Guardian Technologies 4270 User Manual

DIAGNOSTIC REPAIR MANUAL
DIAGNOSTIC REPAIR MANUAL
QUIETPACT®75D
RECREATIONAL VEHICLE GENERATOR
MODEL 4270
SAFETY
DANGER! UNDER THIS HEADING WILL BE FOUND SPECIAL INSTRUCTIONS WHICH, IF NOT COM­PLIED WITH, COULD RESULT IN PERSONAL INJURY OR DEATH.
CAUTION! Under this heading will be found special instructions which, if not complied with, could result in damage to equipment and/or property.
NOTICE TO USERS OF THIS MANUAL
This SERVICE MANUAL has been written and published by Generac to aid our dealers, mechanics, and company service personnel when servicing the products described herein.
It is assumed that these personnel are familiar with the servicing procedures for these products, or similar products manufactured and marketed by Generac; that they have been trained in the recommended servic­ing procedures for these products, including the use of common hand tools, special Generac tools, or tools from other suppliers.
Generac could not possibly know of and advise the service trade of all conceivable procedures by which a service might be performed and of the possible hazards and/or results of each method. Generac has not undertaken any such wide evaluation. Therefore, anyone who uses a procedure or tool not recommended by Generac, must ensure that neither personal safety nor the products safety will be endangered by the service procedure selected.
All information, illustrations and specifications in this manual are based on the latest product information available at the time of publication.
When working on these products, remember that the electrical system and engine ignition system are capa­ble of violent and damaging short circuits or severe electrical shocks. If work must be done where electrical terminals could be grounded or touched, the battery cables should be disconnected at the battery.
Any time the intake or exhaust openings of the engine are exposed during service, they should be covered to prevent accidental entry of foreign material. Entry of such materials will result in extensive damage when the engine is started.
During any maintenance procedure, replacement fasteners must have the same measurements and strength as the fasteners that were removed. Metric bolts and nuts have numbers that indicate their strength. Customary bolts use radial lines to indicate strength, while most customary nuts do not have strength mark­ings. Mismatched or incorrect fasteners can cause damage, malfunction and possible injury.
REPLACEMENT PARTS
Components on Generac recreational vehicle generators are designed and manufactured to comply with Recreational Vehicle Industry Association (RVIA) Rules and Regulations to minimize the risk of fire or explo­sion. The use of replacement parts that are not in compliance with such Rules and Regulations could result in a fire or explosion hazard. When servicing this equipment, It is extremely important that all components be properly installed and tightened. If parts are improperly installed or tightened, sparks could ignite fuel vapors from fuel system leaks.
Table of Contents
Page 1
SAFETY ............................ INSIDE FRONT COVER
SECTION 1:
GENERATOR FUNDAMENTALS ...................... 3-7
MAGNETISM ................................................................ 3
ELECTROMAGNETIC FIELDS .................................... 3
ELECTROMAGNETIC INDUCTION .............................. 3
A SIMPLE AC GENERATOR ........................................ 4
A MORE SOPHISTICATED AC GENERATOR ............ 4
FIELD BOOST .............................................................. 6
GENERATOR AC CONNECTION SYSTEM ................ 6
SECTION 2:
MAJOR GENERATOR COMPONENTS............ 8-11
ROTOR ASSEMBLY ...................................................... 8
STATOR ASSEMBLY .................................................... 8
BRUSH HOLDER .......................................................... 9
BATTERY CHARGE COMPONENTS .......................... 9
EXCITATION CIRCUIT COMPONENTS ...................... 9
VOLTAGE REGULATOR ............................................ 10
CONTROL PANEL
COMPONENT IDENTIFICATION ................................ 11
SECTION 3:
INSULATION RESISTANCE TESTS ............ 12-14
EFFECTS OF DIRT AND MOISTURE ........................ 12
INSULATION RESISTANCE TESTERS ...................... 12
DRYING THE GENERATOR ...................................... 12
CLEANING THE GENERATOR .................................. 12
STATOR INSULATION RESISTANCE ........................ 13
TESTING ROTOR INSULATION ................................ 14
THE MEGOHMMETER .............................................. 14
SECTION 4:
MEASURING ELECTRICITY ........................ 15-17
METERS ...................................................................... 15
THE VOM .................................................................... 15
MEASURING AC VOLTAGE ...................................... 15
MEASURING DC VOLTAGE ...................................... 15
MEASURING AC FREQUENCY ................................ 16
MEASURING CURRENT ............................................ 16
MEASURING RESISTANCE ...................................... 16
ELECTRICAL UNITS .................................................. 17
OHM’S LAW ................................................................ 17
SECTION 5:
ENGINE DC CONTROL SYSTEM ................ 18-28
INTRODUCTION ........................................................ 18
OPERATIONAL ANALYSIS .................................. 18-23
ENGINE CONTROLLER CIRCUIT BOARD ................ 24
BATTERY .................................................................... 24
14 AMP FUSE ............................................................ 26
PRE-HEAT SWITCH .................................................. 26
START-STOP SWITCH .............................................. 26
STARTER CONTACTOR & MOTOR ........................ 26
ENGINE GOVERNOR .................................................. 27
FUEL INJECTION PUMP ............................................ 27
FUEL NOZZLES/INJECTORS ...................................... 27
GLOW PLUGS .............................................................. 27
ENGINE PROTECTIVE DEVICES .............................. 28
LOW OIL PRESSURE SWITCH .................................. 28
HIGH COOLANT TEMPERATURE SWITCH .............. 28
OVERSPEED PROTECTION ...................................... 28
SECTION 6:
TROUBLESHOOTING FLOWCHARTS .................. 29-36
IF PROBLEM INVOLVES AC OUTPUT ...................... 29
PROBLEM 1 ­VOLTAGE & FREQUENCY ARE BOTH
HIGH OR LOW ............................................................ 29
PROBLEM 2 ­GENERATOR PRODUCES ZERO VOLTAGE OR
RESIDUAL VOLTAGE (5-12 VAC) ........................ 30-31
PROBLEM 3 -
NO BATTERY CHARGE OUTPUT .............................. 31
PROBLEM 4 ­EXCESSIVE VOLTAGE/FREQUENCY DROOP
WHEN LOAD IS APPLIED .......................................... 32
PROBLEM 5 -
PRIMING FUNCTION DOES NOT WORK .................. 32
PROBLEM 6 -
ENGINE WILL NOT CRANK ...................................... 33
PROBLEM 7 ­ENGINE CRANKS BUT WILL NOT START /
RUNS HARD .............................................................. 34
PROBLEM 8 -
ENGINE STARTS THEN SHUTS DOWN .................. 35
PROBLEM 9 -
14 AMP (F1) FUSE BLOWING .................................... 36
SECTION 7:
DIAGNOSTIC TESTS...................................... 37-57
INTRODUCTION ........................................................ 37
TEST 1 -
Check No-Load Voltage And Frequency...................... 37
TEST 2 -
Check Engine Governor.......................................... 37-38
TEST 3 -
Test Excitation Circuit Breaker .................................... 38
TEST 4 -
Fixed Excitation Test/Rotor Amp Draw .................. 38-39
TEST 5 -
Wire Continuity ............................................................ 39
TEST 6 -
Check Field Boost .................................................. 39-40
TEST 7 -
Test Stator DPE Winding ........................................ 40-41
TEST 8 -
Check Sensing Leads/Power Windings ...................... 41
TEST 9 -
Check Brush Leads ................................................ 41-42
TEST 10 -
Check Brushes & Slip Rings ........................................ 42
TEST 11 -
Check Rotor Assembly............................................ 42-43
TEST 12 -
Check Main Circuit Breaker.......................................... 43
TEST 13 -
Check Load Voltage & Frequency................................ 43
TEST 14 -
Check Load Watts & Amperage .................................. 43
TEST 15 -
Check Battery Charge Output ................................ 43-44
TEST 16 -
Check Battery Charge Rectifier.................................... 44
TEST 17 ­Check Battery Charge Windings/
Battery Charge Resistor.......................................... 44-45
TEST 18 -
Try Cranking the Engine .............................................. 45
TEST 19 -
Test Pre-Heat Switch.................................................... 45
TEST 20 -
Check Fuel Pump.................................................... 45-46
TEST 21 -
Check 14 Amp Fuse .................................................... 46
TEST 22 -
Check Battery & Cables................................................ 46
TEST 23 -
Check Power Supply to Circuit Board .................... 46-47
TEST 24 -
Check Start-Stop Switch.......................................... 47-48
TEST 25 -
Check Power Supply to Wire 56 .................................. 48
TEST 26 -
Check Starter Contactor .............................................. 48
TEST 27 -
Check Starter Motor .............................................. 48-50
TEST 28 -
Check Fuel Supply........................................................ 51
TEST 29 -
Check Wire 14 Power Supply ...................................... 51
TEST 30 -
Check Wire 18.............................................................. 51
TEST 31 -
Check Fuel Solenoid .............................................. 51-52
TEST 32 -
Test Pre-Heat Contactor .............................................. 52
TEST 33 -
Test Glow Plugs............................................................ 52
TEST 34 -
Test D1 Diode .............................................................. 52
TEST 35 -
Check Valve Adjustment .............................................. 53
TEST 36 -
Fuel Injector Pump ................................................ 53-54
TEST 37 ­Check Engine / Cylinder Leak Down Test /
Compression Test .................................................. 54-55
TEST 38 -
Check Oil Pressure Switch .......................................... 55
TEST 39 -
Check Circuit Board for Ground .................................. 55
TEST 40 -
Test Water Temperature Switch ............................ 55-56
TEST 41 ­Check Wire 14 and Connecting
Components for Ground .............................................. 56
TEST 42 ­Check Wire 56 and Starter Contactor
for Short to Ground ...................................................... 56
TEST 43 -
Check Wire 15 for Short to Ground .............................. 56
SECTION 8:
ASSEMBLY .................................................... 57-59
MAJOR DISASSEMBLY .............................................. 57
Enclosure/Panel Removal ...................................... 57
Stator Removal ........................................................ 57
Rotor Removal ........................................................ 57
Belt Tensioning ........................................................ 57
Engine Removal ...................................................... 57
Starter Removal ...................................................... 58
Fuel Injector Pump Removal .................................... 58
Radiator Removal .................................................... 58
Re-assembly ............................................................ 58
Belt Tensioning .................................................. 58-59
SECTION 9:
EXPLODED VIEWS / PART NUMBERS ...... 60- 87
SECTION 10:
SPECIFICATIONS & CHARTS ...................... 88-90
MAJOR FEATURES AND DIMENSIONS .................... 88
ENGINE SPECIFICATIONS ........................................ 89
GENERATOR SPECIFICATIONS .............................. 89
ROTOR/STATOR RESISTANCE VALUES ................ 90
TORQUE SPECIFICATIONS ...................................... 90
SECTION 11:
ELECTRICAL DATA ............................................ 92
Page 2
Table of Contents
Section 1
GENERATOR FUNDAMENTALS
MAGNETISM
Magnetism can be used to produce electricity and electricity can be used to produce magnetism.
Much about magnetism cannot be explained by our present knowledge. However, there are certain pat­terns of behavior that are known. Application of these behavior patterns has led to the development of gen­erators, motors and numerous other devices that uti­lize magnetism to produce and use electrical energy.
See Figure 1-1. The space surrounding a magnet is permeated by magnetic lines of force called “flux”. These lines of force are concentrated at the magnet's north and south poles. They are directed away from the magnet at its north pole, travel in a loop and re­enter the magnet at its south pole. The lines of force form definite patterns which vary in intensity depend­ing on the strength of the magnet. The lines of force never cross one another. The area surrounding a magnet in which its lines of force are effective is called a “magnetic field”.
Like poles of a magnet repel each other, while unlike poles attract each other.
Figure 1-1. – Magnetic Lines of Force
ELECTROMAGNETIC FIELDS
All conductors through which an electric current is flowing have a magnetic field surrounding them. This field is always at right angles to the conductor. If a compass is placed near the conductor, the compass needle will move to a right angle with the conductor. The following rules apply:
• The greater the current flow through the conductor, the stronger the magnetic field around the conductor.
• The increase in the number of lines of force is directly proportional to the increase in current flow and the field is distributed along the full length of the conductor.
• The direction of the lines of force around a conduc­tor can be determined by what is called the “right hand rule”. To apply this rule, place your right hand around the conductor with the thumb pointing in the direction of current flow. The fingers will then be pointing in the direction of the lines of force.
NOTE: The “right hand rule” is based on the “cur­rent flow” theory which assumes that current flows from positive to negative. This is opposite the “electron” theory, which states that current flows from negative to positive.
Figure 1-2. – The Right Hand Rule
ELECTROMAGNETIC INDUCTION
An electromotive force (EMF) or voltage can be pro­duced in a conductor by moving the conductor so that it cuts across the lines of force of a magnetic field.
Similarly, if the magnetic lines of force are moved so that they cut across a conductor, an EMF (voltage) will be produced in the conductor. This is the basic principal of the revolving field generator.
Figure 1-3, below, illustrates a simple revolving field generator. The permanent magnet (Rotor) is rotated so that its lines of magnetic force cut across a coil of wires called a Stator. A voltage is then induced into the Stator windings. If the Stator circuit is completed by connecting a load (such as a light bulb), current will flow in the circuit and the bulb will illuminate.
Figure 1-3. – A Simple Revolving Field Generator
Page 3
Section 1 GENERATOR FUNDAMENTALS
A SIMPLE AC GENERATOR
Figure 1-4 shows a very simple AC Generator. The generator consists of a rotating magnetic field called a ROTOR and a stationary coil of wire called a STA­TOR. The ROTOR is a permanent magnet which con­sists of a SOUTH magnetic pole and a NORTH mag­netic pole.
As the MOTOR turns, its magnetic field cuts across the stationary STATOR. A voltage is induced into the STATOR windings. When the magnet's NORTH pole passes the STATOR, current flows in one direction. Current flows in the opposite direction when the mag­net's SOUTH pole passes the STATOR. This con­stant reversal of current flow results in an alternating current (AC) waveform that can be diagrammed as shown in Figure 1-5.
The ROTOR may be a 2-pole type having a single NORTH and a single SOUTH magnetic pole. Some ROTORS are 4-pole type with two SOUTH and two NORTH magnetic poles. The following apply:
1. The 2-pole ROTOR must be turned at 3600 rpm to produce an AC frequency of 60-Hertz, or at 3000 rpm to deliver an AC fre­quency of 50-Hertz.
2. The 4-pole ROTOR must operate at 1800 rpm to deliver a 60­Hertz AC frequency or at 1500 rpm to deliver a 50-Hertz AC frequency.
Figure 1-4. – A Simple AC Generator
Figure 1-5. – Alternating Current Sine Wave
A MORE SOPHISTICATED AC GENERATOR
Figure 1-6 represents a more sophisticated genera­tor. A regulated direct current is delivered into the ROTOR windings via carbon BRUSHES AND SLIP RINGS. This results in the creation of a regulated magnetic field around the ROTOR. As a result, a reg­ulated voltage is induced into the STATOR. Regulated current delivered to the ROTOR is called “EXCITATION” current.
Figure 1-6. – A More Sophisticated Generator
See Figure 1-7 (next page). The revolving magnetic field (ROTOR) is driven by the engine at a constant speed. This constant speed is maintained by a mechanical engine governor. Units with a 2-pole rotor require an operating speed of 3600 rpm to deliver a 60-Hertz AC output. Engine governors are set to maintain approximately 3720 rpm when no electrical loads are connected to the generator.
S
OR
S
V
V
SLIP
GS
OU
U
CU
S
OR
V
S
OR
OR
D
Page 4
(+)
(-)
CURRENT
0
180
ONE CYCLE
VOLTAGE
360
TAT
ROT
MAGNETIC FIEL
T TP
RRENT
240
120
120
BRUSHE
RIN
TAT
TAT
Section 1
GENERATOR FUNDAMENTALS
NOTE: AC output frequency at 3720 rpm will be about 62-Hertz. The “No-Load” is set slightly high to prevent excessive rpm, frequency and voltage droop under heavy electrical loading.
Generator operation may be described briefly as fol­lows:
1. Some “residual” magnetism is normally present in the rotor and is sufficient to induce approximately 7 to 12 VAC Into the sta­tor's AC power windings.
2. During startup, an engine controller circuit board delivers bat­tery voltage to the rotor, via the brushes and slip rings.
a. The battery voltage is called “Field Boost”. b. Flow of direct current through the ROTOR
increases the strength of the magnetic field above that of “residual” magnetism alone.
3. “Residual” plus “Field Boost” magnetism induces a voltage into the Stator excitation (DPE), battery charge and AC Power windings.
4. Excitation winding unregulated AC output is delivered to an electronic voltage regulator, via an excitation circuit breaker.
a. A “Reference” voltage has been pre-set into
the Voltage Regulator.
b. An “Actual” (“sensing”) voltage is delivered
to the Voltage Regulator via sensing leads from the Stator AC power windings.
c. The Regulator “compares” the actual (sens-
ing) voltage to its pre-set reference voltage.
(1) If the actual (sensing) voltage is greater than the pre-set reference voltage, the Regulator will decrease the regulated cur­rent flow to the Rotor.
(2) If the actual (sensing) voltage is less than the pre-set reference voltage, the Regulator will increase the regulated cur­rent flow to the Rotor.
(3) In the manner described, the Regulator maintains an actual (sensing) voltage that is equal to the pre-set reference voltage.
NOTE: The Voltage Regulator also changes the Stator excitation windings alternating current (AC) output to direct current (DC).
5. When an electrical load is connected across the Stator power windings, the circuit is completed and an electrical current will flow.
6. The Rotor's magnetic field also induces a voltage Into the Stator battery charge windings.
a. Battery charge winding AC output is deliv-
ered to a battery charge rectifier (BCR) which changes the AC to direct current (DC).
b. The rectified DC is then delivered to the unit
battery, to maintain the battery in a charged state.
c. A one ohm, 25 watt Resistor is installed in
series with the grounded side of the battery charge circuit.
Page 5
Figure 1-7. – Generator Operating Diagram
Section 1 GENERATOR FUNDAMENTALS
FIELD BOOST
When the engine is cranked during startup, the engine control circuit board Terminals 9, 10, and 11 (Wire 14) are energized with 12 VDC. Connected to a Wire 14 is a resistor (R2) and a diode (D2). Battery current flows through the 20 ohm 12-watt resistor and the field boost diode D2, the voltage is reduced to 3-5 VDC. After passing through R2 and D2 it becomes Wire 4 and current travels to the Rotor via brushes and slip rings. This is called “Field Boost” current.
The effect is to “flash the field” every time the engine is cranked. Field boost current helps ensure that suffi­cient “pickup” voltage is available on every startup to turn the Voltage Regulator on and build AC output voltage.
NOTE: Loss of the Field Boost function may or may not result in loss of AC power winding out­put. If Rotor residual magnetism alone is suffi­cient to turn the Regulator on, loss of Field Boost may go unnoticed. However, if residual magnet­ism alone is not enough to turn the Regulator on, loss of the Field Boost function will result in loss of AC power winding output to the load. The AC output voltage will then drop to a value commen­surate with the Rotor's residual magnetism (about 7-12 VAC).
GENERATOR AC CONNECTION SYSTEM
The generator set is equipped with dual stator AC power windings. These two stator windings supply electrical power to customer electrical loads by means of a dual two-wire connection system.
Generators may be installed to provide the following outputs:
1. 120/240 VAC loads — one load with a maximum total wattage requirement equal to the generator’s rated power output, and 240 VAC across the generator output terminals; or two separate loads, each with a maximum total wattage requirement equal to half of the generator’s rated power output (in watts), and 120VAC across the generator output terminals. Figure 1.9 shows the gen­erator lead wire connections for 120/240 VAC loads.
2. 120 VAC loads only — one load with a maximum total wattage requirement equal to the generator’s rated power output (in watts), and 120V across the generator output terminals. Figure
1.8 shows the generator lead wire connections for 120VAC ONLY.
The generator set can be used to supply electrical power for operating one of the following electrical loads:
• QUIETPACT 75D: 120 and/or 240 VAC, single phase, 60-Hertz electrical loads. These loads can require up to 7500 watts (7.5 kW) of total power, but cannot exceed 62.5 AC amperes of current at 120 VAC or exceed 31.2 AC amperes at 240 VAC.
CAUTION! Do not overload the generator. Some installations may require that electrical loads be alternated to avoid overloading. Applying excessively high electrical loads may damage the generator and may shorten its life. Add up the rated watts of all electrical lighting, appliance, tool and motor loads the generator will power at one time. This total should not be greater than the wattage capacity of the gener­ator. If an electrical device nameplate gives only volts and amps, multiply volts times amps to obtain watts (volts x amps = watts). Some electric motors require more watts of power (or amps of current) for starting than for continu­ous operation.
LINE BREAKERS (120 VAC ONLY): Protects generator’s AC output circuit against
overload (i.e., prevents unit from exceeding wattage/amperage capacity). The circuit breaker rat­ings are as follows:
GENERATOR CONVERSION TO
120 VAC ONLY — DUAL CIRCUITS
NOTE: Conversion of a QUIETPACT™ generator from "120/240 VAC dual voltage" to "120 VAC only - dual circuits" (or vice-versa) requires rerouting wires within the unit enclosure. It is rec­ommended that this conversion be performed by a Generac Authorized Service Dealer.
Figure 1-9 shows the stator power winding connec­tions for 120 VAC only - dual circuits. Two stator power windings are used, with each winding capable of supplying half of the unit's rated wattage/amperage capacity. The circuit from each winding is protected against overload by a line breaker (CB1 and CB1A). Line breakers CB1 and CB1A have a trip rating of 35 amps.
To convert from "120/240 VAC dual voltage" to "120 VAC only - dual circuits", disconnect battery power from the generator and reverse stator lead Wires 33 and 44 as follows:
NOTE: It is necessary to feed stator lead Wires 33 and 44 through grommets on the electrical enclo­sure and engine control box in order to perform the rerouting outlined below. The front and top unit enclosure panels, as well as the user control panel, must be removed to perform this. After re­routing, wires should be properly tied down to prevent chafing or contact with moving internal components
1. Remove stator lead Wire 33, as shown in Figure 1-8, from the ground stud adjacent to the four-position terminal block.
Page 6
Model Circuit Breaker 1 Circuit Breaker 2
QuietPact 75D 35A 35A
Section 1
GENERATOR FUNDAMENTALS
Reroute stator lead 44 from the line side terminal of CB1 (renamed as CB1A in Figure 1-9) to the ground stud location previously occupied by stator lead Wire 33.
2. Move smaller gauge (#18 AWG) Wire labeled #44 (not shown), from the top of CB1A to the top of CB1. Renumber this Wire 11.
3. Reroute stator lead Wire 33, removed in step 1, to the line side terminal on CB1A.
4. Renumber ground Wire 33, located between the four-position terminal block and ground in Figure 1-8, as ground Wire 44, as shown in Figure 1-9.
5. Renumber Wire 44A from Figure 1-8 as Wire 33A in Figure 1-9.
6. Connect a 12 AWG jumper wire between line breakers CB1 and CB1A, as shown in Figure 1-9.
7. Remove the "tie bar" between the two-line breaker switch han­dles.
When connecting vehicle load leads, the following rules apply:
• Connect 120 VAC, single-phase, 60-Hertz, AC electrical loads, requiring up to the trip rating of cir­cuit breaker CB1, across AC output leads T1 (red) and T2 (white).
• Connect 120 VAC, single-phase, 60-Hertz, AC electrical loads, requiring up to the trip rating of cir­cuit breaker CB1A, across AC output leads T3 (black) and T2 (white).
• Try to keep the load balanced between the two cir­cuit breakers and the stator windings.
• The neutral line (T2, white) on all units is a ground­ed neutral.
Do NOT connect electrical loads in excess of any circuit breaker rating, or problems will develop with circuit breaker tripping, which causes a loss of AC output. Also, do NOT exceed the generator's rated wattage capacity. Add the watts or amps of all lighting, appliance, tool, and motor loads the generator will operate at one time. This total should be less than the unit's rated wattage/amperage capacity.
Figure 1-8. – Connection for 120/240 VAC Dual
Voltage
Figure 1-9 - Connection for 120 VAC Only —
Dual Circuits
Page 7
Section 2 MAJOR GENERATOR COMPONENTS
ROTOR ASSEMBLY
The Rotor is sometimes called the “revolving field”, since it provides the magnetic field that induces a voltage into the stationary Stator windings. Slip rings on the Rotor shaft allow excitation current from the voltage regulator to be delivered to the Rotor wind­ings. The Rotor is driven by the engine at a constant speed through a pulley and belt arrangement.
The QUIETPACT 75D utilizes a 2-pole Rotor. This type of Rotor must be driven at 3600 rpm for a 60­Hertz AC output, or at 3000 rpm for a 50-Hertz output.
Slip rings should be cleaned. If dull or tarnished, clean them with fine sandpaper (a 400 grit wet sand­paper is recommended). DO NOT USE ANY METAL­LIC GRIT OR ABRASIVE TO CLEAN SLIP RINGS.
STATOR ASSEMBLY
The Stator is assembled between the front and rear bearing carriers and retained in that position by four Stator studs. Windings included in the Stator assem­bly are (a) dual AC power windings, (b) an excitation or DPE winding, and (c) a battery charge winding. A total of eleven (11) leads are brought out of the Stator as follows:
1. Four (4) Stator power winding output leads (Wires No. 11, 22, 33 and 44). These leads deliver power to connected electrical loads.
2. Stator Power winding “sensing” leads (11 and 22). These leads deliver an “actual voltage signal to the electronic Voltage Regulator.
Page 8
Figure 2-1. Exploded View of Generator
BEARING CARRIER
BEARING CARRIER
BRUSH HOLDER
STATOR
BEARING
ENGINE
ROTOR
BEARING
PULLEY
FLYWHEEL/PULLEY
TENSIONER
BELT
Section 2
MAJOR GENERATOR COMPONENTS
3. Two excitation winding output leads (No. 2 and 6). These leads deliver unregulated excitation current to the voltage regulator.
4. Three (3) battery charge output leads (No. 55, 66 and 77).
Figure 2-2. – Stator Output Leads
BRUSH HOLDER
The brush holder is retained in the rear bearing carri­er by two M5 screws. It retains two brushes, which contact the Rotor slip rings and allow current flow from stationary parts to the revolving Rotor. The posi­tive (+) brush is located nearest the Rotor bearing.
Figure 2-3. – Brush Holder
BATTERY CHARGE COMPONENTS
The Stator incorporates dual battery charge windings. A battery charge rectifier (BCR) changes the AC out­put of these windings to direct current (DC). Battery charge winding output is delivered to the unit battery via the rectifier, a 14 amp fuse and Wire No. 15. A one ohm, 25 watt resistor is connected in series with the grounded side of the circuit.
Figure 2-4. – Battery Charge Circuit
EXCITATION CIRCUIT COMPONENTS
GENERAL: During operation, the Rotor's magnetic field induces a
voltage and current flow into the Stator excitation winding. The resultant AC output is delivered to a voltage regulator via an excitation circuit breaker (CB2).
Figure 2-5. – Schematic: Excitation Circuit
EXCITATION CIRCUIT BREAKER: The excitation circuit breaker (CB2) is self-resetting
and cannot be reset manually. Should the breaker open for any reason, excitation current flow to the Rotor is lost. The unit’s AC output voltage will then drop to a value equal to the Rotor's residual magnet­ism (about 7-12 VAC).
G
GE
OR
G
C
0F
CB2
0K
S
4
6
S
G
O
E
CO
R
CIRCU
D
0N
1
55
5
CR
66
66
r
Page 9
T
ENGIN
NTROLLE
IT BOAR
2
6
11
11
22
22
33
44
55
66
77
Leads 2 & 6 =Stator Excitation Winding Leads 11 & 22 = Voltage Sensing Leads Leads 11 & 22, 33 & 44 = AC Power Windings Leads 55, 66, 77 = Battery Charge Windings
TO BATTERY
B
1
BATTERY CHARGE WINDIN
R
BCR = Battery Charge Rectifie R1 = One Ohm, 25 Watt Resistor
POWER WINDIN
22
11
BRUSHES
ELECTRONI
VOLTA
REGULAT
DPE WINDIN
Section 2 MAJOR GENERATOR COMPONENTS
Figure 2-6. – Excitation Circuit Breaker
VOLTAGE REGULATOR: Six (6) leads are connected to the voltage regulator
as follows:
• Two (2) SENSING leads deliver ACTUAL AC out­put voltage signals to the regulator. These are Wires No. 11 and 22.
• Two (2) leads (4 and 1) deliver the regulated direct current to the Rotor, via brushes and slip rings.
• Two (2) leads (No. 6 and 162) deliver Stator excita­tion winding AC output to the regulator.
The regulator mounts a “VOLTAGE ADJUST” poten­tiometer, used for adjustment of the pre-set REFER­ENCE voltage. An LED will turn on to indicate that SENSING voltage is available to the regulator and the regulator is turned on.
Figure 2-7. – Voltage Regulator
ADJUSTMENT PROCEDURE: With the frequency set at 62.5-Hertz and no load on
the generator, slowly turn the voltage adjust pot on the voltage regulator until 124 VAC is measured. If voltage is not adjustable, proceed to Section 6 ­Troubleshooting.
NOTE: If, for any reason, sensing voltage to the regulator is lost, the regulator will shut down and excitation output to the Rotor will be lost. The AC output voltage will then drop to a value that is equal to Rotor residual magnetism (about 7-12 VAC). Without this automatic shutdown feature, loss of sensing (actual) voltage to the regulator would result in a “full field” or “full excitation” condition and an extremely high AC output volt­age.
NOTE: Adjustment of the regulator's “VOLTAGE ADJUST” potentiometer must be done only when the unit is running at its correct governed no-load speed. Speed is correct when the unit's no-load AC output frequency is about 62.5-Hertz. At the stated frequency, AC output voltage should be about 125 volts.
62
Page 10
2
1
11
22
1
4
6
VOLTAGE ADJUST POT
LED
162
Section 2
MAJOR GENERATOR COMPONENTS
Page 11
CONTROL PANEL COMPONENT IDENTIFICATION
Figure 2-9. – Control Panel Components
Section 3 INSULATION RESISTANCE TESTS
EFFECTS OF DIRT AND MOISTURE
Moisture and dirt are harmful to the continued good operation of any generator set.
If moisture is allowed to remain in contact with the Stator and Rotor windings, some of the moisture will be retained in voids and cracks of the winding insula­tion. This will result in a reduced insulation resistance and, eventually, the unit's AC output will be affected.
Insulation used in the generator is moisture resistant. However, prolonged exposure to moisture will gradu­ally reduce the resistance of the winding insulation.
Dirt can enhance the problem, since it tends to hold moisture into contact with the windings. Salt, as from sea air, contributes to the problem since salt can absorb moisture from the air. When salt and moisture combine, they make a good electrical conductor.
Due to the detrimental affects of dirt and moisture, the generator should be kept as clean and as dry as pos­sible. Rotor and Stator windings should be tested periodically with an insulation resistance tester (such as a megohmmeter or hi-pot tester).
If the insulation resistance is excessively low, drying may be required to remove accumulated moisture. After drying, perform a second insulation resistance test. If resistance is still low after drying, replacement of the defective Rotor or Stator may be required.
INSULATION RESISTANCE TESTERS
Figure 3-1 shows one kind of hi-pot tester. The tester shown has a “Breakdown” lamp that will glow during the test procedure to indicate an insulation break­down in the winding being tested.
Figure 3-1. – One Type of Hi-Pot Tester
DANGER! INSULATION RESISTANCE TESTERS SUCH AS HI-POT TESTERS AND MEGOHMMETERS ARE A SOURCE OF HIGH AND DANGEROUS ELECTRICAL VOLTAGE.
FOLLOW THE TESTER MANUFACTURER'S INSTRUCTIONS CAREFULLY. USE COMMON SENSE TO AVOID DANGEROUS ELECTRICAL SHOCK
DRYING THE GENERATOR
GENERAL: If tests indicate the insulation resistance of a winding
is below a safe value, the winding should be dried before operating the generator. Some recommended drying procedures include (a) heating units and (b) forced air.
HEATING UNITS: If drying is needed, the generator can be enclosed in
a covering. Heating units can then be installed to raise the temperature about 15°-18° F. (8°-10° C.) above ambient temperature.
FORCED AIR: Portable forced air heaters can be used to dry the
generator. Direct the heated air into the generator’s air intake openings. Remove the voltage regulator and run the unit at no-load. Air temperature at the point of entry into the generator should not exceed 150° F. (66° C.).
CLEANING THE GENERATOR
GENERAL: The generator can be cleaned properly only while it is
disassembled. The cleaning method used should be determined by the type of dirt to be removed. Be sure to dry the unit after it has been cleaned.
NOTE: A shop that repairs electric motors may be able to assist you with the proper cleaning of gen­erator windings. Such shops are often experi­enced in special problems such as a sea coast environment, marine or wetland applications, mining, etc.
USING SOLVENTS FOR CLEANING: If dirt contains oil or grease a solvent is generally
required. Only petroleum distillates should be used to clean electrical components. Recommended are safety type petroleum solvents having a flash point greater than 100° F. (38° C.).
CAUTION!: Some generators may use epoxy or polyester base winding varnishes. Use sol­vents that will not attack such materials.
Use a soft brush or cloth to apply the solvent. Be careful to avoid damage to wire or winding insulation. After cleaning, dry all components thoroughly using moisture-free, low-pressure compressed air.
Page 12
Section 3
INSULATION RESISTANCE TESTS
DANGER!: DO NOT ATTEMPT TO WORK WITH SOLVENTS IN ANY ENCLOSED AREA. PROVIDE ADEQUATE VENTILATION WHEN WORKING WITH SOLVENTS. WITHOUT ADE­QUATE VENTILATION, FIRE, EXPLOSION OR HEALTH HAZARDS MAY EXIST . WEAR EYE PROTECTION. WEAR RUBBER GLOVES TO PROTECT THE HANDS.
CLOTH OR COMPRESSED AIR: For small parts or when dry dirt is to be removed, a
dry cloth may be satisfactory. Wipe the parts clean, then use low pressure air at 30 psi (206 Kpa) to blow dust away.
BRUSHING AND VACUUM CLEANING: Brushing with a soft bristle brush followed by vacuum
cleaning is a good method of removing dust and dirt. Use the soft brush to loosen the dirt, then remove it with the vacuum.
STATOR INSULATION RESISTANCE
GENERAL: Insulation resistance is a measure of the integrity of
the insulating materials that separate electrical wind­ings from the generator's steel core. This resistance can degrade over time due to the presence of conta­minants, dust, dirt, grease and especially moisture.
The normal insulation resistance for generator wind­ings is on the order of “millions of ohms” or “megohms”.
When checking the insulation resistance, follow the tester manufacturer's instructions carefully. Do NOT exceed the applied voltages recommended in this manual. Do NOT apply the voltage longer than one (1) second.
CAUTION!: DO NOT connect the Hi-Pot Tester or Megohmmeter test leads to any leads that are routed into the generator control panel. Connect the tester leads to the Stator or Rotor leads only.
STATOR SHORT-TO-GROUND TESTS: See Figure 3-2. To test the Stator for a short-to-
ground condition, proceed as follows:
1. Disconnect and isolate all Stator leads as follows: a. Disconnect sensing leads 11 and 22 from
the voltage regulator.
b. Disconnect excitation winding lead No. 6
from the voltage regulator.
c. Disconnect excitation lead No. 2 from the
excitation circuit breaker (CB2).
d. Disconnect battery charge winding leads
No. 66 and 77 from the battery charge recti­fier (BCR).
e. Disconnect battery charge winding lead No.
55 from the battery charge resistor (R1).
f. At the main circuit breakers, disconnect sta-
tor power leads No. 11P and 33.
g. At the ground stud (GND5), disconnect
Stator power leads No. 22 and 33.
2. When all leads have been disconnected as outlined in Step 1 above, test for a short-to-ground condition as follows:
a. Connect the terminal ends of all Stator leads
together (11, 22, 33, 44, 2,6, 55, 66, 77).
b. Follow the tester manufacturer's instructions
carefully. Connect the tester leads across all Stator leads and to frame ground on the Stator can. Apply a voltage of 1500 volts. Do NOT apply voltage longer than one (1) second.
If the test indicates a breakdown in insulation, the Stator should be cleaned, dried and re-tested. If the winding fails the second test (after cleaning and dry­ing), replace the Stator assembly.
TEST BETWEEN ISOLATED WINDINGS:
1. Follow the tester manufacturer's instructions carefully. Connect the tester test leads across Stator leads No. 11 (POWER) and No. 2. Apply a voltage of 1500 volts- DO NOT EXCEED ONE SECOND.
Figure 3-2. – Stator Leads
2. Repeat Step 1 with the tester leads connected across the fol­lowing Stator leads:
Page 13
2
6
11
11
22
22
33
44
55
66
77
Leads 2 & 6 =Stator Excitation Winding Leads 11 & 22 = Voltage Sensing Leads Leads 11 & 22, 33 & 44 = AC Power Windings Leads 55, 66, 77 = Battery Charge Windings
Section 3 INSULATION RESISTANCE TESTS
a. Across Wires No. 33 and 2. b. Across Wires No. 11 (POWER) and 66. c. Across Wires No. 33 and 66. d. Across Wires No. 2 and 66.
If a breakdown in the insulation between isolated windings is indicated, clean and dry the Stator. Then, repeat the test. If the Stator fails the second test, replace the Stator assembly.
TEST BETWEEN PARALLEL WINDINGS: Connect the tester leads across Stator leads No. 11
(POWER) and 33. Apply a voltage of 1500 volts. If an insulation breakdown is indicated, clean and dry the Stator. Then, repeat the test between parallel wind­ings. If the Stator fails the second test, replace it.
TESTING ROTOR INSULATION
To test the Rotor for insulation breakdown, proceed as follows:
1. Remove the brush holders with brushes.
2. Connect the tester positive (+) test lead to the positive (+) slip ring (nearest the Rotor bearing). Connect the tester negative (-) test lead to a clean frame ground (like the Rotor shaft).
Figure 3-3. – Rotor Test Points
3. Apply 1000 volts. DO NOT APPLY VOLTAGE LONGER THAN 1 SECOND.
If an insulation breakdown is indicated, clean and dry the Rotor then repeat the test. Replace the Rotor if it fails the second test (after cleaning and drying).
THE MEGOHMMETER
GENERAL: A megohmmeter, often called a “megger”, consists of
a meter calibrated in megohms and a power supply. Use a power supply of 1500 volts when testing Stators; or 1000 volts when testing the Rotor. DO NOT APPLY VOLTAGE LONGER THAN ONE (1) SECOND.
TESTING STATOR INSULATION: All parts that might be damaged by the high megger
voltages must be disconnected before testing. Isolate all Stator leads (Figure 3-2) and connect all of the Stator leads together. FOLLOW THE MEGGER MANUFACTURER'S INSTRUCTIONS CAREFULLY.
Use a megger power setting of 1500 volts. Connect one megger test lead to the junction of all Stator leads, the other test lead to frame ground on the Stator can. Read the number of megohms on the meter.
MINIMUM INSULATION
GENERATOR RATED VOLTS
RESISTANCE =
__________________________
+1
(in “Megohms”)
1000
The MINIMUM acceptable megger reading for Stators may be calculated using the following formula:
EXAMPLE: Generator is rated at 120 VAC. Divide “120” by “1000” to obtain “0.12”. Then add “1” to obtain “1.12” megohms. Minimum insulation resistance for a 120 VAC Stator is 1.12 megohms.
If the Stator insulation resistance is less than the cal­culated minimum resistance, clean and dry the Stator. Then, repeat the test. If resistance is still low, replace the Stator.
Use the Megger to test for shorts between isolated windings as outlined “Stator Insulation Resistance”.
Also test between parallel windings. See “Test Between Parallel Windings”on this page.
TESTING ROTOR INSULATION: Apply a voltage of 1000 volts across the Rotor posi-
tive (+) slip ring (nearest the rotor bearing), and a clean frame ground (i.e. the Rotor Shaft). DO NOT EXCEED 1000 VOLTS AND DO NOT APPLY VOLT­AGE LONGER THAN ONE SECOND. FOLLOW THE MEGGER MANUFACTURER'S INSTRUCTIONS CAREFULLY.
ROTOR MINIMUM INSULATION RESISTANCE:
1.5 megohms
Page 14
POSITIVE (+) TEST LEAD
Section 4
MEASURING ELECTRICITY
METERS
Devices used to measure electrical properties are called meters. Meters are available that allow one to measure (a) AC voltage, (b) DC voltage, (c) AC fre­quency, and (d) resistance in ohms. The following apply:
• To measure AC voltage, use an AC voltmeter.
• To measure DC voltage, use a DC voltmeter.
• Use a frequency meter to measure AC frequency in “Hertz” or “cycles per second”..
• Use an ohmmeter to read circuit resistance, in “ohms”.
THE VOM
A meter that allows both voltage and resistance to be read is the “volt-ohm-milliammeter” or “VOM”.
Some VOM's are of the “analog” type (not shown). These meters display the value being measured by physically deflecting a needle across a graduated scale. The scale used must be interpreted by the user.
“Digital” VOM's (Figure 4-1) are also available and are generally very accurate. Digital meters display the measured values directly by converting the values to numbers.
NOTE: Standard AC voltmeters react to the AVER­AGE value of alternating current. When working with AC, the effective value is used. For that rea­son a different scale is used on an AC voltmeter. The scale is marked with the effective or “rms” value even though the meter actually reacts to the average value. This is why the AC voltmeter will give an incorrect reading if used to measure direct current (DC).
Figure 4-1. – Digital VOM
MEASURING AC VOLTAGE
An accurate AC voltmeter or a VOM can be used to read the generator's AC output voltage. The following apply:
1.Always read the generator's AC output voltage only at the unit's rated operating speed and AC frequency.
2. The generator's voltage regulator can be adjusted for correct output voltage only while the unit is operating at its correct rated speed and frequency.
3. Only an AC voltmeter may be used to measure AC voltage. DO NOT USE A DC VOLTMETER FOR THIS PURPOSE.
DANGER!: RV GENERATORS PRODUCE HIGH AND DANGEROUS VOLTAGES. CON­TACT WITH HIGH VOLTAGE TERMINALS WILL RESULT IN DANGEROUS AND POSSI­BLY LETHAL ELECTRICAL SHOCK.
MEASURING DC VOLTAGE
A DC voltmeter or a VOM can be used to measure DC voltages. Always observe the following rules:
1. Always observe correct DC polarity.
a. Some VOM's may be equipped with a polar-
ity switch.
b. On meters that do not have a polarity
switch, DC polarity must be reversed by reversing the test leads.
2. Before reading a DC voltage, always set the meter to a higher voltage scale than the anticipated reading. If in doubt, start at the highest scale and adjust the scale downward until correct readings are obtained.
3. The design of some meters is based on the “current flow” theo­ry while others are based on the “electron flow” theory.
a. The “current flow” theory assumes that
direct current flows from the positive (+) to the negative (-).
b. The “electron flow” theory assumes that
current flows from negative (-) to positive (+).
NOTE: When testing generators, the “current flow” theory is applied. That is, current is assumed to flow from positive (+) to negative (-).
Page 15
Section 4 MEASURING ELECTRICITY
MEASURING AC FREQUENCY
The generator's AC output frequency is proportional to Rotor speed. Generators equipped with a 2-pole Rotor must operate at 3600 rpm to supply a frequen­cy of 60-Hertz.
Correct engine and Rotor speed is maintained by an engine speed governor. For models rated 60-Hertz, the governor is generally set to maintain a no-load frequency of about 62-Hertz with a corresponding output voltage of about 125 VAC line-to-neutral. Engine speed and frequency at no-load are set slight­ly high to prevent excessive rpm and frequency droop under heavy electrical loading.
MEASURING CURRENT
To read the current flow, in AMPERES, a clamp-on ammeter can be used. This type of meter indicates current flow through a conductor by measuring the strength of the magnetic field around that conductor. The meter consists essentially of a current trans­former with a split core and a rectifier type instrument connected to the secondary. The primary of the cur­rent transformer is the conductor through which the current to be measured flows. The split core allows the instrument to be clamped around the conductor without disconnecting it.
Current flowing through a conductor may be mea­sured safely and easily. A line-splitter can be used to measure current in a cord without separating the con­ductors.
Figure 4-2. – Clamp-On Ammeter
Figure 4-3. – A Line-Splitter
NOTE: If the physical size of the conductor or ammeter capacity does not allow all lines to be measured simultaneously, measure current flow in each individual line. Then, add the individual readings.
MEASURING RESISTANCE
The volt-ohm-milliammeter may be used to measure the resistance in a circuit. Resistance values can be very valuable when testing coils or windings, such as the Stator and Rotor windings.
When testing Stator windings, keep in mind that the resistance of these windings is very low. Some meters are not capable of reading such a low resis­tance and will simply read “continuity”.
If proper procedures are used, the following condi­tions can be detected using a VOM:
• A “short-to-ground” condition in any Stator or Rotor winding.
• Shorting together of any two parallel Stator wind­ings.
• Shorting together of any two isolated Stator wind­ings.
• An open condition in any Stator or Rotor winding.
Component testing may require a specific resistance value or a test for “infinity” or “continuity.” Infinity is an OPEN condition between two electrical points, which would read as no resistance on a VOM. Continuity is a closed condition between two electrical points, which would be indicated as very low resistance or “ZERO” on a VOM.
Page 16
Section 4
MEASURING ELECTRICITY
ELECTRICAL UNITS
AMPERE: The rate of electron flow in a circuit is represented by
the AMPERE. The ampere is the number of electrons flowing past a given point at a given time. One AMPERE is equal to just slightly more than six thou­sand million billion electrons per second.
With alternating current (AC), the electrons flow first in one direction, then reverse and move in the oppo­site direction. They will repeat this cycle at regular intervals. A wave diagram, called a “sine wave” shows that current goes from zero to maximum posi­tive value, then reverses and goes from zero to maxi­mum negative value. Two reversals of current flow is called a cycle. The number of cycles per second is called frequency and is usually stated in “Hertz”.
VOLT: The VOLT is the unit used to measure electrical
PRESSURE, or the difference in electrical potential that causes electrons to flow. Very few electrons will flow when voltage is weak. More electrons will flow as voltage becomes stronger. VOLTAGE is considered to be a state of unbalance and current flow as an attempt to regain balance. One volt is the amount of EMF that will cause a current of one ampere to flow through one ohm of resistance.
Figure 4-4. – Electrical Units
OHM: The OHM is the unit of RESISTANCE. In every circuit
there is a natural resistance or opposition to the flow of electrons. When an EMF is applied to a complete circuit, the electrons are forced to flow in a single direction rather than their free or orbiting pattern. The resistance of a conductor depends on (a) its physical makeup, (b) its cross-sectional area, (c) its length, and (d) its temperature. As the conductor's tempera­ture increases, its resistance increases in direct pro­portion. One (1) ohm of resistance allows one (1) ampere of current to flow when one (1) volt of electro­motive force (EMF) is applied.
OHM'S LAW
A definite and exact relationship exists between VOLTS, OHMS and AMPERES. The value of one can be calculated when the value of the other two are known. Ohm's Law states that in any circuit the current will increase when voltage increases but resistance remains the same, and current will decrease when resistance increases and voltage remains the same.
Figure 4-5.
If AMPERES is unknown while VOLTS and OHMS are known, use the following formula:
AMPERES =
VOLTS
OHMS
If VOLTS is unknown while AMPERES and OHMS are known, use the following formula:
VOLTS = AMPERES x OHMS
If OHMS is unknown but VOLTS and AMPERES are known, use the following:
OHMS
=
VOLTS
AMPERES
Page 17
VOLTS
(E)
-
Conductor of a Circuit
OHM - Unit measuring resistance
or opposition to flow
AMPERE - Unit measuring rate of
current flow (number of electrons past a given point)
VOLT - Unit measuring force or
difference in potential causing current flow
+
AMPS
(I)
OHMS
(R)
Section 5 ENGINE DC CONTROL SYSTEM
INTRODUCTION
The engine DC control system includes all compo­nents necessary for the operation of the engine. Operation includes off, preheat, cranking/starting, running, shutdown, and fault shutdown. The system is shown schematically.
OPERATIONAL ANALYSIS
CIRCUIT CONDITION- OFF: Battery voltage is available to the engine controller
circuit board from the unit BATTERY and via (a) the RED battery cable, Wire 13, a 14 amp FUSE (F1), Wire 15 and engine controller Terminal 1. However, circuit board action is holding the circuit open and no action can occur.
Battery voltage is available to the contacts of a STARTER CONTACTOR (SC), but the contacts are open.
Battery voltage is available to the contacts of a PRE­HEAT CONTACTOR (PHC), but the contacts are open.
Battery voltage is available to the PREHEAT SWITCH (SW).
The switch is open and the circuit is incomplete. Battery voltage is also available to the remote con­nection for a remote preheat switch.
Battery voltage is available to the BATTERY CHARGE RECTIFIER (BCR). This is used as a return path for Battery Charge Winding current.
Page 18
Section 5
ENGINE DC CONTROL SYSTEM
Page 19
CIRCUIT CONDITION- PRE-HEAT: When the PRE-HEAT SWITCH (SW) or the
REMOTE PANEL PRE-HEAT SWITCH is closed by the operator, battery voltage is delivered across the closed switch contacts to the PRE-HEAT CONTAC­TOR (PHC) via Wire 150. The PRE-HEAT CONTAC­TOR (PHC) is now energized. The normally open (PHC) contacts close, battery voltage is now avail­able to Wire 157.
The GLOW PLUGS (GP) are energized via Wire 157. Wire 157 is also connected to a DIODE (D1), current
is allowed to pass through (D1) and Wire 14 will now have battery voltage applied to it " Engine Controller Terminals 9, 10 , and 11 are connected".
The FUEL PUMP (FP), FUEL SOLENOID (FS), and HOURMETER (HM) will be energized via Wire 14.
Wire 14 is also connected to RESISTOR (R2) and DIODE (D2). After passing through R2 and D2 reduced voltage is applied to Wire 4.
Section 5 ENGINE DC CONTROL SYSTEM
Page 20
CIRCUIT CONDITION- CRANKING: When the START-STOP-SWITCH (SW1) or REMOTE
PANEL START-STOP-SWITCH is held at "START" position, Wire 17 from the Engine Control circuit board is connected to Ground. Engine control circuit board action will then deliver battery voltage to a STARTER CONTACTOR (SC) via Terminal 7 Wire 56.
The STARTER CONTACTOR (SC) energizes and its contacts close, battery output is delivered to the STARTER MOTOR (SM) via Wire 16.The STARTER MOTOR energizes and the engine cranks.
Also, while cranking, engine control circuit board action energizes Terminals 9, 10, and 11 which deliv­ers battery voltage to the Wire 14 circuit. This ener­gizes the FUEL PUMP (FP), FUEL SOLENOID (FS), HOURMETER (HM), and optional light or hourmeter in remote panel.
Wire 14 is also connected to RESISTOR (R2) and DIODE (D2). After passing through R2 and D2 reduced voltage is applied to Wire 4. The reduced voltage, approximately 3-5VDC, is sent to the ROTOR via The BRUSHES and SLIP RINGS. This voltage is used for Field Boost.
Also while cranking, engine control circuit board action energizes Terminal 12 which delivers battery voltage to Wire 85. "Refer to Circuit Condition-Fault Shutdown for operation".
Section 5
ENGINE DC CONTROL SYSTEM
Page 21
CIRCUIT CONDITION-RUNNING: With the FUEL PUMP (FP) and FUEL SOLENOID
(FS) operating the engine should start. The START­STOP SWITCH (SW1) is then released. Engine con­trol circuit board action terminates DC output to the STARTER CONTACTOR (SC), which then de-ener­gizes the (SC) to end cranking.
While running, engine control circuit board action keeps Terminals 9, 10, and 11 energized which deliv­ers battery voltage to the Wire 14 circuit. This ener­gizes the FUEL PUMP (FP), FUEL SOLENOID (FS), HOURMETER (HM), and optional light or hourmeter in remote panel. This will maintain engine operation.
While running, engine control circuit board action keeps Terminal 12 (Wire 85) energized with battery voltage. Connected in parallel to Wire 85 are the LOW OIL PRESSURE SWITCH (LOS) and HIGH WATER TEMP SWITCH (HWT). The (LOS) has nor­mally closed contacts. After start-up, engine oil pres­sure will open the contacts. The HWT has normally open contacts. High coolant temperature will close the contacts. "Refer to Circuit Condition-Fault Shutdown for operation".
A voltage is induced into the Stator's POWER WIND­ING. This voltage is delivered to the Engine control circuit board Terminals 5 & 6 (via Wires 22 & 44). The engine control circuit board uses this frequency signal to determine engine speed for overspeed sensing and starter disengage.
Section 5 ENGINE DC CONTROL SYSTEM
Page 22
CIRCUIT CONDITION- SHUTDOWN: Setting the START-STOP SWITCH (SW1) or the
REMOTE PANEL START-STOP SWITCH to its "STOP" position, connects the Wire 18 circuit to ground. ENGINE CONTROL circuit board action de­energizes DC output to Terminal 9,10, & 11 (Wire
14). The FUEL PUMP (FP), FUEL SOLENOID (FS) and HOURMETER (HM) are de-energized by the loss of DC to Wire 14. Fuel flow terminates and the engine shuts down.
Section 5
ENGINE DC CONTROL SYSTEM
Page 23
CIRCUIT CONDITION- FAULT SHUTDOWNS: The engine has mounted to it a HIGH WATER TEM-
PERATURE SWITCH (HWT) and a LOW OIL PRES­SURE SWITCH (LOS). While running, ENGINE CONTROL circuit board action keeps Terminal 12 Wire 85 energized with battery voltage. Connected in parallel to (Wire 85) are the LOW OIL PRESSURE SWITCH (LOS) and HIGH WATER TEMP SWITCH (HWT). The (LOS) has normally closed contacts. After start-up, engine oil pressure will open the con­tacts. The HWT has normally open contacts. High coolant temperature will close the contacts.
Should engine water temperature exceed a preset value, the switch contacts will close. Wire 85 from the circuit board will connect to ground. Circuit board action will then initiate a shutdown.
Should engine oil pressure drop below a safe pre-set value, the switch contacts will close.
On contact closure, Wire 85 will be connected to ground and circuit board action will initiate an engine shutdown.
The circuit board has a time delay built into it for the Wire 85 fault shutdowns. At STARTUP ONLY the cir­cuit board will wait approximately six (6) seconds before looking at the Wire 85 fault shutdowns. Once running after the six (6) second time delay, grounding Wire 85 through either switch will cause an immedi­ate shutdown.
The ENGINE CONTROL circuit board also has over­speed protection. The circuit board senses the AC output from the stators POWER winding at Terminals 5 & 6 via Wires 22 & 44. This AC voltage and fre­quency signal is used indirectly to monitor engine RPM. If the frequency should increase above a pre­set "adjustable" limit, the ENGINE CONTROL circuit board will cause an immediate shutdown.
Section 5 ENGINE DC CONTROL SYSTEM
ENGINE CONTROL CIRCUIT BOARD
GENERAL: The ENGINE CONTROL circuit board is responsible
for cranking, startup, running, and shutdown opera­tions. The board interconnects with other components of the DC control system to turn them on and off at the proper times. It is powered by fused 12 VDC power from the unit battery.
CIRCUIT BOARD CONNECTIONS: The circuit board mounts two, six-wire terminal strips. They are labeled 1-6 and 7-12. The following chart shows the associated wires and
the function(s) of each terminal and wire.
TERMINAL WIRE FUNCTION
1 15 Power supply (12VDC) for the circuit board
and DC control system. 2 0 Common Ground 3 17 To Start Stop Switch and remote connector.
When grounded by setting Start-Stop
Switch to "START", engine will crank. 4 18 To Start-Stop Switch and remote connector.
When grounded by setting Start-Stop-
Switch to "STOP", engine shuts down. 5 44 Frequency signal for overspeed
shutdown/starter disengage. 6 22 Frequency signal for overspeed
shutdown/starter disengage. 7 56 Delivers 12 VDC to Starter Contactor (SC)
while cranking only. 8 __ Not Used 9 14 Engine run circuit. Delivers 12 VDC during
cranking and running.
Connected to Fuel Pump, Fuel Solenoid,
Hourmeter, and field boost circuit.
10 14 Engine run circuit. Delivers 12 VDC during
cranking and running.
Connected to Fuel Pump, Fuel Solenoid,
Hourmeter, and field boost circuit.
11 14 Engine run circuit. Delivers 12 VDC during
cranking and running.
Connected to Fuel Pump, Fuel Solenoid,
Hourmeter, and field boost circuit.
12 85 Fault shutdown circuit. When grounded by
High Water Temperature or Low Oil
Pressure switch, engine will shut down.
LED FUNCTIONS: Green LED will be illuminated when Wire 14 is ener-
gized during cranking and running. Red LED will be illuminated when Wire 56 is ener-
gized during cranking only.
OVERSPEED SHUTDOWN POTENTIOMETER: The overspeed shutdown potentiometer is used to set
the frequency at which the board will initiate a engine shutdown. Proper setting of the potentiometer is criti­cal to the correct operation of the generator.
ADJUSTMENT PROCEDURE: The overspeed shutdown potentiometer MUST be
adjusted on replacement circuit boards. If not replacing a board, start at STEP 6.
1. Remove 14 amp fuse (F1) from control panel.
2. Disconnect all wires from circuit board terminals.
3. Remove old circuit board and install new circuit board.
4. Connect all wires to proper circuit board terminals. Follow elec­trical schematic if needed.
5. Reinstall 14 amp (F1) fuse into control panel.
6. Turn the overspeed shutdown potentiometer slowly counter­clockwise until it stops. DO NOT FORCE.
Note: If immediate shutdown occurs when the engine starts and the START/STOP switch is released, reverse overspeed shutdown pot set­ting, turn pot clockwise and proceed. In Step 10 and Step 11, turn the overspeed shutdown pot counterclockwise.
7. Connect an accurate AC frequency meter across the genera­tor's AC output leads.
8. Start the generator, let it stabilize and warm up.
9. Use the injection throttle lever to SLOWLY increase engine speed until the frequency meter reads 64 hertz.
10.Hold the throttle at 64 hertz and SLOWLY turn the overspeed shutdown potentiometer clockwise until engine shutdown occurs.
11. Turn the overspeed shutdown potentiometer clockwise an additional 1/8 turn. The overspeed setting is now correct.
BATTERY
RECOMMENDED BATTERY: When anticipated ambient temperatures will be con-
sistently above 32° F. (0° C.), use a 12 VDC automo­tive type storage battery rated 70 amp-hours and capable of delivering at least 360 cold cranking amperes.
The QUIETPACT 75D generator is rated at about 160 DC Amps of cranking current to operate the starter and glow plugs.
BATTERY CABLES: Use of battery cables that are too long or too small in
diameter will result in excessive voltage drop. For best cold weather starting, voltage drop between the
Page 24
Section 5
ENGINE DC CONTROL SYSTEM
battery and starter should not exceed 0.12 VDC per 100 amperes of cranking current.
Select the battery cables based on total cable length and prevailing ambient temperature. Generally, the longer the cable and the colder the weather, the larg­er the required cable diameter.
The following chart applies:
CABLE LENGTH (IN FEET) RECOMMENDED CABLE SIZE
0-10 No. 2 11-15 No. 0 16-20 No. 000
EFFECTS OF TEMPERATURE: Battery efficiency is greatly reduced by a decreased
electrolyte temperature. Such low temperatures have a decided numbing effect on the electrochemical action. Under high discharge rates (such as crank­ing), battery voltage will drop to much lower values in cold temperatures than in warmer temperatures. The freezing point of battery electrolyte fluid is affected by the state of charge of the electrolyte as indicated below:
SPECIFIC GRAVITY FREEZING POINT
1.220 -35° F. (-37° C.)
1.200 --20° F. (-29° C.)
1.160 0° F. (-18° C.)
ADDING WATER: Water is lost from a battery as a result of charging
and discharging and must be replaced. If the water is not replaced and the plates become exposed, they may become permanently sulfated. In addition, the plates cannot take full part in the battery action unless they are completely immersed in electrolyte. Add only
DISTILLED WATER to the battery. DO NOT USE TAP WATER.
NOTE: Water cannot be added to some “mainte­nance-free” batteries.
CHECKING BATTERY STATE OF CHARGE: Use an automotive type battery hydrometer to test the
battery state of charge. Follow the hydrometer manu­facturer's instructions carefully. Generally, a battery may be considered fully charged when the specific gravity of its electrolyte is 1.260. If the hydrometer used does not have a “Percentage of Charge” scale, compare the readings obtained with the following:
SPECIFIC GRAVITY PERCENTAGE OF CHARGE
1.260 100%
1.230 75%
1.200 50%
1.170 25%
CHARGING A BATTERY: Use an automotive type battery charger to recharge a
battery. Battery fluid is an extremely corrosive, sulfu­ric acid solution that can cause severe burns. For that reason, the following precautions must be observed:
• The area in which the battery is being charged must be well ventilated. When charging a battery, an explosive gas mixture forms in each cell.
• Do not smoke or break a live circuit near the top of the battery. Sparking could cause an explosion.
• Avoid spillage of battery fluid. If spillage occurs, flush the affected area with clear water immediately.
• Wear eye protection when handling a battery.
Page 25
Figure 5-4 – Engine Control Circuit Board
TERMINALS:
7 8 9 10 11 12
GREEN LED
RED LED
TERMINALS:
1 2 3 4 5 6
OVERSPEED SHUTDOWN POTENTIOMETER
Section 5 ENGINE DC CONTROL SYSTEM
14 AMP FUSE
This panel-mounted Fuse protects the DC control cir­cuit against overload and possible damage. If the Fuse has melted open due to an overload, neither the priming function nor the cranking function will be available.
Figure5-4
PREHEAT SWITCH
The diesel engine is equipped with glow plugs, one for each cylinder. When the preheat switch is pressed, voltage will go through the switch to the pre­heat contactor. The preheat contactor (normally open) now closes, allowing battery voltage to go to the glow plugs via Wire 157. Power from Wire 157 goes through a diode and changes to Wire 14. This Wire 14 goes to the circuit board powering the fuel pump, fuel solenoid, hourmeter, and field boost through another diode and resistor. The glow plugs now heat the engine combustion chamber, and the injector pump is primed with fuel for starting.
Figure 5-5. – Pre-heat Switch
START/STOP SWITCH
The start/stop switch allows the operator to control cranking, startup, and shutdown. The following wires connect to the start/stop switch:
WIRE 17 (FROM THE ENGINE CONTROL BOARD): This is the crank and start circuit. When the switch is
set to start, Wire 17 is connected to ground via Wire
0. With Wire 17 grounded, a crank relay on the circuit board energizes and battery voltage is delivered to the starter contactor via Wire 56. The starter contac­tor energizes and its normally open contacts close allowing battery voltage through Wire 16 to the starter motor and the engine will now crank. With Wire 17 grounded, a run relay on the circuit board energizes and battery voltage is delivered to the Wire 14 circuit. Now the fuel pump, fuel solenoid, hourmeter, and field boost has battery voltage for operation.
WIRE 18 (FROM THE ENGINE CONTROL BOARD): This is the engine stop circuit. When the start/stop
switch is set to stop, Wire 18 is connected to ground via Wire 0. Circuit board action then opens the circuit to Wire 14, stopping fuel flow, causing the unit to stop.
WIRE 0: Connects the switch to ground.
Figure 5-6. – Start/Stop Switch
STARTER CONTACTOR & MOTOR
Figure 5-7. – Starter Contactor and Connections
8
8
1
)
)
50
5
50
0
Page 26
START
W
1
STOP
1
A. Schematic
B. Pictorial
BH1-1
1
150
1
1
B. Schematic
15
A. Pictorial
TO FUSE
13
OUTER POSTS
SMALL
LUGS
13
0
TO GROUND
56
TO BOARD
16
TO STARTER
TO BATTERY
Section 5
ENGINE DC CONTROL SYSTEM
The positive (+) battery cable (13) attaches to one of the outer posts of the contactor along with Wire 13 for the DC supply to the fuse (F1). The starter cable (16) attaches to the remaining outer post. Attached to the small 2 lugs are Wires 56 and 0. When the start/stop switch is set to start, the circuit board delivers battery voltage to the contactor coil via Wire 56. The contac­tor energizes and its contacts close. Battery voltage is then delivered from the positive battery cable, across contacts and to the starter motor via Wire 16.
ENGINE GOVERNOR
A mechanical, all-speed governor is used on the diesel engine. It is housed in the gear case. A fly­weight movement is transmitted to the injection pump control rack by way of the slider, control lever and link. A spring is attached to the arm and the tension lever. The spring regulates flyweight movement. By changing the set angle of the governor lever, tension on the tension lever spring is changed. In this man­ner, engine speed can be regulated by the governor lever.
The generators A/C output frequency is directly pro­portional to engine speed. Low governor speed will result in a reduced A/C frequency and voltage, and high governor speed will produce an increased fre­quency and voltage.
FUEL INJECTION PUMP
Figure 5-8. – Fuel Injection Pump
The fuel injection pump is mounted on the side of the engine and rides on a three-lobe camshaft. The lobes on the camshaft press the bottom of the pump, which mechanically opens the fuel path to deliver fuel to the fuel injectors. Timing for the fuel injector pump is determined by the distance between the camshaft lobes and the pump. This distance is regulated by metal shims. If the shim space is incorrect, the fuel pressure will be incorrect and combustion will not occur. When the fuel injector pump is removed for maintenance, be sure to reassemble with the same number of shims. The engine governor controls the fuel injector pump by linkage connecting the two.
FUEL NOZZLES/INJECTORS
Fuel supplied by the injector pump is delivered to the nozzle holder and to the nozzle body. When fuel pressure is sufficient to compress the spring, fuel is supplied from the nozzle and into the combustion chamber. Due to the high pressure of fuel being ejected from the nozzle, there is no safe test. If faulty fuel is suspected and a clogged injector pump was diagnosed, the replacement of the injector nozzles would be needed.
Figure 5-9. – Fuel Injectors
Figure 5-10. – Fuel Injector Nozzles
GLOW PLUGS
The glow plug consists of a thin coiled heat-wire that is encased in sintered magnesium oxide powder and enclosed by a stainless steel sheath. One end of the wire is welded to the sheath and the other end is welded to the center electrode. When voltage is applied to the center electrode, it heats the heat-wire, which in turn, heats the combustion chamber.
Glow plugs are connected in parallel. For that rea­son, if one plug fails open, the other plugs will contin­ue to operate. However, loss of one plug will increase the possibility of the heat-wire melting open in the remaining plugs.
OR
PINSERT
T
Page 27
INJECT
A
ASKE
CONTROL RACK
SHIM
INJECTOR PUMP
VALVE
CLOSED
VAL VE
OPEN
FULLY OPEN
Section 5 ENGINE DC CONTROL SYSTEM
Figure 5-11. –
Glow Plug
ENGINE PROTECTIVE DEVICES
The engine will shut down automatically in the event of anyone or more of the following occurrences:
• Low oil
• High engine coolant temperature
• Engine overspeed
LOW OIL PRESSURE SWITCH
The oil pressure switch has normally-closed contacts. When the engine is cranking or running, oil will pass through the switch, which opens the contacts. If oil pressure should drop below 10 PSI, the contacts will close to ground sending a signal to the printed circuit board to shut unit down on wire 85.
Figure 5-12. –
Low Oil Pressure Switch
HIGH COOLANT TEMPERATURE SWITCH
The high coolant temperature switch has normally open contacts. This switch is immersed in engine coolant. If the coolant temperature should exceed 245-266 degrees F, the switches contacts will close to ground, sending a signal to the printed circuit board to shut down the unit via wire 85.
Figure 5-13. – High Coolant Temperature Switch
OVERSPEED PROTECTION
Generator A/C frequency signals are delivered to Terminals 5 and 6 of the engine control circuit board via wires 22 and 44. Should engine/generator speed exceed 69 to 71 Hertz for longer than 4 seconds, the circuit board will cause an engine shutdown.
Page 28
HEAT-WIRE
MAGNESIUM
SHEATH
OXIDE
POWDER
ASBESTOS
BODY
INSULATING
BUSHING
NUT
CENTER
ELECTRODE
LOW OIL
PRESSURE
SWITCH
ADAPTER
Loading...
+ 70 hidden pages