Guardian Equipment G1996 User Manual

Page 1
Stainless Steel Safety Stations
Item Part Number Description
A
AP450-048
B
320-08E
Shower Valve Assembly
C
AP620-335H
Pipe Packs
D
AP520-100
AP520-170
AP530-100
Eyewash Valve Assemblies
E
AP620-101H
AP620-101H-HFC
10” Dia. Stainless Steel Shower Head
1” IPS Stainless Steel Elbow
1” IPS Stainless Steel Stay-Open Ball Valve, Single Activation. Furnished with stainless steel actualing arm.
Stainless Steel Pipe Pack for Units with Eyewash Bowl
Stainless Steel Pipe Pack for Barrier-Free Units
Orange Pipe Covers
1/2” IPS Stainless Steel Ball Valve with Stainless Steel Flag Handle
1/2” IPS Stainless Steel Ball Valve with Stainless Steel Flag Handle for Units with Hand/Foot Control
B C
A
I
J
D
F
320-10F
G
AP050-010SS
H
See Page 2
Shower Pull Rods
I
AP050-079
AP050-080
Sign
J
AP250-008G
Stainless Steel Floor Flange, 1 1/4” N PT Female Connection
Stainless Steel Foot Treadle and Return Spring with Aluminum Clevis Pin
Eyewash and Eye/Face Wash Assemblies
29” Stainless Steel Pull Rod
47 1/2” Stainless Steel Pull Rod
Emergency Safety Station Sign
H
E
Guardian Equipment 1140 N. North Branch Chicago, IL 60642
312 447 8100 telephone 312 447 8101 facsimile
gesafety.com
G
F
rev. 0313 / © 2013 Guardian Equipment
Page 2
Eyewash and Eye/Face Wash Assemblies
for Stainless Steel Safety Stations
Item Part Number Description
Spray Head Dust Covers
470-001
A
470-021
Outlet Assemblies
AP470-100SS-R
B
AP470-110SS-R
AP470-120SS-R
AP470-127SS-R
SI130-02-04
C
GS-Plus™ Spray Head Assy.
FS-Plus™ Spray Head Assy.
(2) GS-Plus™ Spray Heads with Stainless Steel Fittings
(2) FS-Plus™ Spray Heads with Stainless Steel Fittings
(4) GS-Plus™ Spray Heads with Stainless Steel Fittings
(4) GS-Plus™ Spray Heads with Stainless Steel Fittings for Barrier­Free Units
3/8” IPS X 2-1/4” Stainless Steel Shank
A
Item Part Number Description
Bowls
100-008R
D
100-014R
100-008X
100-014X
Drain Plate Assemblies
AP150-012A
E
AP150-012B
Note: Includes Drain Plate, Cupped Washer, And Gasket
Stainless Steel Bowl
Stainless Steel Bowl for Barrier-Free Units
Stainless Steel Bowl with Neck
Stainless Steel Bowl with Neck for Barrier-Free Units
Drain Plate Assembly for Plastic Bowls
Drain Plate Assembly for Stainless Bowls
A
B
B
C
E
C
A
D
B
D
C
Guardian Equipment 1140 N. North Branch Chicago, IL 60642
312 447 8100 telephone 312 447 8101 facsimile
gesafety.com
rev. 0313 / © 2013 Guardian Equipment
Page 3
Assemby Instructions
Stainless Steel Safety Stations
Safety stations are designed for easy assembly in the field. Essentially, these units are assembled from the “bottom up”, as described below:
1. Assemble floor flange (A), 1 1/4” IPS x 6 5/8” plugged nipple (B), and outlet tee (C). If unit has a foot treadle, the floor flange and treadle are pre-assembled. Position foot treadle for proper access by users, and tee for connection to drain.
2. Assemble 1 1/4” IPS x 17 3/4” nipple (D) and frame assembly (E). Position frame assembly for proper access by users.
3. Assemble 1 1/4” IPS x 32” nipple (F) and inlet tee (G). Position tee for connection to supply. If the top vertical inlet will be employed, plug tee with supplied 1 1/4” I PS square head plug.
4. Assemble 1 1/4” IPS x 22” nipple (H) and 1 1/4” x 1” IPS reducing inlet tee (I). Position tee forward for proper location of shower. If the back horizontal inlet will be employed, plug tee with supplied 1 1/4” IPS square head plug.
5. Assemble 1” IPS x 8 7/8” nipple (J), emergency shower valve (K), 1” IPS x 10 1/2” nipple (L), elbow (M), and shower head (N).
6. Place cupped, stainless steel washer (O), rubber gasket (P), and bowl (Q) onto waste receptor. Center components to assure a watertight seal.
7. Thread drain plate (R) down onto mounting shank as far as possible. If neccessary, rotate bowl clockwise to draw drain plate down onto mounting shank.
8. Thread eye or eye/face wash spray head assembly onto mounting shank. Position outlet heads for proper access by user.
9. Secure entire unit to floor and/or wall for stability.
10. If unit has foot treadle, connect foot treadle chain to valve/handle assembly.
11. Attach orange plastic pipe wrap and sign.
Notes:
1. All threads are tapered pipe and require pipe joint compound or Teflon tape to assure watertight connection.
2. If unit is furnished with corrosion-resistant powder coating, care must be taken to avoid damaging finish during assembly. For best results, a strap wrench should be used.
3. Test the entire unit for proper operation.
4. The use of dielectric unions is required when connecting to copper supply to avoid premature corrosion.
JKLMN
10 1/2”
Nipple
8 7/8”
Nipple
I
H
22” Nipple
G
F
32” Nipple17 3/4” Nipple
E
R
Q
D
P
O
C
B
Guardian Equipment 1140 N. North Branch Chicago, IL 60642
312 447 8100 telephone 312 447 8101 facsimile
gesafety.com
A
rev. 0313 / © 2013 Guardian Equipment
Page 4
GS-Plus™ and FS-Plus™ Spray Heads
Each spray head head features:
• Tough polypropylene plastic construction
• Highly visible integrated nylon dust cover
• Easily accessible 1.8 GPM (GS-Plus™) or 3.2 GPM (FS-Plus™)
flow controls.
• Dense (60 pore per inch) polyurethane filter
• Unique design provides a consistently soft, full spray of
water across a range of working pressures from 30 to 100 PSI
A
Item Part Number Description
AP470-001
A B C
D
E
F
G
H
AP470-002R
470-004R
470-005R
AP470-021
AP470-022R
470-024R
470-025R
GS-Plus™ Spray Head (assembled)
Dust Cover and Cap Assembly
60 PPI Polyurethane Filter
1.8 GPM Flow Control
FS-Plus™ Spray Head (assembled)
Dust Cover and Cap Assembly
60 PPI Polyurethane Filter
3.2 GPM Flow Control
E
B
C
F
G
IMPORTANT
In order to operate properly,
the flow control must be
inserted into the body
concave end first.
D
H
Guardian Equipment 1140 N. North Branch Chicago, IL 60642
312 447 8100 telephone 312 447 8101 facsimile
gesafety.com
rev. 0313 / © 2013 Guardian Equipment