2 user manual le guardian vers 2.05 - 201703109
sm electricsGmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 3
sm electrics
In the course of the latest software release LOD_170223_D02, several changes in the
operating philosophy have been made.
Emergency call can only be triggered and reset by pushing the rotary
knob on operating device. In addition it is possible to release an
emergency call via external NMEA-telegram according to iec-regulation
(see page 59-61).
Service menu only contains 3 possible adjustments.
Test menu (1 – 3 sec access period), amount of OOW cabins (4 – 6 sec
access period), en-/disable of NMEA expansion module (7 – 9 sec access
period). All other menus (known from former versions) are no longer
available. In case of service menu’s inactivity within 3 minutes, the LOD
will jump from service menu to READY FOR AUTO ON/OFF
automatically.
In case of connection failure between LOD and NMEA expansion module,
the toggling display alarm indication will not appear on the display. Failure
relay K1 will drop out as usual and the failure indication will be shown at
the select menu’s last position.
In case of any alert, the possibility of dimming the display and the internal
buzzer is disabled.
The possibility to connect external transfer alarms to the NMEA
expansion module is not available anymore.
The possibility to connect external emergency call release button to the
NMEA expansion module is not available anymore.
Starting the countdown is only possible by actuating the key switch on
LOD or by keeping the external steady contact (29, 30) closed.
3 user manual le guardian vers 2.05 - 201703109
sm electricsGmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 4
sm electrics
4 user manual le guardian vers 2.05 - 201703109
sm electricsGmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 5
sm electrics
1 Instruction for use
le guardian 2025 and its extension devices (time period reset units, alarm
devices) must only be installed by trained electricians or other persons who are
familiar with installation of electric equipment.
Parts of the system can be damaged and persons put at risk if system is
connected incorrectly.
Connecting module (LCM 210.24.0.0) and NMEA expansion module (NMEA
210.24.0.0) are designed to be installed in an enclosure switch cabinet or control
console. For service and commissioning work connecting and expansion
modules should be installed in such manner, service personnel is able to see
state LEDs on modules.
Operating device (LOD 210.24.0.0) is designed to be installed on control
console.
Operating device and all time period reset units have to be installed only at
locations on bridge or bridge wings where OOW has a proper look out.
Installation must conform to regulations for electromagnetic compatibility (EMC).
(see chapter technical data & schematics)
5 user manual le guardian vers 2.05 - 201703109
sm electricsGmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 6
sm electrics
connecting module
LCM 210.24.0.0
-Z1
15 pole connector
to operating device
fuse holders
-F1, -F2 (m2A)
terminals for
24VDC power supply
terminals for
periphery equipment
2 Installation
Connecting module (LCM 210.24.0.0) and its extension devices (time period
reset units, alarm devices) have to be connected according to corresponding
wiring diagrams.
description
connecting module (LCM 210.24.0.0)
Module has been designed to click on terminal rail TS 35 inside electric cabinet
or control console. All periphery equipment (time period reset units, alarm
panels, power supply) is to be connected directly on connecting module without
any additional terminal board or distribution boxes according to wiring diagram
which is part of working drawings. Sample system wiring diagram is shown in
chapter “technical data & schematics”.
Outputs for “power on” indication and time period reset push button illumination
are short-cut protected. Maximum loads of outputs and output contacts see
chapter “technical data & schematics”.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
6 user manual le guardian vers 2.05 - 201703109
Page 7
sm electrics
operating device
LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
operating device (LOD 210.24.0.0)
Before mounting operating device into cut-out, plug on 15-pole system cable on device’s
rear side and tighten it properly. Use device clamps to fix device in proper manner.
Do not use longer system cable as standard length: l=3m!
Plug on 15-pole system cable on connecting module LCM 210.24.0.0 (-Z1) and
tighten it properly.
After connecting all additional equipment (time period reset units, alarm devices)
according to corresponding wiring diagram, system is ready for operating.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
7 user manual le guardian vers 2.05 - 201703109
Page 8
sm electrics
display „text 1“
system fail state relay
K1 with control LED 1
READY FOR
POWER ON / AUTO
3 Commissioning
Before switching on 24VDC (nominal) power supply to connecting module LCM
210.24.0.0 terminal board –X1: 1, 2 (+) & 3, 4 (-) make sure power supply, time
period reset units and external alarm devices have been connected correctly
according to wiring diagram.
Diode on LCM 210.24.0.0 connecting module secures system against wrong
power supply polarity.
After switching on 24VDC power supply (generally from24VDC Emergency
Distribution Board) systemfailstaterelay K1is activatedanddisplay on
operating device LOD 210.24.0.0shows “text 1”after a short intro procedure.
In case of system fail, relay K1 is not activated (control LED 1 is switched off).
When system is running properly, relay K1 is triggered and its potential free
contact is closed (-X1: 5, 6)
Make sure that up to now no external “power on” contact (steady contact: X1:29, 30 and pulsed contact: -X1: 26, 27 & 50, 51) is active.
System is running now and is waiting for user’s operation on operating device
LOD 210.24.0.0 or for an external “power on” command. Display shows “text1”.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
8 user manual le guardian vers 2.05 - 201703109
Page 9
sm electrics
operating device
LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
display „text 2“
COUNT-DOWN
*** 2:59 ***
Switch on system by turning key switch S1 on operating device LOD 210.24.0.0
one time to position “ON/OFF”
After system is switched on default dormant period (3:00min) is counting down
and display shows current state of count-down (display “text 3”).
Test of external illuminated time period reset unit:
In this “count-down mode” all illuminated time period reset units are activated.
Illumination of display and of reset units is adjustable by turning rotary encoder.
Minimum illumination is fixed.
Now push external reset units (one by one) and check 2nd line of display (current
value). Every reset should restart count-down ( 2:59).
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
9 user manual le guardian vers 2.05 - 201703109
Page 10
sm electrics
display „text 1“
READY FOR
POWER ON / AUTO
system is
shut down
Test of external “power on” devices: (optional)
In case external “power on” devices are involved, activate these devices (one by
one). Make sure before, display “text 1” is shown. Only in this “auto mode” an
external “power on” is possible.
notice:
Every switching on (from operating device LOD 210.24.0.0 or from external
devices) restarts count-down!
Test of external alarm devices and links
For checking alarm devices (external buzzers on bridge or bridge wing area,
alarm panels in officer’s area, link to general alarm system, link to VDR system
and system failure contact see chapter 4 “test mode” (maintenance & service)
For finishing commissioning procedure “switch off” system by turning key switch
S1 on operating device LOD 210.24.0.0 to position “ON/OFF” for longer than 2
sec.
Display shuts down and system ignores all external inputs now.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
10 user manual le guardian vers 2.05 - 201703109
Page 11
sm electrics
operating device
LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
display „text 4“
TEST MODE 1 OFF
ALARM on BRIDGE
key switch
S1
display „text 5“
TEST MODE 1 ON
ALARM on BRIDGE
4 Test mode - maintenance & service (service menu #1)
le guardian
procedure to check all output relevant devices (alarm panels, external buzzers,
links to alarm devices, links to VDR and system failure contact) in a very
comfortable manner.
To reach this “service mode 1” an authorized person has to “switch off” system
by turning key switch S1 on operating device LOD 210.24.0.0 to position
“ON/OFF” for longer than 2 sec. System shuts down. After that authorized
person has to keep pushing rotary encoder push button S2 and after a period
between 2 and 3 sec he has to “switch on” system by turning key switch S1 on
operating device LOD 210.24.0.0 one time to position “ON/OFF”
System starts in “servicemode”and displayis showing“text 4”
By pushing rotary encoder’s push button S2 for one time, all internal and
external bridge area alarm devices (alarm stage 1) are activated as long as push
button S2 is pushed again. During this manual alarm activation, display is
showing “text 5”.
2025
Bridge Navigational Watch Alarm System owns a test mode
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
11 user manual le guardian vers 2.05 - 201703109
Page 12
sm electrics
display „text 6“
TEST MODE 2 OFF
OFFICERs ALARM
display „text 7“
TEST MODE 2 ON
OFFICERs ALARM
display „text 8“
TEST MODE 3 OFF
ALARM STAGE 3
display „text 9“
TEST MODE 3 ON
ALARM STAGE 3
After a.m. test in “test mode 1” is done, user has to turn rotary encoder
clockwise to reach “test mode 2”.
Display is showing “text 6” and after pushing rotary encoder’s push button S2 for
one time, all alarm devices in officer’s area (alarm stage 2) and link to VDR
system (optional) are activated as long as push button is pushed again.
During this manual alarm activation, display is showing “text 7”.
After a.m. test in “test mode 2” is done, user has to turn rotary encoder
clockwise to reach “test mode 3”.
Display is showing “text 8” and after pushing rotary encoder’s push button S2 for
one time, system’s contact is activating very loud alarm devices in officer’s area
(alarm stage 3) and link to VDR system (optional) as long as push button is
pushed again.
During this manual alarm activation, display is showing “text 9”.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
12 user manual le guardian vers 2.05 - 201703109
Page 13
sm electrics
connecting module
LCM 210.24.0.0
system fail relay
K1 with control LED 1
display „text 10“
TEST MODE 4 OFF
DEVICE FAILURE
display „text 11“
TEST MODE 4 ON
DEVICE FAILURE
alarm stage 3 relay
K4 with control LED 4
alarm stage 1 relay
K2 with control LED 2
alarm stage 2 relay
K3 with control LED 3
After a.m. test in “test mode 3” is done, user has to turn rotary encoder
clockwise to reach “test mode 4”.
Display is showing “text 10” and after pushing rotary encoder’s push button S2
for one time, device’s failure contact opens and activate linked alarm system as
long as push button S2 is pushed again.
Consider possible alarm delay period created by linked alarm system!
During this manual alarm activation, display is showing “text 11”.
State of all output relays is shown by corresponding control LEDs. Consider
reversed relay logic of system failure relay K1!
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
13 user manual le guardian vers 2.05 - 201703109
Page 14
sm electrics
operating device
LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
For finishing “test mode”procedure “switch off” system by turning key switch S1
on operating device LOD 210.24.0.0 to position “ON/OFF”.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
14 user manual le guardian vers 2.05 - 201703109
Page 15
connecting module
LCM 210.24.0.0
system fail relay
K1 with control LED 1
fuse holder
F1, F2
system fail criteria
sm electrics
5 Trouble shooting
In following cases potential free(dry) n/o contact onconnecting module LCM 210.24.0.0
–X1: 5, 6 opens (systemfail state):
power supply failed (or main power supply voltage is lower than 13,2V)
program cycle interrupted (risc controller has been stopped)
link with 15 pole system cable Z1 between operating device and connecting module is
interrupted
in case NMEA expansion module is involved, when communication between operating
device (LOD 210.24.0.0) and expansion module (NMEA 210.24.0.0) has been failed
a) check supply voltage by comparing it with other systems fed from same distribution
source.
b) Switch off system’s power supply for minimum 10 sec by opening fuse holder F1
or F2 on connecting module LCM 210.24.0.0. After switching on power supply,
program will start automatically after 2 sec. in “normal mode”.
c) check system cable between connecting module LCM 210.24.0.0 and operating
device LOD 210.24.0.0, especially system plug on operating device’s rear side.
Cable might be damaged.
System fail state is indicated when system fail relay K1 is not triggered (control LED
D9 is off).
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
15 user manual le guardian vers 2.05 - 201703109
Page 16
sm electrics
Notice:
In case that during watch operations system’s power supply fails temporary (e.g.
black-out situation) watch operations restart automatically with old settings (settings
before power fail).
time period cannot reset, emergency call cannot reset
check all reset units if reset contact is closed permanently by switch’s malfunction or
accidental use.
No indication light is active (reset units & external “power on” devices)
Check if system is might be “switched off” by external system. Use key switch S1 on
operating device LOD 210.24.0.0.
Notice:
time period reset unit illumination and external “power on” indication are active only,
when count-down sequence is started.
If system works properly but without any indication, one bulb or LED in time period
reset units or external “power on” devices might be blown in that way, causing a shortcircuit. Replace damaged bulb / LED. Short-circuit does not damage system due to
short-circuit protected transistor outputs.
16 user manual le guardian vers 2.05 - 201703109
sm electricsGmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 17
sm electrics
operating device
LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
6 Centralized dimmer
le guardian 2025 BNWAS is designed with a centralized dimmer function. That means all
relevant illuminated time period reset units on bridge and bridge wing area as well as blue
display on operating device LOD 210.24.0.0 are adjustable by turning rotary encoder S2
on operating device LOD 210.24.0.0. Minimum illumination is limited. Dispay’s illumination
and time period reset unit’s illumination are sychronized. In case of any alert, the
possibility of dimming the display and the internal buzzer is disabled.
By turning rotary encoder S2 on operating device LOD 210.24.0.0 in counter clock wise
direction, illumination is decreasing. By turning rotary encoder S2 on operating device
LOD 210.24.0.0 in clockwise direction, illumination is increasing.
Notice:
dimmer function is suppressed during any kind of settings changing procedure by
using rotary encoder!
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
17 user manual le guardian vers 2.05 - 201703109
Page 18
sm electrics
new time period of alarm stage 2
[90sec.... 180sec]
date & sign
operating device
LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
7 Adjust time period of alarm stage 2 (alarm in officer’s area)
(for authorized persons only)
IMO regulations allow (MSC 75/24/Add.1 ANNEX 11, 4.1.2.7) to increase standard setting
of 90 sec of alarm stage 2 (alarm in officer’s area). Compare with chapter 9 technical data
and schematics (see watch alarm time table). Adjustment could be necessary due to
large vessel or vessel’s layout. Period can be adjusted to max. 180sec (default value is
90sec), to allow sufficient time for back-up officer and/or Master to reach bridge area
before watch alarm system is triggering alarm stage 3.
Write down decided new value here:
To adjust a.m. time period turn key switch S1 on operating device LOD 210.24.0.0 to
position “SELECT”.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
18 user manual le guardian vers 2.05 - 201703109
Page 19
sm electrics
display „text 3“
SET MAIN PERIOD:
3… 12min ** 3 **
display „text 24“
PERIOD ADJUST
AL.STAGE 2 090s
After turning key switch S1 to position “SELECT” display is showing “text 3”.
Now push rotary encoder’s push button S2 on operating device LOD 210.24.0.0 so often
as display is showing “text 24”.
Now turn rotary encoder in clockwise direction to increase time period value or in counterclock wise direction to decrease time period value. System allows only values between 90
and 180sec. By pushing rotary encoder’s push button S2 on operating device LOD
210.24.0.0 display is changing and system accepts adjusted value.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
19 user manual le guardian vers 2.05 - 201703109
Page 20
sm electrics
operating device
LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
display „text 3“
SET MAIN PERIOD:
3… 12min ** 3 **
display „text 22“
BUZZERs
PROPERTIES 1
8 Adjust buzzer characteristics & volume
le guardian 2025 system is designed with adjust mode to be able to change steady
internal and external alert tone into 7 additional individual buzzer characteristics in case
other systems on bridge area are generating a similar alert tone.
Adjust buzzer’s characteristic
To adjust buzzer’s characteristic turn key switch S1 on operating device LOD 210.24.0.0
to position “SELECT”.
After turning key switch S1 toposition“SELECT” displayis showing “text 3”.
Now push rotary encoder’s push button S2 on operating device LOD 210.24.0.0 so often
as display is showing “text 22”.
Now turn rotary encoder to choose an adequate buzzer characteristic. By pushing rotary
encoder’s push button S2 display is changing and system accepts adjusted value.
Do not accept offered buzzer characteristics during buzzer is activated
(Wait for the brake!)
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
20 user manual le guardian vers 2.05 - 201703109
Page 21
sm electrics
operating device
LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
display „text 3“
SET MAIN PERIOD:
3… 12min ** 3 **
display „text 23“
BUZZERs
SOUND VOLUME 15
Adjust internal buzzer’s volume
To adjust internal buzzer’s volume turn key switch S1 on operating device LOD
210.24.0.0 to position “SELECT”. Minimum sound volume is limted to 65dB(A)
After turning key switch S1toposition“SELECT” displayis showing “text 3”.
Now push rotary encoder’s push button S2 on operating device LOD 210.24.0.0 so often
as display is showing “text 23”.
Now turn rotary encoder in counter clock wise direction to decrease buzzer’s sound
volume or in clock wise direction to increase sound volume. By pushing rotary encoder’s
push button S2 display is changing and system accepts adjusted value.
Notice:
During alarm stage 1 (alarm on bridge & bridge wing area) internal buzzer’s sound
volume can be adjusted by turning rotary encoder on operating device!
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
21 user manual le guardian vers 2.05 - 201703109
Page 22
sm electrics
9 service menu overview
(for commissioning and service staff only!
Service menu #1: Test Mode 1...4 to simulate alarm stage #1, stage #2, stage #3
and system’s fail state.
Pushing period after shut-down: 1-3 sec
Service menu #2: Define quantity of involved back-up OOW cabins
Pushing period after shut-down: 4-7 sec
Menu is available only after NMEA expansion module is enabled!
Service menu #3: Enabling / disabling of NMEA expansion module
Pushing period after shut-down: 7-10 sec
22 user manual le guardian vers 2.05 - 201703109
sm electricsGmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 23
sm electrics
generals
description: le guardian 2025 BNWAS
power supply: 24VDC (nominal), 18,0… 31,2VDC, nominal feeding value: B4A
power consumption: min. 60mA, max. 400mA, nominal value: 120mA
internal fuses: 2x m2,0A, 5x20mm
degree of enclosure: acc. EN 60529 see table
approbation: design & manufacturing acc. IEC 60945, type approvals: GL, KR, RRS
transistor outputs: “power on” indication: max. 400mA, reset p/b illumination: 2x 180mA
max. load of relay contacts: 30VDC, 2A
no.:
type:
description:
weight: [kg]
degree of
enclosure
safety distance
to magnetic
compass [m]:
cable
cross-sections:
spare parts:
1
operating device
LOD 210.24.0.0
console mounted operating device with blue illuminated display,
key switch and rotary encoder with integrated push button,
w 144 x h 72 x d 75mm
device: 0,200
cable: 0,300
front: IP22
back: IP00
0,5
/
-
2
connecting module
LCM 210.24.0.0
terminal board module, to be mounted on terminal rail TS35,
w 162 x h 127 x d 68mm
0,330
IP20
0,5
0,2....1,5mm²
2x micro fuse, m2,0A, 5x20mm
part no.: 097109
3
NMEA exp. module
NMEA 210.24.0.0
terminal board module, to be mounted on terminal rail TS35,
w 87,1 x h 127 x d 68mm
0,164
IP20
0,5
0,2....1,5mm²
1x micro fuse, m2,0A, 5x20mm
part no.: 097109
4
WAP 220.2.0.0
watch alarm panel for officer's cabin, 80 dB(A)
flush mounting
0,150
front: IP23
back: IP00
/
0,2... 2,5mm²
1x bulb, mg28V, 40mA
part no.: 099081
5
WAP 220.5.0.0
watch alarm panel for officer's cabin, 80 dB(A)
bulkhead mounting
0,275
IP23
/
0,2... 2,5mm²
1x bulb, mg28V, 40mA
part no.: 099081
6
WAP 220.4.0.0
watch alarm panel for officer's area (corridor), 64-111dB(A)
bulkhead or flush mounting
- After Failure Alarm Panel is connected to its power supply (terminals 1&2)
and monitoring loop is closed (terminal 3&4) panel is activated for monitoring.
- In case monitoring loop is opened for longer than 250ms visual & audible
indication (H1 & H2) has been activated.
- Audible indication (buzzer H2) can be stopped by pushing reset push button
S1.
- Visual indication (indication lamp H1) is activated as long as monitoring loop
is opened (monitored system is in fail state)
- When loop is opened for a short period only, due to a short fail state of
monitored system, buzzer (H2) is activated as long as reset push button has
been pushed.
- Push button S1 can be used as lamp & buzzer test.
detecting method:
A heating source (human being) has been detected only, when it is passing
a defined quantity of sectors whithin a defined period.
That is to avoid unintentional detection of a fixed heating source (heater,
coffee machine, hot power supply)
That means consequently, OOW has to pass sectors for detecting.
Sensor's sensitivity is depending on distance due to sector geometry
INDEXARTTYP-A/STAND-EAUFTRAG-NR
BNWAS WMS 220.2.0.0ME A
sm electrics
sm electricsGmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
sm electricsGmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
48 user manual le guardian vers 2.05 - 201703109
Page 49
sm electrics
WPS220.24.0.0, 100…240VAC / 24VDC, 2.5A Power Supply Unit
sme part no.: 770466
dfwg
49 user manual le guardian vers 2.05 - 201703109
sm electricsGmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 50
sm electrics
NMEA expansion module
NMEA 210.24.0.0
11 NMEA expansion module
NMEA expansion module (NMEA 210.24.0.0)is designed for the following operations:
transmit permanently system’smodebysendingNMEAsentences acc. IEC 61162-1 to external
systems especially VDR for datalogging
receive NMEA sentences acc.IEC61162-1 fromexternalsystems (e.g. radar) to give
commands to BNWAS (e.g. reset command of dormant period)
Master can decide which back-up OOW’s cabin shall receive stage #2 alarm (multiple selection
is possible, minimum selection: 1 cabin!)
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
50 user manual le guardian vers 2.05 - 201703109
Page 51
sm electrics
NMEA Expansion Module
NMEA 210.24.0.0
-Z1, RJ45 connector
to operating device
fuse holder
-F1, (m2A)
terminals for
24VDC power supply
terminals for
periphery equipment
control LEDs
LED1...LED12
11.1 NMEA expansion module installation
NMEA expansion module (NMEA 210.24.0.0) has to be connected according to
corresponding wiring diagrams.
description
Module has been designed to click onterminal rail TS 35 inside electric cabinet
or control console. All periphery equipment (alarmpanels, input contacts, power
supply) is to be connected directly onNMEAmodule without any additional
terminal board or distribution boxes according to wiring diagram which is part of
working drawings. Sample system wiring diagram is shown in chapter “technical
data & schematics”.
Outputs for stage #2 alarm panels (WAP 220.2.0.0 or WAP 220.5.0.0) are shortcut protected. Maximum output current is 500mA (each output).
Power Supply
It is preferred to feed NMEA expansion module with same 24VDC power supply
as connecting module (LCM 210.24.0.0).
Link to operating device (LOD 210.24.0.0)
Use 3m patch link cable which is part of NMEA expansion module to do serial
link between operating device & NMEA expansion module
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
51 user manual le guardian vers 2.05 - 201703109
Page 52
sm electrics
control LEDs
LED6...LED10
show state of binary inputs
control LEDs
LED1...LED5
show state of binary outputs
display „text 1“
READY FOR
POWER ON / AUTO
11.2 NMEA expansion module commissioning
Before switching on 24VDC (nominal) power supply to NMEA expansion module (NMEA
210.24.0.0) on terminal board –X1: 1, 2 (+) & 3, 4 (-) make sure basic system (operating
device LOD 210.24.0.0 & connecting module LCM 210.24.0.0) is operating in normal
condition.
Diode on NMEA expansion module secures system against wrong power supply
polarity.
After connecting 24VDC power supplyand link cable tooperating device has
been connected, system mustbe switched on for enabling NMEA expansion
module.
11.2.1 Enabling NMEA expansionmodule(service menu #5)
NMEA expansion module (NMEA 210.24.0.0) must beenabled on operating
device (LOD 210.24.0.0) for un-locking several NMEA expansion module’s
operating functions.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
52 user manual le guardian vers 2.05 - 201703109
Page 53
sm electrics
operating device
LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
display „text 62“
ENTER CODE XXXXX
TO ENABLE NMEAXM
key switch
S1
display „text 63“
NMEA EXP. MODULE
IS ENABLED
system is
shut down
Do a system shut-down when display is showing “display text 1” by turning key
switch S1 on operating device LOD 210.24.0.0 to position “ON/OFF” for longer
than 2 sec. System shuts down and operating device’s display is blank.
Then push and keep pushing rotary encoder’s push button S2 and after a period
between 13 and 15 sec “switch on” system by turning key switch S1 on
operating device LOD 210.24.0.0 one time to position “ON/OFF”. A timer shown
on display is supporting this time depending operation.
So system starts in “service menu 5” and display is showing “text 62”
Move key switch S1 into position “SELECT” and push rotary encoder’s push button one time. Display shows “text 63”.
Move key switch S1 into position “ON/OFF” – system start-up is running an
NMEA expansion module has been enabled.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
53 user manual le guardian vers 2.05 - 201703109
Page 54
sm electrics
display „text 1“
READY FOR
POWER ON / AUTO
system is
shut down
To check whether NMEA expansion module has been enabled, move key switch S1
into position “SELECT” and push rotary encoder’s push button S2 two times to
reach an additional menu to select back-up officer’s cabin for receiving stage #2
alarm. This menu is available only, when NMEA expansion module has been
enabled!
NMEA expansion module is running now and is waiting for user’s operation on
operating device LOD 210.24.0.0 or for an external “power on” command. When
display shows “text1” NMEA interface starts sending NMEA telegrams. A control
LED (LED11) on NMEA expansion module is indicating sending process.
11.2.2 Define quantity of involved back-up OOW cabins (service menu #2)
Person in charge for commissioning has to set right parameter for involved back-up OOW
cabins. Allowed number of involved cabins is between 2 and 5 depending on ship’s safety
philosophy. This number must be set into parameter settings to avoid unintentional selection of
“not existing” back-up OOW cabins. To set right parameter do a system shut-down for
reaching “service menu 2” (number of back-up OOW cabins).
Do a system shut-down when display is showing “display text 1” by turning key switch S1 on
operating device LOD 210.24.0.0 to position “ON/OFF” for longer than 2 sec. System shuts
down and operating device’s display is blank.
Then push and keep pushing rotary encoder’s push button S2 and after a period between 4
and 6 sec “switch on” system by turning key switch S1 on operating device LOD 210.24.0.0
one time to position “ON/OFF”. A timer shown on display is supporting this time depending
operation.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
54 user manual le guardian vers 2.05 - 201703109
Page 55
sm electrics
operating device
LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
display „text 40“
NUMBER_OF_OOW’s
CABINS: * * * * 5 * * * *
So system starts in “servicemenu#2”anddisplay is showing “text 40”
Use rotary encoder to adjust right number of involved cabins. Selection between 2 and 5 is
allowed and available only.
After right selection has been done, start-up system by moving key switch S1 into position
“ON/OFF”.
Definition of involved back-up OOW’s cabin quantity is strongly necessary to avoid
unintentional selection of non existing cabins!
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
55 user manual le guardian vers 2.05 - 201703109
Page 56
sm electrics
location:
description:
NMEA expansion
module terminal no.:
cabin no #1
Deck 5, R. 515
Captain
21 (+), 22 (-)
cabin no #2
Deck 5, R. 524
1st Officer
23 (+), 24 (-)
cabin no #3
Deck 5, R. 525
2nd Officer
25 (+), 26 (-)
cabin no #4
Deck 5, R. 526
3rd Officer
27 (+), 28 (-)
cabin no #5
-
not used
29 (+), 30 (-)
location:
description:
NMEA expansion
module terminal no.:
cabin no #1
21 (+), 22 (-)
cabin no #2
23 (+), 24 (-)
cabin no #3
25 (+), 26 (-)
cabin no #4
27 (+), 28 (-)
cabin no #5
29 (+), 30 (-)
11.2.3 Define relation between cabin number and real cabin location
Use the following table to define real cabin location and system’s cabin numbers:
sample table
vessel’s table
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
56 user manual le guardian vers 2.05 - 201703109
Page 57
sm electrics
transmitting LED11
NMEA 210.24.0.0
display „text 1“
READY FOR
POWER ON / AUTO
11.2. Transmit NMEA sentences to external systems (especially VDR)
NMEA expansion module (NMEA 210.24.0.0) is transmitting permanently serial data according
standard IEC 61162-1.
After start-up system display “text 1” is showingandtransmitting LED11 is flashing
(about 3Hz). Flashing frequencyis dependingonsystem’s state!
When count-down is running transmittingLED11is flashing only (1 time) when system’s state
has been changed (e.g. when pre-alarm occurs).
An external system, especially VDR system, can be connected to terminals 16(A) & 17(B) for
data logging.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
57 user manual le guardian vers 2.05 - 201703109
Page 58
sm electrics
NMEA sentences from BNWAS to external systems (especially VDR)
ALR: operating state after 1st power-on / after system start-up
$ B N A L R , , 0 0 0 , V , A , C 1 = A U T ; C 2 = 0 3 ; C 3 = 0 * h h CR
LF
1
2 3 4
5 6
fields:
1: Message type: alarm message
2: Reset / start source:
- 000: start up is reset command
- LOD: integrated reset button or hardware reset inputs
- NME: via NMEA interface from external system
- EXT: via external system (dry contacts, start/stop)
3: Dormant period:
A= Dormant period exceeded
V= Dormant period not exceeded
4: Alarm situation:
A= Alarm situation acknowledged
V= Alarm situation not acknowledged
5: BNWAS mode:
C1 = AUT, MAN or OFF (bei uns ist MAN wenn Schlüssel auf "SELECT"
C2 = Dormant period in minutes (03…12)
C3 = Stage alarm; 0, 1, 2, 3
6: CRC
example (after start-up):
$BNALR,,000,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
Serial NMEA data have been designed according to the following structure:
Transmitting of NMEA sentences cannot be stopped or delayed under any circumstances!
58 user manual le guardian vers 2.05 - 201703109
sm electricsGmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 59
sm electrics
EVE (short):
count-down reset of mainperiod
field length is depending onsource'ssystem ID
$ - - E V E , , B N W A S , Operatoractiv i t y * h
h
CR L
F
1
2
3 4
fields:
1: Message type: Event
2: Event source tag code: BNWAS (sender's view)
3: Event description:
Operator activity
4: CRC
receiving LED12
NMEA 210.24.0.0
11.3. Receive NMEA sentences from external systems
NMEA expansion module (NMEA 210.24.0.0) can receive serial data according standard IEC
61162-1 for remote control of BNWAS le guardian
Receiving LED is active in steady light after a transmitter has been connected correctly.
In case NMEA expansion module is receivinga NMEAsentence (telegram) steady light of
receiving LED12 has been interruptedfor somemilliseconds.
The following control NMEA sentences can be accepted:
2025
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
59 user manual le guardian vers 2.05 - 201703109
Page 60
sm electrics
EVE (long):
count-down reset of main period
field length is depending on source's system ID
$ - - E V E , , h h m m s s . s s , B N W A S , O p e r a t o r a c t i v i t y * h
h
CR L
F
1
2
3
4
5
fields:
1: Message type: Event
2: UTC time
3: Event source tag code: BNWAS (sender's view)
4: Event description:
Operator activity
5: CRC
ALR (short):
release of Em'cy Call without any further delay (stage #2 alarm)
field length depending on source system ID
$ - - A L R , , x x x , A , V , E m e r g e n c y C a l l * h h
CR L
F
1
2 3 4
5 6
fields:
1: Message type: Alarm message
2: Unique alarm number (identifier) from alarm source, e.g. measuring point number
3:Alert condition:
A = threshold exceeded
V = threshold not exceeded
4: Alarm state:
A = acknowledged
V = unacknowledged
5: Alarm description:
Emergency Call (command)
6: CRC
ALR (long):
release of Em'cy Call without any further delay (stage #2 alarm)
field length depending on source system ID
$ - - A L R , h h m m s s . s s , x x x , A , V , E m e r g e n c
y C a l l * h h
CR L
F
1 2
3 4 5 6 7
fields:
1: Message type: Alarm message
2: UTC time
3: Unique alarm number (identifier) from alarm source, e.g. measuring point number
4:Alert condition:
A = threshold exceeded
V = threshold not exceeded
5: Alarm state:
A = acknowledged
V = unacknowledged
6: Alarm description:
Emergency Call (command)
7: CRC
60 user manual le guardian vers 2.05 - 201703109
sm electricsGmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 61
sm electrics
ALR (short):
empty ALR alert list for transfer alarm reset
field length depending on source system ID
$ - - A L R , , , V , V , * h
h
CR L
F
1
2 3 4
fields:
1: Message type: Alarm message
2: Alert condition:
V = threshold not exceeded
3: Alarm state:
V = unacknowledged
4: CRC
ALR (long):
empty ALR alert list for transfer alarm reset
field length depending on source system ID
$ - - A L R , h h m m s s . s s , , V , V , * h h
CR L
F
1
2
3 4 5
fields:
1: Message type: Alarm message
2: UTC time
3:Alert condition:
V = threshold not exceeded
4: Alarm state:
V = unacknowledged
5: CRC
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
12.6.1 System shut down ................................................................. 70
12.1.0 Generals
The purpose of a bridge navigational watch alarm system is to monitor bridge activity and
detect operator disability which could lead to marine accidents. The system monitors
awareness of the Officer of the Watch (OOW) and automatically alerts the Master or another
qualified person if for any reason OOW becomes incapable of performing OOW’s duties.
This purpose is achieved by series of indications and alarm to alert first the OOW and, if he
is not responding, then to alert Master or another qualified person. Additionally, the BNWAS
provide the OOW with means of calling for immediate assistance if required.
This user manual (short version) is made for persons who know basic standards of watch
alarm system. All time period reset inputs are protected against permanent reset.
62 user manual le guardian vers 2.05 - 201703109
sm electricsGmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
Page 63
sm electrics
display „text 1“
READY FOR
POWER ON / AUTO
display „text 2“
COUNT-DOWN
*** 2:59 ***
operating device
LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
12.1.1 Installation
After operating device LOD 210.24.0.0 and connecting module LCM 210.24.0.0 are
installed according to technical documentation by authorized personnel, system has
to be supplied by 24VDC battery power supply (terminal board -X1: 1, 3). Potential
free n/o failure contact (connecting module –X1: 5, 6) closes and system is ready for
switch on. After a short display intro display on operating device is showing “text 1”.
12.2.1 Manual switch on
Authorized person (Master) switches on system by single turning key switch –S1 on
operating device to position “ON/OFF”. System’s running is indicated by activating
last selected dormant (main) period and count-down is active as shown on display
“text 2”.
If dormant (main) period (3... 12 min) shall not be changed, authorized person
(Master) pull off the key. Dormant period is counting down from the moment that
system has been switched on.
Dormant period is period within OOW is monitored but no further alert is triggered.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
63 user manual le guardian vers 2.05 - 201703109
Page 64
sm electrics
display „text 3“
SET MAIN PERIOD:
3… 12min ** 3 **
display „text 1“
READY FOR
POWER ON / AUTO
12.2.2 Automatically switch on
System can be switched on by external systems via potential free steady n/o contact
which has to be connected on connecting module LCM 210.24.0.0 –X1: 29 & 30.
Automatic switch on is possible only in automatic mode - when display is showing
“text 1”.
In case automatic switch on shall not be possible, master has to shut-down system
(see chapter 5.1 System shut-down)
12.3.0 Select dormant (main) period
In case that authorized person (Master) demands to select other dormant period,
person has to turn key switch S1 on operating device to position “SELECT”. In this
position only dormant period can be chosen by using rotary encoder S2 on operating
device. Display is showing “text 3”.
By turning rotary encoder S2 in clock wise direction, value is increasing. By tuning
rotary encoder S2 in counter clock wise direction, value is decreasing. Possible main
period value is limited between 3 and 12 min. Step width is 1 min. By turning key
switch S1 into centre position, system accepts new value and count-down starts
from the moment the key has turned into centre position. Authorized person (Master)
can pull off key only in centre position.
Dormant (main) period (3... 12 min) shows after which period automatically
generated alert sequences will be triggered. (see time table, page 20)
12.3.1 Reset of dormant (main) period
As a rule monitored person (OOW) resets dormant period by pushing illuminating
push buttons or rotary encoder’s integrated push button S2 on operating device
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
64 user manual le guardian vers 2.05 - 201703109
Page 65
sm electrics
display „text 12“
RESET EXPECTED
0:14
display „text 13“
*RESET EXPECTED*
********* 0:13 **********
display „text 14“
RESET EXPECTED
0:14
display „text 15“
ALARM STAGE 1
0:13
during his actual work on bridge area. Every reset is re-starting complete countdown independent of its moment. To serve rules of ergonomics several reset units
should be placed on strategic locations on bridge and bridge wing area. These reset
units are maximum sized illuminated push buttons as well as loud electronic sounder
which have been connected on connecting module LCM 210.24.0.0
12.3.2 Alert sequences start automatically
12.3.2.1 visual alarm indications (pre-alarm)
If dormant (main) period is over without OOW’s reset, system activates all
illuminated reset units by 1Hz flash light. This sequence is calling “pre-alarm”.
Display is showing in 1Hz toggle mode display “text 12” and “text 13”.
All illuminated push buttons and display on operating device are centralized
dimmable via rotary encoder S2 on operating device. Minimum illumination is fixed.
12.3.2.2 Alarm stage 1
If dormant (main) period and pre-alarm period (15 sec) are over without OOW’s
reset, system activates internal electronic buzzer as well as additional buzzers
located on bridge or bridge wing area. This sequence is calling “alarm stage 1”. Display is showing in 1 Hz toggle mode display “text 14” and “text 15”.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
65 user manual le guardian vers 2.05 - 201703109
Page 66
sm electrics
display „text 16“
RESET EXPECTED
1:29
display „text 17“
ALARM STAGE 2
1:28
display „text 18“
RESET EXPECTED
ALARM STAGE 3
Alarm stage 1 is triggered to pay attention to monitored OOW. Sound characteristics
and sound volume are adjustable (see user manual chapter 8 Adjust buzzer
characteristics & volume). One additional potential free (dry) n/o contact is closed
now for further use as well as for VDR link. (Additional buzzers or alarm devices can
be connected directly on connecting module.)
12.3.2.3 Alarm stage 2
If dormant (main) period, pre-alarm period (15 sec) and alarm stage 1 (15 sec) are
over without OOW’s reset, system activates alarm stage 2. Display on operating
device is showing in toggle mode display “text 16” and “text 17”.
One additional potential free (dry) n/o contact is closed now for further use as well as
for VDR link. Optic / acoustical alarm devices in officer’s area (cabins or staircase)
are activated. In case software selector switch is involved (see 11.x.x.x) alarm
devices in selected back-up OOW’s cabins only are activated!
12.3.2.4 Alarm stage 3
If dormant (main) period, pre-alarm period (15 sec), alarm stage 1 (15 sec) and
alarm stage 2 (90... 180 sec) are over without OOW’s reset, system activates alarm
stage 3. Display on operating device is showing in toggle mode display “text 18” and
“text 19”.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
66 user manual le guardian vers 2.05 - 201703109
Page 67
sm electrics
display „text 19“
ALARM STAGE 3
RELEASED
display „text 28“
BACK-UP_OOW_No.1
ON_DUTY: ***ON***
operating device
LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch S1
Stage 2 alarm is active in
Cabin No.1
Two potential free (dry) n/o contacts on connecting module are closed now for alarm
stage 3 trigger (very loud alarm devices in officer’s area or public area) as well as for
VDR link.
12.4.1 Back-up OOW’s selection & indication
le guardian 2025 system can be updated with back-up OOW’s cabins software
selector switch. For using this feature NMEA expansion module 210.24.0.0 has to be
installed and enabled. During commissioning work firm technician / engineer has
defined and reported (see chapter 11.2.2 Define quantity of involved back-up OOW
cabins (service menu #2)) how many back-up OOW’s cabins are involved for alarm
stage 2 activation. That means master can decide into which back-up OOW’s cabins
alarm stage 2 has to be transferred or not.
For that authorized person (Master) moves key switch S1 on operating device to
position “SELECT”. After pushing rotary encoder’s push button S2 display is showing
display “text 28”
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
67 user manual le guardian vers 2.05 - 201703109
Page 68
sm electrics
display „text 29“
BACK-UP_OOW_No.1
ON_DUTY: ***OFF**
Stage 2 alarm is not active
in Cabin No.1
display „text 49“
B.UP_OOW_ON_DUTY
_ _ _1_x_3_x_5_ _ _ _
By turning rotary encoder cabin of back-up OOW No.1 can be switched on “ON” or switched
off “OFF”. This selection can be repeated as many as back-up OOW’s cabins are involved
(minimum 2 cabins, maximum 5 cabins).
Selection overview
To check which cabins have been selected for alarm stage 2, start count-down and wait for 5
sec. Then display is showing e.g. the following selection:
Authorized person (Master) and later on OOW can check / recheck after each count-down
reset, cabin selection. Display “text 49” shows cabin No.1, No.3 & No.5 have been selected to
receive alarm stage 2. Cabin No.2 & No.4 are not selected!
Notice! Software makes sure minimum one cabin has been selected!
When alarm stage 3 is activated, every back-up OOW’s cabins alarm device is active
regardless of its selection state!
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
68 user manual le guardian vers 2.05 - 201703109
Page 69
sm electrics
display „text 20“
EMERGENCY CALL
1:29
display „text 21“
OFFICERs ALARM
1:28
12.5.1 Emergency call
Monitored OOW is able to generate an emergency call...
...by pushing rotary encoder on LOD longer than 5 sec.
That activates without delay alarm stage 2 and subsequently alarm stage 3 later on.
Display on operating device is showing in toggle mode display “text 20” and “text
21”.
Notice! Emergency Call feature is not activated when system is shut-down!
see chapter 11.5.1 System shut-down.
Emergency Call reset is possible by pushing any reset unit longer than 2 sec.
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
69 user manual le guardian vers 2.05 - 201703109
Page 70
sm electrics
system is
shut down
operating device
LOD 210.24.0.0
2x16 character
illuminated display
rotary encoder incl.
push button S2
key switch
S1
connecting module
LCM 210.24.0.0
-Z1
15 pole connector
to operating device
fuse holders
-F1, -F2 (m2A)
terminals for
24VDC power supply
terminals for
periphery equipment
12.6.1 System shut down
If system is not in operation and external automatic “system on” should not be
possible, Master is able to shut down system by turning key switch S2 on operating
device for longer than 2 sec to position “ON/OFF”.
System and display shut down and system ignores all external inputs now.
Notice!When system is shut-down no emergency call is possible!
sm electrics GmbH | Am Wulfsbarg 17 | D-24217 Stakendorf | Germany | tel.: +49 4344 81923-10 | www.sm-electrics.de
70 user manual le guardian vers 2.05 - 201703109