Guardian le User Manual

Page 1
sm electrics
operating device
LOD 210.24.0.0
with display, key switch & rotary
encoder w. push button
connecting module
LCM 210.24.0.0
NMEA Expansion Module
NMEA 210.24.0.0
Bridge Navigational Watch Alarm System
acc. MSC .128/75 & IEC 62616
le guardian 2025
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
1 user manual le guardian vers 2.05 - 201703109
Page 2
sm electrics
content
1 Instruction for use ................................................................................. 5
2 Installation ............................................................................................ 6
3 Commissioning ...................................................................................... 8
4 Test mode - maintenance & service (service menu #1) ............................ 11
5 Trouble shooting .................................................................................. 15
6 Centralized dimmer .............................................................................. 17
7 Adjust time period of alarm stage 2 (alarm in officer’s area) ...................... 18
8 Adjust buzzer characteristics & volume ................................................... 20
9 service menu overview ......................................................................... 22
10 Technical data and schematics ............................................................... 23
11 NMEA expansion module ....................................................................... 50
11.1 NMEA expansion module installation ................................................. 51
11.2 NMEA expansion module commissioning............................................ 52
11.2.1 Enabling NMEA expansion module (service menu #5) ...................... 52
11.2.2 Define quantity of involved back-up OOW cabins (service menu #2) . 54
11.2.3 Define relation between cabin number and real cabin location .......... 56
11.2. Transmit NMEA sentences to external systems (especially VDR) .......... 57
11.3. Receive NMEA sentences from external systems................................ 59
12 user manual short version (for users only) .............................................. 62
12.1.0 Generals ............................................................................. 62
12.1.1 Installation .......................................................................... 63
12.2.1 Manual switch on ................................................................. 63
12.2.2 Automatically switch on ......................................................... 64
12.3.0 Select dormant (main) period ................................................. 64
12.3.1 Reset of dormant (main) period .............................................. 64
12.3.2 Alert sequences start automatically ......................................... 65
12.3.2.1 visual alarm indications (pre-alarm) ........................................ 65
12.3.2.2 Alarm stage 1 ....................................................................... 65
12.3.2.3 Alarm stage 2 ....................................................................... 66
12.3.2.4 Alarm stage 3 ....................................................................... 66
12.4.1 Back-up OOW’s selection & indication ...................................... 67
12.5.1 Emergency call ..................................................................... 69
12.6.1 System shut down ................................................................. 70
2 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 3
sm electrics
In the course of the latest software release LOD_170223_D02, several changes in the operating philosophy have been made.
Emergency call can only be triggered and reset by pushing the rotary
knob on operating device. In addition it is possible to release an emergency call via external NMEA-telegram according to iec-regulation (see page 59-61).
 Service menu only contains 3 possible adjustments.
Test menu (1 – 3 sec access period), amount of OOW cabins (4 – 6 sec access period), en-/disable of NMEA expansion module (7 – 9 sec access period). All other menus (known from former versions) are no longer available. In case of service menu’s inactivity within 3 minutes, the LOD will jump from service menu to READY FOR AUTO ON/OFF automatically.
In case of connection failure between LOD and NMEA expansion module,
the toggling display alarm indication will not appear on the display. Failure relay K1 will drop out as usual and the failure indication will be shown at the select menu’s last position.
In case of any alert, the possibility of dimming the display and the internal
buzzer is disabled.
The possibility to connect external transfer alarms to the NMEA
expansion module is not available anymore.
The possibility to connect external emergency call release button to the
NMEA expansion module is not available anymore.
Starting the countdown is only possible by actuating the key switch on
LOD or by keeping the external steady contact (29, 30) closed.
3 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 4
sm electrics
4 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 5
sm electrics
1 Instruction for use
le guardian 2025 and its extension devices (time period reset units, alarm devices) must only be installed by trained electricians or other persons who are familiar with installation of electric equipment.
Parts of the system can be damaged and persons put at risk if system is connected incorrectly.
Connecting module (LCM 210.24.0.0) and NMEA expansion module (NMEA
210.24.0.0) are designed to be installed in an enclosure switch cabinet or control console. For service and commissioning work connecting and expansion modules should be installed in such manner, service personnel is able to see state LEDs on modules.
Operating device (LOD 210.24.0.0) is designed to be installed on control console.
Operating device and all time period reset units have to be installed only at locations on bridge or bridge wings where OOW has a proper look out.
Installation must conform to regulations for electromagnetic compatibility (EMC). (see chapter technical data & schematics)
5 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 6
sm electrics
connecting module
LCM 210.24.0.0
-Z1
15 pole connector
to operating device
fuse holders
-F1, -F2 (m2A)
terminals for
24VDC power supply
terminals for
periphery equipment
2 Installation
Connecting module (LCM 210.24.0.0) and its extension devices (time period reset units, alarm devices) have to be connected according to corresponding wiring diagrams.
description
connecting module (LCM 210.24.0.0)
Module has been designed to click on terminal rail TS 35 inside electric cabinet or control console. All periphery equipment (time period reset units, alarm panels, power supply) is to be connected directly on connecting module without any additional terminal board or distribution boxes according to wiring diagram which is part of working drawings. Sample system wiring diagram is shown in
chapter “technical data & schematics”.
Outputs for “power on” indication and time period reset push button illumination
are short-cut protected. Maximum loads of outputs and output contacts see chapter “technical data & schematics”.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
6 user manual le guardian vers 2.05 - 201703109
Page 7
sm electrics
operating device LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
operating device (LOD 210.24.0.0)
Before mounting operating device into cut-out, plug on 15-pole system cable on device’s rear side and tighten it properly. Use device clamps to fix device in proper manner.
Do not use longer system cable as standard length: l=3m!
Plug on 15-pole system cable on connecting module LCM 210.24.0.0 (-Z1) and tighten it properly.
After connecting all additional equipment (time period reset units, alarm devices) according to corresponding wiring diagram, system is ready for operating.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
7 user manual le guardian vers 2.05 - 201703109
Page 8
sm electrics
display „text 1“
system fail state relay K1 with control LED 1
READY FOR
POWER ON / AUTO
3 Commissioning
Before switching on 24VDC (nominal) power supply to connecting module LCM
210.24.0.0 terminal board –X1: 1, 2 (+) & 3, 4 (-) make sure power supply, time period reset units and external alarm devices have been connected correctly according to wiring diagram.
Diode on LCM 210.24.0.0 connecting module secures system against wrong power supply polarity.
After switching on 24VDC power supply (generally from 24VDC Emergency Distribution Board) system fail state relay K1 is activated and display on operating device LOD 210.24.0.0 shows “text 1 after a short intro procedure.
In case of system fail, relay K1 is not activated (control LED 1 is switched off). When system is running properly, relay K1 is triggered and its potential free contact is closed (-X1: 5, 6) Make sure that up to now no external power on contact (steady contact: ­X1:29, 30 and pulsed contact: -X1: 26, 27 & 50, 51) is active.
System is running now and is waiting for user’s operation on operating device LOD 210.24.0.0 or for an external “power on” command. Display shows “text1”.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
8 user manual le guardian vers 2.05 - 201703109
Page 9
sm electrics
operating device LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
display „text 2
COUNT-DOWN
*** 2:59 ***
Switch on system by turning key switch S1 on operating device LOD 210.24.0.0 one time to position “ON/OFF”
After system is switched on default dormant period (3:00min) is counting down and display shows current state of count-down (display “text 3”).
Test of external illuminated time period reset unit:
In this “count-down mode” all illuminated time period reset units are activated. Illumination of display and of reset units is adjustable by turning rotary encoder. Minimum illumination is fixed.
Now push external reset units (one by one) and check 2nd line of display (current value). Every reset should restart count-down ( 2:59).
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
9 user manual le guardian vers 2.05 - 201703109
Page 10
sm electrics
display „text 1“
READY FOR
POWER ON / AUTO
system is
shut down
Test of external “power on” devices: (optional)
In case external “power on” devices are involved, activate these devices (one by
one). Make sure before, display “text 1” is shown. Only in this “auto mode” an
external “power on” is possible.
notice:
Every switching on (from operating device LOD 210.24.0.0 or from external devices) restarts count-down!
Test of external alarm devices and links
For checking alarm devices (external buzzers on bridge or bridge wing area,
alarm panels in officer’s area, link to general alarm system, link to VDR system and system failure contact see chapter 4 “test mode” (maintenance & service)
For finishing commissioning procedure “switch off” system by turning key switch
S1 on operating device LOD 210.24.0.0 to position “ON/OFF” for longer than 2 sec.
Display shuts down and system ignores all external inputs now.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
10 user manual le guardian vers 2.05 - 201703109
Page 11
sm electrics
operating device LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
display „text 4
TEST MODE 1 OFF
ALARM on BRIDGE
key switch
S1
display „text 5
TEST MODE 1 ON
ALARM on BRIDGE
4 Test mode - maintenance & service (service menu #1)
le guardian procedure to check all output relevant devices (alarm panels, external buzzers, links to alarm devices, links to VDR and system failure contact) in a very comfortable manner.
To reach this “service mode 1an authorized person has to “switch off” system by turning key switch S1 on operating device LOD 210.24.0.0 to position “ON/OFF” for longer than 2 sec. System shuts down. After that authorized person has to keep pushing rotary encoder push button S2 and after a period between 2 and 3 sec he has to “switch on” system by turning key switch S1 on operating device LOD 210.24.0.0 one time to position “ON/OFF”
System starts in “service mode and display is showing “text 4”
By pushing rotary encoder’s push button S2 for one time, all internal and external bridge area alarm devices (alarm stage 1) are activated as long as push button S2 is pushed again. During this manual alarm activation, display is showing “text 5”.
2025
Bridge Navigational Watch Alarm System owns a test mode
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
11 user manual le guardian vers 2.05 - 201703109
Page 12
sm electrics
display „text 6
TEST MODE 2 OFF
OFFICERs ALARM
display „text 7
TEST MODE 2 ON
OFFICERs ALARM
display „text 8
TEST MODE 3 OFF
ALARM STAGE 3
display „text 9
TEST MODE 3 ON
ALARM STAGE 3
After a.m. test in “test mode 1” is done, user has to turn rotary encoder clockwise to reach “test mode 2”.
Display is showing “text 6” and after pushing rotary encoder’s push button S2 for
one time, all alarm devices in officer’s area (alarm stage 2) and link to VDR
system (optional) are activated as long as push button is pushed again. During this manual alarm activation, display is showing “text 7”.
After a.m. test in “test mode 2” is done, user has to turn rotary encoder clockwise to reach “test mode 3”.
Display is showing “text 8” and after pushing rotary encoder’s push button S2 for
one time, system’s contact is activating very loud alarm devices in officer’s area
(alarm stage 3) and link to VDR system (optional) as long as push button is pushed again.
During this manual alarm activation, display is showing “text 9”.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
12 user manual le guardian vers 2.05 - 201703109
Page 13
sm electrics
connecting module
LCM 210.24.0.0
system fail relay
K1 with control LED 1
display „text 10
TEST MODE 4 OFF
DEVICE FAILURE
display „text 11
TEST MODE 4 ON
DEVICE FAILURE
alarm stage 3 relay
K4 with control LED 4
alarm stage 1 relay
K2 with control LED 2
alarm stage 2 relay
K3 with control LED 3
After a.m. test in “test mode 3” is done, user has to turn rotary encoder clockwise to reach “test mode 4”.
Display is showing “text 10” and after pushing rotary encoder’s push button S2
for one time, device’s failure contact opens and activate linked alarm system as
long as push button S2 is pushed again.
Consider possible alarm delay period created by linked alarm system!
During this manual alarm activation, display is showing “text 11”.
State of all output relays is shown by corresponding control LEDs. Consider reversed relay logic of system failure relay K1!
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
13 user manual le guardian vers 2.05 - 201703109
Page 14
sm electrics
operating device LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
For finishing “test mode” procedure “switch off” system by turning key switch S1 on operating device LOD 210.24.0.0 to position “ON/OFF”.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
14 user manual le guardian vers 2.05 - 201703109
Page 15
connecting module
LCM 210.24.0.0
system fail relay
K1 with control LED 1
fuse holder
F1, F2
system fail criteria
sm electrics
5 Trouble shooting
In following cases potential free (dry) n/o contact on connecting module LCM 210.24.0.0 –X1: 5, 6 opens (system fail state):
power supply failed (or main power supply voltage is lower than 13,2V) program cycle interrupted (risc controller has been stopped) link with 15 pole system cable Z1 between operating device and connecting module is
interrupted
in case NMEA expansion module is involved, when communication between operating
device (LOD 210.24.0.0) and expansion module (NMEA 210.24.0.0) has been failed
a) check supply voltage by comparing it with other systems fed from same distribution
source.
b) Switch off system’s power supply for minimum 10 sec by opening fuse holder F1
or F2 on connecting module LCM 210.24.0.0. After switching on power supply, program will start automatically after 2 sec. in normal mode.
c) check system cable between connecting module LCM 210.24.0.0 and operating
device LOD 210.24.0.0, especially system plug on operating device’s rear side. Cable might be damaged.
System fail state is indicated when system fail relay K1 is not triggered (control LED D9 is off).
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
15 user manual le guardian vers 2.05 - 201703109
Page 16
sm electrics
Notice:
In case that during watch operations system’s power supply fails temporary (e.g. black-out situation) watch operations restart automatically with old settings (settings before power fail).
time period cannot reset, emergency call cannot reset
check all reset units if reset contact is closed permanently by switch’s malfunction or accidental use.
No indication light is active (reset units & external “power on” devices)
Check if system is might be switched off by external system. Use key switch S1 on operating device LOD 210.24.0.0.
Notice:
time period reset unit illumination and external “power on” indication are active only,
when count-down sequence is started.
If system works properly but without any indication, one bulb or LED in time period reset units or external “power on” devices might be blown in that way, causing a short­circuit. Replace damaged bulb / LED. Short-circuit does not damage system due to short-circuit protected transistor outputs.
16 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 17
sm electrics
operating device LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
6 Centralized dimmer
le guardian 2025 BNWAS is designed with a centralized dimmer function. That means all relevant illuminated time period reset units on bridge and bridge wing area as well as blue display on operating device LOD 210.24.0.0 are adjustable by turning rotary encoder S2 on operating device LOD 210.24.0.0. Minimum illumination is limited. Dispay’s illumination and time period reset unit’s illumination are sychronized. In case of any alert, the possibility of dimming the display and the internal buzzer is disabled.
By turning rotary encoder S2 on operating device LOD 210.24.0.0 in counter clock wise direction, illumination is decreasing. By turning rotary encoder S2 on operating device LOD 210.24.0.0 in clockwise direction, illumination is increasing.
Notice:
dimmer function is suppressed during any kind of settings changing procedure by using rotary encoder!
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
17 user manual le guardian vers 2.05 - 201703109
Page 18
sm electrics
new time period of alarm stage 2
[90sec.... 180sec]
date & sign
operating device LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
7 Adjust time period of alarm stage 2 (alarm in officer’s area)
(for authorized persons only)
IMO regulations allow (MSC 75/24/Add.1 ANNEX 11, 4.1.2.7) to increase standard setting of 90 sec of alarm stage 2 (alarm in officer’s area). Compare with chapter 9 technical data and schematics (see watch alarm time table). Adjustment could be necessary due to large vessel or vessel’s layout. Period can be adjusted to max. 180sec (default value is 90sec), to allow sufficient time for back-up officer and/or Master to reach bridge area before watch alarm system is triggering alarm stage 3.
Write down decided new value here:
To adjust a.m. time period turn key switch S1 on operating device LOD 210.24.0.0 to position SELECT”.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
18 user manual le guardian vers 2.05 - 201703109
Page 19
sm electrics
display „text 3
SET MAIN PERIOD:
3… 12min ** 3 **
display „text 24
PERIOD ADJUST
AL.STAGE 2 090s
After turning key switch S1 to position “SELECT” display is showing “text 3”.
Now push rotary encoder’s push button S2 on operating device LOD 210.24.0.0 so often as display is showing “text 24”.
Now turn rotary encoder in clockwise direction to increase time period value or in counter­clock wise direction to decrease time period value. System allows only values between 90
and 180sec. By pushing rotary encoder’s push button S2 on operating device LOD
210.24.0.0 display is changing and system accepts adjusted value.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
19 user manual le guardian vers 2.05 - 201703109
Page 20
sm electrics
operating device LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
display „text 3
SET MAIN PERIOD:
3… 12min ** 3 **
display „text 22
BUZZERs
PROPERTIES 1
8 Adjust buzzer characteristics & volume
le guardian 2025 system is designed with adjust mode to be able to change steady internal and external alert tone into 7 additional individual buzzer characteristics in case other systems on bridge area are generating a similar alert tone.
Adjust buzzer’s characteristic
To adjust buzzer’s characteristic turn key switch S1 on operating device LOD 210.24.0.0 to position “SELECT”.
After turning key switch S1 to position SELECTdisplay is showing “text 3”.
Now push rotary encoder’s push button S2 on operating device LOD 210.24.0.0 so often
as display is showing “text 22”.
Now turn rotary encoder to choose an adequate buzzer characteristic. By pushing rotary encoder’s push button S2 display is changing and system accepts adjusted value.
Do not accept offered buzzer characteristics during buzzer is activated
(Wait for the brake!)
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
20 user manual le guardian vers 2.05 - 201703109
Page 21
sm electrics
operating device LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
display „text 3
SET MAIN PERIOD:
3… 12min ** 3 **
display „text 23
BUZZERs
SOUND VOLUME 15
Adjust internal buzzer’s volume
To adjust internal buzzer’s volume turn key switch S1 on operating device LOD
210.24.0.0 to position “SELECT”. Minimum sound volume is limted to 65dB(A)
After turning key switch S1 to position SELECTdisplay is showing “text 3”.
Now push rotary encoder’s push button S2 on operating device LOD 210.24.0.0 so often
as display is showing “text 23”.
Now turn rotary encoder in counter clock wise direction to decrease buzzer’s sound
volume or in clock wise direction to increase sound volume. By pushing rotary encoder’s
push button S2 display is changing and system accepts adjusted value.
Notice:
During alarm stage 1 (alarm on bridge & bridge wing area) internal buzzer’s sound volume can be adjusted by turning rotary encoder on operating device!
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
21 user manual le guardian vers 2.05 - 201703109
Page 22
sm electrics
9 service menu overview
(for commissioning and service staff only!
Service menu #1: Test Mode 1...4 to simulate alarm stage #1, stage #2, stage #3
and system’s fail state.
Pushing period after shut-down: 1-3 sec Service menu #2: Define quantity of involved back-up OOW cabins
Pushing period after shut-down: 4-7 sec Menu is available only after NMEA expansion module is enabled!
Service menu #3: Enabling / disabling of NMEA expansion module
Pushing period after shut-down: 7-10 sec
22 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 23
sm electrics
generals
description: le guardian 2025 BNWAS power supply: 24VDC (nominal), 18,0… 31,2VDC, nominal feeding value: B4A power consumption: min. 60mA, max. 400mA, nominal value: 120mA internal fuses: 2x m2,0A, 5x20mm degree of enclosure: acc. EN 60529 see table approbation: design & manufacturing acc. IEC 60945, type approvals: GL, KR, RRS transistor outputs: “power on” indication: max. 400mA, reset p/b illumination: 2x 180mA max. load of relay contacts: 30VDC, 2A
no.:
type:
description:
weight: [kg]
degree of enclosure
safety distance
to magnetic
compass [m]:
cable
cross-sections:
spare parts:
1
operating device LOD 210.24.0.0
console mounted operating device with blue illuminated display, key switch and rotary encoder with integrated push button, w 144 x h 72 x d 75mm
device: 0,200
cable: 0,300
front: IP22 back: IP00
0,5
/
-
2
connecting module LCM 210.24.0.0
terminal board module, to be mounted on terminal rail TS35, w 162 x h 127 x d 68mm
0,330
IP20
0,5
0,2....1,5mm²
2x micro fuse, m2,0A, 5x20mm part no.: 097109
3
NMEA exp. module NMEA 210.24.0.0
terminal board module, to be mounted on terminal rail TS35, w 87,1 x h 127 x d 68mm
0,164
IP20
0,5
0,2....1,5mm²
1x micro fuse, m2,0A, 5x20mm part no.: 097109
4
WAP 220.2.0.0
watch alarm panel for officer's cabin, 80 dB(A) flush mounting
0,150
front: IP23 back: IP00
/
0,2... 2,5mm²
1x bulb, mg28V, 40mA part no.: 099081
5
WAP 220.5.0.0
watch alarm panel for officer's cabin, 80 dB(A) bulkhead mounting
0,275
IP23
/
0,2... 2,5mm²
1x bulb, mg28V, 40mA part no.: 099081
6
WAP 220.4.0.0
watch alarm panel for officer's area (corridor), 64-111dB(A) bulkhead or flush mounting
0,870
IP65
/
0,2... 2,5mm²
1x bulb, E14, 24V, 4W part no.: 099141
7
WAR 220.1.0.0
watch alarm reset push button, illuminated, connecting type: welding
0,045
IP67
/
0,2...
0,75mm²
1x bulb, T5,5, 28V, 40mA part no.: 099076
8
WAR 220.1.0.1
watch alarm reset push button, illuminated, connecting type: screws
0,080
IP65
/
0,2... 2,5mm²
1x bulb, Ba9s, 28V, 45mA part no.: 099083
9
WAB 220.1.0.0
watch alarm wall box with buzzer, 85 dB(A)
0,750
IP65
/
0,2... 2,5mm²
/
10
WAB 220.2.0.0
external watch alarm buzzer, 85 dB(A) one whole installation, 22,5mm
0,030
IP65
/
0,2... 2,5mm²
/
11
WAR 220.2.0.0
watch alarm wall box for reset, illuminated
0,750
IP65
/
0,2... 2,5mm²
1x bulb, T5,5, 28V, 40mA part no.: 099076
12
WAR 220.2.1.0
watch alarm wall box for reset, illuminated with buzzer, 85 dB(A)
0,850
IP65
/
0,2... 2,5mm²
1x bulb, T5,5, 28V, 40mA part no.: 099076
13
WMS 220.2.0.0
watch alarm motion sensor kit for OOW’s activity detection for
count-down reset (module data)
0,070
IP20
0,4 / 0,35
0,2... 2,5mm²
10 Technical data and schematics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
23 user manual le guardian vers 2.05 - 201703109
Page 24
sm electrics
24 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 25
D
-
-
modification
F
G
-
-
-
LCM 210.24.0.0 AS RevK
HULL
Drawing No.
sme
­name
spare of:
department:
Shipyard
T. Streit-
-
class
WATCH ALARM SYSTEM
GL
BRIDGE NAVIGATIONAL
A4
Title:Scale
OFFICER'S AREA
75 - 85dB(A), 1m
STAGE 2 ALARM
ALARM DEVICES
OFFICER'S AREA
STAGE 3 ALARM
85 - 112dB(A), 1m
ALARM DEVICES
1
1
-
+
-=
(optional)
WAB 220.2.0.0
or Failure Alarm P.
Naut. Al. System
AUTO PILOT
(optional)
location
FAP 220.1.0.0
24VDC
POWER SUPPLY
FOR NAV. EQUIPM.
+
-
1 2
1 2 21
2x0,75
2x0,75
2x1,5
No.
No.No.
1
212 21
:1
+24V
-X1
:6:5:4:3:2
0V
:30:29
WAR 220.2.1.0
WAP 220.4.0.0
WAP 220.2.0.0
(WAP 220.5.0.0)
2
4
AL ST. #1
AL ST. #2
AL ST. #3
common
2
6
WAP 220.4.0.0
(WAP 220.5.0.0)
WAP 220.2.0.0
1 1
22
5
2 2
6
VDR
3
2 2
4
No.
1
1
No.
1
1
BRIDGE AREA
ALARM & RESET UNITS
WAR 220.1.0.0
1
2
5
2
1
1
type A
1
type B
2
3
WAR 220.1.0.0
1 2
1
21 3 4
WAR 220.2.0.0WAR 220.1.0.1 WAR 220.3.0.0
WAR 220.2.1.0
MOTION SENSOR
MODULE
see drawing no.:
WMS 220.2.0.0AS ME
:49
max. 160mA
max. 160mA
max. load: 160mA
2x0,75
4x0,75
2x0,75
No. No. No.
b3 b1
+
a4 2 a
13 X2
14 X1
:1
:2,4
:3
:3
:1 :2
:1:2 :5 :3 :1:5:2
:18
21
1 2
1 2
43
:32:31:7 :8 :34:10:9 :33 :13:36:35:12:11 :15 :17:14 :16 :43:38:37:20 :21:19 :41 :42:40:39 :24:23:22:44 :45 :48:47:25 :46
:3
:48
:52
:50
:26 :27 :28 :50 :52
le guardian 2025 CONNECTING MODULE
STEADY CONTACT
EXTERNAL SYSTEM ON
POWER SUPPLY
24VDC
2x m1,25A
FAILURE
SYSTEM
D1
k1
F2
F1
LCM 210.24.0.0
15 pole plug
total 400mA
MAX. LOAD:
STAGE 3
OFFICER'S AREABRIDGE AREA
0V
+24V
0V+24V0V+24V
k2 k3 k3
ALARM
VISUAL
k4
k4
CABINS or STAIRCASE(ACOUSTICS)
TRIGGER
ALARM
ALARM
ALARM
PRE-WARNING WARNING
STAGE 1 STAGE 2
STAGE 3
LOAD OF OUTPUT CONTACTS:
30VDC, 2A
l= 3m
DEVICE
LOD 210.24.0.0
OPERATING
PCB08002.x
1 3
2 4
5
6
7
8
sample connecting drawing without NMEA expansion module
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
25 user manual le guardian vers 2.05 - 201703109
Page 26
A
-
-
modification
B
C
-
-
-
le guardian 2025
Drawing No.
LCM NMEA 210.24.0.0 AS01
sme
T. Streit name spare of:
department:
VESSEL
T. StreitT. Streit
T. Streit
customer
class
WATCH ALARM SYSTEM
GL
BRIDGE NAVIGATIONAL
A4
Title:Scale
OFFICER'S AREA
85 - 112dB(A), 1m
STAGE 3 ALARM
ALARM DEVICES
1
2
-
+
-=
see page 2
or Failure Alarm P.
Naut. Al. System
FAP 220.1.0.0
AUTO PILOT
(optional)
location
FOR NAV. EQUIPM.
POWER SUPPLY
24VDC
+
-
1 1 22
21
2x0,75
2x0,75
2x1,5
No.
No.No.
B
1
212 21
A
:1
+24V
-X1
:6:5:4:3:2
0V
:30:29
WAR 220.2.1.0
WAP 220.4.0.0
2
4
WAP 220.4.0.0
1
2
3
2 2
4
No.
1
1
BRIDGE AREA
ALARM & RESET UNITS
WAR 220.1.0.0
type A type B
1
2
3
WAR 220.1.0.0
2
1
1 WAR 220.2.0.0WAR 220.1.0.1 WAR 220.3.0.0
WAR 220.2.1.0
MOTION SENSOR
MODULE
see drawing no.:
WMS 220.2.0.0AS ME
for details
:49
max. 160mA
max. 160mA
2x0,75
No.
b3 b1
a4 2 a
13 X2
14 X1
:1
:2,4
:3
:3
:1 :2
:1:2 :5 :3 :1:5:2
:18
1 2
:32:31:7 :8 :34:10:9 :33 :13:36:35:12:11 :15 :17:14 :16 :43:38:37:20 :21:19 :41 :42:40:39 :24:23:22:44 :45 :48:47:25 :46
:3
:48
:52:50
:26 :27 :50 :52
le guardian 2025 CONNECTING MODULE
STEADY CONTACT
EXTERNAL SYSTEM ON
POWER SUPPLY
24VDC
2x m2,0A
FAILURE
SYSTEM
D1
k1
F2
F1
LCM 210.24.0.0
15 pole plug
STAGE 3
total 400mA
MAX. LOAD:
OFFICER'S AREABRIDGE AREA
0V
+24V
0V+24V0V+24V
k2 k3 k3
ALARM
VISUAL
k4
k4
CABINS or STAIRCASE(ACOUSTICS)
TRIGGER
ALARM
ALARMALARM
PRE-WARNING WARNING
STAGE 1 STAGE 2
STAGE 3
LOAD OF OUTPUT CONTACTS:
30VDC, 2A
l= 3m
DEVICE
LOD 210.24.0.1
OPERATING
PCB08002.x
1 3
2 4
5
6
7 8
sample connecting drawing incl. NMEA expansion module
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
26 user manual le guardian vers 2.05 - 201703109
Page 27
receivetransmit
VESSEL
NAUTIC SYSTEM #4
(FAIL STATE LOOP)
location:
location:
(FAIL STATE LOOP)
NAUTIC SYSTEM #3
(FAIL STATE LOOP)
NAUTIC SYSTEM #2
location:
location:
NAUTIC SYSTEM #1
(FAIL STATE LOOP)
EMERGENCY CALL
RELEASE P/B
location:
modification
A
-
B
C
-
T. Streit-
name spare of:
T. Streit T. Streit-
­T. Streit
e.g. RADAR
(NMEA link)
location:
location:
(NMEA link)
VDR
BA A B
21 2121 211 2 211 2
2x0,75
2x0,75
2x0,75
2x0,75
2x0,75
2x0,75
2x0,75
No.No.
No.
No.No.No.No.
-X1
B
see page 1
A
1 2 2121 1 21 2 1 221
BA A B
:17:16
0V
:2 :3 :4
+24V
:1 :6:5:19:18 :10:9:7 :8 :14:13:11 :12
2
BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM
department: sme
Scale
customer
A4
Title:
class
Drawing No.
LCM NMEA 210.24.0.0 AS01
GL
2
le guardian 2025
+
-
= -
WAP 220.2.0.0 (WAP 220.5.0.0)
STAGE 2 ALARM
BACK-UP OOW #3
OFFICER'S CABINOFFICER'S CABINOFFICER'S CABIN
STAGE 2 ALARM
BACK-UP OOW #2BACK-UP OOW #1
STAGE 2 ALARM
WAP 220.2.0.0 (WAP 220.5.0.0)WAP 220.2.0.0 (WAP 220.5.0.0)
OFFICER'S CABINOFFICER'S CABIN
BACK-UP OOW #4
STAGE 2 ALARM
BACK-UP OOW #5
STAGE 2 ALARM
WAP 220.2.0.0 (WAP 220.5.0.0) WAP 220.2.0.0 (WAP 220.5.0.0)
2121 5 6 1 2 5 665
3x2x0,75
311 6 5 2 45 12 34
No.
342245 13 4 31
2x2x0,75
1 2 5 6 1 2 5 6
2x2x0,75
2312 2 2 11 3
No.
21
1x2x0,75
3x2x0,75
No.
No. No.
31 2 64 5
:30
+ - + - -+-+ -+
:25:23 :24:22:21 :29:26 :28:27
UNACKNOWLEDGED NAUTICAL ALARMS
RJ45
ALARM TRANSFER STAGE #2
0...30sec DELAY ADJUSTABLE
0...30sec DELAY ADJUSTABLE
ALARM TRANSFER STAGE #2
ALARM TRANSFER STAGE #2
0...30sec DELAY ADJUSTABLE
ALARM TRANSFER STAGE #2
0...30sec DELAY ADJUSTABLE
UNDELAYED, PULSE EXPECTED
MANUAL EMERGENCY CALL
24VDC
POWER SUPPLY
NMEA SERIAL INTERFACE
ACC. IEC61162-1 PROTOCOL
1x m2,0A
D1
F1
ALARM TRANSFER OF
l= 3m
DEVICE
LOD 210.24.0.1
OPERATING
2
1 3
STAGE#2 ALARM
BACK-UP OOW #1
BACK-UP OOW #2
STAGE#2 ALARM
STAGE#2 ALARM
BACK-UP OOW #3
BACK-UP OOW #5
STAGE#2 ALARM
STAGE#2 ALARM
BACK-UP OOW #4
SELECTOR SWITCH STAGE #2 ALARM
MULTIPLE SELECTION POSSIBLE
NMEA 210.24.0.0, PCB10002.x
NMEA EXPANSION MODULE
4
5
6
7
8
sample connecting drawing incl. NMEA expansion module
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
27 user manual le guardian vers 2.05 - 201703109
Page 28
ewfdewfe
-k3-k3-k1 -k1
MAIN SUPPLYBACK-UP SUPPLYFAILUREBACK-UP SUPPLY FAILUREMAIN SUPPLY
-
-
D
modification
F
-
G
-
-
K2: coil voltage 115 or 230VAC, contact: 24V/2A
K1: coil voltage 24VDC nominal, contacts: 24V/5A
24VDC nominal LOOP
WPS 220.24.0.0 A AS RevA
HULL
Drawing No.
sme
­name spare of:
department:
Shipyard
T. Streit-
-
BNWAS
class
GL
le guardian 2025
A4
100...240VAC LOOP
K4: coil voltage 24VDC nominal, contact: 24V/2A
K3: coil voltage 115 or 230VAC, contacts: 24V/5A
24VDC nominal 100...240VAC
1
1
-
+
-=
(0V)(+)
K1
A2
A1
1214 24
(+) (0V)
K2
A2
A1
K3
A2
A1
-k3
-k4
K4
L1 N
100...240VAC (IN)
WPS 220.24.0.0
POWER SUPPLY UNIT
14
L1 N
A2
100...240VAC (IN)
WPS 220.24.0.0
POWER SUPPLY UNIT
11
+ -
24VDC (OUT)
-k2
34
22
-k1
A1
-+
24VDC (OUT)
1412 22 24
14
11
34
0V
LCM 210.24.0.0
le guardian 2025 CONNECTING MODULE
POWER SUPPLY
21
in case no 24VDC distribution board for nautic equipment fed from ESB is available!
Dual Power Supply generated with power supply unit and relays is necessary only
24VDC Main Supply / 100...240VAC Back-Up Supply
11
:1 :2 :3
-X1
+24V
2x 2,0A
D1
F1
F2
24VDC
SYSTEM FAILURE
31
:4
:5 :6
11 21
:1 :2
-X1
+24V
:3:5:4
0V
SYSTEM
FAILURE
2x 2,0A
D1
F1
F2
POWER SUPPLY
24VDC
31
:6
100...240VAC Main Supply / 24VDC Back-Up Supply
le guardian 2025 CONNECTING MODULE LCM 210.24.0.0
le guardian 2025 Power Supply Philosophy, version A
1
le guardian 2025 Power Supply Philosophy, version B
3
2 4
5
6
7 8
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
28 user manual le guardian vers 2.05 - 201703109
Page 29
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
29 user manual le guardian vers 2.05 - 201703109
Page 30
edd
BLATT: VON:
2008
28.9. Streit
le guardian 2025 connecting module
-
2
2
to be mounted on terminal rail TS35 system voltage: 18,0...31,2VDC, power consumption: 20W
core size: max 0,2.... 1,5mm, power supply: 0,2.....2,5mm
degree of enclosure: IP 20 max. depth: 70mm weight: 0,35kg safety distance to magnetic compass: 0.5m
INDEXARTTYP-A/STAND-EAUFTRAG-NR
BNWAS LCM 210.24.0.0 ME A
sampl
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
30 user manual le guardian vers 2.05 - 201703109
Page 31
BLATT: VON:
2010
2.8. Streit
le guardian 2025 connecting module
-
1
1
to be mounted on terminal rail TS35
system voltage: 18,0...31,2VDC, power consumption: 1,5W nominal
core size: max 0,2.... 1,5mm
degree of enclosure: IP 20 max. depth: 70mm weight: 0,35kg safety distance to magnetic compass: 0.5m
INDEXARTTYP-A/STAND-EAUFTRAG-NR
NMEA 210.24.0.0 ME A
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
31 user manual le guardian vers 2.05 - 201703109
Page 32
emarks:
SIGNAL DEVICE WITH SOUNDER &
GEZ.
BEARB.
2005
DATUM
31.1. Streit
NAME
FIXING HOLES
4X 6,3
BLATT: VON:
PART No.: 770106
M25x1,5
TRIANGLE LIGHT FOR WATCH ALARM
background: white symbol: black
M25x1,5
sound code: 11100
sound pressure level: 64 - 111 db(A) (adjustable)
cable diameter: 8,0 -16,0mm core size: max 2,5mm degree of enclosure: IP 65
wallbox surface: RAL 7035
nominal values: 24VDC, 275mA
sound characteristic: 2850 Hz continuous
depth without lower wall box part: 30mm bulbs: max. 5W weight: 0,870kg
wall cut-out: d=68mm
for flush mounting only!
upper wallbox part
for flush mounting use only upper part!
1 3
5 6
2 4
-H1
-H2
+24V
+24V
0V
type A
1 2
-H1
-H2
+24V
+24V
0V
type B
3 4
ÄNDARTTYP-A/STAND-EAUFTRAG-NR
BNWAS WAP 220.4.0.0 ME A
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
32 user manual le guardian vers 2.05 - 201703109
Page 33
WATCH ALARM PANEL for OFFICER'S CABIN
GEZ.
GEPRÜFT
/ /
BEARB.
2004
DATUM
10.12
/ /
Streit
NAME
BLATT: VON:
PART No.: 770107
WAP 220.2.0.0
print: white RAL 9010
surface: black anodized nominal values: 24VDC, 50mA
degree of enclosure: IP 23 sounder: 80 dB(A)
core size: max. 2,5mm depth: 45mm
weight: 0,150kg
2
CUT OUT
(for stage #2 alarm)
panel's outline dimensions: 144x72mm
BNWAS WAP 220.2.0.0 ME B
WATCH ALARM
sm electrics
remarks
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
33 user manual le guardian vers 2.05 - 201703109
Page 34
efewfe
WATCH ALARM PANEL BULKHEAD
GEZ.
GEPR.
BEARB.
2010
DATUM
7.5. Streit
NAME
BLATT: VON:
FOR OFFICER'S CABIN, WAP 220.5.0.0
WATCH ALARM
sm electrics
1 2 5 6
PCB03009.3
1 1
INDEXARTTYP-A/STAND-EAUFTRAG-NR
BNWAS WAP 220.5.0.0 A
sm electrics
34 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 35
FAILURE ALARM PANEL BULKHEAD
GEZ.
BEARB.
2010
DATUM
10.8. Streit
NAME
BLATT: VON:
M20x1,5
FOR WATCH ALARM SYSTEM FAIL INDICATION
M20x1,5
M20x1,5
WATCH ALARM
sm electrics
1 2 3 4
PCB10003.1
1 2
FAILURE
RESET
+24V 0V
FAILURE CONTACT
(OPENED IN FAIL STATE)
wh
S1
H1
gy
K2
gn rd
DO NOT USE SAME 24V POWER SOURCE FOR MONITORED SYSTEM AND FAILURE ALARM PANEL
bn
H2
buye
K1
pk
TEST
SUPPLY VOLTAGE
24VDC NOMINAL
(MONITORING LOOP)
INDEXARTTYP-A/STAND-EAUFTRAG-NR
BNWAS FAP 220.1.0.0 A
remarks
sm electrics
35 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 36
sm electrics
Technical data:
- Input / output terminals: 0,2…2,5mm², 0,6 – 0,6 Nm
- Input voltage range: 19,2…31,2VDC
- Monitoring loop: normally closed
- Lamp & buzzer test included
Operational description:
- After Failure Alarm Panel is connected to its power supply (terminals 1&2) and monitoring loop is closed (terminal 3&4) panel is activated for monitoring.
- In case monitoring loop is opened for longer than 250ms visual & audible indication (H1 & H2) has been activated.
- Audible indication (buzzer H2) can be stopped by pushing reset push button S1.
- Visual indication (indication lamp H1) is activated as long as monitoring loop is opened (monitored system is in fail state)
- When loop is opened for a short period only, due to a short fail state of monitored system, buzzer (H2) is activated as long as reset push button has been pushed.
- Push button S1 can be used as lamp & buzzer test.
WATCH ALARM
sm electrics
FAILURE
RESET
TEST
1 2 3 4
PCB10003.1
+24V 0V
FAILURE CONTACT
(OPENED IN FAIL STATE)
wh
S1
H1
gy
K2
gn rdbn
H2
buye
K1
pk
SUPPLY VOLTAGE
24VDC NOMINAL
(MONITORING LOOP)
FAILURE ALARM PANEL
FAP 220.1.0.0
Supply voltage: 24VDC nominal, n/c monitoring loop
part no.: 770423
36 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 37
WATCH ALARM PIR MOTION SENSOR
GEZ.
GEPR.
BEARB.
2010
DATUM
4.1. Streit
NAME
FIXING HOLES
2x d=3,9mm
sheet: 1 of: 2
PART No.: 770307
ALARM
-
WMS 220.2.0.0
+
-X1
optimize mounting height: 2,5m disconnect LED after commissioning!
wallbox surface: RAL 9003 material: ABS
degree of enclosure: IP23
finally connected to distribution box (cable lenght: 1,0m)
current consumption: 12mA
27.0
58.0
27.0
114.9
107.5
126.6
63.7
52.0
12V
LED
1.) motion sensor is in operation only 2 min. after first count-down procedure has been started!
INDEXARTTYP-A/STAND-EAUFTRAG-NR
BNWAS WMS 220.2.0.0 ME A
remarks
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
37 user manual le guardian vers 2.05 - 201703109
Page 38
remarks
WATCH ALARM PIR MOTION SENSOR
GEZ.
GEPR.
BEARB.
2010
DATUM
6.6. Streit
NAME
sheet: 2 of: 2
PART No.: 770307
WMS 220.2.0.0
1.) Do not mount unit in direct sunlight or near heat sources!
8.5m
12.0m
12.0m
INSTALLATION INSTRUCTIONS
DETECTING AREA
12.0m
2.5m
2.) Make sure OOW has a proper look-out inside complete detecting area!
3.) Motion sensor is in operation only 2 min. after first count-down procedure has been started!
4.) Motion sensor's preferred person's moving direction: crosswise to sensor
Rev. A, Sept. 01.2010, intruction items 5 & 6 added
5.) Avoid an installation location with fast temperature fluctuations!
6.) Consider, sensor is designed to detect person in motion, avoiding accidental detections
Rev. B, 26. Dec. 2010, sector view & sector explanation added
detecting method: A heating source (human being) has been detected only, when it is passing a defined quantity of sectors whithin a defined period. That is to avoid unintentional detection of a fixed heating source (heater, coffee machine, hot power supply) That means consequently, OOW has to pass sectors for detecting. Sensor's sensitivity is depending on distance due to sector geometry
INDEXARTTYP-A/STAND-EAUFTRAG-NR
BNWAS WMS 220.2.0.0 ME A
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
38 user manual le guardian vers 2.05 - 201703109
Page 39
remarks
DISTRIBUTION BOX FOR
GEZ.
GEPR.
BEARB.
2010
DATUM
4.1. Streit
NAME
FIXING HOLES
4x 4,2
BLATT: VON:
PART No.: 770444
M20x1,5
1 3
WATCH ALARM PIR MOTION SENSOR KIT
2 4
-X1
core size: 0,5... 1,5mm quick lock: stainless steel
wallbox surface: RAL 7035 material: ABS
2
degree of enclosure: IP65
cable diameter: M20x1,5, 7,0.... 12,3mm
M16x1,5
M16x1,5
cable lenght distribution box / PCB module: max. 15m
M20x1,5
INDEXARTTYP-A/STAND-EAUFTRAG-NR
BNWAS WMS DISTR. BOX ME A
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
39 user manual le guardian vers 2.05 - 201703109
Page 40
remarks
ÄNDERUNGINDEX FELD ÄND.-MITT.DATUMNAME
NAMETAG
GEPR. NORM
BLATT: VON:
BEARB
2010
4.1. Streit
le guardian 2025
-
1
1
part no.: PCB09005.1
to be mounted on terminal rail TS35 system voltage: from connecting module LCM 210.24.0.0 only!
core size: max 0,2.... 2,5mm
degree of enclosure: IP 20 depth: 55mm weight: 0,070kg safety distance to magnetic compass: 0,4 / 0,35m
BNWAS PIR MOTION SENSOR MODULE
LCM 210.24.0.0
PIR MOTION SENSOR MODULE
GN
WH
4x0,5
-X1
PIR MOTION SENSOR
BN
YE
-X1
PIR MOTION SENSOR
GN
WH BN
YE
1 2 3 4
DISTRIBUTION BOX
-X1
31
2x2x0,5
2 4
-X2
3
1 2
4
+
-
AL AL
PIR MOTION SENSOR MODULE
48 50 52
-X1
48 50 52
CONNECTING MODULE LCM 210.24.0.0
LENGHT: MAX 30m
LENGHT: 1,0m fixed
motion sensor is in operation only 2 min.
A additional motion sensor(s) added 3.3.10 Streit
after first count-down procedure has been started!
GN
WH
4x0,5
-X1
BN
YE
-X1
GN
WH BN
YE
1 2 3 4
-X1
31
2x2x0,5
2 4
-X2
3
1 2
4
+
-
AL AL
48 50 52
SENSOR #1 SENSOR #2
to next sensor module (total: up to 4 modules)
(44)
(0V) (+24V)
0,75mm², max. lenght: 1m
power consumption: 1,8W nominal
INDEXARTTYP-A/STAND-EAUFTRAG-NR
BNWAS WMS 220.2.0.0 AS/ME A
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
40 user manual le guardian vers 2.05 - 201703109
Page 41
ewfw
ME/AS
19.0
max.5.0
40.0
37,5
WATCH ALARM RESET, PRE-ALARM & VISUAL STAGE #1
WAR 220.1.0.0 A
sm electrics
41 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 42
max.8.0mm
66.5
WATCH ALARM RESET, PRE-ALARM & VISUAL STAGE #1
40.0
19.0
WAR 220.1.0.1 ME/AS A
sm electrics
ed
42 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 43
qw
WATCH ALARM RESET BOX
GEZ.
BEARB.
2010
DATUM
20.9. Streit
NAME
SHEET: OF:
M20x1,5
FOR INDOOR APPLICATION ONLY
M20x1,5
14 15
1 1
(LCM 210.24.0.0)
wh
S1
H1
gnbn
1 2 3
13
CONNECTING MODULE
PRE-ALARM & VISUAL STAGE #1 ALARM
WAR 220.3.0.0 ME/AS A
sm electrics
43 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 44
rema
BNWAS WAR 220.2.0.0 ME A
TYP-A/STAND-E
for open bridge wing
wall box for reset (pre-alarm & visual stage #1 alarm)
le guardian 2025
151.4
82.0
120.0
nominal values: 24VDC, 50mA
cable diameter: 7,5 -17,0mm
degree of enclosure: IP 65 weight: 0.800kg
core size: max 2,5mm
wallbox surface: RAL 7001
CONNECTING MODULE
LCM 210.24.0.0
14 1315
Rev. A: triple link added, 31.7.2009
Streit
2003
7.12.
AUFTRAG-NR
-
1 2 3 4
122.0
106.0
WATCH ALARM
115.2
90.0
ÄND
OF:
1
SHEET:
ART
part no.: 770041
1
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
44 user manual le guardian vers 2.05 - 201703109
Page 45
sm electrics
BNWAS WAR 220.2.1.0 ME B
TYP-A/STAND-E
for open bridge wing
wall box for reset & buzzer (stage #1 alarm)
le guardian 2025
151.4
82.0
120.0
nominal values: 24VDC, 50mA cable diameter: 7,5 -17,0mm
degree of enclosure: IP 65 weight: 0.850kg
core size: max 2,5mm
wallbox surface: RAL 7001
LCM 210.24.0.0
CONNECTING MODULE
(47)
(48)24(49)
25
23
Rev. A: triple link added, 31.7.2009
Streit
(46)
22
2003
7.12.
AUFTRAG-NR
-
5
1 2 3 4
6
122.0
106.0
WATCH ALARM
115.2
90.0
ÄND
VON:
1
BLATT:
ART
part no.: 770045
1
rkremarks:
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
45 user manual le guardian vers 2.05 - 201703109
Page 46
EXTERNAL WATCH ALARM BUZZER FOR STAGE #1 ALARM
max.12.0mm
60.0
30.0
11.0
WAB 220.2.0.0 ME/AS A
remarks:
sm electrics
46 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 47
sm electrics
BNWAS WAB 220.1.0.0
wall box with buzzer (audible stage #1 alarm)
le guardian 2025
TYP-A/STAND-E
151.4
82.0
120.0
wallbox surface: RAL 7001
degree of enclosure: IP 65
cable diameter: 7,5 -17,0mm
nominal values: 24VDC, 50mA
core size: max 2,5mm
weight: 0.750kg
LCM 210.24.0.0
CONNECTING MODULE
7 8
+ -
sw bl
AUFTRAG-NR
-
Streit
2004
1.3.
X2
NLa Lb
X1
122.0
106.0
WATCH ALARM
115.2
90.0
INDEX
OF:SHEET:
1
ART
1
ME/AS
part no.: 770051
A
f
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
47 user manual le guardian vers 2.05 - 201703109
Page 48
dd
ACCESS FOR LINK CABLE
362.0
346.0
254.0
239.0
wallbox surface: RAL 7035, ABS cable glands: 16 pcs. M20x1,5 cable diameter: 6,0 -13,2mm degree of enclosure: IP23 weight: 3,3kg
6x 4,8
FIXING HOLES
162.0
wall box for connecting module (LCM),
NMEA module, motion sensor module
BNWAS WBC 210.1.0.0
2010
5.3. Streit
part no.: 770317
ART
1
-
SHEET:
le guardian 2025
ME
INDEX
OF:
1
0
sm electrics
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
48 user manual le guardian vers 2.05 - 201703109
Page 49
sm electrics
WPS220.24.0.0, 100…240VAC / 24VDC, 2.5A Power Supply Unit
sme part no.: 770466
dfwg
49 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 50
sm electrics
NMEA expansion module
NMEA 210.24.0.0
11 NMEA expansion module
NMEA expansion module (NMEA 210.24.0.0) is designed for the following operations:
transmit permanently system’s mode by sending NMEA sentences acc. IEC 61162-1 to external
systems especially VDR for data logging
receive NMEA sentences acc. IEC 61162-1 from external systems (e.g. radar) to give
commands to BNWAS (e.g. reset command of dormant period)
Master can decide which back-up OOW’s cabin shall receive stage #2 alarm (multiple selection
is possible, minimum selection: 1 cabin!)
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
50 user manual le guardian vers 2.05 - 201703109
Page 51
sm electrics
NMEA Expansion Module
NMEA 210.24.0.0
-Z1, RJ45 connector to operating device
fuse holder
-F1, (m2A)
terminals for
24VDC power supply
terminals for
periphery equipment
control LEDs
LED1...LED12
11.1 NMEA expansion module installation
NMEA expansion module (NMEA 210.24.0.0) has to be connected according to corresponding wiring diagrams.
description
Module has been designed to click on terminal rail TS 35 inside electric cabinet or control console. All periphery equipment (alarm panels, input contacts, power supply) is to be connected directly on NMEA module without any additional terminal board or distribution boxes according to wiring diagram which is part of
working drawings. Sample system wiring diagram is shown in chapter “technical
data & schematics”.
Outputs for stage #2 alarm panels (WAP 220.2.0.0 or WAP 220.5.0.0) are short­cut protected. Maximum output current is 500mA (each output).
Power Supply It is preferred to feed NMEA expansion module with same 24VDC power supply as connecting module (LCM 210.24.0.0).
Link to operating device (LOD 210.24.0.0) Use 3m patch link cable which is part of NMEA expansion module to do serial link between operating device & NMEA expansion module
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
51 user manual le guardian vers 2.05 - 201703109
Page 52
sm electrics
control LEDs
LED6...LED10
show state of binary inputs
control LEDs
LED1...LED5
show state of binary outputs
display „text 1“
READY FOR
POWER ON / AUTO
11.2 NMEA expansion module commissioning
Before switching on 24VDC (nominal) power supply to NMEA expansion module (NMEA
210.24.0.0) on terminal board –X1: 1, 2 (+) & 3, 4 (-) make sure basic system (operating device LOD 210.24.0.0 & connecting module LCM 210.24.0.0) is operating in normal condition.
Diode on NMEA expansion module secures system against wrong power supply polarity.
After connecting 24VDC power supply and link cable to operating device has been connected, system must be switched on for enabling NMEA expansion module.
11.2.1 Enabling NMEA expansion module (service menu #5)
NMEA expansion module (NMEA 210.24.0.0) must be enabled on operating device (LOD 210.24.0.0) for un-locking several NMEA expansion module’s operating functions.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
52 user manual le guardian vers 2.05 - 201703109
Page 53
sm electrics
operating device LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
display „text 62
ENTER CODE XXXXX TO ENABLE NMEAXM
key switch
S1
display „text 63
NMEA EXP. MODULE IS ENABLED
system is
shut down
Do a system shut-down when display is showing “display text 1” by turning key switch S1 on operating device LOD 210.24.0.0 to position “ON/OFF” for longer than 2 sec. System shuts down and operating device’s display is blank.
Then push and keep pushing rotary encoder’s push button S2 and after a period between 13 and 15 sec “switch on” system by turning key switch S1 on operating device LOD 210.24.0.0 one time to position “ON/OFF”. A timer shown on display is supporting this time depending operation.
So system starts in “service menu 5” and display is showing “text 62
Move key switch S1 into position “SELECT” and push rotary encoder’s push button one time. Display shows “text 63”.
Move key switch S1 into position “ON/OFF” – system start-up is running an NMEA expansion module has been enabled.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
53 user manual le guardian vers 2.05 - 201703109
Page 54
sm electrics
display „text 1“
READY FOR
POWER ON / AUTO
system is
shut down
To check whether NMEA expansion module has been enabled, move key switch S1
into position “SELECT” and push rotary encoder’s push button S2 two times to
reach an additional menu to select back-up officer’s cabin for receiving stage #2 alarm. This menu is available only, when NMEA expansion module has been enabled!
NMEA expansion module is running now and is waiting for user’s operation on operating device LOD 210.24.0.0 or for an external “power on” command. When display shows “text1” NMEA interface starts sending NMEA telegrams. A control LED (LED11) on NMEA expansion module is indicating sending process.
11.2.2 Define quantity of involved back-up OOW cabins (service menu #2)
Person in charge for commissioning has to set right parameter for involved back-up OOW cabins. Allowed number of involved cabins is between 2 and 5 depending on ship’s safety philosophy. This number must be set into parameter settings to avoid unintentional selection of
“not existing” back-up OOW cabins. To set right parameter do a system shut-down for reaching “service menu 2” (number of back-up OOW cabins).
Do a system shut-down when display is showing “display text 1” by turning key switch S1 on operating device LOD 210.24.0.0 to position “ON/OFF” for longer than 2 sec. System shuts down and operating device’s display is blank.
Then push and keep pushing rotary encoder’s push button S2 and after a period between 4 and 6 sec “switch on” system by turning key switch S1 on operating device LOD 210.24.0.0 one time to position “ON/OFF”. A timer shown on display is supporting this time depending operation.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
54 user manual le guardian vers 2.05 - 201703109
Page 55
sm electrics
operating device LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
display „text 40
NUMBER_OF_OOW’s CABINS: * * * * 5 * * * *
So system starts in “service menu #2 and display is showing “text 40”
Use rotary encoder to adjust right number of involved cabins. Selection between 2 and 5 is allowed and available only.
After right selection has been done, start-up system by moving key switch S1 into position “ON/OFF”.
Definition of involved back-up OOW’s cabin quantity is strongly necessary to avoid unintentional selection of non existing cabins!
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
55 user manual le guardian vers 2.05 - 201703109
Page 56
sm electrics
location:
description:
NMEA expansion
module terminal no.:
cabin no #1
Deck 5, R. 515
Captain
21 (+), 22 (-)
cabin no #2
Deck 5, R. 524
1st Officer
23 (+), 24 (-)
cabin no #3
Deck 5, R. 525
2nd Officer
25 (+), 26 (-)
cabin no #4
Deck 5, R. 526
3rd Officer
27 (+), 28 (-)
cabin no #5
-
not used
29 (+), 30 (-)
location:
description:
NMEA expansion
module terminal no.:
cabin no #1
21 (+), 22 (-)
cabin no #2
23 (+), 24 (-)
cabin no #3
25 (+), 26 (-)
cabin no #4
27 (+), 28 (-)
cabin no #5
29 (+), 30 (-)
11.2.3 Define relation between cabin number and real cabin location Use the following table to define real cabin location and system’s cabin numbers: sample table
vessel’s table
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
56 user manual le guardian vers 2.05 - 201703109
Page 57
sm electrics
transmitting LED11
NMEA 210.24.0.0
display „text 1“
READY FOR
POWER ON / AUTO
11.2. Transmit NMEA sentences to external systems (especially VDR)
NMEA expansion module (NMEA 210.24.0.0) is transmitting permanently serial data according standard IEC 61162-1.
After start-up system display “text 1is showing and transmitting LED11 is flashing (about 3Hz). Flashing frequency is depending on system’s state!
When count-down is running transmitting LED11 is flashing only (1 time) when system’s state has been changed (e.g. when pre-alarm occurs).
An external system, especially VDR system, can be connected to terminals 16(A) & 17(B) for data logging.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
57 user manual le guardian vers 2.05 - 201703109
Page 58
sm electrics
NMEA sentences from BNWAS to external systems (especially VDR)
ALR: operating state after 1st power-on / after system start-up
$ B N A L R , , 0 0 0 , V , A , C 1 = A U T ; C 2 = 0 3 ; C 3 = 0 * h h CR
LF
1
2 3 4
5 6
fields:
1: Message type: alarm message
2: Reset / start source:
- 000: start up is reset command
- LOD: integrated reset button or hardware reset inputs
- NME: via NMEA interface from external system
- EXT: via external system (dry contacts, start/stop)
3: Dormant period:
A= Dormant period exceeded
V= Dormant period not exceeded
4: Alarm situation:
A= Alarm situation acknowledged
V= Alarm situation not acknowledged
5: BNWAS mode:
C1 = AUT, MAN or OFF (bei uns ist MAN wenn Schlüssel auf "SELECT"
C2 = Dormant period in minutes (03…12)
C3 = Stage alarm; 0, 1, 2, 3
6: CRC
example (after start-up):
$BNALR,,000,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
Serial NMEA data have been designed according to the following structure:
Transmitting of NMEA sentences cannot be stopped or delayed under any circumstances!
58 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 59
sm electrics
EVE (short):
count-down reset of main period
field length is depending on source's system ID
$ - - E V E , , B N W A S , O p e r a t o r a c t i v i t y * h
h
CR L F
1
2
3 4
fields:
1: Message type: Event
2: Event source tag code: BNWAS (sender's view)
3: Event description:
Operator activity
4: CRC
receiving LED12
NMEA 210.24.0.0
11.3. Receive NMEA sentences from external systems
NMEA expansion module (NMEA 210.24.0.0) can receive serial data according standard IEC 61162-1 for remote control of BNWAS le guardian
Receiving LED is active in steady light after a transmitter has been connected correctly. In case NMEA expansion module is receiving a NMEA sentence (telegram) steady light of receiving LED12 has been interrupted for some milliseconds.
The following control NMEA sentences can be accepted:
2025
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
59 user manual le guardian vers 2.05 - 201703109
Page 60
sm electrics
EVE (long):
count-down reset of main period
field length is depending on source's system ID
$ - - E V E , , h h m m s s . s s , B N W A S , O p e r a t o r a c t i v i t y * h
h
CR L
F
1
2
3
4
5
fields:
1: Message type: Event
2: UTC time
3: Event source tag code: BNWAS (sender's view)
4: Event description:
Operator activity
5: CRC
ALR (short):
release of Em'cy Call without any further delay (stage #2 alarm)
field length depending on source system ID
$ - - A L R , , x x x , A , V , E m e r g e n c y C a l l * h h
CR L
F
1
2 3 4
5 6
fields:
1: Message type: Alarm message
2: Unique alarm number (identifier) from alarm source, e.g. measuring point number
3:Alert condition:
A = threshold exceeded
V = threshold not exceeded
4: Alarm state:
A = acknowledged
V = unacknowledged
5: Alarm description:
Emergency Call (command)
6: CRC
ALR (long):
release of Em'cy Call without any further delay (stage #2 alarm)
field length depending on source system ID
$ - - A L R , h h m m s s . s s , x x x , A , V , E m e r g e n c
y C a l l * h h
CR L
F
1 2
3 4 5 6 7
fields:
1: Message type: Alarm message
2: UTC time
3: Unique alarm number (identifier) from alarm source, e.g. measuring point number
4:Alert condition:
A = threshold exceeded
V = threshold not exceeded
5: Alarm state:
A = acknowledged
V = unacknowledged
6: Alarm description:
Emergency Call (command)
7: CRC
60 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 61
sm electrics
ALR (short):
empty ALR alert list for transfer alarm reset
field length depending on source system ID
$ - - A L R , , , V , V , * h
h
CR L F
1
2 3 4
fields:
1: Message type: Alarm message
2: Alert condition:
V = threshold not exceeded
3: Alarm state:
V = unacknowledged
4: CRC
ALR (long):
empty ALR alert list for transfer alarm reset
field length depending on source system ID
$ - - A L R , h h m m s s . s s , , V , V , * h h
CR L
F
1
2
3 4 5
fields:
1: Message type: Alarm message
2: UTC time
3:Alert condition:
V = threshold not exceeded
4: Alarm state:
V = unacknowledged
5: CRC
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
61 user manual le guardian vers 2.05 - 201703109
Page 62
sm electrics
12 user manual short version (for users only)
le guardian
12.1.0 Generals .............................................................................. 62
12.1.1 Installation ........................................................................... 63
12.2.1 Manual switch on .................................................................. 63
12.2.2 Automatically switch on ......................................................... 64
12.3.0 Select dormant (main) period ................................................. 64
12.3.1 Reset of dormant (main) period .............................................. 64
2025
Watch Alarm System acc. MSC .128/75 & IEC 62616
(Bridge Navigational Watch Alarm System, BNWAS)
12.3.2 Alert sequences start automatically ......................................... 65
12.3.2.1 visual alarm indications (pre-alarm) ........................................ 65
12.3.2.2 Alarm stage 1 ....................................................................... 65
12.3.2.3 Alarm stage 2 ....................................................................... 66
12.3.2.4 Alarm stage 3 ....................................................................... 66
12.4.1 Back-up OOW’s selection & indication ...................................... 67
12.5.1 Emergency call ..................................................................... 67
12.6.1 System shut down ................................................................. 70
12.1.0 Generals
The purpose of a bridge navigational watch alarm system is to monitor bridge activity and detect operator disability which could lead to marine accidents. The system monitors awareness of the Officer of the Watch (OOW) and automatically alerts the Master or another
qualified person if for any reason OOW becomes incapable of performing OOW’s duties.
This purpose is achieved by series of indications and alarm to alert first the OOW and, if he is not responding, then to alert Master or another qualified person. Additionally, the BNWAS provide the OOW with means of calling for immediate assistance if required.
This user manual (short version) is made for persons who know basic standards of watch alarm system. All time period reset inputs are protected against permanent reset.
62 user manual le guardian vers 2.05 - 201703109
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 63
sm electrics
display „text 1“
READY FOR
POWER ON / AUTO
display „text 2
COUNT-DOWN
*** 2:59 ***
operating device LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
12.1.1 Installation After operating device LOD 210.24.0.0 and connecting module LCM 210.24.0.0 are installed according to technical documentation by authorized personnel, system has to be supplied by 24VDC battery power supply (terminal board -X1: 1, 3). Potential free n/o failure contact (connecting module –X1: 5, 6) closes and system is ready for switch on. After a short display intro display on operating device is showing “text 1”.
12.2.1 Manual switch on Authorized person (Master) switches on system by single turning key switch –S1 on operating device to position “ON/OFF”. System’s running is indicated by activating last selected dormant (main) period and count-down is active as shown on display “text 2”.
If dormant (main) period (3... 12 min) shall not be changed, authorized person (Master) pull off the key. Dormant period is counting down from the moment that system has been switched on.
Dormant period is period within OOW is monitored but no further alert is triggered.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
63 user manual le guardian vers 2.05 - 201703109
Page 64
sm electrics
display „text 3
SET MAIN PERIOD:
3… 12min ** 3 **
display „text 1“
READY FOR
POWER ON / AUTO
12.2.2 Automatically switch on
System can be switched on by external systems via potential free steady n/o contact which has to be connected on connecting module LCM 210.24.0.0 –X1: 29 & 30.
Automatic switch on is possible only in automatic mode - when display is showing
“text 1”.
In case automatic switch on shall not be possible, master has to shut-down system (see chapter 5.1 System shut-down)
12.3.0 Select dormant (main) period
In case that authorized person (Master) demands to select other dormant period, person has to turn key switch S1 on operating device to position “SELECT”. In this position only dormant period can be chosen by using rotary encoder S2 on operating device. Display is showing “text 3”.
By turning rotary encoder S2 in clock wise direction, value is increasing. By tuning rotary encoder S2 in counter clock wise direction, value is decreasing. Possible main period value is limited between 3 and 12 min. Step width is 1 min. By turning key switch S1 into centre position, system accepts new value and count-down starts from the moment the key has turned into centre position. Authorized person (Master) can pull off key only in centre position.
Dormant (main) period (3... 12 min) shows after which period automatically generated alert sequences will be triggered. (see time table, page 20)
12.3.1 Reset of dormant (main) period
As a rule monitored person (OOW) resets dormant period by pushing illuminating push buttons or rotary encoder’s integrated push button S2 on operating device
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
64 user manual le guardian vers 2.05 - 201703109
Page 65
sm electrics
display „text 12
RESET EXPECTED
0:14
display „text 13
*RESET EXPECTED*
********* 0:13 **********
display „text 14
RESET EXPECTED
0:14
display „text 15
ALARM STAGE 1
0:13
during his actual work on bridge area. Every reset is re-starting complete count­down independent of its moment. To serve rules of ergonomics several reset units should be placed on strategic locations on bridge and bridge wing area. These reset units are maximum sized illuminated push buttons as well as loud electronic sounder which have been connected on connecting module LCM 210.24.0.0
12.3.2 Alert sequences start automatically
12.3.2.1 visual alarm indications (pre-alarm) If dormant (main) period is over without OOW’s reset, system activates all illuminated reset units by 1Hz flash light. This sequence is calling “pre-alarm”. Display is showing in 1Hz toggle mode display “text 12” and “text 13”.
All illuminated push buttons and display on operating device are centralized dimmable via rotary encoder S2 on operating device. Minimum illumination is fixed.
12.3.2.2 Alarm stage 1 If dormant (main) period and pre-alarm period (15 sec) are over without OOW’s reset, system activates internal electronic buzzer as well as additional buzzers located on bridge or bridge wing area. This sequence is calling “alarm stage 1”. Display is showing in 1 Hz toggle mode display “text 14” and “text 15”.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
65 user manual le guardian vers 2.05 - 201703109
Page 66
sm electrics
display „text 16
RESET EXPECTED
1:29
display „text 17
ALARM STAGE 2
1:28
display „text 18
RESET EXPECTED
ALARM STAGE 3
Alarm stage 1 is triggered to pay attention to monitored OOW. Sound characteristics and sound volume are adjustable (see user manual chapter 8 Adjust buzzer characteristics & volume). One additional potential free (dry) n/o contact is closed now for further use as well as for VDR link. (Additional buzzers or alarm devices can be connected directly on connecting module.)
12.3.2.3 Alarm stage 2
If dormant (main) period, pre-alarm period (15 sec) and alarm stage 1 (15 sec) are
over without OOW’s reset, system activates alarm stage 2. Display on operating device is showing in toggle mode display “text 16” and “text 17”.
One additional potential free (dry) n/o contact is closed now for further use as well as for VDR link. Optic / acoustical alarm devices in officer’s area (cabins or staircase) are activated. In case software selector switch is involved (see 11.x.x.x) alarm devices in selected back-up OOW’s cabins only are activated!
12.3.2.4 Alarm stage 3
If dormant (main) period, pre-alarm period (15 sec), alarm stage 1 (15 sec) and alarm stage 2 (90... 180 sec) are over without OOW’s reset, system activates alarm
stage 3. Display on operating device is showing in toggle mode display “text 18” and
“text 19”.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
66 user manual le guardian vers 2.05 - 201703109
Page 67
sm electrics
display „text 19
ALARM STAGE 3
RELEASED
display „text 28
BACK-UP_OOW_No.1
ON_DUTY: ***ON***
operating device LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch S1
Stage 2 alarm is active in
Cabin No.1
Two potential free (dry) n/o contacts on connecting module are closed now for alarm stage 3 trigger (very loud alarm devices in officer’s area or public area) as well as for VDR link.
12.4.1 Back-up OOW’s selection & indication le guardian 2025 system can be updated with back-up OOW’s cabins software selector switch. For using this feature NMEA expansion module 210.24.0.0 has to be installed and enabled. During commissioning work firm technician / engineer has defined and reported (see chapter 11.2.2 Define quantity of involved back-up OOW cabins (service menu #2)) how many back-up OOW’s cabins are involved for alarm stage 2 activation. That means master can decide into which back-up OOW’s cabins alarm stage 2 has to be transferred or not.
For that authorized person (Master) moves key switch S1 on operating device to
position “SELECT”. After pushing rotary encoder’s push button S2 display is showing
display text 28”
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
67 user manual le guardian vers 2.05 - 201703109
Page 68
sm electrics
display „text 29
BACK-UP_OOW_No.1
ON_DUTY: ***OFF**
Stage 2 alarm is not active
in Cabin No.1
display „text 49
B.UP_OOW_ON_DUTY
_ _ _1_x_3_x_5_ _ _ _
By turning rotary encoder cabin of back-up OOW No.1 can be switched on “ON” or switched off “OFF”. This selection can be repeated as many as back-up OOW’s cabins are involved
(minimum 2 cabins, maximum 5 cabins).
Selection overview To check which cabins have been selected for alarm stage 2, start count-down and wait for 5 sec. Then display is showing e.g. the following selection:
Authorized person (Master) and later on OOW can check / recheck after each count-down reset, cabin selection. Display “text 49” shows cabin No.1, No.3 & No.5 have been selected to receive alarm stage 2. Cabin No.2 & No.4 are not selected!
Notice! Software makes sure minimum one cabin has been selected! When alarm stage 3 is activated, every back-up OOW’s cabins alarm device is active
regardless of its selection state!
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
68 user manual le guardian vers 2.05 - 201703109
Page 69
sm electrics
display „text 20
EMERGENCY CALL
1:29
display „text 21
OFFICERs ALARM
1:28
12.5.1 Emergency call Monitored OOW is able to generate an emergency call...
...by pushing rotary encoder on LOD longer than 5 sec.
That activates without delay alarm stage 2 and subsequently alarm stage 3 later on.
Display on operating device is showing in toggle mode display “text 20” and “text
21”.
Notice! Emergency Call feature is not activated when system is shut-down!
see chapter 11.5.1 System shut-down.
Emergency Call reset is possible by pushing any reset unit longer than 2 sec.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
69 user manual le guardian vers 2.05 - 201703109
Page 70
sm electrics
system is
shut down
operating device LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
connecting module
LCM 210.24.0.0
-Z1
15 pole connector
to operating device
fuse holders
-F1, -F2 (m2A)
terminals for
24VDC power supply
terminals for
periphery equipment
12.6.1 System shut down
If system is not in operation and external automatic “system on” should not be possible, Master is able to shut down system by turning key switch S2 on operating device for longer than 2 sec to position “ON/OFF”.
System and display shut down and system ignores all external inputs now.
Notice! When system is shut-down no emergency call is possible!
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
70 user manual le guardian vers 2.05 - 201703109