GW-INSTEK PSB-2800L User guide

Multi-Range DC Power Supply
PSB-2000 series
User Manual
ISO-9001 CERTIFIED MANUFACTURER
Copyright Statement
This manual contains proprietary information, which is protected by copyright. All rights are reserved. No part of this manual may be photocopied, reproduced or translated to another language without prior written consent of Good Will company.
The information in this manual was correct at the time of printing. However, Good Will continues to improve products and reserves the rights to change specification, equipment, and maintenance procedures at any time without notice.
Good Will Instrument Co., Ltd. No. 7-1, Jhongsing Rd., Tucheng Dist., New Taipei City 236, Taiwan.
Table of Contents
Table of Contents
SAFETY INSTRUCTIONS .................................................. 3
GETTING STARTED .......................................................... 7
PSB 2000 Series Overview ................................ 8
Appearance .................................................... 15
OPERATION .................................................................. 32
Connecting the AC Power Cable ...................... 32
Connecting the Load to the Output Terminals 32 Operation Ranges (PSB-2400L, 2800L, 2400L2,
2800LS) .......................................................... 41
Operation Ranges (PSB-2400H, 2800H) ......... 42
Various Settings ............................................. 43
Menu Key Functions ....................................... 50
Voltage Sense ................................................. 74
External Control Functions ............................. 76
Using the Sequence Function ......................... 86
OTHER FUNCTIONS ...................................................... 89
Display in Alarm Status .................................. 89
Frame Link Controlled Parallel Operation
(excluding PSB-2400L2) .................................. 91
Frame Link Controlled Series Operation
(excluding PSB-2400L2, PSB-H series) ........... 93
Power Extension using PSB-2800LS (Parallel
Connection Only) ........................................... 94
Using the PSB-007 Extension kits ................... 95
EXTERNAL CONTROL .................................................... 99
Remote Control .............................................. 99
Interface Connectors .................................... 100
1
PSB-2000 Series User Manual
PSB-001 Specifications (optional) ................ 100
PSB-002 Specifications (standard) ................ 101
Connection Methods .................................... 102
Connection Cables ........................................ 104
Address Setting ............................................ 105
Using the Interface Boards ........................... 108
Communication Commands ......................... 111
Registers ...................................................... 133
APPENDIX .................................................................... 143
Trouble Shooting .......................................... 143
Maintenance ................................................. 145
Dimensions .................................................. 147
PSB-2000L Series Specifications ................... 150
PSB-2000H Series Specifications .................. 158
EC Declaration of Conformity ....................... 163
2
SAFETY INSTRUCTIONS
WARNING
Warning: Identifies conditions or practices that could result in injury or loss of life.
CAUTION
Caution: Identifies conditions or practices that could result in damage to the PSB or to other properties.
DANGER High Voltage
Attention Refer to the Manual
Protective Conductor Terminal
Earth (ground) Terminal
Do not dispose electronic equipment as unsorted municipal waste. Please use a separate collection facility or contact the supplier from which this instrument was purchased.
SAFETY INSTRUCTIONS
This chapter contains important safety instructions that you must follow during operation and storage. Read the following before any operation to insure your safety and to keep the instrument in the best possible condition.
Safety Symbols
These symbols may appear in the manual or on the instrument.
3
PSB-2000 Series User Manual
General Guideline
CAUTION
Do not place any heavy object on the unit. Avoid severe impact or rough handling that
leads to damaging the unit.
Do not discharge static electricity to the unit. Do not block the cooling fan opening. Do not perform measurements on circuits that
are directly connected to mains power.
Do not disassemble the PSB unless you are
qualified.
(Measurement categories) EN 61010-1:2010 specifies the measurement categories and their requirements as follows. The PSB-2000 doesn’t fall under category II, III or IV.
Measurement category IV is for measurement performed at the
source of low-voltage installation.
Measurement category III is for measurement performed in the
building installation.
Measurement category II is for measurement performed on the
circuits directly connected to the low voltage installation.
O is for measurements performed on circuits not directly
connected to Mains.
Power Supply
WARNING
AC Input voltage range: 100Vac to 240Vac,
1300VA Max
Frequency: 50Hz/60Hz To avoid electrical shock connect the protective
grounding conductor of the AC power cord to an earth ground.
Safety Guidelines
4
SAFETY INSTRUCTIONS
Cleaning the power supply
Disconnect the power cord before cleaning the
oscilloscope.
Use a soft cloth dampened in a solution of mild
detergent and water. Do not spray any liquid into the oscilloscope.
Do not use chemicals containing harsh products
such as benzene, toluene, xylene, and acetone.
Operation Environment
Location: Indoor, no direct sunlight, dust free,
almost non-conductive pollution (Note below)
Relative Humidity: 30% to 80% (no dew or
condensation)
Altitude: < 2000m Temperature: 0°C to 40°C
(Pollution Degree) EN 61010-1:2010 specifies pollution degrees and their requirements as follows. The PSB falls under degree 2.
Pollution refers to “addition of foreign matter, solid, liquid, or
gaseous (ionized gases), that may produce a reduction of dielectric strength or surface resistivity”.
Pollution degree 1: No pollution or only dry, non-conductive
pollution occurs. The pollution has no influence.
Pollution degree 2: Normally only non-conductive pollution
occurs. Occasionally, however, a temporary conductivity caused by condensation must be expected.
Pollution degree 3: Conductive pollution occurs, or dry, non-
conductive pollution occurs which becomes conductive due to condensation which is expected. In such conditions, equipment is normally protected against exposure to direct sunlight, precipitation, and full wind pressure, but neither temperature nor humidity is controlled.
Storage environment
Location: Indoor Relative Humidity: 30% to 70% (no dew or
conensation)
Temperature: -20°C to 70°C
5
PSB-2000 Series User Manual
Green/ Yellow:
Earth
Blue:
Neutral
Brown:
Live (Phase)
Power cord for the United Kingdom
When using the power supply in the United Kingdom, make sure the power cord meets the following safety instructions.
NOTE: This lead/appliance must only be wired by competent persons
WARNING: THIS APPLIANCE MUST BE EARTHED IMPORTANT: The wires in this lead are coloured in accordance with the following code:
As the colours of the wires in main leads may not correspond with the coloured marking identified in your plug/appliance, proceed as follows:
The wire which is coloured Green & Yellow must be connected to the Earth terminal marked with either the letter E, the earth symbol or coloured
Green/Green & Yellow.
The wire which is coloured Blue must be connected to the terminal which is marked with the letter N or coloured Blue or Black.
The wire which is coloured Brown must be connected to the terminal marked with the letter L or P or coloured Brown or Red.
If in doubt, consult the instructions provided with the equipment or contact the supplier.
This cable/appliance should be protected by a suitably rated and approved HBC mains fuse: refer to the rating information on the equipment and/or user instructions for details. As a guide, a cable of 0.75mm2 should be protected by a 3A or 5A fuse. Larger conductors would normally require 13A types, depending on the connection method used.
Any exposed wiring from a cable, plug or connection that is engaged in a live socket is extremely hazardous. If a cable or plug is deemed hazardous, turn off the mains power and remove the cable, any fuses and fuse assemblies. All hazardous wiring must be immediately destroyed and replaced in accordance to the above standard.
6
GETTING STARTED
GETTING STARTED
The PSB series are variable output, high­performance, regulated, switching DC power supplies. They incorporate a high-frequency current suppression circuit and accept input voltages rated from AC100V to 240V without the need to switch inputs. The offer a wide voltage and current range within their maximum rated power envelope. They also have a variable constant power function. They have standard features such as voltage and current settings, an output on/off switch, monitor outputs and other functions via external connectors. The chasis is smaller overall than traditional power supplies to reduce the total work area. The dual channel model and the booster unit extend the series to cover a wider range of applications. The PSB series are also able to execute sequence programs that are written using the optional interface boards.
The optional interface boards also allow you to control the PSB series remotely from a PC using GPIB, RS232C or USB.
7
PSB-2000 Series User Manual
Product name
Voltage range
Current range
Power range
PSB-2400H
0V to 800V
0A to 3A
0W to 400W
PSB-2800H
0V to 800V
0A to 6A
0W to 800W
PSB-2400L
0V to 80V
0A to 40A
10W to 400W
PSB-2800L
0V to 80V
0A to 80A
10W to 800W
PSB-2400L2 (Dual channel type)
0V to 80V ×2CH
0A to 40A ×2CH
10W to 400W ×2CH
PSB-2800LS (Booster unit)
0V to 80V
0A to 80A
10W to 800W
Product name
PSB-2400L
(CE)
PSB-2800L
(CE)
PSB-2400L2
(CE)
PSB-2800LS
(CE)
PSB-2400H
(Non-CE)
PSB-2800H
(Non-CE)
PSB 2000 Series Overview
Series line up
CE Mark
8
GETTING STARTED
400W Type
PSB-2400L
800W Type
PSB-2800L
400W×2-Channel Type   PSB-2400L2
800W Type
Booster unit
PSB-2800LS
400W Type
PSB-2400H
800W Type
PSB-2800H
9
PSB-2000 Series User Manual
Multi-Range Output
Capable of a wide-range of voltage and current settings within the rated power envelope.
Constant-Power Control
Provides constant-power (CP) control in addition to constant-voltage (CV) and constant-current (CC) controls.
Power Factor Correction Circuit
A built-in power factor correction circuit ensures compatibility to a wide AC input voltage range from AC100V to 240V without the need to use a switch. It also suppresses harmonic current.
Rotatable Front Panel Controls
The front panel can be rotated by 90 degrees to allow the unit to be operated horizontally or vertically.
Output Off Timer Function
Turns the output off automatically after a preset amount of time has elapsed. This can be used to prevent the output from being left on inadvertently or to prevent over-charging.
Sequence (SEQ) Function
The Sequence function executes data read from a PC through one of the optional interface boards (PSB­001 and PSB-002). There are two operation modes for the sequence function: Manual mode (for step by step execution) and automatic mode (for automatic execution of up to 99 steps and 999 cycles).
Protective Functions
The power supplies have a number of protection functions. OVP, OCP and OHP. OVP and OCP protection can be set on the front panel.
Preset Functions (Three Settings)
Pressing a preset key directly selects a preset setting, which is set in advance.
Main Features
10
GETTING STARTED
Single Unit Control of Parallel/Series Operation
The PSB-L series uses a single power supply unit (acting as the master unit) to control all connected slave units for series or parallel operation. In parallel, up to 4 units can be controlled (including the master) to increase the total power. In series, a maximum of 2 units (including the master) can be used.
External Control Function
The external control function allows external voltage and restistance-based control, voltage and current monitoring, output on/off control, alarm output and CV/CC status output.
Interface Boards
There are two optional interface boards for remote control.
PSB-001: GPIB and local bus board.
PSB-002: RS-232C, USB and local bus board.
Note also that one of these options must be used to program sequences for the PSB-L series. See page 86 for further details.
Dual Channel Model (PSB-2400L2)
Equipped with two 400W output channels for a wide variety of applications.
Delay (DLY) Function: (PSB-2400L2 Only)
The delay function introduces a switching delay between channel 1 and 2. The delay function can set a rising delay (the time to turn on) and a falling delay (the time to turn off).
Tracking Function: (PSB-2400L2 Only)
The channel 2 setting is made equal to that of channel 1 when the tracking function is activated. Thereafter, both channels change synchronously.
11
PSB-2000 Series User Manual
Model Number
Description
PSB-001
GPIB Control Board. Includes GRJ-1101 modular cables. For further details, see page 100.
PSB-002
RS-232C/USB Control Board. Includes GRJ-1101 modular cables. For further details, see page 101.
PSB-003
Parallel Connection Kit for Horizontal Installation.
Kit includes: PSB-007 Joint kit, Horizontal bus bar x2, PSB-005 x1.
PSB-007 Joint Kit
Horizontal Bus Bar
PSB-005
PSB-004
Parallel Connection Kit for Vertical Installation.
Kit includes: PSB-007 Joint kit, Verical bus bar x2, PSB­005 x1.
PSB-007 Joint Kit
Accessories
12
GETTING STARTED
Vertical Bus Bar
PSB-005 PSB-005
Parallel Connection Signal Cable
PSB-006
Serial Connection Signal Cable
PSB-007
Joint Kit:
Includes 4 joining plates, 4X M3x6 screws, 2X M3x8 screws.
PSB-008
RS-232C Cable
GRJ-1101
Modular Cables: 500mm 6P6C RJ11 (local bus cables)
13
PSB-2000 Series User Manual
Model Number
Description
User Manual CD x 1
AC power cable x 1
Screws for output terminals on rear panel
Protection covers for output terminals on rear panel
Protection caps for output terminals on the front panel
External control connector (26-pin)
GND cable
Standard Accessories
14
GETTING STARTED
2 3 4 14 15 16 17 18 19 20 21 22
POWER
CHECK
ENTER
REMOTE
FAST
LOCK
Hi -
W
V A
CV
MENU
SEQUENCE
PRESET
321
FAST/LOCK(3s)
/LOCAL
OUTPUT
OFF TIMER
DISP
ESCMENU
W
CC CP
A W
R
O
T
A
T
E
V
W
Multi- Range DC Power Supply
DELAY
CH 2
CH 2
CH 1
DISP
CH 1
( L Type ONLY)
CH A
MAX 400W MAX DC 80V MAX DC 40A
CH B
PSB-2400L2
ON / OFF
1 5 6 7 8 9 10 11 12 13
Appearance
Front Panel (PSB-2400L2 shown)
15
PSB-2000 Series User Manual
1 5 6 7 8 9 10 11 12 13
2 3 4 14 15 16 17 18 19 20 21 22
POWER
CAUTION
MAX 400W
MAX DC 800V
MAX DC 3A
PSB - 2400 H
CHECK
ENTER
REMOTE
FAST
LOCK
Hi -
W
V A
CV
MENU
SEQUENCE
PRESET
321
FAST/LOCK(3s)
/LOCAL
OUTPUT
OFF TIMER
DISP
ESCMENU
W
CC CP
A
W
R
O
T
A
T
E
V
(
L Type ONLY
)
W
Regulated DC Power Supply
ON / OFF
PSB-2800LS
Multi-Range DC Power Supply
2 1
Front Panel (PSB-2400H shown)
Front Panel (PSB-2800LS)
16
GETTING STARTED
Item
Description
1
Front grill
This is a ventilation grill for for cooling the internal circuits. It is detachable and has a dust filter inside. Clean the filter periodically. See page
143.
2
Rubber feet
Detachable. If the unit is mounted in a rack and the feet are not needed, they may be removed.
3
POWER ON/OFF switch
Depress the switch to the (I) position to turn on the power supply unit. Press it again to turn off the unit.
4
Front output terminals
Output is supplied through these terminals. The maximum current is 3A(2400H) or 6A(2800H), 40A(2400L, 2400L2), 80A(2800L, 2800LS). The 40A/80A models use screw-type terminals. The 3A/6A models use European-type jack terminals.
17
PSB-2000 Series User Manual
PSB-2400L, PSB-2800L PSB-2400H, PSB-2800H
PSB- 2400L2
Type
Description
5
Address no., Step no., cycle no., Menu no.
Normal operation
Sequence operation
Menu
Tracking
Not displayed.
Number of steps or cycles is displayed.
Menu No. is displayed.
“Ab” is
displayed.
6
Channel LEDs
The LED of the selected channel is lit. Both LEDs are lit when the tracking function is activated.
7
Current LED (7-segment)
Normal operation
Sequence operation
Menu
Alarm
Current or power is displayed.
Step No. is displayed.
Set item is displayed.
OVP, OCP, HARD or OHP is displayed.
The “W” LED on the right of the 7-segment LED is lit in the power display state.
Panel Operation Unit
18
GETTING STARTED
8
Voltage LED (7-segment)
Normal operation
Sequence operation
Menu
Alarm
Voltage or power is displayed.
Cycle No. is displayed.
Set parameter is displayed.
OVP, OCP, HARD or OHP is displayed.
The “W” LED on the right of the 7-segment LED is lit in the power display state.
9
Function LEDs
These LEDs display the On/Off state of the OFF
TIMER, DELAY or HiΩ functions. The LED is lit
green when the corresponding function is activated.
10
ESC/DISP key (ESC /
DISP)
Changes the channel display, sequence operation display (i.e., step No. and cycle No.), remaining time for the off-timer and other displays. When the menu is displayed, pressing it exits the function selection mode and returns to the normal mode.
11
OUTPUT key (red) ( OUTPUT )
This key turns on or off the output. The LED is lit when the output is turned on.
12
CH1 and CH2 keys (red, green, orange) ( CH1 , CH2 )
These keys turn on or off the channel outputs. The color of the corresponding LED indicates the output mode.
Green: CV mode.
Red: CC mode.
Orange: CP mode.
The CH1 and CH2 keys are only available for the PSB-2400L2 only. The PSB-2400L and PSB-2800L have single LEDs only.
19
PSB-2000 Series User Manual
13
Rotary encoder
Used to select the functions and change the values.
14
V key (green) ( V )
Used for setting the voltage. Press the key and rotate the encoder to change the set value. If the A key is pressed while holding the V key, both LEDs are lit and the Current LED enters the power display mode.
15
A key (green) ( A )
Used for setting the current. Press the key and rotate the encoder to change the set value. If the V key is pressed while holding the A key, both LEDs are lit and the Voltage LED enters the power display mode.
16
PRESET 1 key (green) (PRESET 1 )
Reads out data stored in PRESET 1. Serves as a start/pause key ( ) in the sequence mode.
17
PRESET 2 key (green) (PRESET 2 )
Reads out data stored in PRESET 2. Serves as a
back key ( ) to a skip to previous step number in the sequence mode.
18
PRESET 3 key (green) (PRESET 3 )
Reads out data stored in PRESET 3. Serves as a
forward key ( ) to skip to the next step number in the sequence mode.
19
MENU key (MENU )
Used for setting and selecting various functions.
20
GETTING STARTED
20
ENTER/ CHECK Key (ENTER /
CHECK)
Alternates the operation (and display) between the output value and the set value. When the output is on, every press of the ENTER /
CHECK key alternates the display between the
output value and set value. When the V key is lit The voltage setting is
enabled.
When the A key is lit The current setting is
enabled.
When the V and A keys are lit the power
setting is enabled.
When the menu is displayed, press this key to validate functions and values in the menu.
21
FAST/LOCK (3s)/LOCAL key(FAST )
Changes the resolution of the voltage, current or power settings, locks panel operation, or switches the remote mode into the local mode. The color of the LED indicates the current status. FAST (green): The setting resolution is 1V, 1A or 100W. LOCK (3s) (red): Operations on the front panel are disabled. REMOTE (orange): Lit during communication through the optional interface boards.
22
ROTATE key
The operating panel of the PSB-2000 series can be rotated 90 degrees so that the unit can be used in the horizontal or vertical position. Hold the encoder and rotate the panel operation unit while holding the key.
21
PSB-2000 Series User Manual
PSB-002
LOCAL BUS
I I IUSB
J3
EXT CONT
J2
AC INPUT
1
2 26
25
CH 2
CH 1
J1
MADE IN TAIWAN
100V-240V 50Hz / 60Hz
650 VA MAX
MAX 400W MAX DC 80V MAX DC 40A
!
OUTPUT
DC
MAX 400W MAX DC 80V MAX DC 40A
!
OUTPUT
DC
!
23 24 25 26 27 28 29 30 31
J3
EXT CONT
J2
AC INPUT
1
2 26
25
CH 1
J1
MADE IN TAIWAN
PSB-001
LOCAL BUS GP-IB
100V-240V 50Hz / 60Hz 650 VA MAX
MAX 400W MAX DC 80V MAX DC 40A
!
OUTPUT
DC
!
23 24 25 26 27 28 29 30 31
Rear Panel (PSB-2400L2)
Rear Panel (PSB-2400L/PSB-2800L)
22
GETTING STARTED
23 24 25 26 27 28 29 30 31
PSB-002
LOCAL BUS
I I IUSB
2
1
EXT CONT
J3
26
J1 J2
AC INPUT
25
MADE IN TAIWAN
DC
OUTPUT
!
MAX DC 3A
MAX DC 800V
MAX 400W
+  +S
CAUTION
-S   -
!
J2
AC INPUT
CH 1
J1
MADE IN TAIWAN
100V-240V
50Hz / 60Hz
650 VA MAX
MAX 400W MAX DC 80V MAX DC 40A
!
OUTPUT
DC
!
26 27 28 29 30 31
Rear Panel (PSB-2800H)
Rear Panel (PSB-2800LS)
23
PSB-2000 Series User Manual
Description
23
Optional Interface board slot
The optional interface board slot is used to install the optional PSB-001 board for the GPIB interface.
The product is supplied with the USB/RS-232C option as standard.
24
J3 external control connector
The external control connector is used to control or monitor a number of different parameters using external components. The pin assignment of this connector can be found on page 26(40A models) 30(3A/6A models).
25
Sensing terminals
The sensing terminals are used to change the sensing point. These terminals are short-circuited before shipment to select internal sensing.
26
Rear output terminals
The Output of the PSB-2000 series power supply unit is also output through these terminals. The type of rear panel output terminal varies depending on the model. The PSB-2400H and PSB-2800H use pin terminals and the PSB-L models use crimp style voltages designed to accommodate higher current.
For the PSB-2400L2 (dual channel model), the channel 1 terminal block is in the upper part (CH1) and the channel 2 terminal block is in the lower part (CH2) of the rear panel when the unit is viewed from the back. On each terminal block, the positive () terminal is on the left and the negative () terminal is on the right when the unit is viewed from the back. Connect either output terminal to the screw marked with the ground signal if it needs to be grounded with the chassis.
24
GETTING STARTED
27
J1 control signal input connector
This connector is used for parallel and serial control for master/slave operation. The optional frame link cables must be used with this connector.
28
J2 control signal output connector
This connector is used for parallel and serial control for master/slave operation. The optional framelink cables must be used with this connector.
29
Exhaust Grill
Air taken into the unit from the front is blown out through this grill. Leave a gap of a least 30cm or more behind the rear panel for good ventilation. If there is an object obstructing the rear panel, the temperature inside the power supply unit may rise excessively.
30 Functional
ground terminal
The unit can be grounded using this terminal
31
AC INPUT
Connect the AC power cable supplied with the unit with this plug receptacle and supply AC power to the unit.
25
PSB-2000 Series User Manual
Pin No.
Signal name
Function
1
CH2 STATUS COM (COM for 2, 3 & 4)
COM for pins 2, 3 and 4.
2
CH2 ALARM OUT
Open collector output. When the alarm is output for channel 2 then this pin is pulled low.
3
CH2 EXT CC STATUS OUT
Open collector output. Set to the low level when channel 2 is in CC mode.
4
CH2 EXT CV STATUS OUT
Open collector output. Set to the low level when channel 2 is in CV mode.
5
CH2 EXT CV CONTROL IN
Constant-voltage control input pin for channel 2.
In the external voltage control mode, an external voltage of 0V to 10V can be used to control the output voltage from 0V to the rated output voltage. In the external resistance control mode,
an external resistance of 0kΩ to 10kΩ
can be used to control the output voltage from 0V to the rated output voltage.
Pin assignment of the J3 External Control Connector (PSB-2400L, 2800L, 2400L2, 2800LS)
26
GETTING STARTED
6
CH2 EXT CC CONTROL IN
Constant-current control input pin for channel 2.
In the external voltage control mode, an external voltage of 0V to 10V can be used to control the ouput current from 0A to the rated output current. In the external resistance control mode,
an external reistance of 0kΩ to 10kΩ can
be used to control the output current from 0A to the rated output current.
7
CH2 COM
COM pin for channel 2. Connected to the negative output terminal of channel 2.
8
CH2 EXT V MON OUT
Output voltage monitor pin for channel
2. Outputs a voltage of approximately 0V to 10V to represent 0V to the rated output voltage.
9
CH2 EXT A MON OUT
Output current monitor pin for channel
2. Outputs a voltage of approximately 0V to 10V to represent 0A to the rated output current.
10
CH2 COM
COM pin for channel 2. Connected with the negative output terminal of channel
2.
11
CH2 EXT ALARM IN
Causes the alarm state to be triggered when short-circuited with the CH2 COM pin.
12
CH2 EXT OUTPUT IN
This pin turns the CH2 output on when it is shorted to the CH2 COM pin.
27
PSB-2000 Series User Manual
13
CH2 COM
COM pin for channel 2. Connected with the negative output terminal of channel
2.
14
CH1 EXT CV CONTROL IN
Constant-voltage control input pin for the channel 1.
In the external voltage control mode, an external voltage of 0V to 10V can be used to control the output voltage from 0V to the rated output voltage. In the external resistance control mode,
an external resistance of 0kΩ to 10kΩ
can be used to control the output voltage from 0V to the rated output voltage.
15
CH1 EXT CC CONTROL IN
Constant-current control input pin for channel 1.
In the external voltage control mode, an external voltage of 0V to 10V can be used to control the ouput current from 0A to the rated output current. In the external resistance control mode,
an external reistance of 0kΩ to 10kΩ can
be used to control the output current from 0A to the rated output current.
16
CH1 COM
COM pin for channel 1. Connected with the negative output terminal of channel 1.
17
CH1 EXT V MON OUT
Output voltage monitor pin for channel
1. Outputs approx. 0V to 10V to represent 0V to the rated output voltage.
28
GETTING STARTED
18
CH1 EXT A MON OUT
Output current monitor pin for channel
1. Outputs approx. 0V to 10V to represent 0 to the rated output current.
19
CH1 COM
COM pin for channel 1. Connected with the negative output terminal of channel 1.
20
CH1 EXT ALARM IN
Causes the alarm state to be triggered when short-circuited with the CH1 COM pin.
21
CH1 EXT OUTPUT IN
Turns on the CH1 output when short­circuited with the CH1 COM pin.
22
CH1 COM
COM pin for channel 1. Connected with the negative output terminal of channel 1.
23
CH1 EXT CV STATUS OUT
Open collector output. Set to the low level when channel 1 is in CV mode.
24
CH1 EXT CC STATUS OUT
Open collector output. Set to the low level when channel 1 is in CC mode.
25
CH1 ALARM OUT
Open collector output. Set to the low level when channel 1 is in the alarm mode.
26
CH1 STATUS COM (COM of 23, 24 &
25)
COM for pins 23, 24 and 25.
29
PSB-2000 Series User Manual
Pin No.
Signal name
Function
13
NC
14
EXT CV CONTROL IN
Constant-voltage control input pin.
In the external voltage control mode, an external voltage of 0V to 10V can be used to control the output voltage from 0V to 800V. In the external resistance control mode,
an external resistance of 0kΩ to 10kΩ
can be used to control the output voltage from 0V to 800V.
15
EXT CC CONTROL IN
Constant-current control input pin.
In external voltage control mode, an external voltage of 0V to 10V can be used to control the output current from 0A to 3A(2400H) or 6A(2800H).
In the external resistance control mode,
an external resistance of 0kΩ to 10kΩ
can be used to control the output current from 0A to 3A(2400H) or 6A(2800H).
16
COM
COM Connected with the negative output terminal.
17
EXT V MON OUT
Output voltage monitor pin. Outputs approx. 0V to 10V to represent the output voltage from 0V to 800V.
Pin assignment of J3 external control connector (PSB-2400H, 2800H)
30
GETTING STARTED
18
EXT A MON OUT
Output current monitor pin Outputs approx. 0V to 10V to represent the outuput current from 0A to 3A(2400H) or 6A(2800H).
19
COM
COM Connected with the negative output terminal.
20
EXT ALARM IN
Trigger the alarm state when short­circuited with the COM pin.
21
EXT OUTPUT IN
Turns on the output when short­circuited with the COM pin.
22
COM
COM Connected with the negative output terminal.
23
EXT CV STATUS OUT
Open collector output. Set to the low level when the channel is in CV mode.
24
EXT CC STATUS OUT
Open collector output. Set to the low level when the channel is in CC mode.
25
ALARM OUT
Open collector output. Set to the low level when the channel is in the alarm mode.
26
STATUS COM
COM for pins 23, 24 and 25.
31
PSB-2000 Series User Manual
Introduction
Make sure that the power source is shut off. Use the AC power cable supplied with the
product.
Plug the connector of the AC power cable into
the AC INPUT receptacle on the rear panel.
Introduction
Use cables with a rated voltage that exceeds the grounding voltage (500V) for the load.
The front output terminals and rear output terminals are electrically connected internally. When the front output terminals are used, the rear output terminals are also active. Put the protective covers supplied with the product on the rear output terminals to avoid electrocution.
CAUTION
Make sure that the load is only connected when the POWER switch is off.
To connect a load, use cables that have a large enough current capacity for the rated output and
OPERATION
This chapter describes the start up procedures and the preparation that is necessary before operating the DC power supply.
Connecting the AC Power Cable
Connecting the Load to the Output Terminals
32
OPERATION
current in order to prevent a fire.
The current capacity of the cables should be higher still if the cables are twisted to reduce noise or to avoid malfunctioning.
Be careful of the
temperature!
Procedure
1. Remove the AC cable from the AC INPUT.
2. Connect crimped lug terminals to the ends of
the load cables. Tighten the lug terminals firmly using the nuts supplied with the power supply.
CAUTION
The rear output terminals have M6 holes and M3 (tapped) holes. Be sure to use the M6 holes to connect the load. Noise at the load end may be reduced by twisting the load cables or connecting a film capacitor
(several μF, low-impedance, high-frequency) and an electrolytic capacitor (several hundred μF) to
the load end.
Connecting to the Rear Output Terminals (PSB-2400L, 2800L, 2400L2, 2800LS)
33
PSB-2000 Series User Manual
Fig. Connection with Rear Output Terminals
Bolt (M6)
Washer
Nut
Terminal block
Output terminal bar
Note
Connect the cables using the bolts supplied with the power supply as shown above. If different bolts are used, they may contact the protective cover or interfere with the protective cover. The lug terminals must be on the outside of the output terminals.
3. Connect the positive or negative output terminal
to the GND screw with the symbol using the GND cable supplied with the product as the necessity requires.
Note
The negative potential of the external voltage control pin is the same as that of the negative output terminal. If the power supply unit is grounded at the positive terminal and the power source for external control is grounded at the negative terminal, the load cables for external voltage control will short-circuit the output of the power supply unit, which could damage the unit. In this situation, make sure the external voltage control source is floating with respect to the output terminals.
34
OPERATION
Fig. Positive Grounding Connection
Connect with this screw
4. Sandwich the output terminals and the load
cables from above and below with the rear output terminal protective covers, as shown below. Drive the screw into the protective covers at the center.
Fig. Attaching Rear Output Terminal Protective Covers
CAUTION
Make sure that the protection covers are always attached to the terminals even when they are not being used.
The front and rear output terminals are electrically connected internally. Touching a terminal that is not protected may induce an electric shock.
35
PSB-2000 Series User Manual
The rear output terminals have M6 holes and M3 (tapped) holes. Be sure to use the M6 holes to connect the load. Noise at the load end may be reduced by twisting the load cables or connecting a film capacitor (high-frequency, low-impedance
(several μF) and an electrolytic capacitor (several hundred μF) to the load end.
5. Cut the shaded parts shown below with cutting
pliers or the like to connect the power supplies in series or in parallel or to ground the output.
Fig. Parts to be cut
Procedure
1. Remove the AC cable from the AC INPUT.
2. Insert the load line and then use a flathead
screwdriver or similar tool to firmly secure it.
3. If necessary, use the supplied output ground
cable and screw to establish a positive or negative ground connection to the output ground terminal ( mark).
Parts to be cut
Parts to be cut Parts to be cut
Connection with the Rear Output Terminals (PSB-2400H, 2800H)
36
OPERATION
CAUTION
Noise at the load end may be reduced by twisting the cables to the load or connecting a film capacitor (low impedance, high-frequency, several
μF) and an electrolytic capacitor (several hundred μF) to the load end.
Fig. Connection with Rear Output Terminals
負荷線
ライバー
A flathead screwdriver or similar tool
Load line
Note
The negative potential of the external voltage control is the same as that of the negative output terminal. If the power supply unit is grounded at the positive terminal and the power source for external control is grounded at the negative terminal, the load cables for external voltage control will short-circuit the output of the power supply unit, which could damage the unit. In this situation, make sure the external voltage control source is floating with respect to the output terminals.
Fig. Positive Grounding Connection
37
PSB-2000 Series User Manual
CAUTION
The front and rear output terminals are electrically connected internally. Terminals that are NOT in use still carry output voltage.
Be careful not to touch the terminals. Failure to heed this warning may result in electric shock.
38
OPERATION
Procedure
1. Turn on the unit using the POWER switch.
2. Connect crimped lug terminals to the ends of
the load cables. Fix the load cables firmly to eliminate loose connections from the front output terminals and load cables.
3. If current is output through the rear output
terminals, cover the front output terminals with the protective caps for safety.
Fig. Connection with Front Output Terminals
(Good)
(Bad)
CAUTION
The power supply unit may output a
maximum of 40A through the front output terminals. Do not use pin plugs or banana plugs for outputting large current in order to avoid overheating due to contact resistance. Use lug terminals that meet the output current rating and connect them firmly to the front output terminals.
For safety, NEVER output power through both
the front and rear output terminals.
Connection with the Front Output Terminals (PSB-2400L, 2800L, 2400L2, 2800LS)
39
PSB-2000 Series User Manual
Procedure
1. Insert the cable (load line) into the plug.
2. Use a 1.5 mm hex key to fasten the 2 screws.
3. Insert the cover into the plug and make sure it
hooks into place (completion image).
4. Turn the power switch off from the unit.
5. Insert the above-mentioned plug into the front
output terminal.
6. When current is drawn from the rear output
terminals, the plug must be removed from the front output terminal.
wrench
φ4 plug
outside diameter of a cable max. φ4
Completion image
Fig. Assembly diagram of the front output terminal plug
CAUTION
For safety, never output power through both the front and rear output terminals.
Assembling and Connecting the Front Output Terminal Plugs (PSB-2400H, 2800H)
40
OPERATION
Introduction
The PSB-2000 series power supply units offer wider voltage and current range settings, within the rated power envelope, than our traditional models.
70V
10V
60V
50V
40V
30V
20V
80V
5A
10A
15A
20A
25A
30A
35A
40A
Output current
Output voltage
400W Power limit line
70V
10V
60V
50V
40V
30V
20V
80V
10A
20A
30A
40A
50A
60A
70A
80A
800W Power limit line
Output voltage
Output current
Fig. PSB-2400L/L2 Operation Range
Fig. PSB-2800L/LS Operation range
Operation Ranges (PSB-2400L, 2800L, 2400L2, 2800LS)
Voltage setting range: 0V to 80V (All models) Current setting range: 0A to 40A (PSB-2400L & PSB-2400L2)
0A to 80A (PSB-2800L & PSB-2800LS)
Power setting range: 10W to 400W (PSB-2400L & PSB-2400L2)
10W to 800W (PSB-2800L & PSB-2800LS)
41
PSB-2000 Series User Manual
700V
600V
500V
400V
300V
200V
800V
0.5A 1A 1.5A 2A 2.5A 3A
Output current
Output voltage
400W Power limit line
PSB-2400H
133V
700V
600V
500V
400V
300V
200V
800V
1A 2A 3A 4A 5A 6A
800W Power limit line
PSB-2800H
133V
Output voltage
Output current
Fig. Operation Range of PSB­2400H
Operation Range of PSB-2800H
Operation Ranges (PSB-2400H, 2800H)
Voltage setting range: 0V to 800V (All models) Current setting range: 0A to 3A (PSB-2400H)
0A to 6A (PSB-2800H)
Power setting range: 0W to 400W (PSB-2400H)
0W to 800W (PSB-2800H)
42
OPERATION
Introduction
First, press the POWER switch to turn on the power. The power supply unit will show the startup screen (firmware version and models) for several seconds and then displays the last-used settings.
Note
The unit saves the last-used settings automatically when the power supply source is cut off or the POWER switch is shut off.
Model PSB-2400L, version 1.00
The last-used settings are displayed
Procedure
1. Make sure that the V key is lit green. If not,
press the V key to turn it on.
V AW
2. Set the voltage level with the encoder wheel.
Note
Check which channel is selected before setting the voltage on the PSB-2400L2 in order not to change the set value of the other channel.
Various Settings
Turning the Power On
How to Set the Voltage
43
PSB-2000 Series User Manual
Procedure
1. Make sure that the A key is lit green. If not,
press the A key to turn it on.
V AW
2. Set the current with the encoder wheel.
Procedure
1. Make sure that both the V and A keys are lit. If
not, press the V and A keys to turn them on. (Both keys need to be lit when setting the power.)
V AW
If the A key is pressed while keeping the V key depressed, the Current LED display can be used to enter the power setting. (The “A” indicator will turn turn off and the “W” indicator will turn on, indicating that the setting has changed from current to power.) See the figure below, Voltage and Power.
If the V key is pressed while keeping the A key depressed, the Voltage LED display can be used to enter the power setting. (The “V”
indicator will turn turn off and the “W”
indicator will turn on, indicating that the setting has changed from voltage to power.) See the figure below, Current and Power.
2. Set the power with the encoder wheel.
How to Set the Current
How to Set Power
44
OPERATION
Fig. Power Display
Voltage and
Power:
80V and 400W
Current and Power:
400W and 40A
Output Methods
Turning the output on or off using the OUTPUT
key.
Turning the output on or off using the CH1 or
CH2 key (PSB-2400L2 only).
Turning the output on or off using the external
control function.
Note
If the output is quickly turned off then on, then it is possible that the voltage will not discharge normally. Please allow the output to be off for a least 1 second before turning the ouput on again.
Procedure
1. Turning the output on or off using the OUTPUT
key.
Press the OUTPUT key to turn the output on or off. The Output is on while this key is lit. On the PSB-2400L2, pressing the OUTPUT key turns on or off the outputs for channel 1 and channel 2 simultaneously, but only if the CH1 CH2 keys have been pressed beforehand to select channel 1 or B.
2. Turning the output on or off using the CH1 CH2
key. (PSB-2400L2 only)
How to Turn the Output On
45
PSB-2000 Series User Manual
The CH1 and CH2 keys are independent of each other, and it is possible to turn the output on through channel 1 or B by pressing the CH1 or CH2 key to select the corresponding channel. However, the output is disabled unless the OUTPUT key is lit.
Note
For the PSB-2400L2, if neither the CH1 nor CH2 key is lit, the OUTPUT key will not go on even if it is pressed. (No output is provided.)
Fig. Output by Pressing OUTPUT key
OUTPUT
CH 2CH 1
ON / OFF
OUTPUT
CH 2CH 1
ON / OFF
Press CH1 and CH2 to
make them light up. (The
output is still off)
Press Output to output.
46
OPERATION
Output methods
The power supply unit displays the output value when the output is on. Press the ENTER / CHECK key when the output is on to switch the display to the setting value.
Procedure
Every press of the ENTER/CHECK key toggles the display between the setting mode and output mode.
When the output is on and the mode has been switched to the setting mode, the A or V key blinks, indicating that the setting value is being displayed.
Note
is rotated in the setting mode. The output value is changed if the encoder is rotated in the output mode. Do not touch the encoder to check the setting values.
Output value
Press CHECK:
Set value
Press CHECK: Output value
How to Display the Setting Value When the Output is On
47
PSB-2000 Series User Manual
The display panel on the PSB-2000 series can be rotated 90 degrees so that the unit can be operated comfortably in either the horizontal or vertical orientations. Hold the encoder wheel and rotate the orientation of the panel while pressing the ROTATE key below the encoder wheel. Keep turning the panel until a “click” sound is heard. This indicates that the panel is now locked in place.
CAUTION
Be sure to confirm that the POWER switch is off before rotating the display panel. If the display panel is rotated with the power on, the set value may change due to the rotation of the encoder wheel.
Fig. Rotating Display Panel
Horizontal installation
Vertical installation by
rotating the display panel
How to Rotate the Display Panel 90 Degrees for Vertical Installation
48
OPERATION
Operation
It is possible to disable the front panel keys by pressing the FAST/LOCK(3s)/LOCAL key on the left of the encoder. Hold this key for three or more seconds to lock the panel keys. The keys are locked when the LED beside the key turns red. To cancel the key lock function, hold the FAST/LOCK(3s)/LOCAL key for 3 or more seconds.
CAUTION
This key serves as the FAST, LOCK (3s), and LOCAL keys. When putting the power supply into the locked state, it will also automatically cancel the FAST mode setting (if set) and restore the power supply to the SLOW mode.
In the key-locked state, the OUTPUT key is still functional so that the output can be turned off for safety reasons.
How to Disable Panel Operations (Key Lock Function)
49
PSB-2000 Series User Manual
Introduction
Every press of the MENU key changes the menu
numbers:
PSB-2400L, 2800L, 2800LS: MENU Option “01” to “07”.
PSB-2400L2: MENU Option “01” to “09”. PSB-2400H, 2800H: MENU Option “01” to
“06”.
Press the ESC /DISP key to return from the MENU
settings to the normal settings.
To deactivate a function, select the
corresponding setting again from the menu and deactivate it.
Operation Overview
MENU key: Cycles through the menu options.
ENTER / CHECK key: Validates numeric values
and items.
ESC / DISP key: Exits from the menu settings
and returns to the normal settings.
Encoder wheel: Selects numeric values and
items.
Menu Key Functions
50
OPERATION
The diagram below can be used as a reference for the menu operations in the following pages:
General Setting Procedure
1. Press the MENU key until an intended function
number is displayed.
2. Press the ENTER / CHECK key to validate the
function. Proceed to setting of the next item.
3. Set a numeric value or item with the encoder,
and press the ENTER/ CHECK key to validate it.
4. When all intended items have been set, press
the ESC / DISP key to return to the normal state.
CAUTION
Set values are only validated after the ENTER / CHECK key is pressed. Be sure to check that the value is set properly after setting it. Some functions may not be settable as some functions cannot be used together. See the table below for details.
Set function
Functions that cannot be set or used simultaneously
Preset
Sequence External(voltage/resistance)
OVP/OCP
- Hi-Ω (PSB-L Series Only)
-
Off timer
Sequence Delay External (On/Off)
Voltage LED
Current LED
2 digit LED for displaying the number of cycles, step No., and menu No.
51
PSB-2000 Series User Manual
Sequence
Preset Off timer External (voltage/resistance) External (On/Off) Delay Tracking
External (voltage/resistance)
Preset Tracking External (On/Off)
Off timer Delay
Delay (PSB-L Series Only)
Sequence Off timer
Tracking (PSB-L Series Only)
Sequence External (voltage/resistance) External (On/Off)
52
OPERATION
Introduction
This function saves settings to one of the three PRESET keys. The settings shown below may be preset. Note that any other settings/values may not be saved.
Set voltage Set current Set power
Procedure
1. Set the voltage/current/power settings that
you want saved.
2. Press the MENU key until menu number “01” is
displayed.
3. Press the ENTER / CHECK key. All the PRESET
keys blink green.
4. Press the PRESET key that you want to assign
the current settings to. The PRESET key that you press will be lit a solid green to indicate that the save was successful.
5. Press the ESC/ DISP key to return to normal
operation.
CAUTION
Once the MENU key is pressed to activate the preset function, you can no longer set the voltage, current and power. Set the intended values before
Preset Function
Menu Item: 01(All Models)
53
PSB-2000 Series User Manual
activating the preset function.
Introduction
OVP: (Over Voltage Protection)
The OVP function turns off the output when the output voltage of the PSB-2000 series exceeds the preset OVP value.
Model
Setting Range
Resolution
PSB-2400L PSB-2800L PSB-2400L2 PSB-2800LS
1.0V to 84.0V
0.1V
PSB-2400H PSB-2800H
10.0V to 840.0V
1V
OCP: (Over Current Protection)
The OCP function turns off the output when the output current of the PSB-2000 series exceeds the preset OCP value.
Model
Setting Range
Resolution*
PSB-2400L PSB-2400L2
1.0A to 42.0A
0.1A PSB-2800L
1.0A to 84.0A
0.1A
PSB-2400H
0.1A to 3.15A
0.01A
PSB-2800H
0.1A to 6.30A
0.01A
*The resolution may be different for parallel/serial operation. Please see the specifications for details.
OVP/OCP function
Menu Item: 02 (All Models)
54
OPERATION
Procedure
1. Press the MENU key until menu number “02” is
displayed.
2. Press the ENTER / CHECK key to toggle between
the OVP and OCP setting displays. On the PSB­2400L2, the OVP and OCP settings for channel 1 appear first, followed by channel 2 next.
OVP setting
OCP setting
OVP and OCP setting of channel 1
OVP and OCP setting of channel 2
3. When the intended protection function is
displayed (OVP or OCP), rotate the encoder wheel to set the OVP or OCP level.
4. Press the ENTER/ CHECK key to comfirm. The
setting is now complete.
5. Press the ESC/ DISP key to return to the normal
operation.
55
Hi-- Function
Introduction
The PSB-2000 series power supplies have filter capacitors connected to the output. The PSB-L power supplies also have a bleeder circuit to discharge these capacitors to a safe level when the output is turned off. When the Hi-Ω function is activated, the bleeder circuit is deactivated. This allows you to omit reverse-current preventing diodes that are necessary for charging batteries or capacitors when a bleeder circuit is active.
When the Hi-Ω function is activated, the internal filter capacitors can remain charged even after the power has been turned off and thus can be quite dangerous. As a safety measure, the bleeder circuits are programmed to turn back on after a predeterminded amount of time (5 ~ 30 minutes) after the output has been turned off.
Procedure
1. Press the MENU key until menu number “03” is
displayed.
2. Press the ENTER / CHECK key to enter the Hi-Ω
function setting mode. Select ON or OFF with the encoder wheel. The Hi-Ω function is set to OFF by default.
PSB-2000 Series User Manual
Menu Item: 03 (PSB-L Series Only)
56
OPERATION
Hi-Ω Off
Hi- On
3. Press the ENTER / CHECK key to confirm the
setting. The Hi-LED in the center of the panel turns on.
OFF TIMER DELAY
Hi-Ω
4. Next, set the time limit for when the bleeder
circuits are turned back on with the encoder wheel. Setting range: 5~30 minutes. Setting resolution: 5 minute steps.
Press the ENTER / CHECK key to confirm the setting.
Example: Timer set for 20 minutes.
5. Press the ESC / DISP key to quit the setting
mode and return to normal operation.
57
PSB-2000 Series User Manual
CAUTION
When the Hi-Ω function is activated, the output terminals of the power supply unit keep on carrying voltage even after the output is turned off. The Hi-LED will blink when Hi-Ω function is still active as the internal capacitors remain charged. Voltages as high as 80V may remain at the terminals when the output is turned off. Such a state is very dangerous. To avoid accidents, isolate the output terminals from the load cables completely with a relay or switch.
58
OPERATION
Introduction
This function turns the output off automatically after a set amount of time. The timer can be set in ten minute steps to a maximum of 99 hours, 50 minutes.
Procedure
1. Press the MENU key until menu number “04” is
displayed(PSB-L) or “03(PSB-H series)
2. Press the ENTER / CHECK key to enter the Off
Timer settings.
3. Select ON or OFF with the encoder wheel. The
Off Timer is turned off by default.
Initial setting
OFF timer activated
4. Press the ENTER / CHECK key to confirm the
setting. The OFF TIMER LED in the center of the panel will turn on when the timer is active.
OFF TIMER DELAY Hi-Ω
5. Next, set the timer time with the encoder
wheel. Press the ENTER / CHECK key to confirm the setting.
Off Timer Function
Menu Item: 04(PSB-L Series), 03(PSB-H Series)
59
PSB-2000 Series User Manual
The timer may be set in steps of ten minutes to a maximum of 99 hours and 50 minutes. The OFF TIMER LED will blink when the remaining time is less than five minutes. The remaining time for the off-timer may be checked by pressing the ESC/DISP key while the off-timer is running. (On the PSB-2400L2, pressing the ESC/DISP key toggles the display in the following order: CH1 settings, CH2 settings, and then the remaining time of the off­timer.)
Example: Off Timer set to ten minutes
6. Press the ESC / DISP key to quit the setting
menu and return to normal operation.
60
OPERATION
Introduction
This function executes sequence programs. Please note that sequence programs can only be created when one of the interface boards (PSB-001 or PSB-
002) are installed. Without an interface board installed, the sequence function is not available. Please see the PSB_Sequence_203 usermanual or the GW Instek website for more information on how to program sequences.
The following describes how to view steps in a previously-create sequence and screen shots of the PSB_Sequence_203 application that creates the sequences.
Note that the PSB series cannot edit or create sequences.
Fig. Repeating Steps 20 to 22 Three Times, Beginning with Step 20
Step No.
Cycle No.
Start End
20 21 22 20 21 22 20 21 22
1 2 3
Program contents
Continue
Sequence Function
Menu Item: 05(PSB-L), 04(PSB-H)
61
PSB-2000 Series User Manual
CAUTION
If the output is active at the end of the program as shown in the figure above, the power supply output will remain at the level of the last step even after the completion of the sequence operation. (I.e., the output stays active.) The last step number must be set to OFF for the the output to be turned off at the end of a sequence.
The sequence operation will end prematurely if the OUTPUT key pressed when a sequence is running. Note however, that the output will remain active at the level of the last step that was executed when the OUTPUT key was pressed.
Procedure
1. Press the MENU key until menu number
“05(PSB-L) or “4”(PSB-H) is displayed.
2. Press the ENTER / CHECK key to enter the
sequence operation settings. Select ON or OFF with the encoder wheel. By default the sequence function is turned off.
Initial setting
Sequence operation activated
3. Press the ENTER / CHECK key to confirm the
setting. The SEQUENCE LED below the PRESET key turns on. 1 2 3
62
OPERATION
○ ○ ○
―●SEQUENCE
4. Next, set the Start Step number with the
encoder wheel. Press the ENTER / CHECK key to confirm. The setting range is from 0 to 99.
Example: The Start Step is set to No. “00”.
5. Set the End Step number with the encoder
wheel. Press the ENTER / CHECK key to confirm. The setting range is from 0 to 99.
Example: The End Step is set to step No. “99”.
6. Set the number of times to repeat the steps
above with the encoder wheel. Press the ENTER / CHECK key to confirm. Setting the sequence function is now complete. The --- setting repeats the steps infinitely. The setting range is from 1 to 999 or “—“ (infinite).
Example: Repeat the selected steps 999 times.
7. Press the ESC / DISP key to quit the Sequence
settings and enter the sequence operation
63
PSB-2000 Series User Manual
mode.
Introduction
Constant-Voltage (CV) Control Using External
Voltage
This function allows you to control the voltage of the PSB-2000 series power supply unit by applying an external voltage to the unit. An external voltage of 0V to 10V can be used to control the output voltage from ~0V to the rated output voltage.
Constant-Current (CC) Control Using External
Voltage
This function allows you to control the current of the PSB-2000 series power supply unit by applying external voltage to the unit. An external voltage of 0V to 10V can be used to control the output current from ~0A to the rated output current.
Constant-Voltage (CV) Control Using External
Resistance
This function allows you to control the voltage of the PSB-2000 series power supply unit by connecting an external resistance to the unit. An external resistance of 0Ω to 10kΩ can be used to control the output voltage from ~0V to the rated output voltage.
Constant-Current (CC) Control Using External
Resistance This function allows you to control the current
External Control (External Voltage, External Resistance)
Menu Item: 06(PSB-L), 05(PSB-H)
64
OPERATION
of the PSB-2000 series power supply unit by connecting an external resistance to the unit. An external resistance of 0Ω to 10kΩ can be used to control the output current from ~0A to the rated output current.
CAUTION
The PSB-2000 series power supply unit is incapable of simultaneous external voltage and external resistance control. For example: Using an external voltage for CV control and external resistance for CC control is not supported.
Procedure
1. Press the MENU key until menu number
“06(PSB-L) or “05”(PSB-H) is displayed.
2. Press the ENTER / CHECK key to enter the
external control settings. Use the encoder wheel to select external voltage or external resistance, and press the ENTER / CHECK key. By default the External Control is turned off.
Initial setting
External voltage
External resistance
3. Select the external control mode with the
encoder wheel. The modes are listed below: CV= Constant voltage CC= Constant current IN = Control from the front panel or remotely from a PC. OUT= Control using the external control.
65
PSB-2000 Series User Manual
Controlling constant voltage from the front panel
Controlling constant voltage using external control
Controlling constant current from the front panel
Controlling constant current using external control
4. Finally, press the ENTER / CHECK key to
validate the settings. Setting the control mode is now complete.
5. Press the ESC / DISP key to quit the setting
mode and return to normal operation.
Introduction
The PSB series can use external control to turn the output on or off by shorting (output on) or opening certain pins (output off) on the external control connector.
Use this function to choose whether to use external control or the OUTPUT key to turn on the output.
External Control Output On/Off
Menu Item: 07(PSB-L, 06(PSB-H)
66
OPERATION
Procedure
1. Press the MENU key until menu number
“07(PSB-L) or “06”(PSB-H) is displayed.
2. Press the ENTER / CHECK key to enter the
external output On/Off control setting mode.
3. Select On or Off with the encoder wheel, and
press the ENTER / CHECK key again to confirm the settings. The external output on/off setting is now complete. The output control modes are shown below: IN= The output is controlled with the OUTPUT key. OUT= The output is controlled with external contacts.
OUTPUT key control
External Control
4. Press the ESC/ DISP key to quit the settings and
return to normal operation.
67
Delay Function
Introduction
The delay function is available on the dual channel model (PSB-2400L2) only. It adds a rise and fall delay time to the output of channel 2 for a specified amount of time (in seconds) from a reference point (output of channel 1). The rise delay time refers to the delay time for turning the output on. The fall delay time refers to the delay time for turning the output off.
Fig. Temporal Concept of Delay Function
Channel B
Channel A
Positive
(10 seconds Max.)
Negative
(9.99 seconds max.)
Zero
Zero
Negative
(9.99 seconds max.)
Positive
(10 seconds Max.)
Procedure
1. Press the MENU key until menu number “08” is
displayed.
2. Press the ENTER / CHECK key to enter the delay
function settings. Select On or Off with the encoder wheel. By default the delay setting is turned off.
Delay OFF
Delay ON
PSB-2000 Series User Manual
Menu Item: 08 (PSB-L2)
68
OPERATION
3. Press the ENTER / CHECK key to confirm the
setting. The DELAY LED in the center of the panel turns on.
OFF TIMER
DELAY Hi-
4. Set the rise delay time with the encoder wheel.
When a positive time is set, the output of channel 2 is delayed with respect to channel 1. On the contrary, when a negative time is set, the output of channel 2 leads that of channel 1. The delay time can be set in the range of -9.99 seconds to +10.00 seconds in steps 10 ms.
The output of channel 2 is turned on 9.99 seconds earlier
The output of channel 2 is turned on 10.00 seconds later.
5. Set the fall delay time with the encoder wheel, and
press the ENTER / CHECK key. The delay function setting is now complete.
The channel 2 output is turned off 9.99 seconds earlier
The channel 2 output is turned off 10.00 seconds later.
6. Press the ESC / DISP key to quit the delay settings
and return to normal operation.
69
PSB-2000 Series User Manual
Introduction
The tracking function is available on the dual channel model (PSB-2400L2) only. When the tracking function is turned on, the output of channel 2 is made to match the output of channel 1, thus channel 2 can be said to “track” channel 1. This effectively means that the values of both channels change simultaneously.
Fig. Tracking Operation
Channel 1
Channel 2
5V
10V
20V
20V
5V
5V
Tracking function
ON
Changing set values with encoder or through communication
Procedure
1. Press the MENU key until the menu number
“09” is displayed.
2. Press the ENTER / CHECK key to enter the
tracking function setting mode. Select On or Off with the encoder wheel. By default the tracking function is turned off.
3. Press the ENTER / CHECK key to confirm the
setting. Both the CH1 and CH2 LEDs on the right of the channel LED turn on.
4. Press the ESC / DISP key to quit the setting
Tracking Function
Menu Item: 09 (PSB-L2)
70
OPERATION
menu and return to normal operation. “Ab” is displayed on the MENU LED when the tracking function is activated.
Example: Tracking function is activated.
The master-slave function allows the PSB series to operate in parallel or series (PSB-L only). For series operation a maximum of 2 PSB-L units can be used. For parallel operation, a maximum of 4 (PSB-L) units or 2 units (PSB-H) units can be used. Note that for series operation, the same PSB-L models types must be used.
For a slave unit that is connected in series, only the output voltages are displayed when the output is on.
No panel operations can be performed on the slave units. Only the Off Timer, Sequence and External Control function settings are initialized on the slave units.
For parallel connections “---“ is displayed on the display for slave units. The monitor values are displayed on the master unit.
CAUTION
The Hi-Ω function is not available for master­slave operation.
Master-slave function
Menu Item: 10
71
PSB-2000 Series User Manual
Display for a slave unit in a parallel connection
Display for a slave unit in a series connection
Procedure
1. The master-slave settings can be accessed by
turning on the power switch while holding the MENU key.
2. Select the operation mode for the unit with the
encoder wheel and press the ENTER / CHECK key to confirm the setting. By default the master-slave setting is set to OFF
Initial setting: Single unit operation or Master unit in a series connection
Master unit in a parallel connection
Slave unit in a parallel connection
Slave unit in a series connection (PSB-L only)
72
OPERATION
3. Set the total power with the encoder wheel if
the unit is set as the master unit in a parallel connection.
Example: Total power of 3200 W.
4. Press the ESC / DISP key to exit the settings
and return to normal operation.
73
PSB-2000 Series User Manual
Description
The PSB-2000 series power supply units have an output voltage remote sensing function. This function eliminates influences of voltage drops between the power supply unit and load, which is caused by the contact resistance or the resistance of the load cable conductors. Voltage sense compensates for a voltage of up to 1V on a single terminal.
CAUTION
When the voltage sense function is used, the voltage at the front or rear terminals of the power supply unit must not exceed the rated voltage.
If the load cables are long, the inductance and the capacity of the load cables may cause oscillation. To avoid oscillation, connect an electrolytic capacitor of a several hundred to several thousand μF to the load terminals.
Procedure
1. Make sure that the POWER switch is off before
making any connections.
2. Disconnect the wire that shorts the + and +S
terminals or - and -S terminals on the four­terminal block on the left of the output terminals on the rear panel (this will need to be done for both channels on the PSB-2400L2).
3. Connect the positive sensing terminal (+S) to
the positive side of the load and the negative sensing terminal (-S) to the negative side of the load, as shown below. If the sensing wires are disconnected, control will become unstable and a voltage greater than the set voltage could be applied to the load. Connect the sensing wires
Voltage Sense
74
OPERATION
firmly.
NOTE
Approximately 1mA of current flows through the sensing wires at the rated output voltage. Use AWG 26 to 18 wires as the sensing wires.
Fig. Remote Sensing Connection (PSB-L)
+S
+
-
-S
Load
OUTPUT
OUTPUT
Shielded cable or
Twisted pair wires
Fig. Remote Sensing Connection (PSB-H)
+S
+
-
-S
Load
OUTPUT
OUTPUT
Shielded cable or
Twisted pair wires
+ -
75
PSB-2000 Series User Manual
Description
The following connectors are supplied with the power supply for external control.
Procedure
1. XG5M-2635-N (manufactured by OMRON
Corporation) (For all PSB-2000 series)
This section describes how to assemble the external control connector
Procedure
1. Remove the contacts from the housing.
Each contact can be easily removed by pulling it out while using a pin to hold down its catch. The contacts can also be removed using the XY2E-0001 removal tool (manufactured by OMRON Corporation).
2. After connecting a wire to each contact, insert
the contacts into the connector. When inserting the contacts into the connector, ensure that the catch of each contact is firmly latched to the connector. When connecting a wire to each contact, use the XY2B-7006 crimping tool (manufactured by OMRON Corporation). Applicable wire: Twisted wire AWG28 or 26 Outer diameter φ1.1 to 1.3 mm
3. Mount semi-covers on both sides of the
connector.
External Control Functions
Assembling the XG5M-2635-N Connector
76
Fig. Assembling the External Control Connector (XG5M-2635-N)
The 26-pin connector for external control: XG5M-2635­N (OMRON Corporation)
Each contact can be easily removed by pulling it out while using a pin to hold down its catch.
The XY2E-0001 contact removal tool (manufactured by OMRON Corporation), can also be used to remove the contacts.
Applicable wire: Twisted wire AWG28 or 26
Outer diameter φ1.1 to 1.3
mm
Mount the semi-covers on both sides of the connector. Here is a view of the completed assembly (20 pins shown)
Introduction
It is possible to monitor the output voltage and output current of the PSB-2000 series power supply unit using the J3 external control connector. This section describes how to monitor the output voltage and output current of the dual channel model (PSB-2400L2). The single channel models operate in the same manner as the description for the CH1 outputs.
OPERATION
Output Voltage Monitor and Output Current Monitor
77
PSB-2000 Series User Manual
NOTE
The internal impedance of the voltage and current monitoring circuits are approximately 1kΩ. Be careful not draw over 1mA through the monitoring circuits.
Procedure
1. Voltage monitor
CH1: Pins 17 and 16 (COM), CH2: Pins 8 and 7 (COM)
2. Current monitor
CH1: Pins 18 and 16 (COM), CH2: Pins 9 and 7 (COM)
Fig. Monitor Output Pins
M M
1
2
25
26
CH1 Voltage monitor
CH1
Current
monitor
EXT CONT (J3)
M M
1
2
25
26
CH2 Voltage monitor
CH2
Current
monitor
EXT CONT (J3)
Negative output terminal of CH1
Negative output terminal of CH2
Output voltage
FS
10V
Monitor
voltage
Output current
FS
10V
Monitor
voltage
78
OPERATION
Introduction
The output voltage can be controlled by an external voltage or resistance through the J3 external connection (EXT CONT) on the rear panel if external control is selected.
CAUTION
The negative side of the external voltage is connected with the negative output terminal of the power supply unit. Have the external voltage source floating to avoid accidents or malfunctions. If the external resistor is disconnected for some reason when operating in the external control mode, an excessively-high voltage could be applied to the output. This occurs as a disconnected resistor appears as an open circuit, which in turn is interpreted as a resistance of 10kΩ. If fixed resistances are used, use shorting­type switches to switch between the fixed resistances to avoid open circuits.
The pins used for external voltage control or for external resistance control are the same. Check with control method is selected (external voltage or external resistance), before connecting the pins.
External Resistance and External Voltage Control Pins for voltage control:
CH1: Pins 14 and 16 (COM) CH2: Pins 5 and 7 (COM)
Constant-Voltage (CV) Control with External Voltage or Resistance
79
PSB-2000 Series User Manual
Fig.External Voltage/ Resistance Control Terminal(CV)
1
2
25
26
EXT CONT (J3)
Negative output terminal of CH1
0V
10V
0
10k
CH1
External
control
Use a shielded cable or twisted
pair wires for this control.
1
2
25
26
EXT CONT (J3)
Negative output terminal of CH2
0V
10V
0
10k
CH2
External
control
Use a shielded cable or twisted
pair wires for this control.
Output voltage
FS
10V
External
voltage
Output voltage
FS
10k
External
resistance
80
OPERATION
Introduction
The current output can be controlled using an external voltage or external resistance through the connector J3 (EXT CONT) on the rear panel if external control is selected.
External Resistance and External Voltage Control Pins for current control:
CH1: Pins 15 and 16 (COM) CH2: Pins 6 and 7 (COM)
Fig. External Voltage/Resistance Control Pins (CC)
1
2
25
26
EXT CONT (J3)
Negative output
terminal of CH1
0V
10V
0
10k
CH1
External
control
Use a shielded cable or twisted
pair wires for this control.
1
2
25
26
EXT CONT (J3)
Negative output
terminal of CH2
0V
10V
0
10k
CH2
External
control
Use a shielded cable or twisted
pair wires for this control.
Output current
FS
10V
External
voltage
Output current
FS
10k
External
resistance
Constant-Current (CC) Control with External Voltage or Resistance
81
PSB-2000 Series User Manual
Introduction
The output can be turned on or off using external contact switches if the external control function is activated.
External Control Pins for Output ON/OFF control:
CH1: Pins 21 and 22 (COM) CH2: Pins 12 and 13 (COM) Short: OUTPUT ON Open: OUTPUT OFF
Fig. Output ON/OFF Pins with External Contacts
1
2
25
26
EXT CONT (J3)
Negative output terminal of CH1
1
2
25
26
EXT CONT (J3)
Negative output terminal of CH2
CH2 OUTPUT ON/OFF
CH1 OUTPUT ON/OFF
Output ON/OFF with External Contacts
82
OPERATION
Introduction
An external contact switch can force the PSB-L into the alarm state. When in the alarm state, the output is turned off and “HARD” is displayed on the LED display. Remove the input power or turn off the power from the POWER switch to cancel the alarm state.
External Control Pins to activate the alarm state:
CH1: Pins 20 and 22 (COM) CH2: Pins 11 and 13 (COM)
Fig. External Alarm Input Pins
1
2
25
26
EXT CONT (J3)
Negative output terminal of CH1
1
2
25
26
EXT CONT (J3)
Negative output terminal of CH2
CH2
External
alarm input
CH1
External
alarm input
Alarm Function using External Contacts
83
PSB-2000 Series User Manual
Introduction
Constant-Voltage (CV) Status Signal
This status signal goes low when the PSB-2000 series power supply unit enters the constant­voltage (CV) status.
Constant-Current (CC) Status Signal
This status signal goes low when the PSB-2000 series power supply unit enters the constant­current (CC) status.
Alarm Status Signal
This status signal goes low when the PSB-2000 series power supply unit enters the alarm status.
Item
Symbol
Max. rating
Unit
Output
VCEO
66 V VECO
6 V IC
50
mA
PC
150
mW
Total allowable loss
PT
170
mW
Isolation voltage
BVS
2500
Vrms
CH1: Constant-voltage (CV)status: Pins 23 and 26 (COM) Constant-current (CC)status: Pins 24 and 26 (COM)
Alarm status: Pins 25 and 26 (COM)
CH2: Constant-voltage (CV) status: Pins 4 and 1 (COM) Constant-current (CC) status: Pins 3 and 1 (COM)
Alarm status: Pins 2 and 1 (COM)
Status Signals (CV, CC & ALARM)
84
OPERATION
Fig. Status Pins
26
EXT CONT (J3)
1
2
25
CV
CC
ALARM
CH1 status
26
EXT CONT (J3)
1
2
25
CV
CC
ALARM
CH2 status
Inside of
PSB-2000
Series
Fig. Photocoupler current
Internal current
2mA
I=1mA or less
R
V
Select and use proper voltage or resistance so that
the open collector current does not exceed 1mA.
85
PSB-2000 Series User Manual
Description
The section “Sequence Function” (page 61) shows how to execute a sequence program on the power supply when equipped with the optional interface board. The PSB_Sequence_203 software is used to create a program in advance via the optional interface board. See the Sequence Function section on page 61 for details. The PSB_Sequence_203 software can be downloaded at the GW Instek website.
Procedure
1. Write a sequence program through the
interface board. See page 61
2. Activate the sequence function as shown in the
Sequence Function menu on page 61.
3. Execute the sequence operation with the
PRESET key(s). Each PRESET key has two functions. The function of the PRESET keys and the OUTPUT key are different when used in the sequence mode compared to when they are in the normal operating mode.
Below is a description of the function of each of the preset keys and the OUTPUT key when in the sequence mode.
Normal Mode
Sequence Mode
PRESET 1
Starts or pauses the sequence
program. ( )
PRESET 2
Skips to the previous step number. ( ) (when paused)
PRESET3
Skips to the next step number in the sequence. ( ) (when paused)
Using the Sequence Function
86
OPERATION
OUTPUT
Ends the sequence operation.
CAUTION
The OUTPUT key does not the start sequence operation. Use the PRESET 1 ( ) key to start the sequence operation. Even if the sequence function is
activated and the “● SEQUENCE LED” is lit, the
sequence operation will not start unless the PRESET 1 ( ) key is pressed. Functions other than the preset function will work normally even when the “● SEQUENCE LED” is lit. If the OUTPUT key is pressed when a sequence is running, the sequence operation finishes. Note that ending a sequence operation is different from turning off the output in the normal operating mode.
4. The display during a sequence operation is
different from that in normal operation. The differences are shown below. When the ESC /
DISP key is pressed during a sequence
operation, the step number is displayed on the Voltage LED and the number of cycles is displayed on the Current LED. Press the ESC /
DISP key again to return to the previous
display.
Press DISP key
Step No.
Number of cycles
Number of steps
Display 1 in sequence
operation
Display 2 in sequence operation
5. During a sequence operation, the “●
SEQUENCE LED below the PRESET key blinks, indicating that sequence operation is being executed. To stop
87
PSB-2000 Series User Manual
the sequence operation partway, press the OUTPUT key or deactivate the sequence function as shown in the Section “Sequence Function(page 61).
88
OTHER FUNCTIONS
Description
When the PSB-2000 series power supply unit enters an alarm state or if the alarm state is manually set using the external control connector (see page 83), an alarm code is shown on the display. The alarm code will indicate what type of alarm has been triggered. When an alarm occurs, the power supply unit turns off the output and stays in the alarm state. When a protection function (excluding OVP and OCP, see page 54) is triggered, all operations (panel operation, etc.) are disabled and the power supply unit stops operation.
Press the ESC / DISP key for one second to reset the OVP or OCP alarm (see page 54). Reset the power from the AC input source or from the POWER switch to reset the protection functions.
(1) OVP alarm
This alarm code is displayed if the output voltage exceeds the preset OVP value.
OTHER FUNCTIONS
Display in Alarm Status
89
PSB-2000 Series User Manual
(2) OCP alarm
This alarm code is displayed if the output current exceeds the preset OCP value.
(3) OHP alarm
The OHP alarm is displayed if the temperature at an internal detection point exceeds a set temperature. The OHP alarm that is displayed differs from model to model, as shown below. For example, on the 2400L2, an OHP alarm is displayed for each channel.
(2400L, 2400H 2800L, 2800H)
(2800L, 2800H)
(2400L2)
(4) HARD alarm
The HARD alarm is displayed in the following conditions:
Cause
Description
Over-Voltage (OVP)
The output is turned off if the voltage exceeds 110% of the rated output voltage.
Over-Current (OCP)
The output is turned off if the current exceeds 110% of the rated output current.
Alarm using external contacts
An alarm is caused when the External Alarm Input Pins on the external control
90
OTHER FUNCTIONS
ALARM
connector are shorted. For details, see page 83. PSB-L Only.
Description
The PSB Series power supply units are capable of frame link controlled parallel operation of up to four units(PSB-L), or up to 2 units (PSB-H) including the master unit. When performing parallel operation using master units, the master and slave units should be set properly in advance,
see the Master-slave function chapter on page 71.
Connect the master and slave units with the optional parallel signal cables, PSB-005. The parallel connection kit for horizontal installation, PSB-003 or the parallel connection kit for vertical installation, PSB-004 can also be used to physically connect the units together. The joint kit, PSB-007, is included with the PSB-003 and PSB-004 connection kits. Use these kits as the necessity requires.
The sum of the master unit current and slave unit current is displayed on the master unit. See the specifications on page 155 for the displayed items and setting resolution for parallel operation.
Output depends on the master unit. When the OUTPUT key of the master unit is pressed, the outputs of the slave units are turned on automatically.
CAUTION
The PSB-2400L2 is not capable of parallel operation.
Frame Link Controlled Parallel Operation (excluding PSB-2400L2)
91
PSB-2000 Series User Manual
CAUTION
Improper wiring or settings may cause failures. Recheck the settings before starting frame control operation.
If the load cables of a slave unit are disconnected, excessive voltage is applied to the slave unit
instantaneously and a “HArd” alarm occurs.
Check if the cables are connected properly. Repair improper connections. The master unit displays the total current. If the actual value is remarkably different from the set current and/or output current, improper power may possibly be set in the setting shown in the Master-slave function chapter on page 71. Recheck the set power.
When using frame link-controlled parallel operation, the current indicated on the master unit may fluctuate due to the influence of the load wire resistance. In such cases, use the optional connection kit, PSB-003 (Horizontal Installation Connection Kit), PSB-004 (Vertical Installation Connection Kit) or a low-impedance-load wire.
Use the PSB-2400L as the master unit when controlling the PSB-2400L and PSB-2800L using the the frame link control method.
+OUT
-OUT
Master unit
F.G
Frame ground)
Load
+grounding
-grounding
+S
+OUT
-OUT
-S
J1 J2
+OUT
-OUT
Slave unit 1
F.G
Frame ground)
+S
+OUT
-OUT
-S
J1 J2
+OUT
-OUT
Slave unit 2
F.G
Frame ground)
+S
+OUT
-OUT
-S
J1 J2
+OUT
-OUT
Slave unit 3
F.G
Frame ground)
+S
+OUT
-OUT
-S
J1 J2
PSB-005
PSB-005 PSB-005
92
OTHER FUNCTIONS
Description
The PSB-L series power supply (exlcluding the PSB-2400L2) units are capable of frame link controlled series operation of up to two units, including the master unit. When performing series operation using master units, the slave unit should be set properly in advance, see the Master-slave function chapter on page 71.
Output depends on the master unit. When the OUTPUT key on the master unit is pressed, the output of the slave unit is turned on automatically. Connect the master and slave unit with the optional PSB-006 cable.
CAUTION
Improper wiring or setting may cause failures.
Recheck the setting before starting frame link control operation.
Load
grounding
±grounding-grounding
+OUT
-OUT
Master unit
F.G
Frame ground
+S
+OUT
-OUT
-S
J1 J2
+OUT
-OUT
Slave unit
F.G
Frame ground
+S
+OUT
-OUT
-S
J1 J2
PSB-006
Frame Link Controlled Series Operation (excluding PSB-2400L2, PSB-H series)
93
PSB-2000 Series User Manual
Description
The PSB-2800LS (booster unit) is especially designed to boost the power capacity when used in parallel. It is possible to increase the output up to a maximum of 3200W when used in parallel with a PSB-2800L as the master unit).
NOTE
Note that the PSB-2800LS cannot be used for series operation.
Fig. Front and Rear panel of PSB-2800LS
Description
The PSB-2800LS is not equipped with a power switch. The PSB-2800LS relies on a master unit to turn it on when it is connected in parallel. As soon as the master unit is turned on any connected PSB-2800LS power supply is also turned on (see page 71 for details).
In other words, the PSB-2800LS cannot be used alone. So before using the PSB-2800LS, check to make sure that the AC power cable, signal cables and load wires are connected properly. Improper wiring or settings may cause problems.
Power Extension using PSB-2800LS (Parallel Connection Only)
How to use the PSB-2800LS
94
OTHER FUNCTIONS
Fig. Connection Example for Horizontal Installation
Fig. Connection Example for Vertical Installation
Description
The PSB-007 extension kits allow master units to be physically connected to slave units. The extension kits can be used horizontally or vertically.
NOTE
Note that the PSB-2800LS cannot be used for series operation.
Using the PSB-007 Extension kits
95
PSB-2000 Series User Manual
Steps
1. Remove the rubber feet from the bottom of
unit A. (Keep the removed rubber feet and screws with care not to lose them.)
2. Fix the joint kit (PSB-007) to the top panel of
unit B with the flat countersunk head screws supplied with the kit. (Four positions)
3. Place the units as shown in the figure below
so that the prongs from the PSB-007 joint kit on the unit B are inserted in the holes in unit A (revealed from under the rubber feet that were removed).
4. Slide unit A and fix the rear panel to the
brackets on the joint kit (PSB-007) firmly with the screw with washer supplied with the kit. (Two positions)
Unit A
Unit B
(Viewed from side
Unit A
Unit B
Shift and screw
Connection for Vertical Installation
Fix PSB-007 with
attached screw at 4
positions
2 positions
How to Connect the Units Vertically
96
OTHER FUNCTIONS
Steps
1. Remove the rubber feet from the side of unit
B. (Keep the removed rubber feet and screws with care not to lose them.)
2. Fix the joint kit (PSB-007) to the side of the
unit A with the flat countersunk head screws supplied with the kit. (Four positions)
3. Place the units as shown in the figure below
so that the prongs from the joint kit on unit A are inserted in the holes in unit B (revealed from under the rubber feet that were removed).
4. Slide unit B, and fix the rear panel to the
brackets of the joint kit (PSB-004) firmly with the screw with washer supplied with the kit. (Two positions)
Unit A
(Viewed from above
Shift and screw
Connection for Horizontal Installation
Fix PSB-007 with attached
screw at 4 positions
2 positions
Unit A
Unit B
Unit B
How to Connect the Units Horizontally
97
PSB-2000 Series User Manual
Fig. Bus Bar Connections to Fix the Output Terminals
Parallel connection kit for Horizontal installation PSB-003
Parallel connection kit for vertical installation PSB-004
ScrewM6)
Washer
Nut
Terminal block
Output terminal bar
Bus bar Pay attention to the positional relationship with the output terminal
Bus Bar Connection
98
Loading...