6.4.7
Service menu
System settings
(Expert)
BS-06-04-07-00-01-BAEN
Facility for setting special boiler and system parameters
35) Options → None No oxygen sensor or oxygen sensor is deactivated
→ NGK Oxygen sensor type fitted is NGK
→ BOSCH Oxygen sensor type fitted is BOSCH
36) Options → Auto The oxygen sensor heater is switched on/off according to operating mode
→ Constant The oxygen sensor heater is permanently switched on
(Oxygen sensor heater does not switch off until boiler has been in "OFF" mode for more than 50 h)
37) Options → Terminal Data querying via Windows hyper terminal/display
→ DAQ Data querying via online recorder (only usable at factory)
→ GSM module Data querying, information messages and boiler control via GSM module
For setting system type
→ stated on rating plate
For setting boiler type
→ stated on rating plate
For setting outfeed system type
Automatic de-ashing
→ On systems with integral ash box, set to "Off"
For setting heating circuit controller 0
For setting heating circuit controller 1
→ external wall controller
For setting heating circuit controller 2
→ external wall controller
Outside-temperature sensor activation/deactivation
Fuel setting
→ Setting 1 = 15 kW, setting 2 = 23 kW
For photo-cell activation/deactivation
→ Combustion monitoring
For activating photoresistor calibration
For entering photoresistor compensation
35)
For setting oxygen sensor type
36)
For setting oxygen sensor heater
For activating oxygen sensor calibration
For entering oxygen sensor compensation
For setting oxygen sensor characteristic
→ only during "Controller" mode
37)
For activating monitoring mode
Facility for data recording on SD memory cards
Facility for reading data from SD memory cards
For querying manufacturer code
Setting for fault signal from tipper grate motor position monitor
Setting for fault signal from speed monitor for drive motor G1
Setting for fault signal fuel level sensor
Setting for fault signal "Empty ash box"
→ 0h = Deactivated
For activating filling sequence
→ only in OFF mode – do not interrupt
Setting for flue draught fan operation
For selecting drive motor type
For selecting flue draught fan blade type
All pumps are activated once a week for the time set here
Activates all heating circuits up to maximum flow temperature
Pump HP0 continues running until temperature at boiler is below set temperature
If the outside temperature falls below "HCP A/F outside", the heating circuit pumps start running
"HCP A/F Flow" is required flow temperature
→ only in "OFF" mode
Raises boiler temperature until STL trips
→ in Controller mode