Guardian Technologies 4451, 4582, 4583, 5308, 4986 User Manual

...
PORTABLES
MODELS:
4451 & 4986 (12,500 Watt) 4582 & 4987 (15,000 Watt) 4583 (17,500 Watt)
5209 (15,000 Watt) 5308 (17,500 Watt)
DIAGNOSTIC REPAIR MANUAL
www.guardiangenerators.com
SAFETY
Throughout this publication, "DANGER!" and "CAUTION!" blocks are used to alert the mechanic to special instructions concerning a particular service or operation that might be hazardous if performed incorrectly or carelessly. PAY CLOSE ATTENTION TO THEM.
DANGER! UNDER THIS HEADING WILL BE FOUND SPECIAL INSTRUCTIONS WHICH, IF NOT COMPLIED
*
WITH, COULD RESULT IN PERSONAL INJURY OR DEATH.
CAUTION! Under this heading will be found special instructions which, if not complied with, could result
in damage to equipment and/or property.
*
These "Safety Alerts" alone cannot eliminate the hazards that they signal. Strict compliance with these spe­cial instructions plus "common sense" are major accident prevention measures.
NOTICE TO USERS OF THIS MANUAL
This SERVICE MANUAL has been written and published by Generac to aid our dealers' mechanics and com­pany service personnel when servicing the products described herein.
It is assumed that these personnel are familiar with the servicing procedures for these products, or like or similar products manufactured and marketed by Generac. That they have been trained in the recommended servicing procedures for these products, including the use of common hand tools and any special Generac tools or tools from other suppliers.
Generac could not possibly know of and advise the service trade of all conceivable procedures by which a service might be performed and of the possible hazards and/or results of each method. We have not under­taken any such wide evaluation. Therefore, anyone who uses a procedure or tool not recommended by Generac must first satisfy themselves that neither his nor the products safety will be endangered by the ser­vice procedure selected.
All information, illustrations and specifications in this manual are based on the latest product information available at the time of publication.
When working on these products, remember that the electrical system and engine ignition system are capa­ble of violent and damaging short circuits or severe electrical shocks. If you intend to perform work where electrical terminals could be grounded or touched, the battery cables should be disconnected at the battery.
Any time the intake or exhaust openings of the engine are exposed during service, they should be covered to prevent accidental entry of foreign material. Entry of such materials will result in extensive damage when the engine Is started.
During any maintenance procedure, replacement fasteners must have the same measurements and strength as the fasteners that were removed. Metric bolts and nuts have numbers that indicate their strength. Customary bolts use radial lines to indicate strength while most customary nuts do not have strength mark­ings. Mismatched or incorrect fasteners can cause damage, malfunction and possible injury.
REPLACEMENT PARTS
Components on Generac recreational vehicle generators are designed and manufactured to comply with Recreational Vehicle Industry Association (RVIA) Rules and Regulations to minimize the risk of fire or explo­sion. The use of replacement parts that are not in compliance with such Rules and Regulations could result in a fire or explosion hazard. When servicing this equipment, it is extremely important that all components be properly installed and tightened. If improperly installed and tightened, sparks could ignite fuel vapors from fuel system leaks.
Table of Contents
SAFETY .................. INSIDE FRONT COVER (IFC)
NOTICE TO USERS OF THIS MANUAL ..............................IFC
REPLACEMENT PARTS .....................................................IFC
TABLE OF CONTENTS ...................................... 1-2
SECTION 1:
GENERATOR FUNDAMENTALS ....................... 3-5
MAGNETISM ..................................................................... 3
ELECTROMAGNETIC FIELDS ..............................................
ELECTROMAGNETIC INDUCTION ......................................
A SIMPLE AC GENERATOR ................................................
A MORE SOPHISTICATED AC GENERATOR .........................
SECTION 2:
MEASURING ELECTRICITY ............................. 6-8
METERS .......................................................................... 6
THE VOM ........................................................................
MEASURING AC VOLTAGE ..............................................
MEASURING DC VOLTAGE ..............................................
MEASURING AC FREQUENCY .........................................
MEASURING CURRENT ....................................................
MEASURING RESISTANCE ................................................
ELECTRICAL UNITS ..........................................................
OHM'S LAW
.................................................................... 8
SECTION 3:
DESCRIPTION AND COMPONENTS ............. 9-15
INTRODUCTION .............................................................. 9
ENGINE-GENERATOR DRIVE SYSTEM ...............................
THE AC GENERATOR .......................................................
ROTOR ASSEMBLY ..........................................................
STATOR ASSEMBLY
BRUSH HOLDER AND BRUSHES .....................................
OTHER AC GENERATOR COMPONENTS ........................
EXCITATION CIRCUIT BREAKER
VOLTAGE REGULATOR ..............................................
ADJUSTMENT PROCEDURE .......................................
CIRCUIT BREAKERS ................................................... 12
ROTOR RESIDUAL MAGNETISM ..................................... 12
FIELD BOOST CIRCUIT ...................................................
OPERATION ...................................................................
STARTUP ................................................................... 12
ON-SPEED OPERATION .............................................. 12
FIELD EXCITATION .....................................................
AC POWER WINDING OUTPUT ..................................
BATTERY CHARGE WINDING OUTPUT .......................
10 AMP BATTERY CHARGE WINDING OUTPUT
INSULATION RESISTANCE ..............................................
THE MEGOHMMETER ...................................................
GENERAL ..................................................................
TESTING STATOR INSULATION ...................................
TESTING ROTOR INSULATION ....................................
HI-POT TESTER .......................................................... 13
........................................................ 10
10 10
.................................. 10
11 11
12 12
12 12 12
.......... 12
13 13
13 13 13
STATOR INSULATION RESISTANCE TEST ..........................
GENERAL ..................................................................
TESTING ALL STATOR WINDINGS TO GROUND ..........
TEST BETWEEN WINDINGS: .......................................
ROTOR INSULATION RESISTANCE TEST ..........................
CLEANING THE GENERATOR .........................................
DRYING THE GENERATOR .............................................
13 13 14 14
15 15 15
SECTION 4:
ENGINE DC CONTROL SYSTEM .................. 16-27
3 3 4 4
6 6 6 6 7 7 8
PRINTED CIRCUIT BOARD .............................................. 16
GENERAL ..................................................................
CIRCUIT BOARD CONNECTIONS ...............................
DIP SWITCH POSITIONS .............................................
BATTERY .......................................................................
RECOMMENDED BATTERY ........................................
CONTROL PANEL COMPONENT IDENTIFICATION ......
OPERATIONAL ANALYSIS ..........................................
CIRCUIT CONDITION - REST ......................................
CIRCUIT CONDITION - START ....................................
CIRCUIT CONDITION - RUN .......................................
CIRCUIT CONDITION - STOP ...................................... 26
FAULT SHUTDOWN ...................................................
16 16 16
16
16 17-18 20-27
20
22
24
27
SECTION 5:
TROUBLESHOOTING FLOWCHARTS .......... 28-36
INTRODUCTION ............................................................ 28
IF PROBLEM INVOLVES AC OUTPUT
9 9 9
PROBLEM 1 -
VOLTAGE & FREQUENCY ARE BOTH HIGH OR LOW ..
PROBLEM 2 -
GENERATOR PRODUCES ZERO VOLTAGE
OR RESIDUAL VOLTAGE (2-12 VAC) ......................
PROBLEM 3 -
EXCESSIVE VOLTAGE/FREQUENCY
DROOP WHEN LOAD IS APPLIED ...............................
PROBLEM 4 -
NO BATTERY CHARGE OUTPUT .................................
PROBLEM 5 -
NO 10 AMP BATTERY CHARGE OUTPUT ...................
PROBLEM 6 -
ENGINE WILL NOT CRANK ........................................
PROBLEM 7 -
ENGINE CRANKS BUT WILL NOT START .....................
PROBLEM 8 -
ENGINE STARTS HARD AND RUNS ROUGH ................
PROBLEM 9 -
ENGINE STARTS THEN SHUTS DOWN ........................
PROBLEM 10 -
10 AMP FUSE (F1) BLOWING .....................................
PROBLEM 11 -
UNIT OVERSPEEDS ....................................................
PROBLEM 12 -
IDLE CONTROL “RPM DOES NOT DECREASE” ...........
PROBLEM 13 -
IDLE CONTROL “RPM DOES NOT INCREASE
WHEN LOAD IS APPLIED” ..........................................
PROBLEM 14 -
ENGINE “HUNTS” / ERRATIC IDLE ..............................
............................... 28
28
29-30
30
31
31
32
33
34
34
35
36
36
36
36
Page 1
Table of Contents
SECTION 6:
DIAGNOSTIC TESTS ...................................... 37-65
INTRODUCTION .............................................................. 37
TEST 1 - CHECK NO-LOAD VOLTAGE AND FREQUENCY ..
TEST 2 - CHECK MAIN CIRCUIT BREAKER ........................
TEST 3- TEST EXCITATION CIRCUIT BREAKER ...................
TEST 4 - FIXED EXCITATION TEST/ROTOR AMP DRAW .....
TEST 5 - CHECK STEPPER MOTOR CONTROL ................... 40
TEST 6 - WIRE CONTINUITY .............................................
TEST 7 - CHECK FIELD BOOST .........................................
TEST 8 - DIODE/RESISTOR ................................................
TEST 9 - TEST STATOR ..................................................... 43
TEST 10 - SENSING LEADS ...............................................
TEST 11 - EXCITATION WIRING ........................................
TEST 12 - CHECK BRUSH LEADS ......................................
TEST 13 - CHECK BRUSHES & SLIP RINGS ........................
TEST 14 - CHECK ROTOR ASSEMBLY ...............................
TEST 15 - CHECK LOAD VOLTAGE & FREQUENCY ...........
TEST 16 - CHECK LOAD WATTS & AMPERAGE ................
TEST 17 - CHECK BATTERY CHARGE OUTPUT .................
TEST 18 - CHECK 10 AMP BATTERY CHARGE OUTPUT ....
TEST 19 - CHECK BATTERY CHARGE RECTIFIER ...............
TEST 20 - CHECK 10 AMP CIRCUIT BREAKER ..................
TEST 21- CHECK 10 AMP FUSE .......................................
TEST 22- CHECK BATTERY & CABLES ..............................
TEST 23- CHECK VOLTAGE AT STARTER CONTACTOR .....
TEST 24 - CHECK STARTER CONTACTOR .........................
TEST 25 - CHECK STARTER MOTOR .................................
CONDITIONS AFFECTING STARTER MOTOR
PERFORMANCE: ..........................................................
CHECKING THE PINION: ..............................................
TOOLS FOR STARTER PERFORMANCE TEST: ................. 50
MEASURING CURRENT: ...............................................
TACHOMETER: ............................................................
TEST BRACKET: ...........................................................
REMOVE STARTER MOTOR: .........................................
TESTING STARTER MOTOR: .........................................
TEST 26 - TEST STARTER CONTACTOR RELAY (SCR) .........
TEST 27- CHECK START-RUN-STOP SWITCH ...................
TEST 28- CHECK START-RUN-STOP (SW1) WIRING ...........
TEST 29 - CHECK IGNITION SPARK ..................................
TEST 30 - CHECK SPARK PLUGS ......................................
TEST 31 - REMOVE WIRE 18 / SHUTDOWN LEAD ............
TEST 32 - TEST START STOP RELAY ..................................
TEST 33- TEST WIRE 167 .................................................
TEST 34 - TEST START STOP RELAY WIRING .....................
TEST 35 - CHECK AND ADJUST IGNITION MAGNETOS ....
TEST 36: TEST FUEL SHUTOFF SOLENOID .........................
TEST 37: TEST FUEL SHUTOFF SOLENOID VOLTAGE .........
TEST 38: CHECK FUEL PUMP ........................................... 57
37 37 38 38
41 41 42
44 45 45 45 46 46 46 47 47 47 48 48 48 49 49 49
49 50
50 50 51 51 51
51 52 52 53 53 54 54 55 56 56 57 57
TEST 39 - CHECK CARBURETION .....................................
TEST 40 - VALVE ADJUSTMENT ........................................
TEST 41 - CHECK ENGINE / CYLINDER LEAK
DOWN TEST / COMPRESSION TEST .................................
TEST 42 - CHECK OIL PRESSURE SWITCH AND WIRE 86 ..
TEST 43: CHECK START STOP RELAY (SSR) .......................
TEST 44: TEST STARTER CONTACTOR RELAY (SCR) ..........
TEST 45: CHECK WIRE 15 CIRCUIT ..................................
TEST 46: CHECK WIRE 14 CIRCUIT ..................................
TEST 47: CHECK FUEL SHUTOFF SOLENOID .....................
TEST 48: CHECK HOURMETER ........................................ 62
TEST 49: CHECK WIRE 15B .............................................
TEST 50: CHECK WIRE 167 .............................................
TEST 51: CHECK WIRES 11S & 44S ..................................
TEST 52: CHECK IDLE CONTROL SWITCH (SW2) ..............
TEST 53: CHECK IDLE CONTROL WIRING ........................
TEST 54: CHECK IDLE CONTROL TRANSFORMERS ...........
TEST 55: CHECK TR1 & TR2 WIRING ...............................
TEST 56: CHOKE TEST ...................................................
58 58
59 60 60 61 61 61 61
62 62 62 63 63 64 64
65
SECTION 7:
DISASSEMBLY AND EXPLODED VIEWS ..... 66-71
MAJOR DISASSEMBLY ..................................................... 66
GENERATOR – FIGURE A ................................................
FRAME, HANDLE & WHEELS – FIGURE B .........................
68 70
SECTION 8:
ELECTRICAL DATA ......................................... 72-79
WIRING DIAGRAM 12.5 & 15 KW (UNITS WITHOUT
HOURMETER) – DRAWING NO. 0E0228 ..........................
ELECTRICAL SCHEMATIC 12.5 & 15 KW (UNITS
WITHOUT HOURMETER) – DRAWING NO. 0E0229-A .......
WIRING DIAGRAM 12.5 & 15 KW (UNITS WITH HOURMETER) – DRAWING NO. 0D4609-D ..
ELECTRICAL SCHEMATIC 12.5 & 15 KW (UNITS WITH
HOURMETER) – DRAWING NO. 0D6297-A ......................
WIRING DIAGRAM 17.5 KW UNITS –
DRAWING NO. 0G0731 ..................................................
ELECTRICAL SCHEMATIC 17.5 KW UNITS –
DRAWING NO. 0G0733 ..................................................
WIRING DIAGRAM, 17.5 KW MANUAL
TRANSFER SWITCH – DRAWING NO. 0G1065 ................
INTERCONECTION DRAWING – 17.5 KW GENERATOR ....
72
74
76
78
80
82
83 84
SECTION 9:
SPECIFICATIONS & CHARTS ....................... 86-87
GENERATOR SPECIFICATIONS .......................................... 86
ENGINE
SPECIFICATIONS ................................................. 86
ENGINE SPEEDS AND VOLTAGE SPECIFICATIONS .............
TORQUE SPECIFICATIONS ................................................
TRIM TORQUE SPECIFICATIONS .......................................
86 87 87
Page 2
Section 1
GENERATOR FUNDAMENTALS
MAGNETISM
Magnetism can be used to produce electricity and electricity can be used to produce magnetism.
Much about magnetism cannot be explained by our present knowledge. However, there are certain pat­terns of behavior that are known. Application of these behavior patterns has led to the development of gen­erators, motors and numerous other devices that uti­lize magnetism to produce and use electrical energy.
See Figure 1-1. The space surrounding a magnet is permeated by magnetic lines of force called “flux”. These lines of force are concentrated at the magnet's north and south poles. They are directed away from the magnet at its nor th pole, travel in a loop and re-enter the magnet at its south pole. The lines of force form definite patterns which vary in intensity depending on the strength of the magnet. The lines of force never cross one another. The area surround­ing a magnet in which its lines of force are effective is called a “magnetic field”.
Like poles of a magnet repel each other, while unlike poles attract each other.
Figure 1-1. – Magnetic Lines of Force
ELECTROMAGNETIC FIELDS
NOTE: The “right hand rule” is based on the “cur­rent flow” theory which assumes that current flows from positive to negative. This is opposite the “electron” theory, which states that current flows from negative to positive.
Figure 1-2. – The Right Hand Rule
ELECTROMAGNETIC INDUCTION
An electromotive force (EMF) or voltage can be pro­duced in a conductor by moving the conductor so that it cuts across the lines of force of a magnetic field.
Similarly, if the magnetic lines of force are moved so that they cut across a conductor, an EMF (voltage) will be produced in the conductor. This is the basic principal of the revolving field generator.
Figure 1-3, below, illustrates a simple revolving field generator. The permanent magnet (Rotor) is rotated so that its lines of magnetic force cut across a coil of wires called a Stator. A voltage is then induced into the Stator windings. If the Stator circuit is completed by connecting a load (such as a light bulb), current will flow in the circuit and the bulb will light.
All conductors through which an electric current Is flowing have a magnetic field surrounding them. This field is always at right angles to the conductor. If a compass is placed near the conductor, the compass needle will move to a right angle with the conductor. The following rules apply:
• The greater the current flow through the conductor, the stronger the magnetic field around the conductor.
• The increase in the number of lines of force is directly proportional to the increase in current flow and the field is distributed along the full length of the conductor.
• The direction of the lines of force around a conduc tor can be determined by what is called the “right hand rule”. To apply this rule, place your right hand around the conductor with the thumb pointing in the direction of current flow. The fingers will then be pointing in the direction of the lines of force.
-
Figure 1-3. – A Simple Revolving Field Generator
Page 3
Section 1
S
TATOR
ROT
OR
MAGNETIC FIEL
D
CURRENT
VOLTAGE
ONE CYCLE
0
180
360
(+)
(-)
S
TAT
OR
BRUSHE
S
120
V
120
V
SLIP
RIN
GS
OU
TP
U
T
CU
RRENT
S
TAT
OR
240
V
GENERATOR FUNDAMENTALS
A SIMPLE AC GENERATOR
Figure 1-4 shows a very simple AC Generator. The generator consists of a rotating magnetic field called a ROTOR and a stationary coil of wire called a STATOR. The ROTOR is a permanent magnet which consists of a SOUTH magnetic pole and a NORTH magnetic pole.
As the MOTOR turns, its magnetic field cuts across the stationar y STATOR. A voltage is induced Into the STATOR windings. When the magnet's NORTH pole passes the STATOR, current flows in one direc­tion. Current flows in the opposite direction when the magnet's SOUTH pole passes the STATOR. This con­stant reversal of current flow results in an alternating current (AC) waveform that can be diagrammed as shown in Figure 1-5.
The ROTOR may be a 2-pole type having a single NORTH and a single SOUTH magnetic pole. Some ROTORS are 4-pole type with two SOUTH and two NORTH magnetic poles. The following apply:
1. The 2-pole ROTOR must be turned at 3600 rpm to produce
an AC frequency of 60 Hertz, or at 3000 rpm to deliver an AC
frequency of 50 Hertz.
2. The 4-pole ROTOR must operate at 1800 rpm to deliver a 60
Hertz AC frequency or at 1500 rpm to deliver a 50 Hertz AC
frequency.
Figure 1-5. – Alternating Current Sine Wave
A MORE SOPHISTICATED AC GENERATOR
Figure 1-6 represents a more sophisticated generator. A regulated direct current is delivered into the ROTOR windings via carbon BRUSHES AND SLIP RINGS. This results in the creation of a regulated magnetic field around the ROTOR. As a result, a regulated volt­age is induced into the STATOR. Regulated current delivered to the ROTOR is called “EXCITATION” cur­rent.
Page 4
Figure 1-4. – A Simple AC Generator
Figure 1-6. – A More Sophisticated Generator
See Figure 1-7 (next page). The revolving magnet­ic field (ROTOR) is driven by the engine at a con­stant speed. This constant speed is maintained by a mechanical engine governor. Units with a 2-pole rotor require an operating speed of 3600 rpm to deliver a 60 Hertz AC output.
Generator operation may be described briefly as fol­lows:
1. Some “residual” magnetism is normally present in the Rotor
and is sufficient to induce approximately 7 to 12 volts AC Into
the STATOR's AC power windings.
Section 1
ENGINE ­DIRECT DRIVE
CB2
BCR2
BCR1
BCR1 & BCR2 = BATTERY CHARGE RECTIFIER
FIELD BOOST FROM START/STOP RELAY (SSR)
CB1
CB2 = EXCITATION CIRCUIT BREAKER
12V DC
OUTLET
10A STATOR
BATTERY CHARGE
WINDING
STATOR
BATTERY CHARGE
WINDING
STATOR
DPE
WINDING
STATOR POWER
WINDING
STATOR POWER
WINDING
ROTOR
VOLTAGE
REGULATOR
GENERATOR FUNDAMENTALS
Figure 1-7. – Generator Operating Diagram
2. During startup, printed circuit board action controls the START/
STOP RELAY to deliver battery voltage to the ROTOR, via the
brushes and slip rings.
a. The battery voltage is called “Field Boost”. b. Flow of direct current through the ROTOR
increases the strength of the magnetic field above that of “residual” magnetism alone.
3. “Residual” plus “Field Boost” magnetism induces a voltage into
the Stator excitation (DPE), battery charge and AC Power wind-
ings.
4. Excitation winding unregulated AC output is delivered to an
electronic Voltage Regulator, via an Excitation Circuit Breaker.
a. A “Reference” voltage has been preset into
the Voltage Regulator.
b. An “Actual” (“sensing”) voltage is delivered
to the Voltage Regulator via sensing leads from the Stator AC power windings.
c. The Regulator “compares” the actual (sens-
ing) voltage to its pre-set reference voltage.
(1) If the actual (sensing) voltage is great-
er than the pre-set reference voltage, the Regulator will decrease the regulated cur­rent flow to the Rotor.
(2) If the actual (sensing) voltage is less
than the pre-set reference voltage, the Regulator will increase the regulated current flow to the Rotor.
(3) In the manner described, the Regulator
maintains an actual (sensing) voltage that is equal to the pre-set reference voltage.
NOTE: The Voltage Regulator also changes the Stator excitation windings alternating current (AC) output to direct current (DC).
5. When an electrical load is connected across the Stator power
windings, the circuit is completed and an electrical current will
flow.
6. The Rotor's magnetic field also induces a voltage into the
Stator battery charge windings.
a. Battery charge winding AC output is deliv
ered to the battery charge rectifiers (BCR) which changes the AC to direct current (DC).
b. The rectified DC is then delivered to the
units battery and battery charge outlet, to maintain the battery in a charged state.
-
Page 5
Section 2 MEASURING ELECTRICITY
METERS
Devices used to measure electrical properties are called meters. Meters are available that allow one to measure (a) AC voltage, (b) DC voltage, (c) AC frequency, and (d) resistance in ohms. The following apply:
• To measure AC voltage, use an AC voltmeter.
• To measure DC voltage, use a DC voltmeter.
• Use a frequency meter to measure AC frequency in “Hertz” or “cycles per second”..
• Use an ohmmeter to read circuit resistance, in “ohms”.
THE VOM
A meter that will permit both voltage and resistance to be read is the “volt-ohm-milliammeter” or “VOM”.
Some VOMs are of the “analog” type (not shown). These meters display the value being measured by physically deflecting a needle across a graduated scale. The scale used must be interpreted by the user.
“Digital” VOM's (Figure 2-1) are also available and are generally very accurate. Digital meters display the measured values directly by converting the values to numbers.
NOTE: Standard AC voltmeters react to the AVERAGE value of alternating current. When working with AC, the effective value is used. For that reason a different scale is used on an AC voltmeter. The scale is marked with the effective or “rms” value even though the meter actually reacts to the average value. That is why the AC voltmeter will give an incorrect reading if used to measure direct current (DC).
MEASURING AC VOLTAGE
An accurate AC voltmeter or a VOM may be used to read the generator's AC output voltage. The following apply:
1. Always read the generator's AC output voltage only at the unit's
rated operating speed and AC frequency.
2. The generator's Voltage Regulator can be adjusted for correct
output voltage only while the unit is operating at its correct
rated speed and frequency.
3. Only an AC voltmeter may be used to measure AC voltage. DO
NOT USE A DC VOLTMETER FOR THIS PURPOSE.
DANGER!: GENERATORS PRODUCE HIGH
*
AND DANGEROUS VOLTAGES. CONTACT WITH HIGH VOLTAGE TERMINALS WILL RESULT IN DANGEROUS AND POSSIBLY LETHAL ELECTRICAL SHOCK.
MEASURING DC VOLTAGE
A DC voltmeter or a VOM may be used to measure DC voltages. Always observe the following rules:
1. Always observe correct DC polarity.
a. Some VOM's may be equipped with a polar-
ity switch.
b. On meters that do n ot have a polar-
ity switch, DC polarity must be reversed by reversing the test leads.
2. Before reading a DC voltage, always set the meter to a higher
voltage scale than the anticipated reading. If in doubt, start at
the highest scale and adjust the scale downward until correct
readings are obtained.
Page 6
Figure 2-1. – Digital VOM
3. The design of some meters is based on the “current flow”
theory while others are based on the “electron flow” theory.
a. The “current flow” theory assumes that
direct current flows from the positive (+) to the negative (-).
b. The “electron flow” theory assumes that cur-
rent flows from negative (-) to positive (+).
NOTE: When testing generators, the “current flow” theory is applied. That is, current is assumed to flow from positive (+) to negative (-).
MEASURING AC FREQUENCY
The generator's AC output frequency is proportional to Rotor speed. Generators equipped with a 2-pole Rotor must operate at 3600 rpm to supply a frequency of 60 Hertz. Units with 4-pole Rotor must run at 1800 rpm to deliver 60 Hertz.
Correct engine and Rotor speed is maintained by an
Section 2
1.00 A
BATTERY
+-
RELAY
MEASURING ELECTRICITY
engine speed governor. For models rated 60 Hertz, the governor is generally set to maintain a no-load fre­quency of about 62 Hertz with a corresponding output voltage of about 124 volts AC line-to-neutral. Engine speed and frequency at no-load are set slightly high to prevent excessive rpm and frequency droop under heavy electrical loading.
MEASURING CURRENT
CLAMP-ON: To read the current flow, in AMPERES, a clamp-on
ammeter may be used. This type of meter indicates current flow through a conductor by measuring the strength of the magnetic field around that conductor. The meter consists essentially of a current trans­former with a split core and a rectifier type instrument connected to the secondary. The primary of the cur­rent transformer is the conductor through which the current to be measured flows. The split core allows the instrument to be clamped around the conductor without disconnecting it.
Current flowing through a conductor may be mea­sured safely and easily. A line-splitter can be used to measure current in a cord without separating the conductors.
NOTE: If the physical size of the conductor or ammeter capacity does not permit all lines to be measured simultaneously, measure current flow in each individual line. Then, add the individual readings.
IN-LINE: Alternatively, to read the current flow in AMPERES,
an in-line ammeter may be used. Most Digital Volt Ohm Meters (VOM) will have the capability to mea­sure amperes.
This usually requires the positive meter test lead to be connected to the correct amperes plug, and the meter to be set to the amperes position. Once the meter is properly set up to measure amperes the circuit being measured must be physically broken. The meter will be in-line or in series with the component being mea­sured.
In Figure 2-4 the control wire to a relay has been removed. The meter is used to connect and supply voltage to the relay to energize it and measure the amperes going to it.
Figure 2-4. – A VOM as an In-line meter
MEASURING RESISTANCE
The volt-ohm-milliammeter may be used to measure the resistance in a circuit. Resistance values can be
Figure 2-2. – Clamp-On Ammeter
Figure 2-3. – A Line-Splitter
very valuable when testing coils or windings, such as the Stator and Rotor windings.
When testing Stator windings, keep in mind that the resistance of these windings is very low. Some meters are not capable of reading such a low resistance and will simply read CONTINUITY.
If proper procedures are used, the following condi­tions can be detected using a VOM:
• A “short-to-ground” condition in any Stator or Rotor winding.
• Shorting together of any two parallel Stator wind ings.
• Shorting together of any two isolated Stator wind ings.
• An open condition in any Stator or Rotor winding.
Page 7
-
-
Section 2
-
+
AMPERE - Unit measuring rate of
current flow (number of electrons past a given point)
OHM - Unit measuring resistance
or opposition to flow
VOLT - Unit measuring force or
difference in potential causing current flow
Conductor of a Circuit
VOLTS
(E)
AMPS
(I)
OHMS
(R)
MEASURING ELECTRICITY
Component testing may require a specific resis­tance value or a test for INFINITY or CONTINUITY. Infinity is an OPEN condition between two electrical points, which would read as no resistance on a VOM. Continuity is a CLOSED condition between two elec­trical points, which would be indicated as very low resistance or “ZERO” on a VOM.
ELECTRICAL UNITS
AMPERE: The rate of electron flow in a circuit is represented
by the AMPERE. The ampere is the number of elec­trons flowing past a given point at a given time. One AMPERE is equal to just slightly more than six thou­sand million billion electrons per second (6.25 x 1018).
With alternating current (AC), the electrons flow first in one direction, then reverse and move in the oppo­site direction. They will repeat this cycle at regular intervals. A wave diagram, called a “sine wave” shows that current goes from zero to maximum positive value, then reverses and goes from zero to maximum negative value. Two reversals of current flow is called a cycle. The number of cycles per second is called frequency and is usually stated in “Hertz”.
VOLT: The VOLT is the unit used to measure electrical
PRESSURE, or the difference in electrical potential that causes electrons to flow. Very few electrons will flow when voltage is weak. More electrons will flow as voltage becomes stronger. VOLTAGE may be consid­ered to be a state of unbalance and current flow as an attempt to regain balance. One volt is the amount of EMF that will cause a current of 1 ampere to flow through 1 ohm of resistance.
OHM: The OHM is the unit of RESISTANCE. In every circuit
there is a natural resistance or opposition to the flow of electrons. When an EMF is applied to a complete circuit, the electrons are forced to flow in a single direction rather than their free or orbiting pattern. The resistance of a conductor depends on (a) its physical makeup, (b) its cross-sectional area, (c) its length, and (d) its temperature. As the conductor's tempera­ture increases, its resistance increases in direct pro­portion. One (1) ohm of resistance will permit one (1) ampere of current to flow when one (1) volt of electro­motive force (EMF) is applied.
OHM'S LAW
A definite and exact relationship exists between VOLTS, OHMS and AMPERES. The value of one can be calculated when the value of the other two are known. Ohm's Law states that in any circuit the current will increase when voltage increases but resistance remains the same, and current will decrease when resistance Increases and voltage remains the same.
Page 8
Figure 2-5. – Electrical Units
Figure 2-6. – Ohm's Law
If AMPERES is unknown while VOLTS and OHMS are known, use the following formula:
OHMS
If VOLTS is unknown while AMPERES and OHMS are known, use the following formula:
If OHMS is unknown but VOLTS and AMPERES are known, use the following:
AMPERES
AMPERES =
VOLTS = AMPERES x OHMS
OHMS
VOLTS
VOLTS
=
Section 3
STATOR
ENGINE
ENGINE
ADAPTOR
REAR BEARING
CARRIER
BRUSH HOLDER
ASSEMBLY
ROTOR
DESCRIPTION & COMPONENTS
INTRODUCTION
The generator revolving field (rotor) is driven by an air-cooled engine at about 3600 rpm.
The generator may be used to supply electrical power for the operation of 120 and/or 240 volts, 1-phase, 60 Hz, AC loads.
ENGINE-GENERATOR DRIVE SYSTEM
The generator revolving field is driven by an air­cooled, horizontal crankshaft engine. The generator is directly coupled to the engine crankshaft (see Figure
1). Both the engine and generator rotor are driven at approximately 3600 rpm, to provide a 60 Hz AC out­put.
THE AC GENERATOR
Figure 3-1 shows the major components of the AC generator.
ROTOR ASSEMBLY
The 2-pole rotor must be operated at 3600 rpm to supply a 60 Hertz AC frequency. The term “2-pole” means the rotor has a single north magnetic pole and a single south magnetic pole. As the rotor rotates, its lines of magnetic flux cut across the stator assem­bly windings and a voltage is induced into the stator windings. The rotor shaft mounts a positive (+) and a negative (-) slip ring, with the positive (+) slip ring nearest the rear bearing carrier (Figure 3-2). The rotor bearing is pressed onto the end of the rotor shaft. The tapered rotor shaft is mounted to a tapered crankshaft and is held in place with a single through bolt.
Figure 3-1. – AC Generator Exploded View
Page 9
Section 3
11
44
22
77A
55
77
6
2
66
66A
55A
44S
11S
4
0
DESCRIPTION & COMPONENTS
Figure 3-2. – The 2-Pole Rotor Assembly
STATOR ASSEMBLY
The stator can houses and retains (a) dual AC power windings, (b) an excitation winding, and (c) two bat­tery charge windings. A total of thirteen (13) stator leads are brought out of the stator can as shown in Figure 3-3.
The stator can is sandwiched between an engine adapter and a rear bearing carrier. It is retained in that position by four stator studs.
Wire 4 connects to the positive (+) brush and Wire 0 to the negative (-) brush. Wire 0 connects to frame ground. Rectified and regulated excitation current, as well as current from a field boost circuit, are delivered to the rotor windings via Wire 4, and the positive (+) brush and slip ring. The excitation and field boost cur­rent passes through the windings and to frame ground via the negative (-) slip ring and brush, and Wire 0. This current flow creates a magnetic field around the rotor having a flux concentration that is proportional to the amount of current flow.
Figure 3-3. – Stator Assembly Leads
BRUSH HOLDER AND BRUSHES
The brush holder is retained to the rear bearing car­rier by means of two Taptite screws. A positive (+) and a negative (-) brush are retained in the brush holder, with the positive (+) brush riding on the slip ring near­est the rotor bearing.
Page 10
Figure 3-4. – Brush Holder and Brushes
OTHER AC GENERATOR COMPONENTS
Some AC generator components are housed in the generator control panel enclosure. These are (a) an Excitation Circuit Breaker, (b) a Voltage Regulator, and (c) a main line circuit breaker.
EXCITATION CIRCUIT BREAKER: The Excitation Circuit Breaker (CB2) is housed in the
generator control panel enclosure and electrically connected in series with the excitation (DPE) wind­ing output to the Voltage Regulator. The breaker is self-resetting, i.e.; its contacts will close again when excitation current drops to a safe value.
If the circuit breaker has failed open, excitation current flow to the Voltage Regulator and, subsequently, to the rotor windings will be lost. Without excitation cur­rent flow, AC voltage induced into the stator AC power windings will drop to a value that is commensurate with the rotor residual magnetism (see Figure 3-5).
2
162
Figure 3-5. – Excitation Circuit Breaker
VOLTAGE REGULATOR: A typical Voltage Regulator is shown in Figure 3-6
(12.5 & 15 kW Units) or Figure 3-7 (17.5 kW Units). Unregulated AC output from the stator excitation winding is delivered to the regulator’s DPE termi­nals, via Wire 2, the Excitation Circuit Breaker and Wire 162, and Wire 6. The Voltage Regulator recti­fies that current and, based on stator AC power winding sensing, regulates it. The rectified and regulated excitation current is then delivered to the rotor windings from the positive (+) and negative (-) regulator terminals, via Wire 4 and Wire 0. Stator AC power winding “sensing” is delivered to the reg­ulator “SEN” terminals via Wires 11S and 44S.
The regulator provides “over-voltage” protection, but does not protect against “under-voltage”. On occur­rence of an “over-voltage” condition, the regulator will “shut down” and complete loss of excitation current to the rotor will occur. Without excitation current, the generator AC output voltage will drop to approximately one-half (or lower) of the unit’s rated voltage.
Section 3
DESCRIPTION & COMPONENTS
Figure 3-7. – Typical Voltage Regulator Found on 17.5
Units
ADJUSTMENT PROCEDURE (12.5 AND 15 KW UNITS): The Voltage Regulator is equipped with three light
emitting diodes (LED’s). These LED’s are normally on during operation with no faults in the system The RED regulator LED is on when the regulator is on and functioning. The Yellow sensing LED is powered by sensing input to the regulator from the stator AC power windings. The GREEN excitation LED is pow­ered by stator excitation winding output.
Four adjustment potentiometers are provided. They are VOLTAGE ADJUST, GAIN, STABI LITY, and UNDERFREQUENCY ADJUST.
1. Connect an AC Voltage/Frequency meter across wires 11 & 44
at the 50A Main circuit breaker. Verify frequency is between
59-61Hz.
2. On the regulator, set the adjustment pots as follows.
a. Voltage Adjust – Pot-turn fully counterclockwise
b. Gain – turn to midpoint (12 O’clock)
c. Stability – turn to midpoint (12 O’clock)
d. Under Frequency – turn to midpoint (12 O’clock)
3. Start the generator. This adjustment will be done under a no-
load condition.
Figure 3-6. – Typical Voltage Regulator Found on 12.5
kW and 15 kW Units
4. Turn the regulator’s Voltage Adjust pot clockwise to obtain a line
to line voltage of 238-242 VAC.
5. If the red regulator LED is flashing, slowly turn the stability pot
either direction until flashing stops.
ADJUSTMENT PROCEDURE (17.5 KW UNITS): A single red lamp (LED) glows during normal opera-
tion. The lamp will become dim if excitation winding AC output diminishes. It will go out on occurrence of an open condition in the sensing AC output circuit.
An adjustment potentiometer permits the stator AC power winding voltage to be adjusted. Perform this adjustment with the generator running at no-load, and
Page 11
Section 3 DESCRIPTION & COMPONENTS
with a 62 Hz AC frequency (62 Hz equals 3720 rpm). At the stated no-load frequency, adjust to obtain a line-to-line AC voltage of about 252 volts.
CIRCUIT BREAKERS: Each individual outlet on the generator is protected by
a circuit breaker to prevent overload.
ROTOR RESIDUAL MAGNETISM
The generator revolving field (rotor) may be consid­ered to be a permanent magnet. Some “residual” magnetism is always present in the rotor. This residu­al magnetism is sufficient to induce a voltage into the stator AC power windings that is approximately 2-12 volts AC.
FIELD BOOST CIRCUIT
When the engine is cranked during star t-up, the START/STOP RELAY (SSR) will be energized. The normally open contacts of the SSR will close and Wire 15 will supply 12 VDC to Wire 14. Connected to Wire 14 is a resistor (R1) and a diode (D1). The resistor will limit current flow, and the diode will block Voltage Regulator DC output. Once through the resistor and diode it becomes Wire 4, and Wire 4 then connects to the positive brush. The effect is to “flash the field” every time the engine is cranked. Field boost current helps ensure that sufficient “pickup” voltage is avail­able on every startup to turn the Voltage Regulator on and build AC output voltage.
Notice that field boost current is always available dur­ing cranking and running, this is because the SSR is energized the whole time. The diode (D1) prevents or blocks the Voltage Regulators higher DC output from reaching the Wire 14 run circuit.
Field boost voltage is reduced from that of battery voltage by the resistor (R1), and when read with a DC voltmeter will be approximately 9 or 10 volts DC.
OPERATION
STARTUP: When the engine is started, residual plus field boost
magnetism from the rotor induces a voltage into (a) the stator AC power windings, (b) the stator excitation or DPE windings, (c) the stator battery charge wind­ings. In an “on-speed” (engine cranking) condition, residual plus field boost magnetism are capable of creating approximately one-half the unit’s rated volt­age.
ON-SPEED OPERATION: As the engine accelerates, the voltage that is induced
into the stator windings increases rapidly, due to the increasing speed at which the rotor operates.
FIELD EXCITATION: An AC voltage is induced into the stator excitation
(DPE) windings. The DPE winding circuit is completed to the Voltage Regulator, via Wire 2, Excitation Circuit Breaker, Wire 162, and Wire 6. Unregulated alternat­ing current can flow from the winding to the regulator.
The Voltage Regulator “senses” AC power winding output voltage and frequency via stator Wires 11S and 44S.
The regulator changes the AC from the excitation winding to DC. In addition, based on the Wires 11S and 44S sensing signals, it regulates the flow of direct current to the rotor.
The rectified and regulated current flow from the regu­lator is delivered to the rotor windings, via Wire 4, and the positive brush and slip ring. This excitation current flows through the rotor windings and is directed to ground through the negative (-) slip ring and brush, and Wire 0.
The greater the current flow through the rotor wind­ings, the more concentrated the lines of flux around the rotor become.
The more concentrated the lines of flux around the rotor that cut across the stationary stator windings, the greater the voltage that is induced into the stator windings.
Initially, the AC power winding voltage sensed by the regulator is low. The regulator reacts by increasing the flow of excitation current to the rotor until volt­age increases to a desired level. The regulator then maintains the desired voltage. For example, if voltage exceeds the desired level, the regulator will decrease the flow of excitation current. Conversely, if voltage drops below the desired level, the regulator responds by increasing the flow of excitation current.
AC POWER WINDING OUTPUT: A regulated voltage is induced into the stator AC
power windings. When electrical loads are connected across the AC power windings to complete the cir­cuit, current can flow in the circuit. The regulated AC power winding output voltage will be in direct propor­tion to the AC frequency. For example, on units rated 120/240 volts at 60 Hz, the regulator will try to main­tain 240 volts (line-to-line) at 60 Hz. This type of regu­lation system provides greatly improved motor starting capability over other types of systems.
BATTERY CHARGE WINDING OUTPUT: A voltage is induced into the battery charge winding.
Output from these windings is delivered to a Battery Charge Rectifier (BCR2), via Wires 55A, 66A and 77A. The resulting direct current from the BCR is delivered to the unit battery, via Wire 15, a 10 amp fuse, and Wire 13. This output is used to maintain bat­tery state of charge during operation.
10 AMP BATTERY CHARGE WINDING OUTPUT: A voltage is induced into the battery charge winding.
Output from these windings is delivered to a Battery Charge Rectifier (BCR1), via Wires 55, 66 and 77.
Page 12
Section 3
DESCRIPTION & COMPONENTS
The resulting direct current from the BCR is delivered to the 12 VDC receptacle, via Wire 13A, CB1, and Wire 15A. This receptacle allows the capability to recharge a 12 volt DC storage battery with provided battery charge cables.
INSULATION RESISTANCE
The insulation resistance of stator and rotor wind­ings is a measurement of the integrity of the insulat­ing materials that separate the electrical windings from the generator steel core. This resistance can degrade over time or due to such contaminants as dust, dir t, oil, grease and especially moisture. In most cases, failures of stator and rotor windings is due to a breakdown in the insulation. In many cases, a low insulation resistance is caused by moisture that collects while the generator is shut down. When problems are caused by moisture buildup on the windings, they can usually be corrected by drying the windings. Cleaning and drying the windings can usu­ally eliminate dirt and moisture built up in the genera­tor windings.
THE MEGOHMMETER
GENERAL: A megohmmeter, often called a “megger”, consists of
a meter calibrated in megohms and a power supply. Use a power supply of 500 volts when testing stators or rotors. DO NOT APPLY VOLTAGE LONGER THAN ONE (1) SECOND.
TESTING STATOR INSULATION: All parts that might be damaged by the high meg-
ger voltages must be disconnected before testing. Isolate all stator leads (Figure 3-9) and connect all of the stator leads together. FOLLOW THE MEGGER MANUFACTURER’S INSTRUCTIONS CAREFULLY.
Use a megger power setting of 500 volts. Connect one megger test lead to the junction of all stator leads, the other test lead to frame ground on the stator can. Read the number of megohms on the meter.
The MINIMUM acceptable megger reading for stators may be calculated using the following formula:
windings as outlined “Stator Insulation Tests”. Also test between parallel windings. See “Test
Between Windings” on next page.
TESTING ROTOR INSULATION: Apply a voltage of 500 volts across the rotor positive
(+) slip ring (nearest the rotor bearing), and a clean frame ground (i.e. the rotor shaft). DO NOT EXCEED 500 VOLTS AND D O NOT APPLY VOLTAGE LON GER THA N 1 SEC OND. FOL LOW T HE MEGGER MANUFACTURER’S INSTRUCTIONS CAREFULLY.
ROTOR MINIMUM INSULATION RESISTANCE:
1.5 megohms
CAUTION: Before attempting to measure
*
Insulation resistance, first disconnect and Isolate all leads of the winding to be tested. Electronic components, diodes, surge protec
­tors, relays, Voltage Regulators, etc., can be destroyed if subjected to high megger volt­ages.
HI-POT TESTER: A “Hi-Pot” tester is shown in Figure 3-8. The model
shown is only one of many that are commercially available. The tester shown is equipped with a voltage selector switch that permits the power supply voltage to be selected. It also mounts a breakdown lamp that will illuminate to indicate an insulation breakdown dur­ing the test.
MINIMUM INSULATION RESISTANCE = (in “Megohms”)
GENERATOR RATED VOLTS
__________________________
1000
+1
EXAMPLE: Generator is rated at 120 volts AC. Divide “120” by “1000” to obtain “0.12”. Then add “1” to obtain “1.12” megohms. Minimum insulation resistance for a 120 VAC stator is 1.12 megohms.
If the stator insulation resistance is less than the cal­culated minimum resistance, clean and dry the stator. Then, repeat the test. If resistance is still low, replace the stator.
Use the Megger to test for shorts between isolated
Figure 3-8. – One Type of Hi-Pot Tester
STATOR INSULATION RESISTANCE TEST
GENERAL: Units with air-cooled engines are equipped with (a)
center tapped AC power windings, (b) an excitation
Page 13
Section 3
11
44
22
77A
55
77
6
2
66
66A
55A
44S
11S
PIN
LOCATION
6
PIN
LOCATION
7
PIN
LOCATION
1
PIN
LOCATION
12
2
77A
66A
55A
44S
11S
0
4
77
66
55
6
DESCRIPTION & COMPONENTS
or DPE winding, (c) a center tapped battery charge winding and (d) a 10 Amp center tapped battery charge winding. Insulation tests of the stator con­sist of (a) testing all windings to ground, (b) testing between isolated windings, and (c) testing between parallel windings. Figure 3-9 is a pictorial representa­tion of the various stator leads on units with air-cooled engine.
TESTING ALL STATOR WINDINGS TO GROUND:
1. Disconnect stator output leads Wire 11 and Wire 44 from the
generator 50A circuit breaker.
2. Remove stator output lead Wire 22 from the neutral terminal
on the back of the 50A outlet.
3. Disconnect the C1 connector from the bottom of the control
panel. See Figure 3-10. The C1 connector is on the right when
facing the control panel.
cleaning and drying, the stator fails the second test, the stator assembly should be replaced.
6. Now proceed to th e C1 connector ( Fem ale side – Just
removed). Each winding will be individually tested for a short
to ground. Insert a large paper clip (or similar item) into the C1
connector at the following pin locations:
Pin
Location
1 11S Sense Lead Power
2 44S Sense Lead Power
3 55A Battery Charge
4 66A Battery Charge
5 77A Battery Charge
6 2 Excitation
7 6 Excitation
8 55 10 Amp Battery Charge
9 66 10 Amp Battery Charge
10 77 10 Amp Battery Charge
11 4
12 0
Wire
Number
Winding
(Positive lead to Brush)
(Negative lead to Brush)
Figure 3-9. – Stator Winding Leads
4. Connect the terminal ends of Wires 11, 22, and 44 together.
Make sure the wire ends are not touching any part of the gen-
erator frame or any terminal.
5. Connect the red test probe of the Hi-Pot tester to the joined
terminal ends of stator leads 11, 22, and 44. Connect the black
tester lead to a clean frame ground on the stator can. With tes
ter leads connected in this manner, proceed as follows:
a. Turn the Hi-Pot tester switch OFF. b. Plug the tester cord into a 120 volt AC wall sock
et and set its voltage selector switch to “1500 volts”.
c. Turn the tester switch ON and observe the
breakdown lamp on tester. DO NOT APPLY VOLTAGE LONGER THAN 1 SECOND. After one (1) second, turn the tester switch OFF.
If the breakdown lamp comes on during the one-sec­ond test, the stator should be cleaned and dried. After cleaning and drying, repeat the insulation test. If, after
Page 14
Next refer to Steps 5a through 5c of the Hi-Pot proce­dure.
Example: Insert paper clip into Pin 1, Hi-Pot from Pin 1 (Wire 11S) to ground. Proceed to Pin 2, Pin 3, etc. through Pin 10.
-
Figure 3-10. – C1 Connector Pin Location Numbers
(Female Side, Located to the Right When Facing the
-
Control Panel)
TEST BETWEEN WINDINGS:
1. Insert a paper clip into Pin Location 3 (Wire 55A). Connect
the red tester probe to the paper clip. Connect the black tes-
ter probe to Stator Lead 11. Refer to Steps 5a through 5c of
“TESTING ALL STATOR WINDINGS TO GROUND”.
2. Repeat Step 1 at Pin Location 6 (Wire 2) and Stator Lead 11.
Section 3
POSITIVE (+) TEST LEAD
DESCRIPTION & COMPONENTS
3. Repeat Step 1 at Pin Location 8 (Wire 55) and Stator Lead 11.
For the following steps (4 through 6) an additional paper clip (or similar item) will be needed:
4. Insert a paper clip into Pin Location 3 (Wire 55A). Connect the
red tester probe to the paper clip. Insert additional paper clip
into Pin Location 6 (Wire 2). Connect the black tester probe to
this paper clip. Refer to Steps 5a through 5c of “TESTING ALL
STATOR WINDINGS TO GROUND” on the previous page.
5. Insert a paper clip into Pin Location 3 (Wire 55A). Connect the
red tester probe to the paper clip. Insert additional paper clip
into Pin Location 8 (Wire 55). Connect the black tester probe to
this paper clip. Refer to Steps 5a through 5c of “TESTING ALL
STATOR WINDINGS TO GROUND” on the previous page.
6. Insert a paper clip into Pin Location 6 (Wire 2). Connect the red
tester probe to the paper clip. Insert the additional paper clip
into Pin Location 8 (Wire 55). Connect the black tester probe to
this paper clip. Refer to Steps 5a through 5c of “TESTING ALL
STATOR WINDINGS TO GROUND” on the previous
page.
ROTOR INSULATION RESISTANCE TEST
Before attempting to test rotor insulation, the brush holder must be completely removed. The rotor must be completely isolated from other components before starting the test. Attach all leads of all stator windings to ground.
1. Connect the red tester lead to the positive (+) slip ring (nearest
the rotor bearing).
2. Connect the black tester probe to a clean frame ground, such
as a clean metal part of the rotor shaft.
3. Turn the tester switch OFF.
4. Plug the tester into a 120 volts AC wall socket and set the volt
age switch to “1500 volts”.
5. Turn the tester switch “On” and make sure the pilot light has
turned on.
6. Observe the breakdown lamp, then turn the tester switch OFF.
DO NOT APPLY VOLTAGE LONGER THAN ONE (1) SECOND.
If the breakdown lamp came on during the one (1) second test, cleaning and drying of the rotor may be necessary. After cleaning and drying, repeat the insu­lation breakdown test. If breakdown lamp comes on during the second test, replace the rotor assembly.
CLEANING THE GENERATOR
Caked or greasy dirt may be loosened with a soft brush or a damp cloth. A vacuum system may be used to clean up loosened dirt. Dust and dirt may also be removed using dry, low-pressure air (25 psi maximum).
CAUTION: Do not use sprayed water to clean
*
the generator. Some of the water will be retained on generator windings and terminals, and may cause very serious problems.
DRYING THE GENERATOR
To dry a generator, proceed as follows:
1. Open the generator main circuit breaker. NO ELECTRICAL
LOADS MUST BE APPLIED TO THE GENERATOR WHILE
DRYING.
-
Figure 3-10. – Testing Rotor Insulation
2. Provide an external source to blow warm, dry air through the
generator interior (around the rotor and stator windings. DO
NOT EXCEED 185° F. (85° C.).
3. Start the generator and let it run for 2 or 3 hours.
4. Shut the generator down and repeat the stator and rotor insula
tion resistance tests.
Page 15
-
Section 4
DIP SWITCH
1) ON
2) OFF
J2 CONNECTOR
J1 CONNECTOR
POTENTIOMETERS
RESPONSE
RECOVERY
DAMPEN
SENSING
LED
21
ON
ENGINE DC CONTROL SYSTEM
PRINTED CIRCUIT BOARD
GENERAL: The printed board is responsible for cranking, startup,
running and shutdown operations. The board intercon­nects with other components of the DC control system to turn them on and off at the proper times. It is pow­ered by fused 12 VDC power from the unit battery.
CIRCUIT BOARD CONNECTIONS: The circuit board mounts a 12-pin receptacle (J2) and
a 5-pin receptacle (J1). Figure 4-2 shows the 12-pin receptacle (J2), the associated wires and the function of each pin and wire.
DIP SWITCH POSITIONS:
Note: These switches must remain in the positions set at the factory.
1. Stepper Motor Rotation
a. Switch set to ON for clockwise rotation (Factory
Position).
b. Switch set to OFF for counterclockwise rotation.
2. Frequency Setting
a. Switch set to OFF fo r 60 Her tz (Factor y
Position).
b. Switch set to ON for 50 Hertz.
TERMINAL WIRE FUNCTION
1 15B 12 VDC input when the Start Stop Relay
2 83 Ground input when the idle control switch
3 TR1 AC voltage input from the idle control
4 0 Common ground for the PCB
5 167 12 VDC input when SW1 is placed in the
6 TR2 AC voltage input from the idle control
7 86 Fault shutdown circuit. When grounded
8 229 Switched to ground for Start Stop Relay
9 NOT USED
10 44S AC input for frequency control.
11 NOT USED
12 11S AC input for frequency control. 11S/44S
Note: J1 Connector is utilized for governor control.
(SSR) is energized.
(SW2) is placed in the closed position
transformers.
Start position. Ground input when SW1 is placed in the Stop position.
transformers.
by closure of the Low Oil pressure switch (LOP) engine will shut down.
(SSR) operation.
11S/44S 240VAC
240VAC
Figure 4-2. – Receptacle J2
BATTERY
RECOMMENDED BATTERY: When anticipated ambient temperatures will be con-
sistently above 32° F. (0° C.), use a 12 volts Type U1 storage battery capable of delivering at least 300 cold cranking amperes.
Page 16
Figure 4-1. – Printed Circuit Board
ENGINE DC CONTROL SYSTEM
VOLTAGE
REGULATOR
TERMINAL BOARD
(TB1)
TERMINAL BOARD
(TB2)
START STOP RELAY
(SSR)
STARTER CONTACTOR RELAY
(SCR)
IDLE CONTROL
TRANSFORMERS
(ICT)
PRINTED CIRCUIT
BOARD
10 AMP FUSE (F1)
LOCATED IN REAR OF CONTROL PANEL
DIODE (D1)
RESISTOR (R1)
CONNECTOR
(C2)
CONNECTOR
(C1)
50 AMP CIRCUIT BREAKER
EXCITATION CIRCUIT
BREAKER (CB2)
10 AMP AUTO RESET
BREAKER (CB1)
BATTERY CHARGE RECTIFIERS
(BCR1 & BCR2)
CONTROL PANEL COMPONENT IDENTIFICATION
Section 4
Page 17
Section 4
PIN
LOCATION
6
PIN
LOCATION
7
C1 FEMALE SIDE
C2 FEMALE SIDE
C1 MALE SIDE
C2 MALE SIDE
PIN
LOCATION
1
PIN
LOCATION
12
2
77A
66A
55A
44S
11S
0
4
77
66
55
6
PIN
LOCATION
7
PIN
LOCATION
6
0
4
77
66
55
6
2
77A
66A
55A
44S
11S
PIN
LOCATION
6
PIN
LOCATION
7
PIN
LOCATION
1
PIN
LOCATION
12
13
86
167
0
15
18
0
13
15
16
17
14
PIN
LOCATION
7
PIN
LOCATION
6
0
13
15
16
17
14
13
86
167
0
15
18
TERMINAL BLOCK
(TB1)
TERMINAL BLOCK
(TB2)
86 15B
167
BLK
0 229
83
BLK
TR2
TR1
44S
11S
ENGINE DC CONTROL SYSTEM
Page 18
NOTES
Page 19
Section 4
VOLTAGE
ELECTRONIC
REGULATOR
11S
162
0
6
44S
4
6
5
4
3
2
1
BCR2
77A
15
66A
564
1012
SSR
9
18
PRINTED CIRCUIT
BOARD
CONTROL
12 1011 9 278 6 45 3J21
J1
15B83TR10167
TR286229
44S
11S
ACTUATOR
GOVERNOR
11B
0
22
50A
C.B.
30A
C.B.
FIELD
BATTERY CHARGE WINDING
55A
10A BATTERY CHARGE WINDING
77
55
11S
112244
44S
66
77A 66A
62 4 0
C1-12C1-11C1-7C1-6C1-1
C1-2
C1-4
C1-9
C1-8
C1-10
C1-5
C1-3
77
66
BCR1
13A
CB2
83
167
229
15B
0
86
SW2
C2-8
C2-3
C2-4
C2-10
C2-5
C2-7
C2-1
C2-2
C2-12
16
SC
CB1
15A 0
C2-6
C2-11
C2-9
13
13
F1
SCR
22914
15B
18
01515 15
0
0
0
167
15
15
86
0
14
17
18
13
13
16
14
14
14
14
86
13
15
15
1515
15
15
15
15
14
18 18
167167
8686
4
4
162
11S
44S
22
11
0
44
11
0
22
4444
77A
77
66A
66
77
0
2
2
2
6
6
6
11S 4 044S
RED
BLK
BLK
83 0
0
00
0
229
15B
15
15
15
0
17
17
4
120/240V
POWER WINDING
DPE WINDING
I.C.T.
I.C.T.
I.C.
R1D1
TB1
TB2
12Vdc
BA
13
14
13
ENGINE DC CONTROL SYSTEM
Battery voltage is supplied to components of the control system from the unit BATTERY via the RED battery cable connected to the contacts of the starter contactor (SC), wire 13, a 10 Amp fuse (F1), and Wire 15.
Wire 13 is unfused battery supply voltage and is connected to the contacts of the Starter Contactor Relay (SCR). Wire 15 12 VDC fused battery supply voltage is supplied to the SCR coil, it goes through the coil and comes out
as wire 17 12 VDC, wire 17 is connected to the Start-Run-Stop switch (SW1) and is held open to ground. No cur­rent flows through the circuit and the SCR is de-energized.
Wire 15 12 VDC fused battery supply voltage is supplied to SW1 and is held open to Wire 167. Wire 15 12 VDC fused battery supply voltage is supplied to the Start-Stop Relay (SSR) it goes through the coil
and comes out as wire 229 12 VDC, wire 229 is connected to the printed circuit board and is held open to ground. No current flows through the circuit and the SSR is de-energized.
Page 20
CIRCUIT CONDITION - REST:
Section 4
RESET
RESET
TEST
TEST
18
IM2
SP2
IM1
SP1
0 0 44C2211C22
C.B.
0000
222222
44D11D44B
11B
11B
0
11A44A
22
20A
C.B. 20A30A
C.B.
30A
C.B.
30A
C.B.
50A
C.B.
30A
C.B.
0
167
SW1
FSS
LOP
0
15
17
0
17
15
0
0
86
14
C2-8
C2-3
C2-4
C2-10
C2-5
C2-7
C2-1
C2-2
15
C2-12
0
0
16
SC
BATTERY
BLACK
RED
SC
SM
12V
C2-6
C2-11
C2-9
13
13
SCR
0
0
167
15
15
86
0
14
17
18
13
13
16
86
15
15
22
11
0
44
11
0
22
44
11
0
22
44
17
17
SCR - STARTER CONTACTOR RELAY
SW1 - START-RUN-STOP SWITCH
SSR - START / STOP RELAY
SP2 - SPARK PLUG, CYL. 2
SP1 - SPARK PLUG, CYL. 1
SM - STARTER MOTOR
SC - STARTER CONTACTOR
R1 - 25 OHM, 25W RESISTOR
IM2 - IGNITION MODULE, CYL. 2
FSS - FUEL SHUT OFF SOLENOID
CB1 - 10AMP AUTO RESET BREAKER
LOP - LOW OIL PRESSURE
IM1 - IGNITION MODULE, CYL. 1
GND - GROUND BAR
F1 - 10A FUSE
D2, D3 - ENGINE SHUTDOWN DIODE
BA - BRUSH ASSEMBLY
LEGEND
120/240V
50A
TWISTLOK TWISTLOK
120V/30A
TWISTLOK
120V/30A
DUPLEX
120V 120V
GFCI
30A
120/240V
D2
D3
CB2 - 5AMP AUTO RESET BREAKER D1 - 600V 12A DIODE
BCR2 - BATTERY CHARGE RECTIFIER
BCR1 - BATTERY CHARGE RECTIFIER, 10A
I.C.T. - IDLE CONTROL TRANSFORMER
SW2 - IDLE CONTROL SWITCH TB1, TB2 - TERMINAL BLOCK
13
= 12 VDC SUPPLY
= 12 VDC CONTROL
= AC POWER
= GROUND
ENGINE DC CONTROL SYSTEM
Wire 15 12 VDC fused battery supply voltage is supplied to the normally open contacts of the SSR. One set of normally open contacts are connected to Wire 15B, the other set of normally open contacts are connected to Wire
14. The SSR is de-energized and no voltage is available through the contacts. Wire 15 12 VDC fused battery supply voltage is supplied to the Battery Charge Rectifier number 2 (BCR2). This is
a return current path for battery charging. No current flows at this time. Wire 18 connects to the ignition magnetos and to the normally closed contacts of the SSR. The normally closed
contacts are also connected to Wire 0, Wire 0 is frame ground. The SSR is de-energized and the magnetos are grounded out at this time, no spark is available.
Page 21
Section 4
VOLTAGE
ELECTRONIC
REGULATOR
11S
162
0
6
44S
4
6
5
4
3
2
1
BCR2
77A
15
66A
564
1012
SSR
9
18
PRINTED CIRCUIT
BOARD
CONTROL
12 1011 9 278 6 45 3J21
J1
15B83TR10167
TR286229
44S
11S
ACTUATOR
GOVERNOR
11B
0
22
50A
C.B.
30A
C.B.
FIELD
BATTERY CHARGE WINDING
55A
10A BATTERY CHARGE WINDING
77
55
11S
112244
44S
66
77A 66A
62 4 0
C1-12C1-11C1-7C1-6C1-1
C1-2
C1-4
C1-9
C1-8
C1-10
C1-5
C1-3
77
66
BCR1
13A
CB2
83
167
229
15B
0
86
SW2
C2-8
C2-3
C2-4
C2-10
C2-5
C2-7
C2-1
C2-2
C2-12
16
SC
CB1
15A 0
C2-6
C2-11
C2-9
13
13
F1
SCR
22914
15B
18
01515 15
0
0
0
167
15
15
86
0
14
17
18
13
13
16
14
14
14
14
86
13
15
15
1515
15
15
15
15
14
18 18
167167
8686
4
4
162
11S
44S
22
11
0
44
11
0
22
4444
77A
77
66A
66
77
0
2
2
2
6
6
6
11S 4 044S
RED
BLK
BLK
83 0
0
00
0
229
15B
15
15
15
0
17
17
4
120/240V
POWER WINDING
DPE WINDING
I.C.T.
I.C.T.
I.C.
R1D1
TB1
TB2
12Vdc
BA
13
14
13
ENGINE DC CONTROL SYSTEM
With the Start-Run-Stop Switch (SW1) held in the start position, Wire 17 from the Starter Contactor Relay (SCR) is now connected to Wire 0 which is frame ground. This allows current to flow and the SCR is energized. The SCR contacts close connecting Wire 13 battery power to Wire 16. Wire 16 now supplies battery power to the starter contactor (SC) on the Starter Motor (SM), the SC is energized and its contacts close, battery power is available to the Starter Motor (SM) and the engine is cranking.
Page 22
CIRCUIT CONDITION - START:
Section 4
RESET
RESET
TEST
TEST
18
IM2
SP2
IM1
SP1
0 0 44C2211C22
C.B.
0000
222222
44D11D44B
11B
11B
0
11A44A
22
20A
C.B. 20A30A
C.B.
30A
C.B.
30A
C.B.
50A
C.B.
30A
C.B.
0
167
SW1
FSS
LOP
0
15
17
0
17
15
0
0
86
14
C2-8
C2-3
C2-4
C2-10
C2-5
C2-7
C2-1
C2-2
15
C2-12
0
0
16
SC
BATTERY
BLACK
RED
SC
SM
12V
C2-6
C2-11
C2-9
13
13
SCR
0
0
167
15
15
86
0
14
17
18
13
13
16
86
15
15
22
11
0
44
11
0
22
44
11
0
22
44
17
17
SCR - STARTER CONTACTOR RELAY
SW1 - START-RUN-STOP SWITCH
SSR - START / STOP RELAY
SP2 - SPARK PLUG, CYL. 2
SP1 - SPARK PLUG, CYL. 1
SM - STARTER MOTOR
SC - STARTER CONTACTOR
R1 - 25 OHM, 25W RESISTOR
IM2 - IGNITION MODULE, CYL. 2
FSS - FUEL SHUT OFF SOLENOID
CB1 - 10AMP AUTO RESET BREAKER
LOP - LOW OIL PRESSURE
IM1 - IGNITION MODULE, CYL. 1
GND - GROUND BAR
F1 - 10A FUSE
D2, D3 - ENGINE SHUTDOWN DIODE
BA - BRUSH ASSEMBLY
LEGEND
120/240V
50A
TWISTLOK TWISTLOK
120V/30A
TWISTLOK
120V/30A
DUPLEX
120V 120V
GFCI
30A
120/240V
D2
D3
CB2 - 5AMP AUTO RESET BREAKER D1 - 600V 12A DIODE
BCR2 - BATTERY CHARGE RECTIFIER
BCR1 - BATTERY CHARGE RECTIFIER, 10A
I.C.T. - IDLE CONTROL TRANSFORMER
SW2 - IDLE CONTROL SWITCH TB1, TB2 - TERMINAL BLOCK
13
= 12 VDC SUPPLY
= 12 VDC CONTROL
= AC POWER
= GROUND
ENGINE DC CONTROL SYSTEM
With the Start-Run-Stop Switch (SW1) held in the start position, Wire 15 is now connected to Wire 167. Wire 15 supplies fused battery power via Wire 167 to the Printed Circuit Board. This 12 VDC input signals the Printed Circuit Board to internally ground Wire 229 which is connected to the coil of the Start-Stop-Relay (SSR). This action allows current to flow and the SSR is energized. The normally open contacts close supplying battery power from Wire 15 to Wire 14. Wire 14 supplies power to the Fuel Shutoff Solenoid (FSS), it is energized and fuel is available to the engine. Wire 14 supplies power through Resistor (R1) and Diode (D1) to Wire 4, Wire 4 connects to the field or the Rotor assembly and is used as Field Boost. The second set of normally open contacts also close connecting Wire 15 12 VDC battery supply to Wire 15B. Wire 15B now supplies 12 VDC to the printed circuit board for use with the governor control system. The normally closed contacts now open, Wire 18 is no longer con­nected to Wire 0 and the magnetos are no longer grounded out and can produce spark.
Page 23
Section 4
VOLTAGE
ELECTRONIC
REGULATOR
11S
162
0
6
44S
4
6
5
4
3
2
1
BCR2
77A
15
66A
564
1012
SSR
9
18
PRINTED CIRCUIT
BOARD
CONTROL
12 1011 9 278 6 45 3J21
J1
15B83TR10167
TR286229
44S
11S
ACTUATOR
GOVERNOR
11B
0
22
50A
C.B.
30A
C.B.
FIELD
BATTERY CHARGE WINDING
55A
10A BATTERY CHARGE WINDING
77
55
11S
112244
44S
66
77A 66A
62 4 0
C1-12C1-11C1-7C1-6C1-1
C1-2
C1-4
C1-9
C1-8
C1-10
C1-5
C1-3
77
66
BCR1
13A
CB2
83
167
229
15B
0
86
SW2
C2-8
C2-3
C2-4
C2-10
C2-5
C2-7
C2-1
C2-2
C2-12
16
SC
CB1
15A 0
C2-6
C2-11
C2-9
13
13
F1
SCR
22914
15B
18
01515 15
0
0
0
167
15
15
86
0
14
17
18
13
13
16
14
14
14
14
86
13
15
15
1515
15
15
15
15
14
18 18
167167
8686
4
4
162
11S
44S
22
11
0
44
11
0
22
4444
77A
77
66A
66
77
0
2
2
2
6
6
6
11S 4 044S
RED
BLK
BLK
83 0
0
00
0
229
15B
15
15
15
0
17
17
4
120/240V
POWER WINDING
DPE WINDING
I.C.T.
I.C.T.
I.C.
R1D1
TB1
TB2
12Vdc
BA
13
14
13
ENGINE DC CONTROL SYSTEM
Once the engine has started the Start-Run-Stop Switch (SW1) is released and will be in the run position, at this point SW1 is not activated. This action will de-energize the Starter Contactor Relay (SCR) causing the Starter Motor to disengage.
Printed circuit board action keeps Wire 229 held to ground this action holds the Start-Stop Relay (SSR) energized. With the SSR energized Wire 14 maintains 12 VDC to the Fuel Shutoff Solenoid. Once the Voltage Regulator starts functioning the field boost circuit is no longer a factor in operation. With the SSR energized Wire 15B main­tains 12 VDC to the printed circuit board. With the SSR energized Wire 18 is not grounded and the magnetos con­tinue to produce spark.
The two independent battery charge windings are now producing AC voltage and supplying this to BCR1 and BCR2. The AC voltage is rectified through BCR1 and used to supply DC voltage to the 12 VDC accessory outlet. The AC voltage is rectified through BCR2 and used to supply DC voltage to the battery for battery charging.
Page 24
CIRCUIT CONDITION - RUN:
Section 4
RESET
RESET
TEST
TEST
18
IM2
SP2
IM1
SP1
0 0 44C2211C22
C.B.
0000
222222
44D11D44B
11B
11B
0
11A44A
22
20A
C.B. 20A30A
C.B.
30A
C.B.
30A
C.B.
50A
C.B.
30A
C.B.
0
167
SW1
FSS
LOP
0
15
17
0
17
15
0
0
86
14
C2-8
C2-3
C2-4
C2-10
C2-5
C2-7
C2-1
C2-2
15
C2-12
0
0
16
SC
BATTERY
BLACK
RED
SC
SM
12V
C2-6
C2-11
C2-9
13
13
SCR
0
0
167
15
15
86
0
14
17
18
13
13
16
86
15
15
22
11
0
44
11
0
22
44
11
0
22
44
17
17
SCR - STARTER CONTACTOR RELAY
SW1 - START-RUN-STOP SWITCH
SSR - START / STOP RELAY
SP2 - SPARK PLUG, CYL. 2
SP1 - SPARK PLUG, CYL. 1
SM - STARTER MOTOR
SC - STARTER CONTACTOR
R1 - 25 OHM, 25W RESISTOR
IM2 - IGNITION MODULE, CYL. 2
FSS - FUEL SHUT OFF SOLENOID
CB1 - 10AMP AUTO RESET BREAKER
LOP - LOW OIL PRESSURE
IM1 - IGNITION MODULE, CYL. 1
GND - GROUND BAR
F1 - 10A FUSE
D2, D3 - ENGINE SHUTDOWN DIODE
BA - BRUSH ASSEMBLY
LEGEND
120/240V
50A
TWISTLOK TWISTLOK
120V/30A
TWISTLOK
120V/30A
DUPLEX
120V 120V
GFCI
30A
120/240V
D2
D3
CB2 - 5AMP AUTO RESET BREAKER D1 - 600V 12A DIODE
BCR2 - BATTERY CHARGE RECTIFIER
BCR1 - BATTERY CHARGE RECTIFIER, 10A
I.C.T. - IDLE CONTROL TRANSFORMER
SW2 - IDLE CONTROL SWITCH TB1, TB2 - TERMINAL BLOCK
13
= 12 VDC SUPPLY
= 12 VDC CONTROL
= AC POWER
= GROUND
= IDLE CONTROL TRANSFORMER OUTPUT
ENGINE DC CONTROL SYSTEM
The printed circuit board is supplied with AC voltage from Wires 11S and 44S, this voltage /frequency signal is used by the printed circuit board for governor control operation.
When the Idle Control Switch (SW2) is activated to the “ON” position Wire 83 from the printed circuit board will be connected to Wire 0 frame ground. There are two Idle Control Transformers (ICT) that sense current flow off the main power windings. The voltage signal from the ICT’s connect to the Printed Circuit Board via Wires TR1/TR2 and are used for sensing load on the generator. With no-load on the generator there is no current supplied from the ICT’s and the engine will run at a lower RPM. When a load is applied to the generator the ICT’s supply a voltage signal to the Printed Circuit Board and the engine RPM will be increased to running RPM approximately 3600RPM.
Page 25
Loading...
+ 63 hidden pages