storey
For voids above or below the fl oor area of a room, these may be included within the same zone of the room, provided that the void and the room constitute a single fi re compartment
• The fl oor area of a single zone should not exceed 2000m2.
Detectors
A person searching a zone for a fi re in a non- addressable fi re system should not have to travel more than 60m to identify the source of a fi re
The sensing element of a smoke detection device should not be less than 25mm and not more than 600mm below ceiling
The sensing element of a heat detector should not be less than 25mm and not more than 150mm below ceiling
When mounted on a fl at ceiling, smoke detection devices have an individual coverage of 7.5m radius. However these radii must overlap to ensure there are no ‘blind spots’. Therefore individual coverage can be represented by a square measuring 10.6m x 10.6m giving an actual coverage of 112m2 per device
When mounted on a fl at ceiling, heat detection devices have an individual coverage of 5.3m radius. However these radii must overlap to ensure there are no ‘blind spots’. Therefore individual coverage can be represented by a square measuring 7.5m x 7.5m giving an actual coverage of 56.3m2 per device.
Call Points
A person should not have to travel more than 45m along an escape route to reach a Manual Call Point (25m if disabled person to operate, or rapid fi re development is likely). Manual Call Points should be sited at all stair wells and exits from the building.
The frangible element of the manual call point should be positioned 1.4m (+/- 200mm) from the fl oor level. (Unless a wheelchair user is likely to be the fi rst person to raise the alarm).
Sounders
Sounder device cabling should be arranged so that in the event of a fault, at least one sounder will remain operational during a fi re condition.
The minimum sound level should be 65dB(A) or 5dB(A) above a background noise which is louder than 60dB(A) (if lasting more than 30 seconds) and at a frequency of between 500Hz and 1000Hz. The maximum sound level should not be greater than 120dB(A) at any normally accessible point. This may be reduced to 60dB(A) in stairways, enclosures up to 60m2 and specifi c points of limited extent.
For areas where people are sleeping, sounder devices should produce a minimum 75dB(A) at the bed-head with all doors shut. In buildings providing sleeping accomodation for a signifi cant number of people, all bedrooms should have both audible and visual alarms.
This guide is intended as an aid to designers and installers of fi re detection systems. It is NOT to be used as a substitute to BS5839 which should be read in full.
Page 13
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
11
DESIGN CONSIDERATIONS
CABLE TYPES & LIMITATIONS
CABLING
CABLE LENGTHS
MAINS PROVISION
Beacons
Visual alarms such as beacons, should always be mounted at a minimum height of 2.1m from fl oor level.
General
Fire Alarm Control Panels should be installed at a location appropriate for staff and fi re fi ghters
All mains supply isolators must be double pole and suitably marked
All joints to be fi re resisting, junction boxes to be labelled ‘FIRE ALARM’.
All cables to be fi re resisting with a minimum cross-sectional area of 1mm
2.
Cable using trunking as a means of containment must be clipped using fi re resistant supports WITHIN THE TRUNKING.
Zone charts should be fi tted in all appropriate locations (adjacent to control equipment and repeaters).
To comply with EMC (Electro Magnetic Compatibility) regulations and to reduce the risk of electrical
To comply with EMC (Electro Magnetic Compatibility) regulations and to reduce the risk of electrical
interference in the system wiring, we recommend the use of screened cables throughout the installation.
interference in the system wiring, we recommend the use of screened cables throughout the installation.
Acceptable, commonly available, screened cables, which can be used on both the sounder and detector
Acceptable, commonly available, screened cables, which can be used on both the sounder and detector
circuits include, NoBurn™ FP200™, Firetuff™, Firecel™, MICC (Pyro™) or any other cable complying with
circuits include, NoBurn™ FP200™, Firetuff™, Firecel™, MICC (Pyro™) or any other cable complying with
BS 6387 categories C, W, Z.. Refer to BS 5839 pt1 clause 26 for detailed information on cables wiring
BS 6387 categories C, W, Z.. Refer to BS 5839 pt1 clause 26 for detailed information on cables wiring
and interconnections.
and interconnections.
Suitable cables should be brought into the cabinet using the knockouts provided via a suitable cable gland
Suitable cables should be brought into the cabinet using the knockouts provided via a suitable cable gland
recommended for use with that cable. The screen or drain wire of circuits should be bonded to earth at
recommended for use with that cable. The screen or drain wire of circuits should be bonded to earth at
one location only, and should be continuous throughout the circuit. Drain wires should be terminated in the
one location only, and should be continuous throughout the circuit. Drain wires should be terminated in the
cabinet using the earthing terminal provided.
cabinet using the earthing terminal provided.
The maximum recommended cable length for a zone or sounder circuit is 1Km. This, however, is highly dependant on the number and type of devices connected.
If in doubt, cable load and resistance calculations should be undetaken to ensure devices are working within specifi ed limits.
The mains supply to the fi re alarm panel should be hard wired, using suitable three core cable (no less
The mains supply to the fi re alarm panel should be hard wired, using suitable three core cable (no less
than 1.0 mm² and no more than 2.5mm²) or a suitable three conductor system that meets the appropriate
than 1.0 mm² and no more than 2.5mm²) or a suitable three conductor system that meets the appropriate
national wiring regulations. The panel should be fed from an isolating switched fused spur, supplied directly
national wiring regulations. The panel should be fed from an isolating switched fused spur, supplied directly
from the Main Distribution Board, fused at 3A. This should be secure from unauthorised operation and be
from the Main Distribution Board, fused at 3A. This should be secure from unauthorised operation and be
marked ‘FIRE ALARM’.
marked ‘FIRE ALARM’.
The mains supply must be exclusive to the fi re panel.
The mains supply must be exclusive to the fi re panel.
As an alternative to a switched fused spur, an appropriately fused double pole isolating device may be
As an alternative to a switched fused spur, an appropriately fused double pole isolating device may be
used providing it meets the appropriate national wiring regulations.
used providing it meets the appropriate national wiring regulations.
All system wiring should be installed to meet BS5839 Pt 1 : 2002 and BS7671 (Wiring Regulations). Other national standards of installation should be used where applicable.
Page 14
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
12
DESIGN CONSIDERATIONS
GENERAL CONVENTIONAL SYSTEM SCHEMATIC
REMOTE INDICATOR
RIL58
+
_
Typical Conventional
Detection Circuit Wiring
Typical Conventional Sounder
Circuit Wiring
4K7 OHM
END OF LINE
RESISTOR
4K7 OHM
END OF LINE
RESISTOR
-
+
ZONE 1
-
+
SNDR1
-
R
L1
L1
L2
IN
OUT
-
R
L1
L1
L2
IN
OUT
-
R
L1
L1
L2
IN
OUT
APOLLO S65 BASE
45681-201
APOLLO S65 BASE
45681-201
APOLLO S65 BASE
45681-201
MANUAL CALL POINT
MCP1A-R-470
1
2
3
4
_
_
++
470
MOTORISED BELL
POLARISED
MOTORISED BELL
POLARISED
ELECTRONIC SOUNDER
POLARISED
ELECTRONIC SOUNDER
POLARISED
+VE
+VE
+VE
+VE
-VE
-VE
-VE
-VE
Page 15
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
13
DESIGN CONSIDERATIONS
GENERAL TWIN WIRE SYSTEM SCHEMATIC
-VE
E
R+
R
+
R
-
R
-
R
E
M
O
T
E
IN
D
IC
A
TO
R
R
IL
58
+
_
Typical Twin Wire
Circuit Wiring
4K7 OHM
END OF LINE
RESISTOR
Note: On a Twin Wire circuit the sounders are connected in reverse polarity to the detectors and call points
Note: Each zone circuit configuration is set to ‘Conventional’ by default. ‘Twin Wire’ mode must be set zonally using DIL switches 1-4 on the Main PCB.
Or switches A, B, C & D on the zone extension PCBs.
-
+
ZONE 1
APOLLO TWIN WIRE BASE
45681-206
APOLLO TWIN WIRE BASE
45681-206
TWIN WIRE CALL POINT
MCP1B-R-TW
TWIN WIRE CALL POINT
MCP1B-R-TW
1
2
3
4
_
_
++
470
1
2
3
4
_
_
++
470
-VE
+VE
MOTORISED BELL
POLARISED
ELECTRONIC SOUNDER
POLARISED
+VE
+VE
-VE
-VE
+VE
1 2 345
67
ON
1 2 34
ON
D C B A
TWIN
Page 16
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
14
INSTALLATION
SAFETY
Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work Act 1974
Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work Act 1974
to ensure as reasonably as is practical that the article will be safe and without risk to health when properly
to ensure as reasonably as is practical that the article will be safe and without risk to health when properly
used. An article is not regarded as properly used if it is used “without regard to any relevant information or
used. An article is not regarded as properly used if it is used “without regard to any relevant information or
advice” relating to its use made available by the supplier.
advice” relating to its use made available by the supplier.
It is assumed that the system, of which this control panel is a part, has been designed by a competent fi re
It is assumed that the system, of which this control panel is a part, has been designed by a competent fi re
alarm system designer in accordance with BS 5839 Part 1 and with regard to BS EN 54 parts 2 and 4 in
alarm system designer in accordance with BS 5839 Part 1 and with regard to BS EN 54 parts 2 and 4 in
the case of control equipment and power supplies. Design drawings should be provided to clearly show
the case of control equipment and power supplies. Design drawings should be provided to clearly show
the position of any fi eld devices and ancillary equipment.
the position of any fi eld devices and ancillary equipment.
This product should be installed, commissioned and maintained by, or under the supervision of, competent
This product should be installed, commissioned and maintained by, or under the supervision of, competent
persons according to good engineering practice and,
persons according to good engineering practice and,
(i) BS 7671 (IEE wiring regulations for electrical installations)
(i) BS 7671 (IEE wiring regulations for electrical installations)
(ii) Codes of Practice
(ii) Codes of Practice
(iii) Statutory requirements
(iii) Statutory requirements
(iv) Any instructions specifi cally advised by the manufacturer
(iv) Any instructions specifi cally advised by the manufacturer
According to the provisions of the Act you are therefore requested to take such steps as are necessary to
According to the provisions of the Act you are therefore requested to take such steps as are necessary to
ensure that any appropriate information about this product is made available by you to anyone concerned
ensure that any appropriate information about this product is made available by you to anyone concerned
with its use.
with its use.
This equipment is designed to be operated from 230V AC 50/60 Hz mains supplies and is of Class I
This equipment is designed to be operated from 230V AC 50/60 Hz mains supplies and is of Class I
construction. As such it must be connected to a protective earthing conductor in the fi xed wiring of the
construction. As such it must be connected to a protective earthing conductor in the fi xed wiring of the
installation. Failure to ensure that all conductive accessible parts of this equipment are adequately bonded
installation. Failure to ensure that all conductive accessible parts of this equipment are adequately bonded
to the protective earth will render the equipment unsafe.
to the protective earth will render the equipment unsafe.
This equipment must only be installed and maintained by a suitably skilled and technically competent person.
THIS IS A PIECE OF CLASS 1 EQUIPMENT AND MUST BE EARTHED
!
These panels are designed to comply with the requirements of EN 54 part 2.
These panels are designed to comply with the requirements of EN 54 part 2.
Installation of the panel should only be carried out by qualifi ed personnel. The electronic components
Installation of the panel should only be carried out by qualifi ed personnel. The electronic components
within the panel can be damaged by static charge. Suitable precautions must be taken when handling
within the panel can be damaged by static charge. Suitable precautions must be taken when handling
circuit boards. Never insert or remove boards or components, or connect cables, with the mains power
circuit boards. Never insert or remove boards or components, or connect cables, with the mains power
on or batteries connected.
on or batteries connected.
Equipment Guarantee
This equipment is not guaranteed unless the complete system is installed and commissioned in accordance with the laid down national standards by an approved and competent person or organisation.
This product has been manufactured in conformance with the requirements of all applicable EU Council Directives
Page 17
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
15
INSTALLATION
ESD PRECAUTION
GENERAL
MOUNTING THE CABINET
Electronic components are vulnerable to damage by Electrostatic Discharges (ESD). An ESD wrist strap,
Electronic components are vulnerable to damage by Electrostatic Discharges (ESD). An ESD wrist strap,
suitably grounded, should be worn at all times when handling pcbs. These wrist straps are designed to
suitably grounded, should be worn at all times when handling pcbs. These wrist straps are designed to
prevent the build up of static charges, not only within a persons body, but on many other materials.
prevent the build up of static charges, not only within a persons body, but on many other materials.
ESD damage is not always evident immediately, faults can manifest themselves at anytime in the future.
ESD damage is not always evident immediately, faults can manifest themselves at anytime in the future.
All pcbs should be stored in static shielded bags (silvered) for safe keeping, when not mounted in the
All pcbs should be stored in static shielded bags (silvered) for safe keeping, when not mounted in the
control panel.
control panel.
Care should be taken with regards to avoiding the close proximity of high voltage cables or areas likely
Care should be taken with regards to avoiding the close proximity of high voltage cables or areas likely
to induce electrical interference. Earth links should be maintained on all system cables and grounded in
to induce electrical interference. Earth links should be maintained on all system cables and grounded in
the control panel.
the control panel. The detection and sounder circuit cabling is classed as extra low voltage and must be segregated away from mains voltage.
Any junction boxes used should be clearly labelled FIRE ALARM.
Any ancillary devices, e.g. door retaining magnets, must be powered from a separate power source.
Any coils or solenoids used in the system must be suppressed, to avoid damage to the control equipment.
The site chosen for the location of the panel should be clean, dry and not subject to shock or vibration.
The site chosen for the location of the panel should be clean, dry and not subject to shock or vibration.
Damp, salt air or environments where water ingress or extremes of temperature may affect the panel must
Damp, salt air or environments where water ingress or extremes of temperature may affect the panel must
be avoided. The temperature should be in the range -5° to +40°C, and the relative humidity should not
be avoided. The temperature should be in the range -5° to +40°C, and the relative humidity should not
exceed 95%.
exceed 95%.
Before mounting the cabinet remove the main PCB.
Remove the power supply module connecting wires from the main PCB, taking care to note where to re­connect them. The main PCB can then be carefully pulled off it’s mounting clips.
Secure the cabinet to the wall using the four indented holes in the back box. Ensure the box is mounted level and in a convenient location where it may be easily operated and serviced.
External cables should be glanded via preformed knockouts at the top and rear of the cabinet. Remove any knockouts and ensure the cabinet is clear of swarf etc prior to refi tting the PCB. Always ensure that if a knockout is removed, the hole is fi lled with a good quality cable gland. Any unused knockouts must be securely blanked off.
Knockouts should be removed with a sharp tap at the rim of the knockout using a fl at 6mm broad bladed screwdriver.
Use of excessive force will damage the enclosure around the knockout.
Page 18
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
16
INSTALLATION
Typical panel layout
Drawing shows typical internal layout of a 12 zone panel with two 7.0Ah, 12v batteries fi tted
MAINS CONNECTIONS
Do not connect the mains supply to the panel until you are fully conversant with the layout and features of the equipment.
A rating plate is attached to the power supply module describing the nature of the supply permitted.
The incoming mains supply should be brought into the panel via one of the knockouts provided.
A suitable cable gland must be used to secure the outer sheath of the cable used. The earth must fi rst be connected to the primary earth stud (peg) marked with a symbol, using the ring crimp provided.
Suffi cient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the terminal block while leaving the earth connection intact.
V+
V-
E
N
L
PSU
@++-- +-+-+- +-+-+- +-
28V 0V
C NC NO C NC NO
FIRE FAULT
FR
FLTCCPUL
-OP-OP -IP-IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
1 2 3
ON
Low voltage detection and sounder circuit wiringIncoming mains wiring
12V 7.0Ah VRLA BATTERY
12V 7.0Ah VRLA BATTERY
+-+- +-+-
ZONE A ZONE B ZONE C ZONE D
1 2 34
ON
D C B A
TWIN
+-+- +-+-
ZONE A ZONE B ZONE C ZONE D
1 2 34
ON
D C B A
TWIN
+--- +-
OPAOPB AUX SNDR A SNDR B
C
NO
Page 19
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
17
INSTALLATION
CONNECTING THE BATTERIES
BATTERY CHARGING VOLTAGE CHECKS
Batteries of even very small capacity are capable of delivering very high currents which can cause fi re or injury, therefore battery connections should be done with caution.
The panel is supplied with battery leads already connected to the battery terminals on the main PCB. These leads are coloured red for +ve and black for -ve.
2 x 12v batteries should be connected in series using the white jumper lead provided. See diagram.
To optimise the service life of the batteries, the battery charger output voltage varies with temperature.
N.B. In the event of mains failure, the battery charger circuit will protect the batteries from full discharge by disconnecting them when they reach below 19v. When the mains supply is restored the batteries will be automatically reconnected.
+ve-ve
12v SLA Battery 12v SLA Battery
+-
BATTERY
1 2 3
ON
NOTE:
If the mains is connected before the batteries, the panel will show a Power Supply fault for up to 1 minute until the monitoring cylce has fi nished polling. This is normal. If the fault doesn’t clear after 1 minute, check connections.
The battery charging voltage is factory calibrated to 27.3vdc +/- 0.2v @ 20oC. This should not normally require adjustment. Where battery problems are experienced, the following information should be considered.
a) If a battery is disconnected from the charger, no voltage will appear on the output leads or terminals,
due to intelligent battery controls.
b) Check the power supply voltage at the 28v & 0v supply output terminals. With the batteries
disconnected the voltage should be 27.6vdc +/- 0.2v @ between 11oC - 40oC.
c) To test the batteries, turn off the mains and see if the system will run on the batteries. Check the
battery voltage, should be 26.8v for a good battery or 22v for a fl at battery.
d) The power supply voltage can be adjusted using the potentiometer on the power supply module (see
page 9), checking at the 28v & 0v output terminals with a calibrated volt meter. Batteries should be disconnected and the Access Level 3 DIL switch should be set to ‘ON’ (see page 20), which will over ride the temperature compensation controls. Carefully adjust the voltage to 27.6vdc +/- 0.2v. When completed, switch off Access Level 3 DIL switch and re-connect the batteries.
e) When the panel is re-charging a low battery, it should be possible to see the voltage across the
batteries increase gradually. If this is not occurring, the batteries or the panel may be faulty.
Page 20
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
18
SETUP & PROGRAMMING
NETWORK PANELS SETUP
The system can support up to 8 networked control panels, 1 x Master and up to 7 x Slaves.
Comms PCB
To run a network, a Comms PCB (TPCA05) must be fi tted to each control panel. Any Excel-EN or Excel-32 panel from 2 to 32 zones with software version 4.0 and above may be used.
The Comms PCB fi ts into the control panel on top of the main circuit board where the ribbon cable from the display board comms is normally plugged.
To fi t the Comms PCB, power down the panel, un-plug the display board ribbon cable from the main circuit board and plug the Comms PCB into the socket instead.
A socket is provided on the top of the Comms PCB to re-connect the display board ribbon cable.
Each panel to be included in the network is defi ned by setting a switch on the main PCB. In the case of the Excel-EN this is switch 7 on the 7 way DIL switch. OFF = Stand Alone mode, ON = Network/Repeater mode.
With this switch in the ON position the panel will automatically recognise & operate the Comms PCB (TPCA05).
PSU
@++-- +-+-+- +- +-+- +-
28V 0V
C NC NO C NC NO
FIRE FAULT
FR
FLTCCPUL
-OP -OP-IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
PSU
@++-- +-+-+- +- +-+- +-
28V 0V
C NC NO C NC NO
FIRE FAULT
FR
FLTCCPUL
-OP -OP-IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
COMS A COMS B 28V+SW -ve OUTPUTS
+-
+-
12345 6
1 2 34
ON
ADDRESS
Disconnect display board ribbon cable
7 way DIL switch
Plug Comms PCB into the socket and re-connect dispay board ribbon cable to socket on top of Comms PCB
1 2 345
67
ON
1 2 345
67
ON
ON = Network/ Repeater mode
1 2 345
67
ON
Page 21
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
19
SETUP & PROGRAMMING
Programming
The Master panel will need to be programmed for the number of network panels on the system. See panel wide programming settings, code 2-1-2-3, option 10, (Set Number of Network Slave Panels on System).
Addressing
Each panel needs to have a unique address. The addressing is done using the 4 DIL switches on each of the Comms PCBs using binary code values, see diagram below.
The addresses should be set in sequence from 1 - 8, fi rst slave panel = address 01, second slave panel = address 02 etc.
The Master panel is defi ned by being address 00 (all switches off).
Network slave panels and/or repeater panels are designed to be wired in a fault tolerant (fail safe) loop confi guration, from comms A to B and back to the Master panel again (see drawing below). This enables the network to still function if there is a break in the cables.
If replacing an older system where the existing cabling cannot be confi gured in a loop as above, it is possible to change the panel settings to legacy, radial circuit comms monitoring.
See panel wide programming settings, code 2-1-2-3, option 6, (Change Network/Repeater Comms Monitoring Type).
1 2 34
ON
ADD 01
1 2 34
ON
ADD 02
1 2 34
ON
ADD 03
1 2 34
ON
ADD 04
1 2 34
ON
ADD 05
1 2 34
ON
ADD 06
1 2 34
ON
ADD 07
SLAVE PANEL 1
SLAVE PANEL 5 SLAVE PANEL 6 SLAVE PANEL 7
1 2 34
ON
ADD 00
MASTER PANEL
SLAVE PANEL 2 SLAVE PANEL 3 SLAVE PANEL 4
COMS A COMS B 28V+SW -ve OUTPUTS
+-
+-
123456
1 2 34
ON
ADDRESS
COMS A COMS B 28V+SW -ve OUTPUTS
+-
+-
123456
1 2 34
ON
ADDRESS
COMS A COMS B 28V+SW -ve OUTPUTS
+-
+-
123456
1 2 34
ON
ADDRESS
Fault Tolerant Loop Wiring
Master Panel Slave/Repeater Panel 1 Slave/Repeater Panel 2
Page 22
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
20
SETUP & PROGRAMMING
TWIN WIRE MODE
What is Twin Wire?
Twin Wire is what is often referred to as sav wire. The technology enables sounders and beacons to be connected to the same circuit as the detectors and call points. This can result in greatly reduced installation time and cost.
How does it work?
In Twin Wire confi guration the fi re zone circuits reverse polarity in alarm condition to power the sounders and beacons. For this reason the sounders and beacons need to be wired in opposite polarity to the detectors and call points, i.e. zone positive wire connects to detector base and call point positive terminals but sounder and beacon negative terminals.
+- +- +-+- +-
1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
1 2 345
67
ON
1 2 345
67
ON
1 2 345
67
ON
To set Twin Wire mode for zones 1-4 on the main circuit board, move switches 1-4 on the 7 way DIL switch located on the main PCB to the ‘ON’ position.
Each zone can be independantly set to Twin Wire, switch 1 relating to zone 1 etc.
To set Twin Wire mode for zones A-D on the zone extension circuit boards, move switches A-D on the 4 way DIL switch located on the zone card to the ‘ON’ position.
Each zone can be independantly set to Twin Wire, switch A relating to zone A etc.
Zone +ve
Zone -ve
+++ +
--- -
4K7 EOL Resistor
Twin Wire systems require special ‘sav-wire’ detector bases and polarised call points but standard sounders. Most modern, non addressable, low current, polarised sounders, bells and beacons are compatible, Cooper Fulleon, Besson, Klaxon etc.
+- +-+- +-
ZONE A ZONE B ZONE C ZONE D
1 2 34
ON
D C B A
TWIN
1 2 34
ON
D C B A
TWIN
Page 23
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
21
SETUP & PROGRAMMING
This setting confi gures the last zone on the panel, (i.e. zone 2 on a 2 zone, zone 4 on a 4 zone, zone 6 on a 6 zone, zone 8 on an 8 zone and zone 12 on a 12 zone), to be used for interconnection from other control panels.
It is possible, in the Level 3 engineering programming, to setup any zone for this function, however, this is simply a shortcut method.
The function is enabled by setting switch 5 on the 7 way DIL switch located on the main PCB to the ‘ON’ position.
With switch 5 in the ‘ON’ position, the last zone becomes;
1.
1.
Non latching &
Non latching &
2.
2.
Non aux operating.
Non aux operating.
Note:
If the interface zone is also set to Twin Wire mode and sounders are connected to the zone circuit, the following sounder operation will apply:
A fi re (470Ω) signal to the interface zone will NOT operate the sounders connected to that Twin Wire circuit. All other conventional (SNDR1 & SNDR2) and Twin Wire zone sounders will operate as normal.
A fi re (470Ω) signal to any other zone will operate ALL conventional (SNDR1 & SNDR2) and Twin Wire sounder circuits, including the sounders connected to the interface zone, as normal.
ZONE INTERFACE FUNCTION
1 2 345
67
ON
+-+- +-
ZONE2 ZONE3 ZONE4
CNCNONOCNC
FIRE
FAULT
(optional)
PANEL 1 PANEL 2
470Ω
3K3Ω
Example connection
Page 24
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
22
SETUP & PROGRAMMING
LEVEL 3 ENGINEERING OPTIONS
+- +- +-+- +-
1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
1 2 345
67
ON
1 2 345
67
ON
A series of programmable engineering options are available. These programming modes are initiated by entering a four digit code using buttons 1 - 4 on the keypad followed by the ENTER button.
1 2 345
67
ON
P
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
To access Level 3 options, fi rst set switch 6 on the 7 way DIL switch located on the main PCB to the ‘ON’ position. Then activate the controls by turning the key switch or by entering the four digit code (see Activate Controls in the OPERATING section).
Once the controls are active, the ‘Access Level’ indicator will pulse to signify that Level 3 access is active.
Programming throughout the panel is carried out in a sequence where the fi re LEDs indicate the options to set and the fault LEDs indicate the status of these settings.
Generally button 1 is used to scroll the indications (button 3 can also be used to scroll backwards). Pressing and holding button 1 for 3 seconds at any time will exit the programming mode completely.
N.B. The panel will automatically save settings & drop out of programming modes if left idle for more than approximately 30 seconds.
It is possible to review the settings within a programming mode without changing them. Steady Fire LEDs indicate review mode. To edit a setting fi rst use button 1 to select the required option, pressing ENTER enables editing of the option. Flashing fi re LEDs indicates edit mode and button 2 is used to change the setting.
Pressing ENTER again will exit ‘edit’ mode back to ‘review’ mode.
Some programming modes are denoted with (EN54!). Where this symbol appears EN54 compliance may be affected by this setting.
Page 25
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
23
SETUP & PROGRAMMING
PROGRAMMING OPTIONS INDEX
Option/Setting Description Code(s) Page
View History View the last 40 events 1111 24
Set Fault Buzzer Volume Set the fault buzzer volume to high or low
2224 25
Clear All Disablements Remove all disablements which have been set for any zone,
sounder circuit, output or delay
1121 25
Initialise Factory Settings Restores all programming, test modes and disablements back to
factory default settings
1113 25
Panel Wide Settings • Change/remove keypad access code
• Set number of repeater panels on system
• Set time for panel delay timer
• Disable battery monitoring
• Setup internal PCB confi g (add/remove zone cards)
• Change network/repeater comms monitoring type
• Set number of output cards
• Inhibit muted tone beeps
• Inhibit network alarms & faults for panel
• Set number of network slave panels on system (Master Panel only)
• Inhibit network slave panel fi re & fault buzzer
2123 26
Zone Function Settings • Set zone to latching or non latching
• Set zone to old B.S (short circuit = fi re)
• Set zone for use with MTL5061 I.S. barrier
• Set zone to silent mode (provides visual & audible indication at the panel but no sounder operation)
• Turn off priority alarm feature for zone
• Turn off detector removal monitoring for zone
• Set detector removal monitoring type for zone (Schottky or Zener diode detector bases)
• Sprinkler/pump monitoring function
3121 32
Dependancy Modes (False Alarm Management)
Set panel & zones to dependancy mode A, B or C
2124, 2114, 2134 36
EN54 Sounder Resound Options Set zones to not resound alarms after an initial fi re condition 1114 39
Delays to Outputs Apply delays to outputs in response to selected zones 2323 40
Input Functions Change the default functions of the Class Change and Alert inputs 4141 41
Output Programmability & Miscellaneous
Set panel outputs to be programmable, switch on fault latching, invert fault output
4142 42
Panel Output Zonal Responses Set how each output and sounder circuit responds for each zone
(off, continuous or pulsing)
4242, 4342, 3122, 4243
43
Zone of Origin Setting Quick set codes for zone of origin or zonal sounder ringing for
Twin Wire sounder circuits
3311, 3312 45
Panel Output Functional Options Change the default panel output & sounder circuit responses to
‘Silence Alarms’, ‘Evacuate’, ‘Class Change’, ‘Alert’ and ‘Delay’
4244, 3123, 4344 46
Network Output Responses Set local output & relay responses to network fi res 4224 48
Network Sounder Responses Set local sounder cct responses to network fi res 4324, 3224 49
Comms PCB Output Functional Options
Change the default comms PCB o/p responses to ‘Silence Alarms’, ‘Evacuate’, ‘Class Change’, ‘Alert’ and ‘Delay’
4343 50
System Diagnostics Mode Tests system PCB confi g setup for fault diagnosis 3114 51
Repeater Programming Repeater panel setup & programming 4443 52
Page 26
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
24
SETUP & PROGRAMMING
1 1 1 1
View History
The control panel stores a log of the last 40 events which have occurred. This is useful for identifying intermittent faults or activations.
Enter the above code and press ENTER, the most recent event that has occurred is displayed. Use the ENTER button to progress backwards through the indications.
When the end of the log is reached the panel will drop out of view mode.
During viewing it is possible to delete the entire history by pressing and holding button 2. The panel will chirp to acknowledge deletion.
The panel will log and display the following events: zone fi re activations, zone faults, power supply faults, sounder circuit faults and repeater faults.
The last two (sounder circuit faults and repeater faults) have additional information available which can be accessed by pressing and holding the ENTER button continuously.
Sounder circuit faults
If a sounder circuit fault is displayed, pressing and holding the ENTER button will reveal which sounder circuit was at fault. This is indicated by the fi re LEDs 1 - 6 as per the table below.
Repeater faults
If a repeater fault is displayed, pressing and holding the ENTER button will reveal the following further information.
The Repeater Fault LED indicates:
Slow Flash = faulty repeater, Normal Flash = repeater off line, Fast Flash = network cable error.
Red, fi re LEDs 1 - 8 indicate which repeater was off line Amber, fault LEDs 1 - 8 indicate which repeater had a PSU fault
Zone 1 fi re LED Zone 2 fi re LED Zone 3 fi re LED Zone 4 fi re LED Zone 5 fi re LED Zone 6 fi re LED
Main PCB SNDR 1
Main PCB SNDR 2
Zone extension card 1 (zones 5
- 8) SNDR A
Zone extension card 1 (zones 5
- 8) SNDR B
Zone extension card 2 (zones 9
- 12) SNDR A
Zone extension card 2 (zones 9
- 12) SNDR B
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
When fi nished, enter the next programming code or disable the controls and return DIL switch 6 to ‘OFF’.
Page 27
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
25
SETUP & PROGRAMMING
1111123
1
Initialise Factory Default Settings
Clear All Disablements
Enter the above code and press the ENTER button.
Then press the ENTER button again and hold for 3 seconds.
All disablements, test modes and programming will revert back to the factory default settings.
The panel will bleep to acknowledge the reset.
When fi nished, enter the next programming code or disable the controls and return DIL switch 6 to ‘OFF’.
Enter the above code and press the ENTER button.
Then press the ENTER button again and hold for 3 seconds.
Any disabled zone, sounder circuit, output or delay will now be enabled.
The panel will bleep to acknowledge the reset.
When fi nished, enter the next programming code or disable the controls and return DIL switch 6 to ‘OFF’.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
2 2 2 4
Set Fault Buzzer Volume
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
There are two levels of volume for the internal fault buzzer, high and low.
Enter the above code and press the ENTER button to increase or decrease the fault buzzer tone from the previous level.
Setting will change when ENTER button is pressed.
When fi nished, enter the next programming code or disable the controls and return DIL switch 6 to ‘OFF’.
Page 28
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
26
SETUP & PROGRAMMING
2 1 2 3
Panel Wide Settings
OPTION 1. Change / Remove Keypad Access Code
There are 11 general, panel wide, settings available.
Enter the above code and press the ENTER button. The 11 programmable options are represented by fi re zone LEDs 1 - 11.
Use button 1 to move to option required as per table;
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Fire LED Programming Option
1 Change / remove keypad access code
2 Set number of repeater panels on system
3 Set time for panel delay timer (1 - 10 minutes)
4 Disable battery monitoring
5 Setup internal PCB confi guration (adding or removing
extension zone cards)
6 Change network/repeater comms monitoring type
7 Set number of output cards
8 Inhibit muted tone beeps
9 Inhibit network alarms & faults for panel
10 Set number of network slave panels on system
11 Inhibit fi re & fault buzzer on network slave panel
The keypad can be used to activate the panel controls instead of using the key switch. The default code is 1-2-3-4, however, this can be changed. It is also possible to disable the use of a code entry to enable controls, forcing the use of the key switch only.
With the zone 1 fi re LED lit, press the ENTER button. Zone 1 fi re LED will pulse to indicate ‘edit mode’ and the amber, fault LEDs will start to rapidly pulse in sequence to show the currently set code.
Enter the new code slowly and deliberately, one number at a time using buttons 1 - 4
Note: Enable Controls codes must always start with a 1 or 2.
When fi nished entering the new four digit code, press the ENTER button. The panel will then confi rm the new code with rapidly pulsing LEDs in sequence and zone 1 fi re LED will return to steady ‘view mode’.
Changing the keypad code to 1 - 1 - 1 - 1 will disable the use of a keypad to enable controls.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3. (The panel will confi rm the new access code one more time before exiting the programming mode).
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Page 29
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
27
SETUP & PROGRAMMING
OPTION 2. Set Number of Repeater Panels on System
OPTION 3. Set Time For Panel Delay Timer
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
If repeater panels are to be used, the quantity on the system, 1- 8, must be set up for monitoring purposes. An incorrect quantity will cause a repeater fault to be shown on the panel.
With the zone 2 fi re LED lit, the amber, fault LEDs will show the current quantity of repeaters set 0 - 8. (1 LED lit = 1 repeater, 2 = 2 etc..).
Press the ENTER button, zone 2 fi re LED will pulse to indicate ‘edit mode’.
Now use buttons 1 & 3 to increase or decrease the quantity. Button 1 increases, button 3 decreases.
When fi nished press the ENTER button again and the zone 2 fi re LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
The panel delay time for all outputs is set here. To actually apply the delay to the desired outputs, see programming code 2-3-2-3. The default setting is 3 minutes but can be changed to between 1 - 10 minutes.
With the zone 3 fi re LED lit, the amber, fault LEDs will show the current time set. The time is represented by a binary code using LEDs 1 - 4.
LED 1 = 1min, LED 2 = 2min, LED 3 = 4min, LED 4 = 8min. Therefore if LEDs 1 & 2 are lit the time is 3 minutes (1 + 2). If LEDs 2 & 4 are lit the time = 10 minutes (2 + 8).
Press the ENTER button, zone 3 fi re LED will pulse to indicate ‘edit mode’.
Now use buttons 1 & 3 to increase or decrease the time, each press will increase or decrease the time by 1 minute. Button 1 increases, button 3 decreases.
When fi nished press the ENTER button again and the zone 3 fi re LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Page 30
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
28
SETUP & PROGRAMMING
OPTION 4. Disable Battery Monitoring (EN54!) & Disable Battery Hi Z Monitoring (EN54!)
OPTION 5. Setup Internal PCB Confi guration
The battery monitoring may be disabled for applications where this is appropriate such as non fi re alarm use or where no battery backup is required. Note: There is no remote PSU fault input available on the
Excel-EN.
With the zone 4 fi re LED lit, the amber, fault LEDs will show the current setting.
LED 1 OFF = monitored batteries (default). LED 1 ON = batteries un-monitored.
LED 2 OFF = no Hi Z monitoring LED 2 ON = battery Hi Z monitored (default)
Press the ENTER button, zone 1 fi re LED will pulse to indicate ‘edit mode’ for std battery monitoring.
Use button 1 to toggle between pulsing fi re LEDs 1 & 2 for editing std or Hi Z battery monitoring as per above.
Now use button 2 to change the setting indicated by the amber fault LED as per above.
When fi nished press the ENTER button again and the zone 4 fi re LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
The control panel monitors all internal PCBs for correct function. If adding or removing any of the additional extension zone cards, the panel must be programmed for the new confi guration.
With the zone 5 fi re LED lit, the amber, fault LEDs will show the current confi guration setting. Each of the 2 possible additional zone cards are represented by LEDs 1 - 2 as per table below.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Press the ENTER button, zone 1 fi re LED will pulse to indicate editing of 1st additional PCB as per table above. Use button 1 to move to the fi re LED for the relevant PCB as per table.
Now use button 2 to change the setting indicated by the amber fault LED (LED ON = PCB included, OFF = not included).
When fi nished press the ENTER button again and the zone 5 fi re LED will return to steady ‘view mode’, with the amber, fault LEDs showing the new confi guration.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
LED 1 (ON) LED 2 (ON)
Extension zone card 1 (zones 5 - 8)
Extension zone card 2 (zones 9 - 12)
Page 31
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
29
SETUP & PROGRAMMING
OPTION 6. Change Network/Repeater Comms Monitoring Type (EN54!)
The network & repeater panels are designed to be wired in a fault tolerant (fail safe) loop confi guration, from comms A to B and back to the main panel again (see drawing below). This enables network & repeater panels to still work if there is a break in the cables.
If replacing an older system where the existing cabling cannot be confi gured in a loop as above, it is possible to change the panel back to radial circuit comms monitoring.
With the zone 6 fi re LED lit, the amber, fault LED will show the current setting.
LED 1 OFF = fault tolerant monitoring (default). LED 1 ON = legacy, radial circuit monitoring.
Press the ENTER button, zone 6 fi re LED will pulse to indicate ‘edit mode’.
Now use button 2 to change the setting indicated by the amber fault LED ON or OFF as per above.
When fi nished press the ENTER button again and the zone 6 fi re LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
COMS A COMS B 28V+SW -ve OUTPUTS
+-
+-
123456
1 2 34
ON
ADDRESS
COMS A COMS B 28V+SW -ve OUTPUTS
+-
+-
123456
1 2 34
ON
ADDRESS
COMS A COMS B 28V+SW -ve OUTPUTS
+-
+-
123456
1 2 34
ON
ADDRESS
Fault Tolerant Loop Wiring
Main Panel Repeater/Network Panel 1 Repeater/Network Panel 2
Page 32
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
30
SETUP & PROGRAMMING
OPTION 7. Set Number of Output Cards
OPTION 8. Inhibit Muted Tone Beeps
Up to 2 output/relay cards may be added to each control panel to provide additional common or zonal outputs. The presence of the cards must be setup to enable operation.
With the zone 7 fi re LED lit, the amber, fault LEDs (zones 1 - 2) will show the current settings.
Zone 1 amber fault LED ON = Output Card 1, Zone 2 = Output Card 2.
Press the ENTER button, zone 1 fi re LED will pulse to indicate adding or removing card 1.
Use buttons 1 & 3 (1=forward, 3=backward) to move the pulsing fi re LED to the required zone (Cards 1 - 2 indicated by zones 1 & 2 respectively).
Then use button 2 to add or remove the card, indicated by the amber fault LED ON (added) or OFF (removed).
Option to inhibit the intermittant beep that still occurs when a fault or fi re tone has been muted using the Mute Buzzer button.
With the zone 8 fi re LED lit, Press the ENTER button. The zone 1 fi re LED will pulse ‘edit mode’.
Press button 1 to light the zone 1 fault LED. Beeps are now silenced.
When fi nished press the ENTER button again and the zone 7 fi re LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
When fi nished press the ENTER button again and the zone 8 fi re LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
OPTION 9. Inhibit Network Alarms & Faults For Panel
This option prevents any other network panel’s alarms or faults from displaying or having any effect on the panel.
The default setting is ON (panel displays all network alarms & faults and the outputs respond accordingly).
If set to OFF, alarms & faults from other network panels will be ignored. Fires & faults from this panel will still affect other network panels accordingly.
With the zone 9 fi re LED lit, Press the ENTER button. The zone 9 fi re LED will pulse ‘edit mode’.
The zone 9 fault LED will be lit (indicates network alarms & faults active).
Press button 1 to change the fault LED to OFF (network alarms & faults inhibited).
When fi nished press the ENTER button again and the zone 9 fi re LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
Page 33
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
31
SETUP & PROGRAMMING
OPTION 10. Set Number of Network Slave Panels on System (Master Panel Only)
If using network slave control panels, the Master panel will need to be programmed with which slave panel addresses are included in the system, for monitoring purposes. An incorrect quantity will cause a system fault to be displayed on the panels.
With the zone 10 fi re LED lit the amber fault LEDs will display the current slave panel addresses set (0 - 7), amber fault LED 1 = slave address 01 etc.
Press the ENTER button. The zone 1 fi re LED will pulse to indicate adding or removing slave adress 01.
Use buttons 1 & 3 (1=forward, 3=backward) to move the pulsing fi re LED to the required zone (addresses 1 - 7 indicated by zones 1 - 7 respectively).
Then use button 2 to add or remove the slave address, indicated by the amber fault LED ON (added) or OFF (removed).
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Tip - You can use button 4 as a shortcut to add or remove all 7 addresses in one go.
When fi nished press the ENTER button again and the zone 10 fi re LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
OPTION 11. Inhibit Fire & Fault Buzzer on Network Slave Panel
When fi nished all panel wide programming, enter the next programming code or disable the controls and return DIL switch 2 to ‘OFF’.
It is possible to inhibit the fi re and/or fault buzzers of the network slave panels. This is useful if the panels are to be mounted together for a larger system. This option must be set on each individual slave panel.
With the zone 11 fi re LED lit press the ENTER button. The zone 1 fi re LED will pulse to indicate editing the panels fault buzzer.
Editing of the fault buzzer is indicated by the zone 1 LEDs and editing the panels fi re buzzer is indicated by the zone 2 LEDs.
Use buttons 1 & 3 (1=forward, 3=backward) to move the pulsing fi re LED to the required zone as per above.
Then use button 2 to Disable or Activate the buzzer indicated by the amber fault LED.
Fault LED OFF = Buzzer Active ~ Fault LED ON = Buzzer Disabled
When fi nished press the ENTER button again and the zone 11 fi re LED will return to steady ‘view mode’.
Press button 1 to move to next option or hold button 1 for 3 seconds to exit programming mode 2-1-2-3.
Page 34
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
32
SETUP & PROGRAMMING
3 1 2 1
Zone Function Settings
There are 8 functional settings available for each zone. These are as follows:
Fire latching
Normally a zone latches a fi re input signal. This setting allows the panel to clear automatically when a fi re signal is removed. This is useful for interfacing purposes.
Short circuit as alarm (EN54!)
For Older non EN54 or BS5839 compliant systems. This allows a short circuit to generate a fi re condition rather than a fault.
Intrinsically safe operation
This option changes the zone alarm and short circuit thresholds to allow for an MTL 5061 type intrinsically safe barrier to be used in the circuit.
Silent mode
This setting provides a visual & audible alarm at the panel with no local sounder circuit operation.
Priority alarm (EN54!)
Normally a 220R call point will override delays or dependency alarms. This option allows turning off the priority alarm feature.
Detector removal (EN54!)
The detector removal monitoring can be turned off. For use with older non compliant detectors.
Detector removal type
Schottky diode or Zener diode type detector bases for conventional zones (Does not apply to Twin wire circuits). The default operation is for shottky diode bases but can be changed for use with older Hochiki liveline bases or similar.
Gate valve & fi re pump indications
Gate valve and fi re pump status indication zones are confi gured in program option 8. The normal condition for this LED is OFF. Setting the amber fault LED to ON in this option will provide the Gate Valve indication feature, setting the amber fault LED to PULSING in this option will provide the Fire Pump Running functionality.
Page 35
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
33
SETUP & PROGRAMMING
Fire LED (pulsing)
LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7 LED 8 LED 9
Attribute
Fire latching
Short circuit as re
I.S operation
Silent mode
Priority alarm
Detector removal monitoring
Zener diode detector bases
Gate valve & fi re pump (see over page)
Delayed (info only)
Amber fault LED (default setting)
ON OFF OFF OFF ON ON OFF OFF OFF
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Enter the code 3 1 2 1 and press the ENTER button.
The zone 1 fi re LED will light. This indicates setting zone function attributes for zone 1. The amber, fault LEDs will show the current settings for that zone.
Use button 1 to move to the zone that requires editing.
With the required zone for editing LED lit, press the ENTER button to enter ‘editing mode’.
The fi re zone 1 LED will now pulse to indicate the editing of attribute 1 (fi re latching) for the selected zone.
Use button 1 to scroll to the attribute that requires editing, inidicated by a pulsing fi re LED 1 - 9 as per table below.
The setting of the attribute is indicated by the amber, fault LED, ON or OFF.
Use button 2 to switch the attribute ON or OFF, indicated by the amber, fault LED, then use button 1 to move to the next attribute if required.
Press the ENTER button to return back to the zone selection, indicated by a steady zone fi re LED
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
When fi nished all the zone function programming, enter the next programming code or disable the controls and return DIL switch 2 to ‘OFF’.
Page 36
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
34
SETUP & PROGRAMMING
Gate Valve Indication
Fire Pump Status Monitoring
The gate valve open position (i.e ready to allow water to pass through the valve in the event of fi re) is the normal default valve position and can be indicated on the panel with the red fi re LED. If the gate valve is closed, the zone fault LED is illuminated. The zone will operate as follows:
Gate valve open, via 3K9 resistor;
• Zone fi re LED continuously on
General Fire LED off
Internal buzzer will not operate
Fire routing and other fi re outputs will not operate
Alarm sounder circuits will not operate
The indication is non latching
Gate valve closed, via 470 resistor;
The panel will operate as per open or short circuit fault except that;
General Fault LED remains off
Fault output routing will not operate
Valve out of service, via 4K7 EOL only;
This equates to a quiescent condition and the zone will give no indication.
Fire pump status monitoring requires 2 zones to monitor one pump. The zones are confi gured as follows:
ZONE A - Set to Gate Valve Indication
The fi rst zone will monitor the pump power supply healthy / fault condition.
Pump Healthy;
• Zone fi re LED on, exactly the same as the valve open signal above
Pump Power Supply Fault:
Zone fault LED on, exactly the same as the valve closed signal above
Page 37
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
35
SETUP & PROGRAMMING
ZONE B - Set to Fire Pump Indication
The second zone will confi rm that the pump has started to run due to demand for fi re extinuishing water:
Pump idle;
i.e. 4K7 EOL resistor only. No indication at all (normal)
Pump running;
• 3K9, Zone fi re LED comes on and panel buzzer sounds intermittently, the general fi re alarm and alarm bells do NOT operate and the alarm is non latching.
Pump fail to run;
470 Ohm, Zone fault LED on and panel buzzer sounds continuously but with the general fi re and sounder circuits inhibited and the alarm / fault conditions are no latching.
Select zone(s) to be programmed for Gate Valve or Fire Pump status monitoring as per ‘Zone Function Settings’ programming mode 3-1-2-1.
With the required zone for editing LED lit, press the ENTER button to enter ‘editing mode’.
The fi re zone 1 LED will now pulse to indicate the editing of attribute 1 (fi re latching) for the selected zone.
Use button 1 to scroll to pulsing fi re LED 8 (gate valve & fi re pump indications).
Then use button 2 to set the status required for that zone, indicated by the amber, fault LED.
OFF = normal zone ON = Gate Valve Status Indication PULSING = Fire Pump Status Monitoring
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
When fi nished all the zone function programming, enter the next programming code or disable the controls and return DIL switch 2 to ‘OFF’.
Press the ENTER button to return back to the zone selection, indicated by a steady zone fi re LED
Page 38
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
36
SETUP & PROGRAMMING
DEPENDENCY MODES (FALSE ALARM MANAGEMENT)
Dependency modes are features described in EN54-2 for the processing of confi rmation alarms. It is a requirement by some monitoring stations and local fi re authoities in order to reduce the possibility of false alarms.
The panel has 3 dependency mode options, A, B & C. Only one type can be applied to the panel but any or all zones can be independently set for dependency mode.
Dependency mode, if assigned to a zone, is set to type A by default.
Dependency ‘A’ will apply the following sequence:
1.
1.
The fi rst detector alarm is inhibited.
The fi rst detector alarm is inhibited.
2.
2.
The panel resets and re-checks the inhibited zone within 15-30 seconds.
The panel resets and re-checks the inhibited zone within 15-30 seconds.
3.
3.
If an alarm is detected then the panel activates a full fi re condition.
If an alarm is detected then the panel activates a full fi re condition.
4.
4.
If no alarm is detected, the panel stays in an alert condition for 30 minutes. Any new alarm from
If no alarm is detected, the panel stays in an alert condition for 30 minutes. Any new alarm from
the same zone within this time activates a full fi re condition.
the same zone within this time activates a full fi re condition.
5.
5.
After 30 minutes or if RESET, the panel reverts to step 1.
After 30 minutes or if RESET, the panel reverts to step 1.
Note: 220Ω ‘Evacuate’ call points should be used on such zones to provide an instant un-delayed alarm. A 470Ω call point will be included in the dependency delay sequence.
Dependency ‘B’ will apply the following sequence:
1.
1.
The fi rst detector alarm will indicate at the control panel but not activate the sounders.
The fi rst detector alarm will indicate at the control panel but not activate the sounders.
2.
2.
The panel resets and re-checks the inhibited zone within 1 - 4 minutes (programmable, see code
The panel resets and re-checks the inhibited zone within 1 - 4 minutes (programmable, see code
2-1-3-4)
2-1-3-4)
1
1
.
.
3.
3.
If an alarm is detected then the panel activates a full fi re condition.
If an alarm is detected then the panel activates a full fi re condition.
4.
4.
If no alarm is detected, the panel stays in an alert condition for 5 - 30 minutes (programmable,
If no alarm is detected, the panel stays in an alert condition for 5 - 30 minutes (programmable,
see code 2-1-3-4)
see code 2-1-3-4)
2
2
. Any new alarm from the same or a different zone within this time activates a
. Any new alarm from the same or a different zone within this time activates a
full fi re condition.
full fi re condition.
5.
5.
After the time set above or if RESET, the panel reverts to step 1.
After the time set above or if RESET, the panel reverts to step 1.
Note: 220Ω ‘Evacuate’ call points should be used on such zones to provide an instant un-delayed alarm. A 470Ω call point will be included in the dependency delay sequence.
Dependency ‘C’ will apply the following sequence:
1.
1.
The fi rst detector or 470Ω call point alarm will indicate at the control panel but not activate the
The fi rst detector or 470Ω call point alarm will indicate at the control panel but not activate the
sounders.
sounders.
2.
2.
The panel will not activate a full fi re condition unless a second detector or 470Ω call point is
The panel will not activate a full fi re condition unless a second detector or 470Ω call point is
activated in the same or any other zone.
activated in the same or any other zone.
Note: A 220Ω ‘Evacuate’ call point can be used on such zones to provide an instant un-delayed alarm.
Page 39
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
37
SETUP & PROGRAMMING
2
2
2
1
1
1
2
1
3
4
4
4
Dependency Mode Selection
Select Zones For Dependency Mode
Set Timings For Dependency Mode B
To change the dependency mode type for the panel, enter the above code and press ENTER (panel is set to type A by default).
The amber, fault LED 1 will pulse and the current setting will be indicated by a steady amber, fault LED as per table below.
To select which zones should be included in the dependency mode, enter the above code and press ENTER.
The amber, fault LED 1 will pulse and any zones that are currently set to dependency mode will be indicated by a steady amber, fault LED.
Use button 1 to move the pulsing amber LED to the required zone(s) for setting and press ENTER to select. The LED will change to a rapid pulse to indicate that the zone is now set to dependency mode. Pressing ENTER again will de-select the zone and the LED will change back to a slow pulse.
Press and hold button 1 for 3 seconds to save the settings and exit the programming mode.
There are two programmable timings for dependency mode B, the confi rmation time 1, and the auto reset time 2.
Enter the above code and press ENTER. The fi re LED 1 will light indicating changing the timing for the confi rmation time, 1 - 4 minutes. Use button 1 to move to fi re LED 2, for changing the timing for the auto reset time (5 - 30 minutes). A third press of button 1 will light fi re LED 3 which is for changing Twin Wire detector compatibility (see over page), and then back to 1 again.
With the required fi re LED lit, the amber, fault LEDs will indicate the current timings set. Press the ENTER button to enter ‘edit mode’ and the fi re LED will change to pulsing.
Now use buttons 1 & 3 to increase or decrease the time. Button 1 increases, button 3 decreases. When nished press ENTER again to return to ‘view mode’
The confi rmation time 1 is indicated by the amber, fault LEDs 1 - 4 (1 - 4 minutes).
The auto reset time 2 is indicated by the amber, fault LEDs 1 - 5 using binary code values. See table below. Each push will increase or decrease the time by 1 minute.
Use button 1 to move the pulsing amber LED to the required type as per above and press ENTER to select it. The LED will change to a rapid pulse to indicate that it is now the current setting.
Press and hold button 1 for 3 seconds to save the setting and exit the programming mode.
LED 1 LED 2 LED 3 LED 4
No Dependency Mode Type A Type B Type C
AMBER LED 1 AMBER LED 2 AMBER LED 3 AMBER LED 4 AMBER LED 5
1 Minute 2 Minutes 4 Minutes 8 Minutes 16 Minutes
Page 40
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
38
SETUP & PROGRAMMING
2 1 3 4
Dependency mode Twin Wire detector compatibility
If using dependency mode, the panels are designed to work with the following conventional detectors:-
Apollo Series 65
• Apollo Orbis
• Hochiki CDX
Nittan Evolution Conventional
However, if also using
However, if also using
Twin Wire
Twin Wire
mode the panels are optimised for use with Apollo Series 65 heads &
mode the panels are optimised for use with Apollo Series 65 heads &
45681-206 Sav-Wire bases.
45681-206 Sav-Wire bases.
In order for the other three detector types; Apollo Orbis, Hochiki CDX & Nittan Evolution Conventional to
In order for the other three detector types; Apollo Orbis, Hochiki CDX & Nittan Evolution Conventional to
be used with their relevant Sav-Wire bases the above compatibility mode must be switched on.
be used with their relevant Sav-Wire bases the above compatibility mode must be switched on.
Enter the code: 2 - 1 - 3 - 4 and press ENTER. Zone 1 fi re LED will light.
Enter the code: 2 - 1 - 3 - 4 and press ENTER. Zone 1 fi re LED will light.
Use button 1 to move the fi re LED to zone 3.
Use button 1 to move the fi re LED to zone 3.
Press the ENTER button
Press the ENTER button
to enter ‘edit mode’ and zone 3 fi re LED will pulse.
to enter ‘edit mode’ and zone 3 fi re LED will pulse.
Now use button 2 to switch on
Now use button 2 to switch on
compatibility mode. The zone 1
compatibility mode. The zone 1 Fault LED will illuminate indicating that the compatibility mode is set to on,
Pressing button 2 again will toggle the compatibility mode on & off,
Pressing button 2 again will toggle the compatibility mode on & off,
indicated by the zone 1
indicated by the zone 1 Fault LED.
Press and hold button 1 for 3 seconds to save the settings and exit the programming mode.
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
N.B.
N.B.
The above setting is only relevant if you are using
The above setting is only relevant if you are using
Dependency mode AND Twin
Dependency mode AND Twin
Wire mode
Wire mode
but
but
NOT
NOT
using Apollo Series 65 detectors.
using Apollo Series 65 detectors.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Page 41
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
39
SETUP & PROGRAMMING
1 1 1 4
EN54 Sounder Resound Options
By default, after an initial re condition and the (blue) Silence Alarms button has been activated, any new re condition in a different zone will cause the alarms to resound.
It is possible to change this on a zonal basis so that any new alarm in a different zone will not resound the alarms.
Enter the above code and press the ENTER button. The Sounder Status LED will pulse slowly. Zone Fault LEDs will show their current status (see below) with Zone 1 pulsing to indicate it is under selection.
Use Button 1 to move to the zone for programming (indicated by a pulsing LED) and press the ENTER button to change the status.
Pressing the ENTER button again will toggle the status, indicated by a rapid or slow pulsing LED (see below). Then use Button 1 to move to the next zone. If the zone has been set to not resound alarms, the LED will be off. If kept as default, new fi re condition will resound alarms, then the LED will be on steady.
Rapid Pulse = Zone is under selection and is set to have alarms resound (default).
Slow Pulse = Zone is under selection and has been set to not resound alarms on new re condition.
LED Off = Zone has been set to not resound alarms on new re condition.
LED On = Zone is set to have alarms resound (default).
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
When fi nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Page 42
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
40
SETUP & PROGRAMMING
2 3 2 3
Apply Delay to Outputs For Selected Zones
The activation of sounder circuits and aux outputs can be delayed in response to selected zones. The actual delay time is set up in the panel wide programming options, 2-1-2-3.
The setting of delays here applies to all sounder circuits, all aux outputs or all sounder circuits and all aux outputs.
Individual outputs can be programmed to be active during a delay in the output functional options.
To apply the delays for selected zones, enter the above code and press ENTER.
The zone 1 fi re LED will illuminate. This indicates that delays are being applied for zone 1. Use button 1 to move the LED to the required zone for programming.
With the required zone LED lit, press the ENTER button to enter ‘edit mode’. The fi re LED will now pulse. Now use button 2 to turn on delays, this is indicated by the zone, amber, fault LED, ON.
Pressing button 2 again will toggle the delays ON & OFF, indicated by the zone, amber, fault LED.
With the amber LED, ON, use button 3 to select which outputs are to be delayed. The choice toggles between, all sounder circuits, all aux outputs or all sounder circuits and all aux outputs.
The selection is indicated by the Sounder Status LED and the Aux Output Status LED.
When fi nished programming for the zone, press the ENTER button again to return to the zone selection, indicated by a steady fi re LED.
If a delay has been applied to a zone, the Delay Status LED will be lit permanently, to indicate that a programmed delay exists. When a fi re condition is active in a zone with a delay, the Delay Status LED will pulse. When the delay time has expired the LED will extinguish.
To override a delay a 220Ω ‘Evacuate’ call point can used or a different zone can be activated that has no delays programmed.
When the Delay Status LED is active, the delay can be temporarily disabled using the panels disablements feature. If the delay has been disabled the Delay Status LED will be extinguished.
When fi nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Page 43
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
41
SETUP & PROGRAMMING
4 1 4 1
Input Function Settings
The panel has two inputs, located on the main circuit board, Class Change (CC) and Alert (PUL). Switching a negative voltage into these inputs will cause the alarm sounders to operate. The Class Change input (CC) will cause the alarms to sound continously and the Alert input (PUL) will cause the alarms to pulse.
Either or both of these inputs can be programmed to have a different function.
The available functions are:
Class Change (continous sounder operation).
Alert (pulsing sounder operation).
Evacuate (a latching input which activates all the alarms and shows a general fi re indication on the panel).
Silence (for remote silence alarms control).
Reset (for remote reset control).
Fire Zone 12 (a non latching input which indicates zone 12 fi re LED).
Fault Zone 12 (a non latching input which indicates zone 12 fault LED).
To change the default function of the inputs, enter the above code and press ENTER. The zone 1 fi re LED will illuminate. This indicates setting the function of the CC input. Use button 1 to move to zone 2 fi re LED for setting the function of the PUL input and then back to zone 1 again.
The current setting for the input will be indicated by the amber, fault LEDs as per table below.
With the required fi re LED lit, as per above, press the ENTER button to enter ‘editing mode’. The fi re zone 1 LED will now pulse to indicate function 1 (Class Change).
Now use button 1 to move the pulsing fi re LED to the required setting as per the table below, then use button 2 to select the function. The amber, fault LED will move to indicate the new current setting.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
PSU
@++- - +- +- +- +-+- +-
28V 0V
C NC NO C NC NO
FIRE FAULT
FR
FLTCCPUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
CC
PUL
-IP -IP
LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7
Class Change
Alert Evacuate
Remote Silence Alarms
Remote Reset
Fire Zone 12Fault Zone
12
Press the ENTER button again to return to input selection.
When fi nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Page 44
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
42
SETUP & PROGRAMMING
4 1 4 2
Output Programmability & Miscellaneous
All of the relays & outputs on the control panel’s main circuit board (TPC-A01) have default functions, i.e. operate on fi re or fault. The function for each of these outputs, however, can be changed. The outputs can also be programmed to have different responses for selected zones.
Before any programming can be applied to the main circuit board outputs, they must fi rst be made programmable using this mode.
Mode 4-1-4-2 also has 2 other miscellaneous functions, these are:
Set Fault Latching - This sets the latching of all faults on the panel. A useful tool for capturing any random or intermittent faults.
Invert Fault Output - The switched -ve fault output on the main circuit board usually appears when a fault is present. This can be inverted so that the output is constant and dissapears when a fault occurs, for fail safe operation.
To set either of the two miscellaneous options above or to make outputs programmable, enter the above code and press ENTER.
The fi re zone 1 LED will now pulse to indicate the setting of attribute 1 (fault latching).
Use button 1 to scroll to the attribute that requires setting, inidicated by a pulsing fi re LED 1 - 6 as per table below.
The setting of the attribute is indicated by the amber, fault LED, ON or OFF.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
With the required fi re LED pulsing, use button 2 to switch the attribute ON or OFF (amber, fault LED, ON or OFF).
When fi nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Fire LED (pulsing)
LED 1 LED 2 LED 3 LED 4 LED 5 LED 6
Attribute
Fault latching
Invert Fault Output
Fault Relay Programmable
Fault Output Programmable
Fire Relay Programmable
Fire Output Programmable
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Page 45
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
43
SETUP & PROGRAMMING
4 2 4 2
Relay & Output Responses to Selected Zones
Each of the relays and switched -ve outputs on the main circuit board and high spec zone extension cards can be independently programmed to respond in one of three different ways for each zone, ON, OFF or PULSING.
Note:- (Before any programming can be applied to the outputs on the main circuit board, they must rst be made programmable. See programming option 4-1-4-2).
Enter the code, 4-2-4-2 and press the ENTER button.
The zone 1 fi re LED will light. This indicates setting how each of the outputs are to respond for zone 1.
The amber, fault LEDs will show the current output settings for that zone. See table below
Use button 1 to move to the zone that requires editing.
With the required zone for editing LED lit, press the ENTER button to enter ‘editing mode’.
The fi re zone 1 LED will now pulse to indicate setting the response of the fi rst output (fi re relay on main circuit board) for the selected zone.
Use button 1 to scroll to the output that requires editing, inidicated by a pulsing fi re LED 1 - 10 as per table below.
The setting of the output is indicated by the amber, fault LED, ON, OFF or PULSING.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7 LED 8 LED 9 LED 10
Fire Relay (Main PCB)
Fault Relay (Main PCB)
Fire O/P (Main PCB)
Fault O/P (Main PCB)
OPA Zone ext card 1 (Zones 5 - 8)
OPB Zone ext card 1 (Zones 5 - 8)
Aux Relay Zone ext card 1 (Zones 5 - 8)
OPA Zone ext card 2 (Zones 9 - 12)
OPB Zone ext card 2 (Zones 9 - 12)
Aux Relay Zone ext card 2 (Zones 9 - 12)
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Use button 2 to change the response of the output for the selected zone, ON, OFF or PULSING, indicated by the amber, fault LED, then use button 1 to move to the next output if required.
Press the ENTER button to return back to the zone selection, indicated by a steady zone fi re LED
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
When fi nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Tip - You can use button 4 to change the response of all outputs simultaneously to ON, OFF or PULSING (for faster programming).
Page 46
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
44
SETUP & PROGRAMMING
4 3 4 2
Conventional Sounder Circuit Responses to Selected Zones
Each of the conventional sounder circuits on the main circuit board and high spec zone extension cards can be independently programmed to respond in one of three different ways for each zone, ON, OFF or PULSING.
Enter the above code and press the ENTER button.
The zone 1 fi re LED will light. This indicates setting how each of the sounder circuits are to respond for zone 1.
The amber, fault LEDs will show the current sounder circuit settings for that zone. See table below
Use button 1 to move to the zone that requires editing.
With the required zone for editing LED lit, press the ENTER button to enter ‘editing mode’.
The fi re zone 1 LED will now pulse to indicate setting the response of the fi rst sounder circuit (SNDR1 on main circuit board) for the selected zone.
Use button 1 to scroll to the sounder circuit that requires editing, inidicated by a pulsing fi re LED 1 - 6 as per table below.
The setting of the sounder circuit is indicated by the amber, fault LED, ON, OFF or PULSING.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
LED 1 LED 2 LED 3 LED 4 LED 5 LED 6
SNDR1 (Main PCB)
SNDR2 (Main PCB)
SNDR A. Zone ext card 1 (Zones 5
- 8)
SNDR B. Zone ext card 1 (Zones 5
- 8)
SNDR A. Zone ext card 2 (Zones 9 -
12)
SNDR B. Zone ext card 2 (Zones 9 -
12)
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Use button 2 to change the response of the sounder circuit for the selected zone, ON, OFF or PULSING, indicated by the amber, fault LED, then use button 1 to move to the next output if required.
Press the ENTER button to return back to the zone selection, indicated by a steady zone fi re LED
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
When fi nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
Tip - You can use button 4 to change the response of all sounder circuits simultaneously to ON, OFF or PULSING (for faster programming).
Page 47
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
45
SETUP & PROGRAMMING
3
4
3
3
1
2
3
3
2
4
1
1
2
3
1
2
Twin Wire Sounder Circuit Responses to Selected Zones
Comms PCB Outputs Response to Selected Zones
Zone of Origin - Quick Set Option for Twin Wire Circuits
Zonal Sounders - Quick Set Option for Twin Wire Circuits
If using Twin Wire zones, the sounders connected to each of the Twin Wire circuits can be programmed to respond to each Twin Wire zone in the same way as the conventional sounder circuits.
The process is similar as with the conventional sounder circuits, but using the above code.
Use button 1 to fi rst select the Twin Wire sounder cct for editing (indicated by a steady fi re zone LED), press ENTER and then use button 1 again to now select the Twin Wire zone to edit the response for (indicated by a pulsing fi re zone LED).
Then use button 2 to edit the response indicated by the amber, fault LED, ON = Continuous, OFF = No Activation, PULSING = Pulsing
If a repeater/network Comms PCB (TPCA05) has been fi tted to the panel, there are 6, switched -ve outputs on the PCB which can be programmed to respond to selected zones in the same way as the other outputs and sounder circuits.
The process is exactly the same as with the other outputs and sounder circuits, but using the above code.
I.e. Use button 1 to select the zone fi rst (indicated by a steady fi re zone LED), press ENTER and then use button 1 to select the output 1 - 6 to edit (indicated by a pulsing fi re zone LED 1 - 6 as per the table below).
Use button 2 to edit the response indicated by the amber, fault LED, ON, OFF or PULSING
Entering the above code and pressing ENTER will set all Twin Wire sounder circuits to zone of origin, continuous ringing, all other circuits pulsing.
Entering the above code and pressing ENTER will set all Twin Wire sounder circuits to zone of origin, continuous ringing, all other circuits silent.
When fi nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
LED 1 LED 2 LED 3 LED 4 LED 5 LED 6
OP 1 OP 2 OP 3 OP 4 OP 5 OP 6
Tip - You can use button 4 to change the response of each Twin Wire sounder circuit to all zones simultaneously to ON, OFF or PULSING (for faster programming).
Tip - You can use button 4 to change the response of all outputs simultaneously to ON, OFF or PULSING (for faster programming).
Page 48
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
46
SETUP & PROGRAMMING
4 2 4 4
Relay & Output Functional Options
Each of the relays and switched -ve outputs on the main circuit board and high spec zone extension cards can be independently programmed with a custom response to; Silence Alarms (including, Silence button or input programmed for remote Silence Alarms), Evacuate (including, Resound button, input programmed for Evacuate or 220Ω ‘Evacuate’ call point), Class Change Input, Alert Input or during Zone Delays.
Note:- (Before any programming can be applied to the outputs on the main circuit board, they must rst be made programmable. See programming option 4-1-4-2).
Enter the code, 4-2-4-4 and press the ENTER button.
The zone 1 fi re LED will light. This indicates the output to be programmed as per the table below.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7 LED 8 LED 9 LED 10
Fire Relay (Main PCB)
Fault Relay (Main PCB)
Fire O/P (Main PCB)
Fault O/P (Main PCB)
OPA Zone ext card 1 (Zones 5 - 8)
OPB Zone ext card 1 (Zones 5 - 8)
Aux Relay Zone ext card 1 (Zones 5 - 8)
OPA Zone ext card 2 (Zones 9 - 12)
OPB Zone ext card 2 (Zones 9 - 12)
Aux Relay Zone ext card 2 (Zones 9 - 12)
Use button 2 to change the response for the output as per table above, indicated by the amber, fault LED, ON or OFF. Then use button 1 to move to the next function if required.
* Fault relay & output default to ‘OFF’
Press the ENTER button to return back to the output selection, indicated by a steady zone fi re LED
When fi nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Use button 1 to move the fi re LED to the output that requires editing.
With the required output for editing LED lit, press the ENTER button to enter ‘editing mode’.
The fi re zone 1 LED will now pulse to indicate setting the selected output’s response to the fi rst function (Resets on Silence Alarms).
Use button 1 to scroll to the function that requires editing for that output, inidicated by a pulsing fi re LED 1 - 5 as per table below.
Fire LED (pulsing)
LED 1 LED 2 LED 3 LED 4 LED 5
Function
Resets on Silence Alarms
Activates on Evacuate
Activates on Class Change
Activates on Alert
Activates During Delay
Amber fault LED (default setting)
OFF ON * OFF OFF OFF
Page 49
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
47
SETUP & PROGRAMMING
Press the ENTER button to return back to the Twin Wire sounder circuit selection, indicated by a steady zone fi re LED.
When fi nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode.
Press the ENTER button to return back to the sounder circuit selection, indicated by a steady zone fi re LED.
When fi nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode.
Fire LED (pulsing)
LED 1 LED 2 LED 3 LED 4 LED 5
Function
Silences on Silence Alarms
Sounds on Evacuate
Sounds on Class Change
Sounds on Alert
Sounds During Delay
Amber fault LED (default setting)
ON ON ON ON OFF
3413243
4
Twin Wire Sounder Circuit Functional Options
Conventional Sounder Circuit Functional Options
If using Twin Wire zones, the sounders on each of the Twin Wire circuits can be programmed with a custom response to various panel functions in the same way as the relays and switched -ve outputs.
The process is exactly the same as with the relays & switched -ve outputs, but using the above code.
I.e. Use button 1 to select the Twin Wire sounder circuit fi rst (indicated by a steady fi re zone LED), press ENTER and then use button 1 to select the function that requires editing for that sounder circuit (indicated by a pulsing fi re zone LED) as per table below.
Use button 2 to edit the response indicated by the amber, fault LED, ON or OFF.
To programme each of the conventional sounder circuits on the main circuit board and high spec zone extension cards with same custom reponses as above, the process is exactly the same but using the code 4-3-4-4.
I.e. Use button 1 to select the sounder circuit fi rst (indicated by a steady fi re zone LED) as per table below.
Press ENTER and then use button 1 to select the function that requires editing for that sounder circuit (indicated by a pulsing fi re zone LED) as per the sounder CCT function table in the Twin Wire settings above.
Use button 2 to edit the response indicated by the amber, fault LED, ON or OFF.
LED 1 LED 2 LED 3 LED 4 LED 5 LED 6
SNDR1 (Main PCB)
SNDR2 (Main PCB)
SNDR A. Zone ext card 1 (Zones 5
- 8)
SNDR B. Zone ext card 1 (Zones 5
- 8)
SNDR A. Zone ext card 2 (Zones 9 -
12)
SNDR B. Zone ext card 2 (Zones 9 -
12)
Sounder CCT function table
Page 50
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
48
SETUP & PROGRAMMING
4 2 2 4
Output & Relay Network Responses
The Fire relays and switched negative outputs in the panel will, by default, activate continuously for any re condition from the entire network.
The Fault relay and other switched negative outputs will also activate continuously, by default, if they have been made programmable using programming option 4-1-4-2.
This option enables the default to be changed for each of the local relays and outputs. The response can be either; CONTINUOUS, PULSING or NONE when a fi re condition is received from any other panel in the network.
Enter the above code and press the ENTER button.
The zone 1 fi re LED will pulse indicating setting the response for the Fire relay on the main PCB.
The relays and outputs are represented by zone LEDs 1 - 10 as per table below.
A pulsing red fi re LED indicates which relay or output is selected and the setting is represented by the amber fault LED. See tables below.
Use button 1 to move the pulsing fi re LED to the required relay or output, then use button 2 to change the response, indicated by the amber fault LED. Each press of button 2 will toggle through the 3 available responses.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Amber LED ON Relay/output activates CONTINUOUSLY for other network panel fi res
Amber LED PULSING Relay/output PULSES for other network panel fi res
Amber LED OFF Relay/output NO RESPONSE for other network panel fi res
When fi nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode.
Note:- The relay and output responses to a fi re condition from their own panel are set using programming option 4-2-4-2.
If a local response has been programmed, consideration should also be given to the network response which may affect it.
LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7 LED 8 LED 9 LED 10
Fire Relay (Main PCB)
Fault Relay (Main PCB)
Fire O/P (Main PCB)
Fault O/P (Main PCB)
OPA Zone ext card 1 (Zones 5 - 8)
OPB Zone ext card 1 (Zones 5 - 8)
Aux Relay Zone ext card 1 (Zones 5 - 8)
OPA Zone ext card 2 (Zones 9 - 12)
OPB Zone ext card 2 (Zones 9 - 12)
Aux Relay Zone ext card 2 (Zones 9 - 12)
Page 51
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
49
SETUP & PROGRAMMING
4332224
4
Sounder Circuit Network Responses
Twin Wire Sounder Circuit Network Responses
The six possible sounder circuits in the panel will, by default, activate continuously for any fi re condition from the entire network.
This option enables the default to be changed for each of the local circuits. The response can be either; CONTINUOUS, PULSING or NONE when a fi re condition is received from any other panel in the network.
Enter the above code and press the ENTER button.
The zone 1 fi re LED will pulse indicating setting the response for sounder circuit 1.
Sounder circuits 1 - 6 are represented by zone LEDs 1 - 6 respectively. A pulsing red fi re LED indicates which circuit is selected and the setting is represented by the amber fault LED as per table below.
Use button 1 to move the pulsing fi re LED to the required circuit, then use button 2 to change the response of the circuit, indicated by the amber fault LED. Each press of button 2 will toggle through the 3 available responses.
If using Twin Wire zones, the sounders connected to each of the Twin Wire circuits will, by default, activate continuously for any fi re condition from the entire network.
This option enables the default to be changed for each of the local Twin Wire sounder circuits. The response can be either; CONTINUOUS, PULSING or NONE when a fi re condition is received from any other panel in the network.
The process is exactly as descibed above but using code 3-2-2-4.
Use button 1 to select the Twin Wire sounder circuit, represented by zone LEDs 1 - 12 respectively. A pulsing red fi re LED indicates which circuit is selected and the setting is represented by the amber fault LED. Then use button 2 to edit the response as per table above.
Amber LED ON Sounder circuit activates CONTINUOUSLY for other network panel fi res
Amber LED PULSING Sounder circuit PULSES for other network panel fi res
Amber LED OFF Sounder circuit NO RESPONSE for other network panel fi res
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
When fi nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode.
Note:- The sounder circuit & Twin Wire sounder circuit responses to a fi re condition from their own panel are set using programming options 4-3-4-2 & 3-1-2-2.
If a local response has been programmed, consideration should also be given to the network response which may affect it.
LED 1 LED 2 LED 3 LED 4 LED 5 LED 6
SNDR1 (Main PCB)
SNDR2 (Main PCB)
SNDR A. Zone ext card 1 (Zones 5
- 8)
SNDR B. Zone ext card 1 (Zones 5
- 8)
SNDR A. Zone ext card 2 (Zones 9 -
12)
SNDR B. Zone ext card 2 (Zones 9 -
12)
Page 52
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
50
SETUP & PROGRAMMING
4 3 4 3
Comms PCB Output Functional Options
If a repeater Comms PCB (TPCA05) has been fi tted to the panel, the 6, swtched -ve outputs on the PCB can also be independently programmed with a custom response to; Silence Alarms (including, Silence button or input programmed for remote Silence Alarms), Evacuate (including, Resound button, input programmed for Evacuate or 220Ω ‘Evacuate’ call point), Class Change Input, Alert Input or during Zone Delays.
Enter the above code, and press the ENTER button.
The zone 1 fi re LED will light. This indicates the output to be programmed as per the table below.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Use button 2 to change the response for the output as per table above, indicated by the amber, fault LED, ON or OFF. Then use button 1 to move to the next function if required.
Press the ENTER button to return back to the output selection, indicated by a steady zone fi re LED
When fi nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode.
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Use button 1 to move the fi re LED to the output that requires editing.
With the required output for editing LED lit, press the ENTER button to enter ‘editing mode’.
The fi re zone 1 LED will now pulse to indicate setting the selected output’s response to the fi rst function (Resets on Silence Alarms).
Use button 1 to scroll to the function that requires editing for that output, inidicated by a pulsing fi re LED 1 - 5 as per table below.
Fire LED (pulsing)
LED 1 LED 2 LED 3 LED 4 LED 5
Function
Resets on
Silence
Alarms
Activates
on
Evacuate
Activates
on Class
Change
Activates
on Alert
Activates
During
Delay
Amber fault LED (default setting)
OFF OFF OFF OFF OFF
LED 1 LED 2 LED 3 LED 4 LED 5 LED 6
OP 1 OP 2 OP 3 OP 4 OP 5 OP 6
Page 53
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
51
SETUP & PROGRAMMING
3 1 1 4
System Diagnostics Mode
System faults can occur if a PCB in the control panel or one of the repeater panels stops working. This may be due to a fault condition, loss of power, software lockup or memory checksum error.
A system fault can also occur if the internal PCB confi guration or number of repeater panels has not been correctly set up in the panel wide programming options (2-1-2-3).
If the fault originates from the control panel’s main PCB then no further interrogation is possible and the circuit board should be restored or replaced urgently.
The above code has been provided as a quick diagnosis tool to show which additional PCBs, repeater or network slave panels the control panel thinks it should have according to the programming set up, Vs, the actual PCBs and repeater/network panels it can see via it’s internal monitoring capacity.
Enter the above code and press ENTER. The control panel will illuminate LEDs to show the set up. The red, fi re LEDs indicate the confi guration setting. The amber, fault LEDs indicate the presence of the PCBs, repeaters or network slave panels which the control panel thinks it should have according to the programming set up.
See table below.
The LEDs will display for 10 seconds and then the panel will automatically exit the diagnosis mode. Pressing button 2 will reveal the origin of a system fault indication.
Note: After power up, the system should be allowed to initialise for 2 - 3 minutes before using this code otherwise false indications could occur. If in doubt, re-enter the code a second time to check.
Any differences shown here can then be investigated and corrected either by restoring or replacing PCBs or correcting the confi guration settings in the panel wide settings mode 2-1-2-3. Pressing button 1 will show the repeater panel status’s, pressing button 1 again will show the status of the network slave panels.
LED Indicators DIAGNOSTIC MODE
Board Status afer
entry 3114
Repeater Status
Press Button 1
3114
Slave Panel Status
Press Button 1
Local System Fault
Press Button 2
FIRE LED OFF NONE SET NONE SET NONE SET N/A
FIRE LED STEADY CONFIGURED CONFIGURED CONFIGURED N/A
FAULT LED STEADY BOARD PRESENT REPEATER PRESENT SLAVE PRESENT N/A
FAULT LED PULSING N/A
PRESENT WITH
LOCAL FAULT
PRESENT WITH
LOCAL FAULT
SYSTEM WATCHDOG
Z1 Ext Zone Card 1 Repeater 1 Slave Panel 1 Main Processor PCB
Z2 Ext Zone Card 2 Repeater 2 Slave Panel 2 Display PCB
Z3 Comms PCB (TPCA05) Repeater 3 Slave Panel 3 Ext Zone Card 1
Z4 Output Card 1 Repeater 4 Slave Panel 4 Ext Zone Card 2
Z5 Output Card 2 Repeater 5 Slave Panel 5 Comms PCB (TPCA05)
Z6 Output Card 3 Repeater 6 Slave Panel 6 Power Supply PCB
Z7 Output Card 4 Repeater 7 Slave Panel 7 Output Card (TPCA08)
Z8 Repeater 8 Power Up
Page 54
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
52
SETUP & PROGRAMMING
REPEATER PANEL SETUP & PROGRAMMING
The panel can support up to 8, fully functional repeater panels on the network which can be either the 12 way repeater panels or Remote Display Units or a combination of both. N.B. The 12 way repeater panel will only display the fi rst 12 zones of any network system.
Repeater Comms PCB
To run repeaters, a Comms PCB (TPCA05) must be fi tted to the control panel. The repeater panels are supplied with the comms board fi tted.
The Comms PCB fi ts into the control panel on top of the main circuit board where the ribbon cable from the display board is normally plugged.
To fi t the Comms PCB, power down the panel, un-plug the display board ribbon cable from the main circuit board and plug the Comms PCB into the socket instead.
A socket is provided on the top of the Comms PCB to re-connect the display board ribbon cable.
Once the Comms PCB has been fi tted, switch 7 on the 7 way DIL switch located on the main circuit board should be switched to the ON position.
With this switch in the ON position the panel will automatically recognise & operate the Comms PCB (TPCA05).
Next, the panel will need to be programmed for the number of repeater panels on the system. See panel wide settings 2-1-2-3 option 2 (Set Number of Repeater Panels on System).
Addressing
Each repeater panel needs to have a seperate address. The addressing is done using the 4 DIL switches on each of the Comms PCBs using binary code values, see diagram below.
The address should be set in sequence from 1 - 8, fi rst repeater address 01, next repeater address 02 etc. The control panel should always be address 00 (all switches off).
PSU
@++-- +-+-+- +-+-+- +-
28V 0V
C NC NO C NC NO
FIRE FAULT
FR
FLT
CC
PUL
-OP-OP -IP-IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
PSU
@++-- +-+-+- +-+-+- +-
28V 0V
C NC NO C NC NO
FIRE FAULT
FR
FLT
CC
PUL
-OP-OP -IP-IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
COMS A COMS B 28V+SW -ve OUTPUTS
+-
+-
123456
1 2 34
ON
ADDRESS
Disconnect display board ribbon cable
7 way DIL switch
Plug Comms PCB into the socket and re-connect dispay board ribbon cable to socket on top of Comms PCB
1 2 345
67
ON
1 2 345
67
ON
1 2 34
ON
ADD 01
1 2 34
ON
ADD 02
1 2 34
ON
ADD 03
1 2 34
ON
ADD 04
1 2 34
ON
ADD 05
1 2 34
ON
ADD 06
1 2 34
ON
ADD 07
1 2 34
ON
ADD 08
ON = Network/ Repeater mode
1 2 345
67
ON
Network System Note:
Repeater panel addresses are parallel to network slave panel addresses on a network system.
I.e. a repeater and a network slave panel can both have address 01 on the network.
Page 55
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
53
SETUP & PROGRAMMING
Wiring
The repeater panels are designed to be wired in a fault tolerant (fail safe) loop confi guration, from comms A to B and back to the main panel again (see diagram). This enables repeater panels to still work if there is a break in the cables.
If replacing an older system where the existing cabling cannot be confi gured in a loop as shown, it is possible to change the panel back to radial circuit comms monitoring. See panel wide settings 2-1­2-3 option 6 (Repeater Comms Monitoring Type).
COMS A COMS B 28V+SW -ve OUTPUTS
+-
+-
123456
1 2 34
ON
ADDRESS
COMS A COMS B 28V+SW -ve OUTPUTS
+-
+-
123456
1 2 34
ON
ADDRESS
COMS A COMS B 28V+SW -ve OUTPUTS
+-
+-
123456
1 2 34
ON
ADDRESS
Fault Tolerant Loop Wiring
Main Panel Repeater/Network Panel 1 Repeater/Network Panel 2
4 4 4 3
Programming Repeater Panels
Programming of all the repeater panels is done from the main control panel.
The repeater panels have 2 inputs located on the main circuit board, Class Change (CC) and Alert (PUL). Switching a negative voltage into these inputs will cause the alarm sounders to operate. The Class Change input (CC) will cause the alarms to sound continously and the Alert input (PUL) will cause the alarms to pulse.
There are also 6 switch -ve outputs located on the Comms PCB. By default o/p 1 is set to activate on common fi re and o/p 2 is set to activate for common fault.
There are 4 programming options available for the inputs and outputs in the repeater panels.
Outputs 1 - 6 activate on common fi re
Outputs 1 - 6 activate zonally for zones 1 - 6
Outputs 1 - 6 activate zonally for zones 7 - 12
Change inputs CC & PUL to power supply fault inputs.
It is also possible in this programming mode to disable the controls on repeater panels, making them passive instead of active and to disable the battery monitoring on the repeater panel if no battery backup is required.
Enter the above code and press ENTER. The zone 1 fi re LED will light. This indicates which repeater panel is to be programmed 1 - 8. Use button 1 to move the fi re zone LED to the required repeater.
With the required repeater for editing LED lit, press the ENTER button to enter ‘editing mode’. The fi re zone 1 LED will now pulse to indicate setting of attribute 1 (outputs 1 - 6 common fi re) for that repeater.
Use button 1 to scroll to the attribute that requires editing, inidicated by a pulsing fi re LED 1 - 7 as per table below. Now use button 2 to change the setting indicated by the amber, fault LEDs, ON or OFF. Then use button 1 again to move to the next attribute if required. See repeater instruction manual for further
details of option 7
Fire LED (pulsing) LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7
Attribute
O/P 1 - 6
Common Fire
O/P 1 - 6
Zonal (Zones
1 - 6)
O/P 1 - 6
Zonal (Zones
7 - 12)
Inputs For PSU Fault
Controls
Passive
Disable Battery
Monitoring
Repeater
Mimic Display
Mode
Default Setting OFF OFF OFF OFF OFF OFF OFF
Page 56
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
54
OPERATING
PANEL CONTROLS & INDICATIONS
8 Button Keypad For Controls
And Programming
Status Indicator LEDs
Activate Controls Key Switch
RESOUND SILENCE RESET
ENTER
12
34
General Disablement
Test Mo de Sounder Status
Aux Output Status Power Supply Fault
System Fault
Delay Status
Access Level
Repeater Fault
On
Off
Supply Healthy General Fire General Fault
Fire Detection System
Activate
Controls
Zones in Fire
Zone Fault / Disabled / Test
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Zones In Fault, Zones Disabled or Zones In Test Indicator LEDs
Zonal Fire Indicator LEDs
Activate Controls
In normal standby mode the keypad controls are inactive to protect from unauthorised operation. Controls can be activated by using the ‘Activate Controls’ key switch or by entering a four digit code using the keypad.
The use of a code entry to activate the controls is enabled by default but can be disabled in the Level 3 engineering functions.
To activate the controls using the key switch
Turn the key clockwise to the ‘On’ position. The ‘Access Level’ indicator LED will light and all buttons on the keypad will now be operational. To deactivate the controls, turn the key back to the ‘Off’ position and the ‘Access Level’ indicator LED will extinguish.
If the key switch is in the ‘On’ position the keypad will remain active.
NOTE : It is not possible to remove the key in the ‘On’ position.
To activate the controls using the keypad
Enter the four digit code using buttons 1 - 4. The factory default code is 1-2-3-4 but can be changed in the engineering functions. After entering the four digit code press the ‘ENTER’ button. The ‘Access Level’ indicator LED will light and all buttons on the keypad will now be operational.
After activation by code entry, controls will automatically deactivate again after 2 minutes and the panel will return to standby mode.
The test lamps and mute buzzer functions are operational without the need to activate controls.
Page 57
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
55
OPERATING
Keypad
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND (red):
Use to resound the alarms after they have been silenced. Can also be used to invoke full evacuation.
SILENCE (blue):
Use to silence the sounders during an alarm condition.
RESET (green):
Resets the panel back to standby mode.
1: (Disable Mode)
With controls inactive, use to initialise code entry mode for activation of controls. With controls active, use to disable zones, sounder circuits or aux outputs (see DISABLE MODE section). Also has the numeric value 1 for code entry.
2: (Test Mode)
With controls inactive, use to initialise code entry mode for activation of controls. With controls active, use to put zones or sounders circuits into test mode (see TEST MODE section). Also has the numeric value 2 for code entry.
3: (Mute Buzzer)
Mutes the panels internal re and fault buzzer. (The buzzer will still blip every 5-6 seconds during a re or fault condition). This function is operational without the need to activate controls. Also has the
numeric value 3 for code entry.
4: (Test Lamps &
Buzzer)
Use this button to illuminate all LEDs and sound the internal buzzer to check that they are working correctly. This function is operational without the need to activate controls. Also has the numeric value 4 for code entry.
ENTER:
This button is used to confi rm code entries. It can also be used for fault diagnosis (see FAULT DIAGNOSIS section).
LED On LED Pulsing
Zones in Fire 1 - 12
N/A Indicates alarm condition in zone.
Zone Fault/Disabled/Test 1 - 12
Indicates zone circuit is disabled or in test mode.
Indicates a fault in the zone circuit.
Supply Healthy:
Indicates mains and/or battery supply is present.
N/A
General Fire:
N/A Indicates panel is in alarm condition.
General Fault:
N/A Indicates one or more faults are present.
General Disablement:
Indicates one or more circuits have been disabled.
Indicates disablement selection mode is active.
Test Mode:
Indicates one or more circuits are in test mode
Indicates test mode selection is active.
Sounder Status:
Indicates sounder circuits have been disabled or are in test mode
Indicates a fault on one or more sounder circuits.
Aux Output Status:
Indicates auxiliary outputs have been disabled.
N/A
Power Supply Fault:
N/A Indicates a power supply or battery fault.
System Fault:
Indicates a system failure, panel not functional or the internal PCB confi guration has not been set up correctly (see page 26).
Indicates the panel has recovered from a system fault.
Access Level:
Indicates controls are active (access level 2).
Indicates panel is in confi guration mode (access level 3).
Repeater Fault:
N/A
Indicates a fault on one or more repeater panels
Delay Status:
Delays are confi gured Delay is running
Status LED Indicators
Some buttons have other functions within the engineering facilities. These functions are described in the relevant sections.
Page 58
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
56
OPERATING
Disable Mode is used to disable or isolate individual zone circuits or all sounder circuits, all auxiliary outputs and any delays to outputs.
To initialise Disable Mode fi rstly activate the controls by turning the key switch or by entering the four digit code. Then press and hold the Disable Mode button (1) for 3 seconds.
After 3 seconds the panel will bleep and the General Disablement LED and Zone 1 Fault LED will pulse slowly, indicating that Zone 1 is in disable selection mode.
Pressing the Disable Mode button again will move disable selection mode to Zone 2 and the Zone 2 Fault LED will be pulsing instead. Subsequent presses will move the selection to Zones 3 - 12, dependant on the number of zones fi tted to the panel. I.e up to zone 4 on a 4 zone, 6 on a 6 zone, 8 on a 8 zone etc.
After the last available zone the next press will move the selection mode to the sounder circuits, indicated by the Sounder Status LED and then to the Aux outputs, indicated by the Aux Output Status LED and nally to the Delay LED. Pressing the button once more will move the selection back to Zone 1 again.
When the desired circuit, outputs or delays to be disabled is indicated by a slow pulsing LED, use the ENTER button to select it. Once selected the indicator LED will change to a rapid pulse. Pressing ENTER again will toggle the circuit between disabled and enabled. Then use Disable Mode button again to move to the next circuit. Any or all circuits, outputs or delays can be disabled simultaneously.
When all disablements have been set, press and hold the Disable Mode button for 3 seconds again. This will exit the disable selection mode and the panel will return to standby. All disabled circuits and the General Disablement will now be indicated by a steady LED.
To enable the circuits again, repeat the above process using the Disable Mode button to select the circuit and the ENTER button to remove the disablement.
Tip:
With the controls active, pressing the Disable Mode button briefl y will reveal which circuits are disabled (as opposed to in test mode). This is useful if using Disable Mode and Test Mode at the same time.
DISABLE MODE
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Page 59
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
57
OPERATING
Test Mode is used when testing the fi re alarm system. In test mode the devices in the zone(s) in test, detectors and call points etc, can be activated and the panel will automatically reset, enabling the system to be tested by one person. It is possible to test head removal monitoring and to test the system with or without the sounders.
To initialise Test Mode, fi rstly activate the controls by turning the key switch or by entering the four digit code. Then press and hold the Test Mode button (2) for 3 seconds.
After 3 seconds the panel will bleep and the Test Mode LED and Zone 1 Fault LED will pulse slowly, indicating that Zone 1 is in test selection mode. The Sounder Status LED will also be pulsing rapidly, this indicates that the test will be with sounders. (Test mode without sounders is explained below)
Pressing the Test Mode button again will move test selection mode to Zone 2 and the Zone 2 Fault LED will be pulsing instead. Subsequent presses will move the selection to Zones 3 - 12, dependant on the number of zones fi tted to the panel. I.e up to zone 4 on a 4 zone, 6 on a 6 zone, 8 on a 8 zone etc..
After the last available zone the next press will move the selection mode to the sounder circuits, indicated by no Zone Fault LEDs on. This position selects whether or not the sounders will ring during test. Pressing the button once more will move the selection back to Zone 1 again.
When the desired zone to be tested is indicated by a slow pulsing LED, use the ENTER button to select it. Once selected the indicator LED will change to a rapid pulse. Pressing ENTER again will toggle the zone between in and out of test. Then use Test Mode button again to move to the next zone. Any or all zones can be in test mode simultaneously.
When at the sounder status position, use the ENTER button to toggle between testing with or without sounders. A rapid pulse = with sounders (default), a slow pulse = without sounders.
When all zones to be tested have been selected, press and hold the Test Mode button for 3 seconds again. This will exit the test selection mode. All zones in test and the Test Mode will now be indicated by a steady LED.
To take zones out of test mode, repeat the above process using the Test Mode button to select the zone and the ENTER button to change the status.
Test Mode With Sounders
Activation of a call point or detector - sounders will pulse twice, device is automatically reset. Removal of a detector - sounders will pulse once.
Test Mode Without Sounders
Activation of a call point or detector - panel buzzer and LED response only, device is automatically reset.
Tip:
With the controls active, pressing the Test Mode button briefl y will reveal which circuits are in test mode (as opposed to disabled). This is useful if using Disable Mode and Test Mode at the same time.
TEST MODE
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
Page 60
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
58
OPERATING
FAULT DIAGNOSIS
If the panel has detected a fault on the system the General Fault LED will be illuminated and the internal fault buzzer will sound. Secondary LEDs will also be illuminated depending on the location of the fault.
Pressing and holding the ENTER button will reveal more detailed information about the loction and type of fault.
This function will not work if the panel is in a fi re condition. If no faults exist pressing the ENTER button will have no effect.
This function is operational only when controls are not active.
The following table shows details of the indications in fault diagnosis mode:
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
LED Indicator & State before pressing ENTER
LED Pulsing after pressing ENTER
LED Steady after pressing ENTER
LED Off after pressing ENTER
Location
Zone 1 Fire LED (off)
Sounder circuit 1 short circuit
Sounder circuit 1 open circuit
OK Main PCB SNDR 1
Zone 2 Fire LED (off)
Sounder circuit 2 short circuit
Sounder circuit 2 open circuit
OK Main PCB SNDR 2
Zone 3 Fire LED (off)
Sounder circuit 3 short circuit
Sounder circuit 3 open circuit
OK High Spec
Extension Zone Card
Zone 4 Fire LED (off)
Sounder circuit 4 short circuit
Sounder circuit 4 open circuit
OK High Spec
Extension Zone Card
Zone 5 Fire LED (off)
Sounder circuit 5 short circuit
Sounder circuit 5 open circuit
OK High Spec
Extension Zone Card
Zone 6 Fire LED (off)
Sounder circuit 6 short circuit
Sounder circuit 6 open circuit
OK High Spec
Extension Zone Card
Zone 1 - 4 Fault/ Disabled/Test LED (pulsing)
Zone # short circuit
Zone # open circuit
(slow pulse) Zone # detector removed
Main PCB Zones 1 - 4
Zone 1 - 4 Fault/ Disabled/Test LED (steady)
N/A N/A Zone # disabled or
in test mode
Power Supply Fault LED (pulsing)
Mains failure Battery failure or
high impedance
Voltage fault Main PCB
Page 61
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
59
OPERATING
FUNCTIONALITY DURING A SYSTEM FAULT
A system fault is indicated when a processor controlling a function in the panel has a watchdog time out or processor failure. In the event of a system fault the particular board affected may not be functional. The following indications may be observed.
Display Board
System Fault LED only continous and continous buzzer sound. Display board TPCA03 is halted and no other indication or control is possible. Fault relay and fault output are activated. If a fi re occurs alarm sounders and outputs will still function.
Main Board or zone extender boards
System Fault LED continous and General Fault LED pulsing and continous buzzer sound. Main board, or extender card if fi tted are halted. Fault relay is activated. Alarms may be activated on the unaffected board.
Repeater Comms Board
System Fault LED continous and General Fault LED pulsing and Repeater Fault LED continous. The Comms Board TPCA05 is halted. Fault relay and output are active, and repeater panels will cease to function. Fire alarms can still be detected and controlled by the panel.
System Fault recovery
System Fault LED pulsing and General Fault LED pulsing along with a pulsed buzzer (fault tone) a system fault has occurred and the affected board has recovered. The indication will remain until the panel is reset.
Page 62
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
60
SERVICE & MAINTENANCE
Your Fire Alarm System is working 24 hours a day, 365 days a year. The detectors and control & indicating panel are operating continuously and the fi re alarm circuits are constantly monitored.
Legislation such as the Regulatory Reform (Fire Safety) Order 2005 and other legislation protecting both employees and the public require premises operators to conform with standards for Fire Alarm Systems.
It is a requirement of BS 5839 Part 1 that the system is subject to periodic inspection and servicing so that faults are identifi ed, preventive measures can be taken to ensure the continued reliability of the system, false alarm problems are identifi ed and suitably addressed, and the user is made aware of any changes to the building that affect the protection afforded by the system.
The inspection and servicing recommendations in this clause should be carried out by a competent person. A ‘Competent Person’ is a person or fi re alarm servicing organisation with specialist knowledge of fi re detection and fi re alarm systems, including knowledge of the causes of false alarms, suffi cient information regarding the system, and adequate access to spares.
The period between successive inspection and servicing visits should be based upon a risk assessment, taking into account the type of system installed, the environment in which it operates and other factors that may affect the long term operation of the system. The recommended period between successive inspection and servicing visits should not exceed six months. If this recommendation is not implemented, it should be considered that the system is no longer compliant with this part of BS 5839
THE NEED FOR MAINTENANCE
ROUTINE MAINTENANCE & TESTING
DUTIES OF THE RESPONSIBLE PERSON
The system user needs to appoint a single, named member of the premises management to supervise all matters pertaining to the fi re detection and fi re alarm system. The role of this person is to ensure that the system is tested and maintained in accordance with the recommendations of BS 5839 Part 1, that appropriate records are kept and that relevant occupants in the protected premises are aware of their roles and responsibilities in connection with the fi re detection and fi re alarm system.
This person also needs to ensure that necessary steps are taken to avoid situations that are detrimental to the standard of protection afforded by the system and to ensure that the level of false alarms is minimized.
DAILY
The ‘Responsible Person’ should check the control panel to make sure no faults or pre-alarm conditions are indicated and that the green ‘Supply Healthy’ lamp is lit.
WEEKLY
The Fire Alarm System should be tested on a weekly basis as recommended in BS5839 Part 1 clause 44.2.
Every week a manual call point should be operated during normal working hours. The weekly test should be carried out at approximately the same time each week. Instructions to the occupants should be that they report any instance of poor audibility of the fi re alarm signal.
A different manual call point should be used at the time of every weekly test so that all manual call points in the building are tested in rotation over a prolonged period.
The result of the weekly test and the identity or location of the manual call point used should be recorded in the system log book.
The following section is a summary of the requirements in BS5839 Part 1
For comprehensive information a copy of BS5839 Part 1 can be purchased from the British Standards Institution via their web site at www.bsi-global.com.
Page 63
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
61
SERVICE & MAINTENANCE
WEEKLY TEST
The call point test key should be inserted fi rmly and deliberately into the bottom of the manual call point. Once activated it may be necessary to wait up to four seconds before the alarms sound.
Your manual call points may not be the same as the ones described above. If not please refer to your service and maintenance company for instructions.
Note:
Before testing the fi re alarm system it may be necessary to isolate ancillary outputs.
It is essential that any alarm receiving centre is contacted immediately before and immediately after, the weekly test to ensure that unwanted alarms are avoided and that fi re alarm signals are correctly received at the alarm receiving centre.
PERIODIC INSPECTION & SERVICING
Inspection & servicing should only be carried out by a ‘Competent Person’ who has suffi cient knowledge to check the whole system. This would normally be a qualifi ed electrical contractor or fi re alarm specialist.
Inspection & servicing visits are normally conducted on a quarterly basis unless such factors as a dirty environment warrant servicing on a more regular basis. The maximum period between inspections must not exceed six months.
Recommendations of BS5839-1 for periodic service visits include:
Every device on the system should be tested annually. The testing of each device can be split between periodic visits but with a minimum of one detector or call point tested on each circuit, per visit.
On each visit the ‘Competent Person’ should check the record of false alarms. Any persistent occurrence should be investigated and corrective action taken as appropriate.
Battery and connections should be examined and load tested to check serviceable condition and that they are not likely to fail before the next service visit.
All other devices and control & indicating equipment should be checked for correct operation and any faults should be recorded and rectifi ed.
Details of the service visit must be recorded in the log book
EVERY FOUR YEARS
Renew the sealed lead acid batteries and record the fact in the log book
Page 64
DDATE &
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
62
Page 65
DDATE &
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
63
Page 66
DDATE &
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
64
Page 67
DDATE &
DEVICE TESTED &
LOCATION
COMMENTS
(IF ANY)
INITIALS OF
TESTER
TIME OF TEST
SCHEDULE OF TESTING
This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
65
Page 68
FALSE ALARMS, FAULTS & ENGINEERS VISITS
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
66
Fault/Reason For
Call-Out
Action Taken Date Work Completed Engineer’s Details
Page 69
FALSE ALARMS, FAULTS & ENGINEERS VISITS
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
67
Fault/Reason For
Call-Out
Action Taken Date Work Completed Engineer’s Details
Page 70
FALSE ALARMS, FAULTS & ENGINEERS VISITS
Excel-EN Installation, Commissioning & Operating Manual Approved Document Ref: UI-XLEN-01 Issue 7.0
68
Fault/Reason For
Call-Out
Action Taken Date Work Completed Engineer’s Details
Page 71
USER INSTRUCTIONS
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
RESOUND SILENCE RESET
ENTER
1234
Disable
Mode
Tes t
Mode
Mute
Buzzer
Tes t
Lamps
If an alarm condition is present YOU MUST FOLLOW YOUR NORMAL FIRE DRILL PROCEDURES.
A responsible person should then:-
1.
1.
Check the control panel to see which area or zone has caused the system to go into alarm. This
Check the control panel to see which area or zone has caused the system to go into alarm. This
will be indicated by a pulsing red LED on the front of the control panel.
will be indicated by a pulsing red LED on the front of the control panel.
2.
2.
Go to the area which has caused the alarm to check if a fi re exists.
Go to the area which has caused the alarm to check if a fi re exists.
3.
3.
Only when it is safe to do so should the alarms be silenced. Activate the controls by turning the
Only when it is safe to do so should the alarms be silenced. Activate the controls by turning the
key switch or by entering the four digit code (see Activate Controls in the OPERATING section)
key switch or by entering the four digit code (see Activate Controls in the OPERATING section)
and press the (blue) SILENCE ALARMS button (fi g 1). To sound the alarms again press the (red)
and press the (blue) SILENCE ALARMS button (fi g 1). To sound the alarms again press the (red)
RESOUND button (fi g 2).
RESOUND button (fi g 2).
4.
4.
In the event of a false alarm look for the device that has caused the alarm. A detector will have a
In the event of a false alarm look for the device that has caused the alarm. A detector will have a
red LED lit, or check to see if a call point glass is broken (if so replace the glass or call an engineer).
red LED lit, or check to see if a call point glass is broken (if so replace the glass or call an engineer).
5.
5.
When fully satisfi ed that there is no fi re, return to the control panel and press the (green) RESET
When fully satisfi ed that there is no fi re, return to the control panel and press the (green) RESET
button, (fi g 3). The panel display should return to normal and only the green SUPPLY HEALTHY
button, (fi g 3). The panel display should return to normal and only the green SUPPLY HEALTHY
LED should be lit on the control panel.
LED should be lit on the control panel.
g 1 g 2
g 3
If the system continues to false alarm, call an engineer
If the system continues to false alarm, call an engineer
Fault Condition
Fault Condition
If a buzzer is sounding in the control panel but the sounders or bells are not ringing, then there is either a
If a buzzer is sounding in the control panel but the sounders or bells are not ringing, then there is either a
fault on the system, or zones / sounders have been disabled. CALL AN ENGINEER
fault on the system, or zones / sounders have been disabled. CALL AN ENGINEER
The internal fault buzzer can be silenced by pressing MUTE BUZZER (button 3 on the keypad). DO
The internal fault buzzer can be silenced by pressing MUTE BUZZER (button 3 on the keypad). DO
NOT RESET THE SYSTEM UNTIL AN ENGINEER HAS INVESTIGATED THE FAULT.
NOT RESET THE SYSTEM UNTIL AN ENGINEER HAS INVESTIGATED THE FAULT.
Tear Here
Page 72
www.haes-systems.com
Loading...