H3C S6800-54QF, S6800-54HF Quick Start Manual

H3C S6800-54QF & S6800-54HF Switches Installation Quick Start-6W105 H3C S6800-54QF & S6800-54HF 交换机 快速安装指南-6W105
Tool list 工具参考
No installation tools are provided with the switch. Prepare them yourself as required.
交换机不随机提供安装工具,请用户根据实际安装需求自己准备安装工具。
ESD wrist strap
防静电腕带
Flathead screwdriver
一字螺丝刀
Phillips screwdriver
十字螺丝刀
Installation accessories 安装附件介绍
Type A 类型一 Type B 类型二
Mounting brackets and M4 screw
前挂耳和M4螺钉
Rack-mount rail kit A (with long slide rails)
长滑道和导轨
Type A 类型一
Filler module 假面板
Type B 类型二
M6 screw and cage nut
(user supplied)
M6 螺钉和浮动螺母(用户自备)
Rack-mount rail kit B
(with super-short slide rails) (optional)
超短滑道和导轨(选配)
Grounding cable
地线
记号笔
Grounding screw
接地螺钉
Rack-mount rail kit C (optional)
滑道和导轨(选配)
Cable tie
可拆卸式扎带
For an LS-6800-54QF-H3 switch, if the rack has a depth (distance between the front and rea r rack post s) in the range of 621 to 793 mm (24.45 to 31.22 in), use mounting brackets and rack-mount rail kit A. If the rack has a depth in the range of 330 to 505 mm (12.99 to 19.88 in), use mountin g brackets and rack-mount rail kit B (narrow-spacing insta llation of chassis ra ils). If the rack has a depth in the range of 438 to 632 mm (17.24 to 24.8 8 in), u se moun ting br ackets and ra ck-mo unt rail kit B (wide-spacing installation of chassi s rails) . For the other switch models, if the rack has a depth in the range of 621 to 854 mm (24.45 to 33.62 in), use mounting brackets and rack-mount rail kit A. If the rack has a depth in the range of 401 to 634 mm (15.79 to 24.96 in), use mounting brackets and rack-mount rail kit C.
对于LS-6800-54QF-H3机型, 挂耳与长滑道和导轨配合安装适用于机柜前后方孔条间距范围为621 793mm。挂耳与超短滑道和导轨配合安装到机柜时,滑道导轨有正向安装和反向安装两种方式:导轨
正向安装适用于机柜前后方孔条间距范围为330 范围为438 对于其他机型,挂耳与长滑道和导轨配合安装适用于机柜前后方孔条间距范围为621 与滑道和导轨配合安装适用于机柜前后方孔条间距范围为401
The mounting bracket and slide rail installat ion procedures are similar for the switches. The following procedures use an LS-6800-54QF-H3 switch. 交换机各款机型安装挂耳、长滑道或滑道到交换机的方 式相似,此处以产品代码为LS-6800-54QF-H3的机型为例。
Attaching the mounting brackets and chassis rails of rack-mount rail kit A to the switch
挂耳与长滑道的导轨配合安装
632mm
505mm;导轨反向安装适用于机柜前后方孔条间距
854mm。挂耳
634mm
Install the mounting brackets near the power module side 挂耳安装到靠近电源侧
Wear an ESD wrist strap, and make sure the strap makes good skin contact and is reliably grounded.
!
操作者需佩戴防静电腕带,确保防静电腕带与皮肤良好接触,并确认防静电腕带已经良好接地。
Mounting the switch in a rack 安装交换机到机柜
Attach the mounting brackets and chassis rails to the switch
1
安装挂耳和滑道导轨到交换机
Install the mounting brackets near the port side or power module side of the switch as needed. Attach the chassis rails to the switch based on the mounting bracket installation position and rack depth.
用户可以根据安装场景的需要,将挂耳安装在设备靠近端口侧或靠近电源侧,并根据机柜深度,在交换 机侧面板的对应位置安装滑道导轨。
Install the mounting brackets near the port side
挂耳安装到靠近端口侧
Use three screws to secure a mounting bracket at the port side. For the LS-6800-5 4QF-H3, use four screws. 产品代码为LS-6800-54QF-H3的机型,挂耳安装在靠近端口侧时,使用四颗螺钉安装挂耳。
其它机型请使用三颗螺钉将挂耳安装在靠近端口侧。
1
2
Attaching the mounting brackets and chassis rails of rack-mount rail kit B to the switch (applicable only to an LS-6800-54QF-H3 switch)
挂耳与超短滑道的导轨配合安装(只适用于LS-6800-54QF-H3的机型)
Install a mounting bracket (near the power module side) and a chassis rail (narrow-spacing installation)
挂耳安装到靠近电源侧、超短滑道的导轨正向安装
Install the switch in a 19-inch rack 安装交换机到19英寸机柜
3
Before installing cage nuts, mark their installation positions on the rack posts.
安装浮动螺母前,建议用户先使用记号笔在机柜立柱上标注浮动螺母安装位置。
Attach slide rails to the rack posts.
安装滑道到机柜
2
Attach cage nuts to the rack posts.
安装浮动螺母到机柜方孔条上
Mount the switch in the rack (two options)安装交换机到机柜(二选一) 以产品代码为LS-6800-54QF-H3的机型为例
1
Install a mounting bracket (near the port side) and a chassis rail (wide-spacing installation)
挂耳安装到靠近端口侧、超短滑道的导轨反向安装
To use rack-mount rail kit A or C for rack-mounting the switch, make sure the fr ont ends of the long slide rails or slide rails reach out of the chassis rails. To use rack-mount rail kit B for rack-mounting the switch, make sure the super-short slide rails slide a minimum length of 90 mm (3.54 in) into the chassis rails. 为保证设备安装后的稳定性,使用长滑道或滑道和配套的导轨安装完成后,请确保长滑道
或滑道的头部露出导轨。使用超短滑道和配套的导轨安装完成后,请确保超短滑道头部进入导轨的最小 深度为90mm
Ground the switch 安装地线到交换机
2
Correctly connecting the switch grounding cable is crucial to lightning prot ection and EMI protection.
!
交换机地线的正确连接是交换机防雷、防干扰的重要保障,请使用设备随机提供的保护地线正确接地。
Use the primary grounding point at the power module side 使用主接地点 (靠近电源侧)接地
Use the auxiliary grounding point at the port side 使用备用接地点 (靠近端口侧)接地
Mounting brackets near the power module side
挂耳安装在靠近电源侧
4
3
Connect the other end of the grounding cable to the grounding point on the rack
接地线另一端连接到机柜接地点
Mounting brackets near the port side
挂耳安装在靠近端口侧
4
3
Connect the other end of the grounding cable to the grounding point on the rack
接地线另一端连接到机柜接地点
Airflow direction of the switch 交换机的风向设计
Make sure the air inlet and outlet vents are not blocked and the in stallation site has a good ventilation system.
请确保交换机的进、出风孔不被遮挡,并将交换机安装在具有良好通风散热系统的环境中。
You can provide airflow for the switch from the port side to the power module side or from the power module side to the port side by installing different fan trays.
通过配置不同的风扇模块,可提供“端口侧到电源侧”和“电源侧到端口侧”两种气流方向,满足不 同环境下的散热要求。
The LSWM1FANSC and LSPM1FANSA blow air from the power module side to the port side. The LSWM1FANSCB and LSPM1FANSB draw air from the port side to the power module side. LSWM1FANSCLSPM1FANSA为吹风风扇,风向为电源侧进风,端口侧出风;LSWM1FANSCB
LSPM1FANSB为抽风风扇,风向为端口侧进风,电源侧出风。
3
4
Loading...