2.2 Areas of application ............................................................................................................................ 8
6.3 Wear parts ........................................................................................................................................ 39
Section 7 Replacement parts and accessories ................................................................................. 41
7.1 Spare parts ....................................................................................................................................... 41
Section 8 Contact information ............................................................................................................ 43
Section 9 Warranty and liability........................................................................................................... 45
Appendix A MODBUS address setting ............................................................................................... 47
3
Page 4
Table of Contents
4
Page 5
Section 1Specifications
Subject to change without notice.
Industrial Personal Computer (IPC), (Embedded PC)
Processor
Flash memory2 GB compact flash card
Internal working memory256 MB DDR-RAM (not expandable)
InterfaceRJ 45 (Ethernet), 10/100 MBit/s
Diagnostic LEDsPower, LAN speed, LAN activity, TC status, flash access
Expansion slotCompact flash type II slot with ejection mechanism
Clock
Operating systemMicrosoft Windows
Control softwareTwinCAT PLC Runtime or TwinCAT NC PTP Runtime
System bus16 Bit ISA (PC/104 standard)
Power supplyVia system bus (through power supply module CX1100-0002)
Max. power loss6 W (including the system interfaces CX1010-N0xx)
Analog input4–20 mA for flow rate measurement
Internal resistance80 Ohm × diode voltage 0.7 V
Signal current0–20 mA
Pentium®1, MMX compatible, 500 MHz clock rate
Internal, battery-buffered clock for time and date (battery can be
replaced)
®2
CE or Microsoft Windows Embedded Standard
Common mode voltage (U
Measurement error (for entire measurement
range)
Electrical surge resistance35 VDC
Electrical isolation500 V
Analog output4–20 mA for dosing pump
Number of outputs1
Power supply
Signal current0–20 mA
Working resistance< 500 Ω
Measurement error
Resolution12 bit
Conversion time~ 1.5 ms
Electrical isolation 500 V
)35 V max.
CM
< ± 0.3 % (from measurement range end value)
24 V DC via power contacts
(alternatively 15 V DC with bus terminal KL9515)
± 0.5 LSB linearity error
± 0.5 LSB offset error
± 0.1, % (relative to the measuring range end value)
(K-bus/signal voltage)
eff
(K-bus/signal voltage)
eff
5
Page 6
Specifications
Digital outputs
1-channel: 1 × for dosing pump and 1 × alarm
2-channel: 2 × for dosing pump and 1 × alarm
Nominal load voltage24 VDC (–15 % / +20 %)
Load typeOhmic, inductive, lamp load
Max. output current0.5 A (short-circuit proof) per channel
Short-circuit current0.7 to 1.7 A
Reverse polarity protectionYes
Electrical isolation500 V
(K-bus/field voltage)
eff
Power contact current consumption20 mA typ. (for typ. 30 mA 2-channel device)
Equipment properties
Dimensions (L × W × H)
350 mm × 120 mm × 96 mm
(13.78 in. × 4.72 in. × 3.78 in.)
Massapprox. 0.9 kg
Environmental conditions
Working temperature0 to 50 °C (32 to 122 °F)
Storage temperature–25 to +85 °C (–13 to 185 °F)
Relative humidity95 %, non-condensing
Miscellaneous
Pollution Degree
Protection Class
Installation Category
Maximum Altitude
2
1
II
2000 m (6.562 ft.)
Protection classIP20
InstallationDIN rail EN 50022 35 × 15
1
Pentium is a registered trademark of the Intel Corporation.
2
Microsoft Windows is a brand name for operating systems of the Microsoft Corporation.
6
Page 7
Section 2General Information
2.1Safety information
Please read this entire manual before unpacking, setting up, or operating this equipment.
Pay attention to all danger and caution statements. Failure to do so could result in serious
injury to the operator or damage to the equipment.
To prevent damage to or impairment of the device's protection equipment, the device may
only be used or installed as described in this manual.
2.1.1Use of hazard information
DANGER
Indicates a potentially or imminently hazardous situation that, if not avoided, can result in death or
serious injury.
WARNING
Indicates a potentially or imminently dangerous situation that, if it is not avoided, can lead to death
or to serious injuries.
CAUTION
Indicates a possible dangerous situation that can have minor or moderate injuries as the result.
Indicates a situation that, if it is not avoided, can lead to damage to the device. Information that
requires special emphasis.
Note: Information that supplements points in the main text.
2.1.2Warning signs
Read all labels and tags attached to the instrument. Non-observance may result in
personal injury or damage to the equipment..
This symbol is a warning triangle. Follow all safety notes that follow this symbol to prevent possible injuries. If this
symbol is located on the device, it refers to information in the operating and/or safety notes of the user manual.
This symbol can be attached to a housing or a barrier in the product and shows that electric shock risk and/or the
risk of a death through electric shock exists.
Electrical equipment marked with this symbol may not be disposed of in European domestic or public disposal
systems after 12 August 2005. In conformity with local and national regulations, European electrical equipment
users must now return old or end-of life equipment to the manufacturer for disposal at no charge to the user.
Note: You obtain instructions on the correct disposal of all (marked and not marked) electrical products that were
supplied or manufactured by Hach-Lange at your relevant Hach-Lange sales office.
NOTICE
7
Page 8
General Information
2.2Areas of application
The RTC101 P-Module is a universal open-loop control and closed-loop control unit in
waste water treatment plants for automatic precipitant metering for phosphate
precipitation.
Depending on the operating situation, the precipitant dosage can be based on measured
values in the influent or effluent or based on profiles. The system automatically selects the
best possible strategy. The user is able to make restrictions manually.
The use of an RTC Module does not release the operator from the duty of care to the system. No
guarantees as to the functionality or operational safety of the system.
In particular, the operator must make sure that instruments connected to the RTC
open/closed-loop controller are always fully functional.
To make sure these instruments supply correct, reliable measurement values, regular
maintenance work (for example, cleaning of the sensor and laboratory comparative
measurements) is essential! (Refer to the user manual for the relevant instrument.)
2.3Functional principle
In the following, a distinction is made between the open-loop control and the
closed-loop control of the precipitant concentration.
NOTICE
For the open-loop control of the precipitant dosing, the measuring point for the
phosphate concentration is upstream of the precipitant dosing point.
For the closed-loop control of the precipitant dosing, the measuring point for the
phosphate concentration is downstream of the precipitant dosing point.
The measuring point for the flow rate is usually located in the influent of the waste water
treatment plant. At the measuring point, the actual flow rate (influent quantity and
recirculation - e.g. RAS, MLR, etc) is determined via further entries in the RTC module.
If the measured values for the flow rate quantity and/or phosphate concentration are
temporarily not available (e.g. due to a malfunction), the system automatically refers back
to saved profiles.
Connect the following input signals on the control unit in order to make optimum use of all
system functions:
•Flow rate, measurement signal 4–20 mA
•Fault indicator signal of the flow rate measurement (230 V AC or 24 V DC)
In the event that measured value failures are not signaled according to NAMUR 43, as
the values are below the 4
Note: If these signals are not available, the equipment operates with limited functionality.
•sc1000 controller with PO4P PHOSPHAX sc analyzer.
The measured value is adopted directly.
•Dosing pump for the precipitant
The dosing pump is continuously actuated via a 0–20 mA or 4–20 mA current loop
signal as well as via a changeover contact. If the dosing rate is below the minimum
precipitant flow rate of the pump, the system automatically switches to pulse/pause
mode.
mA threshold.
8
Page 9
2.4Scope of delivery
Each RTC101 P-Module is supplied with:
•SUB-D connector (9 pin)
•Ferrite core, folding
•Manual
Check that the order is complete. If anything is missing or damaged, please contact the
manufacturer or distributor.
The combination of pre-assembled components supplied by the manufacturer does not represent
a standalone functional unit. In accordance with EU guidelines, this combination of pre-assembled
components is not supplied with a CE mark, and there is no EU declaration of conformity for the
combination.
However, the conformity of the combination of components with the guidelines can be proved
through technical measurements.
General Information
NOTICE
9
Page 10
General Information
2.5Instrument overview
Figure1 Base module RTC 24 V version .
1PE (protective earth)5sc 1000 connection: RS485 (CX1010-N031)
224 V6Battery compartment
30 V7CPU base module, consisting of Ethernet port with
battery compartment (CX1010-N000), CPU module with
CF card (CX1010-0021) and passive aeration element.
4Automatic circuit breaker (ON/OFF switch for item 7 and
8 without fuse function).
Note: All components are pre-wired.
8Power supply module, consisting of bus coupler
(CX1100-0002) and terminal module 24V.
10
Page 11
Abbildung 2 Base module RTC 100-240 V version
General Information
1L(+)7Automatic circuit breaker (ON/OFF switch for item 10
and 11 without fuse function).
2N(–)8sc 1000 connection: RS485 (CX1010-N041)
3Input AC 100–240 V / Input DC 95 V–250 V9Battery compartment
4PE (protective earth)10 CPU base module, consisting of Ethernet port with
battery compartment (CX1010-N000), CPU module with
CF card (CX1010-0021) and passive aeration element.
524 V transformer (Specification Section 3.1.1, page 13)11 Power supply module, consisting of bus coupler
6Output DC 24 V, 0,75 A
(CX1100-0002) and terminal module 24V.
Note: All components are pre-wired.
11
Page 12
General Information
12
Page 13
Section 3Installation
Only qualified experts may perform the tasks described in this section of the manual, while
adhering to all locally valid safety regulations.
Always lay cables and hoses so that they are straight and do not pose a tripping hazard.
Before the power supply is switched on, refer to the instructions in the relevant manuals!
3.1RTC101 P-Module connection
The RTC module must be installed on a DIN rail/standard rail.
Install the module horizontally, with at least 30 mm clearance at the top and bottom, in
order to guarantee the functionality of the passive ventilation element. The RTC module is
operated solely via the sc1000 controller (see sc1000 controller operating instructions).
When used indoors, the RTC module can be installed in a control cabinet.
When used outdoors, the RTC module requires its own housing that follows the technical
specifications.
DANGER
CAUTION
CAUTION
3.1.1Power supply to the RTC module
Alternating current may destroy the direct current system and therefore jeopardize user safety.
Never connect an alternating current voltage to the 24 V direct current model.
Table1 Supply voltage of the RTC Module
Voltage24 V DC (–15 % / +20 %), max. 25 W
Recommended fuse C2
With 110–230 V option110–230 VAC, 50-60 Hz, approximately 25 VA
Note: An external deactivation switch is recommended for all installations.
3.2Dosing pump connection
There are two connections for the dosing pump:
•Current loop signal 0/4 to 20 mA for analog actuation of pumps with frequency
converters.
•24 V output for the actuation of pumps without frequency converters or below the
analog adjustment range in pulse/pause mode.
Note: It must also be possible to switch the pump off via the digital output in the case of analog
actuation!
WARNING
3.3PHOSPHAX sc analyzer connection
The measuring signal of the PHOSPHAX sc analyzer is transmitted to the RTC101
P-Module from the sc-system via the RTC communication card.
Previous designs of the analyzer (e.g. PHOSPHAX inter) can be connected to an analog
input card (YAB018).
13
Page 14
Installation
3.3.1PHOSPHAX sc analyzer power supply
Refer to the PHOSPHAX sc manual.
3.4sc1000 controller connection
Connect the SUB-D plug supplied to a dual-core, sheathed data cable (signal or bus
cable). For further information regarding the data cable connection, refer to the enclosed
assembly instructions.
3.5Flow rate signal connection
If a flow rate measurement signal of 4 to 20 mA is available, connect it to the analog input
of the RTC module.
3.6Connection to the automation unit on the plant side
Depending on the variant and option, the RTC101 P-Module is equipped with various
components that must be connected to the plant's automation unit.
•The volumetric flow rate is provided to the RTC module as a 0/4 to 20 mA signal for all
variants and options.
•The precipitant volume to be metered is delivered by the RTC module as a 0/4 to
20
mA signal for all variants and options.
Alternatively, the precipitant volume can also be output by the fieldbus variants
provided by the sc1000 (see sc1000 operating instructions).
•The RTC module supplies the digital output signal for activating the precipitant pump
at 0
V or 24 V.
•The RTC module supplies a collective fault message at 0 V (fault) or 24 V (device
functional).
Table 2 Signal allocation of individual components of the RTC module
4.1Open-loop control and closed-loop control programs
Four different programs are provided to enable optimal
adaptation to local conditions and to the available measurement
signals.
Programs 3 and 4 have various functions depending on whether
open-loop control or closed-loop control is selected.
4.1.1Open-loop control
For the open-loop control of precipitant dosing, the measuring
point for phosphate concentration is upstream of the precipitant
dosing point.
4.1.1.1Open-loop control according to phosphate concentration profiles
Program 1
Load-proportional open-loop control:
•Specified profile of the phosphate concentration in the reactor
inlet
•Specified profile for the flow rate
Program 2
Load-proportional open-loop control:
•Specified profile of the phosphate concentration in the reactor
inlet
•Flow rate measured value
Note: The prerequisite for this program is that the flow rate
measurement signal is valid. "Valid" means that the signal is present at
the relevant input.
4.1.1.2Open-loop control according to measured phosphate values
Program 3
Load-proportional open-loop control:
•Measured value of the phosphate concentration in the reactor
inlet
•Specified profile for the flow rate
Note: The prerequisite for this program is that the PO4-P measurement
signal is valid. "Valid" means that the signal is present at the relevant
input.
Program 4
Load-proportional open-loop control:
•Measured value of the phosphate concentration in the reactor
inlet
•Flow rate measurement
Note: The prerequisite for this program is that both measurement signals
are valid. "Valid" means that the signal is present at the relevant input.
15
Page 16
Parameterization and operation
4.1.2Closed-loop control according to measured phosphate values
For the closed-loop control of the precipitant dosing, the
measuring point for the phosphate concentration is downstream
of the precipitant dosing point.
Program 3
Closed-loop control:
•Measured value of the phosphate concentration in the reactor
outlet
•Specified profile for the flow rate (can be deactivated)
Note: The prerequisite for this program is that the PO4-P measurement
signal is valid. "Valid" means that the signal is present at the relevant
input.
Program 4
Load-proportional closed-loop control:
•Measured value of the phosphate concentration in the reactor
inlet
4.2Program change
4.2.1Automatic program change
•Flow rate measurement
Note: The prerequisite for this program is that both measurement signals
are valid. "Valid" means that the signal is present at the relevant input.
If a measurement signal drops out, an automatic program change
occurs and the system refers to the specified profile. The
program selection can be limited manually. The change between
programs occurs with a 5 minute delay, whereby the last
manipulated value set for the dosing is retained at the output.
16
Page 17
Figure 3 Program change
Q/PO4-P
Program 4
Q profile/PO
4
-P
Program 3
Q profile/PO
4
-P profile
Program 1
Q/PO
4
-P profile
Program 2
Parameterization and operation
4.2.2Manual pre-selection
Pre-selection 1:Always Program 1
Pre-selection 2:
Pre-selection 3:
Open-loop
control:
Closed-loop
control:
Program 2On signal drop outProgram 1
Program 3On signal drop outProgram 2 if possible
Program 3Otherwise program 1
4.2.3CF card configuration
If both measurement signals become invalid at the same time,
the system switches between programs 4 and 1 without
intermediate stages.
Manual pre-selection limits the selection of programs.
NOTICE
Never remove the CF card from the RTC module during operation!
This can damage the instrument!
The function of the RTC101 P-Module, i.e. control/regulation, is
indicated on the CF card. If this setting is to be changed, please
contact the manufacturer's service department (Section 8).
17
Page 18
Parameterization and operation
4.3Parameterization on the sc1000
4.3.1User interfaces and navigation
Before the system is used, the user must be familiar with the sc
controller functions. Learn how to navigate through the menu and
perform the relevant functions.
SETPOINT PO4-PDesired orthophosphate value in effluent (refer to 4.5.1, page 31) [mg/L]
CORR FACTORPercentage correction of precipitant dosing (see 4.5.2, page 31) [%]
BIO-PPhosphate biologically eliminated after influent (refer to 4.5.3, page 31) [%]
MIN DOS RATEMinimum flow rate of dosing pump [L/h]
PRESELECT PROGPrograms 1 to 4 (refer to 4.1, page 15)
PROFILEActive when a measurement signal fails
Q-PROFILE
P-PROFILEDaily profiles for PO4-P concentrations, 2 h average (see 4.5.4, page 32) [mg/L]
WEEK PROFILE
IN- OUTPUTS
DOSING PUMP
MIN PUMP RANGELower threshold of flow rate range [L/h]
Select the sensor installed for the open-loop control (see Section 4.4, page 29).
Daily profiles (2 h average) of waste water influent according to feed measurement
signal
Percentage daily averages of the phosphate load (refer to 4.5.4, page 32)
(volume × concentration)
[m³/h]
[%]
MAX PUMP RANGEUpper threshold of flow rate range [L/h]
0/4...20MASelection of transfer range according to pump input
CONTROL CYCLEControl cycle comprising on- and off-time (see 4.5.6, page 33)[s]
MIN RUNTIMEMinimum on-time of pump (refer to 4.5.6, page 33) [s]
FLOW RATE
MIN Q-INFLUENTMinimum flow rate in inlet according to measurement signal [m³/h]
MAX Q-INFLUENTMaximum flow rate in inlet according to measurement signal [m³/h]
0/4...20MATransfer range of 0/4–20 mA current loop, as set in the connected flow measuring instrument
MIN RET SLUDGEMinimum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
MAX RET SLUDGEMaximum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34)[m³/h]
Ratio between measured flow rate and return activated sludge volume, for a return
Q RET RATIO
Q INFL SMOOTHSmoothing of influent signal (refer to 4.5.7, page 34)
activated sludge volume proportional to the measured flow rate (refer to 4.5.7,
page 34)
[%]
19
Page 20
Parameterization and operation
1-channel open-loop control
CONFIGURE (CONTINUE)
PRECIPITANT
METAL CONTENTMetal concentration in precipitant (refer to 4.5.8, page 35) [g/L]
ATOMIC WEIGHTRelative atomic weight of active precipitant substance (refer to 4.5.8, page 35) [g/mol]
MODBUS
Start address of an RTC module within the MODBUS network. Default is 41. This
ADDRESS
DATA ORDER
DATALOG INTRVLIndicates the interval in which the data is saved in the log file[min]
MAINTENANCE
RTC DATA
RTC MEASUREMENDisplays up to 5 measured values; additional values can be selected by scrolling
RTC ACTUAT VARDisplays up to 5 actuating variables; additional variables can be selected by scrolling
setting must only be changed by the manufacturer's service department (Section 8).
(Refer to Appendix A, page 47)
Specifies the register order within a double word. Default is NORMAL. This setting
must only be changed by the manufacturer's service department (Refer to Section 8)
DIAG/TEST
EEPROMHardware test
RTC COMM TOCommunication time-out
RTC CRCCommunication checksum
LOCATION
SOFTWARE VERSIONVersion number for service
RTC MODEIndicates the mode set in the RTC module.
A location name can be issued here for better identification of the RTC module e.g.
activation
2
4.3.42-channel open-loop control
In addition to the 1-channel version, a 2-channel version is also
available. The 2-channel version is able to control 2 phosphate
precipitants separately.
All of the key parameters appear twice and are identified as
channel 1 and channel 2.
In contrast to the 1-channel version, a percentage factor for
distribution of the profile (
measurement signals drop out, the percentage factor
PROFILE
distributes the influent waste water to the precipitant.
DIST PROFILE) has been added. If
DIST
20
Page 21
Parameterization and operation
2-channel open-loop control
CONFIGURE
SELECT SENSORSelect the sensors installed for the open-loop control (see Section 4.4, page 29).
SETPOINT PO4-PDesired orthophosphate value in effluent (refer to 4.5.1, page 31) [mg/L]
CORR FACTORPercentage correction of precipitant dosing (see 4.5.2, page 31) [%]
BIO-PPhosphate biologically eliminated after influent (refer to 4.5.3, page 31) [%]
MIN DOS RATEMinimum flow rate of dosing pump [L/h]
PRESELECT PROGPrograms 1 to 4 (refer to 4.1, page 15)
CHANNEL 2
SETPOINT PO4-PDesired orthophosphate value in effluent (refer to 4.5.1, page 31) [mg/L]
CORR FACTORPercentage correction of precipitant dosing (see 4.5.2, page 31) [%]
BIO-PPhosphate biologically eliminated after influent (refer to 4.5.3, page 31) [%]
MIN DOS RATEMinimum flow rate of dosing pump [L/h]
PRESELECT PROGPrograms 1 to 4 (refer to 4.1, page 15)
PROFILEActive when a measurement signal fails
Q-PROFILE
DIST PROFILEPercentage distribution of flow rate; input refers to channel 1.[%]
P-PROFILEDaily profiles of PO
WEEK PROFILEPercentage daily averages of the phosphate load (refer to4.5.4, page 32) [%]
IN- OUTPUTS
DOSING PUMP
CHANNEL 1
MIN PUMP RANGELower threshold of flow rate range [L/h]
MAX PUMP RANGEUpper threshold of flow rate range [L/h]
0/4...20MASelection of transfer range according to pump input
CONTROL CYCLEControl cycle comprising on- and off-time (see 4.5.6, page 33)[s]
MIN RUNTIMEMinimum on-time of pump (refer to 4.5.6, page 33) [s]
Daily profiles (2 h average) of waste water influent according to feed measurement
signal
-P concentrations, 2 h average (see 4.5.4, page 32) [mg/L]
4
[m³/h]
21
Page 22
Parameterization and operation
2-channel open-loop control
CONFIGURE (CONTINUE)
CHANNEL 2
MIN PUMP RANGELower threshold of flow rate range [L/h]
MAX PUMP RANGEUpper threshold of flow rate range [L/h]
0/4...20MASelection of transfer range according to pump input
CONTROL CYCLEControl cycle comprising on- and off-time (see 4.5.6, page 33)[s]
MIN RUNTIMEMinimum on-time of pump (refer to 4.5.6, page 33) [s]
FLOW RATE
CHANNEL 1
MIN Q-INFLUENTMinimum flow rate in inlet according to measurement signal [m³/h]
MAX Q-INFLUENTMaximum flow rate in inlet according to measurement signal [m³/h]
0/4...20MA
MIN RET SLUDGEMinimum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
Transfer range of 0/4–20 mA current loop, as set in the connected flow measuring
instrument.
MAX RET SLUDGEMaximum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34)[m³/h]
Ratio between measured flow rate and return activated sludge volume, for a return
Q RET RATIO
Q INFL SMOOTHSmoothing of influent signal (refer to 4.5.7, page 34)
CHANNEL 2
MIN Q-INFLUENTMinimum flow rate in inlet according to measurement signal [m³/h]
MAX Q-INFLUENTMaximum flow rate in inlet according to measurement signal [m³/h]
0/4...20MA
MIN RET SLUDGEMinimum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
MAX RET SLUDGEMaximum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34)[m³/h]
Q RET RATIO
Q INFL SMOOTHSmoothing of influent signal (refer to 4.5.7, page 34)
activated sludge volume proportional to the measured flow rate (Refer to 4.5.7,
page 34)
Transfer range of 0/4–20 mA current loop, as set in the connected flow measuring
instrument.
Ratio between measured flow rate and return activated sludge volume, for a return
activated sludge volume proportional to the measured flow rate (Refer to 4.5.7,
page 34)
[%]
[%]
22
Page 23
Parameterization and operation
2-channel open-loop control
CONFIGURE (CONTINUE)
PRECIPITANT
CHANNEL 1
METAL CONTENTMetal concentration in precipitant (refer to 4.5.8, page 35) [g/L]
ATOMIC WEIGHTRelative atomic weight of active precipitant substance (refer to 4.5.8, page 35) [g/mol]
CHANNEL 2
METAL CONTENTMetal concentration in precipitant (refer to 4.5.8, page 35) [g/L]
ATOMIC WEIGHTRelative atomic weight of active precipitant substance (refer to 4.5.8, page 35) [g/mol]
MODBUS
Start address of an RTC module within the MODBUS network. Default is 41. This
ADDRESS
DATA ORDER
DATALOG INTRVLIndicates the interval in which the data is saved in the log file. [min]
setting must only be changed by the manufacturer's service department (Section 8).
(Refer to Appendix A, page 47)
Specifies the register order within a double word. Default is NORMAL. This setting
must only be changed by the manufacturer's service department (Refer to
Section 8)
MAINTENANCE
RTC DATA
RTC MEASUREMENDisplays up to 5 measured values; additional values can be selected by scrolling.
RTC ACTUAT VAR
DIAG/TEST
EEPROMHardware test
RTC COMM TOCommunication time-out
RTC CRCCommunication checksum
LOCATION
SOFTWARE VERSIONVersion number for service
RTC MODEIndicates the mode set in the RTC module.
Displays up to 5 actuating variables; additional variables can be selected by
scrolling.
A location name can be assigned here for better identification of the RTC module,
e.g. activation 2.
23
Page 24
Parameterization and operation
4.3.51-channel closed-loop control
1-channel closed-loop control
CONFIGURE
SELECT SENSOR
CLOSED-LOOP
SETPOINT PO4-PDesired orthophosphate value in effluent (refer to 4.5.1, page 31) [mg/L]
GAIN P CONTR.Proportional gain of the closed-loop control (refer to 4.5.5, page 32)
INTEGRALTIMEIntegral time of closed-loop control (refer to 4.5.5, page 32)[min]
DERIVATIVE TIMEDerivative time of closed-loop control (refer to 4.5.5, page 32)[min]
MIN DOS RATEMinimum flow rate of dosing pump [L/h]
PRESELECT PROGPrograms 1 to 4 (refer to 4.1, page 15)
PROFILEActive when a measurement signal fails
Q-PROFILE
P-PROFILEDaily profiles of PO4-P concentrations, 2 h average (see 4.5.4, page 32) [mg/L]
WEEK PROFILEPercentage daily averages of the phosphate load (refer to 4.5.4, page 32) [%]
IN- OUTPUTS
DOSING PUMP
MIN PUMP RANGELower threshold of flow rate range [L/h]
Select the sensor installed for the closed-loop control (refer to Section 4.4, page 29).
Daily profiles (2 h average) of waste water influent according to feed measurement
signal
[m³/h]
MAX PUMP RANGEUpper threshold of flow rate range [L/h]
0/4...20MASelection of transfer range according to pump input
CONTROL CYCLEControl cycle comprising on- and off-time (see 4.5.6, page 33)[s]
MIN RUNTIMEMinimum on-time of pump (refer to 4.5.6, page 33) [s]
FLOW RATE
MIN Q-INFLUENTMinimum flow rate in inlet according to measurement signal [m³/h]
MAX Q-INFLUENTMaximum flow rate in inlet according to measurement signal [m³/h]
0/4...20MATransfer range of 0/4–20 mA current loop, as set in the connected flow measuring instrument.
MIN RET SLUDGEMinimum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
MAX RET SLUDGEMaximum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34)[m³/h]
Ratio between measured flow rate and return activated sludge volume, for a return
Q RET RATIO
Q INFL SMOOTHSmoothing of influent signal (refer to 4.5.7, page 34)
activated sludge volume proportional to the measured flow rate (Refer to
page 34)
4.5.7,
[%]
24
Page 25
Parameterization and operation
1-channel closed-loop control
CONFIGURE (CONTINUE)
PRECIPITANT
METAL CONTENTMetal concentration in precipitant (refer to 4.5.8, page 35) [g/L]
ATOMIC WEIGHTRelative atomic weight of active precipitant substance (refer to 4.5.8, page 35) [g/mol]
MODBUS
Start address of an RTC module within the MODBUS network. Default is 41. This
ADDRESS
DATA ORDER
DATALOG INTRVLIndicates the interval in which the data is saved in the log file. [min]
MAINTENANCE
RTC DATA
RTC MEASUREMENDisplays up to 5 measured values; additional values can be selected by scrolling.
RTC ACTUAT VARDisplays up to 5 actuating variables; additional variables can be selected by scrolling.
setting must only be changed by the manufacturer's service department (Section 8).
(Refer to Appendix A, page 47)
Specifies the register order within a double word. Default is NORMAL. This setting
must only be changed by the manufacturer's service department (Refer to Section 8)
DIAG/TEST
EEPROMHardware test
RTC COMM TOCommunication time-out
RTC CRCCommunication checksum
LOCATION
SOFTWARE VERSIONVersion number for service
RTC MODEIndicates the mode set in the RTC module.
A location name can be issued here for better identification of the RTC module, e.g.
activation
2.
4.3.62-channel closed-loop control
In addition to the 1-channel version, a 2-channel version is also
available, which enables separate closed-loop control of two
phosphate precipitants.
All of the key parameters appear twice and are identified as
channel 1 and channel 2.
In contrast to the 1-channel version, a percentage factor for
distribution of the profile (
measurement signals drop out, the percentage factor
PROFILE
distributes the influent waste water to the precipitant.
DIST PROFILE) has been added. If
DIST
25
Page 26
Parameterization and operation
2-channel closed-loop control
CONFIGURE
SELECT SENSORSelect the sensors installed for the closed-loop control (see Section 4.4, page 29).
CLOSED-LOOP
CHANNEL 1
SETPOINT PO4-PDesired orthophosphate value in effluent (refer to 4.5.1, page 31) [mg/L]
GAIN P CONTR.Proportional gain of the closed-loop control (refer to 4.5.5, page 32)
INTEGRALTIMEIntegral time of closed-loop control (refer to 4.5.5, page 32)[min]
DERIVATIVE TIMEDerivative time of closed-loop control (refer to 4.5.5, page 32)[min]
MIN DOS RATEMinimum flow rate of dosing pump [L/h]
PRESELECT PROGPrograms 1 to 4 (refer to 4.1, page 15)
CHANNEL 2
SETPOINT PO4-PDesired orthophosphate value in effluent (refer to 4.5.1, page 31) [mg/L]
GAIN P CONTR.Proportional gain of the closed-loop control (refer to 4.5.5, page 32)[%]
INTEGRALTIMEIntegral time of closed-loop control (refer to 4.5.5, page 32)[%]
DERIVATIVE TIMEDerivative time of closed-loop control (refer to 4.5.5, page 32)
MIN DOS RATEMinimum flow rate of dosing pump [L/h]
PRESELECT PROGPrograms 1 to 4 (refer to 4.1, page 15)
PROFILEActive when a measurement signal fails
Q-PROFILE
DIST PROFILEPercentage distribution of flow rate; input refers to channel 1.[%]
P-PROFILEDaily profiles of PO
WEEK PROFILEPercentage daily averages of the phosphate load (refer to4.5.4, page 32) [%]
Daily profiles (2 h average) of waste water influent according to feed measurement
signal
-P concentrations, 2 h average (see 4.5.4, page 32) [mg/L]
4
[m³/h]
26
Page 27
Parameterization and operation
2-channel closed-loop control
CONFIGURE (CONTINUE)
IN- OUTPUTS
DOSING PUMP
CHANNEL 1
MIN PUMP RANGELower threshold of flow rate range [L/h]
MAX PUMP RANGEUpper threshold of flow rate range [L/h]
0/4...20MASelection of transfer range according to pump input
CONTROL CYCLEControl cycle comprising on- and off-time (see 4.5.6, page 33)[s]
MIN RUNTIMEMinimum on-time of pump (refer to 4.5.6, page 33) [s]
CHANNEL 2
MIN PUMP RANGELower threshold of flow rate range [L/h]
MAX PUMP RANGEUpper threshold of flow rate range [L/h]
0/4...20MASelection of transfer range according to pump input
CONTROL CYCLEControl cycle comprising on- and off-time (see 4.5.6, page 33)[s]
MIN RUNTIMEMinimum on-time of pump (refer to 4.5.6, page 33) [s]
FLOW RATE
CHANNEL 1
MIN Q-INFLUENTMinimum flow rate in inlet according to measurement signal [m³/h]
MAX Q-INFLUENTMaximum flow rate in inlet according to measurement signal [m³/h]
0/4...20MATransfer range of 0/4–20 mA current loop, as set in the connected flow measuring instrument
MIN RET SLUDGEMinimum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
MAX RET SLUDGEMaximum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34)[m³/h]
Ratio between measured flow rate and return activated sludge volume, for a return
Q RET RATIO
Q INFL SMOOTHSmoothing of influent signal (refer to 4.5.7, page 34)
CHANNEL 2
MIN Q-INFLUENTMinimum flow rate in inlet according to measurement signal [m³/h]
MAX Q-INFLUENTMaximum flow rate in inlet according to measurement signal [m³/h]
0/4...20MA
activated sludge volume proportional to the measured flow rate (Refer to 4.5.7,
page 34)
Transfer range of 0/4–20 mA current loop, as set in the connected flow measuring
instrument.
[%]
MIN RET SLUDGEMinimum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34) [m³/h]
MAX RET SLUDGEMaximum flow rate of return activated sludge pump(s) (refer to 4.5.7, page 34)[m³/h]
Ratio between measured flow rate and return activated sludge volume, for a return
Q RET RATIO
Q INFL SMOOTHSmoothing of influent signal (refer to 4.5.7, page 34)
activated sludge volume proportional to the measured flow rate (Refer to 4.5.7,
page 34)
[%]
27
Page 28
Parameterization and operation
2-channel closed-loop control
CONFIGURE (CONTINUE)
PRECIPITANT
CHANNEL 1
METAL CONTENTMetal concentration in precipitant (refer to 4.5.8, page 35) [g/L]
ATOMIC WEIGHTRelative atomic weight of active precipitant substance (refer to 4.5.8, page 35) [g/mol]
CHANNEL 2
METAL CONTENTMetal concentration in precipitant (refer to 4.5.8, page 35) [g/L]
ATOMIC WEIGHTRelative atomic weight of active precipitant substance (refer to 4.5.8, page 35) [g/mol]
MODBUS
Start address of an RTC module within the MODBUS network. Default is 41. This
ADDRESS
DATA ORDER
DATALOG INTRVLIndicates the interval in which the data is saved in the log file. [min]
setting must only be changed by the manufacturer's service department (Section 8).
(Refer to Appendix A, page 47)
Specifies the register order within a double word. Default is NORMAL. This setting
must only be changed by the manufacturer's service department (Refer to
Section 8)
MAINTENANCE
RTC DATA
RTC MEASUREMENDisplays up to 5 measured values; additional values can be selected by scrolling.
RTC ACTUAT VARDisplays up to 5 actuating variables; additional variables can be selected by scrolling.
DIAG/TEST
EEPROMHardware test
RTC COMM TOCommunication time-out
RTC CRCCommunication checksum
LOCATION
SOFTWARE VERSIONVersion number for service
RTC MODEIndicates the mode set in the RTC module.
A location name can be assigned here for better identification of RTC module, e.g.
activation 2.
28
Page 29
4.4Select sensors
Figure 4 Select sensor
Parameterization and operation
1.To select the sensors and their sequence for the RTC
module, press RTC > CONFIGURE > SELECT SENSOR.
1ENTER — Saves the setting and returns to the
CONFIGURE menu.
2CANCEL — Returns to the CONFIGURE menu without
saving.
3ADD — Adds a new sensor to the selection.
2.Press ADD (Figure 4, item 3).
A selection list of all subscribers to the sc1000 network
opens.
3.Press the required sensor for the RTC module and confirm
by pressing
Sensors in black type are available for the RTC module.
Sensors in red type are not available for the RTC module.
Note: PROGNOSYS is available for sensors marked (p) if these
sensors have been selected in conjunction with an RTC module
(refer to the PROGNOSYS user manual).
4DELETE — Removes a sensor from the selection.
5UP/DOWN — Moves the sensors up or down.
ENTER below the selection list.
29
Page 30
Parameterization and operation
4.The selected sensor is shown in the sensor list.
Press ADD (Figure 4, item 3) to open the selection list again.
5.Select the second sensor for the RTC module and confirm
by pressing
Note: Previously selected sensors are shown in gray.
The selected sensors are shown in the sensor list.
ENTER below the selection list.
6.To sort the sensors in the order specified for the RTC
module, press the sensor and use the arrow keys to move it
(
Figure 4, item 5).
Press DELETE (Figure 4, item 4) to remove an incorrect
sensor from the sensor list again.
7.Press ENTER (Figure 4, item 1) to confirm the list once it is
finished.
30
Page 31
4.5Explanations
4.5.1Ortho-phosphate and total phosphate
The goal of phosphate control is to reduce the total phosphate in
the effluent stream at a waste water treatment plant. However,
the precipitation only affects the ortho-phosphate content. The
PO
-P target value specifies the ortho-phosphate value to be
4
maintained in the precipitation reactor. Therefore, this value must
be lower than the value to be maintained in the effluent.
Note: If CLOSED-LOOP is set in the controller, the setpoint is effective
immediately. If
effluent concentration of the reactor is required.
4.5.2Recycling the chemical sludge
Precipitant savings can be achieved, particularly in activated
sludge plants, if existing chemical sludge is reused for
phosphorus elimination. In the case of precipitant overdosage,
the stoichiometrically excessive metal content (for metal
phosphate formation) is reused in the formation of metal
phosphate upon renewed contact with dissolved phosphate.
Renewed adsorption of phosphate, by precipitates already
formed, is possible. The existing precipitant·sludge portion thus
represents a reserve for the precipitation of P-influent peaks or
for a short-term failure of the dosing devices; however, other
authors consider this reserve to be minimal.
Parameterization and operation
OPEN-LOOP is set in the controller, the desired PO
-P
4
The precipitant savings automatically take effect for closed-loop
controls. To be able to use the reserve for open-loop controls
as well, the correction (
input reduces the precipitant dosing:
In the event of negative influences on the phosphate
precipitation, a positive correction value can be entered:
4.5.3Biological phosphate elimination
The BIO-P parameter is used to take biological phosphate
elimination into account. If no phosphate elimination is effective at
the phosphate measuring point, the
specify the percentage of influent phosphates that is biologically
incorporated into the sludge on an empirical basis. In this case, it
is important to differentiate between the measurement of
ortho-phosphate and total phosphate. For total phosphate, the
"unavoidable" biological phosphate elimination must always be
taken into account. This can be set at 1 % of the BOD
increased biological phosphate elimination can be added in all
cases and must be estimated on the basis of empirical values.
CORR FACTOR)) can be used. A negative
Example:
A correction value of –50 % is set.
This reduces the precipitant dosing by half.
Example:
A correction value of +100 % is set.
This doubles the precipitant dosing.
BIO-P factor can be used to
. An
5
31
Page 32
Parameterization and operation
4.5.4Phosphate profile
The same conditions as specified under 4.5.3, page 31 must
apply for the phosphate flow rate profile. If biological phosphate
elimination is still not effective at the measuring point, the flow
profile rate remains unaffected by the biological phosphate
elimination. If biological phosphate elimination is already effective
at the measuring point, this must also be reflected in the profile.
Note: In this case, the value zero (0) must be entered as Bio P
proportion!
For open-loop controls, the results of the online measurement
can be directly employed in the profile determination. This also
ensures that the measurement conditions are identical.
Due to missing data, the configuration for closed-loop controls
is more complex. A reliable data pool for a waste water treatment
plant can only be obtained on the basis of 2 h composite
samples. Any samples that were taken during unusual influent
events (heavy rains, unauthorized discharge) are excluded.
A sample unaffected by precipitation can only be taken from the
influent to the activated sludge plant. At this point, the organic
phosphorous has not yet hydrolyzed. If total phosphate is
determined here, the "unavoidable" biological phosphate
elimination must be considered.
Since the entry of a Bio-P amount is not possible for closed-loop
controls (option hidden), lower values can be entered directly. If
the online measurement fails, it is safer to forego a reduction.
Over the course of a week, there can be strong fluctuations in the
load on the waste water treatment plant. To ensure an accurate
representation of actual conditions, the daily profiles can be
superimposed with a weekly profile.
The proportional precipitant dosing quantity calculated by the
RTC module is increased or reduced by the proportional
intensification factor (
As the precipitant has already become effective at the measuring
point, the measurement indicates the following:
•The dosage is too low
•The dosage is sufficient
•The dosage is too high and must be corrected
accordingly
The proportional gain factor specifies the precipitant dosage
required based on the exceedance of the target value. Large
gains result in large changes to the dosing and therefore a high
closed-loop control speed; however, the closed-loop control
oscillations also increase in line with the gain.
GAIN P CONTR.) of the closed loop control.
32
The
DERIVATIVE TIME allows the RTC module to react not only
to the absolute target value deviations but also to the speed with
which the phosphate content rises or falls. Necessary corrections
can thus be made at an earlier stage.
Page 33
Parameterization and operation
Example:
A derivative time of 1 minute means that closed-loop control
takes place according to the phosphate concentration that is
actually achieved in only 1
value change remains the same).
The integration time takes effect by means of the temporal
integration of the control deviation (PO
actual value), to the actuating variable with the weighting by the
INTEGRALTIME. The integral time states when the integral
proportion has the same effect as the P proportion. A short
timeframe can lead to an overshoot or strong oscillations of the
PO
-P concentration. An increase in the integral time reduces the
4
oscillation. In this case, the I proportion of the closed-loop control
can be specified through the entry of
minute (if the current measured
-P setpoint to PO4-P
4
INTEGRAL TIME = 0.
4.5.6Pump runtime
Setting tips: As a
DERIVATIVE TIME >0 min has a highly
significant impact on the metered precipitant quantity, this should
be used only in exceptional cases, e.g. plants demonstrating
rapid escalations in PO
-P concentrations.
4
To ensure the metered precipitant quantity increases/decreases
more quickly, the
INTEGRALTIME reduced. To ensure the metered quantity
changes more slowly, the
INTEGRAL TIME increased.
GAIN P CONTR. must be increased or the
GAIN P CONTR. must be reduced or the
The on/off duration in pulse/pause mode can be influenced via
the control cycle time (
CONTROL CYCLE). For example, with a
cycle time of 100 seconds and a dosing control value of 60 %, the
dosing pump is periodically switched on for 60 seconds and off
for 40 seconds. Short cycle times increase the switch frequency,
but enable more precise adaptation to individual requirements.
A minimum on-time is also configured to protect the dosing pump.
The pump is not activated for less than this time span. The time
must be a fraction of the control cycle time.
33
Page 34
Parameterization and operation
4.5.7Inclusion of return sludge quantity
To be able to record the entire flow at the measuring point, the
return sludge quantity must also be taken into account,
depending on the specific application. For this purpose, the
minimum and maximum flow rate of the return activated sludge
pump(s) can be specified, as well as the ratio of return activated
sludge transport relative to the measured flow rate.
The flow rate, e.g. for simultaneous precipitation with a
measuring point in the activated sludge tank, is calculated as
follows:
Q RS
which the calculated return activated sludge volume is varied
according to Q RS
If the measuring location is at a measuring point that is not
influenced by the return activated sludge volume, all variables
described below must be set to "
Q
= Qto + QRSL
total
Where: QRLS = QRS
ratio
Within the limits of Q RS
minimum
and Q RS
ratio
maximum
.
× Qto
minimum
and Q RS
maximum
thus represent the limits within
0".
Under
MIN RET SLUDGE, the minimum flow rate of the return
sludge pump(s) must be specified in m³/h. In the case of a
constant return sludge flow rate, the relevant value must also be
specified here.
Under
MAX RET SLUDGE, the maximum flow rate of the return
sludge pump(s) must be specified in m³/h. If a constant return
activated sludge volume is pumped, Q RS
"
0".
maximum
can be set to
In the event of a return activated sludge volume that is
proportional to the flow rate (Q), the percentage ratio must be
specified under
Q RET RATIO. If the same return activated sludge
volume is pumped continuously, this volume must be specified
under Q RS
minimum
. The Q RS
must then be selected as "0".
ratio
A heavily fluctuating flow rate signal (e.g. caused by pumping
stations) that is integrated in the RTC module via the 4-20 mA
current loop can be smoothed using
Q INFL SMOOTH. As a result,
only a marginally fluctuating target value is issued.
Q INFL SMOOTH can lie between 1 and 99.
•Q INFL SMOOTH = 1. The influent signal is not smoothed.
•Q INFL SMOOTH = 2. The influent signal is smoothed over 3
minutes.
34
•Q INFLUENT SMOOTH = 3. The influent signal is smoothed
over 2 minutes.
•Q INFLUENT SMOOTH = 5. The influent signal is smoothed
over 12 minutes.
•Q INFLUENT SMOOTH = 10. The influent signal is smoothed
over 25 minutes.
Example:
Page 35
4.5.8Precipitants
4.5.8.1Metal content
Parameterization and operation
With the setting Q INFLUENT SMOOTH = 2, it takes three
minutes for the smoothed value to reach 95
value (following a sudden change of the influent rate).
For calculations, the effective metal content of the precipitant
must be specified in g/l as well as the relative atomic weight of
the metal in g/mol.
The metal content (active component) of the precipitant is
specified by the manufacturer in:
•g/kg
multiply the value by the density δ of the product to obtain the
metal content in g/L
•%
multiply the value by 10 to obtain the concentration in g/kg.
Multiply this value by the density δ of the product to obtain the
metal content in g/L
•mol/L
This value can be entered instead of the concentration in g/L.
Enter a 1 for the atomic weight of the metal.
% of the final
4.5.8.2Atomic weight of metal
The type of the precipitant is determined by the atomic weight.
Atomic weight of iron: 55.8 g/mol
Atomic weight of aluminum: 26.9 g/mol
Composite products
For products that contain both aluminum and iron, the molar
metal concentration is calculated from the sum of the molar
concentrations of iron and aluminum.
Example: Compound of iron (12 %) and aluminum (8 %):
Molar aluminum concentration:
80
26.9
g
kgmol
=2.97
gkg
mol
Molar iron concentration:
120
55.8
g
kgmol
=2.15
gkg
mol
35
Page 36
Parameterization and operation
Molar metal concentration for a compound of iron (12 %) and
aluminum (8 %):
2.79
mol
+2.15
kgkgkg
mol
=5.12
mol
A conversion is performed with the product density for entry in the
RTC module:
1.43
kg
×5.12
Lkg L
mol
=7.32
mol
The product of the molar concentration [mol/kg] and the density
of the product [kg/L] yields the molar metal concentration in
mol/L. As stated above, this numerical value must be entered for
the metal content. Enter a 1 for the atomic weight of the metal.
36
Page 37
Section 5Maintenance
Multiple hazards
Only qualified personnel must conduct the tasks described in this section of the manual.
5.1Maintenance schedule
IntervalMaintenance task
DANGER
Visual inspection
CF card2 years
Battery, type CR2032
Panasonic or Sanyo
Application-specificCheck for contamination and corrosion
5 yearsReplacement
Replacement by manufacturer's service department
(Section 8)
37
Page 38
Maintenance
38
Page 39
Section 6Troubleshooting
6.1Error messages
The sc controller displays the possible sensor errors.
No communication between RTC and RTC
communication card
Interrupted communication between RTC and
RTC communication card
The sensor selection of the RTC was deleted
by deleting or selecting a new sc1000
participant.
Brief general read/write error on the CF card,
mostly caused by a brief interruption to the
power supply.
Test connection cable
Reset the sc1000 and the RTC (switch so it is
completely voltage free and switch back on)
Make sure +/- connections of the connector
cable between RTC and RTC communication
card in the sc1000 are installed correctly.
From MAIN MENU > RTC MODULES /
PROGNOSYS > RTC MODULES > RTC >
CONFIGURE > SELECT SENSOR, select the
correct sensor for the RTC again and confirm.
Acknowledge error. If this message is shown
frequently, eliminate the cause of the power
disruptions. If necessary, inform the service
team of the manufacturer (Section8, page 43).
INFLUENT1 NOT G.Faulty measurement signalTest sensor, check cable connections
INFLUENT2 NOT G.Faulty measurement signalTest sensor, check cable connections
6.2Warnings
The sc controller displays the possible warning messages from the sensor.
Displayed warningsCauseResolution
The RTC menu
MODBUS ADDRESS
PROBE SERVICEA configured sensor is in service status.The sensor must exit service status.
This deletes the MODBUS address of the RTC
module.
PLANT CONFIG was opened.
OPEN THE MODBUS menu of the RTC module
and set the correct MODBUS address.
6.3Wear parts
DesignationNumber Service life
CF card, type RTC module1 piece2 years
Battery, type CR2032 Panasonic or Sanyo1 piece5 years
39
Page 40
Troubleshooting
40
Page 41
Section 7Replacement parts and accessories
7.1Spare parts
DescriptionCat. no.
NS 35/15 DIN rail, punched according to DIN EN 60715 TH35, made from galvanized steel.
Length: 35 cm (13.7 in)
90–240 V AC/24 V DC 0.75 A transformer, module for DIN rail assembly LZH166
Terminal for 24 V connection without power supplyLZH167
Grounding terminalLZH168
SUB-D connectorLZH169
C2 circuit breakerLZH170
CPU base module with Ethernet port, passive venting element (CX1010-0021) and RS422/485
interface module
Power supply module, consists of a bus coupler and a 24 V terminal module (CX1100-0002)LZH172
Digital output module 24 V DC (2 outputs) (KL2032)LZH173
Digital output module 24 V DC (4 outputs) (KL2134)LZH174
Analog output module (1 output) (KL4011)LZH175
Analog output module (2 outputs) (KL4012)LZH176
Analog input module (1 input) (KL3011)LZH177
Bus termination module (KL9010)LZH178
RTC communication cardYAB117
CF card type RTC moduleLZY748-00
Villa 14 – Rue 2 Casa
Plaisance
Quartier Racine Extension
MA-Casablanca 20000
Tél. +212 (0)522 97 95 75
Fax +212 (0)522 36 89 34
info-maroc@hach-lange.com
www.hach-lange.ma
44
Page 45
Section 9Warranty and liability
The manufacturer warrants that the supplied product is free of material and manufacturing
defects, and undertakes to repair or to replace any defective parts without charge.
The warranty period is 24 months. If a maintenance contract is taken out within 6 months
of purchase, the warranty period is extended to 60 months.
With the exclusion of further claims, the supplier is liable for defects, including the lack of
assured properties, as follows: all parts that, within the warranty period calculated from the
day of the transfer of risk, can be demonstrated to have become unusable or that can only
be used with significant limitations owing to circumstances prior to transfer of risk, in
particular due to incorrect design, substandard materials or inadequate finish, shall be
repaired or replaced at the supplier's discretion. The identification of such defects must be
reported to the supplier in writing as soon as possible, but no later than 7 days after the
discovery of the fault. If the customer fails to notify the supplier, the product is considered
approved despite the defect. Further liability for indirect or direct damages is not accepted.
If device-specific maintenance- or inspection work prescribed by the supplier is to be
performed within the guarantee period by the customer (maintenance) or by the supplier
(inspection) and these requirements are not met, claims for damages that result from
non-observance of these requirements are void.
Further claims, in particular for consequential damages, cannot be made.
Wear and damage caused by improper handling, incorrect installation or non-designated
use are excluded from this clause.
The process instruments of the manufacturer have proven their reliability in many
applications and are therefore often used in automatic control loops to enable the most
economical and efficient operation of the relevant process.
To avoid or limit consequential damage, it is therefore recommended that the control loop
be designed such that an instrument malfunction results in an automatic changeover to
the backup control system. This guarantees the safest operating condition both for the
environment and the process.
45
Page 46
Warranty and liability
46
Page 47
Appendix A MODBUS address setting
The same slave address for MODBUS communication must be set on both the sc1000
display and on the RTC101 P-Module. As 20 slave addresses are reserved for internal
purposes, the following slave addresses are available for assignment:
1, 21, 41, 61, 81, 101 etc.
Slave address 41 is preset at the factory.
NOTICE
If this slave address is must be changed because, for example, it is already assigned to another
RTC module , it must be edited on both the sc1000 and on the CF card of the RTC module.
This can only be done by the manufacturer service department (Section 8)!
47
Page 48
MODBUS address setting
48
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.