Guentner GMM f-drive, GMM sincon, GMM EC, GHM spray basic, GHM spray Operating Instructions Manual

...
Operating instructions Güntner Hydro Management GHM spray
www.guentner.de
Operating instructions – Güntner Hydro Management GHM spray V_4.0

Contents

Page 2 / 104
1 General notes............................................................................... 6
1.1 Safety instructions.............................................................................6
1.2 Proper intended use......................................................................... 6
1.3 Transport and storage, copyright notice........................................ 7
1.4 Warranty and liability........................................................................7
1.5 Manufacturer and supplier address................................................8
1.6 EMC-compliant installation..............................................................8
2 Short description......................................................................... 9
3 System operation in a master-slave configuration............... 10
4 Commissioning GHM spray......................................................12
4.1 The initial commissioning procedure........................................... 13
5 Construction of the GHM spray...............................................17
5.1 Remote controllers..........................................................................18
5.1.1 Functional description................................................................................... 18
5.1.1.1 Configurable step generator....................................................................... 22
5.1.2 Installation / Operating conditions.......................................................... 23
5.1.3 Connections....................................................................................................... 25
6 Display and operation...............................................................32
6.1 Info menu......................................................................................... 33
6.2 Operation.......................................................................................... 34
6.3 Edit mode......................................................................................... 35
6.4 Selection mode................................................................................36
6.5 Configuration....................................................................................37
6.5.1 Configuration table......................................................................................... 37
6.5.2 Control outputs on the GRCspray.1........................................................41
6.6 Control inputs.................................................................................. 42
6.6.1 Enabling of GHM spray................................................................................ 42
6.6.2 Enabling the fan................................................................................................... 43
6.6.3 Starting drain from externally............................................................................43
6.6.4 Setpoint switchover........................................................................................ 44
6.7 Analogue inputs...............................................................................44
6.7.1 Connecting a pressure sensor to AI1..................................................... 44
6.7.2 External power signal connection to AI1.............................................. 46
6.7.3 Connecting the conductivity sensor on AI2......................................... 47
6.7.4 Connecting a medium temperature sensor on AI3.......................... 47
6.7.5 Connecting a temperature sensor on AI4............................................ 48
6.7.6 Connecting an external voltage sensor on AI4................................... 48
6.8 Operating menu...............................................................................49
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Page 3 / 104
6.8.1 Actual values..................................................................................................... 50
6.8.1.1 Input current values.......................................................................................50
6.8.1.2 Ambient temperature.................................................................................... 50
6.8.1.3 Control value..................................................................................................... 50
6.8.1.4 Steps..................................................................................................................... 51
6.8.1.5 Speed....................................................................................................................51
6.8.1.6 Conductivity....................................................................................................... 51
6.8.1.7 Setpoint................................................................................................................52
6.8.2 Status....................................................................................................................53
6.8.2.1 Operating modes.............................................................................................53
6.8.2.2 External release - Status.............................................................................. 53
6.8.2.3 Drained.................................................................................................................53
6.8.2.4 Configuration..................................................................................................... 54
6.8.2.5 GHM spray basic/prof................................................................................... 54
6.8.2.6 Section cycling..................................................................................................54
6.8.2.7 Heat exchanger................................................................................................ 54
6.8.2.8 Refrigerant.......................................................................................................... 54
6.8.2.9 Hardware and software versions.............................................................. 55
6.8.2.10 Setpoint displacement active/inactive................................................... 55
6.8.2.11 External drain....................................................................................................55
6.8.2.12 Inlet control........................................................................................................55
6.8.2.13 Bus module........................................................................................................55
6.8.3 Parameters......................................................................................................... 56
6.8.3.1 Parameter – Spraying from........................................................................ 56
6.8.3.1.1 Outdoor temperature.....................................................................................56
6.8.3.1.2 Hysteresis temp............................................................................................... 56
6.8.3.1.3 Speed....................................................................................................................57
6.8.3.1.4 Hysteresis rpm................................................................................................. 57
6.8.3.2 Setpoint................................................................................................................57
6.8.3.2.1 Setpoint 1 and Setpoint 2.......................................................................... 58
6.8.3.2.2 Setpoint delta min..........................................................................................58
6.8.3.2.3 Number of setpoints......................................................................................58
6.8.3.3 Draining................................................................................................................58
6.8.3.3.1 Downtime............................................................................................................ 59
6.8.3.3.2 Frost draining....................................................................................................59
6.8.3.3.3 Number of slave sections............................................................................ 59
6.8.3.4 Fault report.........................................................................................................59
6.8.3.4.1 Hours high..........................................................................................................59
6.8.3.4.2 Conductivity low...............................................................................................59
6.8.3.4.3 Conductivity high.............................................................................................60
6.8.4 Alerts..................................................................................................................... 61
6.8.4.1 Alert memory.................................................................................................... 61
6.8.5 Language.............................................................................................................62
6.8.5.1 Language selection.........................................................................................62
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Page 4 / 104
6.8.6 Time.......................................................................................................................63
6.8.6.1 Time setting.......................................................................................................63
6.8.7 Date....................................................................................................................... 64
6.8.7.1 Set date............................................................................................................... 64
6.8.8 Manual mode.................................................................................................... 65
6.8.8.1 Manual mode.................................................................................................... 65
6.8.8.2 Manual mode settings.................................................................................. 67
6.9 Service...............................................................................................69
6.9.1 Control parameters.........................................................................................70
6.9.1.1 Control parameters Kp, Ti and Td...........................................................70
6.9.2 Heat exchanger................................................................................................ 71
6.9.2.1 Heat exchanger type......................................................................................71
6.9.3 Refrigerant.......................................................................................................... 72
6.9.3.1 Refrigerant selection...................................................................................... 72
6.9.4 Operating mode............................................................................................... 73
6.9.4.1 Auto internal......................................................................................................73
6.9.4.2 Auto external..................................................................................................... 73
6.9.4.3 Auto external BUS.......................................................................................... 74
6.9.4.4 Slave external....................................................................................................74
6.9.4.5 Slave external BUS......................................................................................... 74
6.9.5 Inlet control........................................................................................................75
6.9.6 Step parameters.............................................................................................. 76
6.9.6.1 Section cycling..................................................................................................76
6.9.6.2 Threshold value................................................................................................76
6.9.6.3 Off hysteresis.....................................................................................................76
6.9.6.4 Dead time........................................................................................................... 77
6.9.6.5 Minimum switch time................................................................................... 77
6.9.7 I/O configuration..............................................................................................77
6.9.7.1 Analogue inputs............................................................................................... 77
6.9.7.1.1 Current input AI1............................................................................................ 78
6.9.7.1.2 Current input AI2............................................................................................ 78
6.9.7.1.3 Switchable input AI3 (current/KTY)........................................................ 78
6.9.7.1.4 Voltage input AI4.............................................................................................79
6.9.7.2 Digital inputs..................................................................................................... 80
6.9.7.3 Analogue outputs............................................................................................ 81
6.9.8 SI/IP selection...................................................................................................81
6.9.8.1 SI/IP units system...........................................................................................82
6.9.9 Factory setting.................................................................................................. 83
6.9.9.1 Control reset (factory setting)....................................................................83
6.9.10 Delivery condition............................................................................................84
6.9.10.1 Control reset (delivery condition).............................................................84
6.9.11 H2O conductivity............................................................................................. 85
6.9.11.1 Storage of H2O conductivity values........................................................ 85
6.9.12 External bus module......................................................................................86
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Page 5 / 104
7 Faults and troubleshooting.......................................................87
7.1 General notes...................................................................................87
8 Technical data............................................................................ 88
8.1 Component dimensions - Dimensions / Weight......................... 88
9 Electrical properties of the components................................90
10 Factory setting............................................................................93
11 Error messages and warnings................................................. 94
12 Index............................................................................................ 99
13 Picture index............................................................................103
14 Table index...............................................................................104
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG

1 General notes

1.1 Safety instructions

In order to prevent serious physical injuries or major material damage, work on or with the unit may be performed only by authorised persons with appropriate training and qualifica­tions who are familiar with the set-up, installation, commissioning and operation of electron­ic controllers. These persons must read the operating instructions carefully before the instal­lation and commissioning. In addition to the operating instructions and national accident pre­vention regulations, all recognised technical rules (safety and professional work under UVV, VBG, VDE etc.) must be followed.
Repairs to the device may only be made by the manufacturer or a repair centre authorised by the manufacturer.
UNAUTHORISED AND IMPROPER INTERVENTIONS WILL INVALIDATE THE WARRANTY!
The applicable national accident prevention regulations must be followed when working on control units under voltage.
Page 6 / 104

1.2 Proper intended use

The unit is intended only for the purposes agreed in the order confirmation. Any other appli­cation or use for any additional purpose, is not a proper intended use. The manufacturer ac­cepts no liability for any injury or damage arising from unintended use. Proper intended use is also contingent on compliance with the installation, operating and maintenance procedures described in these operating instructions. The technical data and the details of the connection assignments can be found on the type plate and in the instructions, and must be complied with.
Electronic equipment is not fundamentally failsafe! The user must therefore ensure that his sys­tem reverts to a safe condition in the event of failure of the equipment. The manufacturer accepts no responsibility for any damage to life and limb or to material goods and assets in the event of failure to comply with this provision and in the event of improper use.
The electrical installation must be performed in accordance with the relevant regulations (e.g. cable cross-sections, fuses, earth conductor connections, etc.). Additional information is in­cluded in the documentation. If the control unit is used in a particular area of application, the required standards and regulations must be complied with.
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG

1.3 Transport and storage, copyright notice

The controllers are packaged appropriately for transport and may only be transported in their original packaging. Avoid any impacts and collisions. Unless otherwise noted on the packaging, the maximum stacking height is 4 packs. When you receive the equipment, check for any damage to the packaging or the controller.
Store the equipment in its original packaging and protected from the weather, and avoid ex­tremes of heat and cold.
Subject to technical changes in the interests of further development. Therefore no claims may be derived from information, images and drawings; errors excepted!
All rights, including rights created by patent grant or other registration, are reserved.
These operating instructions are the copyright of
GÜNTNER GmbH & CO. KG
Fürstenfeldbruck

1.4 Warranty and liability

The current General Terms and Conditions of Sales and Delivery of Güntner GmbH & Co. KG apply.
Page 7 / 104
See the homepage at http://www.guentner.de
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG

1.5 Manufacturer and supplier address

Should you have a problem with any of our equipment, or any questions, suggestions or special requests, simply contact
Güntner GmbH & Co. KG
Hans-Güntner-Strasse 2-6
D-82256 Fürstenfeldbruck, Germany
Service Telephone Germany:
0800 48368637
0800 GUENTNER
Service Telephone Worldwide:
+49 (0)8141 242-4815
Fax. +49 (0)8141 242-422
service@guentner.de
http://www.guentner.de
Page 8 / 104
Copyright © 2015 Güntner GmbH & Co. KG
All rights, including rights of photomechanical reproduction and storage in electronic form, are reserved.

1.6 EMC-compliant installation

Controllers in the GHM spray series fulfil the requirements of EN 61000-6-2 as regards resis­tance to EMC interference and those of EN 61000-6-3 as regards emissions.
They also comply with standards IEC 61000-4-4/-5/-6/-11 for grid-bound interference. In or­der to guarantee EM compatibility, the following points must be noted:
All measurement and signalling lines must be connected via shielded cables.
• The shielding of measuring, signal and bus lines must be earthed at one end only.
• Suitable shielding and routing measures must be taken to ensure that mains cables and mo­tor cables do not give rise to any interference in signal and control lines.
If the equipment is installed in a switch cabinet, proper attention must be given to the temperature inside the cabinet. Güntner switch cabinets are provided with sufficient ventilation.
ADVICE
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG

2 Short description

The GHM manages the spraying of heat exchangers. GHM spray basic can be used for only one spraying step.
With GHM spray professional you can manage up to nine steps. This system is notable for its minimal water consumption, which is achieved by spraying just enough sections to reach the specified setpoint.
Page 9 / 104
Accumulated annual temperature curve
The illustrated example shows a cumulated medium temperature curve achieved with GHM spray professional. In dry operation the medium temperature (condenser temperature or re­turn temperature) follows the ambient temperature (areas 1 to3). When the ambient temper­ature is low, the medium temperature is held to the setpoint set up on the speed controller (area4).
Using the GHM to regulate spraying calls for a second setpoint. In this example this setpoint is chosen to be 30°C. This setpoint is set up in the GHM, having been calculated by the product selection program GPC during the configuration process. The spraying setpoint determines the length of time in hours the unit is sprayed, with reference to data pertaining to the local climate. The higher the number of spraying hours for the unit the more precisely it can fulfil the setpoint. While the ambient temperature is low (area4), the medium temperature follows the setpoint of the speed controller. If the ambient temperature rises it will no longer be possi­ble to reach the speed control setpoint (area3) because the fans will already be operating at maximum speed. If the ambient temperature continues to rise (area2), the medium temper­ature will be governed by the setpoint of the GHM. If the ambient temperature rises so high (area1) that the setpoint can no longer be reached, then the medium temperature will contin­ue to rise at a corresponding displacement to the ambient value.
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG

3 System operation in a master-slave configuration

If a number of units are operated in a master-slave configuration, common inlet and drain valves provided by the customer can be used for several units. These valves are then con­trolled exclusively by the master. The following device configurations allow master-slave con­trol:
The master unit is operated in Auto internal mode. Auto internal mode has to be configured on the spraying controller (GHM controller) as well as on the speed controller (GMM con­troller). The slave unit is operated in Slave external analogue mode.
Page 10 / 104
The master unit is operated in Auto external bus mode or Auto external analogue mode. Au­to external mode has to be configured on the spraying controller (GHM controller) as well as on the speed controller (GMM controller). The slave unit is operated in Slave external analogue mode.
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Page 11 / 104
All units are operated in Slave mode. One of the slave units takes over control of the solenoid valves provided by the customer. The device configuration indicates which unit activates the valves provided by the customer. It has to be ensured in this mode of operation that all spray­ing controllers (GHM controller) and speed controllers (GMM controller) are configured in Slave mode.
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG

4 Commissioning GHM spray

The GHM spray must be set up in accordance with the configuration of the heat exchanger and the fans. This commissioning process determines the performance of the heat exchanger.
The GHM spray automatically detects whether commissioning has been carried out when it is switched on and, if it has, continues with normal operation.
If the GHM spray detects that this has not yet been done, it initiates the commissioning proce­dure. When this procedure has been completed, all the specified parameters are saved.
Page 12 / 104
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG

4.1 The initial commissioning procedure

If it is recognized that commissioning has not yet taken place, the following values are interro­gated and set up in accordance with the following flow chart.
Page 13 / 104
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Page 14 / 104
If it is recognized that a commissioning is required, the commissioning menu is displayed.
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Page 15 / 104
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Page 16 / 104
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG

5 Construction of the GHM spray

GHM spray basic system
GHM spray professional system
Page 17 / 104
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG

5.1 Remote controllers

5.1.1 Functional description

Functional description of GRCspray.1
GRCspray.1 is used to manage spraying together with either a GMM speed controller with bus communication or an external speed controller without bus communication. As a minimal so­lution, the GRCspray.1 can control one step (variant GHM spray basic).
Page 18 / 104
Variant GHM spray basic
If you need more steps you will need to combine the GRCspray.1 with the GIOD.1 expansion module, ERP no. 5204183 (variant GHM spray professional).
Variant GHM spray professional
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Page 19 / 104
In order to operate the controller it must have a power supply and must be enabled via digital input DI1. If this is not enabled the process will not be regulated. The unit has an internal PID controller, whose parameters (amplification factor, integral time) can be configured either per menu or via an external bus module. The spraying setpoint can be specified from the internal menu. The current value is determined via a pressure sensor (4-20mA), a temperature sensor (KTY, GTF210) or via BUS from the GMM speed controller. The relay outputs controlling the output stages are switched as appropriate for the setpoint and the number of steps. A switch-on threshold can be configured for each step.
The digital inputs are designed as potential-free contacts that must be connected to +24V. Spraying will be enabled only if the external enable (DI1) is connected and the fans are in op­eration. Fan operation is either conveyed from GMM to GHM via bus communication or by means of an additional enable (D12). This enable (DI2) is valid only if there is no bus commu­nication between GMM and GHM spray.
ADVICE
Please note that connecting the wrong voltage (e.g. 230V) may seriously damage the controller.
Relay outputs are used to control solenoid valves and activate warning messages. The CAN in­terface of the GRCspray.1 is an internal interface for communicating with other Güntner units (such as the GIOD.1 expansion module). Communications modules are available for the fol­lowing external bus connections: Modbus (GCM MOD GHMspray Rail.1, ERP no. 5206138) and Profibus (GCM PROF GHMspray Rail.1, ERP no. 5206140).
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Page 20 / 104
Functional description of GIOD.1
The GIOD.1 is controlled via CAN by a Güntner controller. The GIOD.1 possesses 16 digital in­puts with a rated voltage of 24VDC and 8 relay outputs. The bus address of the GIOD.1 (node ID) is set up using a rotary encoding switch. The address 0xF may not be used for this.
ADVICE
To operate the GIOD on GHM professional the rotary switch must always be set to addressA.
The GIOD reads this address only when first switched on.
To ensure the bus connection between the controller and one or more other units works cor­rectly, bus termination must be activated at the beginning and end of the bus connection by setting the units’ DIP switches labelled “Term”. They must be placed in the “ON” position to activate the termination. Units that are in the middle of the bus and therefore permitted to transfer the bus signal may not have bus termination activated.
The status of the inputs and outputs is indicated by LEDs on the front of the casing. A lit LED against the digital inputs signifies that the corresponding input is receiving a “high” signal. A lit LED against the relay outputs signifies that the closer contact is closed. A power LED signi­fies that the internal electronic components are receiving power. There is also a status display for the bus connection that involves two LEDs.
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Page 21 / 104
Bus status LED Description
On The GIOD.1 is in operation
Flashing 50:50 The GIOD.1 can be taken into operation
Brief single flash The GIOD.1 is currently stopped
Three flashes with error LED The software is attempting to overrun the stack on the
GIOD.1
Alternate flashing with error LED
Synchronous fast flashing with error LED
Bus error LED Description
Off Unit is operating correctly
On There is a static fault on the CAN bus
Brief single flash The warning limit has been reached in the CAN controller
Double flashing A fault was detected in the lifeguard, nodeguard or heart-
Three flashes with the bus sta­tus LED
Alternate flashing with the bus status LED
Synchronous fast flashing with error LED
Power LED Description
On The internal electronics are receiving power
A “layer setting service” is being performed on the GIOD.1
Reset to default has been selected on the rotary coding switch (setting “F”)
beat
The software is attempting to overrun the stack on the GIOD.1
A “layer setting service” is being performed on the GIOD.1
Reset to default has been selected on the rotary coding switch (setting “F”)
Off The unit is not powered or is reverse-poled
Digital input LED Description
On The digital input detects a “High” signal
Off The digital input detects a “Low” signal
Digital output LED Description
On The digital output is closed
Off The digital output is open
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
5.1.1.1 Configurable step generator 
The step generator comprises three main components
1. Step generator
The step generator generates a bit pattern for the outputs that are to be switched depending on the number of steps, their thresholds, their hysteresis and the hold-off time (=default set­ting).
Page 22 / 104
2. Section cycling
Section cycling ensures even distribution of the running times for the outputs (the sections). To this end it records and evaluates the running times of all the active outputs.
Active section cycling means,
- when a step is switched on, the output with the least running time is activated. No change is made to any outputs that were already active.
- when a step is switched off, the output with the highest running time is deactivated.
- when no change is made (the number of outputs does not change for a period of one hour) no outputs are switched over.
- An even distribution of running times can be achieved only in association with the installation’s general control behaviour on the basis of higher or lower heat exchanger perfor­mance.
ADVICE
When section cycling is deactivated, steps and outputs are correlated 1:1. In other words, step1 switches output1, step2 switches output2, and so on.
When section cycling is active, an active step is assigned to an output depending on its run­ning time. The current assignments are shown in the Current values menu.
3. Outputs
The outputs are the physical correlations of steps to outputs. This depends on the type of GHM spray and the number of steps. See also Configuration table, Page 37
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG

5.1.2 Installation / Operating conditions

Installation / Operating conditions GRCspray.1
• The module is designed for mounting on a top-hat rail.
• All measurement and signalling lines must be connected via shielded cables.
• The shielding of measuring, signal and bus lines must be earthed at one end only.
• Suitable shielding and routing measures must be taken to ensure that mains cables and motor cables do not give rise to any interference in signal and control lines.
• Temperature: Storage Transport: Operation:
• Protection rating: IP 20
• Recommended cables: Belden9841, Lapp 2170203, Lapp 2170803, Helukabel 81910
-20°C ... +70°C
-20°C ... +65°C
Page 23 / 104
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Page 24 / 104
Installation / Operating conditions GIOD.1
• The module is designed for mounting on a top-hat rail.
• Bus lines that are not wired via the supplied ribbon cable must be shielded.
• The shielding of bus lines must be earthed at one end only.
• Suitable shielding and routing measures must be taken to ensure that mains cables and motor cables do not give rise to any interference in signal and control lines.
• Temperature: Storage location, Transport Operation:
• Protection rating: IP 20
-20°C .. +70°C
-20°C .. +65°C
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG

5.1.3 Connections

Connections GRCspray.1
Page 25 / 104
Upper row of connections
Name Description
Service Service plug only for use by service personnel
TB1
TB2
Firm Pushbutton only for use by service personnel
+24V
+24V
GND
GND
GND
11
12
14
21
22
24
31
32
34
41
External feed for power supply
Contact ground for external power feed
Terminal not connected
relay DO1
relay DO2
relay DO3
42
44
relay DO4
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Lower row of connections
Name Description
AO1 Analogue output 1, 0-10V
GND Ground
AO2 Analogue output 2, 0-10V
Page 26 / 104
TB3
TB4
GND Ground
+24V Voltage +24V
DI1 Digital input +24V
DI2 Digital input +24V
DI3 Digital input +24V
+24V Voltage +24V
+24V Voltage +24V
GND Ground
AI1 Analogue output 4-20mA
AI2
AI3 Analogue input for temperature sensor GTF
AI4 Analogue input 0-10V
GND Ground
+24V
+24V
Term DIP switch for CAN bus termination (120) / ON = termination activated
Analogue input 4-20mA or for temperature sensor GTF must be configured in the soft-
ware
Voltage +24V
+24V Voltage +24V
TB5
GND Ground
CH CAN high signal
CL CAN low signal
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
GND Ground
+24V Voltage +24V
CAN CAN bus plug including power supply
*TB: Terminal block
Page 27 / 104
Lower row of connections
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Page 28 / 104
Connections GIOD.1
Upper row of connections
Name Description
DI1 Digital input 1
DI2 Digital input 2
TB1
TB2
TB3
DI3 Digital input 3
DI4 Digital input 4
DI5 Digital input 5
DI6 Digital input 6
DI7 Digital input 7
DI8 Digital input 8
13
Relay contact 1 closer
14
23
Relay contact 2 closer
24
33
Relay contact 3 closer
34
43
Relay contact 4 closer
44
53
Relay contact 5 closer
54
63
Relay contact 6 closer
64
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Name Description
73
74
83
84
Page 29 / 104
Upper row of connections
Relay contact 7 closer
Relay contact 8 closer
Operating instructions – Güntner Hydro Management GHM spray V_4.0
© Güntner GmbH & Co. KG
Lower row of connections
Name Description
CAN CAN bus plug including power supply
Page 30 / 104
TB4
TB5
+24V
+24V
GND Contact ground for external power feed
CH CAN high signal
CL CAN low signal
Node ID
DI9 Digital input 9
DI10 Digital input 10
DI11 Digital input 11
DI12 Digital input 12
DI13 Digital input 13
DI14 Digital input 14
DI15 Digital input 15
External feed for power supply
Rotary switch for setting the bus node address 0: Address 0 1: Address 1
-
­E: Address 14 F: Reset CANopen parameters to their default values
DI16 Digital input 16
+24V
+24V
TB6
Operating instructions – Güntner Hydro Management GHM spray V_4.0
+24V
GND
GND
Voltage +24V
Ground
© Güntner GmbH & Co. KG