H3C LS-S5600-26F, LS-S5600-50C-OVS, S5600-26C, S5600-26C-PWR, S5600-26F Installation Manual

...
Page 1
H3C S5600 Series Ethernet Switches
Installation Manual
Hangzhou H3C Technologies Co., Ltd. http://www.h3c.com
Manual Version: T2-08045W-20071218-C-1.04
Page 2
Copyright © 2006-2007, Hangzhou H3C Techn ologies Co ., Ltd. a nd its licensors
All Rights Reserved
No part of this manual may be reproduced or transmitted in any form or by any means without prior written consent of Hangzhou H3C Technologies Co., Ltd.
Trademarks
H3C, , Aolynk, , H3Care,
, TOP G, , IRF, NetPilot, Neocean, NeoVTL, SecPro, SecPoint, SecEngine, SecPath, Comware, Secware, Storware, NQA, VVG, V
2
G, VnG, PSPT, XGbus, N-Bus, TiGem, InnoVision and
HUASAN are trademarks of Hangzhou H3C Technologies Co., Ltd. All other trademarks that may be mentioned in this manual are the property of their
respective owners.
Notice
The information in this document is subject to change without notice. Every effort has been made in the preparation of this document to ensure accuracy of the content s, but all statements, information, and recommendations in this document do not constitute the warranty of any kind, express or implied.
To obtain the latest information, please access: http://www. h3c.com
Technical Support
customer_service@h3c.com http://www. h3c.com
Page 3
About This Manual
Related Documentation
In addition to this manual, each H3C S5600 Series Ethernet Switches documentation set includes the following:
Manual Description
H3C S5600 Series Ethernet Switches Operation Manual
It is used for assisting the users in data configurations and typical applications.
H3C S5600 Series Ethernet Switches Command Manual
It is used for assisting the users in using various commands.
Organization
H3C S5600 Series Ethernet Switches Installation Manual is organized as follows:
Chapter Contents
1 Product Overview
Introduces the characteristics and technical specifications of S5600 Series Ethernet Switches.
2 Preparing for Installation
Introduces the installation preparation and precaution of S5600 Series Ethernet Switches.
3 Installing the Switch
Introduces the procedures to install an S5600 Series Ethernet Switch, including the setup of the mainframe, cards and cables.
4 Starting up the Switch at the Initial Boot
Introduces the booting process of an S5600 Series Ethernet Switch, including the power-on booting of the switch and the system initialization.
5 Loading Boot ROM and Host Software
Introduces how to load BootROM and host software for an S5600 Series Ethernet Switch.
6 Maintenance and Troubleshooting
Introduces the problems that might occur during the installation and the booting of an S5600 Series Ethernet Switch and the related solution.
7 Appendix A Lightning Protection of the Switch
Introduces lightning protection of S5600 Series Ethernet Switches.
Page 4
Conventions
The manual uses the following conventions:
I. GUI conventions
Convention Description
< >
Button names are inside angle brackets. For example, click <OK>.
[ ]
Window names, menu items, data table and field names are inside square brackets. For example, pop up the [New User] window.
/
Multi-level menus are separated by forward slashes. For example, [File/Create/Folder].
II. Symbols
Convention Description
Warning
Means reader be extremely careful. Improper operation may cause bodily injury.
Caution
Means reader be careful. Improper operation may cause data loss or damage to equipment.
Note Means a complementary description.
Environmental Protection
This product has been designed to comply with the requirements on environmental protection. For the proper storage, use and disposal of this product, national laws and regulations must be observed.
Page 5
Installation Manual H3C S5600 Series Ethernet Switches Table of Contents
i
Table of Contents
Chapter 1 Product Overview........................................................................................................1-1
1.1 Overview............................................................................................................................1-1
1.2 S5600-26C/S5600-26C-PWR/S5600-26F Ethernet Switch ..............................................1-2
1.2.1 Front Panel.............................................................................................................. 1-2
1.2.2 Rear Panel ............................................................................................................ 1-10
1.3 S5600-50C/S5600-50C-PWR Ethernet Switch ............................................................... 1-11
1.3.1 Front Panel............................................................................................................ 1-11
1.3.2 Rear panel.............................................................................................................1-12
1.4 Power system .................................................................................................................. 1-13
1.5 Cooling system ................................................................................................................ 1-13
1.6 Attributes of 1000 Mbps SFP port....................................................................................1-14
1.7 Expansion Module...........................................................................................................1-15
1.8 S5600 Series Technical Specifications ...........................................................................1-18
Chapter 2 Preparing for Installation............................................................................................2-1
2.1 Safety Precautions............................................................................................................. 2-1
2.2 Installation Site...................................................................................................................2-1
2.2.1 Temperature/Humidity.............................................................................................2-1
2.2.2 Cleanness ............................................................................................................... 2-2
2.2.3 Electromagnetic Susceptibility ................................................................................ 2-2
2.2.4 Laser Safety............................................................................................................2-3
2.3 Installation Tools................................................................................................................ 2-3
Chapter 3 Installing the Switch.................................................................................................... 3-1
3.1 Rack-Mounting the Switch................................................................................................. 3-1
3.1.1 Introduction to mounting ear ................................................................................... 3-1
3.1.2 Introduction to guide rail..........................................................................................3-2
3.1.3 Use front mounting ears and a tray......................................................................... 3-3
3.1.4 Use front and rear mounting ears ........................................................................... 3-4
3.1.5 Use front mounting ears and guide rails................................................................. 3-7
3.2 Mounting the Switch on a Tabletop/Workbench................................................................ 3-9
3.3 Installing/Removing the Power Module...........................................................................3-10
3.3.1 Installing the Power Module.................................................................................. 3-10
3.3.2 Removing the Power Module................................................................................ 3-10
3.4 Connecting the Power Cord and the Ground Wire.......................................................... 3-11
3.4.1 Connecting the AC-Input Power Cord................................................................... 3-11
3.4.2 Connecting the DC-Input Power Cord ..................................................................3-12
3.4.3 Connecting the Ground Wire.................................................................................3-13
3.5 Connecting the Switch to a Console Terminal................................................................. 3-16
Page 6
Installation Manual H3C S5600 Series Ethernet Switches Table of Contents
ii
3.5.1 Console Cable....................................................................................................... 3-16
3.5.2 Connecting the Console Cable ............................................................................. 3-16
3.6 Installing/Removing the Stack Cable............................................................................... 3-17
3.6.1 Stack Cable........................................................................................................... 3-17
3.6.2 Installing the Stack Cable......................................................................................3-17
3.6.3 Removing the Stack Cable....................................................................................3-18
3.7 Installing/Removing the Optional Interface Module......................................................... 3-18
3.8 Verifying Installation......................................................................................................... 3-19
Chapter 4 Starting up the Switch at the Initial Boot .................................................................. 4-1
4.1 Setting up a Configuration Environment............................................................................4-1
4.2 Connecting the Console Cable.......................................................................................... 4-1
4.3 Setting Terminal Parameters............................................................................................. 4-1
4.4 Booting the Switch.............................................................................................................4-4
4.4.1 Verifying Installation before Power-up .................................................................... 4-4
4.4.2 Powering up the Switch........................................................................................... 4-4
Chapter 5 Loading Boot ROM and Host Software ..................................................................... 5-1
5.1 Introduction to Loading Approaches..................................................................................5-1
5.2 Loading Software Locally...................................................................................................5-1
5.2.1 Boot Menu............................................................................................................... 5-1
5.2.2 Loading Software from Console Port Using XModem............................................5-3
5.2.3 Loading Software from an Ethernet Port Using TFTP ............................................ 5-7
5.2.4 Loading Software from an Ethernet Port Using FTP...............................................5-9
5.3 Loading Software Remotely.............................................................................................5-10
5.3.1 Loading Software Remotely Using FTP................................................................5-10
5.3.2 Loading Software Remotely Using TFTP..............................................................5-11
Chapter 6 Maintenance and Troubleshooting............................................................................ 6-1
6.1 Dealing with Loading Failures............................................................................................6-1
6.2 Dealing with Password Loss..............................................................................................6-1
6.3 Dealing with Power System Failures.................................................................................6-1
6.4 Dealing with Configuration System Failures......................................................................6-1
Page 7
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-1
Chapter 1 Product Overview
1.1 Overview
H3C S5600 Series Ethernet Switches are high-performance, high-density, easy-to-install, NMS-manageable intelligent Ethernet switches which support wire-speed Layer2/3 switching.
Table 1-1 lists the models of H3C S5600 Series Ethernet Switches.
Table 1-1 Models of H3C S5600 Series Ethernet Switches
Model
Number of
10/100/1000M
electrical ports
Number of
1000M SFP
optical ports
Number of
Console ports
S5600-26C S5600-26C-PWR
24 4
S5600-26F 4 24 S5600-50C S5600-50C-PWR
48 4
1
Each SFP port and the corresponding 10/100/1000M Ethernet port form a Combo port. For each Combo port, the SFP port and the 10/100/1000M Ethernet port cannot be used at the same time. For the relationship between the Combo ports and the Ethernet ports, refer to
Table 1-2.
Table 1-2 Combo port list
Switch model Combo Port Corresponding port
25 22 26 24 27 21
S5600-26C/S5600-26C
-PWR/S5600-26F 28 23
49 46 50 48 51 45
S5600-50C/S5600-50C
-PWR 52 47
Page 8
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-2
Note:
z The electrical ports of S5600-26C-PWR/S5600-50C-PWR are capable of sup plying
-48 VDC power to remote PDs (powered devices, such as S2016C, S2008B, S2016B, S2016-EI, and so on).
z The S5600-26C-PWR/S5600-50C-PWR adopts PoE power module, which provides
AC/DC power to PD devices. When delivering the AC input, the module can supply up to 300 W power. If more power is needed, use the DC input or both AC and DC inputs to ensure the operation of all the connected devices.
z The S5600-26C-PWR/S5600-50C-PWR can also adopt AC/DC dual input power
module. In this case, however, the two types of switches have no PoE function. And they function exactly like the S5600-26C and S5600-50C.
1.2 S5600-26C/S5600-26C-PWR/S5600-26F Ethernet Switch
1.2.1 Front Panel
I. Front panel
The S5600-26C/S5600-26C-PWR provides 24 x 10/100/1000Base-TX Ethernet ports, one Console port, and four 1000 Mbps SFP Combo ports on its front panel. Each SFP port and the corresponding 10/100/1000M Ethernet port form a Combo port. For each Combo port, the SFP port and the 10/100/1000M Ethernet port cannot be used at the same time. For the relationship between the Combo ports and the Ethernet port s, refer to
Table 1-2.
Figure 1-1 shows the front panel of an S5600-26C Ethernet switch.:
(1) 10/100/1000M auto-negotiation Ethernet port status LEDs (2) 1000 Mbps SFP Combo port LED (3) Console port (4) 7-segment digitron display (5) Power LED (6) DC LED (7) Fabric LED (8) Module LED (9) Port mode LED (10) Mode button
Figure 1-1 Front panel of the S5600-26C/S5600-26C-PWR
Page 9
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-3
The S5600-26F provides 24 x 1000 Mbps SFP optical port s, one Console port, and four 1000 Mbps RJ-45 Combo ports on it s front panel. Each SFP port an d the corresponding 10/100/1000M Ethernet port form a Combo port. For each Combo port, the SFP port and the 10/100/1000M Ethernet port cannot be used at the same time. For the relationship between the Combo ports and the Ethernet ports, refer to
Table 1-2.
Figure 1-2. shows the front panel of an S5600-26F Ethernet switch.:
(1) SFP optical port status LED (2) 10/100/1000M auto-negotiation Ethernet port status LEDs: left one for speed, right one for duplex mode (3) Console port (4) 7-segment digitron display (5) Power LED (6) RPS LED (7) Fabric LED (8) Module LED
Figure 1-2 Front panel of the S5600-26F
II. LEDs
The S5600-26C/S5600-26C-PWR provides one power LED, one RPS LED, one fabri c LED, one module LED, one mode LED, one 7-segment digitron display, four pairs of 1000 Mbps SFP port status LEDs, and 24 pairs of 10/100/1000M port status LEDs on its front panel.
The S5600-26F provides one power LED, one RPS LED, one fabric LED, one module LED, one 7-segment digitron display , 24 pairs of 1000 Mbps SFP port status LEDs, and four pairs of 10/100/1000M auto-negotiation Ethernet port status LEDs on its front panel.
Table 1-3 and Table 1-4 describe respectively the LEDs on the S5600-26C/S5600-26C-PWR and S5600-26F.
Page 10
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-4
Table 1-3 LEDs on the S5600-26C/S5600-26C-PWR
LED Mark Status Description
Speed Solid green
The port status LEDs are showing the speed of each port.
Duplex Solid yellow
The port LEDs are showing the duplex mode of each port.
Mode LED Mode
PoE
Blinking green (at 1 Hz)
The port LEDs are showing the PoE status of each port.
Solid green The switch is started normally.
Blinking green (at 1 Hz)
The system is running power-on self-test (POST).
Solid red
The system fails the POST, or there is another fault.
Blinking yellow (at 1 Hz)
Some ports fail the POST and do not function.
Power LED
PWR
OFF The switch is power-off.
Solid green
Both the AC power supply and the DC input operate normally.
Solid yellow
The AC power supply fails or the AC input is disconnected, while the DC input operates normally.
DC LED RPS
OFF DC input is disconnected.
Green
The device is in the ring fabric status; the LED blinks quickly when the fabric port is receiving or sending data.
Yellow
The device is in the daisy chain fabric status; the LED blinks quickly when the fabric port is receiving or sending data.
Blinking green (at 3 Hz)
This device is isolated from the whole set of fabric devices (effective when this device is in the fabric status).
Fabric LED
STK
OFF
Neither of the two fabric ports is connected.
Page 11
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-5
LED Mark Status Description
Solid green
The module is seated and operates normally.
Blinking yellow
The module fails or is not supported.
Module LED
Module (MOD)
OFF No module is installed.
POST running
Blinking green
The POST ID of the in-process test is displayed:
POST failed
Blinking red
The POST ID of the failed test blinks.
Software downloading
Blinking green
A light bar rotates clockwise around the display during the downloading procedure.
Fan failed Solid red
An “F” is displayed.
Over temperature alarm
Solid red
A “t” is displayed.
Speed and duplex mode
Solid green
UNIT ID in the fabric; or “1” for a standalone unit is displayed.
7-segment digitron display
Unit
PoE mode
Solid green
The utilization of the power supply is displayed.
0 - 20%
21 - 40%
41 - 60%
61 - 80%
81 - 100%
Page 12
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-6
LED Mark Status Description
Green
The port is operating at 1000 Mbps. The LED blinks quickly when the port is receiving or sending data.
Yellow
The port is operating at 10/100 Mbps. The LED blinks quickly when the port is receiving or sending data.
Blinking yellow (at 3 Hz)
The port fails the POST.
Speed mode
OFF The port is not connected.
Green
The port is operating in full duplex mode. The LED blinks quickly when the port is receiving or sending data.
Yellow
The port is operating in half duplex mode. The LED blinks quickly when the port is receiving or sending data.
Blinking Yellow (3 Hz)
The port fails the POST.
Duplex mode
OFF The port is not connected. Solid
green
The port supplies power normally.
Blinking green (at 1 Hz)
The connected device requires more power than the maximum power a port can supply.
The port cannot supply power because the switch has reached its maximum power supplied.
Solid yellow
The port cannot supply power because the connected device is not a PD.
The port cannot supply power due to the power source failure of PoE.
Blinking yellow (3 Hz)
The port fails the POST.
10/100/ 1000M auto­negotiation Ethernet port status LED
PoE mode
OFF The port does not supply power.
Page 13
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-7
LED Mark Status Description
Green
The port is operating at 1000 Mbps. The LED blinks quickly when the port is receiving or sending data.
Blinking yellow (3 Hz)
The port fails the POST.
Speed mode
OFF The port is not connected.
Green
The port is operating in 1000 Mbps full duplex mode. The LED blinks quickly when the port is receiving or sending data.
Blinking yellow (3 Hz)
The port fails the POST.
Duplex mode
OFF The port is not connected.
1000M Base SFP port mode LED
PoE mode OFF
Table 1-4 LEDs on the S5600-26F
LED Mark Status Description
Solid green The switch is started normally.
Blinking green (at 1 Hz)
The system is running power-on self-test (POST).
Solid red
The system fails the POST, or there is another fault.
Blinking yellow (at 1 Hz)
Some ports fail the POST and do not function.
Power LED
PWR
OFF The switch is power-off.
Solid green
Both the AC power supply and the DC input operate normally.
Solid yellow
The AC power supply fails or the AC input is disconnected, while the DC input operates normally.
DC LED RPS
OFF DC input is disconnected.
Page 14
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-8
LED Mark Status Description
Green
The device is in the ring fabric status; the LED blinks quickly when the fabric port is receiving or sending data.
Yellow
The device is in the daisy chain fabric status; the LED blinks quickly when the fabric port is receiving or sending data.
Blinking green (at 3 Hz)
This device is isolated from the whole set of fabric devices (effective when this device is in the fabric status).
Fabric LED
STK
OFF
Neither of the two fabric ports is connected.
Solid green
The module is seated and operates normally.
Blinking yellow
The module fails or is not supported.
Module LED
Module (MOD)
OFF No module is installed.
POST running
Blinking green
The POST ID of the in-process test is displayed:
POST failed
Blinking red
The POST ID of the failed test blinks.
Software downloading
Blinking green
A light bar rotates clockwise around the display during the downloading procedure.
Fan failed Solid red
An “F” is displayed.
Over temperature alarm
Solid red
A “t” is displayed.
7-segment digitron display
Unit
Speed and duplex mode
Solid green
UNIT ID in the fabric; or “1” for a standalone unit is displayed.
Page 15
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-9
LED Mark Status Description
Green
The port is operating at 1000 Mbps. The LED blinks quickly when the port is receiving or sending data.
Yellow
The port is operating at 10/100 Mbps. The LED blinks quickly when the port is receiving or sending data.
Blinking yellow (at 3 Hz)
The port fails the POST.
Speed mode
OFF The port is not connected.
Green
The port is operating in full duplex mode. The LED blinks quickly when the port is receiving or sending data.
Yellow
The port is operating in half duplex mode. The LED blinks quickly when the port is receiving or sending data.
Blinking Yellow (3 Hz)
The port fails the POST.
10/100/ 1000M auto­negotiation Ethernet port status LED
Duplex mode
OFF The port is not connected.
Green
The port is operating at 1000 Mbps. The LED blinks quickly when the port is receiving or sending data.
Blinking yellow (3 Hz)
The port fails the POST.
1000Base SFP optical port status LED
port status LED
OFF The port is not connected.
III. Console port
The S5600-26C/S5600-26C-PWR/S5600-26F provides an EIA/TIA-232-compliant Console port, which enables you to configure the switch from the local or remote site.
Table 1-5 Attributes of the Console port
Item Description
Connector RJ-45 Standard EIA/TIA-232
Page 16
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-10
Item Description
Baud rate 9600 bps (default), auto-negotiation is supported
Services
Connection to an ASCII terminal Connection to the serial port of a local terminal (a PC for
example) or a remote terminal (through a pair of modems) running terminal emulation software
1.2.2 Rear Panel
I. Rear panel
Note:
The ports of the AC/DC dual input power module and the PoE power module are exactly the same, so only one rear panel illustration is shown below.
The S5600-26C/S5600-26C-PWR/S5600-26F provides two sockets for pluggable power module, two fabric ports, one expansion slot, and one grounding screw on its rear panel, as shown in the following figure.
(1) AC-input power socket for the power module (2) Expansion module (3) Grounding screw (4) Fabric ports (5) Fabric port LEDs (6) RPS LED (7) DC-input power socket for the power module
Figure 1-3 Rear panel of the S5600-26C/S5600-26C-PWR/S5600-26F
II. Fabric port
The fabric port marked with “UP” connects to a port of the same type on an upstream device; the fabric port marked with “DOWN” connects to a port of the same type on a downstream device.
Page 17
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-11
Table 1-6 Fabric port LEDs
LED Mark Status Indicate
Solid green The fabric port is properly connected. Blinking
green
The fabric port is properly connected and the port is receiving or sending data.
Fabric port LED
UP(DOWN)
OFF The fabric port is disconnected.
1.3 S5600-50C/S5600-50C-PWR Ethernet Switch
1.3.1 Front Panel
I. Front panel
The S5600-50C/S5600-50C-PWR provides 48 x 10/100/1000Base-TX Ethernet ports, one Console port, and four 1000 Mbps SFP Combo ports on its front panel. Each SFP port and the corresponding 10/100/1000M Ethernet port form a Combo port. For each Combo port, the SFP port and the 10/100/1000M Ethernet port cannot be used at the same time. For the relationship between the Combo ports and the Ethernet port s, refer to
Table 1-2.
Figure 1-4 shows the front panel of an S5600-50C/S5600-50C-PWR Ethernet switch:
(1) 10/100/1000M auto-negotiation Ethernet port status LEDs (2) Console Port (3) 7-segment digitron display (4) Mode button (5) Mode LED (6) Power LED (7) RPS LED (8) Fabric LED (9) Module LED (10) 1000 Mbps SFP combo port LED
Figure 1-4 Front panel of the S5600-50C/S5600-50C-PWR
Page 18
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-12
II. LEDs
The S5600-50C/S5600-50C-PWR provides one power LED, RPS LED, fabric LED, module LED, mode LED, 7-segment digitron display, 1000 Mbps SFP port statu s LED, and auto-negotiation Ethernet port status LED on its front panel. The meaning of each LED is shown in
Table 1-3
III. Console port
The S5600-50C/S5600-50C-PWR provides an EIA/TIA-232-compliant console port, which enables you to configure the switch from the local or remote site. For the attributes of the port, refer to
Table 1-5.
1.3.2 Rear panel
I. Rear panel
Note:
The ports of the AC/DC dual input power module and the PoE power module are exactly the same, so only one rear panel illustration is shown below.
The S5600-50C/S5600-50C-PWR provides two sockets for pluggable power module, two fabric ports, one expansion slot, and one grounding screw on its rear panel, as shown in the following figure.
(1) AC-input power socket for the power module (2) Expansion module (3) Grounding screw (4) Fabric ports (5) Fabric port LEDs (6) RPS LED (7) DC-input power socket for the power module
Figure 1-5 Rear panel of the S5600-50C/S5600-50C-PWR
II. Fabric ports
For fabric ports and the meanings of their LEDs, refer to Table 1-6.
Page 19
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-13
1.4 Power system
z AC power input range
Rated voltage: 100 to 240 VAC; 50/60 Hz Max. voltage range: 90 to 264 VAC; 50/60 Hz
z DC power input range
Rated voltage: –48 to–60 V Max. voltage range: –36 to–72 V
z AC input of the PoE power module
Rated voltage: 100 to 240 VAC; 50/60 Hz Max. voltage range: 90 to 264 VAC; 50/60 Hz
z DC input of the PoE power module
Rated voltage: –53.5 V Max. voltage range: –52 to –55 V
Note:
The S5600-26C-PWR/S5600-50C-PWR must use the external PoE PSU recommended by H3C as its DC input, but not the -48VDC power supply generally available in the equipment room. Otherwise, the device may be damaged.
1.5 Cooling system
S3100-8TP-PWR-EI Ethernet switches each run two fans for heat dissipation. Table 1-7 S5600 Ethernet switches cooling system
(1)
Model S5600-26C S5600-26C-PWR S5600-26F
Cooling system
Two fans are for the device and two are for the power supply module.
Two fans are for the device and four are for the power supply module.
Four fans are for the device and two are for the power supply module.
Page 20
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-14
Table 1-8 S5600 Ethernet switches cooling system (2)
Model S5600-50C S5600-26C-PWR
Cooling system
Two fans are for the device and two are for the power supply module.
Two fans are for the device and four are for the power supply module.
1.6 Attributes of 1000 Mbps SFP port
The S5600-26C/S5600-26C-PWR/S5600-50C/S5600-50C-PWR provides 4 × 1000 Mbps SFP ports on it s front panel. The S5600 -26F provides 24 × 1000 Mbp s SFP ports on its front panel.
SFP modules allow for great flexibility in networking because they are hot swappable and user configurable.
Table 1-9 lists the available SFP modules that you can select as re quired:
Table 1-9 Optical port module
Type Model
SFP-GE-SX-MM850-A SFP-GE-LX-SM1310-A SFP-GE-LH40-SM1310 SFP-GE-LH40-SM1550
1000M SFP module
SFP-GE-LH70-SM1550
SFP module
SFP electrical interface module SFP-GE-T
Note:
z Only the optical module that H3C Technology provides or recommends can be
used.
z The types of SFP modules may vary with time. Consult H3C marketing personnel or
technical support personnel to obtain the latest information about SFP modules.
z For specifications of SFP modules, refer to H3C Low End Series Ethernet Switches
Pluggable Module Manual.
Page 21
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-15
1.7 Expansion Module
The S5600 Series Ethernet switches provide one expansion module slot on the rear panel. The expansion mode that can be used in this slot includes 8-port 1000 Mbps SFP module, 1-port 10 Gbps XENPAK module, and 2-port 10 Gbps XFP module.
I. 8-port 1000 Mbps SFP module
(1) Port status LEDs (2) SFP ports (3) Module power LED
Figure 1-6 8-port 1000 Mbps SFP module
This module provides eight 1000 Mbps SFP external optical/electrical ports.
z For an optical port, you can choose one of the following SFP modules according to
your needs.
Table 1-10 Optical port module supported by 8-port 1000 Mbps SFP module
SFP module
Central wavelength
Fiber specifications
Maximum transmission distance
SFP-GE-SX-MM850-A SFP-GE-LX-SM1310-A
SFP module 1000M SFP module
SFP-GE-LH40-SM1310
Note:
z The types of SFP modules may vary with time. Consult H3C marketing personnel or
technical support personnel to obtain the latest information about SFP modules.
z For specifications of SFP modules, refer to H3C Low End Series Ethernet Switches
Pluggable Module Manual.
z For an RJ-45 electrical port with the transmission distance is 100 m (328 ft), you
can select the RJ-45 connector as shown in the following figure, and the category-5 twisted pair as the data transmission medium.
Page 22
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-16
Figure 1-7 RJ-45 connector
Table 1-11 Pinouts of the RJ-45 GE port
1000Base-TX
Pin
Signal Function
1 MX_0+ Data transmit/receive 2 MX_0- Data transmit/receive 3 MX_1+ Data transmit/receive 4 MX_2+ Data transmit/receive 5 MX_2- Data transmit/receive 6 MX_1- Data transmit/receive 7 MX_3+ Data transmit/receive 8 MX_3- Data transmit/receive
II. 2-port 10 Gbps XFP module
(1) Module power LED (2) Port status LEDs (3) 10 Gbps XFP optical ports
Figure 1-8 2-port 10 Gbps XFP module
This module provide two 10 Gbps XFP optical port. The following table lists the available XFP optical modules that you can select according to your needs:
Page 23
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-17
Table 1-12 XFP optical port module supported by 2-port 10 Gbps XFP module
Type Model
XFP-SX-MM850 XFP-LX-SM1310
XFP optical module
XFP-LH40-SM1550-F1
Note:
z The switch does not support the 10GBase-ER-XFP module with -5.2 V power
supply.
z The type of 10 Gbps XFP module may be different from those listed above. For the
accurate information about the module type, please consult market personnel or technical support personnel of H3C.
z For specifications of SFP modules, refer to H3C Low End Series Ethernet Switches
Pluggable Module Manual.
III. 1-port 10 Gbps XENPAK module
(1) Module power LED (2) Port status LED (3) 10 Gbps XENPAK optical/electrical port
Figure 1-9 1-port 10 Gbps XENPAK module
z This module can provide one 10 Gbps XENPAK optical port. The following table
lists the available XENPAK optical modules:
Table 1-13 XENPAK optical port module supported by 1-port 10 Gbps XENPAK module
Type Model
XENPAK-LX-SM1310
XENPAK optical module
XENPAK-LH40-SM1550
Page 24
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-18
z This module can also provide a 10 Gbps electrical port. When using this port, you
must select the CX4 connector, and the InfiniBand cable with the transmission distance of 15 m (49.2 ft).
Note:
z For specifications of SFP modules, refer to H3C Low End Series Ethernet Switches
Pluggable Module Manual.
z Use the CX4 modules or the XENPAK optic port modules that H3C Technology
provides or recommends.
1.8 S5600 Series Technical Specifications
Table 1-14 System specifications of the S5600 series
Item
S5600-
26C
S5600-26C
-PWR
S5600-26F
S5600-
50C
S5600-
50C-PWR
Physical dimensions (H x W x D)
43.6 x 440 x 420 mm (1.7 x 17.3 x 16.5 in)
Weight <7.5kg (16.5 lb) <8kg (17.6 lb) Port switching
capacity
88Gbit/s 136Gbit/s
Fixed port
24 x 10/100/1000 Mbps electrical ports and four SFP combo ports
24 x 1000 Mbps SFP ports and four electrical combo ports
48 x 10/100/1000 Mbps electrical ports and four SFP combo ports
Management port
One console port
Number of expansion slot
1
Page 25
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-19
Item
S5600-
26C
S5600-26C
-PWR
S5600-26F
S5600-
50C
S5600-
50C-PWR
Power module
PSL130-AD: 130 W system output, AC/DC input PSL480-AD24P: 24-port PoE power module, 180 W system
output + 300 W PoE output (AC input); 180 W system output + 370 W PoE output (DC input)
PSL180-AD: 180 W system output, AC/DC input PSL480-AD48P: 48-port PoE power module, 180 W system
output + 300 W PoE output (AC input); 180 W system output + 740 W PoE output (DC input)
The input voltage of the AC/DC dual input power module: AC input: Rated voltage: 100 VAC to 240 VAC, 50 Hz or 60Hz Maximum tolerance:90 VAC to 264 VAC, 50 Hz or 60Hz DC input: Rated voltage: –48 VDC to –60 VDC
Maximum tolerance: –36 VDC to –72 VDC
Input voltage
The AC input of the PoE power module: Rated voltage: 100 VAC to 240 VAC, 50 Hz or 60 Hz Max voltage range: 90 VAC to 264 VAC, 50 Hz or 60 Hz The DC input of the PoE power module: Rated voltage: –53.5 VDC
Max voltage range: –52 VDC to–55 VDC For S5600-26C-PWR/S5600-50C-PWR, use the external RPS
recommended by H3C as the DC power input instead of the
48 VDC power supply generally available in the equipment room. Any violation may damage the device due to overvoltage.
Power supply
RPS power
Supported
Power consumption (full load)
170W
540W When with
PoE power supply:
540 W (DC input),
560 W (AC input)
170W 230W
600W When with
PoE power supply:
970 W (DC input),
640 W (AC input)
Page 26
Installation Manual H3C S5600 Series Ethernet Switches Chapter 1 Product Overview
1-20
Item
S5600-
26C
S5600-26C
-PWR
S5600-26F
S5600-
50C
S5600-
50C-PWR
Fans (for heat dissipation)
Two fans are for the device and two are for the power supply module.
Two fans are for the device and four are for the power supply module.
Four fans are for the device and two are for the power supply module.
Two fans are for the device and two are for the power supply module.
Two fans are for the device and four are for the power supply module.
Operating temperature
0 to 45
o
C
Operating humidity (non-condensing )
10% to 90%
Page 27
Installation Manual H3C S5600 Series Ethernet Switches Chapter 2 Preparing for Installation
2-1
Chapter 2 Preparing for Installation
2.1 Safety Precautions
To avoid any device impairment and bodily injury caused by improper use, observe these rules:
z Before cleaning the switch, unplug the power plug of the switch first. Do not clean
the switch with wet cloth or liquid.
z Do not place the switch near water or any damp area. Prevent water or moisture
from entering the switch chassis.
z Do not place the switch on an unstable case or desk. The switch might be
damaged severely in case of a fall.
z Ensure proper ventilation of the equipment room and keep the ventilation vents of
the switch free of obstruction.
z Make sure that the operating voltage is the same one labeled on the switch. z Do not open the chassis while the switch is operating or when electrical hazards
are present to avoid electrical shocks.
z When replacing interface cards, wear ESD-protective gloves to avoid damaging
the cards.
2.2 Installation Site
The S5600 series must be used indoors. You can mount your switch in a rack or on a tabletop/workbench, but make sure:
z Adequate clearance is reserved at the air inlet/exhaust vents for ventilation. z The rack or table/workbench has a good ventilation system. z The rack is sturdy enough to support the device and its accessories. z The rack or table/workbench is well earthed.
To ensure normal operation and long service life of your VG, install it in an environment that meets the requirements described in the following subse ction s.
2.2.1 Temperature/Humidity
You must maintain a proper temperature and humidity in the equipment room. Long-term high humidity may lead to bad insulation, electricity leakage, mechanical property changes, and corrosion. However, if the relative humidity is two low, captive screws may become loose as the result of contraction of insulation washers and static electricity may be produced in a dry environment to jeopardize the CMOS circuits on the device. High temperature is the most undesirable condition, because it accel erates
Page 28
Installation Manual H3C S5600 Series Ethernet Switches Chapter 2 Preparing for Installation
2-2
aging of insulation materials and can thus significantly lower reliability and service life of your switch.
For the temperature and humidity requirements of diff erent models, refer to secti on
1.8
S5600 Series Technical Specifications.
2.2.2 Cleanness
Dust is a hazard to the operating safety of your device. The dust accumulated on the chassis can be adsorbed by static electricity and result in poor contact of metal connectors or metal contact points. This c annot only shorten the service life of your device but also cause communications failures. When the relative indoor humidity is low, electrost atic ad sorptio n is more likely to happen. The contents of the dust must be limited as shown in the
Table 2-1:
Table 2-1 Dust content limits in an equipment room
Substance Unit Content
Dust Particles/m³
3 X 10
4
(No visible dust on the tabletop for three days)
Remark: the diameter of a dust particle 5 μm
Besides dust, there are rigorous limits on the harmful gases that can accelerate the erosion and aging of metals, such as salts, acids, and sulfides, as shown in the
Table
2-2.
Table 2-2 Harmful gas limits in the equipment room
Gas Maximum (mg/m3)
SO2 0.2 H2S 0.006 NH3 0.05 Cl2 0.01
2.2.3 Electromagnetic Susceptibility
The operation of your switch can be affected by external interferences, such as conducted emission by capacitance coupling, inductance coupling, electromagnetic wave radiation, and common impedance (including the grounding system) coupling, and leads (power cords, signaling cables and output wires. To eliminate the interferences, make sure to:
Page 29
Installation Manual H3C S5600 Series Ethernet Switches Chapter 2 Preparing for Installation
2-3
z For the AC power supply that adopts TN system, use a monophase three-line
power socket with Protection Earth (PE) to effectively filter interference from the power grid.
z Keep the device far from radio transmitting stations, radar stations, and
high-frequency devices.
z Use electromagnetic shielding when necessary, for example, use shielded
interface cables.
z Route interface cables only indoors to prevent signal ports from getting damaged
by overvoltage or overcurrent caused by lightning strikes.
2.2.4 Laser Safety
The S5600 Series Ethernet Switches are class-1 laser devices. If the optical boards on your switch are operating, do not stare into the optical ports
because the laser light emitted by the optical fiber can hurt your retina.
Caution:
Staring into the laser beam produced by the fiber can hurt your eyes.
2.3 Installation Tools
z Flat-blade screwdriver z Phillips screwdriver z ESD-preventive wrist strap
Caution:
The installation tools are not provided with the S5600 series.
Page 30
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-1
Chapter 3 Installing the Switch
Caution:
When you ask your sales agent to maintain the switch, you must ensure that the dismantlement-preventive seal on a mounting screw of the switch chassis is intact. If you want to open the chassis, you should contact the agent for permission. Otherwise, you will bear any consequence resulted from your actions without permission.
3.1 Rack-Mounting the Switch
You can install a switch into a 19-inch standard cabinet in one of the following three ways:
z Use front mounting ears and a tray z Use front mounting ears and rear mounting ears z Use front mounting ears and guide rails
Note:
z The front mounting ears and rear mounting ears are delivered with the device, no
guide rails are delivered with the device.
z The front mounting ears only secure the switch rather than bear its weight. z Guide rails purchased from H3C apply only to standard cabinets 1,000 mm (39.4 in)
deep. Use other supports to substitute for guide rails in the case of other cabinet depths.
3.1.1 Introduction to mounting ear
Figure 3-1 shows the appearance of a front mounting ear.
Page 31
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-2
(1) (2)
L1
L2
(1): Screw hole used to fix the mounting ear to the cabinet (Use one M6 screw) (2): Screw hole used to fix the switch to the mounting ear
Figure 3-1 Appearance of a front mounting ear
Figure 3-2 shows the appearance of a rear mounting ear.
(1): Screw hole used to fix the mounting ear to the cabinet (Use one M6 screw)
Figure 3-2 Appearance of a rear mounting ear
3.1.2 Introduction to guide rail
Figure 3-3 shows the appearance of a guide rail.
Page 32
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-3
Slotted hole 1 Cooling hole Slotted hole
2
Slotted hole 1: Used to fix the guide rail to the rear bracket. You can adjust the screw hole position according to the position of the switch. Cooling hole: Used for heat dissipation between switch and cabinet Slotted hole 2: Used to fix the guide rail to the front bracket
Figure 3-3 Appearance of a guide rail
3.1.3 Use front mounting ears and a tray
Follow these steps to install a switch into a 19-inch standard cabinet:
1) Wear an ESD-preventive wrist strap to check the grounding and stability of the cabinet.
2) Fix the delivered tray horizontally in a proper position.
3) Take out the screws which are packed together with the front mounting ears, and fix one end of mounting ears to the switch, as shown in
Figure 3-4.
Front panel
Figure 3-4 Fix front mounting ears
4) Place the switch on the tray horizontally, slide the tray into the cabinet, and fix the other end of mounting ears to the front brackets with crews and captive nuts, as shown in
Figure 3-5.
Page 33
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-4
Fr ont panel
Front mounting ear
Fr ont squar e- holed bracket
Front
mounting ear
Fr ont panel
Front mounting ear
Fr ont squar e- holed bracket
Front
mounting ear
Figure 3-5 Fix front mounting ears and a tray
3.1.4 Use front and rear mounting ears
Follow these steps to install a switch into a 19-inch standard cabinet:
1) Wear an ESD-preventive wrist strap to check the grounding and stability of the cabinet.
2) Take out the screws which are packed together with the front mounting ears, and fix one end of mounting ears to the switch, as shown in
Figure 3-4.
3) Take out the load-bearing screws (packed together with the rear mounting ears) and place them in a proper position on the sides of the switch, as sh own in
Figure
3-6.
Fron t panel
Screw 1
Fron t moun ting ear
Thr ee in stallati on locations for screw 1 (select one according to the actual requiremen t)
Front
mounting ear
Screw 1
Fron t panel
Screw 1
Fron t moun ting ear
Thr ee in stallati on locations for screw 1 (select one according to the actual requiremen t)
Front
mounting ear
Screw 1
Figure 3-6 Fix front mounting ears and load-bearing screws
Page 34
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-5
Note:
There are three positions to mount a load-bearing screw on both sides of a switch. You should select a proper position according to the actual requirements. The rear mounting ears tightly contacted with the load-bearing screws can support the switch.
4) Select a position to install the switch and fix the rear mounting ears to the rear brackets with screws and captive nuts, as shown in
Figure 3-7.
Rear square-holed rac
k
Figure 3-7 Fix rear mounting ears
5) Hold the bottom of the switch with one hand and the front part of the switch with the other hand, and pull the switch into the cabinet gently, as shown in
Figure 3-8.
Page 35
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-6
Front square-holed bracket
Front mounting ear
Rear panel
Screw 2
Rear square-holed
bracket
Rear mounting ear
Screw 1: Used to bear the weight Screw 2: Used to fix rear mounting ears to rear brackets
Figure 3-8 Fix front and rear mounting ears
After the switch is pushed into the cabinet, ensure that the uppe r edge of rear mounting ears is tightly contacted with the load-bearing screw, as shown in
Figure 3-9.
Rear panel
Rear square-
holed bracket
Screw 1
Rear mounting ea
r
Screw 1: Load-bearing screw
Figure 3-9 Effect diagram of front and rear mounting ear installation (1)
6) Fix the other end of the front mounting ears to the front brackets with screws and captive nuts and ensure that front and rear mounting ears have fixed the switch i n the cabinet securely, as shown in
Figure 3-10.
Page 36
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-7
Front panel
Screw 1
Rear
mounting ear
Front square-holed bracket
Front mounting ear
Screw 1: Load-bearing screw
Figure 3-10 Effect diagram of front and rear mounting ear installation (2)
3.1.5 Use front mounting ears and guide rails
Follow these steps to install a switch into a 19-inch standard cabinet
1) Wear an ESD-preventive wrist strap to check the grounding and stability of the cabinet.
2) Take out the screwed packed together with the front mounting ears and fix one end of the front mounting ears to the switch, as shown in
Figure 3-11.
Front panel
Figure 3-11 Fix front mounting ears
3) Install guide rails on the brackets on both sides of the cabinet with M5 self-tapping screws, as shown in
Figure 3-12.
Page 37
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-8
Figure 3-12 Install guide rails
4) Hold the two sides of the switch and slide it gently along the guide rails into the cabinet until it is located in a proper position, as shown in
Figure 3-13. Ensure that
the bottom side of the guide rails and the switch are in close contact.
Front pane
l
Figure 3-13 Install front mounting ears and guide rails
5) Fix the other end of front mounting ears to the front brackets of the cabinet with M6 screws and captive nuts and ensure that the front mounting ears and guide rails have fixed the switch in the cabinet securely, as shown in
Figure 3-14.
Page 38
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-9
Rear panel
Guide
rail
Figure 3-14 Effect diagram of front mounting ear and guide rail installation
Note:
Ensure a clearance of 1U (44.45 mm, namely, 1.75 inches) between devices for the purpose of heat dissipation.
3.2 Mounting the Switch on a Tabletop/Workbench
When placing the switch on a tabletop or workbench, you simply need to:
z Make sure that the tabletop or workbench is clean, flat, and sturdy. z Allow 10 cm (3.9 in.) of clearance around the sides of the chassis. z Do not place heavy objects on the switch.
Page 39
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-10
3.3 Installing/Removing the Power Module
Caution:
To avoid bodily injury, do not touch any bare conducting wire, screw, and the part which is labeled danger voltage.
3.3.1 Installing the Power Module
The power module of the S5600 series is swappable. Follow those steps to install the power module:
Step 1: Wear an ESD wrist strip, and make sure it is well grounded. Step 2: V erify that the power module i s not installed upside-down (th e module should be
installed according to the letters. If the module is installed upside down, it will fail to be fully seated due to the specially designed inside structure of the chassis). Use one hand to hold the handle on the front, and another to hold the bottom. Slide it gently along the power slot. Push the module until it is fully seated.
Step 3: Use a Phillips screwdriver to fasten the captive screws at both sides of the module.
3.3.2 Removing the Power Module
The power module of S5600 series Ethernet switch is swappable. Fo llow those steps to remove the power module:
Step 1: Wear an ESD wrist strip, and make sure it is well grounded. Step 2: Disconnect all power of the switch. Step 3: Use a Phillips screwdriver to unscrew the captive screws at both sides of the
module Step 4: Use one hand to hold the handle on the front, and another to hold the top. Pull
out the module stably towards you along the power slot until it is completely apar t from the chassis bottom.
Page 40
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-11
Caution:
When you use the Phillips screwdriver or power screwdriver to fasten captive screws at both sides of the module, make sure the captive force moment is not larger than 0.4 N•m.
3.4 Connecting the Power Cord and the Ground Wire
3.4.1 Connecting the AC-Input Power Cord
I. AC-input power socket (recommended)
You are recommended to use a monophase three-line power socket with a ground contact or a general purpose PC power socket, making sure that the power point is well connected to building ground. Normally, the ground point of the power source in a building was buried in the ground during the construction and wiring. Still, you must make sure of that.
Neutral point
Zero line
Live line
Ground
Return Hot
Neutral point
Zero line
Live line
Ground
Return Hot
Figure 3-15 Power socket (recommended)
II. Connecting the AC-input power cord
Step 1: Connect on e end of the chassi s ground wire t o the grounding screw on the rear of the chassis and the other end to the ground as near as possible.
Step 2: Connect one end of the power cord to the power socket on the rear of the chassis, and plug the other end to the AC power jack of the power source.
Step 3: Check that the PWR LED on the front panel of the switch is ON.
Caution:
Before powering on the switch, connect the ground wire.
Page 41
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-12
3.4.2 Connecting the DC-Input Power Cord
RTN: -48V working ground -48_-60V: -48_-60V NULL: reserved
Figure 3-16 DC-input power connector (partial)
Step 1: Connect on e end of the chassi s ground wire t o the grounding screw on the rear of the chassis and the other end to the ground as near as possible.
Step 2: Connect DC-input socket.
Screw 1
Screw 2
Screw 3
Cable 1
Dust-proof shield
Cable tie
Connector
Screw 4
Cable 2
Screw 1
Screw 2
Screw 3
Cable 1
Dust-proof shield
Cable tie
Connector
Screw 4
Cable 2
Figure 3-17 RPS DC-input connector
(1) As shown in
Figure 3-17, first insert two cables into the appropriate holes through dust-proof shield, and then fix the cables separately by using screws 1 and 2. Make sure that the positive and negative ends of the cable are inserted appropriately and accord with silkscreen on the holes.
(2) Fix the dust-proof shield by screws 3 and 4 by using a small flathead screwdriver, see
Figure 3-17.
(3) Enlace the two cables to the polarizing key at the back of the dust-proof shield using the cable tie, see
Figure 3-17.
Page 42
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-13
Screw 2
Screw 1
Cabinet
Connector component
Screw 2
Screw 1
Cabinet
Connector component
Figure 3-18 Fix RPS connector to the cabinet
Step 3: After installing connector component, directly insert the component into DC-input socket on the cabinet, and then fix the screws 1 and 2 carried by the connector itself to the appropriate holes on the cabinet socket using a small flathead screwdriver, see
Figure 3-18.
Step 4: Check that the RP S LED on the front panel of the switch is ON.
Caution:
z Before powering on the switch, connect the ground wire. z The DC power cable should be less than 3 meters long. z The S5600-26C-PWR/S5600-50C-PWR must use the external PoE PSU
recommended by H3C as its DC input, but not the -48VDC power supply generally available in the equipment room. Otherwise, the device may be damaged.
3.4.3 Connecting the Ground Wire
Caution:
Correctly connecting the switch ground wire is crucial to the lightning protection and electromagnetic susceptibility (EMS) of a switch.
The power input end of the switch is connected with a noise filter , whose central ground is directly connected to the chassis, forming the chassis ground (commonly known as
Page 43
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-14
PGND). This chassis ground must be securely connected to the earth ground so that the faradism and leakage electricity can be safely released to the ground, enhancing the EMS capability of the switch.
Ground your switch as follows:
z When a grounding strip is available at the installation site, attach one end of the
yellow/green ground wire of the switch to the grounding screw on the grounding strip and fasten the captive nut. (Note that the fire main and lightning rod of a building are not suitable for grounding the switch. The ground wire of the switch should be connected to the grounding device for the equipment room).
(1)
(2)
(4)
(3)
(1)
(2)
(4)
(3)
(1) Power input on the switch (2) Groundi ng screw on the switch (3) Ground wire (4) Grounding strip
Figure 3-19 Grounding the switch through a grounding strip
z When there is no grounding strip but earth near the equipment room that allows a
grounding body to be buried, hammer an angle iron/steel pipe longer than 0.5 m into the earth, weld the yellow-green ground wire of the switch onto the angle iron/steel pipe, and process the joint against erosion.
(1)
(2)
(5)
(3)
(4)
(1)
(2)
(5)
(3)
(4)
(1) Power input (2) Grounding screw (3) Ground wire (4) Earth (5) Angle iron
Figure 3-20 Grounding the switch by burying the grounding body into the earth
Page 44
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-15
z For an AC-powered switch, if none of the above two conditions is available,
ground it through the PE wire of the AC power supply. In this case, make sure this PE wire is well connected to the ground at the power distribution room or AC transformer side.
(4)
(2)
(1)
(5)
(3)
(6)
(4)
(2)
(1)
(5)
(3)
(6)
(1) AC-input (2) Grounding screw (3) Power transformer (4) PE wire (5) AC-input (with 3-wire cable) (6) Ethernet switch
Figure 3-21 Grounding through the AC PE wire
z For a DC-powered switch, if none of the first two conditions is available, ground it
through the return wire (RTN) of the DC power supply. In this case, make sure this RTN wire is well connected to the ground at the DC output of the DC power cabinet.
(1)
(2) (4)
(3)
(6)
(5)
(7)
(8)
(9)
(11)
(10)
(1)
(2) (4)
(3)
(6)
(5)
(7)
(8)(8)
(9)(9)
(11)
(10)
(1) AC/DC power cabinet (2) -48V strip (3) -48V (4) RTN strip (5) RTN (6) PGND strip (7) Grounding (8) Ground wire (9) Grounding screw (10) Ethernet switch (11) DC-input
Figure 3-22 Grounding through the PGND of a power cabinet
Page 45
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-16
3.5 Connecting the Switch to a Console Terminal
3.5.1 Console Cable
Console cable is an 8-core shielded cable. At one end of the cable is a crimped RJ-45 connector for the connection to the console port of the switch; at the other end of the cable is one DB-9 (female) connector for the connection to the serial port on the console terminal. See
Figure 3-23.
Figure 3-23 Console cable
Table 3-1 Console cable pinouts
RJ-45 Signal Direction DB-9
1 RTS ← 7 2 DTR ← 4 3 TXD ← 3 4 CD → 1 5 GND –– 5 6 RXD → 2 7 DSR → 6 8 CTS → 8
3.5.2 Connecting the Console Cable
Follow these steps to connect a terminal device, a PC for example, to the switch: Step 1: Plug the DB-9 (female) connector of the Console cable to the serial port of the
PC where the switch is to be configured. Step 2: Connect the RJ-45 connector of the console cable to the console port of the
switch.
Page 46
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-17
Caution:
Read the mark for the port to be connected carefully to make sure it is the right port.
Note:
The serial ports on PCs do not support hot swapping. Therefore, do not insert or remove a serial interface cable from a PC that is connected to a switch with power. In connecting a PC to the switch, first connect the DB-9 connector of the console cable to the PC and then the RJ45 connector to the switch. In disconnecting them, remove the RJ-45 connector prior to the DB-9 connector.
3.6 Installing/Removing the Stack Cable
3.6.1 Stack Cable
To stack S5600 series switches, you need to use stack cables to connect the Fabric ports of switches.
Figure 3-24 Diagram for stack cable
The stack cable for the S5600 series switch can be 0.65 m (2.1 ft.), 1.2 m (3.9 f t) and 5 m (16.4 ft) long. You can choose them according to your need.
3.6.2 Installing the Stack Cable
Step 1: Before you ta ke the cable out of the package, wea r an ESD wrist strip and make sure it is well grounded.
Step 2: Insert the cable plu g into the switch Fabric port flatly. Step 3: Use a Phillips screwdriver or power screwdriver to fasten the captive screws at
both sides.
Page 47
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-18
3.6.3 Removing the Stack Cable
Step 1: Wear an ESD wrist strip and make sure it is well grounded. Step 2: Use a flat-blade screwdriver or power screwdriver to unscrew the captive
screws at both sides. Step 3: Unplug the cable plug from the switch Fabric port flatly.
Caution:
z The S5600 stack cable is hot swappable. z When you use the flat-blade screwdriver or power screwdriver to fasten captive
screws at both sides, make sure the captive force moment is not la rger than 0.4N•m.
z When you connect the stack cable, the bending radius of the cable with 0.65 m (2.1
ft.) or 1.2 m (3.9 ft) in length should be no less than eight times of the cable diameter; the bending radius of the cable with 5 m (3.9 ft) in length should be no less than 10 times of the cable diameter.
3.7 Installing/Removing the Optional Interface Module
The optional interface modules are hot-swappable.
I. Installing
Step 1: Wear an ESD wrist strip which is well grounded and take a module out of the package.
Step 2: Using a Phillips screwdriver to remove the blank filler panel from the slot where you plan to install the module.
Step 3: Hold the front panel of the module with both hands, align the module with the guides in the slot and slide it gently into the slot. Push the module until it is fully in position.
Step 4: Fasten the captive screws to fix the module using the Phillips screwdriver.
Note:
z Keep the removed blank panel for future use. z When you use the Phillips screwdriver or power screwdriver to fasten captive
screws on both sides of the modular, make sure the captive force moment is not larger than 0.4 N•m.
Page 48
Installation Manual H3C S5600 Series Ethernet Switches Chapter 3 Installing the Switch
3-19
II. Removing
Step 1: Wear an ESD wrist strip which is well grounded. Step 2: Use the Phillips screwdriver to unscrew the captive screws at both sides of the
module. Step 3: Pull the module towards you until it is compl etely apart from the chassi s bottom.
Caution:
When installing/removing an optional interface module, note that:
z Do not exert excessive strength on the module or touch the components on the
module surface.
z Install a blank filler panel, if you do not want to install a new module right after the old
one is removed, to keep the dust out and ensure the normal ventilation of the switch.
3.8 Verifying Installation
z The correct power source is used. z The ground wire is securely connected. z Both of the console cable and power cord are correctly connected. z All the interface cables are routed indoors. If there are cables outdoors, check that
the socket strip with lightning protection and lightning arresters for network ports have been correctly connected.
Page 49
Installation Manual H3C S5600 Series Ethernet Switches Chapter 4 Starting up the Switch at the Initial Boot
4-1
Chapter 4 Starting up the Switch at the Initial Boot
4.1 Setting up a Configuration Environment
Set up a configuration environment as shown in Figure 4-1. Connect a terminal, a PC in this scenario to the console port on the switch with a
console cable.
PC
Console cable
Switch
Console port
Serial port
PC
Console cable
Switch
Console port
Serial port
Figure 4-1 Network diagram for configuring the switch at initial boot
4.2 Connecting the Console Cable
Step 1: Connect the DB-9 female connector of the console cable to the serial port on the PC that is used for configuring the switch.
Step 2: Connect the RJ-45 connector of the console cable to the console port on the switch.
4.3 Setting Terminal Parameters
Follow these steps to set terminal parameters on the PC (running Windows2000 for example):
Step 1: S t art the PC and select [S tart/Programs/Accessories/Communications/HyperTe rminal].
The HyperTerminal window displays the Connection Description dialog box, as shown in
Figure 4-2.
Page 50
Installation Manual H3C S5600 Series Ethernet Switches Chapter 4 Starting up the Switch at the Initial Boot
4-2
Figure 4-2 Setting up a new connection
Step 2: Enter the name of the new connection in the Name field and click <OK>. The dialog box, as shown in
Figure 4-3 displays.
Step 3: Select the serial port to be used from the Connect Using dropdown menu. The serial port must be the same port connected by the console cable.
Figure 4-3 Setting the connection port
Step 5: Click <OK>. The Port Settings tab, shown in
Figure 4-4, appears and you can
set serial port parameters. Set the following parameters:
z Baud rate = 9600 z Databit = 8 z Parity check = none
Page 51
Installation Manual H3C S5600 Series Ethernet Switches Chapter 4 Starting up the Switch at the Initial Boot
4-3
z Stopbit = 1 z Flow control = none
Figure 4-4 Setting communications parameters
Step 6: Click <OK>. The HyperTerminal dialogue box appears.
Figure 4-5 HyperTerminal window
Step 7: Select Properties. Step 8: In the Properties dialog box, sel ect the Settings tab, as shown in
Figure 4-6.
Step 9: Select VT100 or Auto detect in the Emulation dropdown menu.
Page 52
Installation Manual H3C S5600 Series Ethernet Switches Chapter 4 Starting up the Switch at the Initial Boot
4-4
Step 10: Click <OK>.
Figure 4-6 Settings tab
4.4 Booting the Switch
4.4.1 Verifying Installation before Power-up
Before powering up the switch, check that:
z Both the power cord and the grounding wire are correctly connected. z Proper power supply is used. z The console cable is correctly connected. z The console terminal (or PC) has been started and the related parameters have
been set on it.
4.4.2 Powering up the Switch
Starting......
*********************************************************** * * * H3C S5600 BOOTROM, Version 409 * * * ***********************************************************
Copyright(c) 2004-2007 Hangzhou H3C Technologies Co., Ltd.
Page 53
Installation Manual H3C S5600 Series Ethernet Switches Chapter 4 Starting up the Switch at the Initial Boot
4-5
Creation date : Apr 10 2007, 12:51:33 CPU type : BCM1122 CPU Clock Speed : 400MHz BUS Clock Speed : 33MHz Memory Size : 128MB Mac Address : 000fe2005600
Press Ctrl-B to enter Boot Menu... 1
The last line queries that whether you want to enter the Boot Menu and waits fo r you for one seconds:
z To enter Boot Menu, press <Ctrl+B> within one seconds z If no <Ctrl+B> input in one seconds, the system will boot automatically
The following is the system auto-booting interface:
Auto-booting... Decompress
Image...............................................................
....................................................................
....................................................................
....................................................................
....................................................................
....................................................OK!
Starting at 0x80020000...
Initialize:
LSH1LTSU...................................OK!
SDRAM fast selftest........................OK!
Flash fast selftest........................OK!
CPLD selftest..............................OK!
Switch chip selftest.......................OK!
PHY selftest...............................OK!
Please check leds....................FINISHED!
Press ENTER to get started.
The appearance of “Press ENTER to get started” indicates that the switch has completed its boot.
Press <Enter>; the system displays:
<H3C>
Page 54
Installation Manual H3C S5600 Series Ethernet Switches Chapter 4 Starting up the Switch at the Initial Boot
4-6
You can configure the switch now.
Note:
A wide range of command views are available for H3C Series Switches. For more information on configuration commands and command line interfaces, refer to H3C
S5600 Series Ethernet Switches Operation Manual and H3C S5600 Series Ethernet Switches Command Manual.
Page 55
Installation Manual H3C S5600 Series Ethernet Switches Chapter 5 Loading Boot ROM and Host Software
5-1
Chapter 5 Loading Boot ROM and Host Software
Switch software loading through serial ports in the past is time consuming and cannot be operated remotely. To address these problems, TFTP and FTP are used to allow software and file downloading through Ethernet ports. The following subsections describe how to load software and files in these two approaches.
5.1 Introduction to Loading Approaches
To load software remotely, use FTP or TFTP. To load software at the local, use XModem at the console port or TFTP/FTP at an
Ethernet port.
Note:
Ensure that the Boot ROM and host software versions that you download can work with each other.
5.2 Loading Software Locally
If your terminal is directly connected to the switch, you can load Boot ROM and host software locally. But before that, make sure they are correctly connected.
Note:
The steps that you should take to load Boot ROM program and host software are the same, except that during Boot ROM program loading you need to press <Ctrl +U> after accessing the Boot ROM menu and will view different prompt information. Boot ROM loading procedures are described below for example.
5.2.1 Boot Menu
Starting......
*********************************************************** * *
Page 56
Installation Manual H3C S5600 Series Ethernet Switches Chapter 5 Loading Boot ROM and Host Software
5-2
* H3C S5600 BOOTROM, Version 409 * * * ***********************************************************
Copyright(c) 2004-2007 Hangzhou H3C Technologies Co., Ltd. Creation date : Apr 10 2007, 12:51:33 CPU type : BCM1122 CPU Clock Speed : 400MHz BUS Clock Speed : 33MHz Memory Size : 128MB Mac Address : 000fe2005600
Press Ctrl-B to enter Boot Menu... 1
Press <Ctrl+B> as prompted. The system displays:
Password :
Note:
To access the Boot Menu, press <Ctrl+B> within one seconds after the information “Press Ctrl-B to enter Boot Menu...” appears; otherwise the system starts to decompress the program. At this time if you want to access the Boot Menu, you need to restart the switch.
Input the correct Boot ROM password (no password is set by default). The system enters the following Boot Menu:
BOOT MENU
1. Download application file to flash
2. Select application file to boot
3. Display all files in flash
4. Delete file from flash
5. Modify bootrom password
6. Enter bootrom upgrade menu
7. Skip Current Configuration file
8. Set bootrom password recovery
9. Set switch startup mode
0. Reboot Enter your choice(0-9):
Page 57
Installation Manual H3C S5600 Series Ethernet Switches Chapter 5 Loading Boot ROM and Host Software
5-3
5.2.2 Loading Software from Console Port Using XModem
I. Introduction to XModem
XModem is a file transfer protocol widely used for its simplicity and good performance. XModem transfers files through the console port, supporting data p ackets of 128 bytes and 1 KB. With respect to reliability, it supports checksum, CRC, and the error packet retransmission mechanism. Normally, the maximum number of retransmission attempts is ten.
XModem transfer is completed by receiving and sending programs together. Receiving program initiates packet checking method negotiation by sending the negotiation character. If negotiation passes, the sending program starts packet transfer. Upon receipt of a complete packet, the receiving program checks it using the agreed-upon check method. If the check succeeds, the receiving program sends an acknowledgement character; if the check fails, it sends a reject character. Upon receipt of the acknowledgement, the sending program continues to send the next packet; upon receipt of the reject, it retransmits the packet.
II. Loading BootROM
Follow these steps to download the Boot ROM program: Step 1: Enter <6> or <Ctrl + U> in the Boot Menu to access the Boot ROM loading
menu shown below:
Bootrom update menu:
1. Set TFTP protocol parameter
2. Set FTP protocol parameter
3. Set XMODEM protocol parameter
0. Return to boot menu
Step 2: Enter <3> in the loading menu to download through XModem. The system displays the following download speed setting menu:
Please select your download baudrate:
1. 9600
2. 19200
3. 38400
4. 57600
5. 115200
0. Return Enter your choice (0-5):5
Step 3: Choose an appropriate download baud rate. Enter <5> for example to download at 115200 bps. The system displays the following information:
Are you sure to update your bootrom?(Y/N)
Page 58
Installation Manual H3C S5600 Series Ethernet Switches Chapter 5 Loading Boot ROM and Host Software
5-4
Step 4: To download files, enter <Y>; to return to the loading menu, enter <N>. Press <Y> for example, the system displays:
Download baudrate is 115200 bps. Please change the terminal's baudrate to 115200 bps and select XMODEM protocol. Press enter key when ready.
Note:
You do not need to modify the HyperTerminal’s baud rate if you have chosen 9600 bps, and thus can skip Steps 5 through 6 and proceed to Step 7 directly. At this time, the system does not display the above information.
Step 5: Enter HyperTerminal’s [File/Properties] menu, click <Configuration> in the popup dialog box, select the baud rate of 1 15200b p s in the Console Port Configuration dialog box.
Figure 5-1 Properties dialog box
Page 59
Installation Manual H3C S5600 Series Ethernet Switches Chapter 5 Loading Boot ROM and Host Software
5-5
Figure 5-2 Console Port Configuration dialog box
Step 6: Click <Disconnect> to disconnect the HyperTerminal from the switch and then click <Call> to re-establish the connection, thus validating the baud rate setting.
Figure 5-3 <Disconnect> and <Call> buttons
Note:
After changing terminal’s baud rate, you must disconnect and connect the terminal emulation program to validate the new configuration.
Step 7: Press <Enter> to start program loading. The system displays the following information:
Page 60
Installation Manual H3C S5600 Series Ethernet Switches Chapter 5 Loading Boot ROM and Host Software
5-6
Now please start transfer file with XMODEM protocol. If you want to exit, Press <Ctrl+X>. Loading ...CCCCCCCCCC
Step 8: Select [Transfer/Send File] in the HyperTerminal’s window, and in the popup dialog box similar to the following figure click <Browse>, select the software you need to download, and set the protocol to XModem.
Figure 5-4 Send File dialog box
Step 9: Click <Send>. The system displays the following interface.
Figure 5-5 Sending File interface
Step 10: After completing loading, the system displays the following information:
Loading ...CCCCCCCCCC done! ## Total Size = 0x0004bc50 = 310352 Bytes Your baudrate should be set to 9600 bps again! Press enter key when ready.
Page 61
Installation Manual H3C S5600 Series Ethernet Switches Chapter 5 Loading Boot ROM and Host Software
5-7
Note:
You do not need to reset the HyperTerminal’s baud rate and can skip the last step if you have chosen 9600 bps. In this case, the system does not display the above prompt
message but “BootROM is updating now.....................................done!” instead.
Step 11: Reset HyperTerminal’s baud rate to 9600bps with reference to Steps 5 and 6 described above. Then, press any key as prompted. The system will display the following information when it completes the loading.
Bootrom updating.....................................done!
III. Loading host software
Follow these steps to download host software of the switch: Step 1: Select <1> in the Boot Menu. The system displays the following information:
1. Set TFTP protocol parameter
2. Set FTP protocol parameter
3. Set XMODEM protocol parameter
0. Return to boot menu Enter your choice(0-3):3
Select <3>. The subsequent steps are the same as those for loading Boot ROM, except for the program to be downloaded in prompt messages.
5.2.3 Loading Software from an Ethernet Port Using TFTP
I. Introduction to TFTP
Trivial File Transfer Protocol is a TCP/IP protocol used for file transfer between clients and servers. It uses UDP to provide unreliable data stream transfer service.
II. Loading Boot ROM
Step 1: Select an Ethernet port o n the switch for loading and conne ct it to the PC where the file to be downloaded is stored. (Y ou must know PC’ s IP address). Besides, connect the console port on the switch to an external PC. This PC can be the same one that stores the file to be downloaded.
Step 2: Run the TFTP Server program on the PC connected to the Ethernet port, and specify the path for program loading.
Page 62
Installation Manual H3C S5600 Series Ethernet Switches Chapter 5 Loading Boot ROM and Host Software
5-8
Caution:
TFTP Server program is not provided with the H3C Series Switches.
Step 3: Run terminal em ulation program on the PC that is conne cted to the console port. Start the swit ch, access the Boot Menu, and then enter the download protocol menu.
To download the Boot ROM program, enter <6> or <Ctrl + U> to access the menu for Boot ROM downloading when the system displays: “Enter your choice(0-9):”
Enter your choice(0-9):
Please set bootrom download protocol parameter:
1. Set TFTP protocol parameter
2. Set FTP protocol parameter
3. Set XMODEM protocol parameter
0. Return to boot menu
Step 4: In the download protocol me nu, pres s <1>to select TFTP protocol to download Boot ROM or host software. Press <Enter>. The system displays the following information:
Load File name Switch IP address (This address and the server IP address must be on the same
network segment) Server IP address (IP address of the PC where the file is stored)
Step 5: Input the TFTP parameter values and press <Enter>. The system displays the following information:
Are you sure to update your bootrom?Yes or No(Y/N)
Step 6: Press <Y> to start file downloading and <N> to return to the program downloading menu. Suppose you press <Y> and then <Enter>. The system st arts Boot ROM program downloading and automatically start s Boot ROM loading. After finishing loading, it displays the following information:
Initializing net....done!
Loading.........................done!
Bootrom is updating now.....................................done!
III. Loading host software
Follow these steps to download host software of the switch. Step 1: Select <1> in the Boot Menu. The system displays the following information:
1. Set TFTP protocol parameter
Page 63
Installation Manual H3C S5600 Series Ethernet Switches Chapter 5 Loading Boot ROM and Host Software
5-9
2. Set FTP protocol parameter
3. Set XMODEM protocol parameter
0. Return to boot menu Enter your choice(0-3):3
Select <1>. The subsequent steps are the same as those for loading Boot ROM, except for the program to be downloaded in prompt messages.
5.2.4 Loading Software from an Ethernet Port Using FTP
I. Introduction to FTP
With an Ethernet port, you can also use the switch as the FTP server or client to download or configuration files. The following subsections describe how to load software by using the switch as the FTP client for example.
II. Loading Boot ROM
Step 1: Select an Ethernet port o n the switch for loading and conne ct it to the PC where the file to be downloaded is stored. (Y ou must know PC’ s IP address). Besides, connect the console port on the switch to an external PC. This PC can be the same one that stores the file to be downloaded.
Step 2: Run the FTP Server program on the PC that is connected to the Ethernet port, and specify the path for program loading.
Step 3: Run terminal emulation program on the PC connected to the console port. Start the switch, access the Boot Menu, and then enter the download protocol menu.
To download the Boot ROM program, enter <6> or <Ctrl + U> to access the menu for Boot ROM downloading when the system displays: “Enter your choice(0-9):”
Enter your choice(0-9):
Please set bootrom download protocol parameter:
1. Set TFTP protocol parameter
2. Set FTP protocol parameter
3. Set XMODEM protocol parameter
0. Return to boot menu
Step 4: In the download protocol menu, press <2> to select FTP protocol to download Boot ROM and host software. Press <Enter>. The system displays the following information:
Load File name Switch IP address (This address and the server IP address must be on the same
network segment) Server IP address (IP address of the PC that stores the file)
FTP User Name FTP User Password
Page 64
Installation Manual H3C S5600 Series Ethernet Switches Chapter 5 Loading Boot ROM and Host Software
5-10
Step 5: Input the FTP parameter values and press <Enter>. The system displays:
Are you sure to update your bootrom?Yes or No(Y/N)
Step 6: Press <Y> to start file downloading and <N> to return to the program downloading menu. Suppose you press <Y> and then <Enter>. The system starts program downloading and upon its completion, sta rts writing to Fla sh. Af ter co mpleting the writing operation, the system displays:
Initializing net....done!
Loading.........................done!
Bootrom is updating now.....................................done!
III. Loading host software
Follow these steps to download host software: Step 1: Select <1> in the Boot Menu. The system displays:
1. Set TFTP protocol parameter
2. Set FTP protocol parameter
3. Set XMODEM protocol parameter
0. Return to boot menu Enter your choice(0-3):3
Select <2>. The subsequent steps are the same as those for loading Boot ROM, except for the program to be downloaded in prompt messages.
5.3 Loading Software Remotely
If your terminal is connected to the switch by a network, you can load Boot ROM and host software remotely.
5.3.1 Loading Software Remotely Using FTP
Run FTP server on a local PC, provided you have con figured usern ame and p assword and have set the correct file directory. Suppose IP address of the PC is 10.10.110.1. Telnet to the switch and FTP the host program to the switch.
Provided that the host program is SWITCH.bin and the Boot ROM program is SWITCH.btm, you can take these steps after telneting to the switch.
Step 1: FTP the software to the switch.
<H3C> ftp 10.10.110.1 Trying ... Press CTRL+K to abort Connected. 220 WFTPD 2.0 service (by Texas Imperial Software) ready for new user User(none):lyt 331 Give me your password, please
Page 65
Installation Manual H3C S5600 Series Ethernet Switches Chapter 5 Loading Boot ROM and Host Software
5-11
Password: 230 Logged in successfully [ftp] get SWITCH.bin SWITCH.bin [ftp] get SWITCH.btm SWITCH.btm [ftp] bye
Step 2: Load Boot ROM.
<H3C> boot bootrom SWITCH.btm please wait ... Bootrom is updated!
Step 3: Load the host software.
<H3C> boot boot-loader SWITCH.bin <H3C> display boot-loader The app to boot at the next time is: flash:/SWITCH.bin <H3C> reboot
Note:
The configurations that you just make cannot survive a reboot. Make sure you have saved them before you have the system reboot.
To validate the downloaded Boot ROM and host software, you must reboot the switch. In case of inadequate Flash memory space, you can delete some of the program files in Flash, those that are no longer in use for example, after completing Boot ROM loading. Then FTP the host program to the switch.
Note:
Power disconnection must be prevented during the loading process.
5.3.2 Loading Software Remotely Using TFTP
TFTP is similar to FTP in remote software downloading. But with TFTP, the switch can only be used as the client to download software to its Flash memory from the TFTP server. After that, the remaining steps are the same as remote loading using FTP.
Page 66
Installation Manual H3C S5600 Series Ethernet Switches Chapter 6 Maintenance and Troubleshooting
6-1
Chapter 6 Maintenance and Troubleshooting
6.1 Dealing with Loading Failures
If software loading fails, the system operates with the original version. To address the failure cause, take these steps:
1) Check that the physical ports are correctly and securely connected. If they are not,
reconnect them correctly and restart loading.
2) Check information about the loading procedures for input errors on the
HyperTerminal.
z If XModem is used, check that you have reset the baud rate of the HyperTerminal
to 9600 bps after loading the software with another baud rate.
z If TFTP is used, check that you have correctly specified the TFTP parameters:
server and switch IP addresses; name of the software to be loaded; and path for the TFTP server to operate on program files.
z If FTP is used, check that you have correctly specified the FTP parameters: server
and switch IP addresses; name of the software to be loaded; and username and password.
3) Contact your sales agent for help if you cannot address the problem after taking
the preceding two steps.
6.2 Dealing with Password Loss
Contact your sales agent if you lost the BootROM password or user password.
6.3 Dealing with Power System Failures
Y ou can know whether th e power system has failed by reading the POWE R LED on the front panel. If the power system is operating normally, the POWER LED is ON. If not, check that:
z The switch power cord is correctly connected. z The power source can work with the switch.
6.4 Dealing with Configuration System Failures
If the switch is operating normally after it is powered up, it displays the start-up information on the console terminal. If the configuration system has failed, it displays illegible characters or nothing at all.
Page 67
Installation Manual H3C S5600 Series Ethernet Switches Chapter 6 Maintenance and Troubleshooting
6-2
I. No information on the terminal
Take these steps to address the problem:
1) Check that:
z The power system is operating normally. z The console cable is connected correctly.
2) Check that the console cable is in good condition and the terminal (HyperTerminal
for example) parameter settings are correct.
II. Illegible characters on the terminal
Make sure you have set on your terminal (HyperTerminal): Baud rate = 9600 Databit = 8 Parity check = none Stopbit = 1 Flow control = none Terminal emulation = VT100
Page 68
Installation Manual H3C S5600 Series Ethernet Switches Table of Contents
i
Table of Contents
Appendix A Lightning Protection of the Switch.........................................................................A-1
A.1 Installation of Lightning Arrester for AC Power (Socket Strip with Lightning Protection)..A-1
A.2 Installation of Lightning Arrester for Network Port.............................................................A-2
Page 69
Installation Manual H3C S5600 Series Ethernet Switches Appendix A Lightning Protection of the Switch
A-1
Appendix A Lightning Protection of the Switch
A.1 Installation of Lightning Arrester for AC Power (Socket Strip with Lightning Protection)
Caution:
Lightning arrester will not be shipped with the switch. You should purchase it by yourself if needed.
If an outdoor AC power cord should be directly led to the switch, please serially connect the lightning arrester for AC power (Socket Strip with Lightning Protection) before you plug AC power cord into the switch, thus to prevent the possible damage to the switch due to lightning strike. You can use cable clips and screws to fasten the lightning arrester for AC powe r on the cabinet, workbench or the wall of equipment room.
Mainboard
Grounding and polarity indicator (red) : On means that the lines are wrongly connected (either the ground wire is not well connected, or the live and zero lines are wrongly connected). Please check the power supply circuit.
Power switch
Normal operation indicator (green): On means that the arrester works norma lly . Other wise, it means that the protection circuit has been damaged.
Multipurpose power socket, connected to the device
protected by the arrester
Power socket (complied with IEC standar d) , connected to the power supply of the equipment room through power cord
Overload auto protector, which can be manually reset.
Figure A-1 Diagram of lightning arrester
Page 70
Installation Manual H3C S5600 Series Ethernet Switches Appendix A Lightning Protection of the Switch
A-2
Caution:
z Make sure that the arrester is well grounded before using the lightning arrester for
power.
z After inserting AC power cord plug of switch into the socket of lightning arrester, if
the green LED is on and the red LED does not alarm, it means that the lightning arrester of power is running and the function of lightning protection has taken effect.
z Pay adequate attention if the red LED is on. You should correctly locate the proble m,
whether it is caused because the ground wire of the arrester is not well grounded or because the live and zero wires are connected in reverse direction. You may check that in the following way. When the red LED is on, use a multimeter to examine polarity at the power socket of the arrester. If it is same to that of the power socket in the equipment room, it means that arrester is not well grounded. If it is adverse to that of the power socket in the equipment room, it means that the power socket of the arrester is set to the reverse polarity. In this case, you should open the power socket of arrester to correct polarity. After that, if the red LED still alarms, it means that the arrester is not well grounded yet.
A.2 Installation of Lightning Arrester for Network Port
Note:
Lightning arrester for network port is specially designed for the Ethernet port of 10/100M electrical interface (RJ-45 connector is adopted in this case).
Caution:
Lightning arrester for network port will not be provided along with the switch, and you should purchase it by yourself if needed.
If an outdoor network cable should be led to the switch, please serially connect the lightning arrester for network port before you plug this cable into the interface on the switch, in case of the possibility that the switch may be damaged due to lightning strike.
I. Required tools
z Phillips screwdriver or Flat-blade screwdriver
Page 71
Installation Manual H3C S5600 Series Ethernet Switches Appendix A Lightning Protection of the Switch
A-3
z Multimeter z Tilted wire cutter
II. Installation procedure
Step 1: Tear the protection paper at one side of the double faced adhesive tape apart from the tape, and stick the tape on the surface of the arrester. Tear the protection paper at another side apart from the ta pe, and stick the arrester onto the ch assis of the switch. The arrester should be attached on the chassis as close to the grounding screw as possible.
Step 2: According to the distance to the grounding screw of the switch, cut the ground wire of the arrester, and securely tightening its ground wire to the grounding screw of the switch.
Step 3: Use the multimeter to measure whether the g round wire of the arrester contacts well with the grounding screw of chassis.
Step 4: According to the instruction of arrester for network port, connect the arrester with switch by the cables (be carefully with the cable direction. Outdoor network cable should be inserted into the arrester‘s IN end, and the cable connected to the switch should be inserted into the arrester’s OUT end). When you do that, observe whether the arrester indicators normally display.
Note:
The instruction of lightning arrester for network port contains the technical specifications, installation and maintenance guide of the arrester. Please carefully read it before installing the arrester.
Step 5: Use the nylon ties to bundle the cables neatly.
Switch
Network cable indoors
Power input
Network cable led into from outdoor
Lightning arrester for network port (attached onto the chassis)
Ground wire of lightning arrester
Grounding screw of switch
Metal cabinet that contains the switch
Figure A-2 Installation diagram of lightning arrester for network port
Page 72
Installation Manual H3C S5600 Series Ethernet Switches Appendix A Lightning Protection of the Switch
A-4
III. Installation precautions
Fully consider the following items in the installation process, otherwise, the performance of the lightning arrester for network port will be affected:
z Lightning arrester for network port is installed in reverse direction. In practice, the
“IN” end should be connected to the outdoor network cable and the “OUT” end to the network port on the switch.
z Lightning arrester for the network port is not well grounded. The ground wire for
the arrester should be as short as possible, so to ensure its good contact with the grounding screw of the switch. After the connection, use the multimeter to confirm that.
z The lightning arrester for the network port is not installed completely. If the switch
has more than one network ports to interconnect with other devices via cables outdoor, you should install lightning arresters for all these network ports for protection.