D1021 - SIL 2 Powered Isolating Driver with Fault Detection Smart-Hart compatible ISM0022-6
D1021S
INSTRUCTION MANUAL
INSTRUCTION MANUAL
SIL 2 Powered Isolating Driver with
Fault Detection Smart-Hart compatible
DIN-Rail Model D1021S
D1021 - SIL 2 Powered Isolating Driver with Fault Detection Smart-Hart compatible G.M. International ISM0022-6
2
D1021 Analog Output Isolating Drivers
Front Panel and Features................................................................................................................................................................ 2
Characteristics................................................................................................................................................................................. 3
Technical Data................................................................................................................................................................................. 3
Ordering Information........................................................................................................................................................................ 4
Terminal Block Connections............................................................................................................................................................ 4
Parameters Table............................................................................................................................................................................ 5
Function Diagram ............................................................................................................................................................................ 6
Warning ........................................................................................................................................................................................... 6
Operation......................................................................................................................................................................................... 7
Installation ....................................................................................................................................................................................... 7
Start-up............................................................................................................................................................................................ 8
Configuration ................................................................................................................................................................................... 8
Calibration instruction and Troubleshooting .................................................................................................................................... 9
Installation in Cabinet .................................................................................................................................................................... 10
Index
Front Panel and Features
D1021
1 2 3 4
16 15 14 13
5 6 7 8
PWR
ON
FAULT
SIL 2 according to IEC 61508 for Tproof = 1 / 3 years (10 / 20 % of total SIF).
PFDavg (1 year) 5.18 E-04, SFF 70.66 %.
Output to Zone 0 (Zone 20), Division 1,
installation in Zone 2, Division 2.
4-20 mA Input, Output Signal.
Wide Band Smart Communication,
Hart compatible.
Field fault circuit detection with signalling.
Control input fault detection with signalling.
High Accuracy.
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4.
ATEX, IECEx, FM & FM-C,
Russian and Ukrainian Certifications.
Type Approval Certificate DNV A-10169, KR ITA20769-EL001 for marine applications.
High Reliability, SMD components.
Simplified installation using standard
DIN Rail and plug-in terminal blocks.
250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
3
D1021 - SIL 2 Powered Isolating Driver with Fault Detection Smart-Hart compatible G.M. International ISM0022-6
General Description: The single channel DIN Rail Isolating Driver D1021S isolates and transfers a 4-20 mA signal from a controller located in
Safe Area to a load of up to 750 in Hazardous Area. It has a high output capacity of 15 V at 20 mA combined with a low drop across its input terminals. The circuit allows bi-directional communication signals, for Smart I/P. In the 4-20 mA input range, a field open / short circuit (load or wire fault) reflects a high impedance to the control device output circuit and actuates (de-energizes) the fault indication relay / transistor. An output underrange or overrange (< 1 mA or > 25 mA) also de-energizes the fault indication relay / transistor.
Function: 1 channel I.S. mA analog output for 2 wire I/P Smart converters or valve positioners, provides 3 port isolation (input/output/supply). Signalling LEDs: Power supply indication (green), fault condition (red). Smart Communication Frequency Band: 0.5 to 40 KHz within 3 dB (Hart and higher frequency protocols). EMC: Fully compliant with CE marking applicable requirements.
Supply: 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits 5 Vpp.
Current consumption @ 24 V: 70 mA with 20 mA output typical. Power dissipation: 1.5 W with 24 V supply voltage and 20 mA output typical. Max. power consumption: at 30 V supply voltage and overload condition 2.2 W.
Isolation (Test Voltage): I.S. Out/In 1.5 KV; I.S. Out/Supply 1.5 KV; I.S. Out/Fault Out 1.5 KV;
In/Supply 500 V; In/Fault Out 1.5 KV; Supply/Fault Out 1.5 KV; Fault Out (relay)/Fault Out (transistor) 1.5 KV.
Input: 4 to 20 mA with 2.0 V voltage drop, reverse polarity protected. Output: 4 to 20 mA, on max.750 load, current limited at 24 mA.
Response time: 50 ms (10 to 90 % step change). Output ripple: 20 mVrms on 250 communication load on 0.5 to 40 KHz band. Frequency response: 0.5 to 40 KHz bidirectional within 3 dB (Hart and higher frequency protocols).
Fault detection:
Input under/overrange: input current <1 mA or > 25 mA (± 0.5 mA). Short output detection: load resistance configurable from 0  (short fault disabled) to 200 , default setting 50 . Open output detection: load resistance > 50 K. Fault signalling: voltage free NE SPST optocoupled open-collector transistor and voltage free NE SPST relay contact (each output is
de-energized in fault condition).
Open-collector rating: 100 mA at 35 V ( 1 V voltage drop). Leakage current: 50 µA at 35 V. Relay contact rating: 2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load). Response time: from 20 to 500 ms typical.
Performance:
Ref. Conditions 24 V supply, 250 load, 23 ± 1 °C ambient temperature.
Calibration accuracy: ± 0.1 % of full scale. Linearity error:
± 0.1 % of full scale.
Supply voltage influence: ± 0.05 % of full scale for a min to max supply change. Load influence: ± 0.05 % of full scale for a 0 to 100 % load resistance change. Temperature influence: ± 0.01 % on zero and span for a 1 °C change.
Compatibility:
CE mark compliant, conforms to 94/9/EC Atex Directive and to 89/336/CEE EMC Directive.
Environmental conditions:
Operating: temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C. Storage: temperature limits - 45 to + 80 °C.
Safety Description:
II (1) G [Ex ia] IIC, II (1) D [Ex iaD], I (M2) [Ex ia] I, II 3G Ex nA IIC T4, [Zone 0] [Ex ia] IIC, [Ex ia] I, [Ex iaD] associated electrical apparatus. Uo/Voc = 25.2 V, Io/Isc = 87 mA, Po/Po = 548 mW at terminals 14-15. Um = 250 Vrms, -20 °C Ta 60 °C. Approvals: DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26, EN61241-0, EN61241-11, IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26, IEC61241-0, IEC61241-11, GM International CRR028 conforms to EN60079-0, EN60079-15, FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810 and C22.2 No.142, C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15, Russia according to GOST 12.2.007.0-75, R 51330.0-99, R 51330.10-99 [Exia] IIC X, Ukraine according to GOST 12.2.007.0,22782.0,22782.5 Exia IIC X, EXIDA Report No. GM03/07-24 R001, SIL 2 according to IEC 61508. Please refer to Functional Safety Manual for SIL applications. DNV A-10169, KR ITA20769-EL001 Type Approval Certificate for marine applications.
Mounting: T35 DIN Rail according to EN50022.
Weight: about 130 g. Connection: by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm
2
. Location: Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Protection class: IP 20. Dimensions: Width 22.5 mm, Depth 99 mm, Height 114.5 mm.