ABOUT THIS MANUAL
Congratulation! Your purchase of this whole-house HEPA filtration, with optional ventilation will allow you and your family to enjoy clean and healthy air throughout your home for years to come! Please read this manual thoroughly. Several models are described in this publication. Some details of your unit may be slightly different than the ones shown, as the illustration are typical ones. Please take note that this manual uses the following symbols to emphasize particular information:
!
WARNING
Identifies an instruction which, if not followed, might cause serious personal injuries including possibility of death.
CAUTION
Denotes an instruction which, if not followed, may severely damage the unit and/or its components.
NOTE: Indicates supplementary information needed to fully complete an instruction. We welcome any suggestions you may have concerning this manual and/or the product, or ways to better serve you. Please forward all
correspondence at the address below:
Broan-NuTone LLC
Indoor Air Quality Marketing
926 W. State St.,
Hartford, WI 53027
1-800-558-1711
ABOUT THESE UNITS
!
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSON(S) OBSERVE THE FOLLOWING:
1. This unit is intented for residential installation only.
2. Installation must be done in accordance with all applicable codes and standards, including fire-rated construction codes and standards.
3. This unit is not designed to provide combustion and/or dilution air for fuel-burning appliances.
4. Do not install in a cooking area or connect directly to an appliance.
5. Before replacing filters, servicing or cleaning unit, disconnect the power cord from electrical outlet.
6. When cutting or drilling into wall or ceiling, do not damage electrical wiring or other hidden utilities.
7. Do not use this unit with any solid-state speed control device other than wall controls ACCGSC1 or ACCGSC3, provided with the unit.
8. This unit must be grounded. The power supply cord has a 3-prong grounding plug for your personal safety. It must be plugged into a mating 3-prong grounding receptacle, grounded in accordance with the national electrical code and local codes and ordinances. Do not remove the ground prong. Do not use an extension cord.
9. This unit must be installed in a weatherized location out of direct sunlight and protected from the elements.
10. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed in this document.
1. For general filtration and ventilation use only. Do not use to exhaust hazardous or explosive materials and vapors.
2. Intended for residential installation only in accordance with the requirements of NFPA 90B.
3. For GSVH1K, GSHH3K and GSEH3K units only: Be sure to duct air outside. - Do not intake / exhaust air into spaces with in walls or ceiling or into attics, crawl spaces, or garage.
4. Do not run any air ducts directly above or closer than 2 ft (0.61 m) to any furnace or its supply plenum, boiler, or other heat producing appliance. If a duct has to be connected to the furnace return plenum, it must be connected not closer than 2 ft (0.61 m) from this plenum connection to the furnace.
5. The ductwork is intended to be installed in compliance with all local and national codes that are applicable.
6. To avoid prematurate clogged filters, turn OFF the unit during construction or renovation.
7. Please read the unit specification label on the product for further information and requirements.
NOTE: The energy recovery ventilator GSEH3K is designed to assist in the management of humidity introduced into the home.
In extreme humidity conditions, the use of additional dehumidification may be desirable. Quickly remove all excess moisture and keep areas clean.
CAUTION
- 2 -
TABLE OF CONTENTS
1. BEFORE STARTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.1 INSPECT THE CONTENT OF THE BOX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2. TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.1 DIMENSIONS AND AIR DISTRIBUTION PORTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.2 VENTILATION PERFORMANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-6
2.3 MOUNTING AND SERVICING CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3. RECOVERY NEEDS ACCORDING TO GEOGRAPHICAL LOCATION . . . . . . . . . . . . . . . . . . . . . . . . .7
4. PLANNING THE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4.1 PLANNING OF THE DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
5. TYPICAL INSTALLATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
5.1 GSFH1K UNIT INSTALLATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
5.2 GSVH1K, GSHH3K AND GSEH3K UNITS INSTALLATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5.3 STAND ALONE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-12
5.4 CENTRAL DRAW POINT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.5 RETURN-TO-RETURN INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
6. INSTALL THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6.1 TOOLS AND MATERIALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6.2 MOUNT THE PORTS ON THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6.3 INSTALLATION USING ISOLATOR PADS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
6.4 FOR SUSPENDED APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-16
6.5 INSTALLING 8“ DUCTS AND REGISTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-19
6.6 INSTALLING INSULATED FLEXIBLE DUCTS TO TANDEM®TRANSITION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.7 INSTALLING AIRDUO™EXTERIOR HOOD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-21
6.8 INSTALLING TWO EXTERIOR HOODS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21-23
6.9 INSTALLING TWO BREIDERT CAPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-24
6.10 CONNECTION TO THE 5’’ TO 6’’ OVAL PORTS OF THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24-25
6.11 CONNECTING THE DRAIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.12 LOW TEMPERATURE APPLICATIONS BELOW FREEZING (32°F OR 0°C) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-27
7. CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
7.1 MAIN SWITCH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7.2 WALL CONTROLLERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7.3 DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.4 INSTALLATION OF THE WALL CONTROLLERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-30
7.5 OPERATING ACCGSC1 CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
7.6 OPERATING ACCGSC3 CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
8. BALANCING PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
8.1 WHAT YOU NEED TO BALANCE THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
8.2 PRELIMINARY STAGES FOR BALANCING THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
8.3 INSTALLATION OF FLOW COLLAR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
8.4 BALANCING PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
9. MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
9.1 SEMI-ANNUAL MAINTENANCE (ESSENTIAL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33-34
9.2 ANNUAL MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
9.3 MASTER RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
9.4 O
PTIONAL ALPINE/PINE FILTER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
10. TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
11. W
ARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
- 3 -
1. BEFORE STARTING
1.1 INSPECT THE CONTENTS OF THE BOX
!
WARNING
To avoid risk of suffocation, discard the plastic bag wrapping the unit.
• Inspect the exterior of the unit for shipping damage. Ensure there is no damage to the door, door latches, main switch, etc.
CAUTION
Remove the cardboard strip inside the unit (if applicable).
1
VD0126
1) Cardboard strip
• Inspect the interior of the unit for damage. Ensure the blower assembly, heat recovery core (model GSHH3K), energy recovery core (model GSEH3K), insulation, dampers (models GSVH1K , GSHH3K and GSEH3K), prefilter, HEPA filter, etc. are all intact.
• If the unit was damaged during shipping, contact your local distributor, or Broan-NuTone at 1-800-558-1711.
2. TECHNICAL DATA
GSFH1K GSVH1K GSHH3K GSEH3K
HEPA Filtration HEPA Filtration, HEPA Filtration,
Models HEPA Filtration & Fresh Air Fresh Air & Fresh Air &
Ventilation Heat Recovery Energy Recovery
Ventilation Ventilation Weight 34 lbs (15.4 kg) 36 lbs (16.3 kg) 40 lbs (18.2 kg) 40 lbs (18.2 kg) Oval shaped duct collars for non-insulated ducts fits two 8” round ducts to inside Oval shaped duct collars for insulated ducts N/A fits two 5” or 6” round ducts to outside Installation: Suspended Chains, springs and hooks (provided with the unit) or rest on a shelf or floor: or 4 pads (provided with the unit) Electrical Supply 120 Volts AC, 60 Hz Power Consum. (Boost) 170 Watts 224 Watts 229 Watts 224 Watts Power Consum. (Normal) 132 Watts 152 Watts 170 Watts 170 Watts
NOTE: Due to our ongoing commitment to product quality and innovation, all specifications are subjected to change without notice.
- 4 -
2. TECHNICAL DATA (CONT’D)
2.1 DIMENSIONS AND AIR DISTRIBUTION PORTS
HEPA FILTRATION UNIT, MODEL GSFH1K
29''
(737 mm)
22.9'' (581 mm)
VK0047
FILTERED AIR
TO BUILDING
STALE AIR
FROM
BUILDING
FRONT
17.8''
(452 mm
FRONT VIEW TOP VIEW
HEPA FILTRATION UNIT AND FRESH AIR VENTILATION,
MODEL GSVH1K
HEPA FILTRATION, FRESH AIR AND HEAT RECOVERY
VENTILATION, MODEL GSHH3K
HEPA FILTRATION, FRESH AIR AND ENERGY RECOVERY
VENTILATION, MODEL GSEH3K
29.4''
(748 mm)
17.8''
(452 mm)
22.9'' (581 mm)
VK0048
FRONT VIEW TOP VIEW
2.2 VENTILATION PERFORMANCES
2.2.1 GSVH1K VENTILATION PERFORMANCES
STALE AIR
TO
OUTSIDE
FRESH
AIR FROM
OUTSIDE
VF0033
FRESH AND FILTERED
AIR TO BUILDING
STALE AIR
FROM
BUILDING
FRONT
VF0029
EXT STATIC NET VENTILATION GROSS AIR FLOW PRESSURE AIRFLOW SUPPLY EXHAUST FILTERED
Pa
in.w.g.
l/s
cfm
l/s
cfm
l/s
cfm
50
0.2
52
110
56
118
54
115
100
0.4
49
104
52
111
49
104
NOTE: all tests performed at high speed.
132 121
POWER
l/s
cfm
Watts
279
231
257
224
- 5 -
2. TECHNICAL DATA (CONT’D)
2.2 VENTILATION PERFORMANCES (CONTD)
2.2.2 GSHH3K V
ENTILATION PERFORMANCES 2.2.3 GSEH3K VENTILATION PERFORMANCES
EXT STATIC NET VENTILATION GROSS AIR FLOW PRESSURE AIRFLOW SUPPLY EXHAUST FILTERED
Pa
in.w.g.
l/s
cfm
l/s
cfm
l/s
cfm
l/s
50
0.2
52
110
58
124
57
121
131
100
0.4
49
103
55
116
51
108
119
cfm 277 252
POWER
Watts
237 229
EXT STATIC NET VENTILATION GROSS AIR FLOW
PRESSURE AIRFLOW SUPPLY EXHAUST FILTERED
Pa
in.w.g.
l/s
cfm
50
0.2
57
122
100
0.4
53
113
NOTE: all tests performed at high speed.
2.3 MOUNTING AND SERVICING CONSIDERATIONS
The two following pictures are showing the minimum clearance needed to open the door completely.
8”
(203 mm)
22”
(559 mm)
22.5” 15.75”
(572 mm) (400 mm)
VD0117
VD0116
l/s 50 48
cfm 105 102
POWER
l/s
cfm
l/s
cfm
Watts
59
125
127
270
227
55
117
120
254
224
NOTES: 1. The unit door is removable. To do so, remove the stopper (A) located on the
right side of the door hinge, then, slide the door out of its hinge. For servicing, a minimum of 15’’ (381 mm) clearance from any obstruction in front of the unit is sufficient to open the door and remove it.
2. A minimum of 8” (203 mm) clearance from any obstruction on top of the unit is required for the ductwork radius turn.
• The joist opening needed to install the Tandem®transition must be 9 3/4” (248 mm)
minimum. Also, the maximum height of the Tandem®transition is 8 3/4” (222 mm).
See Tandem®transition end view beside.
NOTES: 1. If there is not enough space to use the Tandem®transition, the optional exterior
single hood must be installed to bring the fresh outside air to the unit. See Section 6.8.
2. When installing a HEPA Filtration model GSFH1K, there is no Tandem®transition.
VD0118
VD0170
9 3/4"
248 mm
A
8 3/4"
222 mm
- 6 -
3. RECOVERY NEEDS ACCORDING TO GEOGRAPHICAL LOCATION
N
When recovery is important, it can be hard to find the appropriate unit. Use the map below to determine which between heat
recovery (GSHH3K model) or energy recovery (GSEH3K model) will satisfy the specific needs of the consumers.
OLYMPIA
SALEM
BOISE
RENO
SACRAMENTO
HELENA
SALT LAKE CITY
PHOENIX
ZONE A
DENVER
SANTA FE
BISMARCK
A
TOPEK
OKLAHOMA CITY
ST. PAUL
MADISON
DES MOINES
SPRINGFIELD
DETROIT
INDIANAPOLIS
NASHVILLE
ATLANTA
HARRISBURG
COLUMBUS
COLUMBIA
BOSTO
HARTFORD
WASHINGTON
RALEIGH
ZONE B
When exchanging air with outside:
AUSTIN
BATON ROUGE
ZONE A: GSHH3K unit recommended* ZONE B: GSEH3K unit recommended
* In ZONE A, the GSEH3K unit may be used, but below 16°F, the duration of exchanging air with outside will decrease.
VN0004A
4. PLANNING THE INSTALLATION
The Guardian Plus units are versatile appliances capable of delivering filtered air (model GSFH1K) or both filtered and fresh air to your home (models GSVH1K, GSHH3K and GSEH3K). Because each installation is different, it is recommended you take the time to plan your installation. The three main areas to plan for are:
• Where to locate the GuardianPlus unit
• How to pick-up the air from the room and distribute the filtered or fresh/filtered air
• Where to bring fresh air from outside and exhaust stale air to outside (models GSVH1K, GSHH3K and GSEH3K).
Use the following chart to determine the appropriate installation method for the unit.
Is the house equipped with a furnace or air handler?
YES
Is there enough space to connect the unit duct(s) to the existing
furnace or air handler ductwork? (The unit duct connection can be
performed on the cold air return duct or supply air duct, at a minimum
linear distance of 2’ (0.61 m) from the furnace/air handler.)
NO
Use Stand Alone installation.
See Section 5.3.
NO
YES
The Central Draw Point
installation can be performed.
Example: Basement installation
in Section 5.4.1
OR
The Return-to-Return
installation can be performed.
Example: Crawl space installation
in Section 5.5.1
CAUTION
Do not install duct or duct connector directly above the furnace. Do not connect the plenum connection closer than 2’ (0.61m) to the furnace, as measured along the length of the duct.
- 7 -
4. PLANNING THE INSTALLATION (CONT’D)
4
.1 PLANNING OF THE DUCTWORK
• Keep it simple. Plan for a minimum of bends and joints.
• Keep the length of insulated ducts to the outside of home to a minimum.(not for HEPA Filtration model GSFH1K).
• Do not ventilate crawl spaces or cold rooms.
• If the house has two floors or more, be sure to plan for at least one exhaust register on the highest lived-in level.
Use the table below to plan the flexible ducts length.
FLEXIBLE DUCT LENGTH TABLE
Maximum Maximum
recommended length recommended length
to reach 105 cfm to reach 95 cfm Insulated fresh air duct from outside (6” diameter) Insulated exhaust air duct to outside (6” diameter)
Stale air duct from inside (8” diameter) Combined: 40’ Combined: 60’ with Filtered air duct to inside stale air duct not to (8” diameter) exceed 36’
up to 10’ from 10’ to 20’
up to 10’ from 10’ to 20’
Recommended Recommended
maximum length maximum length to reach 270 cfm to reach 240 cfm
!
WARNING
Do not attempt to recover in any ways the exhaust air from a dryer or a range hood. This would cause clogging of the filters and recovery module (if applicable); this is also a fire hazard. Not following this warning will void the warranty.
5. TYPICAL INSTALLATIONS
Installations may vary according to the model number, the product orientation (vertical or horizontal) and the location in the home where the unit is installed. Use the following illustrations as guidelines to help you decide the appropriate installation.
The unit allows for multi positional mounting (vertical or horizontal). It may be hung to the joists (preferred method),or it may be laid down on one of three surfaces, and installed either vertically or horizontally. NOTE: For more details, see Points 5.3 and 5.4 in Section 5 INSTALL THE UNIT. In every case, bathroom fans and a range hood should be used as spot ventilation to exhaust stale air. Also, for homes with more than one level, we recommend placing one exhaust register at the highest lived-in level. There are threer installation methods: Stand Alone, Central Draw Point* and Return-to-Return*. * Different connections to a forced air system. Multiple furnaces or air handlers may require installation of GuardianPlus on each system for maximum IAQ benefit.
NOTE: A grounded three-prong electrical outlet has to be available within 3 feet from the unit.
- 8 -
INSTALLING 8’’ DUCTS AND
VD0129
VC0059
High
Low
OFF
Reset Filter
Filter Maintenance
Power
VI0013
REGISTERS
SEE SECTIONS 6.5
SECTION 7: CONTROLS
STAND ALONE INSTALLATION
SEE SECTION 5.3.1
VH0037
RETURN-TO-RETURN INSTALLATION
SEE SECTION 5.5.1
VH0047
SEE SECTION 6.4
HOW TO HANG THE UNIT
NOTE:OTHER INSTALLATIONS SHOWN NEXT PAGES
INSTALLATION TYPE SHOWN:CENTRAL DRAW POINT
5.1. GSFH1K UNIT INSTALLATION
SEE SECTION 5.4.1
VH0038
- 9 -
VD0150
VO0029
Off
Recirculation
Reset Filter
Filter Maintenance
Fresh air
High Ventilation
Low Ventilation
VC0060
INSTALLING 8’’ DUCTS AND
VI0011
REGISTERS
SEE SECTIONS 6.5
STAND ALONE INSTALLATION
SEE SECTION 5.3.1
RETURN-TO-RETURN INSTALLATION
SEE SECTION 5.5.1
SECTION 7: CONTROL
VH0039
HOW TO HANG THE UNIT
SEE SECTION 6.4
VH0043
CONNECTING THE DRAIN
NEXT PAGES
NOTE:OTHER INSTALLATIONS SHOWN
SEE SECTION 6.11
5.2. GSVH1K, GSHH3K AND GSEH3K UNITS INSTALLATION
INSTALLATION TYPE SHOWN:CENTRAL DRAW POINT
SEE SECTION 5.4.1
- 10 -
VH0040
OUTDOOR CONNECTION
SEE SECTIONS 6.7, 6.8 AND 6.9
5. TYPICAL INSTALLATIONS (CONT’D)
5.3 STAND ALONE INSTALLATION
(Primarily for homes with no central air mover or equipped with wall furnaces, radiant hot water or electric baseboard heating.)
5.3.1 BASEMENT
• Ideal for homes without a central furnace in the basement. Allows filtration and a better air circulation throughout the house.
• Easy access to perform the periodic
filter maintenance and servicing.
• Offers an ambient temperature
above freezing (32°F - 0°C).
• The HEPA Filtration model GSFH1K
has no connection to the outside, so all parts encircled are not required.
INSTALLATION CONSIDERATIONS:
• Installing the unit near an exterior
wall will shorten the length of the insulated ducts (not necessary for HEPA Filtration only model GSFH1K).
• If a HEPA Filtration Fresh Air &
Heat Recovery Ventilation model GSHH3K is installed, a water drain must be close to collect the run-off.
Only for the models GSVH1K,
GSHH3K and GSEH3K that
use fresh outside air.
VH0039
Drain required only for the GSHH3K model.
5.3.2 GARAGE CLOSET
• Ideal for homes without a central
furnace, or limited space applications, allows filtration and a better air circulation throughout the house.
• Easy access to perform the periodic
maintenance (twice a year).
• The HEPA Filtration model GSFH1K
has no connection to outside, so all parts encircled are not required.
Only for the models GSVH1K,
VH0046
GSHH3K and GSEH3K that
use fresh outside air.
CAUTION
When the ambient temperature for the unit location is below freezing (32°F - 0°C), the unit must run continuously to prevent condensation.
INSTALLATION CONSIDERATIONS:
• Installing the unit near an exterior wall will shorten the length of the insulated ducts
(not necessary for HEPA Filtration model GSFH1K).
• If a HEPA Filtration Fresh Air & Heat Recovery Ventilation model GSHH3K is installed, a water drain must be close to collect
the run-off.
• All ducts must be insulated.
• For the HEPA Filtration, Fresh Air & Heat Recovery Ventilation (GSHH3K) and the HEPA Filtration, Fresh Air & Energy
Recovery Ventilation (GSEH3K) models only, if the ambient temperature around the unit drops below freezing (32°F - 0°C), go to Section 6.12 (Low Temperature Applications) for instructions on drain line protection (GSHH3K only) and other cold environment installation details.
- 11 -