Gude Expert Power Control 1292, Expert Power Control 1202, 8801 User Manual

Page 1
Manual
Expert Power Control 1202 Expert Power Control 1292
© 2018 Gude Analog- und
Digitalsysteme GmbH
Manual Ver. 2.4.3
from Firmware Ver. 1.6
Page 2
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Page 3
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Table of contents
1. Device Description 6
1.1 Security Advice ....................................................................................................... 7
1.2 Content of Delivery ................................................................................................. 7
1.3 Description ............................................................................................................. 7
1.4 Installation ............................................................................................................. 9
1.5 Overvoltage Protection ......................................................................................... 10
1.6 Technical Specifications ........................................................................................ 11
1.6.1 Electrical Measurement ......................................................................................... 12
1.7 Sensor .................................................................................................................. 12
2. Operating 14
2.1 Operating the device directly ................................................................................ 15
2.2 Control Panel ........................................................................................................ 15
2.3 Maintenance ........................................................................................................ 17
2.3.1 Maintenance Page ................................................................................................. 18
2.3.2 Configuration Management .................................................................................. 19
2.3.3 Bootloader Activation ............................................................................................ 21
2.4 GSM ..................................................................................................................... 22
2.4.1 SMS ........................................................................................................................ 24
2.4.1.1
SMS Commands ............................................................................................... 24
2.4.1.1.1 Powerport: Query Power Port State ........................................................... 24
2.4.1.1.2 Powerport: Simple Switching ...................................................................... 24
2.4.1.1.3 Powerport: Advanced Switching (Batchmode) ........................................... 25
2.4.1.1.4 Powerport: Advanced Switching (coldstart) ............................................... 25
2.4.1.1.5 Configuration: Read .................................................................................... 26
2.4.1.1.6 Configuration: Write ................................................................................... 26
2.4.1.1.7 Configuration: All Parameter ...................................................................... 27
2.4.1.1.8 Sensors: Query State ................................................................................... 28
2.4.1.1.9 Query Device State ...................................................................................... 28
2.4.1.2
SMS replies ...................................................................................................... 28
2.4.1.2.1 SMS command replies ................................................................................. 28
2.4.1.2.2 Status Change Report SMS ......................................................................... 29
2.4.2 Voice Call ................................................................................................................ 30
2.4.2.1
Menu ................................................................................................................ 30
2.4.2.1.1 Power Port Menu ........................................................................................ 31
2.4.2.1.2 Status Menu ................................................................................................ 32
2.4.2.1.3 Parameter Description ................................................................................ 32
2.4.3 Power Port Commands .......................................................................................... 33
2.4.4 Security .................................................................................................................. 35
3. Configuration 36
3.1 Power Ports .......................................................................................................... 37
Page 4
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Table of contents
3.1.1 Watchdog ............................................................................................................... 38
3.2 Ethernet ............................................................................................................... 39
3.2.1 IP Address ............................................................................................................... 40
3.2.2 IP ACL ..................................................................................................................... 41
3.2.3 HTTP ....................................................................................................................... 42
3.3 Protocols .............................................................................................................. 43
3.3.1 Console ................................................................................................................... 43
3.3.2 Syslog ..................................................................................................................... 44
3.3.3 SNMP ...................................................................................................................... 44
3.3.4 Radius ..................................................................................................................... 46
3.3.5 Modbus TCP ........................................................................................................... 47
3.4 Sensors ................................................................................................................. 48
3.4.1 Port Switching ........................................................................................................ 49
3.5 E-Mail ................................................................................................................... 50
3.6 Front Panel ........................................................................................................... 51
3.7 GSM ..................................................................................................................... 51
3.7.1 GSM General .......................................................................................................... 52
3.7.2 GSM Misc ............................................................................................................... 53
3.7.3 GSM Phonebook .................................................................................................... 54
3.7.4 GSM SIM Card ........................................................................................................ 54
3.7.5 GSM Provider ......................................................................................................... 54
4. Specifications 56
4.1 IP ACL ................................................................................................................... 57
4.2 IPv6 ...................................................................................................................... 57
4.3 Radius ................................................................................................................... 58
4.4 Automated Access ................................................................................................ 58
4.5 SNMP ................................................................................................................... 59
4.5.1 Device MIB 1202 .................................................................................................... 61
4.5.2 Device MIB 1292 .................................................................................................... 63
4.6 SSL ........................................................................................................................ 64
4.7 Console ................................................................................................................. 67
4.7.1 Console Cmd 1202 ................................................................................................. 69
4.7.2 Console Cmd 1292 ................................................................................................. 75
4.8 Modbus TCP ......................................................................................................... 82
4.9 Messages .............................................................................................................. 86
5. Support 88
5.1 Data Security ........................................................................................................ 89
5.2 Contact ................................................................................................................. 89
5.3 Declaration of Conformity ..................................................................................... 90
Page 5
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Table of contents
5.4 FAQ ...................................................................................................................... 90
91
Index
Page 6
Device Description
Page 7
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Device Description
1 Device Description
1.1 Security Advice
· The device must be installed only by qualified personnel according to the following installation and operating instructions.
· The manufacturer does not accept responsibility in case of improper use of the device and particularly any use of equipment that may cause personal injury or ma­terial damage.
· The device contains no user-maintenable parts. All maintenance has to be per­formed by factory trained service personnel.
· This device contains potentially hazardous voltages and should not be opened or disassembled.
· The device can be connected only to 230V AC (50Hz or 60 Hz) power supply sock­ets.
· The power cords, plugs and sockets have to be in good condition. Always connect the device to properly grounded power sockets.
· The device is intended for indoor use only. Do NOT install them in an area where ex­cessive moisture or heat is present.
· Because of safety and approval issues it is not allowed to modify the device without our permission.
· The device is NOT a toy. It has to be used or stored out or range of children.
· Care about packaging material. Plastics has to be stored out of range of children.
Please recycle the packaging materials.
· In case of further questions, about installation, operation or usage of the device, which are not clear after reading the manual, please do not hesitate to ask our sup­port team.
· Please, never leave connected equipment unattended, that can cause damage.
· Connect only electrical devices that do not have limited on-time. I.e. in case of fail-
ure, all connected appliances have to cope with a continuous on-time without caus­ing damage.
1.2 Content of Delivery
The package includes:
· Expert Power Control 1202 / 1292
· GSM Antenna (only EPC 1292)
· Quick Start Guide
· CD-ROM with Manual and Softwaretools
1.3 Description
The Expert Power Control 1202 / 1292 can switch 4 different load outputs. The device has the following features:
· 4 Power Ports individually switchable directly on the device, via HTTP(S), SNMP
· Case allows mounting in 19 inch racks
Page 8
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Device Description
· Status and Power-up delay (0...9999 seconds) adjustable individually for each Power Port after power blackout
· Simultaneous power-up of multiple Power Ports prevented by latency time of 1 second
· Programmable turn-on/turn-off sequence
· 4-channel watchdog, an individual watchdog (ICMP/TCP) can be assigned for each
Power Port
· Metering of energy, current, power factor, phase angle, frequency, voltage and act­ive/apparent/reactive power
· Two energy meters, one meters continously, the other energy meter is resettable
· A clearly visible LED display on the device reveals total current, IP address, sensor
data and error reports
· Interface for optional sensors for environmental monitoring (temperature and humid­ity)
· Integrated overvoltage protection prevents damage of device and of connected con­sumers (L-N 10 kA)
· Dedicated high-inrush relays avoid welding of relay contacts at start-up peaks
· Firmware update via Ethernet during operation
· Comfortable configuration by web browser, Windows or Linux tool
· Generation of messages (e-mail, Syslog and SNMP traps) and relay switching de-
pending on the energy measurement limits, resp. external sensors
· IPv6 ready
· HTTP/HTTPS, e-mail (SSL, STARTTLS), DHCP, Syslog
· SNMPv1, v2c, v3 (Get/Traps)
· Modbus TCP Support
· Console Commands with telnet support and serial interface.
· TLS 1.0, 1.1, 1.2
· IP Access Control List
· Secure login over SSL
· Low internal power consumption
· Developed and manufactured in Germany
Only Expert Power Control 1292:
· 4 Power Ports individually switchable via voicecall, SMS and Datacall
· GSM admin and user access for all Power Ports definable
· For pre-paid and post-paid SIM cards (SIM card not included)
· Triband network
· FreeCall: Predefined action upon toll-free incoming call from a specific number
Page 9
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Device Description
1.4 Installation
1. Actual Current (7-segment display)
2. OK Button
3. Select Button
4. Signal Tower indicator LED for GSM Connection (only EPC 1292)
5. "Flash" LED Overvoltage Protection (red when inactive)
6. "S1" external sensor indicator
7. GSM signal strength (only EPC 1292)
8. 4 plain text displays (on/off) for the state of the Power Ports
1. Sensor connector
2. Antenna terminal (only EPC 1292)
3. Ethernet connector (RJ45)
4. SIM card slot (only EPC 1292)
Page 10
10
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Device Description
Power Ports 1 to 4 (Expert Power Control 1202-1 / 1292-1)
Power Ports 1 to 4 (Expert Power Control 1202-2 / 1292-2)
Power Ports 1 to 4 (Expert Power Control 1202-3 / 1292-3)
Start-up the device
· Connect the power cord of the unit to the mains supply.
· Plug the network cable into the Ethernet connector (RJ45).
· Attach the optional external sensor to the sensor connector.
1.5 Overvoltage Protection
The device contains an overvoltage protection. The protection is based on input side varistors with thermal fuse between phase (L) and neutral (N) to protect the internal electronics and power ports with failure detection (permanently triggered thermal fuse). The state of the protection is indicated on the front panel by a red flash. A not visible flash means, that the protection is active, a red flash symbolizes that the overvoltage
Page 11
11
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Device Description
protection fails. In addition, the status of the overvoltage protection can be seen on the Webpage (HTTP) and acquired with SNMP. The surge protection module is designed that it can derive a practical unlimited number of voltage pulses in normal installation environments. In an environment with many energy rich surge pulses it can result in permanent loss of function due to aging of the overvoltage protection element.
Recovering of the overvoltage protection function can only be performed by the manufacturer of the device. In the normal case, the device will continue to work even after the failure of the protective function.
A signaling via E-Mail, Syslog or SNMP trap occurs only once during operation, ex­actly at the moment in which the protection fails. In addition, at the start up of the device a message is generated, when the overvoltage protection is not active.
1.6 Technical Specifications
Interfaces
(EPC 1202-1 / EPC 1292-1) 1 x Power supply (CEE 7/4 type F, max.16 A),
length approx 2m
4 x Load outputs (CEE 7/3 type F, max. 16 A) 1 x Ethernet port (RJ45) 1 x Mini-DIN for external sensor
(EPC 1202-2 / EPC 1292-2) 1 x Power supply (CEE 7/4 type E, max.16 A),
length approx 2m
4 x Load outputs (CEE 7/3 type E, max. 16 A) 1 x Ethernet port (RJ45) 1 x Mini-DIN for external sensor
(EPC 1202-3 / EPC 1292-3) 1 x Power supply (CEE 7/4 type J, max.10 A),
length approx 2m
4 x Load outputs (CEE 7/3 type J, max. 10 A) 1 x Ethernet port (RJ45) 1 x Mini-DIN for external sensor
Network connectivity
10/100 MBit/s 10baseT Ethernet
Protocols
TCP/IP, HTTP/HTTPS, SNMP v1/v2c/v3, SNMP traps, Syslog, E-Mail (SMTP)
GSM Modem (only EPC 1292)
Triband GSM Module (900/1800/1900
MHz)
Sim Card (only EPC 1292)
Mini-SIM
Power Supply
internal power supply (90-265V AC / -15% /
+10%)
Overvoltage Protection
· maximum operating voltage
· single peak current for 20/80us pulse
· max. clamping voltage 20/80us pulse,
Ipk = 100 A
20 mm/190 J varistor disk
300 VACrms 10000 A 710 V
Environment
· Operating temperature
· Storage temperature
· Humidity
0°C - 50 °C
-20°C - 70 °C 0% - 95% (non-condensing)
Case
Synthetic
Measurements
484mm x 46mm x 74mm (L x H x W)
Weight
approx. 1050 g
Page 12
12
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Device Description
1.6.1
Electrical Measurement
typical fault tolerances for Ta=25°C, I=1Arms...16Arms, Un=90Vrms...265Vrms
Electrical Measurement Specification
Category
Range
Unit
Resolu­tion
Inaccuracy (typical)
Voltage
90-265
V
0.01
< 1%
Current
0 - 16
A
0.001
< 1.5%
Frequency
45-65
Hz
0.01
< 0.03%
Phase
-180 - +180
°
0.1
< 1%
Active power
0 - 4000
W1< 1.5%
Reactive power
0 - 4000
Var1< 1.5%
Apparent power
0 - 4000
VA1< 1.5%
Power factor
0 - 1-0.01
< 3%
Energy Counter
Active Energy (total)
9.999.999,999
kWh
0.001
< 1.5%
Active Energy (temporary)
9.999.999,999
kWh
0.001
< 1.5%
1.7 Sensor
One external sensor can be connected to the Expert Power Control 1202 / 1292. The following sensors are currently available
Temperature-Sensor 7001
Cable length
Connector
Mini-DIN
Measurement range
-20°C to +80°C at ±2°C (maximum) and ±1°C (typical)
Page 13
13
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Device Description
Humidity/Temperature-Sensor 7002
Cable length
Connector
Mini-DIN
Measurement range
Temp: -20 to +80°C, ±0,5°C (maximum) and ±0,3°C (typical) Humidity: 0-100%, ±3% (maximum) and ±2% (typical)
The sensor is automatically detected after connect. This is indicated by the green "S1" LED on the front panel. The sensor values are displayed at the "Control Panel" web page:
A click on the link in the "Name" column opens the display of the Min and Max values. The values in a column can be reset using the "Reset" button. The "Reset" button in the name column deletes all stored Min and Max values.
Page 14
Operating
Page 15
15
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
2 Operating
2.1 Operating the device directly
Port Switching
The current status of the output is indicated by the color of the LED. Red indicates that the output is off, green shows that the output is on. On the device are the buttons "se­lect" and "ok". If you press "select", the LED will blink for the first output, ie the output is selected. Press "select" again to select the next output. Hold down the button "ok" for two seconds, then the status of the selected output is toggled.
Display Information
If no port is selected manually, repeatedly pressing the "ok" key will show the IP-ad­dress and the values of the external sensors on the display.
Status-LED
The Status LED shows the different states of the device:
· red: The device is not connected to the Ethernet.
· orange: The device is connected to the Ethernet and waits for data from the DHCP
server.
· green: The device is connected to the Ethernet and the TCP/IP settings are alloc-
ated.
· periodic blinking: The device is in Bootloader mode.
2.2 Control Panel
Access the web interface: http://"IP-address" and log-in.
The web page provides an overview of the switching state, energy measurement val­ues, as well as the external sensors, provided that they are connected. When a single
Page 16
16
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
port is clicked at the Expert Power Control 1202 / 1292, a panel with buttons to con­trol a single port appear:
The Port icon is green when the relay is closed, or red in the open state. An additional small clock icon indicates that a timer is active. Timer can be activated by delay, reset or batch mode.
An activated Watchdog is represented by an eye icon. An "X" means, that the address that should be observed, could not be resolved. Two circular arrows show a booting status.
The ports can be switched manually with the "On" and "Off" buttons. If the port is turned on, it can be turned off by pressing the "Reset" button, until after a delay it turns itself on again. The delay time is determined by the parameter Reset Duration, which is described in the chapter "Configuration - Power Ports ". The "Close" button dis­solves the panel again.
Batchmode
Each individual port can be set for a selectable period of time to the state "switch on" or "switch off". After the selected time they are automatically switched to the second preselected state.
Optionally the device can be switched via a Perl script or external tools like wget. More information is available on our support wiki at www.gude.info/wiki.
For devices with a GSM module (Expert Power Control 1292), additional reception in­formation, the prepaid credit and the own call number are displayed. An overview of the GSM activities can be expanded.
37
Page 17
17
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
2.3 Maintenance
The actual device generation with IPv6 and SSL allows all maintenance functions in the web interface to be carried out on the Maintenance Page .
Maintenance in the web interface
The following functions are available from the maintenance web page:
· Firmware Update
· Change the SSL certificate
· Load and save the configuration
· Restart the device
· Factory Reset
· Jump into the Bootloader
· Delete the DNS cache
Upload Firmware, Certificate or Configuration
On the Maintenance Page , select the required file with "Browse .." in the sections "Firmware Update", "SSL Certificate Upload" or "Config Import File Upload" and press "Upload". The file is now transferred to the update area of the device and the contents are checked. Only now, pressing the "Apply" button will permanently update the data, or abort with "Cancel".
Only one upload function can be initiated with a reboot, eg. you cannot transmit
firmware and configuration at the same time.
If after a firmware update, the web page is not displayed correctly anymore, this
may be related to the interaction of Javascript with an outdated browser cache. If a Ctrl-F5 does not help, it is recommended that you manually delete the cache in the browser options. Alternatively, you can test start the browser in "private mode".
Actions in Bootloader mode
If the web interface of the device is no longer accessible, the device can be put into Bootloader mode (see chapter Bootloader activation ). The following functions can be executed using the GBL_Conf.exe application:
· Set IPv4 address, net-mask and gateway
· Turn HTTP password on and off
· Turn IP-ACL on and off
· Factory Reset
· Jump into the bootloader (can be switched on and off)
· Restart the device
For devices with relays, entering or exiting the bootloader mode does not change the state of the relays as long as the operating voltage is maintained.
The GBL_Conf.exe program is available free of charge on our website www.gude.info and can also be found on the enclosed CD-ROM.
18
18
21
Page 18
18
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
Interface GBL_Conf
To check the network settings with GBL_Conf.exe, start the program and choose "All Devices" in the "Search" menu. From the list select the appropriate device. The lower
part of the left half of the window now shows the current network settings of the device. If the IP address is displayed with the default settings (192.168.0.2), either no DHCP server is present on the network, or there could be no free IP address assigned to it.
· Activate the Bootloader Mode (see Chapter Bootloader Mode) and choose in menu
"Search" the item "Bootloader-Mode Devices only"
· Enter the desired settings in the edit window and save them with "Save Config".
· Deactivate the boot loader mode for the changes to take effect. Select again "All
Devices" in the "Search" menu of GBL_Conf.exe.
The new network configuration is now displayed.
Factory Reset
The device can be reset to the factory default via the web interface from the Mainten­ance Page or from the Bootloader mode (see chapter Bootloader activation ). All TCP/IP settings are reset in this operation.
If a unit is set to factory defaults, an uploaded certificate or updated firmware will be preserved.
2.3.1
Maintenance Page
This section provides access to important functions such as Firmware Update or Re­start Device. It is advisable to set an HTTP password for this reason.
18 21
Page 19
19
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
Firmware Update: Start a firmware update.
SSL Certificate Upload: Saves your own SSL certificate. See chapter "SSL " for the generation of a certificate in the right format.
Config Import File Upload: Loads a new configuration from a text file. To apply the new configuration, a "Restart Device" must be executed after the "Upload".
Config File Export: Saves the current configuration in a text file.
Saving the configuration should only be carried out in an SSL connection, since it contains sensitive password information (even if it is encrypted or hashed).
Restart Device: Restarts the device without changing the status of the relays.
Some functions such as a firmware update or changing of the IP-address and HTTP settings require a restart of the device. A jump to the boot loader or a restart of the device lead by no means to a change of the relay states.
Restore Fab Settings and Restart Device: Performs a restart and resets the device to factory default .
Enter Bootloader Mode: Jumps into bootloader mode, where additional settings can be made with GBL_Conf.exe.
Flush DNS Cache: All entries in the DNS cache are discarded and address resolutions are requested again.
2.3.2
Configuration Management
The device configuration can be saved and restored in the maintenance area .
65
22
18
Page 20
20
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
The "Config File Export" function can be used to save the current configuration as a text file. The syntax used in the configuration file corresponds to the commands of the Telnet console. If the configuration of a device is to be restored from a text file, load the file with "Upload" and restart the device with "Restart Device".
Saving the configuration should only be carried out in an SSL connection, since it contains sensitive password information (even if it is encrypted or hashed). For the same reasons, it is advisable to carefully handle the generated configuration files when archiving.
Editing the configuration file
It is possible to customize a saved configuration file with a text editor for your own needs. For example, one scenario would be to use a script language to automate the creation of many customized versions of a configuration, then equip a large number of devices with an individualized configuration. Also Upload and restart with CGI com­mands can be done in scripting languages. With use of the comment sign "#" you can quickly hide single commands or add personal notes.
If you modify a configuration file manually, it is not always clear which limits are allowed for parameters. After uploading and restarting, commands with invalid parameters are ignored. Therefore, the generated configuration includes comments describing the boundaries of the parameters. Where "range:" refers to a numeric value, and "len:" to a text parameter. E.g:
email auth set 0 #range: 0..2 email user set "" #len: 0..100
The command "system fabsettings" from the beginning of a generated configuration file brings the device into the factory state, and then executes the individual commands that modify the configuration state. It may be desirable to make the changes relative to the current configuration, and not out of the factory state. Then the "system fabset­tings" should be removed.
No output of default values
The configuration file contains (with exceptions) only values which differ from the de­fault. The command "system fabsettings" (go to the factory state) from the beginning of a generated configuration file should not be removed, otherwise the device can get in­completely configured.
Configuration via Telnet
The configuration files can in principle also be transferred in a Telnet session, but then the settings are changed during operation, and not completely when restarting, as it would have been the case with an upload. It can happen that events are triggered at the same time as the device is configured. One should therefore:
a) disable the function b) completely parametrize c) reactivate the function
Page 21
21
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
An example:
email enabled set 0 email sender set "" #len: 0..100 email recipient set "" #len: 0..100 email server set "" #len: 0..100 email port set 25 email security set 0 #range: 0..2 email auth set 0 #range: 0..2 email user set "" #len: 0..100 email passwd hash set "" #len: 0..100 email enabled set 1 #range: 0..1
2.3.3
Bootloader Activation
The configuration of the device from the application "GBL_Conf.exe" is only possible, if the device is in Bootloader Mode.
Activation of the Bootloader Mode
1) via push button:
· Hold both buttons for 3 seconds
2) or
· Remove the power supply
· Hold down the "Select" button. If the push button is recessed, use a pin or paper clip
· Connect the operating voltage
3) by Software: (only if "Enable FW to BL" was previously activated in the "GBL_Conf.exe" application)
· Start the "GBL_Conf.exe" program
· Do a network search with the "Search" menu action
· Activate in menu "Program Device" the item "Enter Bootloader"
4) via web interface:
Press "Enter Bootloader Mode" on the maintenance web page.
Whether the device is in Bootloader mode, is indicated by the flashing of the status LED, or it is shown in "GBL_Conf.exe" application after a renewed device search (ap­pendix "BOOT-LDR" after the device name). In Bootloader mode the program "GBL_Conf.exe" can disable the password and the IP ACL, perform a firmware update, and restore the factory settings.
For devices with relays, entering or exiting the bootloader mode does not change the state of the relays as long as the operating voltage is maintained.
Abandonment of the Bootloader Mode
1) via push button:
· Hold both buttons for 3 seconds (only if the device has 2 buttons)
18
Page 22
22
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
2) or
· Remove and connect the power supply without operating a button
3) by Software:
· Start the "GBL_Conf.exe" application
· Do a network search with the "Search" menu action
· In menu "Program Device" activate the item "Enter Firmware"
Factory Reset
If the device is in bootloader mode, it can always be put back to its factory default. All TCP/IP settings are reset in this operation.
If a unit is set to factory defaults, an uploaded certificate or updated firmware will be preserved.
1) via push button:
· Activate the Bootloader Mode of the device
· Hold down the button (or the "Select" button for devices with 2 buttons) for 6
seconds. If the push button is recessed, use a pin or paper clip
· The status LED will blink in a fast rhythm, please wait until the LED blinks slowly
(about 5 seconds)
2) by Software:
· Activate the Bootloader Mode of the device
· "Start the GBL_Conf.exe" program
· In menu "Program Device" activate the item "Reset to Fab Settings"
· The status LED will blink in a fast rhythm, please wait until the LED blinks slowly
(about 5 seconds)
2.4 GSM
To use the GSM functions, there must be an activated SIM card in the SIM card slot.
If the SIM card is inserted, and the device is enabled, the integrated GSM module searches automatically for a connection to the GSM network. If this connection works, you can control and configure the device via SMS or by call.
When operating via SMS, send defined SMS commands to the device. The device ex­ecutes these commands and confirms them with reply SMS.
When operating via phone call, you can perform commands by FreeCall, that allow the unit to perform preconfigured commands, when it is called from a particular phone number. There is no connection established and there are no call charges. Another possibility is the voice call. Here, the device menu is operated using DTMF codes. This type of operation can also be carried out automatically.
Preparing for GSM operation
If you are using a new SIM card, please take note:
Page 23
23
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
1. Preparing the SIM card
· If you are using a contracted SIM card, please start with step 2
· If you are using a prepaid SIM card, please take care:
o There has to be a positiv balance on the card o The card has to be activated. New prepaid cards need some
manual operation at the start of usage. These requests have to be made from a user with a cellphone.
2. SIM-card pin code
· The device awaits the SIM card pin code 1234 first. Enter this PIN to the SIM card, by using a cellphone. In case you are using another pin code, you have to configure the EPC NET GSM before you activate the GSM part of the device! Otherwise this may lead to a lock of the SIM card.
· You can disable the need to enter the PIN code on the SIM card with a mobile phone. In this case the EPC NET GSM accepts the SIM card without checking the code.
3. Install SIM card
· Switch off the device or deactivate the GSM module. Alternatively, you can just turn off the GSM module in the EPC NET GSM via software. Never install a SIM card, when GSM module is active. Otherwise the SIM card may be destroyed.
· Insert the SIM card into the Push Sim Holder.
4. Connect Antenna
· Take the GSM antenna from the box and screw it to the EPC NET GSM by turning clockwise. It is enough to attract the connection hand-tight. Never use pliers to tighten or similar to the antenna, thus inevitably des­troying the antenna connection.
5. Activate the EPC NET GSM
· Power up the device. In factory default state, the GSM module is deac­tivated. This is a security setting in delivery to avoid accidentally locking a SIM card with the wrong code.
· Log in on the web interface.
· Switch to Configuration / GSM / SIM.
· Here the button "Enable GSM" is set to "No", that is the GSM module is
turned off. Set the button to "yes", then press the button "Apply" to trans­mit the data to the EPC NET GSM.
· Wait some minutes, until the device has logged into the GSM. You can see the status change from the Signal Tower indicator LED on the dis­play or in the web interface.
GSM Status LED's
The GSM status LED's displays different states of the GSM module.
Signal Tower indicator off
GSM module is deactivated.
Signal Tower indicator on
GSM module activated.
Signal Strength Indicator
· 0 bars - no signal
· 2 bars - approx. 30%
· 4 bars - approx. 70%
Page 24
24
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
· 6 bars - approx. 100%
2.4.1
SMS
2.4.1.1
SMS Commands
Description of the SMS format to send commands to the device:
Format
%[cmd-name] [param 1] [...] [param N] {param 1} {...} {param N}
[param x] = mandatory parameter
{param x} = optional paramater
If activated, a port code or master code will be required. Entering these codes is initi­ated by p (for Port code) or m (for Master code).
2.4.1.1.1 Powerport: Query Power Port State
Format
%port state [portnumber] {Portcode/Mastercode}
Command:
Request of status of Power Port 1, Portcode 1111
%port state 1 p1111
Answer:
Hostname: EPC-1292 Power Port state: Port 1 is Off
Credit: 130.50 Eur Temp. 1: 25.8 C
2.4.1.1.2 Powerport: Simple Switching
Format
%port [on, off, toggle] [portnumber] {Portcode/Mastercode}
Examples:
Switch off Power Port 2, Mastercode 2222
%port off 2 m2222
Toggle Power Port 8, Portcode 1238
%port toggle 8 p1238
Reset Power Port 6, Portcode 0123
%port reset 6 p0123
Switch on Power Port 1, without Portcode
%port on 1
Answer (example):
Device name: epc007 Power switch: Port 1 off -> on
Page 25
25
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
Account Credit: Credit: 130.50 Eur
2.4.1.1.3 Powerport: Advanced Switching (Batchmode)
Format
%port batchmode [portnumber] [batch-sequence-number] {Portcode/Mastercode}
[batch-sequence-number]
'11' .. '19' off, wait [t1 .. t9]s, on '21' .. '29' on, wait [t1 .. t9]s, off '31' .. '39' toggle, wait [t1 .. t9]s, toggle
Note: Sequence numbers are identical to the DTMF codes for voice calls.
tn
Time in seconds
t11t22t35t410t520t660t7
120t8240t9480
Example:
%port batchmode 1 13 m0123
Answer:
Device name: epc007 Switch sequence: Port 1 off -> t3 -> on Account Credit: Credit 130.50
2.4.1.1.4 Powerport: Advanced Switching (coldstart)
The command 'coldstart' turns off all Powerports at once. Then it switches the ports temporally delayed on again (according to the current power port configuration), as if the device performs a cold start.
Format
%coldstart {mastercode}
Example:
%coldstart m0123
Answer:
Device name: epc007 Switch sequence: coldstart Account Credit: Credit: 130.50 Eur
Page 26
26
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
2.4.1.1.5 Configuration: Read
Format
%config get [config-name] {mastercode}
[config-name ]:
all code telbook gsmstatus temp response error portname adminnum tempmin tempmax gsm
Example:
%config get code m1234
Answer:
Config: code = on
Example:
%config get all
Answer:
Config: code = on telbook = off [...] adminnum = 0161123456 gsm = on
2.4.1.1.6 Configuration: Write
Format
%config set [config-name] [config-value] {Mastercode}
[config-name] :
code telbook gsmstatus temp response error portname adminnum tempmin tempmax gsm
Example:
%config set code off m1234
Answer:
Config: code = off
27
27
Page 27
27
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
2.4.1.1.7 Configuration: All Parameter
Description
SMS [config-name]
SMS [config-value]
default
Master/Port Code enabled?
code
on, off
off
Check of phone book?
telbook
on, off
off
Send GSM Status SMS to 'adminnum'
gsmstatus
on, off
off
Send SMS to 'adminnum' if tempmin / temp­max are changed
temp
on, off
off
Send SMS reply on SMS com­mands to recent SMS user
response
on, off
on
Send SMS reply with error mes­sage, if SMS command was malformed
error
on, off
on
States con­figured Port name instead of Power Port n in SMS replies
portname
on, off
off
Allow deactiva­tion of GSM module via SMS
gsm
on, off
off
Phone number for e-mail mes­sages
email
max. 15 chars Access only for admin
mastergsm
on, off
off Autosync
autosync
on, off
off
DTMF for VoiceCall
calltone
on, off
off
Voice for VoiceCall
callvoice
on, off
on
Phone number for SMS mes­sages
adminnum
max. 15 chars
Minimum value for temperature alerts
tempmin
'-20' .. '0'
0
Maximum value for temperature alerts
tempmax
'0' .. '90'
50
Page 28
28
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
Description
SMS [config-name]
SMS [config-value]
default
Allows freecall operation
freecall
on, off
off
2.4.1.1.8 Sensors: Query State
Format
%sensor state [portnumber, all] {Mastercode}
Example:
Query the state of all sensors, Mastercode 0000
%sensor state m0000
Answer:
Device name: epc007 Port: Sensor port 1 Sensor name: Temperature
Value: NC Port: Sensor port 2
Sensor name: Temperature
Value: T=22.79C Value: RH= 76.64%
Account credit: Credit: 130.50 Eur
2.4.1.1.9 Query Device State
Format
%all state {Mastercode}
Example:
Query the state of the device:
%all state
Answer:
Device name: epc007: Status Outputport state: outp: 1=On 2=On 3=On 4=Off Inputport state: dinp: 1=Off 2=Off 3=Off 4=Off Sensor Port 1: senp 1: NC Sensor Port 2: senp 2: T=22.79C RH= 76.64% Account credit: Credit: 130.50 Eur
2.4.1.2
SMS replies
2.4.1.2.1 SMS command replies
A command reply SMS looks like:
Device name: [name]
prefix
[response text]
Command specific reply
Account credit: [x]
Page 29
29
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
[response text]
Device name: [name]
Power switch: [powerport] [s] -> [s] [powerport] = Port 1 .. Port 99 (or Config:portname) [s] = on .. off
Powerport state: [powerport] is [s], [...], [powerport] is [s] [powerport] = Port 1 .. Port 99 (or Config:portname) [s] = on .. off
Switch sequence: [s] [s]
[powerport] [c] -> wait t -> [c] [powerport] = 'Port 1' .. 'Port 99' (or Config:portname) [c] = on, off, toggle, coldstart
Account credit: [x]
Config: name = value, [...], name = value
or
command parse error
2.4.1.2.2 Status Change Report SMS
A SMS status change request reply looks like:
Device name: [name]
Prefix
[response text]
Status change request specific reply
Account credit: [x]
[response text]
Device name: [name]
[powerport] -> [s] [powerport] = 'Port 1' .. 'Port 99' (or Config:portname) [s] = 'on' .. 'off'
[powerport] [s] [powerport] = 'Port 1' .. 'Port 99' (or Config:portname) [s] = batchmode, toggled, Coldstart
Temperature state: [val] [val] = 'over the MAX limit', 'under the MIN limit'
Account credit: [x]
Page 30
30
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
2.4.2
Voice Call
2.4.2.1
Menu
For operating with VoiceCall, simply call the phone number of the SIM card of the GSM module. When connection is established the device replies with the announcement: "Main menu" and a DTMF tone In the menu the navigation works via DTMF commands.
Each command starts with # and ends with *.
Numbers
Men
*1#
Power Port
*2#
Input Port
*8#
Status
You can combine multiple commands into a command. Just type the commands one after another and terminate it as a whole with #.
*[Command 1][Command 2]...[Command n]#
Some commands may require the Port or MasterCode. These codes have to be added at end of the command
Eample:
Navigate from Main Menu into the Status Menu using mastercode 1111
*8# - enter Status Menu 1111 - Mastercode
For the navigation in menus the following commands are required:
*99# - Jump to Main Menu *98# - Return to prev Menu *97# - Help
Page 31
31
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
2.4.2.1.1 Power Port Menu
Here you can choose and switch Power Ports or request the status of a Power Port.
Example:
*1# - Switch to Power Port menu
*5# - Choose Power Port 5
*01# - Switch on
Or connected into one command: *1501#
Example:
Page 32
32
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
*7# - Choose Power Port 7
*23# - Activate Batchmode No.23 for Power Port 7 - Powerport 7 on, wait t3, off
Example:
*3# - Choose Power Port 3
*03# - Request state of Power Port 4
Or as one command: *303#
Please check the Power Port commands [pc] for further information
2.4.2.1.2 Status Menu
Different states of the device can be requested
*00#
Value of the account of the PrePaid card
*01#
Request of an SMS with all power port information, announcement "SMS sent"
*03#
Request of an SMS with configuration information, announcement "SMS sent"
*04#
Request of actual sensor information (a sensor has to be connected)
*10#
Request of the state of all Power Ports
2.4.2.1.3 Parameter Description
[pn] Power-Port Nummer
- Values: '1' .. '9'
[ps]
- Power-Port State
- Values: '0' .. '1' (on/off)
[pc]
- Power-Port Command
- Values: '00' .. '89'
[in]
- Input-Port Number
- Values: '1' .. '9'
[is]
- Input-Port State
- Values: '0' .. '1' (on/off)
[sq]
- Status Query
- Values '01' .. '89'
Special Menu Commands (90 .. 00)
- 99 : Jump to Main Menu
- 98 : return to prev Menu
Page 33
33
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
2.4.3
Power Port Commands
List of possible Power Port commands (pc)
Port Com­mand
Command
Description
00
off
Switch off
01onSwitch on
02
toggle
Toggle
03
state info
Request of state of Power Port
04
reset
Switch off, wait 30 seconds, switch on
Port Com­mand
Command
Description
11
Batchmode: off, wait t1, on
Powerport off, wait t1, Power Port on
12
Batchmode: off, wait t2, on
Powerport off, wait t2, Power Port on
13
Batchmode: off, wait t3, on
Powerport off, wait t3, Power Port on
14
Batchmode: off, wait t4, on
Powerport off, wait t4, Power Port on
15
Batchmode: off, wait t5, on
Powerport off, wait t5, Power Port on
16
Batchmode: off, wait t6, on
Powerport off, wait t6, Power Port on
17
Batchmode: off, wait t7, on
Powerport off, wait t7, Power Port on
18
Batchmode: off, wait t8, on
Powerport off, wait t8, Power Port on
19
Batchmode: off, wait t9, on
Powerport off, wait t9, Power Port on
Page 34
34
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
Port Com­mand
Command
Description
21
Batchmode: on, wait t1, off
Powerport on, wait t1, Power Port off
22
Batchmode: on, wait t2, off
Powerport on, wait t2, Power Port off
23
Batchmode: on, wait t3, off
Powerport on, wait t3, Power Port off
24
Batchmode: on, wait t4, off
Powerport on, wait t4, Power Port off
25
Batchmode: on, wait t5, off
Powerport on, wait t5, Power Port off
26
Batchmode: on, wait t6, off
Powerport on, wait t6, Power Port off
27
Batchmode: on, wait t7, off
Powerport on, wait t7, Power Port off
28
Batchmode: on, wait t8, off
Powerport on, wait t8, Power Port off
29
Batchmode: on, wait t9, off
Powerport on, wait t9, Power Port off
Port Com­mand
Command
Description
31
Batchmode: toggle, wait t1, toggle
Power Port toggle, wait t1, Power Port toggle
32
Batchmode: toggle, wait t2, toggle
Power Port toggle, wait t2, Power Port toggle
33
Batchmode: toggle, wait t3, toggle
Power Port toggle, wait t3, Power Port toggle
34
Batchmode: toggle, wait t4, toggle
Power Port toggle, wait t4, Power Port toggle
35
Batchmode: toggle, wait t5, toggle
Power Port toggle, wait t5, Power Port toggle
36
Batchmode: toggle, wait t6, toggle
Power Port toggle, wait t6, Power Port toggle
37
Batchmode: toggle, wait t7,toggle
Power Port toggle, wait t7, Power Port toggle
38
Batchmode: toggle, wait t8, toggle
Power Port toggle, wait t8, Power Port toggle
39
Batchmode: toggle, wait t9, toggle
Power Port toggle, wait t91, Power Port toggle
Page 35
35
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Operating
tn
Time in seconds
t11t22t35t410t520t660t7
120t8240t9480
2.4.4
Security
Please note that the device has no security options set in the delivery settings, in order to allow a quick start. For a later use we strongly recommend that you activate the phone book check and code queries. The phone book check provides pretty high se­curity, because only phone book members can operate the device. Unfortunately, there are mobile carriers that allow to simulate any number with some technical effort. These numbers will be marked with a special bit and can only be identified by the police as forged. Unfortunately the GSM network has no possibility to identify this fake numbers. For this reason we recommend the code query.
Access
Phonebook
Check
Port/Maste
rCode
Security
Anybody
off
off
Very low
Phonebook Check
on
off
Normal
Code Check
offonHigh
Phonebook and Code Check
on
on
Very high
Page 36
Configuration
Page 37
37
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
3 Configuration
TCP/IP configuration by DHCP
After switching on the device is scanning on the Ethernet for a DHCP server and re­quests an unused IP address. Check the IP address that has been assigned and ad­just if necessary, that the same IP address is used at each restart. To turn off DHCP use the software GBL_Conf.exe or use the configuration via the web interface.
To check the network settings with GBL_Conf.exe, start the program and choose "All Devices" in the "Search" menu. From the list select the appropriate device. The lower part of the left half of the window now shows the current network settings of the device. If the IP address is displayed with the default settings (192.168.0.2), either no DHCP server is present on the network, or there could be no free IP address assigned to it.
3.1 Power Ports
Choose Power Port to configure: This field is used to select the power ports to be con­figured.
Label: You can assign a name up to 15 characters for each of the power ports. Using the name, an identification of the the device connected to the port can be facilitated.
Start-up Monitoring
It is important, that if necessary the condition of the power ports can be restored after a power failure. Therefore each port can be configured with Initialization status to a spe­cific start-up state. This start-up sequence can be carried out delayed by the parameter Initialization Delay. There is in any case a minimum one-second delay between switch­ing of ports.
Initialization status(coldstart): This is the port state (on, off, remember last state) the port should be set when the device is turned on. The setting "remember last state" saves the last manually set state of the power port in the EEPROM.
Page 38
38
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
Initialization delay: Here can be configured how long the port should wait to switch to its defined state after the device is turned on. The delay may last up to 8191 seconds. This corresponds to a period of approx. two hours and 20 minutes. A value of zero means that the initialization is off.
GSM Portcode (only EPC 1292): Sets the individual port access code.
Repower delay: When this feature is enabled (value greater than 0), the power port will switch itself on again a specified time after it has been disabled. Unlike the "Reset" but­ton this function applies to all switch actions, including SNMP, or an optional serial in­terface.
Reset Duration: When the "Reset" button is triggered, the device turns the power port off, waits for the time entered here (in seconds) and turns the power port on.
3.1.1
Watchdog
The watchdog feature enables to monitor various remote devices. Therefore either ICMP pings or TCP pings are sent to the device to be monitored. If these pings are not answered within a certain time (both the time and the number of attempts can be set), the port is reset. This allows e.g. to automatically restart not responding server or NAS systems. The mode IP master-slave port allows you to switch a port depending on the availability of a remote device.
When a watchdog is activated it presents various information in the Control Panel. The information is color-coded.
· Green text: The watchdog is active and regularly receives ping replies.
· Orange text: The watchdog is currently enabled, and waits for the first Ping re-
sponse.
· Red text: The watchdog is active and receives no ping replies anymore from the con­figured IP address.
After the watchdog has been enabled, the display remains orange until the watchdog receives a ping response for the first time. Only then the watchdog is activated. Even after triggering a watchdog and a subsequent power port reset, the display will remain orange until the device is rebooted and responds again to ping requests. This will pre­vent a premature watchdog reset of the port, e.g. when a server needs a long time for a file check.
You can monitor devices on your own network, as well as devices on an external net­work, e.g. the operating status of a router.
Page 39
39
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
Enable watchdog: Enables the watchdog function for this Power Port.
Watchdog type: Here you can choose between the monitoring by ICMP pings or TCP pings.
· ICMP Pings: The classic ping (ICMP echo request). It can be used to check the ac­cessibility of network devices (for example, a server).
· TCP Pings: With TCP pings, you can check if a TCP port on the target device would accept a TCP connect. Therefore a non-blocked TCP port should be selected. A good choice would be port 80 for http or port 25 for SMTP.
TCP port: Enter the TCP port to be monitored. When using ICMP pings this is not needed.
Hostname: The name or IP address of the monitored network device.
Ping interval: Select the frequency (in seconds) at which the ping packet is sent to each network device to check its operating status.
Ping retries: After this number of consecutive unanswered ping requests the device is considered inactive.
Watchdog mode: When Reset port when host down is enabled, the Power Port is turned off and switched back on after the time set in Reset Duration. In mode Switch off once when host down the Power Port remains disabled.
At the default setting (Infinite wait for booting host after reset) the watchdog monitors the connected device. When there is no longer a reply after a set time, the watchdog performs the specified action, usually a reset of the Power Port. Now the watchdog waits until the monitored device reports again on the network. This may take several minutes depending on the boot duration of the device. Only when the device is access­ible from network again, the watchdog is re-armed. If the option Repeat reset on boot­ing host after x ping timeout is enabled, this mechanism is bypassed. Now the watch­dog is re-activated after N Ping intervals (input field ping timeouts).
When enabling the IP master-slave mode, the port is switched depending on the avail­ability of a remote device. Depending on the configuration, the port is switched on when the terminal is reachable, or vice versa.
The option Repeat reset on booting host after x ping timeout has the following pit­fall: If a server, that is connected to the monitored Port is in need for a long boot pro­cess (e.g. it is doing a file system check), the server would probably exceed the trip­ping time of the watchdog. The server would be switched off and on again, and the file system check is restarted. This would be repeated endlessly.
3.2 Ethernet
Page 40
40
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
3.2.1
IP Address
Hostname: Here you can enter a name with up to 63 characters. This name will be used for registration on the DHCP server.
Special characters and umlauts can cause problems in the network.
IPv4 Address: The IP address of the device.
IPv4 Netmask: The network mask used in the network.
IPv4 Gateway address: The IP address of the gateway.
IPv4 DNS address: The IP address of the DNS server.
Use IPv4 DHCP: Select "yes" if the TCP/IP settings should be obtained directly from the DHCP server: When the function is selected, each time the device powers up it is checked if a DHCP server is available on the network. If not, the last used TCP/IP set­ting will be used further.
Use IPv6 Protocol: Activates IPv6 usage.
Use IPv6 Router Advertisement: The Router Advertisement communicates with the router to make global IPv6 addresses available.
Use DHCP v6: Requests from an existing DHCPv6 server addresses of the configured DNS server.
Use manual IPv6 address settings: Activates the entry of manual IPv6 addresses.
IPv6 status: Displays the IPv6 addresses over which the device can be accessed, and additionally DNS and router addresses.
Page 41
41
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
For IP changes a firmware reset is required. This can be done in the Maintenance web page. A restart of the device leads by no means to a change of the relay states.
Manual IPv6 Configuration
The input fields for the manual setting of IPv6 addresses allow you to configure the prefix of four additional IPv6 device addresses, and to set two DNS addresses, and a gateway.
3.2.2
IP ACL
Reply ICMP ping requests: If you enable this feature, the device responds to ICMP pings from the network.
Page 42
42
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
Enable IP filter: Enable or disable the IP filter here. The IP filter represents an access control for incoming IP packets.
Please note that when IP access control is enabled HTTP and SNMP only work if the appropriate servers and clients are registered in the IP access control list.
If you choose a wrong IP ACL setting and locked yourself out, please activate the Bootloader Mode and use GBL_Conf.exe to deactivate the IP ACL. Alternatively, you can reset the device to factory default.
3.2.3
HTTP
HTTP Server option: Selects whether access is possible only with HTTP, HTTPS, or both.
Server port HTTP: Here can be set the port number of the internal HTTP. Possible val­ues ??are from 1 to 65534 (default: 80). If you do not use the default port, you must ap­pend the port number to the address with a colon to address the device from a web browser. Such as: "http://192.168.0.2:800"
Server port HTTPS; The port number to connect the web server via the SSL (TLS) pro­tocol.
Enable Ajax autorefresh: If this is activated, the information of the status page is auto­matically updated via http request (AJAX).
For some HTTP configuration changes a firmware reset is required. This can be done in the Maintenance web page. A restart of the device leads by no means to a change of the relay states.
Enable password protection: Password access protection can be activated. If the ad­min password is assigned, you can only log in by entering this password to change set­tings. Users can log in by entering the user password in order to query the status in­formation and initiate switching operations.
Page 43
43
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
Use radius server passwords: Username and password are validated by a Radius Sever.
Use locally stored passwords: Username and password are stored locally. In this case, an admin password and a user password must be assigned. The password can have a maximum of 31 characters. The name "admin" and "user" are provided for the user name in the password entry mask of the browser. In factory settings, the password for the admin is set to "admin" or "user" for the user password.
If the password mask is redisplayed, only four "bullets" are shown as a symbolic placeholder, since for security reasons the device never stores the password itself, but only the SHA2-256 hash. If you want to change a password, the complete password must always be re-entered.
If you have forgotten your password, please activate the bootloader mode and then turn off the password prompt in GBL_Conf.exe.
3.3 Protocols
3.3.1
Console
Enable Telnet: Enables Telnet console .
Telnet TCP port: Telnet sessions are accepted on this port.
Raw mode: The VT100 editing and the IAC protocol are disabled.
Activate echo: The echo setting if not changed by IAC.
Active negotiation: The IAC negotiation is initiated by the server.
Require user login: Username and password are required.
Delay after 3 failed logins: After 3 wrong entries of username or password, the next lo­gin attempt is delayed.
Page 44
44
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
Use radius server passwords: Username and password are validated by a Radius Sever.
Use locally stored passwords: Username and password are stored locally
3.3.2
Syslog
Enable Syslog: Enables the usage of Syslog Messages.
Syslog Server: If you have enabled Syslog Messages, enter the IP address of the server to which the syslog information should be transmitted.
3.3.3
SNMP
SNMP-get: Enables the acceptance of SNMP-GET commands.
Page 45
45
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
SNMP-set: Allows the reception of SNMP-SET commands.
SNMP UDP Port: Sets the UDP port where SNMP messages are received.
Enable SNMP v2: Activates SNMP v2.
Because of security issues, it is advisable to use only SNMP v3, and to disable SNMP v2. Accesses to SNMP v2 are always insecure.
Community public: The community password for SNMP GET requests.
Community private: The community password for SNMP SET requests.
Enable SNMP v3: Activates SNMP v3.
SNMP v3 Username: The SNMP v3 User Name.
SNMP v3 Authorization Algorithm: The selected Authentication Algorithm.
SNMP v3 Privacy Algorithm: SNMP v3 Encryption Algorithm..
If the password mask is redisplayed, only four "bullets" are shown as a symbolic placeholder, since for security reasons the device never stores the password itself, but only the key formed using the Authorization Algorithm. If you want to change a pass­word, the complete password must always be re-entered.
The calculation of the password hashes varies with the selected algorithms. If the Authentication or Privacy algorithms are changed, the passwords must be re-entered in the configuration dialog. "SHA-384" and "SHA512" are calculated purely in software. If "SHA-512" is set on the configuration page, the time for the key generation may take once up to approx. 45 seconds.
Send SNMP traps: Here you can specify whether, and in what format the device should send SNMP traps.
SNMP trap receiver: You can insert here up to eight SNMP trap receiver.
MIB table: The download link to the text file with the MIB table for the device.
More information about SNMP settings are available from our support or can be found on the Internet at www.gude.info/wiki.
Page 46
46
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
3.3.4
Radius
Enable Radius Client: Enables validation over Radius.
Use CHAP: Use CHAP password encoding.
Use Message Authentication: Adds the "Message Authentication" attribute to the Authentication Request.
Primary Server: Name or IP address of the Primary Radius server.
Shared secret: Radius Shared Secret.
Timeout: How long (in seconds) will be waited for a response from an Authentication Request.
Retries: How often an authentication request is repeated after a timeout.
Use Backup Server: Activates a Radius Backup server.
Backup Server: Name or IP address of the Radius Backup server.
Shared secret: Radius Shared Secret.
Timeout: How long (in seconds) will be waited for a response from an Authentication Request.
Retries: How often an authentication request is repeated after a timeout.
Page 47
47
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
Test Username: Username input field for Radius test.
Test Password: Password input field for Radius test.
The "Test Radius Server" function allows you to check whether a combination of User­name and Password is accepted by the configured Radius Servers.
3.3.5
Modbus TCP
Enable Modbus TCP: Enables Modbus TCP support.
Modus TCP port: The TCP/IP port number for Modbus TCP.
Page 48
48
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
3.4 Sensors
Sensor: Selects a type of sensor to configure it. The first digit "1" indicates the number of the sensor port (only important for devices with more than one sensor port). This is followed by the sensor name, and the changeable sensor name.
Sensor Name: Changeable name for this sensor. Temperature and humidity can have different names, even if they are from the same sensor.
Select Sensor Field: Selects a data channel from a sensor.
Enable ... Messages: Enables the generation of sensor messages.
Maximum/Minimum value: Here you can choose whether, and at what Maximum/Min­imum temperature or humidity measurements limits the alerts are send via SNMP traps, syslog or e-mail.
Hysteresis: This describes the margin of when an event is generated after the meas­ured value has crossed the chosen limit.
Message channels: Enables the generation of messages on different channels. If you activate SMS messages, several recipients can be selected from the phonebook (only
EPC 1292). On this example screenshot the recipients "Paul" and "Mary" are enabled,
SMS sending for "Peter" is disabled.
Min/Max measurement period: Selects the time range for the sensor min/max values on the overview web page.
Page 49
49
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
Hysteresis Example:
A Hysteresis value prevents that too much messages are generated, when a sensor value is jittering around a sensor limit. The following example shows the behavior for a temperature sensor and a hysteresis value of "1". An upper limit of "50 °C" is set.
Example:
49.9 °C - is below the upper limit
50.0 °C - a message is generated for reaching the upper limit
50.1 °C - is above the upper limit ...
49.1 °C - is below the upper limit, but in the hysteresis range
49.0 °C - is below the upper limit, but in the hysteresis range
48.9 °C - a message is generated for underrunning the upper limit inclusive hysteresis range ...
3.4.1
Port Switching
Depending on the measured Current and the measured sensor values, switching ac­tions can be triggered. During operation, the actions configured for crossing the limits are executed. For example, when a value moves from the range "above max value" in­side the range "below max value", the action defined for "below max value" is per­formed. In the case of device start, configuration or plug-in of the sensor, the actions corresponding to the range in which the current temperature is located are switched.
Example with "Maximum value" of 65 °C, "Minimum value" of 25 °C and hysteresis of 3 °C. The dotted line shows the hysteresis.
Page 50
50
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
Actions during configuration, device start or plugging in the sensor (for given example):
actual temperature
during configuration
actions
70 °C
Port 1 Off (above max) + Port 2 On (above min)
45 °C
Port 1 On (below max) + Port 2 On (above min)
20 °C
Port 1 On (below max) + Port 2 Off (below min)
Action matrix during operation when limit values are exceeded (for given example):
to "above max"
to "below max"
to "above min"
to "below min"
from "above max"
-
P1 On
P1 On
P1 On + P2 Off
from "below max"
P1 Off--
P2 Off
from "above min"
P1 Off--
P2 Off
from "below min"
P1 Off + P2 On
P2 On
P2 On
-
Only the switching operations for which actions have been defined, are triggered. If no "On" or "Off" action is defined for a port, the port can never reach this state by ex­ceeding sensor values. Unless it is the initial state.
3.5 E-Mail
Enable E-Mail: Activates the e-mail dispatch of messages.
Sender address: The e-mail address of the sender.
Page 51
51
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
Recipient address: The e-mail address of the recipient. Additional email addresses, separated by comma, can be specified. The input limit is 100 characters.
SMTP Server: The SMTP IP-address of the e-mail server. Either as FQDN, e.g: "mail.gmx.net", or as IP-address, e.g: "213.165.64.20". If required, attach a designated port, e.g: "mail.gmx.net:25".
SMTP server port: The port address of the e-mail server. In the normal case this should be the same as the default, that is determined by the setting SMTP Connection Security.
SMTP Connection Security: Transmission via SSL or no encryption.
SMTP Authentification (password): Authentication method of the E-Mail Server.
Username: User name that is registered with the SMTP E-Mail server.
Set new password: Enter the password for the login to the e-mail server.
Repeat password: Enter the password again to confirm it.
If the password mask is redisplayed, only four "bullets" are shown as a symbolic placeholder, since for security reasons the password is never shown itself. If you want to change a password, the complete password must always be re-entered.
E-Mail Logs: Logging of E-Mail system messages.
3.6 Front Panel
Button Lock: Disables the front buttons (activates the key lock) with the exception of the bootloader activation.
Dark Display: The 7-segment display remains dark. Front button activity temporarily switches the display on.
Default Display: Selects what sensor is displayed in the display.
3.7 GSM
Page 52
52
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
3.7.1
GSM General
Enable GSM: Activates the built-in GSM module
SIM PIN: Switches the PIN request of the SIM card on. A wrong Pin leads to a blocking of the SIM card. You cannot change the PIN of the SIM card via this menu option.
My phone number: Please enter here the phone number of the inserted SIM card
Admin SMS number: All device changes are sent via SMS to this mobile number.
Enable admin GSM status information: When active, all GSM status changes are sent via SMS to the Admin.
Enable admin GSM E-mail: When active, all GSM status changes are sent via email to the Admin. The e-mails are sent via the SMS to email gateway.
Admin E-mail: Email address to which the GSM messages are sent.
Enable DTMF/SMS access codes: When activated, the Mastercode or Portcode is needed to switch a port.
Master code: Sets the GSM Mastercode.
Page 53
53
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
3.7.2
GSM Misc
Enable phonebook check: If selected, only numbers registered to the phonebook can access the GSM module. All other numbers are ignored.
Enable freecall: When active, without accumulating phone charges, the functions as­signed to a dialed number can be triggered.
Enable GSM for admin only: If enabled, the GSM functions can only be used when ac­tivated from the entered GSM Admin number.
Enable SMS response: When activated, every command SMS is acknowledged from an answer SMS.
Enable SMS errors/warning: Enables the sending of an error SMS when a defective command SMS was received.
Enable coverage messages: Sends status messages, when the signal quality is chan­ging.
Enable port name indication: If selected, the complete portname is sent via SMS. E.g., instead of "Port 1" the name "server 1. floor". This can lead to longer SMS with higher costs.
Enable autosync SMS: When this options is enabled, the EPC tries to request date and time information from the GSM network after power-up.
Enablevoice in voice call: If enabled, you hear voice samples when a call is coming in (Voicecall).
machine-to-machine DTMF tones: Enables DTMF tones in voice steering.
Page 54
54
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
3.7.3
GSM Phonebook
The phonebook can be used to store telephone numbers under a name. When the phonebook is activated only stored numbers can access the device.
Furthermore, the "FreeCall" option can be assigned to every number in the phone book. If this number is recognized, a preselected action is executed without accepting the call.
An active "FreeCall" number cannot activate other functions via "Voicecall". If you want to use the voice menu with a "FreeCall" number, you have to suppress the phone num­ber.
3.7.4
GSM SIM Card
To enter a new SIM card, please press the button "Change GSM SIM-card".
3.7.5
GSM Provider
This menu only appears when you insert a SIM card from a phone company that oper­ates outside of Germany. To receive necessary information, contact your wireless ser­vice provider.
IMSI: Your IMSI number.
Page 55
55
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Configuration
The International Mobile Subscriber Identity (IMSI) is used in GSM and UMTS mobile networks to uniquely identify network nodes (internal subscriber identity). Among other data, the IMSI is stored in a special smart card, the so-called SIM (Subscriber Identity Module). A worldwide unique IMSI number is awarded every customer of a mobile net­work. While the IMSI has nothing to do with the telephone number that is assigned to the SIM card.
SMS to Email Gateway: The number of the SMS to email gateway for your network provider.
Balance request code: Please enter the word that names the prepaid balance: e.g. "balance", "conto", "balances".
You will find this word in the news of your provider when you query your prepaid bal­ance. The correct spelling is important to help the device recognizing whether the cur­rent balance is communicated in a message.
Balance parsing string: Enter the query that you send to your provider to access your prepaid balance: E.g. *101#
Page 56
Specifications
Page 57
57
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
4 Specifications
4.1 IP ACL
IP Access Control List
The IP Access Control List (ACL IP) is a filter for incoming IP packets. If the filter is active, only the hosts and subnets whose IP addresses are registered in the list, can contact via HTTP or SNMP, and make changes. For incoming connections from unau­thorized PCs, the device is not completely transparent. Due to technical restraints, a TCP/IP connection will be accepted at first, but then rejected directly.
Examples:
Entry in the IP ACL
Meaning
192.168.0.123
the PC with IP Address "192.168.0.123" can access the device
192.168.0.1/24
all devices of subnet "192.168.0.1/24" can access the device
1234:4ef0:eec1:0::/64
all devices of subnet "1234:4ef0:eec1:0::/64" can access the device
If you choose a wrong IP ACL setting and locked yourself out, please activate the Bootloader Mode and use GBL_Conf.exe to deactivate the IP ACL. Alternatively, you can reset the device to factory default.
4.2 IPv6
IPv6 Addresses
IPv6 addresses are 128 bit long and thus four times as long as IPv4 addresses. The first 64 bit form a so-called prefix, the last 64 bit designate a unique interface identifier. The prefix is composed of a routing prefix and a subnet ID. An IPv6 network interface can be reached under several IP addresses. Usually this is the case under a global ad­dress and the link local address.
Address Notation
IPv6 addresses are noted in 8 hexadecimal blocks at 16 bit, while IPv4 normally is noted in decimal. The seperator is a colon, not a period.
E.g.: 1234:4ef0:0:0:0019:32ff:fe00:0124
Leading zeros may be omitted within a block. The previous example can be rewritten as:
1234:4ef0:0:0:19:32ff:fe00:124
One may omit one or more successive blocks, if they consist of zeros. This may be done only once within an IPv6 address!
1234:4ef0::19:32ff:fe00:124
Page 58
58
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
One may use the usual decimal notation of IPv4 for the last 4 bytes:
1234:4ef0::19:32ff:254.0.1.36
4.3 Radius
The passwords for HTTP, telnet, and serial console (depending on the model) can be stored locally and / or authenticated via RADIUS. The RADIUS configuration supports a primary server and a backup server. If the primary server does respond, the RADIUS request is sent to the backup server. If the local password and RADIUS are enabled at the same time, the system is first checking locally, and then in the event of a failure the RADIUS servers are contacted.
RADIUS attributes
The following RADIUS attributes are evaluated by the client:
Session-Timeout: This attribute specifies (in seconds) how long an accepted RADIUS request is valid. After this time has elapsed, the RADIUS server must be prompted again. If this attribute is not returned, the default timeout entry from the configuration is used instead. Filter-Id: If the value "admin" is set for this attribute, then an admin rights are assigned for the login, otherwise only user access. Service-Type: This is an alternative to Filter-Id. A service type of "6" or "7" means ad­min rights for the HTTP login, otherwise only limited user access.
HTTP Login
The HTTP login takes place via Basic Authentication. This means that it is the respons­ibility of the web server, how long the login credentials are temporarily stored there. The RADIUS parameter "Session-Timeout" therefore does not determine when the user has to login again, but at what intervals the RADIUS servers are asked again.
4.4 Automated Access
The device can be accessed automatically via four different interfaces, which offer dif­ferent possibilities to access the configuration data and status information. Only http and the console (telnet and serial) provide full access to the device.
List of different access options (if supported by the model):
Interface
Scope of Access
HTTP
read / write all configuration data read / write all status information
Console
read / write all configuration data read / write all status information
SNMP
read / write status of Power Ports (relays) read / write names of Power Ports (relays) read / write status of Port start configuration read / write status Buzzer
67
59
Page 59
59
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
read measurement values of external sensors read measurement values of all energy sensors resetting the energy meters read the status of Overvoltage Protection
Modbus TCP
read / write status of Power Ports (relays) read status of Inputs read measurement values of external sensors read measurement values of all energy sensors
The device can be controlled via HTTP interface with CGI commands and returns the internal configuration and status in JSON format. The structure of the CGI commands and the JSON data is explained in more detail in our Wiki article:
http://wiki.gude.info/EPC_HTTP_Interface
4.5 SNMP
SNMP can be used for status information via UDP (port 161). Supported SNMP com­mands are:
· GET
· GETNEXT
· GETBULK
· SET
To query via SNMP you need a Network Management System, such as HP OpenView, OpenNMS, Nagios etc., or the simple command line tools of NET-SNMP software. The device supports SNMP protocols v1, v2c and v3. If traps are enabled in the configura­tion, the device messages are sent as notifications (traps). SNMP Informs are not sup­ported. SNMP Requests are answered with the same version with which they were sent. The version of the sent traps can be set in the configuration.
MIB Tables
The values that can be requested or changed by the device, the so-called "Managed Objects", are described in Management Information Bases (MIBs). These substruc­tures are subordinate to so-called "OID" (Object Identifiers). An OID digit signifies the location of a value inside a MIB structure. Alternatively, each OID can be referred to with its symbol name (subtree name). The device's MIB table can be displayed as a text file by clicking on the link "MIB table" on the SNMP configuration page in the browser.
SNMP v1 and v2c
SNMP v1 and v2c authenticates the network requests by so-called communities. The SNMP request has to send along the so-called community public for queries (read ac­cess) and the community private for status changes (write access) . The SNMP communities are read and write passwords. In SNMP v1 and v2 the communities are transmitted unencrypted on the network and can be easily intercepted with IP sniffers within this collision domain. To enforce limited access we recommend the use of DMZ or IP-ACL.
SNMP v3
Because the device has no multiuser management, only one user (default name
82
Page 60
60
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
"standard") is detected in SNMP v3. From the User-based Security Model (USM) MIB variables, there is a support of "usmStats ..." counter. The "usmUser ..." variables will be added with the enhancement of additional users in later firmware versions. The sys­tem has only one context. The system accepts the context "normal" or an empty con­text.
Authentication
The algorithms "HMAC-MD5-96" and "HMAC-SHA-96" are available for authentication. In addition, the "HMAC-SHA-2" variants (RFC7630) "SHA-256", "SHA-384" and "SHA­512" are implemented.
"SHA-384" and "SHA512" are calculated purely in software. If "SHA-384" or "SHA-
512" is set on the configuration page, the time for the key generation may take once up to approx. 45 seconds.
Encryption
The methods "DES", "3DES", "AES-128", "AES-192" and "AES-256" are supported in combination with "HMAC-MD5-96" and "HMAC-SHA-96." For the "HMAC-SHA-2" pro­tocols, there is currently neither RFC nor draft that will allow for cooperation with an en­cryption.
While in the settings "AES-192" and "AES256" the key calculation is based on "draft-blumenthalphoto-aes-usm-04", the methods "AES 192-3DESKey" and "AES 256-3DESKey" utilize a key generation, which is also used in the "3DES" configuration ("draft-reeder-snmpv3-usm-3desede-00"). If one is not an SNMP expert, it is recom­mended to try in each case the settings with and without "...- 3DESKey".
Passwords
The passwords for authentication and encryption are stored only as computed hashes for security reasons. Thus it is, if at all, very difficult to infer the initial password. However, the hash calculation changes with the set algorithms. If the authentication or privacy algorithms are changed, the passwords must be re-entered in the configuration dialog.
Security
The following aspects should be considered:
· If encryption or authentication is used, then SNMP v1 and v2c should be turned off.
Otherwise the device could be accessed with it.
· If only authentication is used, then the new "HMAC-SHA-2" methods are superior to
the MD5 or SHA-1 hashing algorithms. Since only SHA-256 is accelerated in hard­ware, and SHA-384 and SHA-512 are calculated purely in software, one should nor­mally select SHA-256. From a cryptographic point of view, the security of SHA-256 is sufficient for today's usage.
· For SHA-1, there are a little less attack scenarios than MD5. If in doubt, SHA-1 is
preferable.
· Encryption "DES" is considered very unsafe, use only in an emergency for reasons
of compatibility!
· For cryptologists it's a debatable point whether "HMAC-MD5-96" and "HMAC-SHA-
96" can muster enough entropy for key lengths of "AES-192" or "AES-256".
· From the foregoing considerations, we would recommended at present "HMAC-
SHA-96" with "AES-128" as authentication and encryption method.
Change in Trap Design
Page 61
61
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
In older MIB tables, a separate trap was defined for each combination of an event
and a port number. This results in longer lists of trap definitions for the devices. For ex­ample, from epc8221SwitchEvtPort1 to epc8221SwitchEvtPort12. Since new firm­ware versions can generate many more different events, this behavior quickly pro­duces several hundred trap definitions. To limit this overabundance of trap definitions, the trap design has been changed to create only one specific trap for each event type. The port or sensor number is now available in the trap as an index OID within the vari­able bindings.
In order to recognize this change directly, the "Notification" area in the MIB table has been moved from sysObjectID.0 to sysObjectID.3. This way, unidentified events are generated until the new MIB table is imported. For compatibility reasons, SNMP v1 traps are created in the same way as before.
NET-SNMP
NET-SNMP provides a very widespread collection of SNMP command-line tools (snm­pget, snmpset, snmpwalk etc.) NET-SNMP is among others available for Linux and Windows. After installing NET-SNMP you should create the device-specific MIB of the device in NET-SMP share directory, e.g. after
c:\usr\share\snmp\mibs
or
/usr/share/snmp/mibs
So later you can use the 'subtree names' instead of OIDs:
Name: snmpwalk -v2c -mALL -c public 192.168.1.232 gudeads OID: snmpwalk -v2c -mALL -c public 192.168.1.232 1.3.6.1.4.1.28507
NET-SNMP Examples
Query Power Port 1 switching state:
snmpget -v2c -mALL -c public 192.168.1.232 epc822XPortState.1
Switch on Power Port 1:
snmpset -v2c -mALL -c private 192.168.1.232 epc822XPortState.1 integer 1
4.5.1
Device MIB 1202
Below is a table of all device-specific OID 's which can be accessed via SNMP. In the numerical representation of the OID the prefix " 1.3.6.1.4.1.28507 " (Gude Enterprise OID) was omitted at each entry in the table to preserve space. The example for a com­plete OID would be "1.3.6.1.4.1.28507.43.1.1.1.1". A distinction is made in SNMP OID 's in between tables and scalars. OID scalar have the extension ".0" and only specify a value. In SNMP tables the "x" is replaced by an index (1 or greater) to address a value from the table.
Name
OID
Type
Acc.
Description
epc1202TrapCtrl
.43.1.1.1.1.0
Integer32
RW
0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3
epc1202TrapIPIndex
.43.1.1.1.2.1.1.x
Integer32
RO
Page 62
62
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
A unique value, greater than zero, for each receiver slot.
epc1202TrapAddr
.43.1.1.1.2.1.2.x
OCTETS
RW
DNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot.
epc1202portNumber
.43.1.3.1.1.0
Integer32
RO
The number of Relay Ports
epc1202PortIndex
.43.1.3.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each Relay Port.
epc1202PortName
.43.1.3.1.2.1.2.x
OCTETS
RW
A textual string containing name of a Relay Port.
epc1202PortState
.43.1.3.1.2.1.3.x
INTEGER
RW
current state of a Relay Port
epc1202PortSwitchCount
.43.1.3.1.2.1.4.x
Integer32
RO
The total number of switch actions ocurred on a Relay Port. Does not count switch commands which will not switch the ralay state, so just real relay switches are displayed here.
epc1202PortStartupMode
.43.1.3.1.2.1.5.x
INTEGER
RW
set Mode of startup sequence (off, on , remember last state)
epc1202PortStartupDelay
.43.1.3.1.2.1.6.x
Integer32
RW
Delay in sec for startup action
epc1202PortRepowerTime
.43.1.3.1.2.1.7.x
Integer32
RW
Delay in sec for repower port after switching off
epc1202ActivePowerChan
.43.1.5.1.1.0
Unsigned32
RO
Number of suppported Power Channels.
epc1202PowerIndex
.43.1.5.1.2.1.1.x
Integer32
RO
Index of Power Channel entries
epc1202ChanStatus
.43.1.5.1.2.1.2.x
Integer32
RO
0 = data not active, 1 = data valid
epc1202AbsEnergyActive
.43.1.5.1.2.1.3.x
Gauge32
RO
Absolute Active Energy counter.
epc1202PowerActive
.43.1.5.1.2.1.4.x
Integer32
RO
Active Power
epc1202Current
.43.1.5.1.2.1.5.x
Gauge32
RO
Actual Curent on Power Channel.
epc1202Voltage
.43.1.5.1.2.1.6.x
Gauge32
RO
Actual Voltage on Power Channel
epc1202Frequency
.43.1.5.1.2.1.7.x
Gauge32
RO
Frequency of Power Channel
epc1202PowerFactor
.43.1.5.1.2.1.8.x
Integer32
RO
Power Factor of Channel between -1.0 and 1.00
epc1202Pangle
.43.1.5.1.2.1.9.x
Integer32
RO
Phase Angle between Voltage and L Line Current between -180.0 and
180.0
epc1202PowerApparent
.43.1.5.1.2.1.10.x
Integer32
RO
L Line Mean Apparent Power
epc1202PowerReactive
.43.1.5.1.2.1.11.x
Integer32
RO
L Line Mean Reactive Power
epc1202AbsEnergyReactive
.43.1.5.1.2.1.12.x
Gauge32
RO
Absolute Reactive Energy counter.
epc1202AbsEnergyActiveReset­table
.43.1.5.1.2.1.13.x
Gauge32
RW
Resettable Absolute Active Energy counter. Writing '0' resets all reset­table counter.
epc1202AbsEnergyReactiveReset­table
.43.1.5.1.2.1.14.x
Gauge32
RO
Resettable Absolute Reactive Energy counter.
epc1202ResetTime
.43.1.5.1.2.1.15.x
Gauge32
RO
Time in seconds since last Energy Counter reset.
epc1202ForwEnergyActive
.43.1.5.1.2.1.16.x
Gauge32
RO
Forward Active Energy counter.
epc1202ForwEnergyReactive
.43.1.5.1.2.1.17.x
Gauge32
RO
Forward Reactive Energy counter.
epc1202ForwEnergyActiveReset­table
.43.1.5.1.2.1.18.x
Gauge32
RO
Resettable Forward Active Energy counter.
epc1202ForwEnergyReactiveRe­settable
.43.1.5.1.2.1.19.x
Gauge32
RO
Resettable Forward Reactive Energy counter.
epc1202RevEnergyActive
.43.1.5.1.2.1.20.x
Gauge32
RO
Reverse Active Energy counter.
epc1202RevEnergyReactive
.43.1.5.1.2.1.21.x
Gauge32
RO
Reverse Reactive Energy counter.
epc1202RevEnergyActiveReset­table
.43.1.5.1.2.1.22.x
Gauge32
RO
Resettable Reverse Active Energy counter.
epc1202RevEnergyReactiveReset­table
.43.1.5.1.2.1.23.x
Gauge32
RO
Page 63
63
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
Resettable Reverse Reactive Energy counter.
epc1202OVPIndex
.43.1.5.2.1.1.x
Integer32
RO
None
epc1202OVPStatus
.43.1.5.2.1.2.x
INTEGER
RO
shows the status of the built-in Overvoltage Protection
epc1202SensorIndex
.43.1.6.1.1.1.x
Integer32
RO
None
epc1202TempSensor
.43.1.6.1.1.2.x
Integer32
RO
actual temperature
epc1202HygroSensor
.43.1.6.1.1.3.x
Integer32
RO
actual humidity
epc1202InputSensor
.43.1.6.1.1.4.x
INTEGER
RO
logical state of input sensor
epc1202AirPressure
.43.1.6.1.1.5.x
Integer32
RO
actual air pressure
epc1202DewPoint
.43.1.6.1.1.6.x
Integer32
RO
dew point for actual temperature and humidity
epc1202DewPointDiff
.43.1.6.1.1.7.x
Integer32
RO
difference between dew point and actual temperature (Temp ­DewPoint)
4.5.2
Device MIB 1292
Below is a table of all device-specific OID 's which can be accessed via SNMP. In the numerical representation of the OID the prefix " 1.3.6.1.4.1.28507 " (Gude Enterprise OID) was omitted at each entry in the table to preserve space. The example for a com­plete OID would be "1.3.6.1.4.1.28507.50.1.1.1.1". A distinction is made in SNMP OID 's in between tables and scalars. OID scalar have the extension ".0" and only specify a value. In SNMP tables the "x" is replaced by an index (1 or greater) to address a value from the table.
Name
OID
Type
Acc.
Description
epc1292TrapCtrl
.50.1.1.1.1.0
Integer32
RW
0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3
epc1292TrapIPIndex
.50.1.1.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each receiver slot.
epc1292TrapAddr
.50.1.1.1.2.1.2.x
OCTETS
RW
DNS name or IP address specifying one Trap receiver slot. A port can optionally be specified: 'name:port' An empty string disables this slot.
epc1292portNumber
.50.1.3.1.1.0
Integer32
RO
The number of Relay Ports
epc1292PortIndex
.50.1.3.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each Relay Port.
epc1292PortName
.50.1.3.1.2.1.2.x
OCTETS
RW
A textual string containing name of a Relay Port.
epc1292PortState
.50.1.3.1.2.1.3.x
INTEGER
RW
current state of a Relay Port
epc1292PortSwitchCount
.50.1.3.1.2.1.4.x
Integer32
RO
The total number of switch actions ocurred on a Relay Port. Does not count switch commands which will not switch the ralay state, so just real relay switches are displayed here.
epc1292PortStartupMode
.50.1.3.1.2.1.5.x
INTEGER
RW
set Mode of startup sequence (off, on , remember last state)
epc1292PortStartupDelay
.50.1.3.1.2.1.6.x
Integer32
RW
Delay in sec for startup action
epc1292PortRepowerTime
.50.1.3.1.2.1.7.x
Integer32
RW
Delay in sec for repower port after switching off
epc1292ActivePowerChan
.50.1.5.1.1.0
Unsigned32
RO
Number of suppported Power Channels.
epc1292PowerIndex
.50.1.5.1.2.1.1.x
Integer32
RO
Index of Power Channel entries
epc1292ChanStatus
.50.1.5.1.2.1.2.x
Integer32
RO
0 = data not active, 1 = data valid
epc1292AbsEnergyActive
.50.1.5.1.2.1.3.x
Gauge32
RO
Absolute Active Energy counter.
epc1292PowerActive
.50.1.5.1.2.1.4.x
Integer32
RO
Active Power
epc1292Current
.50.1.5.1.2.1.5.x
Gauge32
RO
Actual Curent on Power Channel.
Page 64
64
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
epc1292Voltage
.50.1.5.1.2.1.6.x
Gauge32
RO
Actual Voltage on Power Channel
epc1292Frequency
.50.1.5.1.2.1.7.x
Gauge32
RO
Frequency of Power Channel
epc1292PowerFactor
.50.1.5.1.2.1.8.x
Integer32
RO
Power Factor of Channel between -1.0 and 1.00
epc1292Pangle
.50.1.5.1.2.1.9.x
Integer32
RO
Phase Angle between Voltage and L Line Current between -180.0 and
180.0
epc1292PowerApparent
.50.1.5.1.2.1.10.x
Integer32
RO
L Line Mean Apparent Power
epc1292PowerReactive
.50.1.5.1.2.1.11.x
Integer32
RO
L Line Mean Reactive Power
epc1292AbsEnergyReactive
.50.1.5.1.2.1.12.x
Gauge32
RO
Absolute Reactive Energy counter.
epc1292AbsEnergyActiveReset­table
.50.1.5.1.2.1.13.x
Gauge32
RW
Resettable Absolute Active Energy counter. Writing '0' resets all reset­table counter.
epc1292AbsEnergyReactiveReset­table
.50.1.5.1.2.1.14.x
Gauge32
RO
Resettable Absolute Reactive Energy counter.
epc1292ResetTime
.50.1.5.1.2.1.15.x
Gauge32
RO
Time in seconds since last Energy Counter reset.
epc1292ForwEnergyActive
.50.1.5.1.2.1.16.x
Gauge32
RO
Forward Active Energy counter.
epc1292ForwEnergyReactive
.50.1.5.1.2.1.17.x
Gauge32
RO
Forward Reactive Energy counter.
epc1292ForwEnergyActiveReset­table
.50.1.5.1.2.1.18.x
Gauge32
RO
Resettable Forward Active Energy counter.
epc1292ForwEnergyReactiveRe­settable
.50.1.5.1.2.1.19.x
Gauge32
RO
Resettable Forward Reactive Energy counter.
epc1292RevEnergyActive
.50.1.5.1.2.1.20.x
Gauge32
RO
Reverse Active Energy counter.
epc1292RevEnergyReactive
.50.1.5.1.2.1.21.x
Gauge32
RO
Reverse Reactive Energy counter.
epc1292RevEnergyActiveReset­table
.50.1.5.1.2.1.22.x
Gauge32
RO
Resettable Reverse Active Energy counter.
epc1292RevEnergyReactiveReset­table
.50.1.5.1.2.1.23.x
Gauge32
RO
Resettable Reverse Reactive Energy counter.
epc1292OVPIndex
.50.1.5.2.1.1.x
Integer32
RO
None
epc1292OVPStatus
.50.1.5.2.1.2.x
INTEGER
RO
shows the status of the built-in Overvoltage Protection
epc1292SensorIndex
.50.1.6.1.1.1.x
Integer32
RO
None
epc1292TempSensor
.50.1.6.1.1.2.x
Integer32
RO
actual temperature
epc1292HygroSensor
.50.1.6.1.1.3.x
Integer32
RO
actual humidity
epc1292InputSensor
.50.1.6.1.1.4.x
INTEGER
RO
logical state of input sensor
epc1292AirPressure
.50.1.6.1.1.5.x
Integer32
RO
actual air pressure
epc1292DewPoint
.50.1.6.1.1.6.x
Integer32
RO
dew point for actual temperature and humidity
epc1292DewPointDiff
.50.1.6.1.1.7.x
Integer32
RO
difference between dew point and actual temperature (Temp ­DewPoint)
4.6 SSL
TLS Standard
The device is compatible with the standards TLSv1.0 to TLSv1.2. Due to lack of secur­ity, SSLv3.0 as well as RC4 and DES encryptions are deactivated.
Page 65
65
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
The following TLS Ciphersuites are supported:
· TLS_RSA_WITH_3DES_EDE_CBC_SHA
· TLS_DHE_RSA_WITH_3DES_EDE_CBC_SHA
· TLS_RSA_WITH_AES_128_CBC_SHA
· TLS_DHE_RSA_WITH_AES_128_CBC_SHA
· TLS_RSA_WITH_AES_256_CBC_SHA
· TLS_DHE_RSA_WITH_AES_256_CBC_SHA
· TLS_RSA_WITH_AES_128_CBC_SHA256
· TLS_RSA_WITH_AES_256_CBC_SHA256
· TLS_DHE_RSA_WITH_AES_128_CBC_SHA256
· TLS_DHE_RSA_WITH_AES_256_CBC_SHA256
· TLS_RSA_WITH_AES_128_GCM_SHA256
· TLS_DHE_RSA_WITH_AES_128_GCM_SHA256
· TLS_PSK_WITH_AES_128_GCM_SHA256
· TLS_PSK_WITH_AES_128_CBC_SHA256
· TLS_ECDH_ECDSA_WITH_3DES_EDE_CBC_SHA
· TLS_ECDH_ECDSA_WITH_AES_128_CBC_SHA
· TLS_ECDH_ECDSA_WITH_AES_256_CBC_SHA
· TLS_ECDHE_ECDSA_WITH_3DES_EDE_CBC_SHA
· TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA
· TLS_ECDHE_ECDSA_WITH_AES_256_CBC_SHA
· TLS_ECDH_RSA_WITH_3DES_EDE_CBC_SHA
· TLS_ECDH_RSA_WITH_AES_128_CBC_SHA
· TLS_ECDH_RSA_WITH_AES_256_CBC_SHA
· TLS_ECDHE_RSA_WITH_3DES_EDE_CBC_SHA
· TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA
· TLS_ECDHE_RSA_WITH_AES_256_CBC_SHA
· TLS_ECDHE_ECDSA_WITH_AES_128_CBC_SHA256
· TLS_ECDH_ECDSA_WITH_AES_128_CBC_SHA256
· TLS_ECDHE_RSA_WITH_AES_128_CBC_SHA256
· TLS_ECDH_RSA_WITH_AES_128_CBC_SHA256
· TLS_ECDHE_ECDSA_WITH_AES_128_GCM_SHA256
· TLS_ECDH_ECDSA_WITH_AES_128_GCM_SHA256
· TLS_ECDHE_RSA_WITH_AES_128_GCM_SHA256
· TLS_ECDH_RSA_WITH_AES_128_GCM_SHA256
· TLS_RSA_WITH_AES_128_CCM
· TLS_RSA_WITH_AES_256_CCM
· TLS_DHE_RSA_WITH_AES_128_CCM
· TLS_DHE_RSA_WITH_AES_256_CCM
· TLS_RSA_WITH_AES_128_CCM_8
· TLS_RSA_WITH_AES_256_CCM_8
· TLS_DHE_RSA_WITH_AES_128_CCM_8
· TLS_DHE_RSA_WITH_AES_256_CCM_8
· TLS_ECDHE_RSA_WITH_CHACHA20_POLY1305_SHA256
· TLS_ECDHE_ECDSA_WITH_CHACHA20_POLY1305_SHA256
· TLS_DHE_RSA_WITH_CHACHA20_POLY1305_SHA256
Creating your own Certificates
The SSL stack is supplied with a specially newly generated certificate. There is no function to generate the local certificate anew at the touch of a button, since the required random numbers in an embedded device are usually not independent enough. However, you can create new cer­tificates and import them to the device. The server accepts RSA (1024/2048/4096) and ECC (Elliptic Curve Cryptography) certificates.
Usually OpenSSL is used to create an SSL certificate. For Windows for example, there is the light version of Shining Light Productions. There you open a command prompt, change to the directory "C:\OpenSSL-Win32\bin" and set these environment variables:
set openssl_conf=C:\OpenSSL-Win32\bin\openssl.cfg
Page 66
66
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
set RANDFILE=C:\OpenSSL-Win32\bin\.rnd
Here are some examples for the generation with OpenSSL:
Creation of a self-signed RSA 2048-bit certificate
openssl genrsa -out server.key 2048 openssl req -new -x509 -days 365 -key server.key -out server.crt
RSA 2048-bit certificate with Sign Request:
openssl genrsa -out server.key 2048 openssl req -new -key server.key -out server.csr openssl req -x509 -days 365 -key server.key -in server.csr -out server.crt
The server keys should be generated with "openssl genrsa". If in the generated key file it reads only "----- BEGIN PRIVATE KEY -----" and not "----- BEGIN RSA PRIVATE KEY -----", the key is not recognized.
ECC Certificate with Sign Request:
openssl ecparam -genkey -name prime256v1 -out server.key openssl req -new -key server.key -out server.csr openssl req -x509 -days 365 -key server.key -in server.csr -out server.crt
If you have created your key and certificate, both files are concatenated to one file:
Linux:
cat server.crt server.key > server.pem
Windows:
copy server.crt + server.key server.pem
The created server.pem can only be uploaded in the maintenance section of the device.
If several certificates (Intermediate CRT's) should also be uploaded to the device, one should make sure, that firstly the server certificate and secondly the Intermediates are assembled , e.g:
cat server.crt IM1.crt IM2.crt server.key > server.pem
An uploaded certificate will be preserved, when a device is put back to factory de-
faults .
Performance Considerations
If RSA 4096 certificates are used, the first access to the web server can take 8-10 seconds, because the math unit of the embedded CPU is highly demanded. After that, the parameters are in the SSL session cache, so all other requests are just as fast as with other certificate lengths. For a quick response even on the first access, we recom­mend RSA 2048-bit certificates that offer adequate security, too.
22
Page 67
67
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
4.7 Console
For the configuration and control of the device, there is a set of commands with para­meters that can be entered through a console. The console is available via Telnet, or for devices with RS232 port through using a serial terminal. The communication can also be performed automated (e.g. via scripting languages). The console features are configured through the web interface .
Command Set
There are several command levels. The following commands are usable from each level:
back
go back one level
help
all commands of the actual level
help all
show all commands
logout
logout (only when login required)
quit
quit console
The "help" command returns all the commands of the current level. If "help" is called from the top level, e.g. the line "http [subtopics]" appears. This means that there is an­other level for "http". With the command "http help" all commands below "http" are shown. Alternatively, with entering "http" you can select the http level, and "help" shows all the commands on the selected level. The command "back" again selects the top level. It is possible to use "help" at any position: "http passwd help" provides all com­mands that have the prefix "http passwd".
You will find a complete list of all possible device commands in the chapter "Cmd Overview".
Parameter
If parameters are expected for the command, the parameter may be passed as nu­meric or constant. If e.g. you get the following line as help:
http server set {http_both=0|https_only=1|http_only=2}
the following instruction pairs are equivalent:
http server set https_only http server set 1
or
http server set https_both http server set 0
Numerical parameters can be entered with different bases. Here is an example of the decimal value 11:
Base
Input
decimal (10)
11
hexadecimal (16)
0xb
octal (8)
013
binary (2)
0b1011
43
Page 68
68
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
Return Values
If a command is unknown or a parameter is incorrect, the output "ERR." is given at the beginning of the line, followed by a description of the fault. Successful instructions without special return value will be acknowledged by "OK.". All other return values are output within a single line. There are of two exceptions:
1. Some configuration changes, that affect TCP / IP and UDP, need a restart to be ap-
plied. These parameters are output on two lines. In the first line the current value is shown, on the second row the value after a restart. In the "Cmd Overview" table this is marked with "Note 2".
2. Other configurations (such as the assigned IPv6 addresses) have several values
that can change dynamically. This is marked with "Note 3" in the "Cmd Overview" table.
Numerical Returns
For parameters that support constants, these constants are output as return values. To better deal with scripting languages, it may be easier to work only with numerical re­turns. The command "vt100 numeric set ON" enables that only numerical values appear.
Comments
If you use a tool to send an entire file of commands via Telnet, it is helpful, if you can place comments in there. Beginning with the comment character "#", the remaining contents of a line is ignored.
Telnet
If the configuration "Raw Mode" is turned off, it is tried to negotiate the Telnet configur­ation between client and server using IAC commands. If this fails, the editing functions are not active, and the "Activate echo" option determines whether the characters sent to the Telnet server will be returned. Normally the client begins with the IAC negoti­ation. If this is not the case with the client, the device configuration "Active negotiation" should be turned on.
Raw Mode
If you want to use the console only automated, it may be advantageous to set the con­figuration "Raw mode" to "yes" and "Activate echo" to "no" to. Then there is no interfer­ing interaction with the editor functions and the is no need to filter the sent characters to process the return values.
If in the console "Raw mode" is activated but not in the used Telnet client, the IAC commands sent at the beginning can appear as interfering characters in the command line (partially invisible).
Editing
The following edit functions are available when the terminal supports VT100, and Raw Mode is deactivated. Entered characters are inserted at the cursor position.
Page 69
69
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
Keys
Function
Left, Right
moves cursor left or right
Pos1, End
moves cursor to the beginning or end of line
Del
deletes character under the cursor
Backspace
deletes character left of cursor
Up, Down
shows input lines history
Tab, Ctrl-Tab
completes the word at cursor
Ctrl-C
clears the line
When a shrink of the terminal window leads to the result, that the input line ex-
tends over multiple lines on the terminal, the editing does not work reliably.
4.7.1
Console Cmd 1202
Command
Description
Note
logout
go to login prompt when enabled
2
quit
quits telnet session - nothing in serial console
2
back
back one cmd level
2
help
show all cmds from this level
2
help all
show all cmds
2
console
enters cmd group "console"
console version
shows unique console version number
console telnet enabled set {OFF=0|ON=1}
enables telnet on/off
console telnet enabled show
shows if telnet enabled
console telnet port set {ip_port}
sets telnet port
console telnet port show
shows telnet port
console telnet raw set {OFF=0|ON=1}
sets raw mode (disables editing) on/off
console telnet raw show
shows if raw mode enabled
console telnet echo set {OFF=0|ON=1}
enables echo on/off
console telnet echo show
shows if echo enabled
console telnet activeneg set {OFF=0|ON=1}
enables telnet active negotiation (IAC) on/off
console telnet activeneg show
shows if active negotiation enabled
console telnet login set {OFF=0|ON=1}
enables login on/off
console telnet login show
shows if login enabled
console telnet login local set {OFF=0|ON=1}
enables local login on/off
console telnet login local show
shows if local login enabled
console telnet login radius set {OFF=0|ON=1}
enables login for RADIUS on/off
console telnet login radius show
shows if RADIUS login enabled
console telnet login delay set {OFF=0|ON=1}
enables delay (after 3 login fails) on/off
console telnet login delay show
shows if login delay enabled
console telnet user set "{username}"
sets login user name
console telnet user show
shows login user name
console telnet passwd set "{passwd}"
sets login password
console telnet passwd hash set "{passwd}"
sets login hashed password
email
enters cmd group "email"
email enabled set {OFF=0|ON=1}
enables email on/off
email enabled show
shows if email is enabled
email sender set "{email_addr}"
sets email sender address
email sender show
shows email sender address
email recipient set "{email_addr}"
sets email recipient address
email recipient show
shows email recipient address
email server set "{dns_name}"
sets email SMTP server address
email server show
shows email SMTP server address
email port set {ip_port}
sets email SMTP port
email port show
shows email SMTP port
email security set {NONE=0|STARTTLS=1| SSL=2}
sets SMTP connection security email security show
shows SMTP connection security
email auth set {NONE=0|PLAIN=1|LOGIN=2}
sets email authentication
email auth show
show email authentication
email user set "{username}"
sets SMTP username
email user show
shows SMTP username
email passwd set "{passwd}"
sets SMTP password
email passwd hash set "{passwd}"
sets crypted SMTP password
email testmail
send test email
Page 70
70
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
ethernet
enters cmd group "ethernet"
ethernet mac show
shows MAC address
ethernet link show
shows ethernet link state
ethernet phyprefer set {10MBIT_HD=0| 10MBIT_FD=1|100MBIT_HD=2|100MBIT_FD=3}
sets preferred speed for PHY Auto Negotiation ethernet phyprefer show
shows preferred speed for PHY Auto Negotiation
extsensor
enters cmd group "extsensor"
extsensor {port_num} {sen_field} value show
shows sensor value
6
extsensor {port_num} {sen_type} label set "{name}"
sets sensor name to label
6
extsensor {port_num} {sen_type} label show
shows label of sensor
6
extsensor {port_num} type show
shows type of sensor
extsensor {port_num} {sen_type} {sen_field} events set {off=0|on=1}
enables sensor events on/off
6
extsensor {port_num} {sen_type} {sen_field} events show
shows if sensor events are enabled
6
extsensor {port_num} {sen_type} {sen_field} events type set "{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2 ,EVT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER =5}"
enables different event types
6 extsensor {port_num} {sen_type} {sen_field} events type show
shows what event types are enabled
6
extsensor {port_num} {sen_type} {sen_field} maxval set {num}
sets maximum value for sensor
6
extsensor {port_num} {sen_type} {sen_field} maxval show
shows maximum value for sensor
6
extsensor {port_num} {sen_type} {sen_field} min­val set {num}
sets minimum value for sensor
6
extsensor {port_num} {sen_type} {sen_field} min­val show
shows minimum value for sensor
6
extsensor {port_num} {sen_type} {sen_field} hyst set {num}
sets hysterese value for sensor
6
extsensor {port_num} {sen_type} {sen_field} hyst show
shows hysterese value for sensor
6
extsensor {port_num} {sen_type} {sen_field} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} port set {port_num}
sets Port for Power Port Switching actions
6
extsensor {port_num} {sen_type} {sen_field} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} port show
shows Port for Power Port Switching actions
6
extsensor {port_num} {sen_type} {sen_field} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} state set {OFF=0|ON=1| DISABLED=2}
sets Port state for Power Port Switching actions
6
extsensor {port_num} {sen_type} {sen_field} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} state show
shows Port state for Power Port Switching actions
6
extsensor period set {24H=0|12H=1|2H=2|1H=3| 30MIN=4}
sets sensor Min/Max measurement period extsensor period show
shows sensor Min/Max measurement period
http
enters cmd group "http"
http server set {HTTP_BOTH=0|HTTPS_ONLY=1| HTTP_ONLY=2}
sets connection types the webserver accepts http server show
shows webserver accepting connection types
http port set {ip_port}
sets http port
http port show
shows http port
http portssl set {ip_port}
sets https port
http portssl show
shows https port
http ajax enabled set {OFF=0|ON=1}
enables ajax autorefresh on/off
http ajax enabled show
shows if ajax autorefresh enabled
http passwd enabled set {OFF=0|ON=1}
enables http password on/off
http passwd enabled show
shows if http password enabled
http passwd user set "{passwd}"
sets http user password
http passwd admin set "{passwd}"
sets http admin password
http passwd hash user set "{passwd}"
sets hashed http user password
http passwd hash admin set "{passwd}"
sets hashed http admin password
ip4
enters cmd group "ip4"
ip4 hostname set "{name}"
sets device hostname
ip4 hostname show
shows device hostname
3
ip4 address set "{ip_address}"
sets IPv4 address
ip4 address show
shows IPv4 address
3
ip4 netmask set "{ip_address}"
sets IPv4 netmask
ip4 netmask show
shows IPv4 netmask
3
Page 71
71
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
ip4 gateway set "{ip_address}"
sets IPv4 gateway address
ip4 gateway show
shows IPv4 gateway address
3
ip4 dns set "{ip_address}"
sets IPv4 DNS server address
ip4 dns show
shows IPv4 DNS server address
3
ip4 dhcp enabled set {OFF=0|ON=1}
enables IPv4 DHCP on/off
ip4 dhcp enabled show
shows IPv4 DHCP state
3
ip6
enters cmd group "ip6"
ip6 enabled set {OFF=0|ON=1}
enables IPv6 on/off
ip6 enabled show
shows if IPv6 is enabled
3
ip6 routadv enabled set {OFF=0|ON=1}
enables IPv6 router advertisement
ip6 routadv enabled show
shows IPv6 router advertisement state
3
ip6 dhcp enabled set {OFF=0|ON=1}
enables IPv6 DHCP on/off
ip6 dhcp enabled show
shows if IPv6 DHCP is enabled
3
ip6 address show
show all IPv6 addresses
4
ip6 gateway show
show all IPv6 gateways
4
ip6 dns show
show all IPv6 DNS server
4
ip6 manual enabled set {OFF=0|ON=1}
enables manual IPv6 addresses
ip6 manual enabled show
shows if manual IPv6 addresses are enabled
3
ip6 manual address {1..4} set "{ip_address}"
sets manual IPv6 address
ip6 manual address {1..4} show
shows manual IPv6 address
3
ip6 manual gateway set "{ip_address}"
sets manual IPv6 gateway address
ip6 manual gateway show
shows manual IPv6 gateway address
3
ip6 manual dns {1..2} set "{ip_address}"
sets manual IPv6 DNS server address
ip6 manual dns {1..2} show
shows manual IPv6 DNS server address
3
ipacl
enters cmd group "ipacl"
ipacl ping enabled set {OFF=0|ON=1}
enables ICMP ping on/off
ipacl ping enabled show
shows if ICMP ping enabled
ipacl enabled set {OFF=0|ON=1}
enable IP filter on/off
ipacl enabled show
shows if IP filter enabled
ipacl filter {ipacl_num} set "{dns_name}"
sets IP filter {ipacl_num}
ipacl filter {ipacl_num} show
shows IP filter {ipacl_num}
linesensor
enters cmd group "linesensor"
linesensor {line_num} {energy_sensor} value show
shows energy sensor of given line
5
linesensor {line_num} counter reset
resets energy metering counter
linesensor {line_num} label set "{name}"
sets line meter to label
linesensor {line_num} label show
shows label of line meter
linesensor {line_num} {energy_sensor} events set {OFF=0|ON=1}
enables events on/off
linesensor {line_num} {energy_sensor} events show
shows if events are enabled
linesensor {line_num} {energy_sensor} events type set "{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2 ,EVT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER =5}"
enables different event types linesensor {line_num} {energy_sensor} events type show
shows what event types are enabled
linesensor {line_num} {energy_sensor} maxval set {float}
sets maximum value for line meter
linesensor {line_num} {energy_sensor} maxval show
shows maximum value for line meter
linesensor {line_num} {energy_sensor} minval set {float}
sets minimum value for line meter
linesensor {line_num} {energy_sensor} minval show
shows minimum value for line meter
linesensor {line_num} {energy_sensor} hyst set {float}
sets hysterese value for line meter linesensor {line_num} {energy_sensor} hyst show
shows hysterese value for line meter
linesensor {line_num} {energy_sensor} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} port set {port_num}
sets Port for Power Port Switching actions
linesensor {line_num} {energy_sensor} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} port show
shows Port for Power Port Switching actions
linesensor {line_num} {energy_sensor} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} state set {OFF=0|ON=1| DISABLED=2}
sets Port state for Power Port Switching actions
linesensor {line_num} {energy_sensor} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} state show
shows Port state for Power Port Switching actions linesensor {line_num} events set {OFF=0|ON=1}
LEGACY - enables events on/off
L
linesensor {line_num} events show
LEGACY - shows if events are enabled
L
linesensor {line_num} events type set
LEGACY - enables different event types
L
Page 72
72
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
"{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2 ,EVT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER =5}"
linesensor {line_num} events type show
LEGACY - shows what event types are enabled
L
linesensor {line_num} maxval set {float}
LEGACY - sets maximum value for line meter
L
linesensor {line_num} maxval show
LEGACY - shows maximum value for line meter
L
linesensor {line_num} minval set {float}
LEGACY - sets minimum value for line meter
L
linesensor {line_num} minval show
LEGACY - shows minimum value for line meter
L
linesensor {line_num} hyst set {float}
LEGACY - sets hysterese value for line meter
L
linesensor {line_num} hyst show
LEGACY - shows hysterese value for line meter
L
linesensor {line_num} {BELOWMIN=0| ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3} port set {port_num}
LEGACY - sets Port for Power Port Switching ac­tions
L
linesensor {line_num} {BELOWMIN=0| ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3} port show
LEGACY - shows Port for Power Port Switching actions
L
linesensor {line_num} {BELOWMIN=0| ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3} state set {OFF=0|ON=1|DISABLED=2}
LEGACY - sets Port state for Power Port Switch­ing actions
L
linesensor {line_num} {BELOWMIN=0| ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3} state show
LEGACY - shows Port state for Power Port Switching actions
L modbus
enters cmd group "modbus"
modbus enabled set <off=0/on=1>
enables Modbus TCP support
modbus enabled show
shows if Modbus is enabled
modbus port set <ip_port>
sets Modbus TCP port
modbus port show
shows Modbus TCP port
port
enters cmd group "port"
port {port_num} state set {OFF=0|ON=1}
sets port to new state
port {port_num} state show
shows port state
port all state set "{port_list}" {OFF=0|ON=1}
sets several ports in one cmd - e.g. port all state set "1,3,5" 1
port all state {MODE0=0|MODE1=1|MODE2=2} show
shows all port states in 3 different view modes
4 port {port_num} reset
start reset sequence for port
port {port_num} toggle
toggles port
port {port_num} batch set {OFF=0|ON=1} wait {num_secs} {OFF=0|ON=1}
starts batch mode for port port {port_num} batch cancel
cancels batch mode
port {port_num} label set "{name}"
sets port label name
port {port_num} label show
shows port label name
port {port_num} initstate coldstart set {OFF=0| ON=1|REMEMBER=2}
sets port coldstart initialization port {port_num} initstate coldstart show
shows port coldstart initialization
port {port_num} initstate delay set {num}
sets port init delay
port {port_num} initstate delay show
shows port init delay
port {port_num} repowerdelay set {num}
sets port repower delay
port {port_num} repowerdelay show
shows port repower delay
port {port_num} resettime set {num}
sets port reset duration
port {port_num} resettime show
shows port reset duration
port {port_num} watchdog enabled set {OFF=0| ON=1}
sets port watchdog to on/off port {port_num} watchdog enabled show
shows port watchdog state
port {port_num} watchdog mode set {OFF=0| PORT_RESET=1|IP_MS=2|IP_MS_INV=3}
sets port watchdog mode port {port_num} watchdog mode show
shows port watchdog mode
port {port_num} watchdog type set {WD_ICMP=0| WD_TCP=1}
sets port watchdog type port {port_num} watchdog type show
shows port watchdog type
port {port_num} watchdog host set "{dns_name}"
sets port watchdog host target
port {port_num} watchdog host show
shows port watchdog host target
port {port_num} watchdog port set {ip_port}
sets port watchdog TCP port
port {port_num} watchdog port show
shows port watchdog TCP port
port {port_num} watchdog pinginterval set {num}
sets port watchdog ping interval
port {port_num} watchdog pinginterval show
shows port watchdog ping interval
port {port_num} watchdog pingretries set {num}
sets port watchdog ping retries
port {port_num} watchdog pingretries show
shows port watchdog ping retries
port {port_num} watchdog retrybooting set {OFF=0|ON=1}
sets port watchdog retry booting to on/off port {port_num} watchdog retrybooting show
shows port watchdog retry booting state
port {port_num} watchdog bootretries set {num}
sets port watchdog retry boot timeout
port {port_num} watchdog bootretries show
hows port watchdog retry boot timeout
radius
enters cmd group "radius"
radius {PRIMARY=0|SECONDARY=1} enabled
enables radius client
Page 73
73
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
set <off=0/on=1>
radius {PRIMARY=0|SECONDARY=1} enabled show
show if radius client enabled
radius {PRIMARY=0|SECONDARY=1} server set "<dns_name>"
sets radius server address
radius {PRIMARY=0|SECONDARY=1} server show
shows radius server address
radius {PRIMARY=0|SECONDARY=1} password set "{passwd}"
sets radius server shared secret
radius {PRIMARY=0|SECONDARY=1} password hash set "{passwd}"
sets radius server crypted shared secret
radius {PRIMARY=0|SECONDARY=1} auth timeout set {num_secs}
sets server request timeout
radius {PRIMARY=0|SECONDARY=1} auth timeout show
shows server request timeout
radius {PRIMARY=0|SECONDARY=1} retries set {num}
sets server number of retries
radius {PRIMARY=0|SECONDARY=1} retries show
shows server number of retries radius chap enabled set <off=0/on=1>
enables CHAP
radius chap enabled show
shows if CHAP is enabled
radius message auth set <off=0/on=1>
enables request message authentication
radius message auth show
shows if request message authentication is en­abled
radius default timeout set {num_secs}
sets default session timeout (when not returned as Session-Timout Attribute)
radius default timeout show
shows default session timeout
snmp
enters cmd group "snmp"
snmp port set {ip_port}
sets SNMP UDP port
snmp port show
shows SNMP UDP port
snmp snmpget enabled set {OFF=0|ON=1}
enables SNMP GET cmds on/off
snmp snmpget enabled show
show if SNMP GET cmds are enabled
snmp snmpset enabled set {OFF=0|ON=1}
enables SNMP SET cmds on/off
snmp snmpset enabled show
show if SNMP SET cmds are enabled
snmp snmpv2 enabled set {OFF=0|ON=1}
enables SNMP v2 on/off
snmp snmpv2 enabled show
show if SNMP v2 is enabled
snmp snmpv2 public set "{text}"
enables SNMP v3 on/off
snmp snmpv2 public show
show if SNMP v3 isenabled
snmp snmpv2 private set "{text}"
sets SNMP v2 public cummnity
snmp snmpv2 private show
shows SNMP v2 public community
snmp snmpv3 enabled set {OFF=0|ON=1}
sets SNMP v2 private community
snmp snmpv3 enabled show
shows SNMP v2 private community
snmp snmpv3 username set "{text}"
sets SNMP v3 username
snmp snmpv3 username show
shows SNMP v3 username
snmp snmpv3 authalg set {NONE=0|MD5=1| SHA1=2|SHA256=3|SHA384=4|SHA512=5}
sets SNMP v3 authentication snmp snmpv3 authalg show
show SNMP v3 authentication algorithm
snmp snmpv3 privalg set {NONE=0|DES=1| 3DES=2|AES128=3|AES192=4|AES256=5| AES192*=6|AES256*=7}
sets SNMP v3 privacy algorithm snmp snmpv3 privalg show
show SNMP v3 privacy algorithm
snmp snmpv3 authpasswd set "{passwd}"
sets SNMP v3 authentication password
snmp snmpv3 privpasswd set "{passwd}"
sets SNMP v3 privacy password
snmp snmpv3 authpasswd hash set "{passwd}"
sets SNMP v3 authentication hashed password
snmp snmpv3 privpasswd hash set "{passwd}"
sets SNMP v3 privacy hashed password
snmp trap type set {NONE=0|V1=1|V2=2|V3=3}
sets type of SNMP traps
snmp trap type show
show SNMP trap type
snmp trap receiver {trap_num} set "{dns_name}"
sets address and port of SNMP trap receiver {trap_num}
snmp trap receiver {trap_num} show
show address and port of SNMP trap receiver {trap_num}
syslog
enters cmd group "syslog"
syslog enabled set {OFF=0|ON=1}
enables syslog msgs on/off
syslog enabled show
show if syslog enabled
syslog server set "{dns_name}"
sets address of syslog server
syslog server show
shows address of syslog server
system
enters cmd group "system"
system restart
restarts device
system fabsettings
restore fab settings and restart device
system bootloader
enters bootloader mode
system flushdns
flush DNS cache
system uptime
number of seconds the device is running
system panel enabled set {OFF=0|ON=1}
blocks panel buttons when not enabled
system panel enabled show
shows if panel buttons are enabled
Page 74
74
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
system display enabled set {OFF=0|ON=1}
dark display when not enabled
system display enabled show
shows if display enabled
system display default extsensor {port_num} {7x01=0|7x02=1|7x03=2} set {sen_field}
sets default display to external sensor
system display default linesensor {line_num} set {sen_field}
sets default display to linesensor system display default show
shows default display
vt100
enters cmd group "vt100"
vt100 echo set {OFF=0|ON=1}
sets console echo state
vt100 echo show
shows console echo state
vt100 numeric set {OFF=0|ON=1}
sets numeric mode
vt100 numeric show
shows numeric mode state
vt100 reset
resets terminal
Notes
1. Legacy - The command has been replaced by a newer version
2. Command can be entered on any level
3. The output may show 2 lines - the 1st line shows the actual state, the 2nd line the status after reboot
4. The output may show several lines
5. Please see the Energy Sensor Table for the right energy index
6. Please see the External Type and External Sensor Field Tables for the correct sensor index
Energy Sensor Table "{energy_sensor}"
Index
Description
Unit
0
Forward Active Energy
Wh
1
Power Active
W
2
VoltageV3
Current A4
Frequency
0.01 hz
5
Power Factor
0.001
6
Power Angle
0.1 degree
7
Power Apparent
VA
8
Power Reactive
VAR
9
Forward Active Energy Resettable
Wh
10
Forward Reactive Energy
VARh
11
Forward Reactive Energy Resettable
VARh
12
Reset Time - sec. since last Energy Counter Reset
s
13
Reverse Active Energy
Wh
14
Reverse Reactive Energy
VARh
15
Reverse Active Energy Resettable
Wh
16
Reverse Reactive Energy Resettable
VARh
17
Absolute Active Energy
Wh
18
Absolute Reactive Energy
VARh
19
Absolute Active Energy Resettable
Wh
20
Absolute Reactive Energy Resettable
VARh
21
Residual Current
A
Dependent on the device model Residual Current may not be supported
External Sensor Type Table "{sen_type}"
Constants "{7x01=0|7x04=0|7x02=1|7x05=1|7x06=2}"
Index
Description
Products
Page 75
75
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
0
Temperature
7001, 7101, 7201
0
Temperature
7004, 7104, 7204
1
Temperature, Humidity
7002, 7102, 7202
1
Temperature, Humidity
7005, 7105, 7205
2
Temperature, Humidity, Air Pressure
7006, 7106, 7206
External Sensor Field Table "{sen_field}"
Index
Description
Unit
0
Temperature
°C
1
Humidity%2
Digital Input
bool
3
Air Pressure
hPa
4
Dew Point
°C
5
Dew Point Temperature Difference
°C
4.7.2
Console Cmd 1292
Command
Description
Note
logout
go to login prompt when enabled
2
quit
quits telnet session - nothing in serial console
2
back
back one cmd level
2
help
show all cmds from this level
2
help all
show all cmds
2
console
enters cmd group "console"
console version
shows unique console version number
console telnet enabled set {OFF=0|ON=1}
enables telnet on/off
console telnet enabled show
shows if telnet enabled
console telnet port set {ip_port}
sets telnet port
console telnet port show
shows telnet port
console telnet raw set {OFF=0|ON=1}
sets raw mode (disables editing) on/off
console telnet raw show
shows if raw mode enabled
console telnet echo set {OFF=0|ON=1}
enables echo on/off
console telnet echo show
shows if echo enabled
console telnet activeneg set {OFF=0|ON=1}
enables telnet active negotiation (IAC) on/off
console telnet activeneg show
shows if active negotiation enabled
console telnet login set {OFF=0|ON=1}
enables login on/off
console telnet login show
shows if login enabled
console telnet login local set {OFF=0|ON=1}
enables local login on/off
console telnet login local show
shows if local login enabled
console telnet login radius set {OFF=0|ON=1}
enables login for RADIUS on/off
console telnet login radius show
shows if RADIUS login enabled
console telnet login delay set {OFF=0|ON=1}
enables delay (after 3 login fails) on/off
console telnet login delay show
shows if login delay enabled
console telnet user set "{username}"
sets login user name
console telnet user show
shows login user name
console telnet passwd set "{passwd}"
sets login password
console telnet passwd hash set "{passwd}"
sets login hashed password
email
enters cmd group "email"
email enabled set {OFF=0|ON=1}
enables email on/off
email enabled show
shows if email is enabled
email sender set "{email_addr}"
sets email sender address
email sender show
shows email sender address
email recipient set "{email_addr}"
sets email recipient address
email recipient show
shows email recipient address
email server set "{dns_name}"
sets email SMTP server address
email server show
shows email SMTP server address
email port set {ip_port}
sets email SMTP port
email port show
shows email SMTP port
email security set {NONE=0|STARTTLS=1| SSL=2}
sets SMTP connection security email security show
shows SMTP connection security
email auth set {NONE=0|PLAIN=1|LOGIN=2}
sets email authentication
email auth show
show email authentication
email user set "{username}"
sets SMTP username
Page 76
76
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
email user show
shows SMTP username
email passwd set "{passwd}"
sets SMTP password
email passwd hash set "{passwd}"
sets crypted SMTP password
email testmail
send test email
ethernet
enters cmd group "ethernet"
ethernet mac show
shows MAC address
ethernet link show
shows ethernet link state
ethernet phyprefer set {10MBIT_HD=0| 10MBIT_FD=1|100MBIT_HD=2|100MBIT_FD=3}
sets preferred speed for PHY Auto Negotiation ethernet phyprefer show
shows preferred speed for PHY Auto Negotiation
extsensor
enters cmd group "extsensor"
extsensor {port_num} {sen_field} value show
shows sensor value
6
extsensor {port_num} {sen_type} label set "{name}"
sets sensor name to label
6
extsensor {port_num} {sen_type} label show
shows label of sensor
6
extsensor {port_num} type show
shows type of sensor
extsensor {port_num} {sen_type} {sen_field} events set {off=0|on=1}
enables sensor events on/off
6
extsensor {port_num} {sen_type} {sen_field} events show
shows if sensor events are enabled
6
extsensor {port_num} {sen_type} {sen_field} events type set "{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2 ,EVT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER =5}"
enables different event types
6 extsensor {port_num} {sen_type} {sen_field} events type show
shows what event types are enabled
6
extsensor {port_num} {sen_type} {sen_field} phonebook sms events set "{1..20}"
sets for what phonebook entries SMS are sent
6
extsensor {port_num} {sen_type} {sen_field} phonebook sms events show
shows for what phonebook entries SMS are sent
6
extsensor {port_num} {sen_type} {sen_field} maxval set {num}
sets maximum value for sensor
6
extsensor {port_num} {sen_type} {sen_field} maxval show
shows maximum value for sensor
6
extsensor {port_num} {sen_type} {sen_field} min­val set {num}
sets minimum value for sensor
6
extsensor {port_num} {sen_type} {sen_field} min­val show
shows minimum value for sensor
6
extsensor {port_num} {sen_type} {sen_field} hyst set {num}
sets hysterese value for sensor
6
extsensor {port_num} {sen_type} {sen_field} hyst show
shows hysterese value for sensor
6
extsensor {port_num} {sen_type} {sen_field} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} port set {port_num}
sets Port for Power Port Switching actions
6
extsensor {port_num} {sen_type} {sen_field} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} port show
shows Port for Power Port Switching actions
6
extsensor {port_num} {sen_type} {sen_field} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} state set {OFF=0|ON=1| DISABLED=2}
sets Port state for Power Port Switching actions
6
extsensor {port_num} {sen_type} {sen_field} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} state show
shows Port state for Power Port Switching actions
6
extsensor period set {24H=0|12H=1|2H=2|1H=3| 30MIN=4}
sets sensor Min/Max measurement period extsensor period show
shows sensor Min/Max measurement period
gsm
enters cmd group "gsm"
gsm enabled set {OFF=0|ON=1}
activates the built-in GSM module
gsm enabled show
shows if the built-in GSM module is enabled
gsm pin set "{pin_num}"
sets PIN and switches the PIN request on
gsm pin show
shows the PIN of the SIM card
gsm phonenum set "{phone_num}"
sets the phone number of the SIM card
gsm phonenum show
shows the phone number of the SIM card
gsm admin sms set "{phone_num}"
sets phone number for SMS status changes
gsm admin sms show
shows phone number for SMS status changes
gsm admin sms enabled set {OFF=0|ON=1}
enables status changes sent via SMS
gsm admin sms enabled show
shows if status changes via SMS are enabled
gsm admin email enabled set {OFF=0|ON=1}
enables status changes sent via email
gsm admin email enabled show
shows if status changes via email are enabled
gsm admin email set "{email_addr}"
sets status email recipient address
gsm admin email show
shows status email recipient address
Page 77
77
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
gsm dtmf sms pin enabled set {OFF=0|ON=1}
enables necessary pin for port changes
gsm dtmf sms pin enabled show
shows if pin is needed for port changes
gsm dtmf sms master pin set "{pin_num}"
sets master pin for port changes
gsm dtmf sms master pin show
shows master pin for port changes
gsm phonebook check set {OFF=0|ON=1}
only allow access to calls that correspond to phonebook entries
gsm phonebook check show
shows if phonebook change enabled
gsm freecall enabled set {OFF=0|ON=1}
enable functions associated with incoming phone numbers
gsm freecall enabled show
show if freecall enabled
gsm admin only set {OFF=0|ON=1}
only allow caller actions from the admin phonenum
gsm admin only show
show if caller actions limited to admin phoennum
gsm sms response set {OFF=0|ON=1}
send a SMS respone for every SMS cmd
gsm sms response show
show if a SMS respone is sent for every SMS cmd
gsm sms error set {OFF=0|ON=1}
send a error SMS for a defective incoming SMS
gsm sms error show
show if error SMS are sent for defective incoming SMS
gsm sms signal set {OFF=0|ON=1}
send status messages when signal quality changes
gsm sms signal show
shows if status messages are sent for signal qual­ity changes
gsm port name set {OFF=0|ON=1}
enable that complete port names are sent via SMS
gsm port name show
show if complete port names are sent
gsm sms autosync set {OFF=0|ON=1}
get date and time from GSM after power-up
gsm sms autosync show
show if autosync is enabled
gsm call voice enabled set {OFF=0|ON=1}
enable voice samples when a call is coming in
gsm call voice enabled show
show if voice samples are enabled
gsm call dtmf enabled set {OFF=0|ON=1}
allow DTMF tones in voice steering
gsm call dtmf enabled show
show if DTM tones are enabled
gsm phonebook {1..20} name set "{name}"
set name for phonebook entry
gsm phonebook {1..20} name show
show name for phonebook entry
gsm phonebook {1..20} phonenum set "{phone_num}"
set number for phonebook entry gsm phonebook {1..20} phonenum show
show number for phonebook entry
gsm phonebook {1..20} port set {port_num}
set power port num for freecall actions
gsm phonebook {1..20} port show
set power port num for freecall actions
gsm phonebook {1..20} action set {NONE=0| GSM_TOGGLE=1|GSM_ON=2|GSM_OFF=3| GSM_RESET=4|GSM_ONOFF1S=5| GSM_ONOFF5S=6|GSM_OFFON1S=7| GSM_OFFON5S=8}
set freecall action
gsm phonebook {1..20} action show
show freecall action
gsm imsi set "{num}"
enter your IMSI number
gsm imsi show
show entered IMSI number
gsm sms email gateway set "{phone_num}"
set number of SMS to email gateway
gsm sms email gateway show
show number of SMS to email gateway
gsm balance name set "{name}"
enter word that names prepaid balance
gsm balance name show
show prepaid balance string
gsm balance action set "{text}"
enter provider query for prepaid balance
gsm balance action show
show prepaid balance provider query
http
enters cmd group "http"
http server set {HTTP_BOTH=0|HTTPS_ONLY=1| HTTP_ONLY=2}
sets connection types the webserver accepts http server show
shows webserver accepting connection types
http port set {ip_port}
sets http port
http port show
shows http port
http portssl set {ip_port}
sets https port
http portssl show
shows https port
http ajax enabled set {OFF=0|ON=1}
enables ajax autorefresh on/off
http ajax enabled show
shows if ajax autorefresh enabled
http passwd enabled set {OFF=0|ON=1}
enables http password on/off
http passwd enabled show
shows if http password enabled
http passwd user set "{passwd}"
sets http user password
http passwd admin set "{passwd}"
sets http admin password
http passwd hash user set "{passwd}"
sets hashed http user password
http passwd hash admin set "{passwd}"
sets hashed http admin password
ip4
enters cmd group "ip4"
ip4 hostname set "{name}"
sets device hostname
ip4 hostname show
shows device hostname
3
ip4 address set "{ip_address}"
sets IPv4 address
ip4 address show
shows IPv4 address
3
ip4 netmask set "{ip_address}"
sets IPv4 netmask
ip4 netmask show
shows IPv4 netmask
3
Page 78
78
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
ip4 gateway set "{ip_address}"
sets IPv4 gateway address
ip4 gateway show
shows IPv4 gateway address
3
ip4 dns set "{ip_address}"
sets IPv4 DNS server address
ip4 dns show
shows IPv4 DNS server address
3
ip4 dhcp enabled set {OFF=0|ON=1}
enables IPv4 DHCP on/off
ip4 dhcp enabled show
shows IPv4 DHCP state
3
ip6
enters cmd group "ip6"
ip6 enabled set {OFF=0|ON=1}
enables IPv6 on/off
ip6 enabled show
shows if IPv6 is enabled
3
ip6 routadv enabled set {OFF=0|ON=1}
enables IPv6 router advertisement
ip6 routadv enabled show
shows IPv6 router advertisement state
3
ip6 dhcp enabled set {OFF=0|ON=1}
enables IPv6 DHCP on/off
ip6 dhcp enabled show
shows if IPv6 DHCP is enabled
3
ip6 address show
show all IPv6 addresses
4
ip6 gateway show
show all IPv6 gateways
4
ip6 dns show
show all IPv6 DNS server
4
ip6 manual enabled set {OFF=0|ON=1}
enables manual IPv6 addresses
ip6 manual enabled show
shows if manual IPv6 addresses are enabled
3
ip6 manual address {1..4} set "{ip_address}"
sets manual IPv6 address
ip6 manual address {1..4} show
shows manual IPv6 address
3
ip6 manual gateway set "{ip_address}"
sets manual IPv6 gateway address
ip6 manual gateway show
shows manual IPv6 gateway address
3
ip6 manual dns {1..2} set "{ip_address}"
sets manual IPv6 DNS server address
ip6 manual dns {1..2} show
shows manual IPv6 DNS server address
3
ipacl
enters cmd group "ipacl"
ipacl ping enabled set {OFF=0|ON=1}
enables ICMP ping on/off
ipacl ping enabled show
shows if ICMP ping enabled
ipacl enabled set {OFF=0|ON=1}
enable IP filter on/off
ipacl enabled show
shows if IP filter enabled
ipacl filter {ipacl_num} set "{dns_name}"
sets IP filter {ipacl_num}
ipacl filter {ipacl_num} show
shows IP filter {ipacl_num}
linesensor
enters cmd group "linesensor"
linesensor {line_num} {energy_sensor} value show
shows energy sensor of given line
5
linesensor {line_num} counter reset
resets energy metering counter
linesensor {line_num} label set "{name}"
sets line meter to label
linesensor {line_num} label show
shows label of line meter
linesensor {line_num} {energy_sensor} events set {OFF=0|ON=1}
enables events on/off
linesensor {line_num} {energy_sensor} events show
shows if events are enabled
linesensor {line_num} {energy_sensor} events type set "{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2 ,EVT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER =5}"
enables different event types linesensor {line_num} {energy_sensor} events type show
shows what event types are enabled
linesensor {line_num} {energy_sensor} phonebook sms events set "{1..20}"
sets for what phonebook entries SMS are sent
linesensor {line_num} {energy_sensor} phonebook sms events show
shows for what phonebook entries SMS are sent
linesensor {line_num} {energy_sensor} maxval set {float}
sets maximum value for line meter
linesensor {line_num} {energy_sensor} maxval show
shows maximum value for line meter
linesensor {line_num} {energy_sensor} minval set {float}
sets minimum value for line meter
linesensor {line_num} {energy_sensor} minval show
shows minimum value for line meter
linesensor {line_num} {energy_sensor} hyst set {float}
sets hysterese value for line meter linesensor {line_num} {energy_sensor} hyst show
shows hysterese value for line meter
linesensor {line_num} {energy_sensor} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} port set {port_num}
sets Port for Power Port Switching actions
linesensor {line_num} {energy_sensor} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} port show
shows Port for Power Port Switching actions
linesensor {line_num} {energy_sensor} {BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2| BELOWMAX=3} state set {OFF=0|ON=1| DISABLED=2}
sets Port state for Power Port Switching actions linesensor {line_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
shows Port state for Power Port Switching actions
Page 79
79
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
BELOWMAX=3} state show
linesensor {line_num} events set {OFF=0|ON=1}
LEGACY - enables events on/off
L
linesensor {line_num} events show
LEGACY - shows if events are enabled
L
linesensor {line_num} events type set "{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2 ,EVT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER =5}"
LEGACY - enables different event types
L linesensor {line_num} events type show
LEGACY - shows what event types are enabled
L
linesensor {line_num} maxval set {float}
LEGACY - sets maximum value for line meter
L
linesensor {line_num} maxval show
LEGACY - shows maximum value for line meter
L
linesensor {line_num} minval set {float}
LEGACY - sets minimum value for line meter
L
linesensor {line_num} minval show
LEGACY - shows minimum value for line meter
L
linesensor {line_num} hyst set {float}
LEGACY - sets hysterese value for line meter
L
linesensor {line_num} hyst show
LEGACY - shows hysterese value for line meter
L
linesensor {line_num} {BELOWMIN=0| ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3} port set {port_num}
LEGACY - sets Port for Power Port Switching ac­tions
L
linesensor {line_num} {BELOWMIN=0| ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3} port show
LEGACY - shows Port for Power Port Switching actions
L
linesensor {line_num} {BELOWMIN=0| ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3} state set {OFF=0|ON=1|DISABLED=2}
LEGACY - sets Port state for Power Port Switch­ing actions
L
linesensor {line_num} {BELOWMIN=0| ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3} state show
LEGACY - shows Port state for Power Port Switching actions
L modbus
enters cmd group "modbus"
modbus enabled set <off=0/on=1>
enables Modbus TCP support
modbus enabled show
shows if Modbus is enabled
modbus port set <ip_port>
sets Modbus TCP port
modbus port show
shows Modbus TCP port
port
enters cmd group "port"
port {port_num} state set {OFF=0|ON=1}
sets port to new state
port {port_num} state show
shows port state
port all state set "{port_list}" {OFF=0|ON=1}
sets several ports in one cmd - e.g. port all state set "1,3,5" 1
port all state {MODE0=0|MODE1=1|MODE2=2} show
shows all port states in 3 different view modes
4 port {port_num} reset
start reset sequence for port
port {port_num} toggle
toggles port
port {port_num} batch set {OFF=0|ON=1} wait {num_secs} {OFF=0|ON=1}
starts batch mode for port port {port_num} batch cancel
cancels batch mode
port {port_num} label set "{name}"
sets port label name
port {port_num} label show
shows port label name
port {port_num} initstate coldstart set {OFF=0| ON=1|REMEMBER=2}
sets port coldstart initialization port {port_num} initstate coldstart show
shows port coldstart initialization
port {port_num} initstate delay set {num}
sets port init delay
port {port_num} initstate delay show
shows port init delay
port {port_num} gsm pin set "{pin_num}"
sets the individual port access code
port {port_num} gsm pin show
shows the individual port access code
port {port_num} repowerdelay set {num}
sets port repower delay
port {port_num} repowerdelay show
shows port repower delay
port {port_num} resettime set {num}
sets port reset duration
port {port_num} resettime show
shows port reset duration
port {port_num} watchdog enabled set {OFF=0| ON=1}
sets port watchdog to on/off port {port_num} watchdog enabled show
shows port watchdog state
port {port_num} watchdog mode set {OFF=0| PORT_RESET=1|IP_MS=2|IP_MS_INV=3}
sets port watchdog mode port {port_num} watchdog mode show
shows port watchdog mode
port {port_num} watchdog type set {WD_ICMP=0| WD_TCP=1}
sets port watchdog type port {port_num} watchdog type show
shows port watchdog type
port {port_num} watchdog host set "{dns_name}"
sets port watchdog host target
port {port_num} watchdog host show
shows port watchdog host target
port {port_num} watchdog port set {ip_port}
sets port watchdog TCP port
port {port_num} watchdog port show
shows port watchdog TCP port
port {port_num} watchdog pinginterval set {num}
sets port watchdog ping interval
port {port_num} watchdog pinginterval show
shows port watchdog ping interval
port {port_num} watchdog pingretries set {num}
sets port watchdog ping retries
port {port_num} watchdog pingretries show
shows port watchdog ping retries
port {port_num} watchdog retrybooting set {OFF=0|ON=1}
sets port watchdog retry booting to on/off
Page 80
80
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
port {port_num} watchdog retrybooting show
shows port watchdog retry booting state
port {port_num} watchdog bootretries set {num}
sets port watchdog retry boot timeout
port {port_num} watchdog bootretries show
hows port watchdog retry boot timeout
radius
enters cmd group "radius"
radius {PRIMARY=0|SECONDARY=1} enabled set <off=0/on=1>
enables radius client
radius {PRIMARY=0|SECONDARY=1} enabled show
show if radius client enabled
radius {PRIMARY=0|SECONDARY=1} server set "<dns_name>"
sets radius server address
radius {PRIMARY=0|SECONDARY=1} server show
shows radius server address
radius {PRIMARY=0|SECONDARY=1} password set "{passwd}"
sets radius server shared secret
radius {PRIMARY=0|SECONDARY=1} password hash set "{passwd}"
sets radius server crypted shared secret
radius {PRIMARY=0|SECONDARY=1} auth timeout set {num_secs}
sets server request timeout
radius {PRIMARY=0|SECONDARY=1} auth timeout show
shows server request timeout
radius {PRIMARY=0|SECONDARY=1} retries set {num}
sets server number of retries
radius {PRIMARY=0|SECONDARY=1} retries show
shows server number of retries radius chap enabled set <off=0/on=1>
enables CHAP
radius chap enabled show
shows if CHAP is enabled
radius message auth set <off=0/on=1>
enables request message authentication
radius message auth show
shows if request message authentication is en­abled
radius default timeout set {num_secs}
sets default session timeout (when not returned as Session-Timout Attribute)
radius default timeout show
shows default session timeout
snmp
enters cmd group "snmp"
snmp port set {ip_port}
sets SNMP UDP port
snmp port show
shows SNMP UDP port
snmp snmpget enabled set {OFF=0|ON=1}
enables SNMP GET cmds on/off
snmp snmpget enabled show
show if SNMP GET cmds are enabled
snmp snmpset enabled set {OFF=0|ON=1}
enables SNMP SET cmds on/off
snmp snmpset enabled show
show if SNMP SET cmds are enabled
snmp snmpv2 enabled set {OFF=0|ON=1}
enables SNMP v2 on/off
snmp snmpv2 enabled show
show if SNMP v2 is enabled
snmp snmpv2 public set "{text}"
enables SNMP v3 on/off
snmp snmpv2 public show
show if SNMP v3 isenabled
snmp snmpv2 private set "{text}"
sets SNMP v2 public cummnity
snmp snmpv2 private show
shows SNMP v2 public community
snmp snmpv3 enabled set {OFF=0|ON=1}
sets SNMP v2 private community
snmp snmpv3 enabled show
shows SNMP v2 private community
snmp snmpv3 username set "{text}"
sets SNMP v3 username
snmp snmpv3 username show
shows SNMP v3 username
snmp snmpv3 authalg set {NONE=0|MD5=1| SHA1=2|SHA256=3|SHA384=4|SHA512=5}
sets SNMP v3 authentication snmp snmpv3 authalg show
show SNMP v3 authentication algorithm
snmp snmpv3 privalg set {NONE=0|DES=1| 3DES=2|AES128=3|AES192=4|AES256=5| AES192*=6|AES256*=7}
sets SNMP v3 privacy algorithm snmp snmpv3 privalg show
show SNMP v3 privacy algorithm
snmp snmpv3 authpasswd set "{passwd}"
sets SNMP v3 authentication password
snmp snmpv3 privpasswd set "{passwd}"
sets SNMP v3 privacy password
snmp snmpv3 authpasswd hash set "{passwd}"
sets SNMP v3 authentication hashed password
snmp snmpv3 privpasswd hash set "{passwd}"
sets SNMP v3 privacy hashed password
snmp trap type set {NONE=0|V1=1|V2=2|V3=3}
sets type of SNMP traps
snmp trap type show
show SNMP trap type
snmp trap receiver {trap_num} set "{dns_name}"
sets address and port of SNMP trap receiver {trap_num}
snmp trap receiver {trap_num} show
show address and port of SNMP trap receiver {trap_num}
syslog
enters cmd group "syslog"
syslog enabled set {OFF=0|ON=1}
enables syslog msgs on/off
syslog enabled show
show if syslog enabled
syslog server set "{dns_name}"
sets address of syslog server
syslog server show
shows address of syslog server
system
enters cmd group "system"
system restart
restarts device
Page 81
81
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
system fabsettings
restore fab settings and restart device
system bootloader
enters bootloader mode
system flushdns
flush DNS cache
system uptime
number of seconds the device is running
system panel enabled set {OFF=0|ON=1}
blocks panel buttons when not enabled
system panel enabled show
shows if panel buttons are enabled
system display enabled set {OFF=0|ON=1}
dark display when not enabled
system display enabled show
shows if display enabled
system display default extsensor {port_num} {7x01=0|7x02=1|7x03=2} set {sen_field}
sets default display to external sensor
system display default linesensor {line_num} set {sen_field}
sets default display to linesensor system display default show
shows default display
vt100
enters cmd group "vt100"
vt100 echo set {OFF=0|ON=1}
sets console echo state
vt100 echo show
shows console echo state
vt100 numeric set {OFF=0|ON=1}
sets numeric mode
vt100 numeric show
shows numeric mode state
vt100 reset
resets terminal
Notes
1. Legacy - The command has been replaced by a newer version
2. Command can be entered on any level
3. The output may show 2 lines - the 1st line shows the actual state, the 2nd line the status after reboot
4. The output may show several lines
5. Please see the Energy Sensor Table for the right energy index
6. Please see the External Type and External Sensor Field Tables for the correct sensor index
Energy Sensor Table "{energy_sensor}"
Index
Description
Unit
0
Forward Active Energy
Wh
1
Power Active
W
2
VoltageV3
Current A4
Frequency
0.01 hz
5
Power Factor
0.001
6
Power Angle
0.1 degree
7
Power Apparent
VA
8
Power Reactive
VAR
9
Forward Active Energy Resettable
Wh
10
Forward Reactive Energy
VARh
11
Forward Reactive Energy Resettable
VARh
12
Reset Time - sec. since last Energy Counter Reset
s
13
Reverse Active Energy
Wh
14
Reverse Reactive Energy
VARh
15
Reverse Active Energy Resettable
Wh
16
Reverse Reactive Energy Resettable
VARh
17
Absolute Active Energy
Wh
18
Absolute Reactive Energy
VARh
19
Absolute Active Energy Resettable
Wh
20
Absolute Reactive Energy Resettable
VARh
21
Residual Current
A
Dependent on the device model Residual Current may not be supported
Page 82
82
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
External Sensor Type Table "{sen_type}"
Constants "{7x01=0|7x04=0|7x02=1|7x05=1|7x06=2}"
Index
Description
Products
0
Temperature
7001, 7101, 7201
0
Temperature
7004, 7104, 7204
1
Temperature, Humidity
7002, 7102, 7202
1
Temperature, Humidity
7005, 7105, 7205
2
Temperature, Humidity, Air Pressure
7006, 7106, 7206
External Sensor Field Table "{sen_field}"
Index
Description
Unit
0
Temperature
°C
1
Humidity%2
Digital Input
bool
3
Air Pressure
hPa
4
Dew Point
°C
5
Dew Point Temperature Difference
°C
4.8 Modbus TCP
If Modbus TCP is activated in the configuration, the ports (relays) can be switched and the following data is callable:
· State of Port (relay)
· State of DC input
· Number of ports (relays)
· Number of energy sensors
· Measured values of energy sensors
· Measured values of the external sensors
This chapter is general for all Gude devices. Depending on the device type, some
ports or certain sensors are not available.
Address Range:
Device Resource
Start
End
Modbus Data Type
Power/Output Ports
0x000
0x3ff
Coils
DC Inputs
0x400
0x7ff
Discrete Inputs
Info Area
0x000
0x005
Input Registers
External Sensors
0x100
0x1ff
Input Registers
Line Energy Sensors
0x400
0x39ff
Input Registers
Port Energy Sensors
0x3a00
0x6fff
Input Registers
These functions are supported:
· Read Coils (0x01)
Reads the state of the ports (relay):
Page 83
83
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
Request Code
1 Byte
0x01
Starting Address
2 Bytes
0x000 to 0x3ff
Quantity of coils
2 Bytes
1 to 0x400
Response Code
1 Byte
0x01
Byte count
1 Byte
n
Coil Status
n Byte
each Bit represents a state
· Read Discrete Inputs (0x02)
Reads state informations:
Request Code
1 Byte
0x02
Starting Address
2 Bytes
0x400 to 0x7ff
Quantity of Inputs
2 Bytes
1 to 0x400
Response Code
1 Byte
0x02
Byte count
1 Byte
n
Input Status
n Byte
each Bit represents a state
Address
Information
0x400 to 0x7ff
State of passive device Inputs
0x800
Stop Condition active (ENC 2302)
0x801
POE active
0x1000 to 0x100f
State of Power Sources
· Write Single Coil (0x05)
Sets the state of a port (relay):
Request Code
1 Byte
0x05
Output Address
2 Bytes
0x00 to 0x3ff
Output Value
2 Bytes
0x0000 or 0xff00
Response Code
1 Byte
0x05
Output Address
2 Bytes
n
· Write Multiple Coils (0x0F)
Sets the state of several ports (relays):
Request Code
1 Byte
0x0f
Starting Address
2 Bytes
0x00 to 0x3ff
Quantity of Outputs
2 Bytes
1 to 0x400
Byte count
1 Byte
n
Outputs Value
n x 1 Byte
each Bit represents a state
Response Code
1 Byte
0x0f
Starting Address
2 Bytes
0x00 to 0x3ff
Page 84
84
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
Quantity of Outputs
2 Bytes
1 to 0x400
· Read Input Registers (0x04)
Read 16-bit values that contain different device information depending on the address:
Request Code
1 Byte
0x04
Starting Address
2 Bytes
0x0000 to 0xffff
Quantity of Inputs
2 Bytes
1 to 0x7d
Response Code
1 Byte
0x04
Byte count
1 Byte
2 x n
Input Status
n x 2 Byte
16-bit or 32-bit data
Various state information and measured values of the device are arranged in the input registers:
Address
Width
Information
0
16-bit
Number of Ports (Relay)
1
16-bit
Number of Ports with Energy Measurement
2
16-bit
Number of Banks
3
16-bit
Lines per Bank
4
16-bit
Phases per line
5
16-bit
Number of Inputs
0x100 to 0x1ff
16-bit (signed)
external Sensors
0x400 to 0x39ff
32-bit (signed)
Line Energy Sensors
0x3a00 to 0x6fff
32-bit (signed)
Port Energy Sensors
External Sensors:
The measured value of the external sensors are coded as fixed point arithmetic. For a factor of e.g. 0.1 in the unit the value must be divided by 10 in order to reach the real measured value. A value of 0x8000 means that no sensor is plugged into the corres­ponding port, or the corresponding field in the sensor is not available. The formula for the address is (the port numbers start at zero):
0x100 + Port * 8 + Offset
Offset
Sensor Field
Unit
0
Temperature
0.1 °C
1
Humidity
0.1 %
2
Digital Input
bool
3
Air Pressure
1 hPa (millibar)
4
Dew Point
0.1 °C
5
Dew Point Difference
0.1 °C
For example, the humidity of the second port has the address: 0x100 + 1 * 8 + 1 = 0x109
Energy Sensors:
We distinguish the line sensors (which correspond to the input circuits) and the port sensors, which measure the energy that is passed over the switched port. The meas-
Page 85
85
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
ured values of the energy sensors are returned as signed 32-bit integers. The high-or­der 16-bits are starting on the even address, followed by the low-order 16-bits on the odd address. To calculate the address, there are the following formulas (the values for line, port and phase start at zero):
Line: 0x0400 + Line * 0x120 + Phase * 0x60 + Offset * 2
Port: 0x3a00 + Port * 0x120 + Phase * 0x60 + Offset * 2
For devices with only one phase, the phase is set to zero in the formula.
Examples:
"Power Active" for 1st line sensor and 3rd phase: 0x400 + 0 * 0x120 + 2 * 0x60 + 1 * 2 = 0x4C2
"Voltage" for 2nd line sensor and single phase device: 0x400 + 1 * 0x120 + 2 * 2 = 0x524
"Power Angle" for 4th port sensor and single phase device: 0x3a00 + 3 * 0x120 + 6 * 2 = 0x3d6c
Offset
Sensor Field
Unit
0
Absolute Active Energy
Wh
1
Power Active
W
2
VoltageV3
Current
mA
4
Frequency
0.01 hz
5
Power Factor
0.001
6
Power Angle
0.1 degree
7
Power Apparent
VA
8
Power Reactive
VAR
9
Absolute Active Energy Resettable
Wh
10
Absolute Reactive Energy
VARh
11
Absolute Reactive Energy Resettable
VARh
12
Reset Time - sec. since last Energy Counter Reset
s
13
Forward Active Energy
Wh
14
Forward Reactive Energy
VARh
15
Forward Active Energy Resettable
Wh
16
Forward Reactive Energy Resettable
VARh
17
Reverse Active Energy
Wh
18
Reverse Reactive Energy
VARh
19
Reverse Active Energy Resettable
Wh
20
Reverse Reactive Energy Resettable
VARh
21
Residual Current Type A
mA
22
Neutral Current
mA
23
Residual Current Type B RMS
0.1 mA
24
Residual Current Type B DC
0.1 mA
Whether the measured values "Residual Current" and "Neutral Current" are sup-
ported depends on the respective device model. For measured values such as "Neut­ral Current", which are independent of the phase, the same value is returned for all phases.
Page 86
86
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
· Read Device Identification (0x2B / 0x0E)
Returns manufacturer name and device identification:
Request Code
1 Byte
0x2b
MEI Type
1 Byte
0x0e
Read Dev ID code
1 Byte
0x01
Object Id
1 Byte
0x00
Response Code
1 Byte
0x2b
MEI Type
1 Byte
0x0e
Read Dev ID code
1 Byte
0x01
Conformity Level
1 Byte
0x01
More Follows
1 Byte
0x00
NextObjectID
1 Byte
0x00
Number of Objects
1 Byte
0x03
Object ID
1 Byte
0x00
Object Length
1 Byte
n1
Object Value
n1 Bytes
"Company Id"
Object ID
1 Byte
0x00
Object Length
1 Byte
n2
Object Value
n2 Bytes
"Product Id"
Object ID
1 Byte
0x00
Object Length
1 Byte
n3
Object Value
n3 Bytes
"Product Version"
4.9 Messages
Depending on adjustable events, various messages can be sent from the device. The following message types are supported:
· Sending of e-mails
· SNMP Traps
· Syslog messages
E-Mail messages
Email messages are triggered by the following events:
· Turning on the device
· Switching of the Power Ports
· Exceeding of the max / min values of attached sensors
· State change of digital sensor input ports
· Exceeding of max / min values of the measured power consumption
· Condition change of overvoltage protection
SNMP Traps
SNMP Traps are system messages that are sent via the SNMP protocol to different re­cipients. SNMP traps are triggered by the following events:
· Switching of the Power Ports
Page 87
87
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Specifications
· Exceeding of the max / min values of attached sensors
· State change of digital sensor input ports
· Exceeding of max / min values of the measured power consumption
· Condition change of overvoltage protection
Syslog messages
Syslog messages are simple text messages that are sent via UDP to a syslog server. Under Linux, normally a syslog daemon is already running (eg. syslog-ng), for Mi­crosoft Windows systems some freeware programs are available on the market. The syslog messages are sent for the following events:
· Turning on the device
· Enable/disable of syslog in the configuration
· Switching of the Power Ports
· Exceeding of the max / min values of attached sensors
· State change of digital sensor input ports
· Exceeding of max / min values of the measured power consumption
· Condition change of overvoltage protection
Page 88
Support
Page 89
89
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Support
5 Support
You will find the latest product software on our website at www.gude.info available for download. If you have further questions about installation or operation of the unit, please contact our support team. Furthermore, we present in our support wiki at www.gude.info/wiki FAQs and configuration examples.
5.1 Data Security
To provide the device with a high level of data security, we recommend the following measures:
· Check that the HTTP password is switched on.
· Set up your own HTTP password.
· Allow access to HTTP via SSL only.
· Authentication and encryption is activated in SNMPv3.
· SNMP v2 access is disabled.
· enable STARTTLS or SSL in the e-mail configuration.
· Archive configuration files securely.
· In the IP ACL, enter only the devices that require access to HTTP or SNMP.
· Because Telnet is unencrypted, only use it in a secure environment.
· Since Modbus TCP is not encrypted, only activate it in a secure environment.
· Activate "Message Authentication" in RADIUS.
When accessed from the Internet
· Use a randomized password with at least 32 characters.
· If possible, place the device behind a firewall.
5.2 Contact
Gude Analog- und Digitalsysteme GmbH Eintrachtstraße 113 50668 Cologne Germany
Phone: +49-221-912 90 97 Fax: +49-221-912 90 98 E-Mail: mail@gude.info Internet: www.gude.info shop.gude.info
Managing Director: Dr.-Ing. Michael Gude
District Court: Köln, HRB-Nr. 17 7 84 WEEE-number: DE 58173350 Value added tax identification number (VAT): DE 122778228
Page 90
90
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Support
5.3 Declaration of Conformity
This product from the Expert Power Control 1202 / 1292 series is in conformity with the European directives for CE marking applicable to this product. The complete CE declaration of conformity for this product can be found on the website www.gude.info in the download section of the product.
5.4 FAQ
1. What can I do if the device is no longer accessible?
· If the Status LED is red, the device has no connection to the switch. Unplug and plug
the Ethernet cable. If the Status LED is still red, try other switches. If one uses no switch, but connects e.g. a laptop directly to the device, make sure you are using a crossover Ethernet cable.
· If the status LED is orange for a longer time after unplugging and plugging the Ether-
net cable, then DHCP is configured, but no DHCP server was found in the network. After a timeout, the last IP address is configured manually.
· If there is a physical link (status LED is green) to the device, but you can not access
the web server, bring the device into bootloader mode and search for it with GBL_Conf.exe . Then check the TCP-IP parameters and change them if neces­sary.
· If the device is not found by GBL_Conf.exe in bootloader mode, you can reset the
settings to factory defaults as the last option.
2. Why does it sometimes take so long to configure new SNMPv3 passwords on
the website?
The authentication methods "SHA-384" and "SHA-512" are calculated purely in soft­ware, and can not use the crypto hardware. On the configuration page, e.g. "SHA-512", needs up to 45 seconds to calculate the key.
3. Can you enter multiple e-mail recipients?
· Yes. In the E-Mail configuration in the Recipient Address field, it is possible to enter
multiple e-mail addresses separated by commas. The input limit is 100 characters.
4. Why did the MIB tables change after the firmware update?
Since the number of possible event types was increased, the previous trap design res­ulted in an excess of trap definitions: See Change in Trap Design .
17
22
60
Page 91
91
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Index
- A -
Antenna terminal 9 automated Access 58
- B -
Bootloader Mode 17, 21 Button Lock 51
- C -
Certificate-Upload 17, 18 clear DNS-Cache 18 Configuration Management 19 Content of Delivery 7 creating certificates 64
- D -
Data Security 89 Declaration of Conformity 90 Default Display 51 Description 7 device MIB 61
- E -
Electrical Measurement 12 E-Mail 50 Ethernet connnector 9
- F -
Factory Reset 17 FAQ 90 Firmware Upload 17 Firmware-Update 18
- G -
GBL_Conf.exe 17 GSM 22 GSM General 52 GSM Misc 53 GSM Phone 54 GSM Provider 54 GSM SIM Card 54
- H -
HTTP 42 HTTPS 42
- I -
Installation 9 IP-ACL 41, 57 IP-Address 40 IPv6 57
- L -
load Configuration 18
- M -
Maintenance 17 messages 86 Modbus TCP 82
- O -
Ok button 9 Operating the device directly 15 Overvoltage Protection 10
- P -
Power Ports 37
- R -
Radius 58 Restart 18 RS232 connector 9
- S -
Security Advice 7 Select button 9 Sensors 12, 48 signal strength 9 SIM card slot 9 SMS Commands 24 SMS replies 28 SNMP 44, 59
Page 92
92
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Index
SSL 64 Start-up the device 9 Status LED 9 Status-LED 15 syslog 44
- T -
Technical Specifications 11 TLS 64
- V -
Voice Call 30
- W -
Watchdog 38
Page 93
93
Expert Power Control 1202/1292 © 2018 Gude Analog- und Digitalsysteme GmbH
Expert Power Control 1202/1292
© 2018 Gude Analog- und Digitalsysteme GmbH
10/16/2018