Guardian 5240, 5241, 5282, 5281, 5280 Diagnostic Repair Manual

...
Page 1
MODELS:
5240, 5280 (7 kW NG, 6 kW LP) 5241, 5281 (9 kW NG, 10 kW LP) 5242, 5282 (13 kW NG, 13 kW LP)
5243, 5283 (15 kW NG, 16 kW LP) 5244, 5284 (15 kW NG, 16 kW LP)
DIAGNOSTIC
DIAGNOSTIC
REPAIR MANUAL
REPAIR MANUAL
AUTOMATIC STANDBY GENERATORS
www.guardiangenerators.com
Page 2
ELECTRICAL FORMULAS
TO FIND KNOWN VALUES 1-PHASE 3-PHASE
KILOWATTS (kW)
KVA
AMPERES
WATTS
NO. OF ROTOR POLES
FREQUENCY
RPM
kW (required for Motor)
Volts, Current, Power Factor
Volts, Current
kW, Volts, Power Factor
Volts, Amps, Power Factor Volts x Amps E x I x 1.73 x PF
Frequency, RPM
RPM, No. of Rotor Poles
Frequency, No. of Rotor Poles
Motor Horsepower, Efficiency
E x I 1000
E x I 1000
kW x 1000
E
2 x 60 x Frequency
RPM
RPM x Poles
2 x 60
2 x 60 x Frequency
Rotor Poles
HP x 0.746
Efficiency
E x I x 1.73 x PF
1000
E x I x 1.73
1000
kW x 1000
E x 1.73 x PF
2 x 60 x Frequency
RPM
RPM x Poles
2 x 60
2 x 60 x Frequency
Rotor Poles
HP x 0.746
Efficiency
RESISTANCE
VOLTS
AMPERES
E = VOLTS I = AMPERES R = RESISTANCE (OHMS) PF = POWER FACTOR
Volts, Amperes
Ohm, Amperes I x R I x R
Ohms, Volts
E
I
E R
E
I
E R
Page 3
Contents
SPECIFICATIONS..................................................... 4
Generator ................................................................ 4
Stator Winding Resistance Values/
Rotor Resistance ..................................................... 4
Engine ..................................................................... 5
Fuel Consumption ................................................... 5
Mounting Dimensions ........................................... 6-7
Major Features ........................................................ 8
PART 1 - GENERAL INFORMATION ....................... 9
1.1 Generator Identification ................................... 10
1.2 Prepackaged Installation Basics ..................... 11
Introduction ......................................................11
Selecting A Location ........................................11
Grounding The Generator ................................11
The Fuel Supply ...............................................11
The Transfer Switch / Load Center ...................11
Power Source And Load Lines .........................13
System Control Interconnections .....................13
1.3 Preparation Before Use ................................... 14
General ............................................................14
Fuel Requirements...........................................14
Fuel Consumption ............................................14
Reconfiguring The Fuel System .......................14
Engine Oil Recommendations .........................16
1.4 Testing, Cleaning and Drying........................... 16
Meters ............................................................17
The VOM ..........................................................17
Measuring AC Voltage .....................................17
Measuring DC Voltage .....................................17
Measuring AC Frequency ................................17
Measuring Current ...........................................18
Measuring Resistance .....................................18
Electrical Units .................................................19
Ohm's Law .......................................................19
Visual Inspection ..............................................20
Insulation Resistance .......................................20
The Megohmmeter...........................................20
Stator Insulation Resistance Test .....................21
Rotor Insulation Resistance Test ......................22
Cleaning The Generator...................................22
Drying The Generator ......................................22
1.5 Engine-Generator Protective Devices ............. 23
General ............................................................23
Low Battery ......................................................23
Low Oil Pressure Shutdown .............................23
High Temperature Switch .................................23
Overspeed Shutdown ......................................23
RPM Sensor Failure .........................................23
Overcrank Shutdown .......................................24
1.6 Operating Instructions ..................................... 25
Control Panel ...................................................25
To Select Automatic Operation ........................26
Manual Transfer To “Standby” And
Manual Startup ....................................26
Manual Shutdown And Retransfer
Back To “Utility” ....................................27
1.7 Automatic Operating Parameters .................... 28
Introduction ......................................................28
Automatic Operating Sequences .....................28
PART 2 - AC GENERATORS.................................. 29
2.1 Description and Components .......................... 30
Introduction ......................................................30
Engine-generator Drive System .......................30
The AC Generator ............................................30
Rotor Assembly ................................................30
Stator Assembly ...............................................31
Brush Holder And Brushes ..............................31
Other AC Generator Components ...................31
2.2 Operational Analysis ....................................... 33
Rotor Residual Magnetism...............................33
Field Boost .......................................................33
Operation .........................................................34
2.3 Troubleshooting Flowcharts ............................. 35
Problem 1 - Generator Produces Zero
Voltage or Residual Voltage .......... 35-36
Problem 2 - Generator Produces
Low Voltage at No-Load ......................37
Problem 3 - Generator Produces
High Voltage at No-Load .....................37
Problem 4 - Voltage and Frequency Drop
Excessively When Loads are Applied .38
2.3 Diagnostic Tests .............................................. 39
Introduction ......................................................39
Safety ............................................................39
Test 1 - Check Main Circuit Breaker.................39
Test 2 - Check AC Output Voltage ....................39
Test 4 - Fixed Excitation Test/Rotor
Amp Draw Test ....................................40
Test 5 - Wire Continuity ....................................41
Test 6 - Check Field Boost ...............................42
Test 7 - Testing The Stator With a VOM ...........42
Test 8 - Resistance Check of Rotor Circuit ......44
Test 9 - Check Brushes and Slip Rings ............44
Test 10 - Test Rotor Assembly .........................45
Test 11 - Check AC Output Frequency.............45
Page 1
Page 4
Test 12 - Check And Adjust Engine Governor
(Single Cylinder Units) .........................46
Test 12A - Check Stepper Motor Control
(V-twin Engine Units) ...........................46
Test 13 - Check And Adjust
Voltage Regulator ................................48
Test 14 - Check Voltage And
Frequency Under Load ........................48
Test 15 - Check For Overload Condition ..........48
Test 16 - Check Engine Condition ....................48
PART 3 - "V-TYPE PREPACKAGED
TRANSFER SWITCHES.......................... 49
3.1 Description and Components .......................... 50
General ............................................................50
Enclosure .........................................................50
Transfer Mechanism .........................................51
Transfer Relay .................................................51
Neutral Lug ......................................................52
Manual Transfer Handle ..................................52
Terminal Block .................................................52
Fuse Holder .....................................................53
3.2 Operational Analysis ....................................... 54
Utility Source Voltage Available .......................56
Utility Source Voltage Failure ..........................57
Transfer To Standby ........................................58
Transfer To Standby ........................................59
Utility Restored.................................................60
Utility Restored, Transfer Switch
De-energized .......................................61
Utility Restored,
Retransfer Back To Utility ....................62
Transfer Switch In Utility ...................................63
3.3 Troubleshooting Flow Charts ........................... 64
Introduction To Troubleshooting .......................64
Problem5-InAutomatic Mode,
No Transfer to Standby ........................64
Problem6-InAutomatic Mode, Generator
Starts When Loss of Utility Occurs, Generator Shuts Down When Utility Returns But There Is
No Retransfer To Utility Power .............65
Problem 7 - Blown F1 or F2 Fuse ....................65
3.4 Diagnostic Tests .............................................. 66
General ............................................................66
Test 21 - Check Voltage at
Terminal Lugs E1, E2 ..........................66
Test 22 - Check Voltage at
Standby Closing Coil C2 .....................67
Test 23 - Test Transfer Relay TR ......................67
Test 24 - Check Manual Transfer
Switch Operation .................................68
Test 25 - Test Limit Switch XB1 ........................69
Test 26 - Check 23 And 194
Wiring/Connections .............................69
Test 27- Check Voltage At
Terminal Lugs N1, N2 ..........................70
Test 28 - Check Voltage At Utility 1
And Utility 2 Ter minals .........................70
Test 29 - Check Voltage At
Utility Closing Coil C1 ..........................71
Test 30 - Check Fuses F1 And F2 ...................71
Test 31 - Test Limit Switch Xa1 ........................72
Test 32 - Continuity Test Of Wiring (C1) ...........72
Test 33 - Continuity Test Of Wiring (C2) ...........72
Test 34 - Check N1 And N2 Wiring ..................73
Test 35 - Check Transformer (Tx) .....................73
PART 4 - DC CONTROL ......................................... 75
4.1 Description and Components .......................... 76
General ............................................................76
Terminal Strip / Interconnection Ter minal .........76
Transformer (TX) ..............................................76
Circuit Board ....................................................76
AUTO-OFF-MANUAL Switch ...........................80
15 Amp Fuse....................................................80
4.2 Operational Analysis ....................................... 82
Introduction ......................................................82
Utility Source Voltage Available ........................82
Initial Dropout Of Utility Source Voltage ...........84
Utility Voltage Dropout And
Engine Cranking ..................................86
Engine Startup And Running ...........................88
Initial Transfer To The “Standby” Source ...........90
Utility Voltage Restored /
Re-transfer To Utility ............................92
Engine Shutdown ........................................... 94
4.3 Troubleshooting Flow Charts ........................... 96
Problem 8 - Engine Will Not Crank
When Utility Power Source Fails .........96
Problem 9 - Engine Will Not Crank
When AUTO-OFF-MANUAL Switch
is Set to "MANUAL" .............................96
Problem 10 - Engine Cranks
but Won't Start .....................................97
Problem 11 - Engine Starts Hard and
Runs Rough / Lacks Power .................98
Problem 12 - Engine Starts and Runs,
Then Shuts Down ................................99
Problem 13 - No Battery Charge ...................100
Problem 14 - Unit Starts and Transfer Occurs
When Utility Power is Available ........101
Page 2
Page 5
Problem 15 - Generator Starts
Immediately in Auto - No Transfer to
Standby. Utility Voltage is Present .....101
Problem 16 - 15 Amp Fuse (F1) Blown ..........102
Problem 17 - Generator Will Not Exercise .....102
Problem 18 - No Low Speed Exercise ...........102
4.4 Diagnostic Tests ............................................ 103
Introduction .................................................. 103
Test 41 - Check Position Of
AUTO-OFF-MANUAL Switch ........... 103
Test 42 - Try A Manual Start ......................... 103
Test 43 - Test AUTO-OFF-MANUAL Switch . 103
Test 44 - Check Wire 15/15A/15B/239/0
Voltage ..............................................104
Test 45 - Check 15 Amp Fuse ........................105
Test 46 - Check Battery .................................105
Test 47 - Check Wire 56 Voltage ...................106
Test 48 - Test Starter Contactor Relay
(V-twin Only) ......................................106
Test 49 - Test Starter Contactor .....................106
Test 50 - Test Starter Motor ............................107
Test 51 - Check Fuel Supply
And Pressure.....................................109
Test 52 - Check Circuit Board
Wire 14 Output ..................................110
Test 53 - Check Fuel Solenoid .......................111
Test 54 - Check Choke Solenoid
(V-twins Units Only) ...........................112
Test 55 - Check For Ignition Spark .................113
Test 56 - Check Spark Plugs ..........................114
Test 57 - Check Engine / Cylinder Leak Down
Test / Compression Test114
Test 58 - Check Shutdown Wire .....................115
Test 59 - Check And Adjust
Ignition Magnetos ..............................116
Test 60 - Check Oil Pressure Switch
And Wire 86 .......................................117
Test 61 - Check High Oil
Temperature Switch ...........................118
Test 62 - Check And Adjust Valves ................119
Test 63 - Check Fuel Regulator
(7 Kw Natural Gas Units Only) ..........117
Test 64 - Check Battery Charge Output .........120
Test 65 - Check Transformer (TX)
Voltage Output ...................................118
Test 66 - Check AC Voltage At
Battery Charger .................................121
Test 67 - Check Battery Charge
Relay (BCR) ......................................122
Test 68 - Check Battery Charge
Winding Harness ...............................122
Test 69 - Check Battery Charger Wiring .......123
Test 70 - Check Wire 18 Continuity ................123
Test 71 - Check N1 And N2 Voltage ...............123
Test 72 - Check Utility Sensing Voltage
At The Circuit Board ..........................124
Test 73 - Test Set Exercise Switch .................124
Test 75 - Check Battery Voltage Circuit ..........124
Test 76 - Check Cranking And
Running Circuits ................................124
Test 77 - Test Exercise Function ....................126
Test 78 - Check Dip Switch Settings ..............126
Test 79 - Check Idle Control Transformer
(V-twin Units Only) .............................126
Test 80 - Check LC1 & LC2 Wiring ................126
Test 81 - Check Idle Control Transformer
Primary Wiring ...................................127
PART 5 - OPERATIONAL TESTS......................... 129
5.1 System Functional Tests ................................ 130
Introduction ....................................................130
Manual Transfer Switch Operation .................130
Electrical Checks ...........................................130
Generator Tests Under Load ..........................131
Checking Automatic Operation ......................132
Setting The Exercise Timer ............................132
PART 6 - DISASSEMBLY ..................................... 133
6.1 Major Disassembly ........................................ 134
Major Disassembly .........................................134
Front Engine Access. .....................................136
Torque Requirements
(Unless Otherwise Specified) ............136
PART 7 - ELECTRICAL DATA .............................. 137
Drawing 0F7820 Wiring Diagram, 7kWHSB
Models 005240 & 005280 ................................... 138
Drawing 0F7821 Wiring Schematic, 7kWHSB
Models 005240 & 005280 ................................... 140
Drawing 0F7822 Wiring Diagram, 10, 13 & 16 kW HSB Models 005241 & 005281 Models 005242 & 005282 Models 005243 & 005283
Models 005244 & 005284 ................................... 142
Drawing 0F7823 Schematic, 10, 13 & 16 kW HSB Models 005241 & 005281 Models 005242 & 005282 Models 005243 & 005283
Models 005244 & 005284 ................................... 144
Drawing 0F9070 Wiring Diagram, Transfer Switch
8 Circuit/16 Circuit ............................................... 146
Drawing 0F9775 Wiring Diagram, Schematic
8 Circuit/16 Circuit ............................................... 147
Page 3
Page 6
SPECIFICATIONS
GENERATOR
Model
005240 & 005280 005241 & 005281 005242 & 005282
Rated Max. Continuous Power Capacity (Watts*) 6,000 NG/7,000 LP 9,000 NG/10,000 LP 13,000 NG/13,000 LP 15,000 NG/16,000 LP
Rated Voltage 120/240 120/240 120/240 120/240
Rated Max. Continuous Load Current (Amps)
120 Volts** 50.0 NG/58.3 LP 75.0 NG/83.3 LP 108.3 NG/108.3 LP 125 NG/133.3 LP
240 Volts 25.0 NG/29.2 LP 37.5 NG/41.7 LP 54.1 NG/54.1 LP 52.5 NG/66.6 LP
Main Line Circuit Breaker 30 Amp 45 Amp 55 Amp 65 Amp
Circuits***
50A, 240V - - - 1
40A, 240V - - 1 1
30A, 240V 1 1 1 -
20A, 240V - 1 - 1
20A, 120V 1 3 3 5
15A, 120V 5 3 5 5
Phase 1 1 1 1
Number of Rotor Poles 2 2 2 2
Rated AC Frequency 60 Hz 60 Hz 60 Hz 60 Hz
Power Factor 1 1 1 1
Recommended Air Filter Part # 0C8127 Part # 0E9581 Part # 0C8127 Part # 0C8127
Battery Requirement Group 26
12 Volts and
350 Cold-cranking
Amperes Minimum
Group 26
12 Volts and
525 Cold-cranking
Amperes Minimum
Group 26
12 Volts and
525 Cold-cranking
Amperes Minimum
Battery Warming Blanket 0F6148DSRV
Weight (Unit Only) 336 Pounds 375 Pounds 425.5 Pounds 445 & 414 Pounds
Enclosure Steel/Aluminum
Normal Operating Range -20°F (-28.8°C) to 104°F (40°C)
005243 & 005283
005244 & 005284
Group 26
12 Volts and
525 Cold-cranking
Amperes Minimum
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.Maximum power
decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60° F) ambient temperature.
** Load current values shown for 120 volts are maximum TOTAL values for two separate circuits.The maximum current in each circuit must not exceed the value stated for 240 volts.
*** Circuits to be moved from main panel to transfer switch load center must be protected by same size breaker. For example, a 15 amp circuit in main panel must be a 15 amp circuit in
transfer switch.
STATOR WINDING RESISTANCE VALUES / ROTOR RESISTANCE
Power Winding: Across 11 & 22 0.223-0.259 ohms 0.144 ohms 0.115 ohms 0.080 ohms
Power Winding: Across 33 & 44 0.223-0.259 ohms 0.144 ohms 0.115 ohms 0.080 ohms
Excitation Winding: Across2&6 1.528-1.769 ohms 1.238 ohms 1.256 ohms 1.092 ohms
Battery Charge Winding: Across 66 & 77 0.146-0.169 ohms 0.158 ohms 0.164 ohms 0.130 ohms
Rotor Resistance 11.88-13.76 ohms 11.8 ohms 12.6 ohms 22.0 ohms
Page 4
005240, 005280
(6/7 kW)
005241, 005281
(9/10 kW)
005242, 005282
(13/13 kW)
005243, 005283 005244, 005284
(15/16 kW)
Page 7
ENGINE
SPECIFICATIONS
Model 005240 & 005280 005241 & 005281 005242 & 005282
005243 & 005283
005244 & 005284
Type of Engine GH-410 GT-530 GT-990 GT-990
Number of Cylinders 1 2 2 2
Rated Horsepower 14.5 @ 3,600 rpm 18 @ 3,600 rpm 30 @ 3,600 rpm 30 @ 3,600 rpm
Displacement 410cc 530cc 992cc 992cc
Cylinder Block
Aluminum w/Cast Iron
Sleeve
Aluminum w/Cast Iron
Sleeve
Aluminum w/Cast Iron
Sleeve
Aluminum w/Cast Iron
Sleeve
Valve Arrangement Overhead Valves Overhead Valves Overhead Valves Overhead Valves
Ignition System Solid-state w/Magneto Solid-state w/Magneto Solid-state w/Magneto Solid-state w/Magneto
Recommended Spark Plug RC14YC BPR6HS RC12YC RC12YC
Spark Plug Gap 0.76 mm (0.030 inch) 0.76 mm (0.030 inch) 1.02 mm (0.040 inch) 1.02 mm (0.040 inch)
Compression Ratio 8.6:1 9.5:1 9.5:1 9.5:1
Starter 12 VDC 12 VDC 12 VDC 12 VDC
Oil Capacity Including Filter Approx. 1.5 Qts Approx. 1.7 Qts Approx. 1.7 Qts Approx. 1.7 Qts
Recommended Oil Filter Part # 070185B Par t # 070185B Part # 070185B Part # 070185B
Recommended Air Filter Part # 0C8127 Part # 0E9581 Part # 0C8127 Part # 0C8127
Operating RPM 3,600 3,600 3,600 3,600
FUEL CONSUMPTION
Model # Natural Gas* LP Vapor**
1/2 Load Full Load 1/2 Load Full Load
005240, 005280 (6/7 kW) 66 119 0.82/30 1.47/54
005241, 005281 (9/10 kW) 102 156 1.25/46 1.93/70
005242, 005282 (13/13 kW) 156 220 1.55/57 2.18/80
005243, 005283 (15/16 kW) 005244, 005284 (15/16 kW)
* Natural gas is in cubic feet per hour.
**LP is in gallons per hour/cubic feet per hour.
Values given are approximate.
173 245 1.59/59 2.51/92
Page 5
Page 8
SPECIFICATIONS
MOUNTING DIMENSIONS
Page 6
Page 9
MOUNTING DIMENSIONS
SPECIFICATIONS
Page 7
Page 10
SPECIFICATIONS
MAJOR FEATURES
7 kW, Single Cylinder GH-410 Engine
Exhaust Enclosure
Composite Base
Oil Dipstick
Data Decal
Air Filter Cover
Battery CompartmentOil Filter
Control Panel
Fuel Inlet (Back)
Fuel Regulator
Exhaust Enclosure
Composite Base
10 kW, V-twin GT-530 Engine
Control
Oil Dipstick
Data Decal
Battery CompartmentOil Filter
Panel
Air Filter
Fuel Inlet (Back)
Fuel Regulator
13 kW and 16 kW, V-twin GT-990 Engine
Air Filter Cover
Oil Dipstick
Exhaust Enclosure
Composite Base
Data Decal
Control Panel
Fuel Inlet (Back)
Fuel Regulator
Battery CompartmentOil Filter
Page 8
Page 11
PART 1
GENERAL
INFORMATION
Air-cooled, Prepackaged
Automatic Standby Generators
TABLE OF CONTENTS
PART TITLE PAGE
1.1 Generator Identification 10
1.2 Prepackaged Installation
Basics
1.3 Preparation Before Use 14
1.4 Testing, Cleaning and Drying 16
1.5 Engine-Generator Protective
Devices
1.6 Operating Instructions 25
1.7 Automatic Operating
Parameters
11
23
28
1.1 Generator Identification
1.2 Prepackaged Installation Basics ..................... 11
Introduction ......................................................11
Selecting A Location ........................................11
Grounding The Generator ................................11
The Fuel Supply ...............................................11
The Transfer Switch / Load Center ...................11
Power Source And Load Lines .........................13
System Control Interconnections .....................13
1.3 Preparation Before Use ................................... 14
General ............................................................14
Fuel Requirements...........................................14
Fuel Consumption ............................................14
Reconfiguring The Fuel System .......................14
Engine Oil Recommendations .........................16
1.4 Testing, Cleaning and Drying........................... 16
Meters ............................................................17
The VOM ..........................................................17
Measuring AC Voltage .....................................17
Measuring DC Voltage .....................................17
Measuring AC Frequency ................................17
Measuring Current ...........................................18
Measuring Resistance .....................................18
Electrical Units .................................................19
Ohm's Law .......................................................19
................................... 10
Visual Inspection ..............................................20
Insulation Resistance .......................................20
The Megohmmeter...........................................20
Stator Insulation Resistance Test .....................21
Rotor Insulation Resistance Test ......................22
Cleaning The Generator...................................22
Drying The Generator ......................................22
1.5 Engine-Generator Protective Devices ............. 23
General ............................................................23
Low Battery ......................................................23
Low Oil Pressure Shutdown .............................23
High Temperature Switch .................................23
Overspeed Shutdown ......................................23
RPM Sensor Failure .........................................23
Overcrank Shutdown .......................................24
1.6 Operating Instructions ..................................... 25
Control Panel ...................................................25
To Select Automatic Operation ........................26
Manual Transfer To “Standby” And
Manual Startup ....................................26
Manual Shutdown And Retransfer
Back To “Utility” ....................................27
1.7 Automatic Operating Parameters .................... 28
Introduction ......................................................28
Automatic Operating Sequences .....................28
Page 9
Page 12
SECTION 1.1
GENERATOR IDENTIFICATION
INTRODUCTION
This Diagnostic Repair Manual has been prepared especially for the purpose of familiarizing service per­sonnel with the testing, troubleshooting and repair of air-cooled, prepackaged automatic standby genera­tors. Every effort has been expended to ensure that information and instructions in the manual are both accurate and current. However, Generac reserves the right to change, alter or otherwise improve the product at any time without prior notification.
The manual has been divided into seven PARTS. Each PART has been divided into SECTIONS. Each SECTION consists of two or more SUBSECTIONS.
It is not our intent to provide detailed disassembly and reassemble instructions in this manual. It is our intent to (a) provide the service technician with an under standing of how the various assemblies and systems work, (b) assist the technician in finding the cause of malfunctions, and (c) effect the expeditious repair of the equipment.
ITEM NUMBER: Many home standby generators are manufactured
to the unique specifications of the buyer. The Model Number identifies the specific generator set and its unique design specifications.
PART 1
Item #
Serial
Volts
Amps
Watts
-
1 PH, 60 HZ, RPM 3600
MAX OPERATING AMBIENT
FOR STANDBY SERVICE
0055555
1234567
120/240 AC
108.3/108.3
13000
CLASS F INSULATION
TEMP - 120F/49C
GENERAL INFORMATION
NEUTRAL FLOATING
MAX LOAD UNBALANCED - 50%
GENERAC POWER SYSTEMS
WAUKESHA, WI MADE IN U.S.A.
SERIAL NUMBER: Used for warranty tracking purposes.
Figure 1. A Typical Data Plate
Page 10
Page 13
GENERAL INFORMATION
PART 1
SECTION 1.2
PREPACKAGED INSTALLATION BASICS
INTRODUCTION
Information in this section is provided so that the ser­vice technician will have a basic knowledge of instal­lation requirements for prepackaged home standby systems. Problems that arise are often related to poor or unauthorized installation practices.
A typical prepackaged home standby electric system is shown in Figure 1 (next page). Installation of such a system includes the following:
• Selecting a Location
• Grounding the generator.
• Providing a fuel supply.
• Mounting the load center.
• Connecting power source and load lines.
• Connecting system control wiring.
• Post installation tests and adjustments.
SELECTING A LOCATION
Install the generator set as close as possible to the electrical load distribution panel(s) that will be pow­ered by the unit, ensuring that there is proper ventila­tion for cooling air and exhaust gases. This will reduce wiring and conduit lengths. Wiring and conduit not only add to the cost of the installation, but excessively long wiring runs can result in a voltage drop.
Control system interconnections non-prepackaged generator consist of N1 and N2, and leads 23 and
194. Control system interconnection leads must be run in a conduit that is separate from the AC power leads. Recommended wire gauge size depends on the length of the wire:
Max. Cable Length Recommended Wire Size
460 feet (140m) No. 18 AWG.
461 to 730 feet (223m) No. 16 AWG.
731 to 1,160 feet (354m) No. 14 AWG.
1,161 to 1850 feet (565m) No. 12 AWG.
GROUNDING THE GENERATOR
The National Electric Code requires that the frame and external electrically conductive parts of the gen­erator be property connected to an approved earth ground. Local electrical codes may also require prop­er grounding of the unit. For that purpose, a ground­ing lug is attached to the unit. Grounding may be accomplished by attaching a stranded copper wire of the proper size to the generator grounding lug and to an earth-driven copper or brass grounding-rod (elec­trode). Consult with a local electrician for grounding requirements in your area.
THE FUEL SUPPLY
Prepackaged units with air-cooled engines were oper­ated, tested and adjusted at the factory using natural gas as a fuel. These air-cooled engine units can be converted to use LP (propane) gas by making a few adjustments for best operation and power.
LP (propane) gas is usually supplied as a liquid in pressure tanks. Both the air-cooled and the liquid cooled units require a “vapor withdrawal” type of fuel supply system when LP (propane) gas is used. The vapor withdrawal system utilizes the gaseous fuel vapors that form at the top of the supply tank.
The pressure at which LP gas is delivered to the generator fuel solenoid valve may vary considerably, depending on ambient temperatures. In cold weather, supply pressures may drop to “zero”. In warm weath er, extremely high gas pressures may be encountered. A primary regulator is required to maintain correct gas supply pressures.
Current recommended gaseous fuel pressure at the inlet side of the generator fuel solenoid valve is as follows:
LP NG
Minimum water column 10 inches 5 inches
Maximum water column 12 inches 7 inches
A primary regulator is required to ensure that proper fuel supply pressures are maintained.
DANGER: LP AND NATURAL GAS ARE BOTH
Use of a flexible length of hose between the genera­tor fuel line connection and rigid fuel lines is required. This will help prevent line breakage that might be caused by vibration or if the generator shifts or settles. The flexible fuel line must be approved for use with gaseous fuels.
Flexible fuel line should be kept as straight as possi ble between connections. The bend radius for flexible fuel line is nine (9) inches. Exceeding the bend radius can cause the fittings to crack.
HIGHLY EXPLOSIVE. GASEOUS FUEL LINES MUST BE PROPERLY PURGED AND TESTED FOR LEAKS BEFORE THIS EQUIPMENT IS PLACED INTO SERVICE AND PERIODICALLY THEREAFTER. PROCEDURES USED IN GASEOUS FUEL LEAKAGETESTS MUST COMPLY STRICTLY WITH APPLICABLE FUEL GAS CODES. DO NOT USE FLAME OR ANY SOURCE OF HEAT TO TEST FOR GAS LEAKS. NO GAS LEAKAGE IS PERMITTED. LP GAS IS HEAVIER THAN AIR AND TENDS TO SETTLE IN LOW AREAS. NATURAL GAS IS LIGHTER THAN AIR AND TENDS TO SETTLE IN HIGH PLACES. EVEN THE SLIGHTEST SPARK CAN IGNITE THESE FUELS AND CAUSE AN EXPLOSION.
THE TRANSFER SWITCH / LOAD CENTER
A transfer switch is required by electrical code, to pre­vent electrical feedback between the utility and stand­by power sources, and to transfer electrical loads from one power supply to another safely.
PREPACKAGED TRANSFER SWITCHES: Instructions and information on prepackaged transfer
switches may be found in Part 3 of this manual.
Page 11
-
-
Page 14
SECTION 1.2
PREPACKAGED INSTALLATION BASICS
BAR
NEUTRAL
100A OR 200A
HOUSE MAIN
SERVICE
GROUND
PANEL BOARD
TRANSFER SWITCH)
GENERAC UL LISTED
(8, 10, 12 OR 16 CIRCUIT
PART 1
CONNECTION OF GENERATOR
TO EXTERNAL CONNECTION PANEL
GENERAL INFORMATION
TO HOUSE BRANCH
CIRCUITS SPLICED
USING WIRE NUTS
GROUND
CIRCUITS
EMERGENCY
STUD
NEUTRAL
40A OR 70A 2-POLE
CIRCUIT BREAKER
194N1 N2 23
2 POLE
EARTH
GENERATOR OUTPUT CIRCUIT BREAKER
SPIKE
CONNECTION BOX
4 PIN
EXTERNAL CUSTOMER
CONNECTOR
Page 12
Figure 1. Typical Prepackaged Installation
GENERATOR GROUND
(LOCATED ON THE REAR OF UNIT)
Page 15
GENERAL INFORMATION
PART 1
SECTION 1.2
PREPACKAGED INSTALLATION BASICS
POWER SOURCE AND LOAD LINES
The utility power supply lines, the standby (genera­tor) supply lines, and electrical load lines must all be connected to the proper terminal lugs in the transfer switch. The following rules apply: In 1-phase systems with a 2-pole transfer switch, connect the two utility source hot lines to Transfer Switch Terminal Lugs N1 and N2. Connect the standby source hot lines (E1, E2) to Transfer Switch Terminal Lugs E1 and E2. Connect the load lines from Transfer Switch Terminal Lugs T1 and T2 to the electrical load circuit. Connect UTILITY, STANDBY and LOAD neutral lines to the neutral block in the transfer switch.
SYSTEM CONTROL INTERCONNECTIONS
Prepackaged home standby generators are equipped with a terminal board identified with the following ter­minals: (a) UTILITY 1, (b) UTILITY 2, (c) 23, and (d)
194. Prepackaged load centers house an identically marked terminal board. When these four terminals are properly interconnected, dropout of utility source voltage below a preset value will result in automatic generator startup and transfer of electrical loads to the “Standby” source. On restoration of utility source voltage above a preset value will result in retransfer back to that source and generator shutdown.
5-7" WC REGULATOR TO HOUSEHOLD
GAS METER CAPABLE
OF PROVIDING FUEL
SAFETY
SHUT OFF
VALV E
0000001
Figure 2. Proper Fuel Installation
FLOW OF:
119,000 (6/7KW) 156,000 (9/10KW) 220,000 (13kW) 245,000 (15/16KW)
+HOUSEHOLD APPLIANCES
(BASED ON 1000 BTU/CU FT)
BTU/HOUR
}
GAS MAIN
2-5 PSI
Page 13
Page 16
SECTION 1.3
PREPARATION BEFORE USE
PART 1
GENERAL INFORMATION
GENERAL
The installer must ensure that the home standby gen­erator has been properly installed. The system must be inspected carefully following installation. All appli­cable codes, standards and regulations pertaining to such installations must be strictly complied with. In addition, regulations established by the Occupational Safety and Health Administration (OSHA) must be complied with.
Prior to initial startup of the unit, the installer must ensure that the engine-generator has been properly prepared for use. This includes the following:
• An adequate supply of the correct fuel must be available for generator operation.
• The engine must be properly serviced with the rec ommended oil.
FUEL REQUIREMENTS
With LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed above the liquid fuel in the storage tank.
The engine has been fitted with a fuel carburetion system that meets the specifications of the 1997 California Air Resources Board for tamper-proof dual fuel systems. The unit will run on natural gas or LP gas, but it has been factory set to run on natural gas. Should the primary fuel need to be changed to LP gas, the fuel system needs to be reconfigured. See the Reconfiguring the Fuel System section for instruc tions on reconfiguration of the fuel system.
Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is 5 inches to 7 inches water column (0.18 to 0.25 psi); and for liq uid propane, 10 inches to 12 inches of water column (0.36 to 0.43 psi).
NOTE: All pipe sizing, construction and layout must comply with NFPA 54 for natural gas applica tions and NFPA 58 for liquid propane applications. Once the generator is installed, verify that the fuel pressure NEVER drops below four (4) inches water column for natural gas or 10 inches water column for liquid propane.
Prior to installation of the generator, the installer should consult local fuel suppliers or the fire marshal to check codes and regulations for proper installation. Local codes will mandate correct routing of gaseous fuel line piping around gardens, shrubs and other landscaping to prevent any damage.
Special considerations should be given when install ing the unit where local conditions include flood­ing, tornados, hurricanes, earthquakes and unstable ground for the flexibility and strength of piping and their connections.
Use an approved pipe sealant or joint compound on all threaded fitting.
All installed gaseous fuel piping must be purged and leak tested prior to initial start-up in accordance with local codes, standards and regulations.
FUEL CONSUMPTION
The fuel consumption rates are listed in the SPECIFICATIONS section at the front of this manual.
BTU FLOW REQUIREMENTS - NATURAL GAS: BTU flow required for each unit based on 1000 BTU
per cubic foot. 6/7 kW — 119,000 BTU/Hour
9/10 kW — 156,000 BTU/Hour
-
13 kW — 220,000 BTU/Hour 15/16 kW — 245,000 BTU/Hour
DANGER
Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even
the slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is per­mitted. Natural gas, which is lighter than air, tends to collect in high areas. LP gas is heavi-
-
-
-
-
er than air and tends to settle in low areas.
NOTE: A minimum of one approved manual shut­off valve must be installed in the gaseous fuel supply line. The valve must be easily accessible. Local codes determine the proper location.
RECONFIGURING THE FUEL SYSTEM
7 KW, 410CC ENGINE: To reconfigure the fuel system from NG to LP, follow
these steps (Figure 1):
NOTE: The primary regulator for the propane sup ply is NOT INCLUDED with the generator. A fuel pressure of 10 to 12 inches of water column (0.36 to 0.43 psi) to the fuel inlet of the generator must be supplied.
1. Turn off the main gas supply (if connected).
2. Open the roof and remove the door.
3. Remove the battery (if installed).
4. Disconnect Wire 0 and Wire 14 from the gas solenoid on top of the demand regulator.
5. Remove the carburetor fuel hose from the outlet port of the demand regulator.
6. Remove the demand regulator by removing the fastener that retains the regulator mounting bracket.
-
Page 14
Page 17
GENERAL INFORMATION
FUEL SELECTION LEVER -
“IN” POSITION FOR NATURAL GAS
FUEL SELECTION LEVER -
“OUT” POSITION FOR LIQUID PROPANE (VAPOR) FUEL
PART 1
SECTION 1.3
PREPARATION BEFORE USE
7. Remove the square headed steel pipe plug from out­let port #1 and the brass hose barb fitting from outlet port #2.
8. Refit the brass hose barb fitting to outlet port #1 and the square headed steel pipe plug to outlet port #2.
PIPE
HOSE & PLUG SWITCHED SIDES
LP FUEL SYSTEM
PRESSURE TAP
FUEL HOSE
BRASS HOSE FITTING
OUTLET PORT
FUEL JET
FUEL HOSE
BRASS HOSE
FITTING
ADJUSTMENT
SCREW
PLUG
NG FUEL SYSTEM
12.Check for gas leakage at the pipe plug, hose connection and fittings.
10, 13 AND 16 KW, V-TWIN ENGINES: To reconfigure the fuel system from NG to LP, follow
these steps:
NOTE: The primary regulator for the propane sup ply is NOT INCLUDED with the generator. A fuel pressure of 10 to 12 inches of water column (0.36 to 0.43 psi) to the fuel inlet of the generator must be supplied.
-
3/4” HOLE
NOTE: Use an approved pipe sealant or joint com pound on all threaded fittings to reduce the pos­sibility of leakage.
9. Reverse procedure Steps 1-6 to reinstall demand regulator.
10.Take the plastic plug supplied in the poly-bag with the generator and press it into the 3/4” hole on the bottom of the air cleaner base (Figure 2).
11.Reverse the procedure to convert back to natural gas.
Figure 1. Demand Regulator
Figure 2. Demand Regulator
AIR CLEANER
Figure 3. 10 kW, GT-530 (Inlet Hose Slid Back)
-
Figure 4. 10 kW, GT-530 (Inlet Hose Slid Back)
1. Open the roof.
2. For 10 kW units: Loosen clamp and slide back the
air inlet hose.
• Slide fuel selector on carburetor out towards the back of the enclosure (Figures 3 and 4).
• Return the inlet hose and tighten clamp securely. For 13 and 16 kW units: remove the air cleaner
cover.
Page 15
Page 18
SECTION 1.3
PREPARATION BEFORE USE
PART 1
GENERAL INFORMATION
• Slide the selector lever out towards the back of the enclosure (Figures 5 and 6).
• Return the air cleaner cover and tighten the two thumb screws.
3. Close the roof.
4. Reverse the procedure to convert back to natural gas.
FUEL SELECTION LEVER -
“IN” POSITION FOR NATURAL GAS
Figure 5. 13/16 kW, GT-990 (Airbox Cover Removed)
ENGINE OIL RECOMMENDATIONS
The primary recommended oil for units with air­cooled, single cylinder or V-Twin engines is synthetic oil. Synthetic oil provides easier starts in cold weather and maximum engine protection in hot weather. Use high quality detergent oil that meets or exceeds API (American Petroleum Institute) Service class SG, SH, or SJ requirements for gasoline engines. The follow­ing chart lists recommended viscosity ranges for the lowest anticipated ambient temperatures.
Engine crankcase oil capacities for the engines cov ered in this manual can be found in the specifications section at the beginning of the book.
Lowest Anticipated Ambient Temperature
Above 60° F (16° C) Use SAE 30 oil
20° to 59° F (-7° to 15° C) Use SAE 10W-30 oil
Below 20° F (-7° C) SAE 5W-20/5W-30
For all seasons Use SAE 5W-30 Synthetic oil
Oil Grade (Recommended)
-
FUEL SELECTION LEVER -
“OUT” POSITION FOR LIQUID PROPANE (VAPOR) FUEL
Figure 6. 13/16 kW, GT-990 (Airbox Cover Removed)
Page 16
Page 19
GENERAL INFORMATION
PART 1
SECTION 1.4
TESTING, CLEANING AND DRYING
METERS
Devices used to measure electrical properties are called meters. Meters are available that allow one to measure (a) AC voltage, (b) DC voltage, (c) AC frequency, and (d) resistance In ohms. The following apply:
• To measure AC voltage, use an AC voltmeter.
• To measure DC voltage, use a DC voltmeter.
• Use a frequency meter to measure AC frequency In “Hertz” or “cycles per second”.
• Use an ohmmeter to read circuit resistance, in “ohms”.
THE VOM
A meter that will permit both voltage and resistance to be read is the “volt-ohm-milliammeter” or “VOM”.
Some VOMs are of the “analog” type (not shown). These meters display the value being measured by physically deflecting a needle across a graduated scale. The scale used must be Interpreted by the user.
“Digital” VOM's (Figure 1) are also available and are generally very accurate. Digital meters display the measured values directly by converting the values to numbers.
NOTE: Standard AC voltmeters react to the AVERAGE value of alternating current. When working with AC, the effective value is used. For that reason a different scale is used on an AC voltmeter. The scale is marked with the effective or “rms” value even though the meter actually reacts to the average value. That is why the AC voltmeter will give an Incorrect reading if used to measure direct current (DC).
MEASURING AC VOLTAGE
An accurate AC voltmeter or a VOM may be used to read the generator's AC output voltage. The following apply:
1. Always read the generator's AC output voltage only at the unit's rated operating speed and AC frequency.
2. The generator's Voltage Regulator can be adjusted for correct output voltage only while the unit is operating at its correct rated speed and frequency.
3. Only an AC voltmeter may be used to measure AC voltage. DO NOT USE A DC VOLTMETER FOR THIS PURPOSE.
DANGER!: GENERATORS PRODUCE HIGH
AND DANGEROUS VOLTAGES. CONTACT WITH HIGH VOLTAGE TERMINALS WILL RESULT IN DANGEROUS AND POSSIBLY LETHAL ELECTRICAL SHOCK.
MEASURING DC VOLTAGE
A DC voltmeter or a VOM may be used to measure DC voltages. Always observe the following rules:
1. Always observe correct DC polarity.
a. Some VOM's may be equipped with a polar-
ity switch.
b. On meters that do not have a polarity switch,
DC polarity must be reversed by reversing the test leads.
2. Before reading a DC voltage, always set the meter to a higher voltage scale than the anticipated reading. If in doubt, start at the highest scale and adjust the scale downward until correct readings are obtained.
Figure 1. Digital VOM
3. The design of some meters is based on the “current flow” theory while others are based on the “electron flow” theory.
a. The “current flow” theory assumes that
direct current flows from the positive (+) to the negative (-).
b. The “electron flow” theory assumes that cur-
rent flows from negative (-) to positive (+).
NOTE: When testing generators, the “current flow” theory is applied. That is, current is assumed to flow from positive (+) to negative (-).
MEASURING AC FREQUENCY
The generator's AC output frequency is proportional to Rotor speed. Generators equipped with a 2-pole Rotor must operate at 3600 rpm to supply a frequency of 60 Hertz. Units with 4-pole Rotor must run at 1800 rpm to deliver 60 Hertz.
Page 17
Page 20
SECTION 1.4
TESTING, CLEANING AND DRYING
PART 1
GENERAL INFORMATION
Correct engine and Rotor speed is maintained by an engine speed governor. For models rated 60 Hertz, the governor is generally set to maintain a no-load fre­quency of about 62 Hertz with a corresponding output voltage of about 124 volts AC line-to-neutral. Engine speed and frequency at no-load are set slightly high to prevent excessive rpm and frequency droop under heavy electrical loading.
MEASURING CURRENT
CLAMP-ON: To read the current flow, in AMPERES, a clamp-on
ammeter may be used. This type of meter indicates current flow through a conductor by measuring the strength of the magnetic field around that conductor. The meter consists essentially of a current trans­former with a split core and a rectifier type instrument connected to the secondary. The primary of the cur­rent transformer is the conductor through which the current to be measured flows. The split core allows the Instrument to be clamped around the conductor without disconnecting it.
Current flowing through a conductor may be mea sured safely and easily. A line-splitter can be used to measure current in a cord without separating the conductors.
NOTE: If the physical size of the conductor or ammeter capacity does not permit all lines to be measured simultaneously, measure current flow in each individual line. Then, add the Individual readings.
IN-LINE: Alternatively, to read the current flow in AMPERES,
an in-line ammeter may be used. Most Digital Volt Ohm Meters (VOM) will have the capability to mea­sure amperes.
This usually requires the positive meter test lead to be connected to the correct amperes plug, and the meter to be set to the amperes position. Once the meter is properly set up to measure amperes the circuit being measured must be physically broken. The meter will be in-line or in series with the component being mea sured.
In Figure 4 the control wire to a relay has been removed. The meter is used to connect and supply voltage to the relay to energize it and measure the amperes going to it.
-
1.00 A
-
Figure 2. Clamp-On Ammeter
BATTERY
+-
Figure 4. A VOM as an In-line meter
RELAY
MEASURING RESISTANCE
The volt-ohm-milliammeter may be used to measure the resistance in a circuit. Resistance values can be very valuable when testing coils or windings, such as the Stator and Rotor windings.
When testing Stator windings, keep in mind that the resistance of these windings is very low. Some meters are not capable of reading such a low resistance and will simply read CONTINUITY.
If proper procedures are used, the following condi tions can be detected using a VOM:
• A “short-to-ground” condition in any Stator or Rotor winding.
• Shorting together of any two parallel Stator wind ings.
• Shorting together of any two isolated Stator wind ings.
• An open condition in any Stator or Rotor winding.
-
-
-
Figure 3. A Line-Splitter
Page 18
Page 21
GENERAL INFORMATION
PART 1
SECTION 1.4
TESTING, CLEANING AND DRYING
Component testing may require a specific resis­tance value or a test for INFINITY or CONTINUITY. Infinity is an OPEN condition between two electrical points, which would read as no resistance on a VOM. Continuity is a closed condition between two electrical points, which would be indicated as very low resis­tance or “ZERO” on a VOM.
ELECTRICAL UNITS
AMPERE: The rate of electron flow in a circuit is represented
by the AMPERE. The ampere is the number of elec­trons flowing past a given point at a given time. One AMPERE is equal to just slightly more than six thou­sand million billion electrons per second.
With alternating current (AC), the electrons flow first in one direction, then reverse and move in the oppo site direction. They will repeat this cycle at regular intervals. A wave diagram, called a “sine wave” shows that current goes from zero to maximum positive value, then reverses and goes from zero to maximum negative value. Two reversals of current flow is called a cycle. The number of cycles per second is called frequency and is usually stated in “Hertz”.
VOLT: The VOLT is the unit used to measure electrical
PRESSURE, or the difference in electrical potential that causes electrons to flow. Very few electrons will flow when voltage is weak. More electrons will flow as voltage becomes stronger. VOLTAGE may be consid­ered to be a state of unbalance and current flow as an attempt to regain balance. One volt is the amount of EMF that will cause a current of 1 ampere to flow through 1 ohm of resistance.
OHM: The OHM is the unit of RESISTANCE. In every circuit
there is a natural resistance or opposition to the flow of electrons. When an EMF is applied to a complete circuit, the electrons are forced to flow in a single direction rather than their free or orbiting pattern. The resistance of a conductor depends on (a) its physical makeup, (b) its cross-sectional area, (c) its length, and (d) its temperature. As the conductor's tempera­ture increases, its resistance increases in direct pro­portion. One (1) ohm of resistance will permit one (1) ampere of current to flow when one (1) volt of electro­motive force (EMF) is applied.
OHM'S LAW
A definite and exact relationship exists between VOLTS, OHMS and AMPERES. The value of one can be calculated when the value of the other two are
-
known. Ohm's Law states that in any circuit the current will increase when voltage increases but resistance remains the same, and current will decrease when resistance Increases and voltage remains the same.
VOLTS
(E)
AMPS
(I)
OHMS
(R)
Conductor of a Circuit
OHM - Unit measuring resistance
-
AMPERE - Unit measuring rate of
Figure 5. Electrical Units
current flow (number of electrons past a given point)
VOLT - Unit measuring force or
difference in potential causing current flow
or opposition to flow
+
Figure 6. Ohm's Law
If AMPERES is unknown while VOLTS and OHMS are known, use the following formula:
=
AMPERES
VOLTS
OHMS
VOLTS
Page 19
AMPERES =
If VOLTS is unknown while AMPERES and OHMS are known, use the following formula:
VOLTS = AMPERES x OHMS
If OHMS is unknown but VOLTS and AMPERES are known, use the following:
OHMS
Page 22
SECTION 1.4
TESTING, CLEANING AND DRYING
PART 1
GENERAL INFORMATION
VISUAL INSPECTION
When it becomes necessary to test or troubleshoot a generator, it is a good practice to complete a thorough visual inspection. Remove the access covers and look closely for any obvious problems. Look for the follow­ing:
• Burned or broken wires, broken wire connectors,
MINIMUM INSULATION RESISTANCE = (in “Megohms”)
damaged mounting brackets, etc.
• Loose or frayed wiring insulation, loose or dirty con nections.
• Check that all wiring is well clear of rotating parts.
• Verify that the Generator properly connected for the correct rated voltage. This is especially important on new installations. See Section 1.2, “AC Connection Systems”.
• Look for foreign objects, loose nuts, bolts and other fasteners.
• Clean the area around the Generator. Clear away paper, leaves, snow, and other objects that might blow against the generator and obstruct its air openings.
GENERATOR RATED VOLTS
__________________________
1000
+1
INSULATION RESISTANCE
Use a megger power setting of 500 volts. Connect one megger test lead to the junction of all stator leads, the other test lead to frame ground on the sta­tor can. Read the number of megohms on the meter.
The MINIMUM acceptable megger reading for stators may be calculated using the following formula:
EXAMPLE: Generator is rated at 120 volts AC. Divide “120” by “1000” to obtain “0.12”. Then add “1” to obtain “1.12” megohms. Minimum Insulation resistance for a 120 VAC stator is 1.12 megohms.
If the stator insulation resistance is less than the cal culated minimum resistance, clean and dry the stator. Then, repeat the test. If resistance is still low, replace the stator.
­Use the Megger to test for shorts between isolated windings as outlined “Stator Insulation Tests”.
Also test between parallel windings. See “Test Between Windings” on next page.
TESTING ROTOR INSULATION: Apply a voltage of 500 volts across the rotor posi-
tive (+) slip ring (nearest the rotor bearing), and a clean frame ground (i.e. the rotor shaft). DO NOT EXCEED 500 VOLTS AND DO NOT APPLY VOLTAGE LONGER THAN 1 SECOND. FOLLOW THE MEGGER MANUFACTURER’S INSTRUCTIONS CAREFULLY.
ROTOR MINIMUM INSULATION RESISTANCE:
1.5 megohms
-
The insulation resistance of stator and rotor windings is a measurement of the integrity of the insulating materials that separate the electrical windings from the generator steel core. This resistance can degrade over time or due to such contaminants as dust, dirt, oil, grease and especially moisture. In most cases, failures of stator and rotor windings is due to a break­down in the insulation. And, in many cases, a low insu­lation resistance is caused by moisture that collects while the generator is shut down. When problems are caused by moisture buildup on the windings, they can usually be corrected by drying the windings. Cleaning and drying the windings can usually eliminate dirt and moisture built up in the generator windings.
THE MEGOHMMETER
GENERAL: A megohmmeter, often called a “megger”, consists of
a meter calibrated in megohms and a power supply. Use a power supply of 500 volts when testing stators or rotors. DO NOT APPLY VOLTAGE LONGER THAN ONE (1) SECOND.
TESTING STATOR INSULATION: All parts that might be damaged by the high meg-
ger voltages must be disconnected before testing. Isolate all stator leads (Figure 8) and connect all of the stator leads together. FOLLOW THE MEGGER MANUFACTURER’S INSTRUCTIONS CAREFULLY.
Page 20
CAUTION: Before attempting to measure
HI-POT TESTER: A “Hi-Pot” tester is shown in Figure 7. The model
shown is only one of many that are commercially available. The tester shown is equipped with a voltage
Insulation resistance, first disconnect and Isolate all leads of the winding to be tested. Electronic components, diodes, surge protec­tors, relays, voltage regulators, etc., can be destroyed if subjected to high megger volt­ages.
Figure 7. One Type of Hi-Pot Tester
Page 23
GENERAL INFORMATION
PART 1
SECTION 1.4
TESTING, CLEANING AND DRYING
selector switch that permits the power supply voltage to be selected. It also mounts a breakdown lamp that will illuminate to indicate an insulation breakdown dur­ing the test.
STATOR INSULATION RESISTANCE TEST
GENERAL: Units with air-cooled engines are equipped with (a)
dual stator AC power windings, (b) an excitation or DPE winding, and (c) a battery charge winding. Insulation tests of the stator consist of (a) testing all windings to ground, (b) testing between isolated wind­ings, and (c) testing between parallel windings. Figure 8 is a pictorial representation of the various stator leads on units with air-cooled engine.
TESTING ALL STATOR WINDINGS TO GROUND:
1. Disconnect stator output leads 11 and 44 from the gen­erator main line circuit breaker.
2. Remove stator output leads 22 and 33 from the neutral connection and separate the two leads.
3. Disconnect C2 Connector from the side of the control panel. The C2 Connector is the closest to the back panel (see Figure 9, Section 6.1).
c.Turn the tester switch ON and observe the
breakdown lamp on tester. DO NOT APPLY VOLTAGE LONGER THAN 1 SECOND. After one (1) second, turn the tester switch OFF.
If the breakdown lamp comes on during the one-sec ond test, the stator should be cleaned and dried. After cleaning and drying, repeat the insulation test. If, after cleaning and drying, the stator fails the second test, the stator assembly should be replaced.
6. Now proceed to the C2 Connector. Each winding will be individually tested for a short to ground. Insert a large paper clip (or similar item) into the C2 Connector at the following pin locations:
Pin
Location
1 77 Battery Charge
2 66 Battery Charge
3 22 Sense Lead Power
4 11 Sense Lead Power
5 6 Excitation
6 2 Excitation
7 0 Ground
8 4 Positive to Brush
Wire
Number
Winding
-
2
6
11P
11S
22P
22S
33
44
66
77
Figure 8. Stator Winding Leads
4. Connect the terminal ends of Wires 11, 22, 33 and 44 together. Make sure the wire ends are not touching any part of the generator frame or any terminal.
5. Connect the red test probe of the Hi-Pot tester to the joined terminal ends of stator leads 11, 22, 33 and 44. Connect the black tester lead to a clean frame ground on the stator can. With tester leads connected in this manner, proceed as follows:
a.Turn the Hi-Pot tester switch OFF. b.Plug the tester cord into a 120 volt AC wall
socket and set its voltage selector switch to “1500 volts”.
Next refer to Steps 5a through 5c of the Hi-Pot proce­dure.
Example: Insert paper clip into Pin 1, Hi-Pot from Pin 1 (Wire 77) to ground. Proceed to Pin 2, Pin 3, etc. through Pin 8.
5
6
7
8
Figure 9. C2 Connector Pin Location Numbers
(Female Side)
TEST BETWEEN WINDINGS:
1 2
3
4
1. Insert a large paper clip into Pin Location 1 (Wire 77). Connect the red tester probe to the paper clip. Connect the black tester probe to Stator Lead 11. Refer to Steps 5a through 5c of “TESTING ALL STATOR WINDINGS TO GROUND” on previous page.
2. Repeat Step 1 at Pin Location 5 (Wire 6) and Stator Lead 11.
3. Connect the red test probe to Stator Lead 33. Connect the black test probe to Stator Lead 11. Refer to Steps 5a through 5c of “TESTING ALL STATOR WINDINGS TO GROUND” on previous page.
Page 21
Page 24
SECTION 1.4
TESTING, CLEANING AND DRYING
4. Insert a large paper clip into Pin Location No. 1 (Wire
77). Connect the red tester probe to the paper clip. Connect the black tester probe to Stator Lead 33. Refer to Steps 5a through 5c of “TESTING ALL STATOR WINDINGS TO GROUND” on the previous page.
5. Repeat Step 4 at Pin Location 3 (Wire 6) and Stator Lead 33.
For the following Step (7) an additional large paper clip (or similar item) will be needed:
7. Insert a large paper clip into Pin Location 1 (Wire 77). Connect the red tester probe to the paper clip. Insert the additional large paper clip into Pin Location 5 (Wire 6). Connect the black tester probe to this paper clip. Refer to Steps 5a through 5c of “TESTING ALL STATOR WINDINGS TO GROUND” on the previous page.
PART 1
POSITIVE (+) TEST LEAD
Figure 10. Testing Rotor Insulation
GENERAL INFORMATION
ROTOR INSULATION RESISTANCE TEST
Before attempting to test rotor insulation, the brush holder must be completely removed. The rotor must be completely isolated from other components before starting the test. Attach all leads of all stator windings to ground.
1. Connect the red tester lead to the positive (+) slip ring (nearest the rotor bearing).
2. Connect the black tester probe to a clean frame ground, such as a clean metal part of the rotor shaft.
3. Turn the tester switch OFF.
4. Plug the tester into a 120 volts AC wall socket and set the voltage switch to “1500 volts”.
5. Turn the tester switch “On” and make sure the pilot light has turned on.
6. Observe the breakdown lamp, then turn the tester switch OFF. DO NOT APPLY VOLTAGE LONGER THAN ONE (1) SECOND.
If the breakdown lamp came on during the one (1) second test, cleaning and drying of the rotor may be necessary. After cleaning and drying, repeat the insu­lation breakdown test. If breakdown lamp comes on during the second test, replace the rotor assembly.
CLEANING THE GENERATOR
Caked or greasy dirt may be loosened with a soft brush or a damp cloth. A vacuum system may be used to clean up loosened dirt. Dust and dirt may also be removed using dry, low-pressure air (25 psi maximum).
CAUTION: Do not use sprayed water to clean
the generator. Some of the water will be
retained on generator windings and terminals, and may cause very serious problems.
DRYING THE GENERATOR
To dry a generator, proceed as follows:
1. Open the generator main circuit breaker. NO ELECTRICAL LOADS MUST BE APPLIED TO THE GENERATOR WHILE DRYING.
2. Disconnect all Wires 4 from the voltage regulator.
3. Provide an external source to blow warm, dry air through the generator interior (around the rotor and stator wind­ings. DO NOT EXCEED 185° F. (85° C.).
4. Start the generator and let it run for 2 or 3 hours.
5. Shut the generator down and repeat the stator and rotor insulation resistance tests.
Page 22
Page 25
GENERAL INFORMATION
LOW OIL SWITCH HIGH TEMP SWITCH
PART 1
SECTION 1.5
ENGINE-GENERATOR PROTECTIVE DEVICES
GENERAL
Standby electric power generators will often run unattended for long periods of time. Such operating parameters as (a) battery voltage, (b) engine oil pres­sure, (c) engine temperature, (d) engine operating speed, and (e) engine cranking and startup are not monitored by an operator during automatic operation. Because engine operation will not be monitored, the use of engine protective safety devices is required to prevent engine damage in the event of a problem.
Prepackaged generator engines mount several engine protective devices. These devices work in conjunction with a circuit board, to protect the engine against such operating faults as (a) low battery, (b) low engine oil pressure, (c) high temperature, (d) overspeed, and (e) overcrank. On occurrence of any one or more of those operating faults, circuit board action will effect an engine shutdown.
LOW BATTERY
The microprocessor will continually monitor the bat­tery voltage and turn on the Low Battery LED if the battery voltage falls below 11.0 volts for one (1) min­ute. No other action is taken on a low battery condi­tion. Low battery voltage is a non-latching alarm which will automatically clear if the battery voltage rises above 11.0 volts. Battery voltage is NOT moni­tored during the crank cycle.
OVERSPEED SHUTDOWN
During engine cranking and operation, the circuit board receives AC voltage and frequency signals from the ignition magneto, via Wire 18. Should the speed exceed approximately 72 Hz (4320 rpm), circuit board action will de-energize a “run relay” (mounted on the circuit board). The relay’s contacts will open, to termi­nate engine ignition and close a fuel shutoff solenoid. The engine will then shut down. This feature protects the engine-generator against damaging overspeeds.
NOTE: The circuit board also uses rpm sensing to terminate engine cranking.
RPM SENSOR FAILURE
During cranking, if the board does not see a valid RPM signal within three (3) seconds, it will shut down and latch out on RPM sensor loss.
During running, if the RPM signal is lost for one full second the board will shut down the engine, wait 15 seconds, then re-crank the engine.
• If an RPM signal is not detected within the first three (3) seconds of cranking, the control board will shut the engine down and latch out on RPM sensor loss.
• If the RPM signal is detected the engine will start and run normally. If the RPM signal is subsequently lost again, the control board will try one more re­crank attempt before latching out and flashing the overspeed LED.
LOW OIL PRESSURE SHUTDOWN
See Figure 1. An oil pressure switch is mounted on the engine oil filter adapter. This switch has normally closed contacts that are held open by engine oil pres­sure during cranking and startup. Should oil pressure drop below approximately 8 psi, the switch contacts will close. On closure of the switch contacts, a Wire 86 circuit from the circuit board will be connected to ground. Circuit board action will then de-energize a “run relay” (on the circuit board). The run relay’s nor­mally open contacts will then open and a 12 volts DC power supply to a Wire 14 circuit will then be terminat­ed. This will result in closure of a fuel shutoff solenoid and loss of engine ignition.
HIGH TEMPERATURE SWITCH
This switch’s contacts (Figure 1) close if the tempera­ture should exceed approximately 140° C (284° F), initiating an engine shutdown. The generator will auto­matically restart and the LED on the generator control panel will reset once the temperature has returned to a safe operating level.
Figure 1. Engine Protective Switches on an
Air-Cooled Engine
Page 23
Page 26
SECTION 1.5
ENGINE-GENERATOR PROTECTIVE DEVICES
OVERCRANK SHUTDOWN
This feature prevents the generator from damaging itself when it continually attempts to start and another problem, such as no fuel supply, prevents it from start­ing. The unit will crank and rest for a preset time limit. Then, it will stop cranking, and the LED on the gen­erator control panel will light indicating an overcrank failure. The AUTO/OFF/MANUAL switch will need to be set to OFF and then back to AUTO to reset the generator control board.
NOTE: If the fault is not repaired, the overcrank feature will continue to activate.
APPROXIMATE CRANK CYCLE TIMES:
7 KW UNITS: 15 seconds ON
7 seconds OFF 7 seconds ON 7 seconds OFF 7 seconds ON 7 seconds OFF 7 seconds ON 7 seconds OFF 7 seconds ON 7 seconds OFF 7 seconds ON
If the unit fails to start, the overcrank alarm LED will be illuminated.
PART 1
GENERAL INFORMATION
10 KW, 13 KW AND 16 KW UNITS: 16 seconds ON
7 seconds OFF 16 seconds ON 7 seconds OFF 7 seconds ON 7 seconds OFF 7 seconds ON 7 seconds OFF 7 seconds ON 7 seconds OFF
If the unit fails to start, the overcrank alarm LED will be illuminated.
Page 24
Page 27
GENERAL INFORMATION
PART 1
SECTION 1.6
OPERATING INSTRUCTIONS
CONTROL PANEL
GENERAL: See Figure 1 for control panel configurations.
CONTROL AND INFORMATION CENTER
SYSTEM SET
LOW BATTERY
OFF
AUTO. MAN.
SYSTEM FUSE
15A
ASSY: 0F8418/0F8419
SET
EXERCISE
TIME
Figure 1. Control Panel
AUTO-OFF-MANUAL SWITCH: Use this switch to (a) select fully automatic operation,
(b) to crank and start the engine manually, and (c) to shut the unit down or to prevent automatic startup.
1. AUTO position:
a.Select AUTO for fully automatic operation. b.When AUTO is selected, circuit board will moni-
tor utility power source voltage.
c. Should utility voltage drop below a preset level
and remain at such a low level for a preset time, circuit board action will initiate engine cranking and startup.
d.Following engine startup, circuit board action
will initiate transfer of electrical loads to the “Standby” source side.
e.On restoration of utility source voltage above
a preset level, circuit board action will initiate retransfer back to the “Utility Source” side.
f. Following retransfer, circuit board will shut the
engine down and will then continue to monitor utility source voltage.
2. OFF Position:
a.Set the switch to OFF to stop an operating
engine.
b.To prevent an automatic startup from occurring,
set the switch to OFF.
3. MANUAL Position:
a.Set switch to MANUAL to crank and start unit
manually.
b.Engine will crank cyclically and start (same as
automatic startup, but without transfer). The unit will transfer if utility voltage is not available.
DANGER: WHEN THE GENERATOR IS
INSTALLED IN CONJUNCTION WITH AN
AUTOMATIC TRANSFER SWITCH, ENGINE CRANKING AND STARTUP CAN OCCUR AT
LOW OIL
HIGH TEMP
OVER SPEED NO RPM SENSE IF FLASHING
OVER CRANK
FLASHING GREEN LED= NO UTILITY SENSE 5 FLASHING RED LEDS= EXERCISER NOT SET
ANY TIME WITHOUT WARNING (PROVIDING THE AUTO-OFF-MANUAL SWITCH IS SET TO AUTO). TO PREVENT AUTOMATIC STARTUP AND POSSIBLE INJURY THAT MIGHT BE CAUSED BY SUCH STARTUP, ALWAYS SET THE AUTO-OFF-MANUAL SWITCH TO ITS OFF POSITION BEFORE WORKING ON OR AROUND THIS EQUIPMENT.
15 AMP FUSE: This fuse protects the DC control circuit (including the
circuit board) against overload. If the fuse element has melted open due to an overload, engine cranking or running will not be possible. Should fuse replace­ment become necessary, use only an identical 15 amp replacement fuse.
THE SET EXERCISE SWITCH: This generator is equipped with an exercise timer.
Once it is set, the generator will start and exercise once every seven days, on the day of the week and at the time of day the following sequence is completed. During this exercise period, the unit runs for approxi­mately 12 minutes and then shuts down. Transfer of loads to the generator output does not occur during the exercise cycle unless utility power is lost.
A switch on the control panel (see Figure 1) per mits selection of the day and time for the system to exercise. At the chosen time, perform the following sequence to select the desired day and time of day the system will exercise. Remember seasonal time changes affect the exercise time settings.
1. Verify that the AUTO/OFF/MANUAL switch is set to
AUTO.
2. Press and hold the "Set Exercise Time" switch for sev-
eral seconds, then release. All the red LED's will flash for approximately 10 seconds and then stop.
3. Once the red LED's stop flashing, the generator will start
and run for approximately 12 minutes and then shut down. The exerciser is now set to run at this time of day each week.
Example: If the "Set Exercise Time" switch is pressed
on Saturday afternoon at 2:00 p.m., the generator will start and exercise for approximately 12 minutes every Saturday at 2:00 p.m..
NOTE: The exerciser will only work in the AUTO mode and will not work unless this procedure is performed. The exerciser will need to be reset every time the 12 volt battery is disconnected and then reconnected, and when the 15A fuse is removed.
The 16 kW unit has a low speed exercise option. Dip switch 1 on the control board is factory set to OFF. This allows the engine to run at a slower speed during weekly exercise periods for quieter operation. If this Dip switch is set to ON, the generator will exercise at it's normal speed.
-
Page 25
Page 28
SECTION 1.6
OPERATING INSTRUCTIONS
PART 1
GENERAL INFORMATION
This DIP switch position is only read at board power up. If the DIP switch position is changed, power to the board must be cycled for the micro controller to recog­nize the new DIP switch position.
Low speed exercise will be handled as follows:
1. The standard start sequence will be initiated.
2. The unit will run at 2,400 RPM.
3. If utility is lost during exercise, the controller will do the following:
• Wait 10 seconds for utility to return.
• If utility returns within 10 seconds, continue to exer
cise at 2,400 RPM.
• If utility is still lost after 10 seconds, run the engine
up to 3600 RPM and transfer the load. At this time the controller will exit the exercise routine and assume full automatic operation.
PROTECTION SYSTEMS: Unlike an automobile engine, the generator may have
to run for long periods of time with no operator pres­ent to monitor engine conditions. For that reason, the engine is equipped with the following systems that protect it against potentially damaging conditions:
• Low Battery
• Low Oil Pressure Sensor
• High Temperature Sensor
• Overcrank
• Overspeed
• No RPM Sense
There are LED readouts on the control panel to notify you that one of these faults has occurred. There is also a “System Set” LED that is lit when all of the fol lowing conditions are true:
1. The AUTO-OFF-MANUAL switch is set to the AUTO position.
2. The NOT IN AUTO dip switch is set to the OFF position on the control board.
3. No alarms are present.
To select automatic operation when a prepackaged transfer switch is installed along with a prepackaged home standby generator, proceed as follows:
1. Check that the prepackaged transfer switch main con­tacts are at their UTILITY position, i.e., the load is connected to the power supply. If necessary, manu­ally actuate the switch main contacts to their UTILITY source side. See Part 5 of this manual, as appropriate, for instructions.
2. Check that utility source voltage is available to transfer
-
switch terminal lugs N1 and N2 (2-pole, 1-phase trans­fer switches).
3. Set the generator AUTO-OFF-MANUAL switch to its AUTO position.
4. Actuate the generator main line circuit breaker to its “On” or “Closed” position. With the preceding Steps 1 through 4 completed, a dropout in utility supply voltage below a preset level will result in automatic generator cranking and start-up. Following startup, the prepackaged transfer switch will be actuated to its “Standby” source side, i.e., loads powered by the standby generator.
MANUAL TRANSFER TO “STANDBY” AND
MANUAL STARTUP
To transfer electrical loads to the “Standby” (genera­tor) source and start the generator manually, proceed as follows:
1. On the generator panel, set the AUTO-OFF-MANUAL
-
switch to OFF.
2. On the generator, set the main line circuit breaker to it’s OFF or “Open” position.
3. Turn OFF the power supply to the transfer switch, using whatever means provided (such as a utility source line circuit breaker).
TO SELECT AUTOMATIC OPERATION
The following procedure applies only to those installa­tions in which the air-cooled, prepackaged automatic standby generator is installed in conjunction with a prepackaged transfer switch. Prepackaged transfer switches do not have an intelligence circuit of their own. Automatic operation on prepackaged transfer switch and generator combinations is controlled by circuit board action.
Page 26
4. Manually actuate the transfer switch main contacts to their “Standby” position, i.e., loads connected to the “Standby” power source side.
NOTE: For instructions on manual operation of prepackaged transfer switches, see Part 5.
5. On the generator panel, set the AUTO-OFF-MANUAL switch to MANUAL. The engine should crank and start.
6. Let the engine warm up and stabilize for a minute or two at no-load.
7. Set the generator main line circuit breaker to its “On” or “Closed” position. The generator now powers the electri­cal loads.
Page 29
GENERAL INFORMATION
PART 1
MANUAL SHUTDOWN AND RETRANSFER
BACK TO “UTILITY”
To shut the generator down and retransfer electrical loads back to the UTILITY position, proceed as fol­lows:
1. Set the generator main line circuit breaker to its OFF or “Open” position.
2. Let the generator run at no-load for a few minutes, to cool.
3. Set the generator AUTO-OFF-MANUAL switch to OFF. Wait for the engine to come to a complete stop.
4. Turn off the utility power supply to the transfer switch using whatever means provided (such as a utility source main line circuit breaker)
5. Manually actuate the prepackaged transfer switch to its UTILITY source side, i.e., load connected to the utility source.
6. Turn on the utility power supply to the transfer switch, using whatever means provided.
SECTION 1.6
OPERATING INSTRUCTIONS
7. Set the generator AUTO-OFF-MANUAL switch to AUTO.
Page 27
Page 30
SECTION 1.7
AUTOMATIC OPERATING PARAMETERS
PART 1
GENERAL INFORMATION
INTRODUCTION
When the prepackaged generator is installed in conjunction with a prepackaged transfer switch, either manual or automatic operation is possible. Manual transfer and engine startup, as well as manual shutdown and retransfer are covered in Section 1.6. Selection of fully automatic operation is also discussed in that section. This section will provide a step-by-step description of the sequence of events that will occur during automatic operation of the system.
AUTOMATIC OPERATING SEQUENCES
The generator’s control panel houses a control logic circuit board. This board constantly monitors util­ity power source voltage. Should that voltage drop below a preset level, circuit board action will signal the engine to crank and start. After the engine starts, the circuit board signals the transfer switch to activate and connect load circuits to the standby power supply (load terminal lugs T1/T2 connect to terminal lugs E1/ E2). Refer to the Electrical Data section.
The generator must run at 50 Hz or greater for the transfer output to be activated. Once activated, it will remain active even if the frequency dips below 50 Hz.
Upon restoration of utility source voltage above a preset level, generator circuit board action signals the transfer switch to transfer loads back to that power supply. After retransfer, the engine is signalled to shut down.
The actual sequence of operation is controlled by sensors and timers on a control logic circuit board, as follows:
A. Utility Voltage Dropout Sensor
• This sensor monitors utility source voltage.
• If utility source voltage drops below about 65 percent of the nominal supply voltage, the sensor energizes a 10 second timer.
• Once the timer has expired, the engine will crank and start if utility is still low.
B. Engine Warm-up Time Delay
• This mechanism lets the engine warm up for about five (5) seconds before the load is transferred to the standby source.
C. Standby Voltage Sensor
• This sensor monitors generator AC output voltage. When the voltage has reached 50 percent of the nominal rated voltage, transfer to standby can occur.
D. Utility Voltage Pickup Sensor
• This sensor monitors utility power supply voltage. When that voltage is restored above 75 percent of the nominal source voltage, a retransfer time delay starts timing.
E. Retransfer Time Delay
• This timer runs for about 15 seconds.
• At end of a 15-second delay, circuit board action de­energizes transfer relay in the transfer switch if utility is still present.
• Retransfer to utility power source then occurs.
F. Engine Cool-down Timer
Page 28
• When the load is transferred back to utility power source, the engine cool-down timer starts timing.
• The timer will run for about one minute, and the gen erator will then shut down.
-
Page 31
PART 2
AC GENERATORS
Air-cooled, Prepackaged
Automatic Standby
Generators
TABLE OF CONTENTS
PART TITLE PAGE#
2.1. Description and Components 30
2.2 Operational Analysis 33
2.3 Troubleshooting Flow Charts 35
2.4 Diagnostic Tests 39
2.1 Description and Components
Introduction ......................................................30
Engine-generator Drive System .......................30
The AC Generator ............................................30
Rotor Assembly ................................................30
Stator Assembly ...............................................31
Brush Holder And Brushes ..............................31
Other AC Generator Components ...................31
2.2 Operational Analysis ....................................... 33
Rotor Residual Magnetism...............................33
Field Boost .......................................................33
Operation .........................................................34
2.3 Troubleshooting Flowcharts ............................. 35
Problem 1 - Generator Produces Zero
Voltage or Residual Voltage .......... 35-36
Problem 2 - Generator Produces
Low Voltage at No-Load ......................37
Problem 3 - Generator Produces
High Voltage at No-Load .....................37
Problem 4 - Voltage and Frequency Drop
Excessively When Loads are Applied .38
2.3 Diagnostic Tests .............................................. 39
Introduction ......................................................39
Safety ............................................................39
.......................... 30
Test 1 - Check Main Circuit Breaker.................39
Test 2 - Check AC Output Voltage ....................39
Test 4 - Fixed Excitation Test/Rotor
Amp Draw Test ....................................40
Test 5 - Wire Continuity ....................................41
Test 6 - Check Field Boost ...............................42
Test 7 - Testing The Stator With a VOM ...........42
Test 8 - Resistance Check of Rotor Circuit ......44
Test 9 - Check Brushes and Slip Rings ............44
Test 10 - Test Rotor Assembly .........................45
Test 11 - Check AC Output Frequency.............45
Test 12 - Check And Adjust Engine Governor
(Single Cylinder Units) .........................46
Test 12A - Check Stepper Motor Control
(V-twin Engine Units) ...........................46
Test 13 - Check And Adjust
Voltage Regulator ................................48
Test 14 - Check Voltage And
Frequency Under Load ........................48
Test 15 - Check For Overload Condition ..........48
Test 16 - Check Engine Condition ....................48
Page 29
Page 32
SECTION 2.1
DESCRIPTION & COMPONENTS
PART 2
AC GENERATORS
INTRODUCTION
The air-cooled, pre-packaged automatic standby sys­tem is an easy to install, fully enclosed and self-suf­ficient electric power system. It is designed especially for homeowners, but may be used in other applica­tions as well. On occurrence of a utility power failure, this high performance system will (a) crank and start automatically, and (b) automatically transfer electrical loads to generator AC output.
The generator revolving field (rotor) is driven by an air-cooled engine at about 3600 rpm.
The generator may be used to supply electrical power for the operation of 120 and/or 240 volts, 1-phase, 60 Hz, AC loads.
A 2-pole, “V-Type”, prepackaged transfer switch is shipped with the unit (see Part 3). Prepackaged trans fer switches do not include an “intelligence circuit” of their own. Instead, automatic startup, transfer, run­ning, retransfer and shutdown operations are con­trolled by a solid state circuit board in the generator control panel.
ENGINE-GENERATOR DRIVE SYSTEM
The generator revolving field is driven by an air­cooled, horizontal crankshaft engine. The generator is
directly coupled to the engine crankshaft (see Figure
1), and mounted in an enclosure. Both the engine and generator rotor are driven at approximately 3600 rpm, to provide a 60 Hz AC output.
THE AC GENERATOR
Figure 1 shows the major components of the AC gen­erator.
ROTOR ASSEMBLY
The 2-pole rotor must be operated at 3600 rpm to supply a 60 Hertz AC frequency. The term “2-pole” means the rotor has a single north magnetic pole and a single south magnetic pole. As the rotor rotates, its
­lines of magnetic flux cut across the stator assem-
bly windings and a voltage is induced into the stator windings. The rotor shaft mounts a positive (+) and a negative (-) slip ring, with the positive (+) slip ring nearest the rear bearing carrier. The rotor bearing is pressed onto the end of the rotor shaft. The tapered rotor shaft is mounted to a tapered crankshaft and is held in place with a single through bolt.
BRUSH HOLDER
ASSEMBLY
ROTOR
S TATO R
ENGINE
ENGINE
ADAPTOR
REAR BEARING
CARRIER
Figure 1. AC Generator Exploded View
Page 30
Page 33
AC GENERATORS
PART 2
SECTION 2.1
DESCRIPTION & COMPONENTS
Wire 4 connects to the positive (+) brush and Wire 0 to the negative (-) brush. Wire 0 connects to frame ground. Rectified and regulated excitation current, as well as current from a field boost circuit, are delivered to the rotor windings via Wire 4, and the positive (+) brush and slip ring. The excitation and field boost cur­rent passes through the windings and to frame ground via the negative (-) slip ring and brush, and Wire 0. This current flow creates a magnetic field around the rotor having a flux concentration that is proportional to the amount of current flow.
Figure 2. The 2-Pole Rotor Assembly
STATOR ASSEMBLY
The stator can houses and retains (a) dual AC power windings, (b) excitation winding, and (c) battery charge winding. A total of ten (10) stator leads are brought out of the stator can as shown in Figure 3.
The stator can is sandwiched between an engine adapter and a rear bearing carrier. It is retained in that position by four stator studs.
2
6
11P
11S
22P
22S
33
44
66
77
Figure 3 Stator Assembly Leads
BRUSH HOLDER AND BRUSHES
The brush holder is retained to the rear bearing car­rier by means of two #10-32 x 9/16 Taptite screws. A positive (+) and a negative (-) brush are retained in the brush holder, with the positive (+) brush riding on the slip ring nearest the rotor bearing.
0
-
+
Figure 4. Brush Holder and Brushes
4
OTHER AC GENERATOR COMPONENTS
Some AC generator components are housed in the generator control panel enclosure, and are not shown in Figure 1. These are (a) a voltage regulator, and (b) a main line circuit breaker.
VOLTAGE REGULATOR: A typical voltage regulator is shown in Figure 5.
Unregulated AC output from the stator excitation winding is delivered to the regulator’s DPE terminals, via Wire 2 and Wire 6. The voltage regulator rectifies that current and, based on stator AC power winding sensing, regulates it. The rectified and regulated exci­tation current is then delivered to the rotor windings from the positive (+) and negative (-) regulator termi­nals, via Wire 4 and Wire 0. Stator AC power winding “sensing” is delivered to the regulator “SEN” terminals via Wires 11 and 22.
The regulator provides “over-voltage” protection, but does not protect against “under-voltage”. On occur rence of an “over-voltage” condition, the regulator will “shut down” and complete loss Of excitation current to the rotor will occur. Without excitation current, the generator AC output voltage will drop to approximately one-half (or lower) of the unit’s rated voltage.
-
Page 31
Page 34
SECTION 2.1
DESCRIPTION & COMPONENTS
Figure 5. Typical Voltage Regulator
PART 2
AC GENERATORS
A single red lamp (LED) glows during normal opera tion. The lamp will become dim if excitation winding AC output diminishes. It will go out on occurrence of an open condition in the sensing AC output circuit.
An adjustment potentiometer permits the stator AC power winding voltage to be adjusted. Perform this adjustment with the generator running at no-load, and with a frequency of:
• 57.5-59.5 Hz (V-Twins units)
• 62-63 Hz (Single Cylinder units)
At the stated no-load frequency, adjust to obtain a line-to-line AC voltage of:
• 250-252 volts (V-Twins units)
• 247-252 volts (Single Cylinder units)
MAIN LINE CIRCUIT BREAKER: The main line circuit breaker protects the generator
against electrical overload. See “Specifications” in front of manual for amp ratings.
-
Page 32
Page 35
AC GENERATORS
PART 2
SECTION 2.2
OPERATIONAL ANALYSIS
ROTOR RESIDUAL MAGNETISM
The generator revolving field (rotor) may be consid­ered to be a permanent magnet. Some “residual” magnetism is always present in the rotor. This residu­al magnetism is sufficient to induce a voltage into the stator AC power windings that is approximately 2-12 volts AC.
FIELD BOOST
FIELD BOOST CIRCUIT: When the engine is cranking, direct current flow is
delivered from a circuit board to the generator rotor windings, via Wire 4.
The field boost system is shown schematically in Figure 2. Manual and automatic engine cranking is initiated by circuit board action, when that circuit board energizes a crank relay. Battery voltage is then delivered to field boost Wire 4 (and to the rotor), via a field boost resistor and diode. The crank relay, field boost resistor and diode are all located on the circuit board.
Notice that field boost current is available only while the crank relay is energized, i.e., while the engine is cranking.
Field boost voltage is reduced from that of battery voltage by the resistor action and, when read with a DC voltmeter, will be approximately 9 or 10 volts DC.
+12 VDC
13
56
4
FIELD
BOOST
TO
ROTOR
TO STARTER
STARTER CONTACTOR
DIODE
BASE
TRANSISTOR
RESISTOR
CRANK RELAY K1
CIRCUIT BOARD
FIELD
BOOST
DIODE
FIELD
BOOST
PIN 5
PIN 1
Figure 2. Field Boost Circuit Schematic
Figure 1. Operating Diagram of AC Generator
Page 33
Page 36
SECTION 2.2
OPERATIONAL ANALYSIS
PART 2
AC GENERATORS
OPERATION
STARTUP: When the engine is started, residual plus field boost
magnetism from the rotor induces a voltage into (a) the stator AC power windings, (b) the stator exci­tation or DPE windings, and (c) the stator battery charge winding. In an “on-speed” condition, residual plus field boost magnetism are capable of creating approximately one-half the unit’s rated voltage.
ON-SPEED OPERATION: As the engine accelerates, the voltage that is induced
into the stator windings increases rapidly, due to the increasing speed at which the rotor operates.
FIELD EXCITATION: An AC voltage is induced into the stator excitation
(DPE) windings. The DPE winding circuit is com­pleted to the voltage regulator, via Wire 2 and Wire
6. Unregulated alternating current can flow from the winding to the regulator.
The voltage regulator “senses” AC power winding out put voltage and frequency via stator Wires 11 and 22.
The regulator changes the AC from the excitation winding to DC. In addition, based on the Wires 11 and 22 sensing signals, it regulates the flow of direct cur­rent to the rotor.
The rectified and regulated current flow from the regu lator is delivered to the rotor windings, via Wire 4, and the positive brush and slip ring. This excitation current flows through the rotor windings and is directed to ground through the negative (-) slip ring and brush, and Wire 0.
The greater the current flow through the rotor wind­ings, the more concentrated the lines of flux around the rotor become.
The more concentrated the lines of flux around the rotor that cut across the stationary stator windings, the greater the voltage that is induced into the stator windings.
Initially, the AC power winding voltage sensed by the regulator is low. The regulator reacts by increasing the flow of excitation current to the rotor until volt age increases to a desired level. The regulator then maintains the desired voltage. For example, if voltage exceeds the desired level, the regulator will decrease the flow of excitation current. Conversely, if voltage drops below the desired level, the regulator responds by increasing the flow of excitation current.
AC POWER WINDING OUTPUT: A regulated voltage is induced into the stator AC
power windings. When electrical loads are connected across the AC power windings to complete the cir­cuit, current can flow in the circuit. The regulated AC power winding output voltage will be in direct propor­tion to the AC frequency. For example, on units rated
­120/240 volts at 60 Hz, the regulator will try to main-
tain 240 volts (line-to-line) at 60 Hz. This type of regu­lation system provides greatly improved motor starting capability over other types of systems.
BATTERY CHARGE WINDING OUTPUT:
­A voltage is induced into the battery charge windings.
Output from these windings is delivered to a battery charger, via Wires 66 and 77. The resulting direct cur­rent from the battery charger is delivered to the unit battery, via Wire 13. This output is used to maintain battery state of charge during operation.
-
Page 34
Page 37
AC GENERATORS
PART 2
GENERAL
Use the “Flow Charts” in conjunction with the detailed instructions in Section 2.4. Test numbers used in the flow charts correspond to the numbered tests in Section 2.4.
Problem 1 - Generator Produces Zero Voltage or Residual Voltage
TEST 1 - CHECK
MAIN CIRCUIT
BREAKER
RESET TO
“ON”
OR REPLACE
IF BAD
TEST 4 - PERFORM
FIXED EXCITATION /
A
ROTOR AMP DRAW
D
B
C
SECTION 2.3
TROUBLESHOOTING FLOWCHARTS
The first step in using the flow charts is to correctly identify the problem. Once that has been done, locate the problem on the following pages. For best results, perform all tests in the exact sequence shown in the flow charts.
RE-TEST
G
REPAIR
OR REPLACE
FUSES
CHECK
FUSES
VOM
TEST 5 - WIRE
CONTINUITY
GOOD
TEST 6 -
FIELD BOOST
BAD
GOOD
REPLACE
VO LTAG E
REGULATOR
BAD
REPAIR
OR
REPLACE
THEN
RETEST
TEST 7 - TEST
S TATO R
BAD
REPAIR
OR
REPLACE
GOOD
PERFORM STATOR
INSULATION
RESISTANCE TEST
-
SECTION 1.4
BAD
TEST 8 -
CIRCUIT
REPAIR
OR
REPLACE
CHECK ROTOR
BAD
BAD
BAD
GOOD
BAD
TEST 9 -
CHECK
BRUSHES &
SLIP RINGS
GOOD
TEST 10 -
TEST ROTOR
ASSEMBLY
GOOD
PERFORM ROTOR
INSULATION
RESISTANCE TEST
-
SECTION 1.4
Page 35
Page 38
SECTION 2.3
TROUBLESHOOTING FLOWCHARTS
Problem 1 - Generator Produces Zero Voltage or Residual Voltage
(Continued)
PART 2
AC GENERATORS
TEST 10 -
TEST ROTOR
ASSEMBLY
GOOD
PERFORM ROTOR
INSULATION
RESISTANCE TEST -
SECTION 1.4
GOOD
TEST 7 - TEST
S TATO R
TEST 4 - PERFORM
FIXED EXCITATION /
E
ROTOR AMP DRAW
BAD
BAD
BAD
H
REPAIR
OR
REPLACE
F
TEST 7 - TEST
S TATO R
GOOD
PERFORM STATOR
INSULATION
RESISTANCE TEST -
SECTION 1.4
GOOD
TEST 10 -
TEST ROTOR
ASSEMBLY
GOOD
BAD
BAD
REPAIR
OR
REPLACE
BAD
GOOD
PERFORM STATOR
INSULATION
RESISTANCE TEST -
SECTION 1.4
GOOD
RE-TEST
TEST 4
BAD
PERFORM ROTOR
INSULATION
RESISTANCE TEST -
SECTION 1.4
GOOD
RE-TEST
TEST 4
BAD
Page 36
Page 39
AC GENERATORS
PART 2
TROUBLESHOOTING FLOWCHARTS
Problem 2 - Generator Produces Low Voltage at No-Load
SECTION 2.3
TEST 2 - CHECK
AC OUTPUT
VOLTAGE
TEST 13- ADJUST
VO LTAG E
REGULATOR
FREQUENCY O.K.,
BUT VOLTAGE IS
STILL LOW
LOW
TEST 11 - CHECK
AC OUTPUT
FREQUENCY
FREQUENCY O.K.,
BUT VOLTAGE LOW
VOLTAGE AND FREQUENCY O.K.
GO TO “PROBLEM 1” FLOW CHART - START AT “TEST 4 - F/E”
LOW -
SINGLE CYLINDER
UNITS
LOW -
V-TWIN UNITS
TEST 12 - ADJUST
ENGINE GOVERNOR
TEST 12A - CHECK
STEPPER MOTOR
CONTROL
Problem 3 - Generator Produces High Voltage at No-Load
FREQUENCY AND
VOLTAGE O.K.
STOP
TESTS
TEST 2 - CHECK
AC OUTPUT
VOLTAGE
TEST 13- ADJUST
VO LTAG E
REGULATOR
FREQUENCY O.K.,
BUT VOLTAGE IS
STILL HIGH
HIGH
TEST 11 - CHECK
AC OUTPUT
FREQUENCY
FREQUENCY O.K.,
BUT VOLTAGE HIGH
VOLTAGE AND FREQUENCY O.K.
REPLACE DEFECTIVE VOLTAGE REGULATOR
HIGH -
SINGLE CYLINDER
UNITS
HIGH -
V-TWIN UNITS
TEST 12 - ADJUST
ENGINE GOVERNOR
TEST 12A - CHECK
STEPPER MOTOR
CONTROL
FREQUENCY AND
VOLTAGE O.K.
STOP
TESTS
Page 37
Page 40
SECTION 2.3
PART 2
TROUBLESHOOTING FLOWCHARTS
Problem 4 - Voltage and Frequency Drop Excessively When Loads Are Applied
AC GENERATORS
TEST 14 - CHECK
VOLTAGE AND
FREQUENCY UNDER LOAD
GOOD
DISCONTINUE
TESTING
TEST 80 - CHECK
LC1 & LC2 WIRING
REPAIR OR REPLACE
DEFECTIVE WIRING
BOTH
LOW
TEST 15 - CHECK
FOR OVERLAOD
CONDITION
OVERLOADED
REDUCE LOADS TO UNIT’S
RATED CAPACITY
TEST 81 - CHECK
IDLE CONTROL
TRANSFORMER
PRIMARY WIRING
BAD BADBAD
REPAIR OR REPLACE
DEFECTIVE WIRING
NOT
OVERLOADED
GOODGOOD
IF RECONFIGURED TO LP GAS, VERIFY THAT PROPER PROCEDURE WAS FOLLOWED (REFER TO SECTION 1.3)
UNITS WITH
V-TWIN
ENGINES
TEST 79 - CHECK
IDLE CONTROL
TRANSFORMER
REPAIR OR REPLACE
THE IDLE CONTROL
TRANSFORMER
UNITS WITH
SINGLE
CYLINDER
ENGINES
LOOK FOR A SHORTED
CONDITION IN A
CONNECTED LOAD OR
IN ONE OF THE LOAD
CIRCUITS
REPAIR OR REPLACE
GOOD
GOOD
TEST 12A - CHECK
REPAIR OR REPLACE
TEST 7 - CHECK
S TATO R A C
POWER WINDINGS
BAD
STEPPER MOTOR
CONTROL
BAD
ENGINE
CONDITION
GOOD
GOOD
TEST 12 - CHECK AND
ADJUST ENGINE
GOVERNOR
GOOD
GO TO “PROBLEM 11 - ENGINE
STARTS HARD AND RUNS
ROUGH/LACKS POWER”
SECTION 4.3
Page 38
Page 41
AC GENERATORS
OFF
WIRE 11
TERMINAL
E1 TERMINAL
E2 TERMINAL
WIRE 44
TERMINAL
PART 2
SECTION 2.4
DIAGNOSTIC TESTS
INTRODUCTION
This section is provided to familiarize the service technician with acceptable procedures for the test­ing and evaluation of various problems that could be encountered on prepackaged standby generators with air-cooled engine. Use this section of the manual in conjunction with Section 2.3, “Troubleshooting Flow Charts”. The numbered tests in this section corre­spond with those of Section 2.3.
Test procedures in this section do not require the use of specialized test equipment, meters or tools. Most tests can be performed with an inexpensive volt­ohm-milliammeter (VOM). An AC frequency meter is required, where frequency readings must be taken. A clamp-on ammeter may be used to measure AC loads on the generator.
Testing and troubleshooting methods covered in this section are not exhaustive. We have not attempted to discuss, evaluate and advise the home stand by service trade of all conceivable ways in which service and trouble diagnosis might be performed. We have not undertaken any such broad evaluation. Accordingly, anyone who uses a test method not rec­ommended herein must first satisfy himself that the procedure or method he has selected will jeopardize neither his nor the product’s safety.
1. Set a volt-ohm-milliammeter (VOM) to its “R x 1” scale and zero the meter.
2. With the generator shut down, disconnect all wires from the main circuit breaker terminals, to prevent interaction.
3. With the generator shut down, connect one VOM test probe to the Wire 11 terminal of the breaker and the other test probe to the Wire E1 terminal.
4. Set the breaker to its “On” or “Closed” position. The VOM should read CONTINUITY.
5. Set the breaker to its OFF or “Open” position and the VOMshould indicate
INFINITY.
6. Repeat Steps 4 and 5 with the VOM test probes con­nected across the breaker’s Wire 44 terminal and the E2 terminal.
­RESULTS:
1. If the circuit breaker tests good, go on to Test 2.
2. If the breaker tests bad, it should be replaced.
SAFETY
Service personnel who work on this equipment must be made aware of the dangers of such equipment. Extremely high and dangerous voltages are present that can kill or cause serious injury. Gaseous fuels are highly explosive and can be ignited by the slightest spark. Engine exhaust gases contain deadly carbon monoxide gas that can cause unconsciousness or even death. Contact with moving parts can cause seri­ous injury. The list of hazards is seemingly endless.
When working on this equipment, use common sense and remain alert at all times. Never work on this equipment while you are physically or mentally fatigued. If you don’t understand a component, device or system, do not work on it.
TEST 1- CHECK MAIN CIRCUIT BREAKER
DISCUSSION: Often the most obvious cause of a problem is over-
looked. If the generator main line circuit breaker is set to OFF or “Open”, no electrical power will be supplied to electrical loads. If loads are not receiving power, perhaps the main circuit breaker is open or has failed.
PROCEDURE: The generator main circuit breaker is located on the
control panel. If loads are not receiving power, make sure the breaker is set to “On” or “Closed”.
If you suspect the breaker may have failed, it can be tested as follows (see Figure 1):
Figure 1. Generator Main Circuit Breaker Test Points
TEST 2- CHECK AC OUTPUT VOLTAGE
DISCUSSION: A volt-ohm-milliammeter (VOM) may be used to check
the generator output voltage. Output voltage may be checked at the unit’s main circuit breaker terminals. Refer to the unit’s DATA PLATE for rated line-to-line and line-to-neutral voltages.
Page 39
Page 42
SECTION 2.4
DIAGNOSTIC TESTS
PART 2
AC GENERATORS
DANGER: USE EXTREME CAUTION
PROCEDURE:
DURING THIS TEST. THE GENERATOR WILL BE RUNNING. HIGH AND DANGEROUS VOLTAGES WILL BE PRESENT AT THE TEST TERMINALS. CONNECT METER TEST CLAMPS TO THE HIGH VOLTAGE TERMINALS WHILE THE GENERATOR IS SHUT DOWN. STAY CLEAR OF POWER TERMINALS DURING THE TEST. MAKE SURE METER CLAMPS ARE SECURELY ATTACHED AND WILL NOT SHAKE LOOSE.
1. With the engine shut down, connect the AC voltmeter test leads across the Wires 11 and 44 terminals of the generator main circuit breaker (see Figure 1). These connections will permit line-to-line voltages to be read.
2. Set the generator main circuit breaker to its OFF or “Open” position. This test will be conducted with the generator running at no-load.
3. Start the generator, let it stabilize and warm up for a minute or two.
ning, this should create a proportional voltage output from the stator windings.
PROCEDURE:
1. Disconnect Wire 4 from the voltage regulator, 3rd termi­nal from the top. See Figure 2.
2. Connect a jumper wire to the disconnected Wire 4 and to the 12 volt fused battery supply Wire 15 (located at 15A fuse).
3. Set VOM to AC volts.
4
0
6
2
4
22
11
4. Take the meter reading. On unit’s having a rated line-to­line voltage of 240 volts, the no-load voltage should be about 242-252 volts AC.
5. Shut the engine down and remove the meter test leads.
RESULTS:
1. If zero volts or residual voltage is indicated, go on to Test 4.
2. If the voltage reading is higher than residual, but is lower than the stated limits, go to Test 11.
3. If a high voltage is indicated, go on to Test 11.
NOTE: “Residual” voltage may be defined as the voltage that is produced by rotor residual mag­netism alone. The amount of voltage induced into the stator AC power windings by residual volt­age alone will be approximately 2 to 16 volts AC, depending on the characteristics of the specific generator. If a unit is supplying residual voltage only, either excitation current is not reaching the rotor or the rotor windings are open and the exci­tation current cannot pass. On current units with air-cooled engine, “field boost” current flow is available to the rotor only during engine cranking.
TEST 4- FIXED EXCITATION TEST
/ROTOR AMP DRAW TEST
Figure 2. Voltage Regulator
4. Disconnect Wire 2 from the voltage regulator and con­nect one meter test lead to that wire. Disconnect Wire 6 from the voltage regulator and connect the other meter test lead to that wire. Wires 2 and 6 are located at the bottom two terminals of the voltage regulator (see Figure 2).
5. Set the AUTO-OFF-MANUAL switch to MANUAL. Once the engine starts, record the AC voltage.
6. Set the AUTO-OFF-MANUAL switch to OFF. Reconnect Wire 2 and Wire 6.
7. Disconnect Wire 11 from the voltage regulator and con­nect one meter test lead to that wire. Disconnect Wire 22 from the voltage regulator and connect the other meter test lead to that wire (both wires are located at the top two terminals of the voltage regulator, see Figure 2).
8. Set the AUTO-OFF-MANUAL switch to MANUAL. Once the engine starts, record the AC voltage.
9. Set the AUTO-OFF-MANUAL switch to OFF. Reconnect Wire 11 and Wire 22.
10.Set VOM to DC amperage.
DISCUSSION: Supplying a fixed DC current to the rotor will induce
a magnetic field in the rotor. With the generator run-
Page 40
11.Remove jumper lead connected to Wire 4 and Wire 15.
12.Connect one meter test lead to battery positive twelve­volt supply Wire 15, located at the 15A fuse. Connect
Page 43
AC GENERATORS
PART 2
the other meter test lead to Wire 4 (still disconnected from previous tests). Measure and record static rotor amp draw.
13.Set the AUTO-OFF-MANUAL switch to the MANUAL position. Once the engine starts, repeat Step 12. Measure and record running rotor amp draw with the engine running.
14.Set the AUTO-OFF-MANUAL switch to OFF. Reconnect Wire 4 to the voltage regulator.
RESULTS: Refer to the chart on this page: “Results - Fixed
Excitation Test/Rotor Amp Draw Test”.
SECTION 2.4
DIAGNOSTIC TESTS
0.91-1.06A
0.91-1.06A
0.91-1.06A
0.91-1.06A
Above 1.5A
Zero
Draw
Current
Zero
Current
Draw
Î
EXAMPLE:
MODEL 5240
WIRE2&6VOLTAGE 87VAC
WIRE 11 & 22 VOLTAGE 31 VAC
STATIC ROTOR AMP DRAW 1.0 AMP
RUNNING ROTOR AMP DRAW 1.0 AMP
These results match Column B in the chart. Refer back to Problem 1 Flow Chart and follow Letter B.
TEST 5: WIRE CONTINUITY
DISCUSSION: The voltage regulator receives unregulated alternating
current from the stator excitation winding, via Wires 2 and 6. It also receives voltage sensing from the sta­tor AC power windings, via Wires 11 and 22. The regulator rectifies the AC from the excitation winding and based on the sensing signals, regulates the DC current flow to the rotor. The rectified and regulated current flow is delivered to the rotor brushes via Wires 4 (positive) and 0 (negative). This test will verify the integrity of Wire 0.
Below 60 VAC Below 60 VAC Above 60 VAC Below 60 VAC
Volts
Zero or Residual
Below 60 VAC Below 60 VAC Above 60 VAC Below 60 VAC
Volts
Zero or Residual
0.91-1.06A
0.91-1.06A
Above 1.5A
Above 1.5A
Zero
Current
0.91-1.06A
0.91-1.06A
0.91-1.06A
0.91-1.06A
0.91-1.06A
0.91-1.06A
Above 1.5A
Above 1.1A
Draw
0.91-1.06A
0.91-1.06A
0.91-1.06A
0.91-1.06A
Above 1.5A 0.91-1.06A
Zero
Draw
Current
PROCEDURE:
1. Set VOM to its “R x 1” scale.
2. Remove Wire 0 from the voltage regulator, 4th terminal from the top. Also voltage regulator is labeled (-) next to terminal.
3. Connect one test lead to Wire 0, connect the other test lead to a clean frame ground. The meter should read CONTINUITY.
RESULTS: If CONTINUITY was not measured, repair or replace
the wire as needed.
TEST 4 RESULTS - FIXED EXCITATION TEST/ROTOR AMP DRAWTEST
ALL Above 60 VAC Above 60 VAC Below 60 VAC
Results: (Model #) ABCDEFGH
Voltage Results
Wire2&6
ALL Above 60 VAC Below 60 VAC Above 60 VAC
Voltage Results
Wire 11 & 22
1.06A
0.91-1.06A
005240, 005280
005241, 005282
005242, 005282
Static Rotor
Amp Draw
1.0A
0.57A
005243, 005283
005244, 005284
ALL 0.91-1.06A 0.91-1.06A 0.91-1.06A
Running Rotor
Amp Draw
Page 41
MATCH RESULTS WITH LETTER AND REFER TO FLOW CHART IN SECTION 2.3 “Problem 1”
Í
Page 44
SECTION 2.4
DIAGNOSTIC TESTS
PART 2
AC GENERATORS
TEST 6 - CHECK FIELD BOOST
DISCUSSION: See “Field Boost Circuit” in Section 2.2. Field boost
current (from the circuit board) is available to the rotor only while the engine is cranking. Loss of field boost output to the rotor may or may not affect power wind­ing AC output voltage. The following facts apply:
• A small amount of voltage must be induced into the DPE winding to turn the voltage regulator on.
• If rotor residual magnetism is sufficient to induce a voltage into the DPE winding that is high enough to turn the voltage regulator on, regula­tor excitation current will be supplied even if field boost has failed. Normal AC output voltage will then be supplied.
• If rotor residual magnetism has been lost or is not sufficient to turn the regulator on, and field boost has also been lost, excitation current will not be supplied to the rotor. Generator AC output voltage will then drop to zero or nearly zero.
PROCEDURE:
1. Disconnect Wire 4 from the voltage regulator, third termi-
nal from the top (see Figure 4).
2. Set a VOM to read DC volts.
RESULTS:
1. If normal field boost voltage is indicated in Step 6, replace the voltage regulator.
2. If normal field boost voltage is NOT indicated in Step 6, check Wire 4 (between regulator and circuit board) for open or shorted condition. If wire is good, replace the circuit board.
3. Disconnect C2 Connector from the control panel (see Figure 3).
4. Connect the positive (+) VOM test probe to the terminal end of disconnected Wire 4.
5. Connect the common (-) VOM test probe to the grounding lug.
6. Crank the engine while observing the VOM reading. While the engine is cranking, the VOM should read approximately 9-10 volts DC. When engine is not crank­ing, VOM should indicate “zero” volts (see Figure 4).
7. Reconnect the C2 Connector and Wire 4.
BACK PANEL
C1 CONNECTOR
C2 CONNECTOR
C3 CONNECTOR
Figure 4. Field Boost Test Points
TEST 7 - TESTING THE STATOR WITH A VOM
DISCUSSION: A Volt-OHM-Milliammmeter (VOM) can be used to test
the stator windings for the following faults:
• An open circuit condition
• A “short-to-ground” condition
• A short circuit between windings
Note: The resistance of stator windings is very low. Some meters will not read such a low resis­tance, and will simply indicate CONTINUITY. Recommended is a high quality, digital type meter capable of reading very low resistances.
PROCEDURE:
1. Disconnect stator leads 11 and 44 from the main circuit breaker.
2. Disconnect stator leads 22 and 33 from the neutral con­nection separate the leads.
Figure 3. C2 Connector Location
Page 42
3. Disconnect C2 Connector from the side of the control panel (see Figure 3).
4. Make sure all of the disconnected leads are isolated
Page 45
AC GENERATORS
PART 2
SECTION 2.4
DIAGNOSTIC TESTS
from each other and are not touching the frame during the test.
5. Set a VOM to measure resistance.
6. Refer to Figure 5 for pin locations of C2 Connector. Use a large paper clip or similar metallic object to access pins in C2 Connector (Female Side).
8
4 3
2
1
Figure 5. C2 Connector Pin Locations
Pin
Location
1 77 Battery Charge
2 66 Battery Charge
3 22 Sense Lead Power
4 11 Sense Lead Power
5 6 Excitation
6 2 Excitation
7 0 Ground
8 4 Positive to Brush
Wire
Number
8
7
7
6
6
5
5
FEMALE SIDEMALE SIDE
Winding
4 3
2
1
7. Connect one test lead to stator lead Wire 11. Connect the other test lead to stator lead Wire 22 (power wind­ing). Note the resistance reading and compare to the specifications in the front of this manual.
8. Connect one test lead to stator lead Wire 33. Connect the other test lead to stator lead Wire 44 (power wind­ing). Note the resistance reading and compare to the specifications in the front of this manual.
9. Connect one test lead to Pin 1. Connect the other test lead to Pin 2 (battery charge winding). Note the resis­tance reading, compare to specifications in the front of this manual.
10.Connect one test lead to Pin 3. Connect the other test lead to Pin 4 (power winding-sense leads). Note the resistance reading, compare to specification in the front of this manual.
11.Connect on test lead to Pin 5. Connect the other test lead to Pin 6 (excitation winding). Note the resistance reading, compare to specifications in the front of this manual.
TEST WINDINGS FOR A SHORT TO GROUND:
12. Make sure all leads are isolated from each other and are not touching the frame.
13. Connect one test lead to a clean frame ground. Connect the other test lead to stator lead Wire 11.
a.The meter should read INFINITY. b.Any reading other than INFINITY indicates a
“short-to-ground” condition.
14. Repeat Step 13 using stator lead Wire 33.
15. Repeat Step 13 using Pin 1.
16. Repeat Step 13 using Pin 3.
17. Repeat Step 13 using Pin 5.
TEST FOR A SHORT CIRCUIT BETWEEN WINDINGS:
18. Connect one test lead to stator lead Wire 11. Connect the other test lead to stator lead Wire 33.
a.The meter should read INFINITY. b.Any reading other than INFINITY indicates a
short circuit between windings.
19.Repeat Step 18 using stator lead Wire 11; Pin 1.
20.Repeat Step 18 using stator lead Wire 11; Pin 5.
21.Repeat Step 18 using stator lead Wire 33; Pin 1.
22.Repeat Step 18 using stator lead Wire 33; Pin 5.
23.Repeat Step 18 using Pin 1; Pin 3.
24.Repeat Step 18 using Pin 1; Pin 5.
25.Repeat Step 18 using Pin 3; Pin 5.
TEST CONTROL PANEL WIRES FOR CONTINUITY:
26.Disconnect the C2 Connector from the control panel. Refer to Figure 5 for the pin locations (Male Side).
27.Connect one meter test lead to Pin 3 of the C2 Connector (Male Side), connect the other test lead to Wire 22 at the voltage regulator. CONTINUITY should be measured.
28.Connect one meter test lead to Pin 4 of the C2 Connector (Male Side), connect the other test lead to Wire 11 at the voltage regulator. CONTINUITY should be measured.
29.Connect one meter test lead to Pin 5 of the C2 Connector (Male Side), connect the other test lead to Wire 6 at the voltage regulator. CONTINUITY should be measured.
30. Connect one meter test lead to Pin 6 of the C2 Connector (Male Side), connect the other test lead to Wire 2. CONTINUITY should be measured at the voltage regulator.
Page 43
Page 46
SECTION 2.4
DIAGNOSTIC TESTS
PART 2
AC GENERATORS
RESULTS:
1. Stator winding resistance values is a test of winding continuity and resistance. If a very high resistance or INFINITY is indicated, the winding is open or partially open.
2. Testing for a “grounded” condition: Any resistance read­ing indicates the winding is grounded.
3. Testing for a “shorted” condition: Any
indicates the winding is shorted.
ing
resistance read-
4. If the stator tests good and wire continuity tests good , perform “Insulation Resistance Test” in Section 1.4.
5. If any test of wire continuity failed in the control panel, repair or replace the wire, terminal or pin connectors for that associated wire as needed.
NOTE: Read Section 1.4, “Testing, Cleaning and Drying” carefully. If the winding tests good, per­form an insulation resistance test. If the winding fails the insulation resistance test, clean and dry the stator as outlined in Section 1.4. Then, repeat the insulation resistance test. If the winding fails the second resistance test (after cleaning and dry­ing), replace the stator assembly.
out or fail. However, slip rings can develop a tarnish or film that can inhibit or offer a resistance to the flow of electricity. Such a non-conducting film usually devel­ops during non-operating periods. Broken or discon­nected wiring can also cause loss of excitation current to the rotor.
PROCEDURE:
1. Disconnect C2 Connector. Refer to Figure 3 on Page 40.
2. Set a VOM to measure resistance.
TEST 8 - RESISTANCE CHECK OF
ROTOR CIRCUIT
DISCUSSION: To verify the zero current draw reading and measure
the rotor circuit.
PROCEDURE:
1. Disconnect Wire 4 from the voltage regulator. It is locat­ed 3rd terminal from the top of the volt regulator.
2. Set VOM to measure resistance.
3. Connect one test lead to Wire 4. Connect the other test lead to a clean frame ground. Note the resistance reading. Compare to specifications in the front of this manual.
RESULTS:
1. If the resistance reading is correct, check your VOM meters fuse and repeat Test 4.
2. If INFINITY is measured on your VOM meter, go to Test 9.
TEST 9 - CHECK BRUSHES AND SLIP RINGS
DISCUSSION: The function of the brushes and slip rings is to pro-
vide for passage of excitation current from stationary components to the rotating rotor. Brushes are made of a special long lasting material and seldom wear
Page 44
Figure 6. Checking Brushes and Slip Rings
3. Connect one meter test lead to Pin 7 (Wire 0) of the C2 Connector (female side). Connect the other meter test lead to Pin 8 (Wire 4) of the C2 Connector (female side). Rotor resistance should be measured (see Specifications in front of book). If rotor resistance is not measured proceed to Step 4. If rotor resistance is mea­sured proceed to Step 12. Refer to Figure 5.
4. See Figure 6. Carefully inspect brush wires; make sure they are properly and securely connected.
5. Wire 0 from the negative (-) brush terminal connects to
Pin 7 of the C2 Connector.
Test this wire for an open condition. Remove Wire 0
from the brush assembly. Connect one meter test lead to Wire 0. Connect the other test lead to Pin 7 (Wire
0) of the C2 Connector ( female side). CONTINUITY should be measured. If INFINITY is measured repair or replace Wire 0 between the brush assembly and the C2 Connector.
6. Wire 4 from the positive (+) brush terminal connects to Pin 8 of the C2 Connector. Test this wire for an open condition. Remove Wire 4 from the brush assem­bly. Connect one meter test lead to Wire 4. Connect the other meter test lead to Pin 8 (Wire 0) of the C2 Connector (female side). CONTINUITY should be mea­sured. If INFINITY is measured repair or replace Wire 4 between the brush assembly and the C2 Connector.
Page 47
AC GENERATORS
PART 2
SECTION 2.4
DIAGNOSTIC TESTS
7. Connect one meter test lead to Wire 4 Connect the other meter test lead to frame ground. INFINITY should be measured. If CONTINUITY is measured a short to ground exists on Wire 4 repair or replace Wire 4 between the brush assembly and the C2 Connector.
8. If CONTINUITY was measured in Steps 5 and 6 proceed to Step 9.
9. Disconnect Wire 0 and Wire 4 from the brush assembly. Remove the brush assembly from the bearing carrier. Inspect the brushes for excessive wear, or damage.
10.Inspect the rotor slip rings. If they appear dull or tar­nished, they may be polished with a fine sandpaper. DO NOT USE METALLIC GRIT TO POLISH SLIP RINGS.
11.If brush assembly and slip rings look good proceed to Test 10 ( Test Rotor Assembly)
12.Wire 0 connects from the C2 Connector to the control panel ground lug. Connect one meter test lead to Pin 7 (Wire 0) of the C2 Connector (male side). Connect the other meter test lead to the ground terminal in the control panel. CONTINUITY should be measured. If INFINITY is measured repair or replace Wire 0 between the C2 Connector and the ground terminal.
tive (+) rotor slip ring (nearest the rotor bearing); and the common (-) test lead to the negative (-) slip ring. The meter should read rotor resistance. Compare to “Specifications,” in the front of this manual.
4. Connect the positive (+) VOM test lead to the positive (+) slip ring and the common (-) test lead to a clean frame ground. The meter should indicate INFINITY.
RESULTS:
1. Replace rotor assembly if it is open or shorted.
2. If rotor tests good, perform “Insulation Resistance Test” in Section 1.4.
NOTE: Be sure to read Section 1.4, “Testing, Cleaning and Drying”, carefully. If the rotor tests good, try per­forming an insulation resistance test. Clean and dry the rotor if it fails that test. Then, repeat the test. If the rotor fails the second insulation resistance test, it should be replaced.
13.Remove Wire 4 from the voltage regulator.
14.Connect one meter test lead to Pin 8 (Wire 4) of the C2 Connector (male side). Connect the other meter test lead to Wire 4 removed from the Voltage regula­tor. CONTINUITY should be measured. If INFINITY is measured repair or replace Wire 4 between the C2 Connector and the voltage regulator.
RESULTS:
1. Repair, replace or reconnect wires as necessary.
2. Replace any damaged slip rings or brush holder.
3. Clean and polish slip rings as required.
TEST 10 - TEST ROTOR ASSEMBLY
DISCUSSION: A rotor having completely open windings will cause
loss of excitation current flow and, as a result, genera­tor AC output voltage will drop to “residual” voltage. A “shorted” rotor winding can result in a low voltage condition.
PROCEDURE:
I. Disconnect the brush wires or remove the brush holder,
to prevent interaction.
2. Set a VOM to measure resistance.
3. Connect the positive (+) VOM test lead to the posi-
Figure 7. The Rotor Assembly
TEST 11 - CHECK AC OUTPUT FREQUENCY
DISCUSSION: The generator AC frequency is proportional to the
operating speed of the rotor. The 2-pole rotor will sup­ply a 60 Hertz AC frequency at 3600 rpm. The unit’s AC output voltage is proportional to the AC frequency. For example, a unit rated 240 volts (line-to-line) will supply that rated voltage (plus or minus 2 percent) at a frequency of 60 Hertz. If, for any reason, the frequency should drop to 30 Hertz, the line-to-line voltage will drop to a matching voltage of 120 volts AC. Thus, if the AC voltage output is high or low and the AC frequency is correspondingly high or low, the engine speed governor may require adjustment.
PROCEDURE:
1. Connect an accurate AC frequency meter across the Wires 11 and 44 terminals of the generator main line circuit breaker (see Figure 1, Section 2.4).
Page 45
Page 48
SECTION 2.4
DIAGNOSTIC TESTS
PART 2
AC GENERATORS
2. Start the engine, let it stabilize and warm up at no-load.
3. When engine has stabilized, read the frequency meter. The no-load frequency for single cylinder units should be about 62-63 Hertz. For V-Twin units, the no-load fre­quency should be about 57.5-59.5 Hertz.
RESULTS:
1. If the AC frequency is high or low, go on to Test 12 for single cylinder units, or Test 12A for V-Twin units.
2. If frequency is good, but voltage is high or low, go to Test
13.
3. If frequency and voltage are both good, tests may be discontinued.
TEST 12 - CHECK AND ADJUST ENGINE
GOVERNOR (SINGLE CYLINDER UNITS)
DISCUSSION: The generator AC frequency output is directly pro-
portional to the speed of the rotor. A two-pole rotor (having a single north and a single south magnetic pole) will produce an AC frequency of 60 hertz at 3600 RPM.
The generator is equipped with a “voltage over fre­quency” type AC voltage regulator. The units AC output voltage is generally proportional to AC fre­quency. A low or high governor speed will result in a correspondingly low or high AC frequency and voltage output. The governed speed must be adjusted before any attempt to adjust the voltage regulator is made.
SECONDARY
ADJUST SCREW
GOVERNOR
SHAFT
GOVERNOR
CLAMP
BOLT
PRIMARY
ADJUST SCREW
PROCEDURE (7 KW UNITS WITH DUAL GOVERNOR SPRINGS):
1. Loosen the governor clamp bolt (Figure 8).
2. Hold the governor lever at its wide open throttle position, and rotate the governor shaft clockwise as far as it will go. Then, tighten the governor lever clamp bolt to 70 inch-pounds (8 N-m).
3. Start the generator; let it stabilize and warm up at no­load.
4. Connect a frequency meter across the generators AC output leads.
5. Turn the primary adjust screw to obtain a frequency reading of 61.5 Hz. Turn the secondary adjust screw to obtain a frequency reading of 62.5 Hz.
6. When frequency is correct at no load, check the AC volt­age reading. If voltage is incorrect, the voltage regulator may require adjustment.
RESULTS:
1. If, after adjusting the engine governor, frequency and voltage are good, tests may be discontinued.
2. If frequency is now good, but voltage is high or low, go to Test 13.
3. If engine was overspeeding, check linkage and throttle for binding. If no governor response is indicated refer to engine service manual.
4. If engine appears to run rough and results in low fre­quency, proceed to Problem 11, Section 4.3.
TEST 12A - CHECK STEPPER MOTOR
CONTROL (V-TWIN ENGINE UNITS)
PROCEDURE:
1. Remove air cleaner cover to access stepper motor.
2. Physically grab the throttle and verify the stepper motor, linkage and throttle do not bind in any way, if any bind­ing is felt repair or replace components as needed. Some resistance should be felt as the stepper motor moves through it's travel.
(7KW UNITS WITH DUAL GOVERNOR SPRINGS)
Figure 8. Engine Governor Adjustment Single
Cylinder Engines
Page 46
3. Physically move the throttle to the closed position by pulling the stepper motor arm towards the idle stop. See Figures 9 and 10 (for 10 kW units) or Figure 11 (for 13/16 kW Units).
a.Place the AUTO-OFF-MANUAL switch (SW1)
to MANUAL and watch for stepper motor move­ment. It should move to the wide open position during cranking. Once the unit starts the stepper motor should move the throttle to a position to maintain 57.5-59.5 Hertz.
Page 49
AC GENERATORS
STEPPER MOTOR
STEPPER MOTOR ARM
PULL ARM THIS DIRECTION TO CLOSE THROTTLE
RED
EMPTY
ORANGE
BROWN
YELLOW
BLACK
PART 2
SECTION 2.4
DIAGNOSTIC TESTS
4. If no movement is seen in Step 3 remove the control panel cover. Verify the six pin connector on the printed circuit board is seated properly, remove the connector and then replace it and test again. Verify the switches are correctly set.
5. If problem continues remove six pin connector from printed circuit board. Set Volt meter to measure ohms. Carefully measure from the end of the six pin harness as follows:
NOTE: Press down with the meter leads on the connectors exposed terminals, do not probe into the connector.
a.Connect one meter lead to Red, connect the
remaining test lead to Orange, approximately 10 ohms should be measured.
b.Connect one meter lead to Red, connect the
remaining test lead to Yellow, approximately 10 ohms should be measured.
STEPPER MOTOR
c. Connect one meter lead to Red, connect the
remaining test lead to Brown, approximately 10 ohms should be measured.
d.Connect one meter lead to Red, connect the
remaining test lead to Black, approximately 10 ohms should be measured.
e.
Connect one meter lead to Red, connect the remaining test to the stepper motor case. No resistance should be measured INFINITY or Open”
PULL ARM THIS DIRECTION TO CLOSE THROTTLE
Figure 9. Throttle Positions 10 kW Units
STEPPER MOTOR
PULL ARM THIS DIRECTION TO CLOSE THROTTLE
Figure 10. Throttle Positions 10 kW Units
STEPPER MOTOR ARM
Figure 11. Throttle Positions 13/16 kW Units
Figure 12. Six Pin Connector Wire Colors
RESULTS:
1. If the stepper motor fails any part of Step 5 replace the stepper motor.
2. If the stepper motor passes all steps replace the Printed Circuit Board.
Page 47
Page 50
SECTION 2.4
DIAGNOSTIC TESTS
PART 2
AC GENERATORS
TEST 13 - CHECK AND ADJUST VOLTAGE
REGULATOR
DISCUSSION:
For additional information, refer to description and components Section 2.1.
PROCEDURE (SINGLE CYLINDER UNITS): With the frequency between 62-63 Hertz, slowly turn
the slotted potentiometer (Figure 13) until line voltage reads 247-252 volts.
PROCEDURE (V-TWIN ENGINE UNITS): With the frequency between 58-59 Hertz, slowly turn
the slotted potentiometer (Figure 13) until line voltage reads 250-252 volts.
NOTE: You must remove the access panel on top of the control panel to adjust the voltage regulator.
NOTE: The voltage regulator is housed above the generator control panel. The regulator maintains a voltage in direct proportion to frequency at a 2­to-1 ratio. For example, at 62 Hertz, line-to-neutral voltage will be 124 volts.
PROCEDURE:
1. Connect an accurate AC frequency meter and an AC voltmeter across the stator AC power winding leads.
2. Start the engine, let it stabilize and warm-up.
3. Apply electrical loads to the generator equal to the rated capacity of the unit.
4. Check the AC frequency and voltage.
a.Single Cylinder Units: Frequency should not
drop below approximately 58 Hertz. Voltage should not drop below about 230 volts.
b.V-Twin Engine Units: Frequency should not drop
below approximately 60 Hertz. Voltage should not drop below about 240 volts.
RESULTS:
1. If frequency and voltage drop excessively under load, go to Test 15.
2. If frequency and voltage under load are good, discon­tinue tests.
TEST 15 - CHECK FOR OVERLOAD CONDITION
Figure 13. Voltage Adjustment Potentiometer
RESULTS:
1. If the frequency and voltage are now good, discontinue tests.
2. If frequency is now good but voltage is high or low, go to Problem 1, Test 4.
TEST 14 - CHECK VOLTAGE AND FREQUENCY
UNDER LOAD
DISCUSSION: It is possible for the generator AC output frequency
and voltage to be good at no-load, but they may drop excessively when electrical loads are applied. This condition, in which voltage and frequency drop exces­sively when loads are applied, can be caused by (a) overloading the generator, (b) loss of engine power, or (c) a shorted condition in the stator windings or in one or more connected loads.
Page 48
DISCUSSION: An “overload” condition is one in which the generator
rated wattage/amperage capacity has been exceed­ed. To test for an overload condition on an installed unit, the best method is to use an ammeter. See “Measuring Current” in Section 1.4.
PROCEDURE:
Use a clamp-on ammeter to measure load current draw, with the generator running and all normal electrical loads turned on.
RESULTS:
1. If the unit is overloaded, reduce loads to the unit’s rated capacity.
2. If unit is not overloaded, but rpm and frequency drop excessively when loads are applied, go to Test 16.
TEST 16 - CHECK ENGINE CONDITION
DISCUSSION: If engine speed and frequency drop excessively under
load, the engine may be under-powered. An under­powered engine can be the result of a dirty air clean­er, loss of engine compression, faulty fuel settings, incorrect ignition timing, etc.
PROCEDURE: For engine testing, troubleshooting and repair pro-
cedures refer to Problem 11 in Section 4.3. For fur­ther engine repair information refer to the appropri­ate engine service manuals
.
Page 51
PART 3
“V-TYPE”
TABLE OF CONTENTS
PART TITLE PG#
3.1. Description and Components 50
3.2 Operational Analysis 54
3.3 Troubleshooting Flow Charts 64
PREPACKAGED
TRANSFER
SWITCHES
Air-cooled, Prepackaged
Automatic Standby Generators
3.1 Description and Components .......................... 50
General ............................................................50
Enclosure .........................................................50
Transfer Mechanism .........................................51
Transfer Relay .................................................51
Neutral Lug ......................................................52
Manual Transfer Handle ..................................52
Terminal Block .................................................52
Fuse Holder .....................................................53
3.2 Operational Analysis ....................................... 54
Utility Source Voltage Available .......................56
Utility Source Voltage Failure ..........................57
Transfer To Standby ........................................58
Transfer To Standby ........................................59
Utility Restored.................................................60
Utility Restored, Transfer Switch
De-energized .......................................61
Utility Restored,
Retransfer Back To Utility ....................62
Transfer Switch In Utility ...................................63
3.3 Troubleshooting Flow Charts ........................... 64
Introduction To Troubleshooting .......................64
Problem5-InAutomatic Mode,
No Transfer to Standby ........................64
Problem6-InAutomatic Mode, Generator
Starts When Loss of Utility Occurs, Generator Shuts Down When Utility Returns But There Is
No Retransfer To Utility Power .............65
Problem 7 - Blown F1 or F2 Fuse ....................65
3.4 Diagnostic Tests 66
3.4 Diagnostic Tests .............................................. 66
General ............................................................66
Test 21 - Check Voltage at
Terminal Lugs E1, E2 ..........................66
Test 22 - Check Voltage at
Standby Closing Coil C2 .....................67
Test 23 - Test Transfer Relay TR ......................67
Test 24 - Check Manual Transfer
Switch Operation .................................68
Test 25 - Test Limit Switch XB1 ........................69
Test 26 - Check 23 And 194
Wiring/Connections .............................69
Test 27- Check Voltage At
Terminal Lugs N1, N2 ..........................70
Test 28 - Check Voltage At Utility 1
And Utility 2 Ter minals .........................70
Test 29 - Check Voltage At
Utility Closing Coil C1 ..........................71
Test 30 - Check Fuses F1 And F2 ...................71
Test 31 - Test Limit Switch Xa1 ........................72
Test 32 - Continuity Test Of Wiring (C1) ...........72
Test 33 - Continuity Test Of Wiring (C2) ...........72
Test 34 - Check N1 And N2 Wiring ..................73
Test 35 - Check Transformer (Tx) .....................73
Page 49
Page 52
30
9
9
3
31
8
5
3
39
36
9
5
5
6
38
33
3
34
3435
3
8
3
3B
3A
SECTION 3.1
DESCRIPTION & COMPONENTS
PART 3
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
GENERAL
The prepackaged, “V-Type” transfer switch is rated 100 amps at 250 volts maximum. It is available in 2­pole configuration only and, for that reason, is usable with 1-phase systems only.
Prepackaged transfer switches do not have an intel ligence system of their own. Instead, automatic opera­tion of these transfer switches is controlled by a circuit board housed in the generator control panel.
ITEM DESCRIPTION
1 BOX GTS LOAD CENTER 2 COVER, 12 POSITION GTS LOAD CENTER 3 TRANSFER SWITCH HOME STANDBY 100A2P250V 4 SCREW TAPTITE M5-0.8 X 10 BP 5 SCREW TAPTITE 1/4-20 X 5/8 BP 6 LOCK WASHER, SPECIAL-1/4" 7 RELAY PANEL 12VDC DPDT 10A@240VA 8 BASE, MOUNTING 12 CIRCUIT 125A/240V 9 SCREW TAPTITE M4-0.7X10 BP 10 RIVET POP .156 X .160-.164/#20 11 WASHER FLAT 1/4 ZINC 12 PLUG 13 HARNESS ADAPTER PLATE 14 PANEL-SUB BREAKER BASE 15 TRIM VINYL BLACK 1/8GP 16 WASHER LOCK #10 17 NUT WING M6-1.0 18 HANDLE, TRANSFER SWITCH HOME STANDBY 19 HOLDER CABLE TIE 21 LUG DIS QK NI-S 10X45 DEG BR/T 22 SCREW PPHM #10-32 X 1/4 23 LUG SLDLSS 1/0-#14X9/16 AL/CU 24 BLOCK TERMINAL 20A 5 X 6 X 1100V 25 TIE WRAP 3.9" X .10" NAT’L UL 26 WASHER FLAT #8 ZINC 27 COVER, RELAY & TERM BLOCK 28 WIRE HARNESS,GTS LOAD CENTER (NOT SHOWN FOR CLARITY) 29 FUSE HOLDER 30 ASSEMBLY FUSE 5A X BUSS HLDR73591 31 PCB SUPPORT SNAP-IN 1-3/8" 32 CIRCT BRK 20 X 1 HOM120 33 CIRCT BRK 20 X 2 HOM220 34 CIRCT BRK 15 X 1 HOM115 35 CIRCT BRK 30 X 2 HOM230 36 COVER - HARNESS ENTRY 37 HARNESS, GTS TO EXT CONN BOX 38 WASHER LOCK M4 39 SCREW SW 1/4-20X5/8 N WA JS500 40 SCREW SWAGE 1/4-20 X 1/2 ZINC 41 SCREW PPHM M4-0.7 X 10 42 HARNESS,GTS TO MAIN PANEL
1
ENCLOSURE
The standard prepackaged, “V-Type” transfer switch enclosure is a NEMA 1 type (“NEMA” stands for “National Electrical Manufacturer’s Association”). Based on NEMA Standard 250, the NEMA 1 enclo­sure may be defined as one that is intended for indoor
­use primarily to provide a degree of protection against
contact with the enclosed equipment and where unusual service conditions do not exist.
2
1
1 2
1
2
2
2
Figure 1. Exploded View of V-Type Prepackaged Transfer Switch
Page 50
Page 53
“V-TYPE” PREPACKAGED
U
TILIT
Y
CLOSING
COIL(C1
)
S
TANDB
Y
CLOSING
COIL(C2
)
BRID
GE
RECTIFIE
R
BRID
GE
RECTIFIE
R
MANUA
L
TRANSFE
R
S
WITCH
(
XA1
)
S
WITCH
(
XB1
)
N2A A
A
B
126
2
05
B
E2
TRANSFER SWITCHES
PART 3
SECTION 3.1
DESCRIPTION & COMPONENTS
TRANSFER MECHANISM
The 2-pole transfer mechanism consists of a pair of moveable LOAD contacts, a pair of stationary UTILITY contacts, and a pair of stationary STANDBY contacts. The load contacts can be connected to the utility contacts by a utility closing coil; or to the stand­by contacts by a standby closing coil. In addition, the load contacts can be actuated to either the UTILITY or STANDBY side by means of a manual transfer handle. See Figures 2 and 3.
STANDBY
LOAD
Figure 2. Load Connected to Utility Power Source
UTILITY
source side. Energizing the coil moves the load con­tacts to an overcenter position; limit switch action then opens the circuit and spring force will complete the transfer action to “Standby”. This coil’s bridge rectifier is also sealed in the coil wrappings. Replace the coil and bridge rectifier as a unit.
LIMIT SWITCHES XA1 AND XB1: Switches are mechanically actuated by load contacts
movement. When the load contacts are connected to the utility contacts, limit switch XA1 opens the utility circuit to utility closing coil C1 and limit switch XB1 closes the standby circuit to standby closing coil C2. The limit switches “arm” the system for retransfer back to UTILITY when the load contacts are connected to the STANDBY side. Conversely, when the load con­tacts are connected to the UTILITY side, the switches “arm” the system for transfer to STANDBY. An open condition in limit switch XA1 will prevent retransfer to “Utility”. An open switch XB1 will prevent transfer to STANDBY.
STANDBY
LOAD
Figure 3. Load Connected to Standby Power Source
UTILITY CLOSING COIL C1: See Figure 4. This coil is energized by rectified util-
ity source power, to actuate the load contacts to the UTILITY power source side. When energized, the coil will move the main contacts to an “overcenter” posi­tion. A limit switch will then be actuated to open the circuit and spring force will complete the retransfer to STANDBY. A bridge rectifier, which changes the utility source alternating current (AC) to direct current (DC), is sealed in the coil wrappings. If coil or bridge recti-
fier replacement becomes necessary, the entire coil and bridge assembly should be replaced.
STANDBY CLOSING COIL C2: Coil C2 is energized by rectified standby source
power, to actuate the load contacts to their “Standby”
UTILITY
Figure 4. The “V-Type” Transfer Mechanism
TRANSFER RELAY
Transfer relay operation is controlled by a circuit board. That circuit board is a part of a control panel assembly, mounted on the standby generator set.
Figure 5 shows the transfer relay pictorially and sche matically. Relay operation may be briefly described as follows:
1. Generator battery voltage (12 volts DC) is available to the transfer relay coil from the generator circuit board, via Wire 194 and Relay Terminal A.
a.The 12 volts DC circuit is completed through the
transfer relay coil and back to the generator cir­cuit board, via Wire 23.
b.Circuit board action normally holds the Wire
23 circuit open to ground and the relay is de­energized.
Page 51
-
Page 54
SECTION 3.1
DESCRIPTION & COMPONENTS
PART 3
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
c. When de-energized, the relay’s normally open
contacts are open and its normally-closed con­tacts are closed.
d.The normally-closed relay contacts will deliver
utility source power to the utility closing circuit of the transfer mechanism.
e.The normally open relay contacts will deliver
standby source power to the transfer mecha nism’s standby closing circuit.
194
23
126
205
7
1
69
A
B
N1A
E1
NEUTRAL LUG
The standby generator is equipped with an UNGROUNDED neutral. The neutral lug in the trans­fer switch is isolated from the switch enclosure.
MANUAL TRANSFER HANDLE
­The manual transfer handle is retained in the transfer switch enclosure by means of a wing stud. Use the handle to manually actuate the transfer mechanism load contacts to either the UTILITY or STANDBY source side.
Instructions on use of the manual transfer handle may be found in Part 5, “Operational Tests and Adjustments”.
TERMINAL BLOCK
During system installation, this 5-point terminal block must be properly interconnected with an identically labeled terminal block in the generator control panel assembly.
N1 N2 23 194
Figure 5. Transfer Relay Schematic
2. During automatic system operation, when the genera­tor circuit board “senses” that utility source voltage has dropped out, the circuit board will initiate engine crank­ing and startup.
3. When the circuit board “senses” that the engine has started, an “engine warm-up timer” on the circuit board starts timing.
4. When the “engine warm-up timer” has timed out,
circuit
board action completes the Wire 23 circuit to ground.
a.The transfer relay then energizes. b.The relay’s normally-closed contacts open and
its normally open contacts close.
c. When the normally open contacts close, standby
source power is delivered to the standby closing coil and transfer to “Standby” occurs.
5. When the generator circuit board “senses” that utility source voltage has been restored above a preset level, the board will open the Wire 23 circuit to ground.
a.The transfer relay will de-energize, its normally-
closed contacts will close and its normally open contacts will open.
b.When the normally-closed relay contacts close,
utility source voltage is delivered to the utility closing coil to energize that coil.
c. Retransfer back to UTILITY occurs.
23
194
UTILITY 1
UTILITY 2
Figure 6. Transfer Switch Terminal Block
Terminals used on the terminal block are identified as Utility N1 and N2; 23 and 194.
UTILITY N1 AND N2: Interconnect with identically labeled terminals in the
generator control panel assembly. This is the utility voltage signal to the circuit board. The signal is deliv­ered to a step-down transformer in the control module assembly and the resultant reduced voltage is then delivered to the circuit board. Utility 1 and 2 power is used by the circuit board as follows:
• If utility source voltage should drop below a pre set level, circuit board action will initiate automatic cranking and startup, followed by automatic transfer to the standby source.
• Utility source voltage is used to operate a battery trickle charge circuit which helps to maintain battery state of charge during non-operating periods.
-
Page 52
Page 55
“V-TYPE” PREPACKAGED
N1A N2A
N1
N2
F1
F2
TRANSFER SWITCHES
PART 3
TERMINALS 23 AND 194: These terminals connect the transfer relay to the
generator circuit board. See “Transfer Relay” in Section 3.1.
FUSE HOLDER
The fuse holder holds two (2) fuses, designated as fuses F1 and F2. Each fuse is rated 5 amperes.
FUSES F1, F2: These two fuses protect the terminal board UTILITY 1
and 2 circuit against overload.
SECTION 3.1
DESCRIPTION & COMPONENTS
Figure 7. The Fuse Holder
Page 53
Page 56
SECTION 3.2
OPERATIONAL ANALYSIS
OPERATIONAL ANALYSIS
Figure 1 is a schematic for a typical “V-Type” transfer switch.
PART 3
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
E1
N1A
E1
N1A
B
B
N2A
A
79
174
126
126
NO
XA
COM
VR1
9
36
205
B
NC NC
C1
205
COM
194
TR
23
A
B
N1A
N1A
N2A
NO
XB
VR2
C2
AT S
N2A
N2A
T1 T2
194
23
F2
E2
E2
F1
NEUTRAL CONNECTION INSIDE SWITCH
N1AN1A
E1
E1
E1
E2
194
23
OPEN
N2
N1
E1
E2
CIRCUIT 14
CIRCUIT 13
CIRCUIT 10
CIRCUIT 9
CIRCUIT 6
194
12Vdc TRANSER COIL
23
N2
240VAC OUTPUT
N1
BLACK
RED
NEUTRAL (WHITE)
NEUTRAL (WHITE)
RED (MAIN 2)
BLACK (MAIN 1)
TS TO GENERATOR CONTROL PANEL
TO GENERATOR OUTPUT CIRCUIT BREAKER
240VAC TO MAIN DISTRIBUTION PANEL
N2A
B
E2
B
LEGEND ATS-AUTOMATIC TRANSFER SWITCH C1-UTILITY COIL & RECTIFIER C2-GENERATOR COIL & RECTIFIER F1,F2-5A, 600V FUSE LC-CIRCUIT BREAKER (LOADS) TR-TRANSFER RELAY TS-TERMINAL STRIP XA,XB-LIMIT SWITCHES
Page 54
CIRCUIT 5
CIRCUIT 2
T1
T2
E2
CIRCUIT 1
CIRCUIT 3
CIRCUIT 4
CIRCUIT 7
CIRCUIT 8
CIRCUIT 11
CIRCUIT 12
CIRCUIT 15
CIRCUIT 16
8 CIRCUIT LOAD CENTER
10 CIRCUIT LOAD CENTER
16 CIRCUIT LOAD CENTER
12 CIRCUIT LOAD CENTER
LC
Figure 1. Schematic
Page 57
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
PART 3
Figure 2 is a wiring diagram for a typical “V-Type” transfer switch.
SECTION 3.2
OPERATIONAL ANALYSIS
Figure 2. Wiring Diagram
Page 55
Page 58
SECTION 3.2
OPERATIONAL ANALYSIS
PART 3
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
UTILITY SOURCE VOLTAGE AVAILABLE
Figure 3 is a schematic representation of the transfer switch with utility source power available. The circuit condi­tion may be briefly described as follows:
• Utility source voltage is available to terminal lugs N1 and N2 of the transfer mechanism, transfer switch is in the UTILITY position and source voltage is available to T1, T2 and customer load.
• Utility source voltage is available to limit switch (XA1) via the normally-closed transfer relay contacts (1 and 7) and Wire 126. However, XA1 is open and the Circuit to the utility closing coil is open.
• Utility voltage “sensing” signals are delivered to a circuit board on the generator, via Wire N1A, a 5 amp fuse (F1), transfer switch Terminal N1, generator Terminal N1 and a sensing transformer. The second line of the util ity voltage “sensing” circuit is via Wire N2A, a 5 amp Fuse (F2), transfer switch Terminal N2, generator Terminal N2, and the sensing transformer.
-
E1
N1A
E1
N1A
B
N2A
79
174
126
B
126
NO
XA
COM
A
9
36
205
B
NC NC
VR1
C1
205
COM
194
TR
23
N2A
XB
A
B
N1A
N1A
NO
VR2
C2
AT S
N2A
N2A
T1 T2
194
23
F2
N1AN1A
E1
E1
E2
F1
E1
E2
NEUTRAL CONNECTION INSIDE SWITCH
E2
194
23
OPEN
N2
N1
E1
E2
CIRCUIT 14
CIRCUIT 13
CIRCUIT 10
CIRCUIT 9
CIRCUIT 6
194
12VDC TRANSER COIL
23
N2
240VAC OUTPUT
N1
BLACK
RED
NEUTRAL (WHITE)
NEUTRAL (WHITE)
RED (MAIN 2)
BLACK (MAIN 1)
TS TO GENERATOR CONTROL PANEL
TO GENERATOR OUTPUT CIRCUIT BREAKER
240VAC TO MAIN DISTRIBUTION PANEL
N2A
B
E2
B
LEGEND ATS-AUTOMATIC TRANSFER SWITCH C1-UTILITY COIL & RECTIFIER C2-GENERATOR COIL & RECTIFIER F1,F2-5A, 600V FUSE LC-CIRCUIT BREAKER (LOADS) TR-TRANSFER RELAY TS-TERMINAL STRIP XA,XB-LIMIT SWITCHES
Figure 3. Utility Source Power Available
Page 56
E2
T1
T2
UTILITY
DC
GROUND
GENERATOR
LC
CIRCUIT 5
CIRCUIT 2
CIRCUIT 1
CIRCUIT 3
CIRCUIT 4
CIRCUIT 7
CIRCUIT 8
CIRCUIT 11
CIRCUIT 12
CIRCUIT 15
CIRCUIT 16
8 CIRCUIT LOAD CENTER
10 CIRCUIT LOAD CENTER
16 CIRCUIT LOAD CENTER
12 CIRCUIT LOAD CENTER
Page 59
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
PART 3
OPERATIONAL ANALYSIS
SECTION 3.2
UTILITY SOURCE VOLTAGE FAILURE
If utility source voltage should drop below a preset value, the generator circuit board will sense the dropout. That circuit board will then initiate generator cranking and startup after a time delay circuit times out.
Figure 4 is a schematic representation of the transfer switch with generator power available, waiting to transfer.
• Generator voltage available E1, E2.
• Circuit board action holding Wire 23 open to ground.
• Power available to standby coil C2, upon closure of TR, normally open contacts (9 & 6) will close and initiate a transfer.
E1
N1A
E1
N1A
B
N2A
79
174
126
B
126
NO
XA
COM
A
9
36
205
B
NC NC
VR1
C1
205
COM
194
TR
23
A
B
N1A
N1A
N2A
NO
XB
VR2
C2
AT S
N2A
N2A
T1 T2
194
194
23
F2
N1AN1A
E1
E1
E2
F1
E1
E2
NEUTRAL CONNECTION INSIDE SWITCH
E2
23
OPEN
N2
N1
E1
E2
CIRCUIT 14
CIRCUIT 13
CIRCUIT 10
CIRCUIT 9
CIRCUIT 6
194
12VDC TRANSER COIL
23
N2
240VAC OUTPUT
N1
BLACK
RED
NEUTRAL (WHITE)
NEUTRAL (WHITE)
RED (MAIN 2)
BLACK (MAIN 1)
TS TO GENERATOR CONTROL PANEL
TO GENERATOR OUTPUT CIRCUIT BREAKER
240VAC TO MAIN DISTRIBUTION PANEL
N2A
B
E2
B
LEGEND ATS-AUTOMATIC TRANSFER SWITCH C1-UTILITY COIL & RECTIFIER C2-GENERATOR COIL & RECTIFIER F1,F2-5A, 600V FUSE LC-CIRCUIT BREAKER (LOADS) TR-TRANSFER RELAY TS-TERMINAL STRIP XA,XB-LIMIT SWITCHES
Figure 4. Generator Power Available, Waiting to Transfer.
E2
T1
T2
UTILITY
DC
GROUND
GENERATOR
LC
CIRCUIT 5
CIRCUIT 2
CIRCUIT 1
CIRCUIT 3
CIRCUIT 4
CIRCUIT 7
CIRCUIT 8
CIRCUIT 11
CIRCUIT 12
CIRCUIT 15
CIRCUIT 16
8 CIRCUIT LOAD CENTER
10 CIRCUIT LOAD CENTER
16 CIRCUIT LOAD CENTER
12 CIRCUIT LOAD CENTER
Page 57
Page 60
SECTION 3.2
OPERATIONAL ANALYSIS
PART 3
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
TRANSFER TO STANDBY
The generator circuit board delivers 12 volts DC to the transfer relay, via Terminal 194 and back to the circuit board via Terminal 23. However, circuit board action holds the Wire 23 circuit open and the transfer relay remains de-energized. On generator startup, an “engine warm-up timer” on the generator circuit board starts timing. When that timer has timed out, circuit board action completes the Wire 23 circuit to ground. The transfer relay then ener­gizes, its normally open contacts close, and standby source voltage is delivered to the standby closing coil via Wires E1 and E2, the transfer relay (TR) contacts, limit switch (XB1), Wire “B”, and a bridge rectifier. The standby closing coil energizes and the main contacts actuate to their “Standby” side.
E1
N1A
E1
N1A
B
N2A
79
174
126
B
126
NO
XA
COM
A
9
36
205
B
NC NC
VR1
C1
205
COM
194
TR
23
N2A
A
B
N1A
N1A
NO
XB
VR2
C2
AT S
N2A
N2A
T1 T2
194
23
194
23
OPEN
F2
N1AN1A
E1
E1
E2
F1
E1
E2
NEUTRAL CONNECTION INSIDE SWITCH
E2
N2
E2
CIRCUIT 14
CIRCUIT 13
CIRCUIT 10
CIRCUIT 9
CIRCUIT 6
N1
E1
194
12VDC TRANSER COIL
23
N2
240VAC OUTPUT
N1
BLACK
RED
NEUTRAL (WHITE)
NEUTRAL (WHITE)
RED (MAIN 2)
BLACK (MAIN 1)
TS TO GENERATOR CONTROL PANEL
TO GENERATOR OUTPUT CIRCUIT BREAKER
240VAC TO MAIN DISTRIBUTION PANEL
N2A
B
E2
B
LEGEND ATS-AUTOMATIC TRANSFER SWITCH C1-UTILITY COIL & RECTIFIER C2-GENERATOR COIL & RECTIFIER F1,F2-5A, 600V FUSE LC-CIRCUIT BREAKER (LOADS) TR-TRANSFER RELAY TS-TERMINAL STRIP XA,XB-LIMIT SWITCHES
Figure 5. Transfer Action to Standby Position
Page 58
E2
T1
T2
UTILITY
DC
GROUND
GENERATOR
LC
CIRCUIT 5
CIRCUIT 2
CIRCUIT 1
CIRCUIT 3
CIRCUIT 4
CIRCUIT 7
CIRCUIT 8
CIRCUIT 11
CIRCUIT 12
CIRCUIT 15
CIRCUIT 16
8 CIRCUIT LOAD CENTER
10 CIRCUIT LOAD CENTER
16 CIRCUIT LOAD CENTER
12 CIRCUIT LOAD CENTER
Page 61
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
PART 3
OPERATIONAL ANALYSIS
SECTION 3.2
TRANSFER TO STANDBY
When the standby coil is energized it pulls the transfer switch mechanism to a overcenter position towards the standby power source side, the transfer switch mechanically snaps to the standby position. On closure of the main contacts to the standby power source side, limit switches XA1 and XB1 are mechanically actuated to “arm” the circuit for re- transfer to utility power source side.
Generator power from E1 and E2 is now connected to the customer load through T1 and T2.
E1
N1A
E1
N1A
B
N2A
79
174
126
B
126
NO
XA
COM
A
9
36
205
B
NC NC
VR1
C1
205
COM
194
TR
23
N2A
XB
A
B
N1A
N1A
NO
VR2
C2
AT S
N2A
N2A
T1 T2
194
194
23
F2
N1AN1A
E1
E1
E2
F1
E1
E2
NEUTRAL CONNECTION INSIDE SWITCH
E2
23
OPEN
N2
E2
CIRCUIT 14
CIRCUIT 13
CIRCUIT 10
CIRCUIT 9
CIRCUIT 6
N1
E1
194
12VDC TRANSER COIL
23
N2
240VAC OUTPUT
N1
BLACK
RED
NEUTRAL (WHITE)
NEUTRAL (WHITE)
RED (MAIN 2)
BLACK (MAIN 1)
TS TO
GENERATOR
CONTROL PANEL
TO GENERATOR OUTPUT CIRCUIT BREAKER
240VAC TO MAIN DISTRIBUTION PANEL
N2A
B
B
E2
LEGEND ATS-AUTOMATIC TRANSFER SWITCH C1-UTILITY COIL & RECTIFIER C2-GENERATOR COIL & RECTIFIER F1,F2-5A, 600V FUSE LC-CIRCUIT BREAKER (LOADS) TR-TRANSFER RELAY TS-TERMINAL STRIP XA,XB-LIMIT SWITCHES
CIRCUIT 5
CIRCUIT 2
T1
T2
E2
UTILITY
DC
GROUND
GENERATOR
CIRCUIT 1
CIRCUIT 3
CIRCUIT 4
CIRCUIT 7
CIRCUIT 8
CIRCUIT 11
CIRCUIT 12
CIRCUIT 15
CIRCUIT 16
LC
Figure 6. Generator Powering Load.
8 CIRCUIT LOAD CENTER
10 CIRCUIT LOAD CENTER
16 CIRCUIT LOAD CENTER
12 CIRCUIT LOAD CENTER
Page 59
Page 62
SECTION 3.2
OPERATIONAL ANALYSIS
PART 3
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
UTILITY RESTORED
Utility voltage is restored and is available to Terminals N1 and N2. The utility voltage is sensed by the generators circuit board. If it is above a preset value for a preset time interval a transfer back to utility power will occur.
E1
N1A
E1
N1A
B
N2A
79
174
126
B
126
NO
XA
COM
A
9
36
205
B
NC NC
VR1
C1
205
COM
194
TR
23
N2A
XB
A
B
N1A
N1A
NO
VR2
C2
AT S
N2A
N2A
T1 T2
194
23
194
23
OPEN
F2
N1AN1A
E1
E1
E2
F1
E1
E2
NEUTRAL CONNECTION INSIDE SWITCH
E2
N2
N1
E1
E2
CIRCUIT 14
CIRCUIT 13
CIRCUIT 10
CIRCUIT 9
CIRCUIT 6
194
12VDC TRANSER COIL
23
N2
240VAC OUTPUT
N1
BLACK
RED
NEUTRAL (WHITE)
NEUTRAL (WHITE)
RED (MAIN 2)
BLACK (MAIN 1)
TS TO GENERATOR CONTROL PANEL
TO GENERATOR OUTPUT CIRCUIT BREAKER
240VAC TO MAIN DISTRIBUTION PANEL
N2A
B
E2
B
LEGEND ATS-AUTOMATIC TRANSFER SWITCH C1-UTILITY COIL & RECTIFIER C2-GENERATOR COIL & RECTIFIER F1,F2-5A, 600V FUSE LC-CIRCUIT BREAKER (LOADS) TR-TRANSFER RELAY TS-TERMINAL STRIP XA,XB-LIMIT SWITCHES
Figure 7. Utility Restored, Generator Still Providing Output to Load.
Page 60
E2
T1
T2
UTILITY
DC
GROUND
GENERATOR
LC
CIRCUIT 5
CIRCUIT 2
CIRCUIT 1
CIRCUIT 3
CIRCUIT 4
CIRCUIT 7
CIRCUIT 8
CIRCUIT 11
CIRCUIT 12
CIRCUIT 15
CIRCUIT 16
8 CIRCUIT LOAD CENTER
10 CIRCUIT LOAD CENTER
16 CIRCUIT LOAD CENTER
12 CIRCUIT LOAD CENTER
Page 63
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
PART 3
OPERATIONAL ANALYSIS
SECTION 3.2
UTILITY RESTORED, TRANSFER SWITCH DE-ENERGIZED
After the preset time interval expires the circuit board will open the Wire 23 circuit to ground. The transfer relay de­energizes, it’s normally closed contacts close, and utility source voltage is delivered to the utility closing coil (C1), via Wires N1A and N2A, closed Transfer Relay Contacts 1 and 7, and Limit Switch XA1.
E1
N1A
E1
N1A
B
N2A
79
174
126
B
126
NO
XA
COM
A
9
36
205
B
NC NC
VR1
C1
205
COM
194
TR
23
A
B
N1A
N1A
N2A
NO
XB
VR2
C2
AT S
N2A
N2A
T1 T2
194
194
23
F2
N1AN1A
E1
E1
E2
F1
E1
E2
NEUTRAL CONNECTION INSIDE SWITCH
E2
23
OPEN
N2
E2
CIRCUIT 14
CIRCUIT 13
CIRCUIT 10
CIRCUIT 9
CIRCUIT 6
N1
E1
194
12VDC TRANSER COIL
23
N2
240VAC OUTPUT
N1
BLACK
RED
NEUTRAL (WHITE)
NEUTRAL (WHITE)
RED (MAIN 2)
BLACK (MAIN 1)
TS TO GENERATOR CONTROL PANEL
TO GENERATOR OUTPUT CIRCUIT BREAKER
240VAC TO MAIN DISTRIBUTION PANEL
N2A
B
E2
B
LEGEND ATS-AUTOMATIC TRANSFER SWITCH C1-UTILITY COIL & RECTIFIER C2-GENERATOR COIL & RECTIFIER F1,F2-5A, 600V FUSE LC-CIRCUIT BREAKER (LOADS) TR-TRANSFER RELAY TS-TERMINAL STRIP XA,XB-LIMIT SWITCHES
Figure 8. Utility Restored, Transfer Relay De-energized.
E2
T1
T2
UTILITY
DC
GROUND
GENERATOR
LC
CIRCUIT 5
CIRCUIT 2
CIRCUIT 1
CIRCUIT 3
CIRCUIT 4
CIRCUIT 7
CIRCUIT 8
CIRCUIT 11
CIRCUIT 12
CIRCUIT 15
CIRCUIT 16
8 CIRCUIT LOAD CENTER
10 CIRCUIT LOAD CENTER
16 CIRCUIT LOAD CENTER
12 CIRCUIT LOAD CENTER
Page 61
Page 64
SECTION 3.2
OPERATIONAL ANALYSIS
PART 3
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
UTILITY RESTORED, RETRANSFER BACK TO UTILITY
As the utility coil pulls the transfer switch to an OVER CENTER position, the switch mechanically snaps to Utility. On closure of the main contacts to the utility power source side, Limit Switches XA1 and XB1 are mechanically actuated to “arm” the circuit for transfer to standby.
E1
N1A
E1
N1A
B
N2A
79
174
126
B
126
NO
XA
COM
A
9
36
205
B
NC NC
VR1
C1
205
COM
194
TR
23
N2A
A
B
N1A
N1A
NO
XB
VR2
C2
AT S
N2A
N2A
T1 T2
194
23
194
23
OPEN
F2
N1AN1A
E1
E1
E2
F1
E1
E2
NEUTRAL CONNECTION INSIDE SWITCH
E2
N2
N1
E1
E2
CIRCUIT 14
CIRCUIT 13
CIRCUIT 10
CIRCUIT 9
CIRCUIT 6
194
12VDC TRANSER COIL
23
N2
240VAC OUTPUT
N1
BLACK
RED
NEUTRAL (WHITE)
NEUTRAL (WHITE)
RED (MAIN 2)
BLACK (MAIN 1)
TS TO GENERATOR CONTROL PANEL
TO GENERATOR OUTPUT CIRCUIT BREAKER
240VAC TO MAIN DISTRIBUTION PANEL
N2A
B
E2
B
LEGEND ATS-AUTOMATIC TRANSFER SWITCH C1-UTILITY COIL & RECTIFIER C2-GENERATOR COIL & RECTIFIER F1,F2-5A, 600V FUSE LC-CIRCUIT BREAKER (LOADS) TR-TRANSFER RELAY TS-TERMINAL STRIP XA,XB-LIMIT SWITCHES
Figure 9. Utility Restored, Retransfer Back to Utility.
Page 62
E2
T1
T2
UTILITY
DC
GROUND
GENERATOR
LC
CIRCUIT 5
CIRCUIT 2
CIRCUIT 1
CIRCUIT 3
CIRCUIT 4
CIRCUIT 7
CIRCUIT 8
CIRCUIT 11
CIRCUIT 12
CIRCUIT 15
CIRCUIT 16
8 CIRCUIT LOAD CENTER
10 CIRCUIT LOAD CENTER
16 CIRCUIT LOAD CENTER
12 CIRCUIT LOAD CENTER
Page 65
“V-TYPE” PREPACKAGED
NEUTRAL CONNECTION INSIDE SWITCH
XB
NO
C1
COM
XA
VR1
NC NC
COM
C2
VR2
NO
TR
194
23
174
79
36
9
F2
CIRCUIT 10
BLACK (MAIN 1)
12VDC TRANSER COIL
RED (MAIN 2)
NEUTRAL (WHITE)
NEUTRAL (WHITE)
23
OPEN
F1
N2
N1
194
23
BLACK
RED
N2
N1
194
240VAC TO
TO GENERATOR OUTPUT
PANEL
MAIN DISTRIBUTION
LC-CIRCUIT BREAKER (LOADS)
F1,F2-5A, 600V FUSE
XA,XB-LIMIT SWITCHES
TS-TERMINAL STRIP
TR-TRANSFER RELAY
C2-GENERATOR COIL & RECTIFIER
LEGEND
C1-UTILITY COIL & RECTIFIER
T1
T2
T1 T2
E2
E2
E2
E2
E1
E1
N1A
N1A
N2A
N2A
B
B
B
B
B
E1
E1
E1
N1AN1A
N1A
194
23
E1
E2
205
205
126
126
E2
N1A
N2A
N2A
A
N2A
240VAC OUTPUT
GENERATOR
TS TO
CONTROL PANEL
CIRCUIT BREAKER
A
B
AT S
ATS-AUTOMATIC TRANSFER SWITCH
LC
CIRCUIT 9
CIRCUIT 6
CIRCUIT 5
CIRCUIT 2
CIRCUIT 1
CIRCUIT 3
CIRCUIT 4
CIRCUIT 7
CIRCUIT 8
CIRCUIT 11
CIRCUIT 12
CIRCUIT 13
CIRCUIT 14
CIRCUIT 16
CIRCUIT 15
16 CIRCUIT LOAD CENTER
12 CIRCUIT LOAD CENTER
10 CIRCUIT LOAD CENTER
8 CIRCUIT LOAD CENTER
UTILITY
GENERATOR
GROUND
DC
TRANSFER SWITCHES
PART 3
OPERATIONAL ANALYSIS
SECTION 3.2
TRANSFER SWITCH IN UTILITY
When the transfer switch returns to the utility side, generator shutdown occurs after approximately one (1) minute.
Figure 10. Transfer Switch in UTILITY.
Page 63
Page 66
SECTION 3.3
TROUBLESHOOTING FLOW CHARTS
PART 3
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
INTRODUCTION TO TROUBLESHOOTING
The first step in troubleshooting is to correctly identify the problem. Once that is done, the cause of the problem can be found by performing the tests in the appropriate flow chart.
Test numbers assigned in the flow charts are identical to test numbers in Section 3.4, “Diagnostic Tests.” Section
3.4 provides detailed instructions for performance of each test.
Problem 5 - In Automatic Mode, No Transfer to Standby
TEST 21 - CHECK
VO LTAG E AT
TERMINAL LUGS
E1 & E2
GOOD
TEST 22 - CHECK VOLTAGE
AT STANDBY CLOSING COIL
C2 AND LIMIT SWITCH XB1
C2 COIL VOLTAGE
BAD / LIMIT SWITCH
XB1 VOLTAGE BAD
BAD
C2 COIL VOLTAGE
GOOD BUT NO
TRANSFER
C2 COIL VOLTAGE
BAD / LIMIT SWITCH
XB1 VOLTAGE GOOD
FIND CAUSE OF NO AC
OUTPUT TO TRANSFER
SWITCH FROM
GENERATOR
TEST 24 - CHECK
MANUAL TRANSFER
SWITCH OPERATION
TEST 25 - TEST
LIMIT SWITCH
XB1
BAD
GOOD
BAD
GOOD
REPAIR OR
REPLACE
REPLACE STANDBY
COIL C2
REPLACE
LIMIT
SWITCH
REPAIR
WIRE #B
TEST 23 - TEST
TRANSFER
RELAY
BAD
REPLACE
GOOD
Page 64
TEST 33 -
CONTINUITY TEST
OF WIRING (C2)
GOOD
BAD
TEST 26 - CHECK #23
AND #194 WIRING
CONNECTIONS
REPAIR OR
REPLACE
Page 67
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
PART 3
TROUBLESHOOTING FLOW CHARTS
SECTION 3.3
Problem 6 - In Automatic Mode, Generator Starts When Loss of Utility Occurs, Generator Shuts
Down When Utility Returns But There Is No Retransfer To Utility Power
TEST 29 - CHECK
VOLTAGE ATUTILITY
CLOSING COIL C1 AND
LIMIT SWITCH XA1
C1 COIL VOLTAGE
BAD / LIMIT
SWITCH XA1
VOLTAGE BAD
TEST 23 - TEST
TRANSFER
RELAY
GOOD
C1 COIL VOLTAGE
GOOD BUT NO
TRANSFER
C1 COIL VOLTAGE
BAD / LIMIT
SWITCH XA1
VOLTAGE GOOD
GOOD
BAD
CONTINUITY TEST
OF WIRING (C1)
REPLACE
TEST 24 - CHECK
MANUAL TRANSFER
SWITCH OPERATION
TEST 31 -
TEST LIMIT
SWITCH XA1
TEST 32 -
TEST 26 - CHECK
#23 AND #194
WIRING
CONNECTIONS
BAD
BAD
GOOD
GOOD
REPLACE
UTILITY COIL C1
REPAIR
WIRE #A
REPLACE
LIMIT
SWITCH
REPAIR OR
REPLACE
TEST 30 - CHECK
FUSE F1 & F2
GOOD
FINISH
BAD
Problem 7 - Blown F1 or F2 Fuse
TEST 34 - CHECK
N1 & N2 WIRING
BAD
REPAIR OR REPLACE
GOOD GOOD
TEST 35 - CHECK
TRANSFORMER TX
BAD
REPLACE
FINISH
Page 65
Page 68
SECTION 3.4
DIAGNOSTIC TESTS
PART 3
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
GENERAL
Test numbers in this section correspond to the num­bered tests in Section 3.3, “Troubleshooting Flow Charts”. When troubleshooting, first identify the problem. Then, perform the diagnostic tests in the sequence given in the flow charts.
TEST 21 - CHECK VOLTAGE AT TERMINAL
LUGS E1, E2
DISCUSSION: In automatic mode, the standby closing coil (C2) must
be energized by standby generator output if transfer to the “Standby” source is to occur. Transfer to “Standby” cannot occur unless that power supply is available to
the transfer switch.
DANGER: BE CAREFUL! HIGH AND
DANGEROUS VOLTAGES ARE PRESENT AT TERMINAL LUGS E1 AND E2 WHEN THE GENERATOR IS RUNNING. AVOID CONTACT WITH HIGH VOLTAGE TERMINALS OR DANGEROUS AND POSSIBLY LETHAL ELECTRICAL SHOCK MAY RESULT. DO NOT PERFORM THIS VOLTAGE TEST WHILE STANDING ON WET OR DAMP GROUND, WHILE BAREFOOT, OR WHILE HANDS OR FEET ARE WET.
PROCEDURE:
1. If the generator engine has started automatically (due to a utility power source outage) and is running, check the position of the generator main circuit breaker. The circuit breaker must be set to its “On” or “Closed” position. When you are sure the generator main circuit breaker is set to ON (or closed), check the voltage at transfer mechanism Terminal Lugs E1 and E2 with an accurate AC voltmeter or with an accurate volt-ohm-milliammeter (VOM). The generator line-to line voltage should be indicated.
2. If the generator has been shut down, proceed as follows:
a.On the generator control panel, set the AUTO-
OFF-MANUAL switch to OFF.
b.Turn off all power voltage supplies to the trans-
fer switch. Both the utility and standby power supplies must be positively turned off before proceeding.
c. Check the position of the transfer mechanism
main contacts. The moveable LOAD contacts must be connected to the stationary UTILITY source contacts. If necessary, manually actuate the main contacts to the “Utility” power source side.
d.Actuate the generator main line circuit breaker
to its “On” or “Closed” position. The utility power supply to the transfer switch must be turned off.
BRIDGE RECTIFIER
UTILITY CLOSING COIL (C1)
LIMIT SWITCH (XB1)
STANDBY CLOSING COIL (C2)
BRIDGE RECTIFIER
LIMIT SWITCH (XA1)
MANUAL TRANSFER LEVER
N2A A
E2
N1
N2
A
126
205
E1
E2
T2
B
T1
B
Figure 1. The “V-Type” Transfer Mechanism
Page 66
Page 69
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
PART 3
SECTION 3.4
DIAGNOSTIC TESTS
e.Set the generator AUTO-OFF-MANUAL switch
to AUTO. (1) The generator should crank and start. (2) When the generator starts, an “engine
warm-up timer” should start timing. After about 15 seconds, the transfer relay should energize and transfer to the “Standby” source should occur.
f. If transfer to “Standby” does NOT occur, check
the voltage across transfer switch Terminal Lugs
E1 and E2. The generator line-to-line voltage
should be indicated.
RESULTS:
1. If normal transfer to “Standby” occurs, discontinue tests.
2. If transfer to “Standby” does NOT occur and no voltage is indicated across Terminal Lugs E1/E2, determine why generator AC output has failed.
3. If transfer to “Standby” does NOT occur and voltage reading across Terminal Lugs E1/E2 is good, go on to Test 22.
TEST 22 - CHECK VOLTAGE AT STANDBY
CLOSING COIL C2
DISCUSSION: Standby source voltage is used to energize the stand-
by closing coil and actuate the main contacts to their “Standby” source side. Standby source alternating current (AC) is changed to direct current (DC) by a bridge rectifier before reaching the closing coil. This test will determine if voltage is available to the closing coil.
If normal source voltage is available to the terminals of the closing coil but transfer to “Standby” does not occur, look for (a) binding or sticking in the transfer mechanism, (b) a defective coil, or (c) a bad bridge rectifier. The coil and the bridge rectifier must be replaced as a unit.
PROCEDURE:
1. Set the generator main line circuit breaker to the OFF or “Open” position.
2. Set the generators AUTO-OFF-MANUAL switch to the OFF position.
3. Set a VOM to measure AC voltage.
DANGER: BE CAREFUL! HIGH AND
DANGEROUS VOLTAGES ARE PRESENT AT TERMINAL LUGS WHEN THE GENERATOR IS RUNNING. AVOID CONTACT WITH HIGH VOLTAGE TERMINALS OR DANGEROUS AND POSSIBLY LETHAL ELECTRICAL SHOCK MAY RESULT. DO NOT PERFORM THIS
VOLTAGE TEST WHILE STANDING ON WET OR DAMP GROUND, WHILE BAREFOOT, OR WHILE HANDS OR FEET ARE WET.
4. Disconnect Wire E2 from the standby closing coil (C2). Connect one meter test Lead to Wire E2. Use a suitable and safe connection to this wire, such as an alligator clip that attaches to the meter test probe. Isolate this wire and test probe from any other potential source or ground.
5. If necessary, repeat Step 2 under “Procedure” of Test 21. The system must be in automatic operating mode, with engine running, and standby source voltage available to Terminal Lugs E1 and E2.
6. Locate on the standby closing coil the terminal that Wire B is connected to. (Figure 1, previous page). Connect the other meter test lead to this terminal. Generator line to line voltage should be indicated. If generator voltage is NOT indicated, proceed to Step 7.
7. With Wire E2 still connected to one test probe, connect the other meter test lead to Wire 205 on Limit Switch XB1 (see Figure 1 on previous page). Generator line to line voltage should be measured.
RESULTS:
1. If generator line-to-line voltage is indicated in “Procedure, Step 6,” but transfer does NOT occur, proceed to Test
24.
2. If generator line-to-line voltage is NOT indicated in “Procedure, Step 7,” proceed to Test 33.
3. If generator line-to-line voltage is indicated in “Procedure, Step 7,” proceed to Test 25.
TEST 23 - TEST TRANSFER RELAY TR
DISCUSSION: In automatic operating mode, the transfer relay must
be energized by circuit board action or standby source power will not be available to the standby closing coil. Without standby source power, the closing coil will remain de-energized and transfer to “Standby” will not occur. This test will determine if the transfer relay is functioning normally.
PROCEDURE:
1. See Figure 2. Disconnect all wires from the transfer relay, to prevent interaction.
2. Set a VOM to its “R x 1” scale and zero the meter.
3. Connect the VOM test leads across Relay Terminals 6 and 9 with the relay de-energized. The VOM should read INFINITY.
Page 67
Page 70
SECTION 3.4
DIAGNOSTIC TESTS
PART 3
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
CONNECT VOM TEST
LEADS ACROSS
Terminals 6 and 9 Continuity Infinity
Terminals 1 and 7 Infinity Continuity
DESIRED METER READING
ENERGIZED DE-ENERGIZED
4. Using jumper wires, connect the positive (+) post of a 12 volt battery to relay Terminal “A” and the negative (-) battery post to Relay Terminal “B”. The relay should energize and the VOM should read CONTINUITY.
126
N1A
194
205
E1
23
RESULTS:
1. Replace transfer relay if it is defective.
2. If transfer relay checks good go to Test 26.
TEST 24- CHECK MANUAL TRANSFER
SWITCH OPERATION
DISCUSSION: In automatic operating mode, when utility source volt-
age drops below a preset level, the engine should crank and start. On engine startup, an “engine warm­up timer” on the generator circuit board should start timing. When that timer has timed out (about 15 sec­onds), the transfer relay should energize to deliver utility source power to the standby closing coil termi­nals. If normal utility source voltage is available to the standby closing coil terminals, but transfer to Standby does not occur, the cause of the failure may be (a) a failed standby closing coil and/or bridge rectifier, or (b) a seized or sticking actuating coil or load contact. This test will help you evaluate whether any sticking or binding is present in the transfer mechanism.
PROCEDURE:
1. With the generator shut down, set the generator AUTO­OFF-MANUAL switch to OFF.
Figure 2. Transfer Relay Test Points
5. Now, connect the VOM test leads across Relay Terminals 1 and 7.
a.Energize the relay and the meter should indicate
INFINITY.
b.De-energize the relay and the VOM should read
CONTINUITY.
LOAD CONNECTED TO UTILITY POWER SOURCE
MANUAL TRANSFER HANDLE
TRANSFER SWITCH OPERATING LEVER
2. Set the generator main circuit breaker to OFF or “Open”.
3. Turn off the utility power supply to the transfer switch, using whatever means provided (such as a utility source main line breaker).
DANGER: DO NOT ATTEMPT MANUAL
TRANSFER SWITCH OPERATION UNTIL ALL POWER VOLTAGE SUPPLIES TO THE SWITCH HAVE BEEN POSITIVELY TURNED
LOAD CONNECTED TO STANDBY POWER SOURCE
TRANSFER SWITCH OPERATING LEVER
MANUAL TRANSFER HANDLE
Figure 3. Manual Transfer Switch Operation
Page 68
Page 71
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
PART 3
SECTION 3.4
DIAGNOSTIC TESTS
OFF. FAILURE TO TURN OFF ALL POWER VOLTAGE SUPPLIES MAY RESULT IN EXTREMELY HAZARDOUS AND POSSIBLY LETHAL ELECTRICAL SHOCK.
4. In the transfer switch enclosure, locate the manual trans­fer handle. Handle is retained in the enclosure with a wing nut. Remove the wing nut and handle.
5. See Figure 3. Insert the un-insulated end of the handle over the transfer switch operating lever.
a.Move the transfer switch operating lever up to
actuate the load contacts to the Utility position, i.e., load connected to the utility source.
b.Actuate the operating lever down to move the
load contacts against the standby contacts, i.e., load connected to the Standby source.
6. Repeat Step 5 several times. As the transfer switch oper­ating lever is moved slight force should be needed until the lever reaches its center position. As the lever moves past its center position, an over-center spring should snap the moveable load contacts against the stationary STANDBY
or UTILITY contacts.
7. Finally, actuate the main contacts to their UTILITY power source side, i.e., load contacts against the UTILITY con­tacts (upward movement of the operating lever).
RESULTS:
1. If there is no evidence of binding, sticking, excessive force required, replace the appropriate closing coil.
2. If evidence of sticking, binding, excessive force required to move main contacts, find cause of binding or sticking and repair or replace damaged part(s).
3. See Figure 1. Connect the VOM test probes across the two outer terminals from which the wires were disconnected.
4. Manually actuate the main contacts to their “Standby” position. The meter should read INFINITY.
5. Manually actuate the main contacts to their UTILITY position. The meter should read CONTINUITY.
6. Repeat Steps 4 and 5 several times and verify the VOM reading at each switch position.
RESULTS:
1. If Limit Switch XB1 fails the test, remove and replace the switch or adjust switch until it is actuated properly.
2. If limit switch is good, repair or replace Wire B between limit switch and Standby Coil (C2).
TEST 26 - CHECK 23 AND 194 WIRING/
CONNECTIONS
DISCUSSION: An open circuit in the transfer switch control wiring
can prevent a transfer action from occurring. In the auto mode, the circuit board supplies +12 VDC to Wire 194. This DC voltage is supplied to the transfer relay (TR) at Terminal Location “A”. The opposite side of the transfer relay (TR) coil (Terminal B) is con­nected to Wire 23. Positive 12 VDC is present on this also. Circuit board action will allow current to flow through the circuit and the (TR) is energized.
PROCEDURE/RESULTS:
1. Set VOM to DC volts
TEST 25- TEST LIMIT SWITCH XB1
DISCUSSION: Standby power source voltage must be available
to the standby closing coil in order for a transfer to standby action to occur. To deliver that source volt­age to the coil, limit switch XB1 must be closed to the “Standby” power source side. If the limit switch did not get actuated or has failed open, the source voltage will not be available to the closing coil and transfer to “Standby” will not occur.
PROCEDURE: With the generator shut down, the generator main
circuit breaker turned OFF, and with the utility power supply to the transfer switch turned OFF, test limit switch XB1 as follows:
1. To prevent interaction, disconnect Wire 205 and Wire B from the limit switch terminals.
2. Set a VOM to its “R x 1” scale and zero the meter.
2. Place generator AUTO-OFF-MANUAL switch to the AUTO position. Utility power should be present; the generator should not start.
3. Connect the negative (-) test lead to a suitable frame ground in the transfer switch.
4. Connect the positive (+) test lead to Wire 194 at the ter­minal strip in the transfer switch.
a.If voltage is present, proceed to Step 5. b.If voltage is not present, proceed to Step 9.
5. Connect the positive (+) test lead to Wire 23 at the termi­nal strip in the transfer switch.
a.If voltage is present, proceed to Step 6. b.If voltage is not present, repair wiring between
terminal strip and transfer relay (TR).
6. Connect the negative (-) test lead to the ground lug in the generator control panel. Connect the positive (+) test lead to Wire 23 in the generator control panel at the interconnection terminals (ICT) or at the terminal strip.
Page 69
Page 72
SECTION 3.4
DIAGNOSTIC TESTS
PART 3
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
a.If voltage is present, proceed to Step 7. b.If voltage is not present, repair wiring between
transfer switch and generator control panel.
7. Connect the positive (+) test lead to Wire 23 located in the J1 Connector Pin Location 3, connected to the cir­cuit board (see Figure 3, Section 4.1).
a.If voltage is present, proceed to Step 8. b.If voltage is not present, repair wiring between
(ICT and J1 Connector).
8. Turn off utility power to transfer switch, simulating a utility failure.
a.Generator starts and transfer occurs, discon-
tinue tests.
b.Generator starts and transfer does not occur.
With the generator running and utility off, ground Wire 23 in the control panel at interconnection terminals (ICT) or at the terminal strip. If trans­fer occurs replace circuit board.
9. Connect the negative (-) test lead to the ground lug in the generator control panel. Connect the positive (+) test lead to Wire 194 in the generator control panel at the interconnection terminals (ICT) or at the terminal strip.
a.If the voltage is present, repair wiring between
ICT (or terminal strip) and transfer switch
b.If voltage is not present, proceed to Step 10.
10.
Connect the positive (+)
test lead to Wire 194
located at AUTO-OFF-MANUAL switch (SW1) (see Figure 3, Section 4.1).
a.If voltage is present, repair wiring betweenJ1
Connector and ICT (or terminal strip).
b.If voltage is not present, perform Test 44. Repair
or replace SW1 or wiring as needed.
TEST 27- CHECK VOLTAGE AT TERMINAL
LUGS N1, N2
DISCUSSION: If retransfer to the “Utility” power source side is to
occur, utility source voltage must be available to Terminal Lugs N1 and N2 of the transfer mechanism. In addition, If that source voltage is not available to NI/N2 terminals, automatic startup and transfer to STANDBY will occur when the generator AUTO-OFF­MANUAL switch is set to AUTO. This test will prove that “Utility” voltage is available to those terminals, or is not available. It is the first test in a series of tests that should be accomplished when (a) retransfer back to “Utility” does not occur, or (b) startup and transfer occurs unnecessarily.
DANGER: PROCEED WITH CAUTION! HIGH
Page 70
AND DANGEROUS VOLTAGES ARE PRESENT AT TERMINAL LUGS N1/N2. CONTACT WITH HIGH VOLTAGE TERMINALS WILL RESULT
IN DANGEROUS AND POSSIBLY LETHAL ELECTRICAL SHOCK. DO NOT ATTEMPT THIS TEST WHILE STANDING ON WET OR DAMP GROUND, WHILE BAREFOOT, OR WHILE HANDS OR FEET ARE WET.
PROCEDURE:
1. Make sure that all main line circuit breakers in the utility line to the transfer switch are “On” or “Closed.”
2. Test for utility source line-to-line voltage across Terminal Lugs N1 and N2 (see Figure 1). Normal utility source voltage should be indicated.
RESULTS:
1. If low or no voltage is indicated, find the cause of the problem and correct.
2. If normal utility source voltage is indicated, go on to Test 28.
3. For Problem 14 ONLY, if voltage is good, repair or replace Wire N1A/N2A between Transfer Switch Lugs N1/N2 and Fuse Holder connections.
TEST 28 - CHECK VOLTAGE AT UTILITY 1 AND
UTILITY 2 TERMINALS
The UTILITY 1 and UTILITY 2 terminals in the trans­fer switch deliver utility voltage “sensing” to a circuit board. If voltage at the terminals is zero or low, stand­by generator startup and transfer to the “Standby” source will occur automatically as controlled by the circuit board. A zero or low voltage at these terminals will also prevent retransfer back to the “Utility” source.
PROCEDURE: With utility source voltage available to terminal lugs
N1 and N2, use an AC voltmeter or a VOM to test for utility source line-to-line voltage across terminal block UTILITY 1 and UTILITY 2 terminals. Normal line-to­line utility source voltage should be indicated.
N1 N2 23 194
1
2
UTILITY
UTILITY
Figure 4. Transfer Switch Terminal Block
23
194
Page 73
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
PART 3
SECTION 3.4
DIAGNOSTIC TESTS
RESULTS:
1. If voltage reading across the UTILITY 1 and UTILITY 2 terminals is zero, go to Test 30.
2. If voltage reading is good, go to Test 29.
3. For Problem 14 ONLY; if voltage is good, repair N1/N2 open wiring between Transfer Switch and Generator.
TEST 29- CHECK VOLTAGE AT UTILITY
CLOSING COIL C1
DISCUSSION: Utility source voltage is required to energize util-
ity closing coil C1 and effect retransfer back to the “Utility” source. This voltage is delivered to the util­ity closing coil via Wires N1A and N2A, the transfer relay’s normally-closed contacts (relay de-energized), Wire 126, Limit Switch XA1, and a bridge rectifier.
PROCEDURE:
1. On the generator control panel, set the AUTO-OFF­MANUAL switch to OFF.
2. Turn off the utility power supply to the transfer switch, using whatever means provided (such as a utility source main line circuit breaker).
3. Set the generator main line circuit breaker to its OFF or “Open” position.
4. Check the position of the transfer mechanism main con­tacts. The moveable load contacts must be connected to the stationary utility contacts. If necessary, manually actuate the main contacts to their “Utility” source side (load connected to the “Utility” source).
DANGER: BE CAREFUL! HIGH AND
5. Disconnect Wire N2A from the utility closing coil (C1).
6. Set the generator main line circuit breaker to its “On” or
7. Set the generator AUTO-OFF-MANUAL switch to AUTO.
DANGEROUS VOLTAGES ARE PRESENT AT TERMINAL LUGS WHEN THE GENERATOR IS RUNNING. AVOID CONTACT WITH HIGH VOLTAGE TERMINALS OR DANGEROUS AND POSSIBLY LETHAL ELECTRICAL SHOCK MAY RESULT. DO NOT PERFORM THIS VOLTAGE TEST WHILE STANDING ON WET OR DAMP GROUND, WHILE BAREFOOT, OR WHILE HANDS OR FEET ARE WET.
Connect one meter test Lead to Wire N2A. Use a suitable and safe connection to this wire, such as an alligator clip that attaches to the meter test probe. Isolate this wire and test probe from any other potential source or ground.
“Closed” position.
a.The generator should crank and start.
b. About 15 seconds after engine startup, the
transfer relay should energize and transfer to the “Standby” source should occur.
8. When you are certain that transfer to “Standby” has occurred, turn ON the utility power supply to the transfer switch. After a 15 seconds, retransfer back to the “Utility” source should occur.
9. Locate on the utility closing coil the terminal that Wire A is connected to (see Figure 1, Section 3.4). Connect the other meter test lead to this terminal. Utility line to line voltage should be indicated. If utility voltage is NOT indicated, proceed to Step 10.
10.With Wire N2A still connected to one test probe, connect the other meter test lead to Wire 126 on Limit Switch XA1 (see Figure 1, Section 3.4). Utility line to line volt­age should be measured.
RESULTS:
1. In Step 7, if the generator does NOT crank or start, refer to Part 4, “DC Control”.
2. In Step 7, if transfer to the “Standby” source does NOT occur, go to Problem 1.
3. In Step 9, if normal utility source line-to-line voltage is indicated but retransfer back to “Utility” does NOT occur, go to Test 24.
4. If normal utility source line-to-line voltage is NOT indi­cated in Step 9, but is indicated in Step 10, proceed to Test 31.
5. If normal utility source line-to-line voltage is NOT indicat­ed in Step 8, and is NOT indicated in Step 9, proceed to Test 32.
TEST 30 - CHECK FUSES F1 AND F2
DISCUSSION: Fuses F1 and F2 are connected in series with the
UTILITY 1 and UTILITY 2 circuits, respectively. A blown fuse will open the applicable circuit and will result in (a) generator startup and transfer to “Standby”, or (b) failure to retransfer back to the utility source.
PROCEDURE:
1. On the generator panel, set the AUTO-OFF-MANUAL switch to OFF.
2. Turn off the utility power supply to the transfer switch, using whatever means provided.
3. Remove fuses F1 and F2 from the fuse holder (see Figure 5).
4. Inspect and test fuses for blown condition.
Page 71
Page 74
SECTION 3.4
DIAGNOSTIC TESTS
N1A N2A
PART 3
NOTE: Problems with transfer switch opera­tion can also be caused by (a) defective wiring between the generator and transfer switch, or (b) a defective component in the generator circuit board. See Part 4, “DC Control”.
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
TEST 32 - CONTINUITY TEST OF WIRING (C1)
RESULTS:
F1
N1
Figure 5. Fuse Holder and Fuses
N2
F2
1. Replace blown fuse(s) and proceed to Test 34.
2. For Problem 7 (DC Control, Section 4), go to Test 27.
TEST 31 - TEST LIMIT SWITCH XA1
DISCUSSION: When the transfer switch main contacts are actuated
to their “Utility” position, limit switch XA1 should be mechanically actuated to its open position. On transfer to the “Standby” position, the limit switch should actu­ate to its closed position. If the switch does not actu­ate to its closed position, retransfer back to “Utility” will not occur.
PROCEDURE:
1. With the standby generator shut down, set its AUTO­OFF-MANUAL switch to OFF.
DISCUSSION: This test will ensure that all control wiring has continuity.
1. Set the AUTO-OFF-MANUAL switch to the OFF position.
2. Turn the generator main circuit breaker to the OFF position.
3. Turn off the utility power supply to the transfer switch using whatever means provided. (Such as utility source main line circuit breaker).
4. Set your VOM to the “R x 1” scale.
5. Disconnect Wire N2A from the Utility Coil C1 and con­nect one test lead to it. Connect the other test lead to Terminal Lug N2 of the transfer switch. CONTINUITY should be read. Reconnect Wire N2A.
6. Disconnect Wire 126 from transfer relay (TR) and connect one test lead to it. Connect the other test lead to limit switch XA1 bottom Terminal Wire 126. CONTINUITY should be read. Reconnect Wire 126.
7. Disconnect Wire N1A from transfer relay (TR) terminal and connect one test lead to it. Connect the other test lead to F1 top fuse Terminal Wire N1A. CONTINUITY should be read. Reconnect Wire N1A.
RESULTS: Repair any defective wiring that does not read
CONTINUITY. If wiring tests good, proceed to Test 23.
TEST 33 - CONTINUITY TEST OF WIRING (C2)
2. Turn off the utility power supply to the transfer switch, using whatever means provided.
3. To prevent interaction, disconnect Wire 126 and Wire A from the limit switch terminals.
4. Set a VOM to its “R x 1” scale and zero the meter.
5. Connect the VOM test leads across the two limit switch terminals from which Wires A and 126 were removed.
6. Manually actuate the main contacts to their “Standby” position. The VOM should indicate CONTINUITY.
7. Manually actuate the main contacts to their “Utility” posi­tion. The VOM should read INFINITY.
RESULTS: Replace limit switch XA1 if it checks bad.
Page 72
DISCUSSION: This test will ensure that all control wiring has continuity.
1. See Test 32, Step 1
2. See Test 32, Step 2
3. See Test 32, Step 3
4. See Test 32, Step 4
5. Disconnect Wire E2 from the standby coil (C2) and con­nect one test lead to it. Connect the other test lead to Terminal Lug E2 of the transfer switch. CONTINUITY should be read. Reconnect Wire E2.
6. Disconnect Wire 205 from transfer relay (TR) Terminal 6 and connect one test lead to it. Connect the other test lead to limit switch XB1 top Terminal Wire 205. CONTINUITY should be read. Reconnect Wire 205.
Page 75
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
PART 3
SECTION 3.4
DIAGNOSTIC TESTS
7. Disconnect Wire E1 from Transfer Relay (TR) Terminal 9 and connect one test lead to it. Connect the other test lead to Terminal Lug E1 of the transfer switch. CONTINUITY should be read. Reconnect Wire E1.
RESULTS: Repair any defective wiring that does not read
CONTINUITY. If wiring tests good, proceed to Test 23.
TEST 34 - CHECK N1 AND N2 WIRING
DISCUSSION: A shorted Wire N1 or N2 to ground can cause fuse F1
or F2 to blow.
PROCEDURE:
1. On the generator panel, set the AUTO-OFF-MANUAL switch to OFF.
2. Turn off the utility power supply to the transfer switch, using whatever means are provided.
3. Remove fuses F1 and F2 from the fuse holder (see Figure 5).
4. Remove the generator control panel cover. Disconnect Wire N1 and Wire N2 from the interconnection terminal in the control panel, or the terminal strip.
5. Set your VOM to the “R x 1” scale. Connect the positive meter test lead to Wire N1.
a.Connect the negative meter lead to the ground
lug. INFINITY should be measured.
b.Connect the negative meter lead to Wire 23
at ICT or terminal strip. INFINITY should be measured.
c. Connect the negative meter lead to Wire 194
at ICT or terminal strip. INFINITY should be measured.
d.Connect the negative meter lead to the neutral
connection. INFINITY should be measured.
6. Set your VOM to the “R x 1” scale. Connect the positive meter test lead to Wire N2.
a.Connect the negative meter lead to the ground
lug. INFINITY should be measured.
b.Connect the negative meter lead to Wire 23
at ICT or terminal strip. INFINITY should be measured.
c. Connect the negative meter lead to Wire No.
194 at ICT or terminal strip. INFINITY should be measured.
d.Connect the negative meter lead to the neutral
connection. INFINITY should be measured.
7. Disconnect Wire N1 and Wire N2 from transformer TX.
8. Connect one test lead to Wire N1 removed in Step 7, and the other test lead to the ground terminal. INFINITY should be measured.
9. Connect one test lead to Wire N2 removed in Step 7, and the other test lead to the ground terminal. INFINITY should be measured.
10.If no short is indicated in Steps 5 through 9, proceed with Steps 11 through 15. If a short is indicated in Steps 5 through 9, repair shorted wiring.
11.Reconnect Wires N1 and N2 to the interconnection ter­minal or terminal strip.
12.Replace fuses F1 and F2 in the fuse holder.
13.Turn on the utility power supply to the transfer switch using whatever means is provided.
14.Set VOM to measure AC voltage. Connect one test lead to Wire N1 and the other test lead to Wire N2. Utility line to line voltage should be measured.
15.Turn off the utility power supply to the transfer switch using whatever means is provided.
RESULTS: If a short is indicated in Steps 5 through 9, repair
wiring and re-test. If utility line to line voltage is mea­sured in Step 14, proceed to Test 35.
TEST 35 - CHECK TRANSFORMER (TX)
DISCUSSION: The transformer is a step down type and has two
functions. It supplies approximately 16 VAC to the control board for utility sensing. It also supplies approximately 16 VAC to the battery charger when utility is available for trickle charge. A shorted trans­former can result in fuse F1 or F2 blowing.
PROCEDURE:
1. On the generator panel, set the AUTO-OFF-MANUAL switch to OFF.
2. Turn off the utility power supply to the transfer switch, using whatever means is provided.
3. See Figure 6. Disconnect Wires N1, N2, 224, 225, 224A, 225A from transformer (TX).
4. Set a VOM to the “R x 1” scale.
5. Connect one test lead to TX Terminal 1. Connect the other test lead to TX Terminal 5. Approximately 38.5 ohms should be measured
6. Connect one test lead to TX Terminal 10. Connect the other test lead to TX Terminal 9. Approximately 1.5 ohms should be measured.
7. Connect one test lead tot TX Terminal 7. Connect the other test lead to TX Terminal 6. Approximately 0.3 ohms should be measured.
Page 73
Page 76
SECTION 3.4
DIAGNOSTIC TESTS
PART 3
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
8. Connect one test lead to TX Terminal 1. Connect the other test lead to the transformer case. INFINITY should be measured.
9. Connect one test lead to TX Terminal 7. Connect the other test lead to the transformer case. INFINITY should be measured.
10.Connect one test lead to TX Terminal 9. Connect the other test lead to the transformer case. INFINITY should be measured.
11.Connect one test lead to TX Terminal 1. Connect the other test lead to TX Terminal 10. INFINITY should be measured.
12.Connect one test lead to TX Terminal 1. Connect the other test lead to TX Terminal 7. INFINITY should be measured.
13.Connect one test lead to TX Terminal 10. Connect the other test lead to TX Terminal 7. INFINITY should be measured.
RESULTS: For Steps 5, 6, and 7, replace transformer if an open
is indicated, or if the resistance value indicated is zero. If the resistance value is not within the approxi­mate range, proceed to test 65.
For Steps 8 through 13, replace the transformer if it fails any of these steps.
10
6
7
9
1
5
225
224
225A
224A
N2
N1
Figure 6. Transformer (TX)
Page 74
Page 77
PART 4
DC CONTROL
Air-cooled, Prepackaged
Automatic Standby Generators
TABLE OF CONTENTS
PART TITLE PAGE#
4.1. Description and Components 76
4.2 Operational Analysis 82
4.3 Troubleshooting Flow Charts 96
4.4 Diagnostic Tests 103
4.1 Description and Components ...............................................76
General 76
Terminal Strip / Interconnection Terminal ............................76
Transformer (TX) .................................................................76
Circuit Board ....................................................................... 76
AUTO-OFF-MANUAL Switch .............................................. 80
15 Amp Fuse ......................................................................80
4.2 Operational Analysis .............................................................82
Introduction ......................................................................... 82
Utility Source Voltage Available ........................................... 82
Initial Dropout Of Utility Source Voltage .............................. 84
Utility Voltage Dropout And
Engine Cranking ................................................. 86
Engine Star tup And Running .............................................. 88
Initial Transfer To The “Standby” Source .............................90
Utility Voltage Restored /
Re-transfer To Utility ............................................ 92
Engine Shutdown .............................................................. 94
4.3 Troubleshooting Flow Charts ................................................ 96
Problem 8 - Engine Will Not Crank
When Utility Power Source Fails ......................... 96
Problem 9 - Engine Will Not Crank
When AUTO-OFF-MANUAL Switch
is Set to "MANUAL" ............................................. 96
Problem 10 - Engine Cranks
but Won't Start..................................................... 97
Problem 11 - Engine Starts Hard and
Runs Rough / Lacks Power ................................. 98
Problem 12 - Engine Starts and Runs,
Then Shuts Down ............................................... 99
Problem 13 - No Battery Charge ...................................... 100
Problem 14 - Unit Starts and Transfer Occurs
When Utility Power is Available ........................ 101
Problem 15 - Generator Starts
Immediately in Auto - No Transfer to
Standby. Utility Voltage is Present .....................101
Problem 16 - 15 Amp Fuse (F1) Blown.............................102
Problem 17 - Generator Will Not Exercise ........................ 102
Problem 18 - No Low Speed Exercise .............................. 102
4.4 Diagnostic Tests ..................................................................103
Introduction ..................................................................... 103
Test 41 - Check Position Of
AUTO-OFF-MANUAL Switch .......................... 103
Test 42 - Try A Manual Start ........................................... 103
Test 43 - Test AUTO-OFF-MANUAL Switch .................... 103
Test 44 - Check Wire 15/15A/15B/239/0
Voltage ..............................................................104
Test 45 - Check 15 Amp Fuse .......................................... 105
Test 46 - Check Battery ................................................... 105
Test 47 - Check Wire 56 Voltage ...................................... 106
Test 48 - Test Starter Contactor Relay
Test 49 - Test Starter Contactor ........................................ 106
Test 50 - Test Starter Motor .............................................. 107
Test 51 - Check Fuel Supply
Test 52 - Check Circuit Board
Test 53 - Check Fuel Solenoid .......................................... 111
Test 54 - Check Choke Solenoid
Test 55 - Check For Ignition Spark.................................... 113
Test 56 - Check Spark Plugs ............................................114
Test 57 - Check Engine / Cylinder Leak Down
Test 58 - Check Shutdown Wire ........................................ 115
Test 59 - Check And Adjust
Test 60 - Check Oil Pressure Switch
Test 61 - Check High Oil
Test 62 - Check And Adjust Valves ...................................119
Test 63 - Check Fuel Regulator
Test 64 - Check Battery Charge Output ............................ 120
Test 65 - Check Transformer (TX)
Test 66 - Check AC Voltage At
Test 67 - Check Battery Charge
Test 68 - Check Battery Charge
Test 69 - Check Battery Charger Wiring .......................... 123
Test 70 - Check Wire 18 Continuity ................................... 123
Test 71 - Check N1 And N2 Voltage .................................. 123
Test 72 - Check Utility Sensing Voltage
Test 73 - Test Set Exercise Switch .................................... 124
Test 75 - Check Battery Voltage Circuit ............................124
Test 76 - Check Cranking And
Test 77 - Test Exercise Function ....................................... 126
Test 78 - Check Dip Switch Settings ................................. 126
Test 79 - Check Idle Control Transformer
Test 80 - Check LC1 & LC2 Wiring ................................... 126
Test 81 - Check Idle Control Transformer
(V-twin Only)...................................................... 106
And Pressure .................................................... 109
Wire 14 Output .................................................. 110
(V-twins Units Only)...........................................112
Test / Compression Test ......... 114
Ignition Magnetos .............................................. 116
And Wire 86 ...................................................... 117
Temperature Switc
(7 Kw Natural Gas Units Only)
Voltage Output ..................................................118
Battery Charger................................................. 121
Relay (BCR) ...................................................... 122
Winding Harness............................................... 122
At The Circuit Board .......................................... 124
Running Circuits ................................................ 124
(V-twin Units Only) ............................................ 126
Primary Wiring .................................................. 127
h .......................................... 118
.......................... 117
Page 75
Page 78
SECTION 4.1
DESCRIPTION AND COMPONENTS
PART 4
DC CONTROL
GENERAL
This section will familiarize the reader with the various components that make up the DC control system.
Major DC control system components that will be cov ered include the following:
• A Terminal Strip / Interconnection Terminal
• A Transformer (TX)
• A Circuit Board.
• An AUTO-OFF-MANUAL Switch.
• A 15 Amp Fuse.
• A 5 Amp Fuse.
TERMINAL STRIP / INTERCONNECTION
TERMINAL
The terminals of this terminal strip are connected to identically numbered terminals on a prepackaged transfer switch terminal board. The terminal board connects the transfer switch to the circuit board and transformer.
The terminal board provides the following connection points:
A. UTILITY 1 and UTILITY 2
1.Connect to identically marked terminals on a prepackaged transfer switch terminal board.
2.The circuit delivers “Utility” power source voltage to the transformer (TX) located in the control panel assembly.
B. 23 and 194
1.Connect to identically numbered terminals on the terminal board of the prepackaged transfer switch.
2.This circuit connects the circuit board to the transfer relay coil in the prepackaged transfer switch.
23
194
UTILITY 1
UTILITY 2
Figure 1. Terminal Board
a reduced voltage (about 12 to 16 volts) into both secondary transformer windings. Reduced voltage from one secondary winding is delivered to the circuit board as “Utility” source sensing voltage. Reduced voltage from the other secondary winding is delivered
­to the battery charger for trickle charging.
• If the Utility sensing voltage drops below a preset
value, circuit board action will initiate automatic gen­erator startup and transfer to the “Standby” source side.
The sensing transformer is shown in Figure 2, both pictorially and schematically.
6
7
9
10
5
1
1
230V
50/60Hz
5
SCHEMATIC
Figure 2. The Transformer
CIRCUIT BOARD
The circuit board controls all standby electric system operations including (a) engine startup, (b) engine running, (c) automatic transfer, (d) automatic retrans­fer, and (e) engine shutdown. In addition, the circuit board performs the following functions:
• Delivers “field boost” current to the generator rotor
windings (see “Field Boost Circuit” in Section 2.2).
• Starts and “exercises” the generator once every
seven days.
• Provides automatic engine shutdown in the event of
low oil pressure, low battery, high oil temperature, or overspeed.
A 23-pin and a 5-pin connector are used to intercon nect the circuit board with the various circuits of the DC systems. Connector pin numbers, associated wires and circuit functions are listed in the CHART on the next page.
The run relay is energized by circuit board action at the same time as the crank relay, to energize and open a fuel solenoid valve.
16V
56VA
16V 1VA
6
7
9
10
-
TRANSFORMER (TX)
The control panel assembly’s transformer is a step­down type. The line-to-line voltage from the UTILITY 1/UTILITY 2 terminals is delivered to the transformer’s primary winding. Transformer action then induces
Page 76
DANGER: THE GENERATOR ENGINE WILL
CRANK AND START WHEN THE 7-DAY
EXERCISER SWITCH IS ACTUATED. THE UNIT WILL ALSO CRANK AND START EVERY 7 DAYS THEREAFTER, ON THE DAY AND AT THE TIME OF DAY THE SWITCH WAS ACTUATED.
Page 79
DC CONTROL
CUSTOMER CONNECTIONS (TS)
IDLE CONTROL TRANSFORMER (ICT) (V-TWINS ONLY)
PART 4
SECTION 4.1
DESCRIPTION AND COMPONENTS
GROUND TERMINAL
NEUTRAL BLOCK
TRANSFORMER (TX)
STARTER CONTACTOR RELAY (SCR) (V-TWINS ONLY)
BATTERY CHARGER
GROUND TERMINAL
FUSE HOLDER (F1)
AUTO-OFF-MANUAL SWITCH (SW1)
VOLTAGE REGULATOR
BATTERY CHARGE RELAY (BCR)
4-TAB TERMINAL BLOCK (TB)
PRINTED CIRCUIT BOARD
SET EXERCISE SWITCH (SW2)
Figure 3. Control Panel Component Identification
Page 77
Page 80
SECTION 4.1
DESCRIPTION AND COMPONENTS
OVERCRANK
OVERSPEED
HI OIL TEMPERATURE
LOW OIL PRESSURE
LOW BATTERY
SYSTEM READY
PART 4
DC CONTROL
J1 CONNECTOR HARNESS END
23
22
21
20
19
18
12
ON
17
16
8
15
7
14
6
13
5
12
4
11
3
10
2
9
1
J1
J2
Figure 4. 10/13/16 kW Printed Circuit Board and J1 Connector
10/13/16 kW J1 Connector Pin Descriptions
PIN WIRE CIRCUIT FUNCTION
1 15A 12 VDC into the circuit board for source voltage
2 4 Field boost current to rotor (about 9-10 volts DC).
3 23 Switched to ground for Transfer Relay (TR)
4 86 Low oil pressure shutdown: Shutdown occurs
5 18 Ignition Shutdown: Circuit board action grounds
BROWN
6
BROWN
7
8 LC1 Current sensing for governor control.
9 56 12 VDC output to starter contactor relay
10 224 Transformer reduced “Utility” source
Page 78
when SW1 is in the AUTO or MANUAL position.
operation.
when Wire 86 is grounded by loss of oil pressure to the LOP.
Wire 18 for ignition shutdown.
RPM Sense: Circuit board monitors ignition magneto voltage/frequency for engine speed when running
INTERNAL USE
INTERNAL USE
for V-twin engine.
sensing voltage.
ON
12
DIPSWITCH 1 ON = NORMAL EXERCISE OFF = LOW SPEED EXERCISE
} 16 kW UNITS ONLY
DIPSWITCH 2 SPARE
PIN WIRE CIRCUIT FUNCTION
11 239 12 VDC input when SW1 is in the
12 85 High temperature shutdown: Shutdown occurs
13 NOT USED
14 NOT USED
15 LC2 Current sensing for governor control.
16 14 12 VDC output for engine run condition.
17 225 Transformer reduced “Utility”
18 NOT USED
19 15B 12 VDC source voltage for the circuit board.
20 0 Common ground.
GREY
21
GREY
22
23 90 Switched to ground for choke solenoid operation
MANUAL position
when Wire 85 is grounded by contact closure of the HTO.
Used for fuel solenoid and battery charge relay.
source sensing voltage.
Also runs timer for exerciser.
INTERNAL USE
INTERNAL USE
Page 81
DC CONTROL
PART 4
OVERCRANK
OVERSPEED
HI OIL TEMPERATURE
LOW OIL PRESSURE
LOW BATTERY
SYSTEM READY
SECTION 4.1
DESCRIPTION AND COMPONENTS
J1 CONNECTOR HARNESS END
J1
Figure 5. 7 kW Printed Circuit Board and J1 Connector
7 kW J1 Connector Pin Descriptions
PIN WIRE CIRCUIT FUNCTION
1 15A 12 VDC into the circuit board for source voltage
when SW1 is in the AUTO or MANUAL position.
2 4 Field boost current to rotor (about 9-10 volts DC).
3 23 Switched to ground for Transfer Relay (TR)
operation.
4 86 Low oil pressure shutdown: Shutdown occurs
when Wire 86 is grounded by loss of oil pressure to the LOP.
5 18 Ignition Shutdown: Circuit board action grounds
Wire 18 for ignition shutdown.
RPM Sense: Circuit board monitors ignition mag­neto voltage/frequency for engine speed when running
6 56 12 VDC output to star ter contactor for
single cylinder engine.
14
13
12
11
10
PIN WIRE CIRCUIT FUNCTION
7 224 Transformer reduced “Utility” source
sensing voltage.
8 239 12 VDC input when SW1 is in the
MANUAL position
9 85 High temperature shutdown: Shutdown occurs
when Wire 85 is grounded by contact closure of the HTO.
10 14 12 VDC output for engine run condition. Used for
fuel solenoid and battery charge relay.
11 225 Transformer reduced “Utility” source
sensing voltage.
12 NOT USED
13 15B 12 VDC source voltage for the circuit board.
Also runs timer for exerciser.
14 0 Common ground.
5
9
4
8
3
7
2
6
1
Page 79
Page 82
SECTION 4.1
DESCRIPTION AND COMPONENTS
PART 4
DC CONTROL
AUTO-OFF-MANUAL SWITCH
This 3-position switch permits the operator to (a) select fully automatic operation, (b) start the genera­tor manually, or (c) stop the engine and prevent auto­matic startup. Switch terminals are shown pictorially and schematically in Figure 6, below.
1
2
3
SW1
MANUAL AUTO
4
5
6
194
6
15A
194
43
5
SW1
15 239
15
2
SCHEMATIC
194
15A
1
15
15 AMP FUSE
This fuse protects the circuit board against excessive current. If the fuse has blown, engine cranking and operation will not be possible. Should fuse replace­ment become necessary, use only an identical 15­amp replacement fuse.
Figure 7. 15 Amp Fuse
Figure 6. The AUTO-OFF-MANUAL Switch
Page 80
Page 83
DC CONTROL
PART 4
SECTION 4.1
DESCRIPTION AND COMPONENTS
6
5
4
C1 C2 C3
3 2
1
3 2
1
FEMALE SIDE
MALE SIDE
6
5
4
8
7
6
5
4 3
2
1
4 3
2
2
1
8
7
6
5
1
2
1
BACK PANEL
C1 CONNECTOR
C2 CONNECTOR
C3 CONNECTOR
Figure 8. C1, C2 & C3 Connector Locations and Pin Number Identification
Page 81
Page 84
SECTION 4.2
PART 4
DC CONTROL
OPERATIONAL ANALYSIS
INTRODUCTION
This “Operational Analysis” is intended to familiarize the service technician with the operation of the DC con­trol system on prepackaged units with air-cooled engine. A thorough understanding of how the system works is essential to sound and logical troubleshooting. The DC control system illustrations on the following pages include a “V-Type” prepackaged transfer switch.
UTILITY SOURCE VOLTAGE AVAILABLE
See Figure 1, below. The circuit condition with the AUTO-OFF-MANUAL switch set to AUTO and with “Utility” source power available can be briefly described as follows:
= 12 VDC ALWAYS PRESENT
SCR
3
0
2
1
BATTERY
CHARGER
13
0
0
56
ELECTRONIC
VOLTAGE
REGULATOR
1
224B
2
225B
13
0
15
16
56
11
22
4
4
0
6
2
=AC VOLTAGE
= GROUND FOR CONTROL PURPOSES
0
0
16 0
= 12 VDC DURING CRANKING ONLY
= 12 VDC DURING ENGINE RUN CONDITION
224B
13
225B
86
18
85
18
86
85
4
13
6
2
16
14
MANUAL
194 15A
194
15
J2
CONTROL
PRINTED CIRCUIT
BOARD
SW1
GOVERNOR
ACTUATOR
AUTO
194
15A
4
194
15A
23915
239
SW2
15
15B
15A
1
J1
2
4
3
23
86
4 5
18 6 7 8
LC1
9
56
224
10
239
11 12
85 13 14
LC2
15
14
16
225
17 18 19
15B 20 21 22 23
0
90 CS1414
22 11
0
0
11
22
15
56
0
13
F1
15
86 LC2140
1823
14
14
85LC1
LC1
LC2
0
23
194
225B
224B
224
225
Page 82
Page 85
DC CONTROL
PART 4
SECTION 4.2
OPERATIONAL ANALYSIS
• Utility source voltage is available to transfer switch Terminal Lugs N1/N2. With the transfer switch main contacts at their “Utility” side, this source voltage is available to Terminal Lugs T1/T2 and to the “Load” circuits.
• Utility voltage is delivered to the primary winding of a sensing transformer (TX), via transfer switch Wires N1/ N2, fuses F1/F2, connected wiring, and Control Panel UTILITY 1 and UTILITY 2 terminals. A resultant voltage (about 16 volts AC) is induced into the transformer secondary windings and then delivered to the circuit board via Wires 224/225. The circuit board uses this reduced utility voltage as sensing voltage. Wires 224A/225A sup ply 16 VAC to the battery charger.
• Battery output is delivered to the circuit board with the AUTO-OFF-MANUAL switch (SW1) set to AUTO, as shown.
Figure 1. Circuit Condition - Utility Source Voltage Available
ENGINE AND ALTERNATOR
66
6
2
DPE
POWER
WINDING
BA
FIELD
0
11
S TATO R
22
33
44
POWER
WINDING
11
22
LC1
LC2
IM2
SP2
18
86
85
4
13
6
2
16
14
0
0
HTO
LOP
0
0
0
7766
0
62
FS1
0
FS2
IM1
SP1
4
13
16
SC
0
0
0
0
11
22
22
LC2
LC1
16
SM
11
33
RED
SC
BATTERY
12V
0
0
I.C.T.
BATTERY
CHARGE
WINDING
77
WINDING
0
11
22
33
44
-
0
23
194
225B
224B
7
67394
1
7766
77 66
224A 225A
224
225
14
224A
225A
56VA
225A
224A
225
1VA
224
0
9
BCR
14
N2
TX
N1
33
22
NEUTRAL
240VAC GENERATOR
OUTPUT TO
TRANSFER SWITCH
CONTACTOR
DIAGRAM KEY
BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB - CIRCUIT BREAKER, MAIN OUTPUT CS - IDLE CHOKE SOLENOID FS1 - FUEL SOLENOID FS2 - FUEL SOLENOID(530cc V-TWIN ONLY) F1 - FUSE 15 AMP HTO - HIGH OIL TEMPERATURE SWITCH ICT - IDLE CONTROL TRANSFORMER IM1 - IGNITION MODULE, CYLINDER #1 IM2 - IGNITION MODULE, CYLINDER #2
44
11
CB
23194 N2 N1
12Vdc
TRANSFER
RELAY
COIL
TR
240VAC
UTILITY
INPUT
LOP - LOW OIL PRESSURE SWITCH SC - STARTER CONTACTER SCR - STARTER CONTACTOR RELAY SM - STARTER MOTOR SP1, SP2 - SPARK PLUGS SW1 - SWITCH, AUTO / OFF / MANUAL DPDT, ON-OFF-ON SW2 - SWITCH, SET EXERCISE SPST, N.C., ON-(OFF) TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)
Page 83
Page 86
SECTION 4.2
PART 4
DC CONTROL
OPERATIONAL ANALYSIS
INITIAL DROPOUT OF UTILITY SOURCE VOLTAGE
Refer to Figure 2, below. Should a “Utility” power source failure occur, circuit condition may be briefly described as follows:
• The circuit board constantly senses for an acceptable “Utility” source voltage, via transfer switch fuses F1/F2, transfer switch UTILITY 1 and UTILITY 2 terminals, connected wiring, control panel UTILITY 1 and UTILITY 2 terminals, the sensing transformer (TX), and Wires 224/225.
= 12 VDC ALWAYS PRESENT
SCR
3
0
2
1
BATTERY
CHARGER
13
0
0
56
ELECTRONIC
VOLTAGE
REGULATOR
1
224B
2
225B
13
0
15
16
56
11
22
4
4
0
6
2
=AC VOLTAGE
= GROUND FOR CONTROL PURPOSES
0
0
16 0
= 12 VDC DURING CRANKING ONLY
= 12 VDC DURING ENGINE RUN CONDITION
224B
13
225B
18
86
85
18
86
85
4
13
6
2
16
14
MANUAL
194 15A
194
15
J2
CONTROL
PRINTED CIRCUIT
BOARD
SW1
GOVERNOR
ACTUATOR
AUTO
194
15A
4
194
15A
23915
239
SW2
15
15B
15A
1
J1
4
2
23
3
86
4 5
18 6 7 8
LC1
56
9
224
10
239
11 12
85 13 14
LC2
15
14
16
225
17 18 19
15B 20 21 22 23
0
90 CS1414
22 11
0
0
11
22
56
15
0
13
F1
15
1823
86 LC2140
85LC1
14
14
LC1
LC2
0
23
194
225B
224B
224
225
Page 84
Page 87
DC CONTROL
PART 4
SECTION 4.2
OPERATIONAL ANALYSIS
• Should utility voltage drop below approximately 65 percent of the nominal source voltage, a 10-second timer on the circuit board will turn on.
• In Figure 2, the 10-second timer is still timing and engine cranking has not yet begun.
• The AUTO-OFF-MANUAL switch is shown in its AUTO position. Battery voltage is available to the circuit board, via Wire 13, 15 amp fuse (F1), Wire 15, the AUTO-OFF-MANUAL switch (SW1), Wire 15A, and Pin 1 of the cir cuit board connector.
Figure 2. Circuit Condition - Initial Dropout of Utility Source Voltage
ENGINE AND ALTERNATOR
66
6
2
DPE
POWER
WINDING
BA
FIELD
0
11
S TATO R
22
33
44
POWER
WINDING
11
22
LC1
LC2
IM2
SP2
18
86
85
4
13
6
2
16
14
0
0
HTO
LOP
0
0
0
7766
0
62
FS1
0
FS2
IM1
SP1
13
16
SC
0
0
0
0
11
22
22
33
LC1
LC2
4
RED
SC
BATTERY
16
SM
11
12V
0
0
I.C.T.
BATTERY
CHARGE
WINDING
77
WINDING
0
11
22
33
44
-
0
23
194
225B
224B
7
67394
1
7766
77 66
224A 225A
224
225
14
224A
225A
56VA
225A
224A
225
1VA
224
0
9
BCR
14
N2
TX
N1
33
22
NEUTRAL
240VAC GENERATOR
OUTPUT TO
TRANSFER SWITCH
CONTACTOR
DIAGRAM KEY
BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB - CIRCUIT BREAKER, MAIN OUTPUT CS - IDLE CHOKE SOLENOID FS1 - FUEL SOLENOID FS2 - FUEL SOLENOID(530cc V-TWIN ONLY) F1 - FUSE 15 AMP HTO - HIGH OIL TEMPERATURE SWITCH ICT - IDLE CONTROL TRANSFORMER IM1 - IGNITION MODULE, CYLINDER #1 IM2 - IGNITION MODULE, CYLINDER #2
44
11
CB
23194 N2 N1
12Vdc
TRANSFER
RELAY
COIL
TR
240VAC
UTILITY
INPUT
LOP - LOW OIL PRESSURE SWITCH SC - STARTER CONTACTER SCR - STARTER CONTACTOR RELAY SM - STARTER MOTOR SP1, SP2 - SPARK PLUGS SW1 - SWITCH, AUTO / OFF / MANUAL DPDT, ON-OFF-ON SW2 - SWITCH, SET EXERCISE SPST, N.C., ON-(OFF) TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)
Page 85
Page 88
SECTION 4.2
PART 4
DC CONTROL
OPERATIONAL ANALYSIS
UTILITY VOLTAGE DROPOUT AND ENGINE CRANKING
• After ten (10) seconds and when the circuit board’s 10-second timer has timed out, if utility voltage is still below 65 percent of nominal, circuit board action will energize the circuit board’s crank and run relays simultaneously.
• Printed circuit board action delivers 12 volts DC to a starter contactor relay (SCR), via Wire 56. When the SCR energizes, its contacts close and battery power is delivered to a starter contactor (SC). When the SC energizes, its contacts close and battery power is delivered to the starter motor (SM).The engine cranks.
= 12 VDC ALWAYS PRESENT
SCR
3
0
2
1
BATTERY
CHARGER
13
0
0
56
ELECTRONIC
VOLTAGE
REGULATOR
1
224B
2
225B
13
0
15
16
56
11
22
4
4
0
6
2
=AC VOLTAGE
= GROUND FOR CONTROL PURPOSES
0
0
16 0
= 12 VDC DURING CRANKING ONLY
= 12 VDC DURING ENGINE RUN CONDITION
224B
13
225B
86
18
85
18
86
85
4
13
6
2
16
14
MANUAL
194 15A
194
15
J2
CONTROL
PRINTED CIRCUIT
BOARD
SW1
GOVERNOR
ACTUATOR
AUTO
194
15A
4
194
15A
23915
239
SW2
15
15B
15A
1
J1
2
4
3
23
86
4 5
18 6 7 8
LC1
9
56
224
10
239
11 12
85 13 14
LC2
15
14
16
225
17 18 19
15B 20 21 22 23
0
90 CS1414
22 11
0
0
11
22
15
56
0
13
F1
15
86 LC2140
1823
14
14
85LC1
LC1
LC2
0
23
194
225B
224B
224
225
Page 86
Page 89
DC CONTROL
PART 4
SECTION 4.2
OPERATIONAL ANALYSIS
• Printed circuit board action delivers 12 volts DC to the fuel solenoids (FS1 & FS2), via Wire 14. The fuel sole­noids energize open and fuel is available to the engine. Wire 14 energizes the battery charge relay (BCR), which will allow the BCR to power the battery charger. Wire 14 supplies power to the choke solenoid (CS). Circuit board action grounds Wire 90, energizing the choke solenoid cyclically during cranking and continuously while running.
• As the engine cranks, magnets on the engine flywheel induce a high voltage into the engine ignition magnetos
(IM1/IM2). A spark is produced that jumps the spark plug (SP1/SP2) gap.
• During cranking, Wire 4 supplies 3-5 VDC (9-10 VDC isolated) to the rotor for field flash.
• With ignition and fuel flow available the engine can start.
Figure 3. Circuit Condition - Engine Cranking
ENGINE AND ALTERNATOR
66
6
2
DPE
POWER
WINDING
BA
FIELD
0
11
S TATO R
22
33
44
POWER
WINDING
11
22
LC1
LC2
IM2
SP2
18
86
85
4
13
6
2
16
14
0
0
HTO
LOP
0
0
0
7766
0
62
FS1
0
FS2
IM1
SP1
4
13
16
SC
0
0
0
0
11
22
22
LC2
LC1
16
SM
11
33
RED
SC
BATTERY
12V
0
0
I.C.T.
BATTERY
CHARGE
WINDING
77
WINDING
0
11
22
33
44
0
23
194
225B
224B
7
67394
1
7766
77 66
224A 225A
224
225
14
224A
225A
56VA
225A
224A
225
1VA
224
0
9
BCR
14
N2
TX
N1
33
22
NEUTRAL
240VAC GENERATOR
OUTPUT TO
TRANSFER SWITCH
CONTACTOR
DIAGRAM KEY
BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB - CIRCUIT BREAKER, MAIN OUTPUT CS - IDLE CHOKE SOLENOID FS1 - FUEL SOLENOID FS2 - FUEL SOLENOID(530cc V-TWIN ONLY) F1 - FUSE 15 AMP HTO - HIGH OIL TEMPERATURE SWITCH ICT - IDLE CONTROL TRANSFORMER IM1 - IGNITION MODULE, CYLINDER #1 IM2 - IGNITION MODULE, CYLINDER #2
44
11
CB
23194 N2 N1
12Vdc
TRANSFER
RELAY
COIL
TR
240VAC
UTILITY
INPUT
LOP - LOW OIL PRESSURE SWITCH SC - STARTER CONTACTER SCR - STARTER CONTACTOR RELAY SM - STARTER MOTOR SP1, SP2 - SPARK PLUGS SW1 - SWITCH, AUTO / OFF / MANUAL DPDT, ON-OFF-ON SW2 - SWITCH, SET EXERCISE SPST, N.C., ON-(OFF) TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)
Page 87
Page 90
SECTION 4.2
PART 4
DC CONTROL
OPERATIONAL ANALYSIS
ENGINE STARTUP AND RUNNING
With the fuel solenoids open and ignition occurring, the engine starts. Engine startup and running may be briefly described as follows:
• Voltage pulses from the ignition magnetos are delivered to the circuit board via Wire 18. Once the circuit board determines that the engine is running, the circuit board (a) terminates cranking, and (b) terminates the choke solenoid (CS), and (c) turns on an “engine warm-up timer”.
= 12 VDC ALWAYS PRESENT
SCR
3
0
2
1
BATTERY
CHARGER
13
0
0
56
ELECTRONIC
VOLTAGE
REGULATOR
1
224B
2
225B
13
0
15
16
56
11
22
4
4
0
6
2
=AC VOLTAGE
= GROUND FOR CONTROL PURPOSES
0
0
16 0
= 12 VDC DURING CRANKING ONLY
= 12 VDC DURING ENGINE RUN CONDITION
224B
13
225B
86
18
85
18
86
85
4
13
6
2
16
14
MANUAL
194 15A
194
15
J2
CONTROL
PRINTED CIRCUIT
BOARD
SW1
GOVERNOR
ACTUATOR
AUTO
194
15A
4
194
15A
23915
239
SW2
15
15B
15A
1
J1
2
4
3
23
86
4 5
18 6 7 8
LC1
9
56
224
10
239
11 12
85 13 14
LC2
15
14
16
225
17 18 19
15B 20 21 22 23
0
90 CS1414
22 11
0
0
11
22
15
56
0
13
F1
15
86 LC2140
1823
14
14
85LC1
LC1
LC2
0
23
194
225B
224B
224
225
Page 88
Page 91
DC CONTROL
PART 4
SECTION 4.2
OPERATIONAL ANALYSIS
• The “engine warm-up timer” will run for about 5 seconds. When this timer finishes timing, board action will initi­ate transfer to the STANDBY power source. As shown in Figure 4 (below), the timer is still running and transfer
has not yet occurred.
• Generator AC output is available to transfer switch Terminal Lugs E1/E2 and to the normally open contacts of a
transfer relay. However, the transfer relay is de-energized and its contacts are open.
Figure 4. Circuit Condition - Engine Startup and Running
ENGINE AND ALTERNATOR
66
6
2
DPE
POWER
WINDING
BA
FIELD
0
11
S TATO R
22
33
44
POWER
WINDING
11
22
LC1
LC2
IM2
SP2
18
86
85
4
13
6
2
16
14
0
0
HTO
LOP
0
0
0
7766
0
62
FS1
0
FS2
IM1
SP1
4
13
16
SC
0
0
0
0
11
22
22
LC2
LC1
16
SM
11
33
RED
SC
BATTERY
12V
0
0
I.C.T.
BATTERY
CHARGE
WINDING
77
WINDING
0
11
22
33
44
0
23
194
225B
224B
7
67394
1
7766
77 66
224A 225A
224
225
14
224A
225A
56VA
225A
224A
225
1VA
224
0
9
BCR
14
N2
TX
N1
33
22
NEUTRAL
240VAC GENERATOR
OUTPUT TO
TRANSFER SWITCH
CONTACTOR
DIAGRAM KEY
BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB - CIRCUIT BREAKER, MAIN OUTPUT CS - IDLE CHOKE SOLENOID FS1 - FUEL SOLENOID FS2 - FUEL SOLENOID(530cc V-TWIN ONLY) F1 - FUSE 15 AMP HTO - HIGH OIL TEMPERATURE SWITCH ICT - IDLE CONTROL TRANSFORMER IM1 - IGNITION MODULE, CYLINDER #1 IM2 - IGNITION MODULE, CYLINDER #2
44
11
CB
23194 N2 N1
12Vdc
TRANSFER
RELAY
COIL
TR
240VAC
UTILITY
INPUT
LOP - LOW OIL PRESSURE SWITCH SC - STARTER CONTACTER SCR - STARTER CONTACTOR RELAY SM - STARTER MOTOR SP1, SP2 - SPARK PLUGS SW1 - SWITCH, AUTO / OFF / MANUAL DPDT, ON-OFF-ON SW2 - SWITCH, SET EXERCISE SPST, N.C., ON-(OFF) TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)
Page 89
Page 92
SECTION 4.2
PART 4
DC CONTROL
OPERATIONAL ANALYSIS
INITIAL TRANSFER TO THE “STANDBY” SOURCE
The generator is running, the circuit board’s “engine warm-up timer” is timing, and generator AC output is avail­able to transfer switch terminal lugs E1 and E2 and to the open contacts on the transfer relay. Initial transfer to the STANDBY power supply may be briefly described as follows:
• 12 volts DC output is delivered to the transfer relay (TR) actuating coil, via Wire 194, and terminal A of the transfer relay (TR) in the transfer switch. This 12 volts DC circuit is completed back to the board, via transfer
relay terminal B, and Wire 23. However, circuit board action holds the Wire 23 circuit open to ground and the transfer relay (TR) is de-energized.
• When the circuit board’s “engine warm-up timer” times out, circuit board action completes the Wire 23 circuit to
ground. The transfer relay then energizes and its normally open contacts close.
= 12 VDC ALWAYS PRESENT
SCR
3
0
2
1
BATTERY
CHARGER
13
0
0
56
ELECTRONIC
VOLTAGE
REGULATOR
1
224B
2
225B
13
0
15
16
56
11
22
4
4
0
6
2
=AC VOLTAGE
= GROUND FOR CONTROL PURPOSES
0
0
16 0
= 12 VDC DURING CRANKING ONLY
= 12 VDC DURING ENGINE RUN CONDITION
224B
13
225B
86
18
85
18
86
85
4
13
6
2
16
14
MANUAL
194 15A
194
15
J2
CONTROL
PRINTED CIRCUIT
BOARD
SW1
GOVERNOR
ACTUATOR
AUTO
194
15A
4
194
15A
23915
239
SW2
15
15B
15A
1
J1
2
4
3
23
86
4 5
18 6 7 8
LC1
9
56
224
10
239
11 12
85 13 14
LC2
15
14
16
225
17 18 19
15B 20 21 22 23
0
90 CS1414
22 11
0
0
11
22
15
56
0
13
F1
15
86 LC2140
1823
14
14
85LC1
LC1
LC2
0
23
194
225B
224B
224
225
Page 90
Page 93
DC CONTROL
PART 4
SECTION 4.2
OPERATIONAL ANALYSIS
• Standby power is now delivered to the standby closing coil (C2), via Wires E1 /E2, the normally open transfer relay contacts, Wire 205, limit switch XB1, Wire B, and a bridge rectifier. The standby closing coil energizes and the main current carrying contacts of the transfer switch are actuated to their STANDBY source side.
• As the main contacts move to their STANDBY source side, a mechanical interlock actuates limit switch XB1 to its open position and limit switch XA1 to its “Utility” side position. When XB1 opens, standby closing coil C2 3 de-energizes.
• Standby power is delivered to the LOAD terminals (T1/T2) of the transfer switch.
• As load is applied to the generator, the current transformer (ICT) induces AC voltage that is applied to the circuit board via Wires LC1 & LC2. This voltage is utilized for stepper motor control.
Figure 5. Circuit Condition - InitialTransfer to Standby
ENGINE AND ALTERNATOR
66
6
2
DPE
POWER
WINDING
BA
FIELD
0
11
S TATO R
22
33
44
POWER
WINDING
11
22
LC1
LC2
IM2
SP2
18
86
85
4
13
6
2
16
14
0
0
HTO
LOP
0
0
0
7766
0
62
FS1
0
FS2
IM1
SP1
4
13
16
SC
0
0
0
0
11
22
22
LC2
LC1
16
SM
11
33
RED
SC
BATTERY
12V
0
0
I.C.T.
BATTERY
CHARGE
WINDING
77
WINDING
0
11
22
33
44
0
23
194
225B
224B
7
67394
1
7766
77 66
224A 225A
224
225
14
224A
225A
56VA
225A
224A
225
1VA
224
0
9
BCR
14
N2
TX
N1
33
22
NEUTRAL
240VAC GENERATOR
OUTPUT TO
TRANSFER SWITCH
CONTACTOR
DIAGRAM KEY
BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB - CIRCUIT BREAKER, MAIN OUTPUT CS - IDLE CHOKE SOLENOID FS1 - FUEL SOLENOID FS2 - FUEL SOLENOID(530cc V-TWIN ONLY) F1 - FUSE 15 AMP HTO - HIGH OIL TEMPERATURE SWITCH ICT - IDLE CONTROL TRANSFORMER IM1 - IGNITION MODULE, CYLINDER #1 IM2 - IGNITION MODULE, CYLINDER #2
44
11
CB
23194 N2 N1
12Vdc
TRANSFER
RELAY
COIL
TR
240VAC
UTILITY
INPUT
LOP - LOW OIL PRESSURE SWITCH SC - STARTER CONTACTER SCR - STARTER CONTACTOR RELAY SM - STARTER MOTOR SP1, SP2 - SPARK PLUGS SW1 - SWITCH, AUTO / OFF / MANUAL DPDT, ON-OFF-ON SW2 - SWITCH, SET EXERCISE SPST, N.C., ON-(OFF) TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)
Page 91
Page 94
SECTION 4.2
PART 4
DC CONTROL
OPERATIONAL ANALYSIS
UTILITY VOLTAGE RESTORED / RE-TRANSFER TO UTILITY
The “Load” is powered by the standby power supply. The circuit board continues to seek an acceptable utility source voltage. On restoration of utility source voltage, the following events will occur:
• On restoration of utility source voltage above 75 percent of the nominal rated voltage, a “retransfer time delay” on the circuit board starts timing. The timer will run for about fifteen (15) seconds.
• At the end of fifteen (15) seconds, the “retransfer time delay” will stop timing and circuit board action will open the Wire 23 circuit to ground.The transfer relay (TR) will then de-energize.
• When the transfer relay (TR) de-energizes, its normally-closed contacts close. Utility source voltage is then delivered to the utility closing coil (C1), via Wires N1A/N2A, the closed TR contacts, Wire 126, limit switch XA1,
and a bridge rectifier.
= 12 VDC ALWAYS PRESENT
SCR
3
0
2
1
BATTERY
CHARGER
13
0
0
56
ELECTRONIC
VOLTAGE
REGULATOR
1
224B
2
225B
13
0
15
16
56
11
22
4
4
0
6
2
=AC VOLTAGE
= GROUND FOR CONTROL PURPOSES
0
0
16 0
= 12 VDC DURING CRANKING ONLY
= 12 VDC DURING ENGINE RUN CONDITION
224B
13
225B
86
18
85
18
86
85
4
13
6
2
16
14
MANUAL
194 15A
194
15
J2
CONTROL
PRINTED CIRCUIT
BOARD
SW1
GOVERNOR
ACTUATOR
AUTO
194
15A
4
194
15A
23915
239
SW2
15
15B
15A
1
J1
2
4
3
23
86
4 5
18 6 7 8
LC1
9
56
224
10
239
11 12
85 13 14
LC2
15
14
16
225
17 18 19
15B 20 21 22 23
0
90 CS1414
22 11
0
0
11
22
15
56
0
13
F1
15
86 LC2140
1823
14
14
85LC1
LC1
LC2
0
23
194
225B
224B
224
225
Page 92
Page 95
DC CONTROL
PART 4
SECTION 4.2
OPERATIONAL ANALYSIS
• The utility closing coil (C1) energizes and moves the main current carrying contacts to their NEUTRAL posi­tion. The main contacts move to an over center position past NEUTRAL and spring force closes them to their UTILITY side. LOAD terminals are now powered by the UTILITY source.
• Movement of the main contacts to UTILITY actuates limit switches XA1/XB1. XA1 opens and XB1 actuates to its STANDBY source side.
• The generator continues to run.
Figure 6. Circuit Condition - Utility Voltage Restored
ENGINE AND ALTERNATOR
66
6
2
DPE
POWER
WINDING
BA
FIELD
0
11
S TATO R
22
33
44
POWER
WINDING
11
22
LC1
LC2
IM2
SP2
18
86
85
4
13
6
2
16
14
0
0
HTO
LOP
0
0
0
7766
0
62
FS1
0
FS2
IM1
SP1
4
13
16
SC
0
0
0
0
11
22
22
LC2
LC1
16
SM
11
33
RED
SC
BATTERY
12V
0
0
I.C.T.
BATTERY
CHARGE
WINDING
77
WINDING
0
11
22
33
44
0
23
194
225B
224B
7
67394
1
7766
77 66
224A 225A
224
225
14
224A
225A
56VA
225A
224A
225
1VA
224
0
9
BCR
14
N2
TX
N1
33
22
NEUTRAL
240VAC GENERATOR
OUTPUT TO
TRANSFER SWITCH
CONTACTOR
DIAGRAM KEY
BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB - CIRCUIT BREAKER, MAIN OUTPUT CS - IDLE CHOKE SOLENOID FS1 - FUEL SOLENOID FS2 - FUEL SOLENOID(530cc V-TWIN ONLY) F1 - FUSE 15 AMP HTO - HIGH OIL TEMPERATURE SWITCH ICT - IDLE CONTROL TRANSFORMER IM1 - IGNITION MODULE, CYLINDER #1 IM2 - IGNITION MODULE, CYLINDER #2
44
11
CB
23194 N2 N1
12Vdc
TRANSFER
RELAY
COIL
TR
240VAC
UTILITY
INPUT
LOP - LOW OIL PRESSURE SWITCH SC - STARTER CONTACTER SCR - STARTER CONTACTOR RELAY SM - STARTER MOTOR SP1, SP2 - SPARK PLUGS SW1 - SWITCH, AUTO / OFF / MANUAL DPDT, ON-OFF-ON SW2 - SWITCH, SET EXERCISE SPST, N.C., ON-(OFF) TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)
Page 93
Page 96
SECTION 4.2
PART 4
DC CONTROL
OPERATIONAL ANALYSIS
ENGINE SHUTDOWN
Following retransfer back to the utility source, an “engine cool-down timer” on the circuit board starts timing. When that timer has timed out (approximately one minute), circuit board action will de-energize the circuit board’s run relay. The following events will then occur:
• The DC circuit to Wire 14 and the fuel solenoids (FS1 & FS2) will be opened. The fuel solenoids will de-ener gize and close to terminate the engine fuel supply.
= 12 VDC ALWAYS PRESENT
SCR
3
0
2
1
BATTERY
CHARGER
13
0
0
56
ELECTRONIC
VOLTAGE
REGULATOR
1
224B
2
225B
13
0
15
16
56
11
22
4
4
0
6
2
=AC VOLTAGE
= GROUND FOR CONTROL PURPOSES
0
0
16 0
= 12 VDC DURING CRANKING ONLY
= 12 VDC DURING ENGINE RUN CONDITION
224B
13
225B
86
18
85
18
86
85
4
13
6
2
16
14
-
MANUAL
194 15A
194
15
J2
CONTROL
PRINTED CIRCUIT
BOARD
SW1
GOVERNOR
ACTUATOR
AUTO
194
15A
4
194
15A
23915
239
SW2
15
15B
15A
1
J1
2
4
3
23
86
4 5
18 6 7 8
LC1
9
56
224
10
239
11 12
85 13 14
LC2
15
14
16
225
17 18 19
15B 20 21 22 23
0
90 CS1414
22 11
0
0
11
22
15
56
0
13
F1
15
86 LC2140
1823
14
14
85LC1
LC1
LC2
0
23
194
225B
224B
224
225
Page 94
Page 97
DC CONTROL
PART 4
SECTION 4.2
OPERATIONAL ANALYSIS
• The battery charge relay (BCR) connected to Wire 14 will be de-energized. This will cause transformer (TX) voltage to power the battery charger again.
• Circuit board action will connect the engine’s ignition magnetos (IM1 & IM2) to ground, via Wire 18. Ignition will be terminated.
• Without fuel flow and without ignition, the engine will shut down.
Figure 7. Circuit Condition - Retransfer to “Utility” and Engine Shutdown
ENGINE AND ALTERNATOR
66
6
2
DPE
POWER
WINDING
BA
FIELD
0
11
S TATO R
22
33
44
POWER
WINDING
11
22
LC1
LC2
IM2
SP2
18
86
85
4
13
6
2
16
14
0
0
HTO
LOP
0
0
0
7766
0
62
FS1
0
FS2
IM1
SP1
4
13
16
SC
0
0
0
0
11
22
22
LC2
LC1
16
SM
11
33
RED
SC
BATTERY
12V
0
0
I.C.T.
BATTERY
CHARGE
WINDING
77
WINDING
0
11
22
33
44
0
23
194
225B
224B
7
67394
1
7766
77 66
224A 225A
224
225
14
224A
225A
56VA
225A
224A
225
1VA
224
0
9
BCR
14
N2
TX
N1
33
22
NEUTRAL
240VAC GENERATOR
OUTPUT TO
TRANSFER SWITCH
CONTACTOR
DIAGRAM KEY
BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB - CIRCUIT BREAKER, MAIN OUTPUT CS - IDLE CHOKE SOLENOID FS1 - FUEL SOLENOID FS2 - FUEL SOLENOID(530cc V-TWIN ONLY) F1 - FUSE 15 AMP HTO - HIGH OIL TEMPERATURE SWITCH ICT - IDLE CONTROL TRANSFORMER IM1 - IGNITION MODULE, CYLINDER #1 IM2 - IGNITION MODULE, CYLINDER #2
44
11
CB
23194 N2 N1
12Vdc
TRANSFER
RELAY
COIL
TR
240VAC
UTILITY
INPUT
LOP - LOW OIL PRESSURE SWITCH SC - STARTER CONTACTER SCR - STARTER CONTACTOR RELAY SM - STARTER MOTOR SP1, SP2 - SPARK PLUGS SW1 - SWITCH, AUTO / OFF / MANUAL DPDT, ON-OFF-ON SW2 - SWITCH, SET EXERCISE SPST, N.C., ON-(OFF) TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)
Page 95
Page 98
SECTION 4.3
TROUBLESHOOTING FLOW CHARTS
Problem 8 - Engine Will Not Crank When Utility Power Source Fails
PART 4
DC CONTROL
VERIFY UTILITY
SOURCE IS “OFF”
SYSTEM READY
LIGHT SHOULD BE
FLASHING
ON
TURN “OFF” -
RETEST
TEST 41 - CHECK
OFF
REPLACE PRINTED
CIRCUIT BOARD
POSITION OF
AUTO-OFF-MANUAL
SWITCH IS “OFF”
SET TO “AUTO” -
SWITCH
RETEST
SWITCH IS
IN “AUTO”
TEST 44 - CHECK
WIRE
15/15A/15B/239/0
VOLTAGE
TEST 42 - TRY A
MANUAL START
ENGINE DOES
NOT CRANK
GO TO PROBLEM 9
GOOD
ENGINE
CRANKS
TEST 43 - TEST
AUTO-OFF-MANUAL
SWITCH
BAD
REPLACE
Problem 9 - Engine Will Not Crank When AUTO-OFF-MANUAL Switch is Set to MANUAL
TEST 45 - CHECK15
AMP FUSE
BAD
REPLACE
REPAIR /
REPLACE
NOTE: If a starting problem is encountered, the engine itself should be thoroughly checked to eliminate it as the cause of star ting difficulty. It is a good practice to check the engine for freedom of rotation by removing the spark plugs and turning the crankshaft over slowly by hand, to be sure it rotates freely.
WARNING: DO NOT ROTATE
ENGINE WITH ELECTRIC STARTER WITH SPARK PLUGS REMOVED. ARCING AT THE PLUG ENDS MAY IGNITE THE LP OR NG VAPOR EXITING THE SPARK PLUG HOLE.
GOOD
RECHARGE /
REPLACE
BAD
TEST 46 - CHECK
BATTERY - LOW
BATTERY LED SHOULD
BE OFF
BAD
TEST 44 - CHECK
WIRE
15/15A/15B/239/0
VOLTAGE
GOOD
GOOD
GOOD
GOOD
AUTO-OFF-MANUAL
REPLACE PRINTED
CIRCUIT BOARD
TEST 50 - TEST
STARTER MOTOR
TEST 47 - CHECK
WIRE 56 VOLTAGE
BAD
TEST 43 - TEST
SWITCH
BAD
BAD
BAD
REPLACE
GOOD
REPLACE
GOOD
TEST 48 - CHECK
STARTER
CONTACTOR RELAY
(V-TWIN ONLY)
GOOD
TEST 49 - CHECK
STARTER
CONTACTOR
BAD
Page 96
Page 99
DC CONTROL
BAD
REPLACE CHOKE SOLENOID
CLEAN,
REGAP OR
REPLACE
REPLACE CIRCUIT BOARD
REPLACE FUEL SOLENOID
TEST 51 - CHECK
FUEL SUPPLY
AND PRESSURE
TEST 63 - CHECK
FUEL REGULATOR
TEST 55 -
CHECK FOR
IGNITION
SPARK
TEST 54 - CHECK
CHOKE SOLENOID
TEST 59 - CHECK
AND ADJUST
IGNITION
MAGNETOS
TEST 58 - CHECK
SHUTDOWN
WIRE
TEST 62 - CHECK
AND ADJUST
VALVES
TEST 56 -
CHECK SPARK
PLUGS
TEST 57 - CHECK
ENGINE
COMPRESSION
TEST 53 - CHECK
FUEL SOLENOID
TEST 52 - CHECK
CIRCUIT BOARD
WIRE 14 OUTPUT
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
BAD
BAD
BAD
BAD
BAD
BAD
BAD
BAD
BAD
BAD
REPAIR OR
REPLACE
BAD
REPAIR OR REPLACE
ADJUST OR
REPLACE
REPAIR OR
REPLACE SHORTED
WIRE 18 OR CIRCUIT
BOARD
CHECK
FLYWHEEL
KEY TEST 59
REFER TO ENGINE
SERVICE MANUAL
FIND AND CORRECT
CAUSE OF NO FUEL
OR LOW PRESSURE
READJUST
Problem 10 - Engine Cranks but Won’t Start
CHECK AIR FILTER -
REPLACE AS NEEDED
SINGLE CYLINDER UNITS
V-TWIN UNITS
TEST 12A - CHECK
STEPPER MOTOR
CONTROL
PART 4
SECTION 4.3
TROUBLESHOOTING FLOW CHARTS
Page 97
Page 100
SECTION 4.3
TROUBLESHOOTING FLOW CHARTS
Problem 11 - Engine Starts Hard and Runs Rough / Lacks Power
PART 4
DC CONTROL
TEST 51 - CHECK
FUEL SUPPLY
AND PRESSURE
BAD
FIND AND CORRECT
CAUSE OF NO FUEL OR LOW PRESSURE
BAD
TEST 59 - CHECK
AND ADJUST
IGNITION MAGNETOS
IF RECONFIGURED TO LP GAS,
GOOD
TEST 55 - CHECK
FOR IGNITION
SPARK
PROCEDURE WAS FOLLOWED.
VERIFY THAT PROPER
(REFER TO SECTION 1.3)
TEST 54 - CHECK
CHOKE SOLENOID
BAD
REPLACE CHOKE SOLENOID
GOOD
TEST 56 - CHECK
SPARK PLUGS
CLEAN, REGAP
OR REPLACE
BAD
GOOD
SINGLE CYLINDER UNITS
CHECK AIR FILTER -
REPLACE AS NEEDED
V-TWIN UNITS
GOOD
READJUST
BAD
TEST 62 - CHECK
AND ADJUST
VALVES
GOOD
GOOD
BAD
ADJUST OR
REPLACE
GOOD
CHECK
FLYWHEEL
KEY TEST 59
READJUST
TEST 63 - CHECK
FUEL REGULATOR
BAD
REPAIR OR
REPLACE
BAD
GOOD
TEST 12 - CHECK
AND ADJUST
ENGINE
GOVERNOR
GOOD
TEST 57 - CHECK
ENGINE
COMPRESSION
BAD
REFER TO ENGINE
SERVICE MANUAL
SINGLE CYLINDER UNITS
TEST 12A - CHECK
STEPPER MOTOR
CONTROL
BAD
REPAIR OR
REPLACE
V-TWIN UNITS
Page 98
Loading...