Hach-Lange WTOS P-RTC User Manual

Page 1
DOC023.52.90202

RTC101 P-Module

Real-Time Control System for Phosphorus Removal

User manual
02/2013, edition 4A
© HACH-LANGE GmbH, 2010, 2011,2013 All rights reserved. Printed in Germany.
Page 2
Page 3
Table of Contents
Section 2 General Information............................................................................................................... 7
2.1 Safety information............................................................................................................................... 7
2.2 Areas of application ............................................................................................................................ 8
2.3 Functional principle............................................................................................................................. 8
2.4 Scope of delivery ................................................................................................................................ 9
2.5 Instrument overview.......................................................................................................................... 10
Section 3 Installation............................................................................................................................ 13
3.1 RTC101 P-Module connection.......................................................................................................... 13
3.2 Dosing pump connection .................................................................................................................. 13
3.3 PHOSPHAX sc analyzer connection ................................................................................................ 13
3.4 sc1000 controller connection ............................................................................................................ 14
3.5 Flow rate signal connection .............................................................................................................. 14
3.6 Connection to the automation unit on the plant side.........................................................................14
Section 4 Parameterization and operation ......................................................................................... 15
4.1 Open-loop control and closed-loop control programs....................................................................... 15
4.2 Program change ............................................................................................................................... 16
4.3 Parameterization on the sc1000....................................................................................................... 18
4.4 Select sensors .................................................................................................................................. 29
4.5 Explanations ..................................................................................................................................... 31
Section 5 Maintenance ......................................................................................................................... 37
5.1 Maintenance schedule...................................................................................................................... 37
Section 6 Troubleshooting................................................................................................................... 39
6.1 Error messages ................................................................................................................................ 39
6.2 Warnings........................................................................................................................................... 39
6.3 Wear parts ........................................................................................................................................ 39
Section 7 Replacement parts and accessories ................................................................................. 41
7.1 Spare parts ....................................................................................................................................... 41
Section 8 Contact information ............................................................................................................ 43
Section 9 Warranty and liability........................................................................................................... 45
Appendix A MODBUS address setting ............................................................................................... 47
3
Page 4
Table of Contents
4
Page 5

Section 1 Specifications

Subject to change without notice.
Industrial Personal Computer (IPC), (Embedded PC)
Processor
Flash memory 2 GB compact flash card
Internal working memory 256 MB DDR-RAM (not expandable)
Interface RJ 45 (Ethernet), 10/100 MBit/s
Diagnostic LEDs Power, LAN speed, LAN activity, TC status, flash access
Expansion slot Compact flash type II slot with ejection mechanism
Clock
Operating system Microsoft Windows
Control software TwinCAT PLC Runtime or TwinCAT NC PTP Runtime
System bus 16 Bit ISA (PC/104 standard)
Power supply Via system bus (through power supply module CX1100-0002)
Max. power loss 6 W (including the system interfaces CX1010-N0xx)
Analog input 4–20 mA for flow rate measurement
Internal resistance 80 Ohm × diode voltage 0.7 V
Signal current 0–20 mA
Pentium®1, MMX compatible, 500 MHz clock rate
Internal, battery-buffered clock for time and date (battery can be replaced)
®2
CE or Microsoft Windows Embedded Standard
Common mode voltage (U
Measurement error (for entire measurement range)
Electrical surge resistance 35 VDC
Electrical isolation 500 V
Analog output 4–20 mA for dosing pump
Number of outputs 1
Power supply
Signal current 0–20 mA
Working resistance < 500
Measurement error
Resolution 12 bit
Conversion time ~ 1.5 ms
Electrical isolation 500 V
) 35 V max.
CM
< ± 0.3 % (from measurement range end value)
24 V DC via power contacts (alternatively 15 V DC with bus terminal KL9515)
± 0.5 LSB linearity error ± 0.5 LSB offset error ± 0.1, % (relative to the measuring range end value)
(K-bus/signal voltage)
eff
(K-bus/signal voltage)
eff
5
Page 6
Specifications
Digital outputs
1-channel: 1 × for dosing pump and 1 × alarm 2-channel: 2 × for dosing pump and 1 × alarm
Nominal load voltage 24 VDC (–15 % / +20 %)
Load type Ohmic, inductive, lamp load
Max. output current 0.5 A (short-circuit proof) per channel
Short-circuit current 0.7 to 1.7 A
Reverse polarity protection Yes
Electrical isolation 500 V
(K-bus/field voltage)
eff
Power contact current consumption 20 mA typ. (for typ. 30 mA 2-channel device)
Equipment properties
Dimensions (L × W × H)
350 mm × 120 mm × 96 mm (13.78 in. × 4.72 in. × 3.78 in.)
Mass approx. 0.9 kg
Environmental conditions
Working temperature 0 to 50 °C (32 to 122 °F)
Storage temperature –25 to +85 °C (–13 to 185 °F)
Relative humidity 95 %, non-condensing
Miscellaneous
Pollution Degree Protection Class Installation Category Maximum Altitude
2 1 II 2000 m (6.562 ft.)
Protection class IP20
Installation DIN rail EN 50022 35 × 15
1
Pentium is a registered trademark of the Intel Corporation.
2
Microsoft Windows is a brand name for operating systems of the Microsoft Corporation.
6
Page 7

Section 2 General Information

2.1 Safety information

Please read this entire manual before unpacking, setting up, or operating this equipment. Pay attention to all danger and caution statements. Failure to do so could result in serious injury to the operator or damage to the equipment.
To prevent damage to or impairment of the device's protection equipment, the device may only be used or installed as described in this manual.

2.1.1 Use of hazard information

DANGER
Indicates a potentially or imminently hazardous situation that, if not avoided, can result in death or serious injury.
WARNING
Indicates a potentially or imminently dangerous situation that, if it is not avoided, can lead to death or to serious injuries.
CAUTION
Indicates a possible dangerous situation that can have minor or moderate injuries as the result.
Indicates a situation that, if it is not avoided, can lead to damage to the device. Information that requires special emphasis.
Note: Information that supplements points in the main text.

2.1.2 Warning signs

Read all labels and tags attached to the instrument. Non-observance may result in personal injury or damage to the equipment..
This symbol is a warning triangle. Follow all safety notes that follow this symbol to prevent possible injuries. If this symbol is located on the device, it refers to information in the operating and/or safety notes of the user manual.
This symbol can be attached to a housing or a barrier in the product and shows that electric shock risk and/or the risk of a death through electric shock exists.
Electrical equipment marked with this symbol may not be disposed of in European domestic or public disposal systems after 12 August 2005. In conformity with local and national regulations, European electrical equipment users must now return old or end-of life equipment to the manufacturer for disposal at no charge to the user.
Note: You obtain instructions on the correct disposal of all (marked and not marked) electrical products that were supplied or manufactured by Hach-Lange at your relevant Hach-Lange sales office.
NOTICE
7
Page 8
General Information

2.2 Areas of application

The RTC101 P-Module is a universal open-loop control and closed-loop control unit in waste water treatment plants for automatic precipitant metering for phosphate precipitation.
Depending on the operating situation, the precipitant dosage can be based on measured values in the influent or effluent or based on profiles. The system automatically selects the best possible strategy. The user is able to make restrictions manually.
The use of an RTC Module does not release the operator from the duty of care to the system. No guarantees as to the functionality or operational safety of the system.
In particular, the operator must make sure that instruments connected to the RTC open/closed-loop controller are always fully functional.
To make sure these instruments supply correct, reliable measurement values, regular maintenance work (for example, cleaning of the sensor and laboratory comparative measurements) is essential! (Refer to the user manual for the relevant instrument.)

2.3 Functional principle

In the following, a distinction is made between the open-loop control and the closed-loop control of the precipitant concentration.
NOTICE
For the open-loop control of the precipitant dosing, the measuring point for the phosphate concentration is upstream of the precipitant dosing point.
For the closed-loop control of the precipitant dosing, the measuring point for the phosphate concentration is downstream of the precipitant dosing point.
The measuring point for the flow rate is usually located in the influent of the waste water treatment plant. At the measuring point, the actual flow rate (influent quantity and recirculation - e.g. RAS, MLR, etc) is determined via further entries in the RTC module.
If the measured values for the flow rate quantity and/or phosphate concentration are temporarily not available (e.g. due to a malfunction), the system automatically refers back to saved profiles.
Connect the following input signals on the control unit in order to make optimum use of all system functions:
Flow rate, measurement signal 4–20 mA
Fault indicator signal of the flow rate measurement (230 V AC or 24 V DC)
In the event that measured value failures are not signaled according to NAMUR 43, as the values are below the 4
Note: If these signals are not available, the equipment operates with limited functionality.
sc1000 controller with PO4P PHOSPHAX sc analyzer. The measured value is adopted directly.
Dosing pump for the precipitant The dosing pump is continuously actuated via a 0–20 mA or 4–20 mA current loop signal as well as via a changeover contact. If the dosing rate is below the minimum precipitant flow rate of the pump, the system automatically switches to pulse/pause mode.
mA threshold.
8
Page 9

2.4 Scope of delivery

Each RTC101 P-Module is supplied with:
SUB-D connector (9 pin)
Ferrite core, folding
Manual
Check that the order is complete. If anything is missing or damaged, please contact the manufacturer or distributor.
The combination of pre-assembled components supplied by the manufacturer does not represent a standalone functional unit. In accordance with EU guidelines, this combination of pre-assembled components is not supplied with a CE mark, and there is no EU declaration of conformity for the combination.
However, the conformity of the combination of components with the guidelines can be proved through technical measurements.
General Information
NOTICE
9
Page 10
General Information

2.5 Instrument overview

Figure1 Base module RTC 24 V version .
1 PE (protective earth) 5 sc 1000 connection: RS485 (CX1010-N031) 2 24 V 6 Battery compartment 3 0 V 7 CPU base module, consisting of Ethernet port with
battery compartment (CX1010-N000), CPU module with CF card (CX1010-0021) and passive aeration element.
4 Automatic circuit breaker (ON/OFF switch for item 7 and
8 without fuse function).
Note: All components are pre-wired.
8 Power supply module, consisting of bus coupler
(CX1100-0002) and terminal module 24V.
10
Page 11
Abbildung 2 Base module RTC 100-240 V version
General Information
1 L(+) 7 Automatic circuit breaker (ON/OFF switch for item 10
and 11 without fuse function).
2 N(–) 8 sc 1000 connection: RS485 (CX1010-N041) 3 Input AC 100–240 V / Input DC 95 V–250 V 9 Battery compartment 4 PE (protective earth) 10 CPU base module, consisting of Ethernet port with
battery compartment (CX1010-N000), CPU module with CF card (CX1010-0021) and passive aeration element.
5 24 V transformer (Specification Section 3.1.1, page 13) 11 Power supply module, consisting of bus coupler 6 Output DC 24 V, 0,75 A
(CX1100-0002) and terminal module 24V.
Note: All components are pre-wired.
11
Page 12
General Information
12
Page 13

Section 3 Installation

Only qualified experts may perform the tasks described in this section of the manual, while adhering to all locally valid safety regulations.
Always lay cables and hoses so that they are straight and do not pose a tripping hazard.
Before the power supply is switched on, refer to the instructions in the relevant manuals!

3.1 RTC101 P-Module connection

The RTC module must be installed on a DIN rail/standard rail.
Install the module horizontally, with at least 30 mm clearance at the top and bottom, in order to guarantee the functionality of the passive ventilation element. The RTC module is operated solely via the sc1000 controller (see sc1000 controller operating instructions).
When used indoors, the RTC module can be installed in a control cabinet. When used outdoors, the RTC module requires its own housing that follows the technical specifications.
DANGER
CAUTION
CAUTION

3.1.1 Power supply to the RTC module

Alternating current may destroy the direct current system and therefore jeopardize user safety. Never connect an alternating current voltage to the 24 V direct current model.
Table1 Supply voltage of the RTC Module
Voltage 24 V DC (–15 % / +20 %), max. 25 W
Recommended fuse C2
With 110–230 V option 110–230 VAC, 50-60 Hz, approximately 25 VA
Note: An external deactivation switch is recommended for all installations.

3.2 Dosing pump connection

There are two connections for the dosing pump:
Current loop signal 0/4 to 20 mA for analog actuation of pumps with frequency converters.
24 V output for the actuation of pumps without frequency converters or below the analog adjustment range in pulse/pause mode.
Note: It must also be possible to switch the pump off via the digital output in the case of analog actuation!
WARNING

3.3 PHOSPHAX sc analyzer connection

The measuring signal of the PHOSPHAX sc analyzer is transmitted to the RTC101 P-Module from the sc-system via the RTC communication card.
Previous designs of the analyzer (e.g. PHOSPHAX inter) can be connected to an analog input card (YAB018).
13
Page 14
Installation

3.3.1 PHOSPHAX sc analyzer power supply

Refer to the PHOSPHAX sc manual.

3.4 sc1000 controller connection

Connect the SUB-D plug supplied to a dual-core, sheathed data cable (signal or bus cable). For further information regarding the data cable connection, refer to the enclosed assembly instructions.

3.5 Flow rate signal connection

If a flow rate measurement signal of 4 to 20 mA is available, connect it to the analog input of the RTC module.

3.6 Connection to the automation unit on the plant side

Depending on the variant and option, the RTC101 P-Module is equipped with various components that must be connected to the plant's automation unit.
The volumetric flow rate is provided to the RTC module as a 0/4 to 20 mA signal for all variants and options.
The precipitant volume to be metered is delivered by the RTC module as a 0/4 to 20
mA signal for all variants and options. Alternatively, the precipitant volume can also be output by the fieldbus variants provided by the sc1000 (see sc1000 operating instructions).
The RTC module supplies the digital output signal for activating the precipitant pump at 0
V or 24 V.
The RTC module supplies a collective fault message at 0 V (fault) or 24 V (device functional).
Table 2 Signal allocation of individual components of the RTC module
RTC module options
Component Name Connection Signal Function 1-channel 2-channel
1
1
KL2032
KL2134
2-fold digital output
4-fold digital output
Single analog output KL4011 1(+) 3(-) +24 V/0 V Precipitant pump dosing rate X
2-fold analog output KL4012
1-fold analog input KL3011 1(+) – 2(-) 0/4 to 20 mA Feed volume flow Channel 1 X X 2-fold analog input KL3011 1(+) – 2(-) 0/4 to 20 mA Feed volume flow Channel 2 X
1
Ground to connections 3 and 7 or equal to voltage supply
1 +24 V/0 V Precipitant pump on/off X 5 +24 V/0 V No fault/fault X 1 +24 V/0 V Precipitant pump 1 on/off X 5 +24 V/0 V No fault/fault in channel 1 X 4 +24 V/0 V Precipitant pump 2 on/off X 8 +24 V/0 V No fault/fault in channel 2 X
1(+) 3(-) +24 V/0 V Precipitant pump 1 dosing rate X 5(+) 7(-) +24 V/0 V Precipitant pump 2 dosing rate X
14
Page 15

Section 4 Parameterization and operation

4.1 Open-loop control and closed-loop control programs

Four different programs are provided to enable optimal adaptation to local conditions and to the available measurement signals.
Programs 3 and 4 have various functions depending on whether open-loop control or closed-loop control is selected.

4.1.1 Open-loop control

For the open-loop control of precipitant dosing, the measuring point for phosphate concentration is upstream of the precipitant dosing point.
4.1.1.1 Open-loop control according to phosphate concentration profiles
Program 1
Load-proportional open-loop control:
Specified profile of the phosphate concentration in the reactor inlet
Specified profile for the flow rate
Program 2
Load-proportional open-loop control:
Specified profile of the phosphate concentration in the reactor inlet
Flow rate measured value
Note: The prerequisite for this program is that the flow rate measurement signal is valid. "Valid" means that the signal is present at the relevant input.
4.1.1.2 Open-loop control according to measured phosphate values
Program 3
Load-proportional open-loop control:
Measured value of the phosphate concentration in the reactor inlet
Specified profile for the flow rate
Note: The prerequisite for this program is that the PO4-P measurement signal is valid. "Valid" means that the signal is present at the relevant input.
Program 4
Load-proportional open-loop control:
Measured value of the phosphate concentration in the reactor inlet
Flow rate measurement
Note: The prerequisite for this program is that both measurement signals are valid. "Valid" means that the signal is present at the relevant input.
15
Page 16
Parameterization and operation

4.1.2 Closed-loop control according to measured phosphate values

For the closed-loop control of the precipitant dosing, the measuring point for the phosphate concentration is downstream of the precipitant dosing point.
Program 3
Closed-loop control:
Measured value of the phosphate concentration in the reactor outlet
Specified profile for the flow rate (can be deactivated)
Note: The prerequisite for this program is that the PO4-P measurement signal is valid. "Valid" means that the signal is present at the relevant input.
Program 4
Load-proportional closed-loop control:
Measured value of the phosphate concentration in the reactor inlet

4.2 Program change

4.2.1 Automatic program change

Flow rate measurement
Note: The prerequisite for this program is that both measurement signals are valid. "Valid" means that the signal is present at the relevant input.
If a measurement signal drops out, an automatic program change occurs and the system refers to the specified profile. The program selection can be limited manually. The change between programs occurs with a 5 minute delay, whereby the last manipulated value set for the dosing is retained at the output.
16
Page 17
Figure 3 Program change
Q/PO4-P
Program 4
Q profile/PO
4
-P
Program 3
Q profile/PO
4
-P profile
Program 1
Q/PO
4
-P profile
Program 2
Parameterization and operation

4.2.2 Manual pre-selection

Pre-selection 1: Always Program 1
Pre-selection 2:
Pre-selection 3:
Open-loop control:
Closed-loop control:
Program 2 On signal drop out Program 1
Program 3 On signal drop out Program 2 if possible
Program 3 Otherwise program 1

4.2.3 CF card configuration

If both measurement signals become invalid at the same time, the system switches between programs 4 and 1 without intermediate stages.
Manual pre-selection limits the selection of programs.
NOTICE
Never remove the CF card from the RTC module during operation! This can damage the instrument!
The function of the RTC101 P-Module, i.e. control/regulation, is indicated on the CF card. If this setting is to be changed, please contact the manufacturer's service department (Section 8).
17
Page 18
Parameterization and operation

4.3 Parameterization on the sc1000

4.3.1 User interfaces and navigation

Before the system is used, the user must be familiar with the sc controller functions. Learn how to navigate through the menu and perform the relevant functions.

4.3.2 System setup

1. Open the MAIN MENU.
2. Select RTC MODULE / PROGNOSYS and confirm.
3. Select the RTC MODULE menu and confirm.
4. Select the RTC module and confirm.
18
Page 19

4.3.3 1-channel open-loop control

1-channel open-loop control
CONFIGURE
Parameterization and operation
SELECT SENSOR
OPEN-LOOP
PRECIP. TYPE Precipitation, simultaneous precipitation, post-precipitation
SETPOINT PO4-P Desired orthophosphate value in effluent (refer to 4.5.1, page 31) [mg/L]
CORR FACTOR Percentage correction of precipitant dosing (see 4.5.2, page 31) [%]
BIO-P Phosphate biologically eliminated after influent (refer to 4.5.3, page 31) [%]
MIN DOS RATE Minimum flow rate of dosing pump [L/h]
PRESELECT PROG Programs 1 to 4 (refer to 4.1, page 15) PROFILE Active when a measurement signal fails
Q-PROFILE
P-PROFILE Daily profiles for PO4-P concentrations, 2 h average (see 4.5.4, page 32) [mg/L]
WEEK PROFILE
IN- OUTPUTS
DOSING PUMP
MIN PUMP RANGE Lower threshold of flow rate range [L/h]
Select the sensor installed for the open-loop control (see Section 4.4, page 29).
Daily profiles (2 h average) of waste water influent according to feed measurement signal
Percentage daily averages of the phosphate load (refer to 4.5.4, page 32) (volume × concentration)
[m³/h]
[%]
MAX PUMP RANGE Upper threshold of flow rate range [L/h]
0/4...20MA Selection of transfer range according to pump input
CONTROL CYCLE Control cycle comprising on- and off-time (see 4.5.6, page 33) [s]
MIN RUNTIME Minimum on-time of pump (refer to 4.5.6, page 33) [s]
FLOW RATE
MIN Q-INFLUENT Minimum flow rate in inlet according to measurement signal [m³/h]
MAX Q-INFLUENT Maximum flow rate in inlet according to measurement signal [m³/h]
0/4...20MA Transfer range of 0/4–20 mA current loop, as set in the connected flow measuring instrument
MIN RET SLUDGE Minimum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
MAX RET SLUDGE Maximum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
Ratio between measured flow rate and return activated sludge volume, for a return
Q RET RATIO
Q INFL SMOOTH Smoothing of influent signal (refer to 4.5.7, page 34)
activated sludge volume proportional to the measured flow rate (refer to 4.5.7,
page 34)
[%]
19
Page 20
Parameterization and operation
1-channel open-loop control
CONFIGURE (CONTINUE)
PRECIPITANT
METAL CONTENT Metal concentration in precipitant (refer to 4.5.8, page 35) [g/L]
ATOMIC WEIGHT Relative atomic weight of active precipitant substance (refer to 4.5.8, page 35) [g/mol]
MODBUS
Start address of an RTC module within the MODBUS network. Default is 41. This
ADDRESS
DATA ORDER
DATALOG INTRVL Indicates the interval in which the data is saved in the log file [min]
MAINTENANCE
RTC DATA
RTC MEASUREMEN Displays up to 5 measured values; additional values can be selected by scrolling
RTC ACTUAT VAR Displays up to 5 actuating variables; additional variables can be selected by scrolling
setting must only be changed by the manufacturer's service department (Section 8). (Refer to Appendix A, page 47)
Specifies the register order within a double word. Default is NORMAL. This setting must only be changed by the manufacturer's service department (Refer to Section 8)
DIAG/TEST
EEPROM Hardware test
RTC COMM TO Communication time-out
RTC CRC Communication checksum
LOCATION
SOFTWARE VERSION Version number for service
RTC MODE Indicates the mode set in the RTC module.
A location name can be issued here for better identification of the RTC module e.g. activation
2

4.3.4 2-channel open-loop control

In addition to the 1-channel version, a 2-channel version is also available. The 2-channel version is able to control 2 phosphate precipitants separately.
All of the key parameters appear twice and are identified as channel 1 and channel 2.
In contrast to the 1-channel version, a percentage factor for distribution of the profile ( measurement signals drop out, the percentage factor
PROFILE
distributes the influent waste water to the precipitant.
DIST PROFILE) has been added. If
DIST
20
Page 21
Parameterization and operation
2-channel open-loop control
CONFIGURE
SELECT SENSOR Select the sensors installed for the open-loop control (see Section 4.4, page 29).
OPEN-LOOP
PRECIP. TYPE Precipitation, simultaneous precipitation, post-precipitation
CHANNEL 1
SETPOINT PO4-P Desired orthophosphate value in effluent (refer to 4.5.1, page 31) [mg/L]
CORR FACTOR Percentage correction of precipitant dosing (see 4.5.2, page 31) [%]
BIO-P Phosphate biologically eliminated after influent (refer to 4.5.3, page 31) [%]
MIN DOS RATE Minimum flow rate of dosing pump [L/h]
PRESELECT PROG Programs 1 to 4 (refer to 4.1, page 15)
CHANNEL 2
SETPOINT PO4-P Desired orthophosphate value in effluent (refer to 4.5.1, page 31) [mg/L]
CORR FACTOR Percentage correction of precipitant dosing (see 4.5.2, page 31) [%]
BIO-P Phosphate biologically eliminated after influent (refer to 4.5.3, page 31) [%]
MIN DOS RATE Minimum flow rate of dosing pump [L/h]
PRESELECT PROG Programs 1 to 4 (refer to 4.1, page 15)
PROFILE Active when a measurement signal fails
Q-PROFILE
DIST PROFILE Percentage distribution of flow rate; input refers to channel 1. [%]
P-PROFILE Daily profiles of PO
WEEK PROFILE Percentage daily averages of the phosphate load (refer to4.5.4, page 32) [%]
IN- OUTPUTS
DOSING PUMP
CHANNEL 1
MIN PUMP RANGE Lower threshold of flow rate range [L/h]
MAX PUMP RANGE Upper threshold of flow rate range [L/h]
0/4...20MA Selection of transfer range according to pump input
CONTROL CYCLE Control cycle comprising on- and off-time (see 4.5.6, page 33)[s]
MIN RUNTIME Minimum on-time of pump (refer to 4.5.6, page 33) [s]
Daily profiles (2 h average) of waste water influent according to feed measurement signal
-P concentrations, 2 h average (see 4.5.4, page 32) [mg/L]
4
[m³/h]
21
Page 22
Parameterization and operation
2-channel open-loop control
CONFIGURE (CONTINUE)
CHANNEL 2
MIN PUMP RANGE Lower threshold of flow rate range [L/h]
MAX PUMP RANGE Upper threshold of flow rate range [L/h]
0/4...20MA Selection of transfer range according to pump input
CONTROL CYCLE Control cycle comprising on- and off-time (see 4.5.6, page 33)[s]
MIN RUNTIME Minimum on-time of pump (refer to 4.5.6, page 33) [s]
FLOW RATE
CHANNEL 1
MIN Q-INFLUENT Minimum flow rate in inlet according to measurement signal [m³/h]
MAX Q-INFLUENT Maximum flow rate in inlet according to measurement signal [m³/h]
0/4...20MA
MIN RET SLUDGE Minimum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
Transfer range of 0/4–20 mA current loop, as set in the connected flow measuring instrument.
MAX RET SLUDGE Maximum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
Ratio between measured flow rate and return activated sludge volume, for a return
Q RET RATIO
Q INFL SMOOTH Smoothing of influent signal (refer to 4.5.7, page 34)
CHANNEL 2
MIN Q-INFLUENT Minimum flow rate in inlet according to measurement signal [m³/h]
MAX Q-INFLUENT Maximum flow rate in inlet according to measurement signal [m³/h]
0/4...20MA
MIN RET SLUDGE Minimum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
MAX RET SLUDGE Maximum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
Q RET RATIO
Q INFL SMOOTH Smoothing of influent signal (refer to 4.5.7, page 34)
activated sludge volume proportional to the measured flow rate (Refer to 4.5.7,
page 34)
Transfer range of 0/4–20 mA current loop, as set in the connected flow measuring instrument.
Ratio between measured flow rate and return activated sludge volume, for a return activated sludge volume proportional to the measured flow rate (Refer to 4.5.7,
page 34)
[%]
[%]
22
Page 23
Parameterization and operation
2-channel open-loop control
CONFIGURE (CONTINUE)
PRECIPITANT
CHANNEL 1
METAL CONTENT Metal concentration in precipitant (refer to 4.5.8, page 35) [g/L]
ATOMIC WEIGHT Relative atomic weight of active precipitant substance (refer to 4.5.8, page 35) [g/mol]
CHANNEL 2
METAL CONTENT Metal concentration in precipitant (refer to 4.5.8, page 35) [g/L]
ATOMIC WEIGHT Relative atomic weight of active precipitant substance (refer to 4.5.8, page 35) [g/mol]
MODBUS
Start address of an RTC module within the MODBUS network. Default is 41. This
ADDRESS
DATA ORDER
DATALOG INTRVL Indicates the interval in which the data is saved in the log file. [min]
setting must only be changed by the manufacturer's service department (Section 8). (Refer to Appendix A, page 47)
Specifies the register order within a double word. Default is NORMAL. This setting must only be changed by the manufacturer's service department (Refer to
Section 8)
MAINTENANCE
RTC DATA
RTC MEASUREMEN Displays up to 5 measured values; additional values can be selected by scrolling.
RTC ACTUAT VAR
DIAG/TEST
EEPROM Hardware test
RTC COMM TO Communication time-out
RTC CRC Communication checksum
LOCATION
SOFTWARE VERSION Version number for service
RTC MODE Indicates the mode set in the RTC module.
Displays up to 5 actuating variables; additional variables can be selected by scrolling.
A location name can be assigned here for better identification of the RTC module, e.g. activation 2.
23
Page 24
Parameterization and operation

4.3.5 1-channel closed-loop control

1-channel closed-loop control
CONFIGURE
SELECT SENSOR
CLOSED-LOOP
SETPOINT PO4-P Desired orthophosphate value in effluent (refer to 4.5.1, page 31) [mg/L]
GAIN P CONTR. Proportional gain of the closed-loop control (refer to 4.5.5, page 32)
INTEGRALTIME Integral time of closed-loop control (refer to 4.5.5, page 32) [min]
DERIVATIVE TIME Derivative time of closed-loop control (refer to 4.5.5, page 32) [min]
MIN DOS RATE Minimum flow rate of dosing pump [L/h]
PRESELECT PROG Programs 1 to 4 (refer to 4.1, page 15) PROFILE Active when a measurement signal fails
Q-PROFILE
P-PROFILE Daily profiles of PO4-P concentrations, 2 h average (see 4.5.4, page 32) [mg/L]
WEEK PROFILE Percentage daily averages of the phosphate load (refer to 4.5.4, page 32) [%]
IN- OUTPUTS
DOSING PUMP
MIN PUMP RANGE Lower threshold of flow rate range [L/h]
Select the sensor installed for the closed-loop control (refer to Section 4.4, page 29).
Daily profiles (2 h average) of waste water influent according to feed measurement signal
[m³/h]
MAX PUMP RANGE Upper threshold of flow rate range [L/h]
0/4...20MA Selection of transfer range according to pump input
CONTROL CYCLE Control cycle comprising on- and off-time (see 4.5.6, page 33) [s]
MIN RUNTIME Minimum on-time of pump (refer to 4.5.6, page 33) [s]
FLOW RATE
MIN Q-INFLUENT Minimum flow rate in inlet according to measurement signal [m³/h]
MAX Q-INFLUENT Maximum flow rate in inlet according to measurement signal [m³/h]
0/4...20MA Transfer range of 0/4–20 mA current loop, as set in the connected flow measuring instrument.
MIN RET SLUDGE Minimum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
MAX RET SLUDGE Maximum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
Ratio between measured flow rate and return activated sludge volume, for a return
Q RET RATIO
Q INFL SMOOTH Smoothing of influent signal (refer to 4.5.7, page 34)
activated sludge volume proportional to the measured flow rate (Refer to
page 34)
4.5.7,
[%]
24
Page 25
Parameterization and operation
1-channel closed-loop control
CONFIGURE (CONTINUE)
PRECIPITANT
METAL CONTENT Metal concentration in precipitant (refer to 4.5.8, page 35) [g/L]
ATOMIC WEIGHT Relative atomic weight of active precipitant substance (refer to 4.5.8, page 35) [g/mol]
MODBUS
Start address of an RTC module within the MODBUS network. Default is 41. This
ADDRESS
DATA ORDER
DATALOG INTRVL Indicates the interval in which the data is saved in the log file. [min]
MAINTENANCE
RTC DATA
RTC MEASUREMEN Displays up to 5 measured values; additional values can be selected by scrolling.
RTC ACTUAT VAR Displays up to 5 actuating variables; additional variables can be selected by scrolling.
setting must only be changed by the manufacturer's service department (Section 8). (Refer to Appendix A, page 47)
Specifies the register order within a double word. Default is NORMAL. This setting must only be changed by the manufacturer's service department (Refer to Section 8)
DIAG/TEST
EEPROM Hardware test
RTC COMM TO Communication time-out
RTC CRC Communication checksum
LOCATION
SOFTWARE VERSION Version number for service
RTC MODE Indicates the mode set in the RTC module.
A location name can be issued here for better identification of the RTC module, e.g. activation
2.

4.3.6 2-channel closed-loop control

In addition to the 1-channel version, a 2-channel version is also available, which enables separate closed-loop control of two phosphate precipitants.
All of the key parameters appear twice and are identified as channel 1 and channel 2.
In contrast to the 1-channel version, a percentage factor for distribution of the profile ( measurement signals drop out, the percentage factor
PROFILE
distributes the influent waste water to the precipitant.
DIST PROFILE) has been added. If
DIST
25
Page 26
Parameterization and operation
2-channel closed-loop control
CONFIGURE
SELECT SENSOR Select the sensors installed for the closed-loop control (see Section 4.4, page 29).
CLOSED-LOOP
CHANNEL 1
SETPOINT PO4-P Desired orthophosphate value in effluent (refer to 4.5.1, page 31) [mg/L]
GAIN P CONTR. Proportional gain of the closed-loop control (refer to 4.5.5, page 32)
INTEGRALTIME Integral time of closed-loop control (refer to 4.5.5, page 32)[min]
DERIVATIVE TIME Derivative time of closed-loop control (refer to 4.5.5, page 32)[min]
MIN DOS RATE Minimum flow rate of dosing pump [L/h]
PRESELECT PROG Programs 1 to 4 (refer to 4.1, page 15)
CHANNEL 2
SETPOINT PO4-P Desired orthophosphate value in effluent (refer to 4.5.1, page 31) [mg/L]
GAIN P CONTR. Proportional gain of the closed-loop control (refer to 4.5.5, page 32)[%]
INTEGRALTIME Integral time of closed-loop control (refer to 4.5.5, page 32)[%]
DERIVATIVE TIME Derivative time of closed-loop control (refer to 4.5.5, page 32)
MIN DOS RATE Minimum flow rate of dosing pump [L/h]
PRESELECT PROG Programs 1 to 4 (refer to 4.1, page 15)
PROFILE Active when a measurement signal fails
Q-PROFILE
DIST PROFILE Percentage distribution of flow rate; input refers to channel 1. [%]
P-PROFILE Daily profiles of PO
WEEK PROFILE Percentage daily averages of the phosphate load (refer to4.5.4, page 32) [%]
Daily profiles (2 h average) of waste water influent according to feed measurement signal
-P concentrations, 2 h average (see 4.5.4, page 32) [mg/L]
4
[m³/h]
26
Page 27
Parameterization and operation
2-channel closed-loop control
CONFIGURE (CONTINUE)
IN- OUTPUTS
DOSING PUMP
CHANNEL 1
MIN PUMP RANGE Lower threshold of flow rate range [L/h]
MAX PUMP RANGE Upper threshold of flow rate range [L/h]
0/4...20MA Selection of transfer range according to pump input
CONTROL CYCLE Control cycle comprising on- and off-time (see 4.5.6, page 33)[s]
MIN RUNTIME Minimum on-time of pump (refer to 4.5.6, page 33) [s]
CHANNEL 2
MIN PUMP RANGE Lower threshold of flow rate range [L/h]
MAX PUMP RANGE Upper threshold of flow rate range [L/h]
0/4...20MA Selection of transfer range according to pump input
CONTROL CYCLE Control cycle comprising on- and off-time (see 4.5.6, page 33)[s]
MIN RUNTIME Minimum on-time of pump (refer to 4.5.6, page 33) [s]
FLOW RATE
CHANNEL 1
MIN Q-INFLUENT Minimum flow rate in inlet according to measurement signal [m³/h]
MAX Q-INFLUENT Maximum flow rate in inlet according to measurement signal [m³/h]
0/4...20MA Transfer range of 0/4–20 mA current loop, as set in the connected flow measuring instrument
MIN RET SLUDGE Minimum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
MAX RET SLUDGE Maximum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
Ratio between measured flow rate and return activated sludge volume, for a return
Q RET RATIO
Q INFL SMOOTH Smoothing of influent signal (refer to 4.5.7, page 34)
CHANNEL 2
MIN Q-INFLUENT Minimum flow rate in inlet according to measurement signal [m³/h]
MAX Q-INFLUENT Maximum flow rate in inlet according to measurement signal [m³/h]
0/4...20MA
activated sludge volume proportional to the measured flow rate (Refer to 4.5.7,
page 34)
Transfer range of 0/4–20 mA current loop, as set in the connected flow measuring instrument.
[%]
MIN RET SLUDGE Minimum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
MAX RET SLUDGE Maximum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
Ratio between measured flow rate and return activated sludge volume, for a return
Q RET RATIO
Q INFL SMOOTH Smoothing of influent signal (refer to 4.5.7, page 34)
activated sludge volume proportional to the measured flow rate (Refer to 4.5.7,
page 34)
[%]
27
Page 28
Parameterization and operation
2-channel closed-loop control
CONFIGURE (CONTINUE)
PRECIPITANT
CHANNEL 1
METAL CONTENT Metal concentration in precipitant (refer to 4.5.8, page 35) [g/L]
ATOMIC WEIGHT Relative atomic weight of active precipitant substance (refer to 4.5.8, page 35) [g/mol]
CHANNEL 2
METAL CONTENT Metal concentration in precipitant (refer to 4.5.8, page 35) [g/L]
ATOMIC WEIGHT Relative atomic weight of active precipitant substance (refer to 4.5.8, page 35) [g/mol]
MODBUS
Start address of an RTC module within the MODBUS network. Default is 41. This
ADDRESS
DATA ORDER
DATALOG INTRVL Indicates the interval in which the data is saved in the log file. [min]
setting must only be changed by the manufacturer's service department (Section 8). (Refer to Appendix A, page 47)
Specifies the register order within a double word. Default is NORMAL. This setting must only be changed by the manufacturer's service department (Refer to
Section 8)
MAINTENANCE
RTC DATA
RTC MEASUREMEN Displays up to 5 measured values; additional values can be selected by scrolling.
RTC ACTUAT VAR Displays up to 5 actuating variables; additional variables can be selected by scrolling.
DIAG/TEST
EEPROM Hardware test
RTC COMM TO Communication time-out
RTC CRC Communication checksum
LOCATION
SOFTWARE VERSION Version number for service
RTC MODE Indicates the mode set in the RTC module.
A location name can be assigned here for better identification of RTC module, e.g. activation 2.
28
Page 29

4.4 Select sensors

Figure 4 Select sensor
Parameterization and operation
1. To select the sensors and their sequence for the RTC
module, press RTC > CONFIGURE > SELECT SENSOR.
1ENTER — Saves the setting and returns to the
CONFIGURE menu.
2 CANCEL — Returns to the CONFIGURE menu without
saving.
3ADD — Adds a new sensor to the selection.
2. Press ADD (Figure 4, item 3).
A selection list of all subscribers to the sc1000 network opens.
3. Press the required sensor for the RTC module and confirm by pressing
Sensors in black type are available for the RTC module. Sensors in red type are not available for the RTC module.
Note: PROGNOSYS is available for sensors marked (p) if these sensors have been selected in conjunction with an RTC module (refer to the PROGNOSYS user manual).
4 DELETE — Removes a sensor from the selection.
5UP/DOWN — Moves the sensors up or down.
ENTER below the selection list.
29
Page 30
Parameterization and operation
4. The selected sensor is shown in the sensor list.
Press ADD (Figure 4, item 3) to open the selection list again.
5. Select the second sensor for the RTC module and confirm by pressing
Note: Previously selected sensors are shown in gray.
The selected sensors are shown in the sensor list.
ENTER below the selection list.
6. To sort the sensors in the order specified for the RTC
module, press the sensor and use the arrow keys to move it (
Figure 4, item 5).
Press DELETE (Figure 4, item 4) to remove an incorrect sensor from the sensor list again.
7. Press ENTER (Figure 4, item 1) to confirm the list once it is finished.
30
Page 31

4.5 Explanations

4.5.1 Ortho-phosphate and total phosphate

The goal of phosphate control is to reduce the total phosphate in the effluent stream at a waste water treatment plant. However, the precipitation only affects the ortho-phosphate content. The PO
-P target value specifies the ortho-phosphate value to be
4
maintained in the precipitation reactor. Therefore, this value must be lower than the value to be maintained in the effluent.
Note: If CLOSED-LOOP is set in the controller, the setpoint is effective immediately. If effluent concentration of the reactor is required.

4.5.2 Recycling the chemical sludge

Precipitant savings can be achieved, particularly in activated sludge plants, if existing chemical sludge is reused for phosphorus elimination. In the case of precipitant overdosage, the stoichiometrically excessive metal content (for metal phosphate formation) is reused in the formation of metal phosphate upon renewed contact with dissolved phosphate. Renewed adsorption of phosphate, by precipitates already formed, is possible. The existing precipitant·sludge portion thus represents a reserve for the precipitation of P-influent peaks or for a short-term failure of the dosing devices; however, other authors consider this reserve to be minimal.
Parameterization and operation
OPEN-LOOP is set in the controller, the desired PO
-P
4
The precipitant savings automatically take effect for closed-loop controls. To be able to use the reserve for open-loop controls
as well, the correction ( input reduces the precipitant dosing:
In the event of negative influences on the phosphate precipitation, a positive correction value can be entered:

4.5.3 Biological phosphate elimination

The BIO-P parameter is used to take biological phosphate elimination into account. If no phosphate elimination is effective at the phosphate measuring point, the specify the percentage of influent phosphates that is biologically incorporated into the sludge on an empirical basis. In this case, it is important to differentiate between the measurement of ortho-phosphate and total phosphate. For total phosphate, the "unavoidable" biological phosphate elimination must always be taken into account. This can be set at 1 % of the BOD increased biological phosphate elimination can be added in all cases and must be estimated on the basis of empirical values.
CORR FACTOR)) can be used. A negative
Example:
A correction value of –50 % is set. This reduces the precipitant dosing by half.
Example:
A correction value of +100 % is set. This doubles the precipitant dosing.
BIO-P factor can be used to
. An
5
31
Page 32
Parameterization and operation

4.5.4 Phosphate profile

The same conditions as specified under 4.5.3, page 31 must apply for the phosphate flow rate profile. If biological phosphate elimination is still not effective at the measuring point, the flow profile rate remains unaffected by the biological phosphate elimination. If biological phosphate elimination is already effective at the measuring point, this must also be reflected in the profile.
Note: In this case, the value zero (0) must be entered as Bio P proportion!
For open-loop controls, the results of the online measurement can be directly employed in the profile determination. This also ensures that the measurement conditions are identical.
Due to missing data, the configuration for closed-loop controls is more complex. A reliable data pool for a waste water treatment plant can only be obtained on the basis of 2 h composite samples. Any samples that were taken during unusual influent events (heavy rains, unauthorized discharge) are excluded.
A sample unaffected by precipitation can only be taken from the influent to the activated sludge plant. At this point, the organic phosphorous has not yet hydrolyzed. If total phosphate is determined here, the "unavoidable" biological phosphate elimination must be considered.
Since the entry of a Bio-P amount is not possible for closed-loop controls (option hidden), lower values can be entered directly. If the online measurement fails, it is safer to forego a reduction.
Over the course of a week, there can be strong fluctuations in the load on the waste water treatment plant. To ensure an accurate representation of actual conditions, the daily profiles can be superimposed with a weekly profile.

4.5.5 PID closed-loop (proportional, integral, differential closed-loop)

The proportional precipitant dosing quantity calculated by the RTC module is increased or reduced by the proportional intensification factor (
As the precipitant has already become effective at the measuring point, the measurement indicates the following:
The dosage is too low
The dosage is sufficient
The dosage is too high and must be corrected
accordingly
The proportional gain factor specifies the precipitant dosage required based on the exceedance of the target value. Large gains result in large changes to the dosing and therefore a high closed-loop control speed; however, the closed-loop control oscillations also increase in line with the gain.
GAIN P CONTR.) of the closed loop control.
32
The
DERIVATIVE TIME allows the RTC module to react not only
to the absolute target value deviations but also to the speed with which the phosphate content rises or falls. Necessary corrections can thus be made at an earlier stage.
Page 33
Parameterization and operation
Example:
A derivative time of 1 minute means that closed-loop control takes place according to the phosphate concentration that is actually achieved in only 1 value change remains the same).
The integration time takes effect by means of the temporal integration of the control deviation (PO actual value), to the actuating variable with the weighting by the
INTEGRALTIME. The integral time states when the integral
proportion has the same effect as the P proportion. A short timeframe can lead to an overshoot or strong oscillations of the PO
-P concentration. An increase in the integral time reduces the
4
oscillation. In this case, the I proportion of the closed-loop control can be specified through the entry of
minute (if the current measured
-P setpoint to PO4-P
4
INTEGRAL TIME = 0.

4.5.6 Pump runtime

Setting tips: As a
DERIVATIVE TIME >0 min has a highly
significant impact on the metered precipitant quantity, this should be used only in exceptional cases, e.g. plants demonstrating rapid escalations in PO
-P concentrations.
4
To ensure the metered precipitant quantity increases/decreases more quickly, the
INTEGRALTIME reduced. To ensure the metered quantity
changes more slowly, the
INTEGRAL TIME increased.
GAIN P CONTR. must be increased or the
GAIN P CONTR. must be reduced or the
The on/off duration in pulse/pause mode can be influenced via the control cycle time (
CONTROL CYCLE). For example, with a
cycle time of 100 seconds and a dosing control value of 60 %, the dosing pump is periodically switched on for 60 seconds and off for 40 seconds. Short cycle times increase the switch frequency, but enable more precise adaptation to individual requirements.
A minimum on-time is also configured to protect the dosing pump. The pump is not activated for less than this time span. The time must be a fraction of the control cycle time.
33
Page 34
Parameterization and operation

4.5.7 Inclusion of return sludge quantity

To be able to record the entire flow at the measuring point, the return sludge quantity must also be taken into account, depending on the specific application. For this purpose, the minimum and maximum flow rate of the return activated sludge pump(s) can be specified, as well as the ratio of return activated sludge transport relative to the measured flow rate.
The flow rate, e.g. for simultaneous precipitation with a measuring point in the activated sludge tank, is calculated as follows:
Q RS which the calculated return activated sludge volume is varied according to Q RS
If the measuring location is at a measuring point that is not influenced by the return activated sludge volume, all variables described below must be set to "
Q
= Qto + QRSL
total
Where: QRLS = QRS
ratio
Within the limits of Q RS
minimum
and Q RS
ratio
maximum
.
× Qto
minimum
and Q RS
maximum
thus represent the limits within
0".
Under
MIN RET SLUDGE, the minimum flow rate of the return
sludge pump(s) must be specified in m³/h. In the case of a constant return sludge flow rate, the relevant value must also be specified here.
Under
MAX RET SLUDGE, the maximum flow rate of the return
sludge pump(s) must be specified in m³/h. If a constant return activated sludge volume is pumped, Q RS "
0".
maximum
can be set to
In the event of a return activated sludge volume that is proportional to the flow rate (Q), the percentage ratio must be specified under
Q RET RATIO. If the same return activated sludge
volume is pumped continuously, this volume must be specified under Q RS
minimum
. The Q RS
must then be selected as "0".
ratio
A heavily fluctuating flow rate signal (e.g. caused by pumping stations) that is integrated in the RTC module via the 4-20 mA current loop can be smoothed using
Q INFL SMOOTH. As a result,
only a marginally fluctuating target value is issued.
Q INFL SMOOTH can lie between 1 and 99.
Q INFL SMOOTH = 1. The influent signal is not smoothed.
Q INFL SMOOTH = 2. The influent signal is smoothed over 3
minutes.
34
Q INFLUENT SMOOTH = 3. The influent signal is smoothed
over 2 minutes.
Q INFLUENT SMOOTH = 5. The influent signal is smoothed over 12 minutes.
Q INFLUENT SMOOTH = 10. The influent signal is smoothed over 25 minutes.
Example:
Page 35

4.5.8 Precipitants

4.5.8.1 Metal content
Parameterization and operation
With the setting Q INFLUENT SMOOTH = 2, it takes three minutes for the smoothed value to reach 95 value (following a sudden change of the influent rate).
For calculations, the effective metal content of the precipitant must be specified in g/l as well as the relative atomic weight of the metal in g/mol.
The metal content (active component) of the precipitant is specified by the manufacturer in:
g/kg multiply the value by the density δ of the product to obtain the metal content in g/L
% multiply the value by 10 to obtain the concentration in g/kg. Multiply this value by the density δ of the product to obtain the metal content in g/L
mol/L This value can be entered instead of the concentration in g/L. Enter a 1 for the atomic weight of the metal.
% of the final
4.5.8.2 Atomic weight of metal
The type of the precipitant is determined by the atomic weight.
Atomic weight of iron: 55.8 g/mol
Atomic weight of aluminum: 26.9 g/mol
Composite products
For products that contain both aluminum and iron, the molar metal concentration is calculated from the sum of the molar concentrations of iron and aluminum.
Example: Compound of iron (12 %) and aluminum (8 %):
Molar aluminum concentration:
80
26.9
g
kg mol
=2.97
gkg
mol
Molar iron concentration:
120
55.8
g
kg mol
=2.15
gkg
mol
35
Page 36
Parameterization and operation
Molar metal concentration for a compound of iron (12 %) and aluminum (8 %):
2.79
mol
+2.15
kg kg kg
mol
=5.12
mol
A conversion is performed with the product density for entry in the RTC module:
1.43
kg
×5.12
Lkg L
mol
=7.32
mol
The product of the molar concentration [mol/kg] and the density of the product [kg/L] yields the molar metal concentration in mol/L. As stated above, this numerical value must be entered for the metal content. Enter a 1 for the atomic weight of the metal.
36
Page 37

Section 5 Maintenance

Multiple hazards Only qualified personnel must conduct the tasks described in this section of the manual.

5.1 Maintenance schedule

Interval Maintenance task
DANGER
Visual inspection
CF card 2 years
Battery, type CR2032 Panasonic or Sanyo
Application-specific Check for contamination and corrosion
5 years Replacement
Replacement by manufacturer's service department (Section 8)
37
Page 38
Maintenance
38
Page 39

Section 6 Troubleshooting

6.1 Error messages

The sc controller displays the possible sensor errors.
Displayed errors Cause Resolution
Supply RTC with voltage
RTC MISSING
RTC CRC
CHECK CONFIG
RTC FAILURE
FAULTY PUMP 1 Faulty measurement signal Test sensor, check cable connections
No communication between RTC and RTC communication card
Interrupted communication between RTC and RTC communication card
The sensor selection of the RTC was deleted by deleting or selecting a new sc1000 participant.
Brief general read/write error on the CF card, mostly caused by a brief interruption to the power supply.
Test connection cable Reset the sc1000 and the RTC (switch so it is
completely voltage free and switch back on)
Make sure +/- connections of the connector cable between RTC and RTC communication card in the sc1000 are installed correctly.
From MAIN MENU > RTC MODULES / PROGNOSYS > RTC MODULES > RTC > CONFIGURE > SELECT SENSOR, select the correct sensor for the RTC again and confirm.
Acknowledge error. If this message is shown frequently, eliminate the cause of the power disruptions. If necessary, inform the service team of the manufacturer (Section8, page 43).
FAULTY PUMP 2 Faulty measurement signal Test sensor, check cable connections
INFLUENT1 NOT G. Faulty measurement signal Test sensor, check cable connections
INFLUENT2 NOT G. Faulty measurement signal Test sensor, check cable connections

6.2 Warnings

The sc controller displays the possible warning messages from the sensor.
Displayed warnings Cause Resolution
The RTC menu
MODBUS ADDRESS
PROBE SERVICE A configured sensor is in service status. The sensor must exit service status.
This deletes the MODBUS address of the RTC module.
PLANT CONFIG was opened.
OPEN THE MODBUS menu of the RTC module
and set the correct MODBUS address.

6.3 Wear parts

Designation Number Service life
CF card, type RTC module 1 piece 2 years Battery, type CR2032 Panasonic or Sanyo 1 piece 5 years
39
Page 40
Troubleshooting
40
Page 41

Section 7 Replacement parts and accessories

7.1 Spare parts

Description Cat. no.
NS 35/15 DIN rail, punched according to DIN EN 60715 TH35, made from galvanized steel. Length: 35 cm (13.7 in)
90–240 V AC/24 V DC 0.75 A transformer, module for DIN rail assembly LZH166 Terminal for 24 V connection without power supply LZH167 Grounding terminal LZH168 SUB-D connector LZH169 C2 circuit breaker LZH170 CPU base module with Ethernet port, passive venting element (CX1010-0021) and RS422/485
interface module Power supply module, consists of a bus coupler and a 24 V terminal module (CX1100-0002) LZH172 Digital output module 24 V DC (2 outputs) (KL2032) LZH173 Digital output module 24 V DC (4 outputs) (KL2134) LZH174 Analog output module (1 output) (KL4011) LZH175 Analog output module (2 outputs) (KL4012) LZH176 Analog input module (1 input) (KL3011) LZH177 Bus termination module (KL9010) LZH178 RTC communication card YAB117 CF card type RTC module LZY748-00
LZH165
LZH171
41
Page 42
Replacement parts and accessories
42
Page 43

Section 8 Contact information

HACH Company World Headquarters
P.O. Box 389 Loveland, Colorado 80539-0389 U.S.A. Tel (800) 227-HACH (800) -227-4224 (U.S.A. only) Fax (970) 669-2932 orders@hach.com www.hach.com
HACH LANGE GMBH
Willstätterstraße 11 D-40549 Düsseldorf Tel. +49 (0)2 11 52 88-320 Fax +49 (0)2 11 52 88-210 info@hach-lange.de www.hach-lange.de
HACH LANGE GMBH
Rorschacherstrasse 30a CH-9424 Rheineck Tel. +41 (0)848 55 66 99 Fax +41 (0)71 886 91 66 info@hach-lange.ch www.hach-lange.ch
HACH LANGE APS
Åkandevej 21 DK-2700 Brønshøj Tel. +45 36 77 29 11 Fax +45 36 77 49 11 info@hach-lange.dk www.hach-lange.dk
Repair Service in the United States:
HACH Company Ames Service 100 Dayton Avenue Ames, Iowa 50010 Tel (800) 227-4224 (U.S.A. only) Fax (515) 232-3835
HACH LANGE LTD
Pacific Way Salford GB-Manchester, M50 1DL Tel. +44 (0)161 872 14 87 Fax +44 (0)161 848 73 24 info@hach-lange.co.uk www.hach-lange.co.uk
HACH LANGE FRANCE S.A.S.
8, mail Barthélémy Thimonnier Lognes F-77437 Marne-La-Vallée cedex 2 Tél. +33 (0) 820 20 14 14 Fax +33 (0)1 69 67 34 99 info@hach-lange.fr www.hach-lange.fr
HACH LANGE AB
Vinthundsvägen 159A SE-128 62 Sköndal Tel. +46 (0)8 7 98 05 00 Fax +46 (0)8 7 98 05 30 info@hach-lange.se www.hach-lange.se
Repair Service in Canada:
Hach Sales & Service Canada Ltd. 1313 Border Street, Unit 34 Winnipeg, Manitoba R3H 0X4 Tel (800) 665-7635 (Canada only) Tel (204) 632-5598 Fax (204) 694-5134 canada@hach.com
HACH LANGE LTD
Unit 1, Chestnut Road Western Industrial Estate IRL-Dublin 12 Tel. +353(0)1 460 2522 Fax +353(0)1 450 9337 info@hach-lange.ie www.hach-lange.ie
HACH LANGE NV/SA
Motstraat 54 B-2800 Mechelen Tel. +32 (0)15 42 35 00 Fax +32 (0)15 41 61 20 info@hach-lange.be www.hach-lange.be
HACH LANGE S.R.L.
Via Rossini, 1/A I-20020 Lainate (MI) Tel. +39 02 93 575 400 Fax +39 02 93 575 401 info@hach-lange.it www.hach-lange.it
Repair Service in Latin America, the Caribbean, the Far East, Indian Subcontinent, Africa, Europe, or the Middle East:
Hach Company World Headquarters, P.O. Box 389 Loveland, Colorado, 80539-0389 U.S.A. Tel +001 (970) 669-3050 Fax +001 (970) 669-2932 intl@hach.com
HACH LANGE GMBH
Hütteldorfer Str. 299/Top 6 A-1140 Wien Tel. +43 (0)1 912 16 92 Fax +43 (0)1 912 16 92-99 info@hach-lange.at www.hach-lange.at
DR. LANGE NEDERLAND B.V.
Laan van Westroijen 2a NL-4003 AZ Tiel Tel. +31(0)344 63 11 30 Fax +31(0)344 63 11 50 info@hach-lange.nl www.hach-lange.nl
HACH LANGE S.L.U.
Edificio Seminario C/Larrauri, 1C- 2ª Pl. E-48160 Derio/Vizcaya Tel. +34 94 657 33 88 Fax +34 94 657 33 97 info@hach-lange.es www.hach-lange.es
HACH LANGE LDA
Av. do Forte nº8 Fracção M P-2790-072 Carnaxide Tel. +351 214 253 420 Fax +351 214 253 429 info@hach-lange.pt www.hach-lange.pt
HACH LANGE KFT.
Vöröskereszt utca. 8-10. H-1222 Budapest XXII. ker.
Tel. +36 1 225 7783 Fax +36 1 225 7784 info@hach-lange.hu www.hach-lange.hu
HACH LANGE SP. ZO.O.
ul. Krakowska 119 PL-50-428 Wrocław Tel. +48 801 022 442 Zamówienia: +48 717 177 707 Doradztwo: +48 717 177 777 Fax +48 717 177 778 info@hach-lange.pl www.hach-lange.pl
HACH LANGE S.R.L.
Str. Căminului nr. 3, et. 1, ap. 1, Sector 2 RO-021741 Bucureşti Tel. +40 (0) 21 205 30 03 Fax +40 (0) 21 205 30 17 info@hach-lange.ro www.hach-lange.ro
HACH LANGE S.R.O.
Zastrčená 1278/8 CZ-141 00 Praha 4 - Chodov Tel. +420 272 12 45 45 Fax +420 272 12 45 46 info@hach-lange.cz www.hach-lange.cz
HACH LANGE
8, Kr. Sarafov str. BG-1164 Sofia Tel. +359 (0)2 963 44 54 Fax +359 (0)2 866 15 26 info@hach-lange.bg www.hach-lange.bg
HACH LANGE S.R.O.
Roľnícka 21 SK-831 07 Bratislava – Vaj nory Tel. +421 (0)2 4820 9091 Fax +421 (0)2 4820 9093 info@hach-lange.sk www.hach-lange.sk
HACH LANGE SU ANALİZ SİSTEMLERİ LTD. ŞTİ.
Ilkbahar mah. Galip Erdem Cad. 616 Sok. No:9 TR-Oran-Çankaya/ANKARA Tel. +90312 490 83 00 Fax +90312 491 99 03 bilgi@hach-lange.com.tr www.hach-lange.com.tr
43
Page 44
Contact information
HACH LANGE D.O.O.
Fajfarjeva 15 SI-1230 Domžale Tel. +386 (0)59 051 000 Fax +386 (0)59 051 010 info@hach-lange.si www.hach-lange.si
HACH LANGE OOO
Finlyandsky prospekt, 4A Business Zentrum “Petrovsky fort”, R.803 RU-194044, Sankt-Petersburg Tel. +7 (812) 458 56 00 Fax. +7 (812) 458 56 00 info.russia@hach-lange.com www.hach-lange.com
ΗΑCH LANGE E.Π.Ε.
Αυλίδος 27 GR-115 27 Αθήνα Τηλ . +30 210 7777038 Fax +30 210 7777976 info@hach-lange.gr www.hach-lange.gr
HACH LANGE D.O.O.
Ivana Severa bb HR-42 000 Varaždin Tel. +385 (0) 42 305 086 Fax +385 (0) 42 305 087 info@hach-lange.hr www.hach-lange.hr
HACH LANGE MAROC SARLAU
Villa 14 – Rue 2 Casa Plaisance Quartier Racine Extension MA-Casablanca 20000 Tél. +212 (0)522 97 95 75 Fax +212 (0)522 36 89 34 info-maroc@hach-lange.com www.hach-lange.ma
44
Page 45

Section 9 Warranty and liability

The manufacturer warrants that the supplied product is free of material and manufacturing defects, and undertakes to repair or to replace any defective parts without charge.
The warranty period is 24 months. If a maintenance contract is taken out within 6 months of purchase, the warranty period is extended to 60 months.
With the exclusion of further claims, the supplier is liable for defects, including the lack of assured properties, as follows: all parts that, within the warranty period calculated from the day of the transfer of risk, can be demonstrated to have become unusable or that can only be used with significant limitations owing to circumstances prior to transfer of risk, in particular due to incorrect design, substandard materials or inadequate finish, shall be repaired or replaced at the supplier's discretion. The identification of such defects must be reported to the supplier in writing as soon as possible, but no later than 7 days after the discovery of the fault. If the customer fails to notify the supplier, the product is considered approved despite the defect. Further liability for indirect or direct damages is not accepted.
If device-specific maintenance- or inspection work prescribed by the supplier is to be performed within the guarantee period by the customer (maintenance) or by the supplier (inspection) and these requirements are not met, claims for damages that result from non-observance of these requirements are void.
Further claims, in particular for consequential damages, cannot be made.
Wear and damage caused by improper handling, incorrect installation or non-designated use are excluded from this clause.
The process instruments of the manufacturer have proven their reliability in many applications and are therefore often used in automatic control loops to enable the most economical and efficient operation of the relevant process.
To avoid or limit consequential damage, it is therefore recommended that the control loop be designed such that an instrument malfunction results in an automatic changeover to the backup control system. This guarantees the safest operating condition both for the environment and the process.
45
Page 46
Warranty and liability
46
Page 47

Appendix A MODBUS address setting

The same slave address for MODBUS communication must be set on both the sc1000 display and on the RTC101 P-Module. As 20 slave addresses are reserved for internal purposes, the following slave addresses are available for assignment:
1, 21, 41, 61, 81, 101 etc.
Slave address 41 is preset at the factory.
NOTICE
If this slave address is must be changed because, for example, it is already assigned to another RTC module , it must be edited on both the sc1000 and on the CF card of the RTC module.
This can only be done by the manufacturer service department (Section 8)!
47
Page 48
MODBUS address setting
48
Loading...