CALM System (All solenoids located in the lube panel)
Use needle tipped probes and take care not to touch probes tips together when checking voltage.
Set the meter to AC voltage.
In MDI command an M43 and press cycle start to unclamp the turret.
Measure the voltage to the clamp and unclamp solenoid. The solenoids are inside the CALM (consolidated air/lubrication
manifold) panel. The voltage should measure 120 VAC.
If there is no voltage, refer to:
• NEXT GENERATION CONTROL - I/O PCB - TROUBLESHOOTING GUIDE
With the turret clamped, rotate the turret back and
forth by hand. If there is movement in the turret the
die springs are broken and need to be replaced.
If the o-ring under the rear turret chip skirt fails it can cause binding and prevent the turret from rotating into position. A
failed o-ring will also allow for coolant and chip intrusion into the back side of the turret. In this case the turret should be
removed to clear the chips and inspected for possible damage.
A failed o-ring will also allow for coolant and chip intrusion into the back side of the turret. In this case the turret should be
removed to clear the chips and inspect for possible damage.
Alignment
If the turret is knocked out of alignment you may have to re-align the turret motor coupler.
Refer to SL-10/20/30, ST-10/10Y - MOTOR COUPLING - ALIGNMENT procedure.
If the turret is knocked out of alingment a full geometry inspection should be done. Make corrections as needed.
Servo Motor
Corrective Action:
The servo motor has an electrical fault. Possible failed motor, bad or contaminated cable connection, a damaged cable, or
failed amplifier.
Refer to SIGMA 1 - AXIS SERVO MOTOR AND CABLES - TROUBLESHOOTING GUIDE or SIGMA 5 - AXIS SERVO
MOTOR AND CABLES - TROUBLESHOOTING GUIDE for detailed information.
Page 5 of 5 pages
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.