Guardian SA12020 User Manual

N8724V1 5/00
downloaded from: http://www.guardianalarms.net
PTDCM
(SA12020)
PassPoint Door Control Module
INSTALLATION INSTRUCTIONS
General Information
The Door Control Module (DCM) is used to control access points, or doors. When connected between door hardware and the Main Logic Board, the DCM accepts data from card readers and/or keypads, and operates the electromagnetic devices used to lock and unlock the door. The DCM mounts in a standard cabinet and communicates with the system’s MLB via a twisted pair network connection.
Each DCM provides all the inputs and outputs necessary to manage two single-reader access points or one two-reader access point.
Power Requirements
When mounted in a cabinet with a dedicated power supply, the DCM obtains its power from the LOCAL (J1) power output connection of its associated power supply. When added to a cabinet along with an MLB or other module, the DCM obtains power from the power supply’s REMOTE (J5) power output.
The DCM board requires 10.5-14VDC @ 170mA, but its actual current requirement will be determined by the addition of the current requirements of two card readers (or keypads), which are typically 90mA each. The DCM also provides two power supply monitoring inputs: Low Battery and AC Loss. These two inputs are compatible with the corresponding monitoring outputs of the PassPoint PTDPSU power supply only. (Do not enable AC or Low Battery monitoring without first wiring the power supply.)
DCM Relay Outputs
In addition to card reader inputs, each DCM has two Form C, voltage-supervised output relays. These relays are used to operate electromagnetic door locks or doorjamb mounted lock strikes. Use appropriate transient suppression for the installed locking devices.
All DCM relays may be used as committed resources to control access points. For instance, one of the operating parameters that can be configured for DCM relays is the length of time that the relay output is energized when allowing entry or exit through an access point. DCM relays cannot be commanded ON or OFF when used as a committed resource. Instead, the access point these relays are assigned to must be bypassed or locked.
The relay output circuitry provides for a supervision input (30VRMS or 30VDC max.) which, when connected to the common contact of the relay, indicates that a voltage of more than approximately 4VDC or 4VAC is present at the relay contacts. The supervision input is rectified and filtered before going to the comparator, therefore DC & AC voltages can be supervised. The module's firmware doesn't know or care if the voltage is DC or AC. This supervision can be useful to determine if the power supply that is used to power a connected load is fully operational. Each relay can be programmed to monitor the relay contact voltage or to ignore it.
– 1 –
If you choose to connect the supervision inputs, make sure that you enable the corresponding relay’s voltage supervision.
DCM Trigger Outputs
The DCM provides two trigger outputs (15mA, 15VDC, open collector, sink to ground). Each trigger contains a 680 ohm series resistor. A trigger is considered “ON” when its output transistor is turned on, allowing current (up to 15mA) to flow into the trigger output pin from a higher potential.
Normally, triggers are configured as part of an access point, as pre-alarm triggers. Pre-alarm triggers can operate a sounder or LED to indicate to a user that a door is being held open too long and, unless the door is closed, the access point will go into alarm. The pre-alarm trigger is also turned on when an access point is in an alarm state. If it is desired that the trigger control a loud sounder that requires more than 15 mA to operate, the trigger can be used to energize a separate relay that in turn will control the sounder.
Triggers can be configured in three different ways:
Controlled - The system or a user can command the trigger on or off.
One-Shot - When commanded by the system or a user, the trigger turns on or off for a specified number of seconds, then de-energizes.
Repeating - When commanded by the system or a user, the trigger turns on for a specified number of seconds, then turns off for a specified number of seconds. This cycle is then repeated, also for a specified period of time or repeated indefinitely until commanded to stop.
DCM Zone Inputs
The DCM provides four zone inputs. Each zone is capable of a supervised (3-state) or unsupervised (2-state) configuration. Normally, zones are configured as part of an access point to provide Door Status Monitoring or Request-To-Exit inputs.
DCM zone inputs can be configured in one of four ways:
Normally Open
Normally Closed
EOLR (End of Line Resistor) Normally Open
EOLR (End of Line Resistor) Normally Closed (EOLR zones require Ademco’s standard 2K ohm end of line resistors)
The following table details the various configuration options for DCM zone inputs:
Zone States TWO STATE ZONE
Normal
Sensor State
0
(short)
R NA NA NORMAL NORMAL
2R NA NA NA NA infinite (open)
Sensor
Connections
(unsupervised)
Normally
Open (N.O.)
FAULT NORMAL FAULT TROUBLE
NORMAL FAULT TROUBLE FAULT
Normally
Closed (N.C.)
THREE STATE ZONE
(EOLR supervised)
Normally
Open (N.O.)
R
Normally
Closed (N.C.)
R
– 2 –
Loading...
+ 2 hidden pages