Guardian 5240, 5241, 5282, 5281, 5280 Diagnostic Repair Manual

...
MODELS:
5240, 5280 (7 kW NG, 6 kW LP) 5241, 5281 (9 kW NG, 10 kW LP) 5242, 5282 (13 kW NG, 13 kW LP)
5243, 5283 (15 kW NG, 16 kW LP) 5244, 5284 (15 kW NG, 16 kW LP)
DIAGNOSTIC
DIAGNOSTIC
REPAIR MANUAL
REPAIR MANUAL
AUTOMATIC STANDBY GENERATORS
www.guardiangenerators.com
ELECTRICAL FORMULAS
TO FIND KNOWN VALUES 1-PHASE 3-PHASE
KILOWATTS (kW)
KVA
AMPERES
WATTS
NO. OF ROTOR POLES
FREQUENCY
RPM
kW (required for Motor)
Volts, Current, Power Factor
Volts, Current
kW, Volts, Power Factor
Volts, Amps, Power Factor Volts x Amps E x I x 1.73 x PF
Frequency, RPM
RPM, No. of Rotor Poles
Frequency, No. of Rotor Poles
Motor Horsepower, Efficiency
E x I 1000
E x I 1000
kW x 1000
E
2 x 60 x Frequency
RPM
RPM x Poles
2 x 60
2 x 60 x Frequency
Rotor Poles
HP x 0.746
Efficiency
E x I x 1.73 x PF
1000
E x I x 1.73
1000
kW x 1000
E x 1.73 x PF
2 x 60 x Frequency
RPM
RPM x Poles
2 x 60
2 x 60 x Frequency
Rotor Poles
HP x 0.746
Efficiency
RESISTANCE
VOLTS
AMPERES
E = VOLTS I = AMPERES R = RESISTANCE (OHMS) PF = POWER FACTOR
Volts, Amperes
Ohm, Amperes I x R I x R
Ohms, Volts
E
I
E R
E
I
E R
Contents
SPECIFICATIONS..................................................... 4
Generator ................................................................ 4
Stator Winding Resistance Values/
Rotor Resistance ..................................................... 4
Engine ..................................................................... 5
Fuel Consumption ................................................... 5
Mounting Dimensions ........................................... 6-7
Major Features ........................................................ 8
PART 1 - GENERAL INFORMATION ....................... 9
1.1 Generator Identification ................................... 10
1.2 Prepackaged Installation Basics ..................... 11
Introduction ......................................................11
Selecting A Location ........................................11
Grounding The Generator ................................11
The Fuel Supply ...............................................11
The Transfer Switch / Load Center ...................11
Power Source And Load Lines .........................13
System Control Interconnections .....................13
1.3 Preparation Before Use ................................... 14
General ............................................................14
Fuel Requirements...........................................14
Fuel Consumption ............................................14
Reconfiguring The Fuel System .......................14
Engine Oil Recommendations .........................16
1.4 Testing, Cleaning and Drying........................... 16
Meters ............................................................17
The VOM ..........................................................17
Measuring AC Voltage .....................................17
Measuring DC Voltage .....................................17
Measuring AC Frequency ................................17
Measuring Current ...........................................18
Measuring Resistance .....................................18
Electrical Units .................................................19
Ohm's Law .......................................................19
Visual Inspection ..............................................20
Insulation Resistance .......................................20
The Megohmmeter...........................................20
Stator Insulation Resistance Test .....................21
Rotor Insulation Resistance Test ......................22
Cleaning The Generator...................................22
Drying The Generator ......................................22
1.5 Engine-Generator Protective Devices ............. 23
General ............................................................23
Low Battery ......................................................23
Low Oil Pressure Shutdown .............................23
High Temperature Switch .................................23
Overspeed Shutdown ......................................23
RPM Sensor Failure .........................................23
Overcrank Shutdown .......................................24
1.6 Operating Instructions ..................................... 25
Control Panel ...................................................25
To Select Automatic Operation ........................26
Manual Transfer To “Standby” And
Manual Startup ....................................26
Manual Shutdown And Retransfer
Back To “Utility” ....................................27
1.7 Automatic Operating Parameters .................... 28
Introduction ......................................................28
Automatic Operating Sequences .....................28
PART 2 - AC GENERATORS.................................. 29
2.1 Description and Components .......................... 30
Introduction ......................................................30
Engine-generator Drive System .......................30
The AC Generator ............................................30
Rotor Assembly ................................................30
Stator Assembly ...............................................31
Brush Holder And Brushes ..............................31
Other AC Generator Components ...................31
2.2 Operational Analysis ....................................... 33
Rotor Residual Magnetism...............................33
Field Boost .......................................................33
Operation .........................................................34
2.3 Troubleshooting Flowcharts ............................. 35
Problem 1 - Generator Produces Zero
Voltage or Residual Voltage .......... 35-36
Problem 2 - Generator Produces
Low Voltage at No-Load ......................37
Problem 3 - Generator Produces
High Voltage at No-Load .....................37
Problem 4 - Voltage and Frequency Drop
Excessively When Loads are Applied .38
2.3 Diagnostic Tests .............................................. 39
Introduction ......................................................39
Safety ............................................................39
Test 1 - Check Main Circuit Breaker.................39
Test 2 - Check AC Output Voltage ....................39
Test 4 - Fixed Excitation Test/Rotor
Amp Draw Test ....................................40
Test 5 - Wire Continuity ....................................41
Test 6 - Check Field Boost ...............................42
Test 7 - Testing The Stator With a VOM ...........42
Test 8 - Resistance Check of Rotor Circuit ......44
Test 9 - Check Brushes and Slip Rings ............44
Test 10 - Test Rotor Assembly .........................45
Test 11 - Check AC Output Frequency.............45
Page 1
Test 12 - Check And Adjust Engine Governor
(Single Cylinder Units) .........................46
Test 12A - Check Stepper Motor Control
(V-twin Engine Units) ...........................46
Test 13 - Check And Adjust
Voltage Regulator ................................48
Test 14 - Check Voltage And
Frequency Under Load ........................48
Test 15 - Check For Overload Condition ..........48
Test 16 - Check Engine Condition ....................48
PART 3 - "V-TYPE PREPACKAGED
TRANSFER SWITCHES.......................... 49
3.1 Description and Components .......................... 50
General ............................................................50
Enclosure .........................................................50
Transfer Mechanism .........................................51
Transfer Relay .................................................51
Neutral Lug ......................................................52
Manual Transfer Handle ..................................52
Terminal Block .................................................52
Fuse Holder .....................................................53
3.2 Operational Analysis ....................................... 54
Utility Source Voltage Available .......................56
Utility Source Voltage Failure ..........................57
Transfer To Standby ........................................58
Transfer To Standby ........................................59
Utility Restored.................................................60
Utility Restored, Transfer Switch
De-energized .......................................61
Utility Restored,
Retransfer Back To Utility ....................62
Transfer Switch In Utility ...................................63
3.3 Troubleshooting Flow Charts ........................... 64
Introduction To Troubleshooting .......................64
Problem5-InAutomatic Mode,
No Transfer to Standby ........................64
Problem6-InAutomatic Mode, Generator
Starts When Loss of Utility Occurs, Generator Shuts Down When Utility Returns But There Is
No Retransfer To Utility Power .............65
Problem 7 - Blown F1 or F2 Fuse ....................65
3.4 Diagnostic Tests .............................................. 66
General ............................................................66
Test 21 - Check Voltage at
Terminal Lugs E1, E2 ..........................66
Test 22 - Check Voltage at
Standby Closing Coil C2 .....................67
Test 23 - Test Transfer Relay TR ......................67
Test 24 - Check Manual Transfer
Switch Operation .................................68
Test 25 - Test Limit Switch XB1 ........................69
Test 26 - Check 23 And 194
Wiring/Connections .............................69
Test 27- Check Voltage At
Terminal Lugs N1, N2 ..........................70
Test 28 - Check Voltage At Utility 1
And Utility 2 Ter minals .........................70
Test 29 - Check Voltage At
Utility Closing Coil C1 ..........................71
Test 30 - Check Fuses F1 And F2 ...................71
Test 31 - Test Limit Switch Xa1 ........................72
Test 32 - Continuity Test Of Wiring (C1) ...........72
Test 33 - Continuity Test Of Wiring (C2) ...........72
Test 34 - Check N1 And N2 Wiring ..................73
Test 35 - Check Transformer (Tx) .....................73
PART 4 - DC CONTROL ......................................... 75
4.1 Description and Components .......................... 76
General ............................................................76
Terminal Strip / Interconnection Ter minal .........76
Transformer (TX) ..............................................76
Circuit Board ....................................................76
AUTO-OFF-MANUAL Switch ...........................80
15 Amp Fuse....................................................80
4.2 Operational Analysis ....................................... 82
Introduction ......................................................82
Utility Source Voltage Available ........................82
Initial Dropout Of Utility Source Voltage ...........84
Utility Voltage Dropout And
Engine Cranking ..................................86
Engine Startup And Running ...........................88
Initial Transfer To The “Standby” Source ...........90
Utility Voltage Restored /
Re-transfer To Utility ............................92
Engine Shutdown ........................................... 94
4.3 Troubleshooting Flow Charts ........................... 96
Problem 8 - Engine Will Not Crank
When Utility Power Source Fails .........96
Problem 9 - Engine Will Not Crank
When AUTO-OFF-MANUAL Switch
is Set to "MANUAL" .............................96
Problem 10 - Engine Cranks
but Won't Start .....................................97
Problem 11 - Engine Starts Hard and
Runs Rough / Lacks Power .................98
Problem 12 - Engine Starts and Runs,
Then Shuts Down ................................99
Problem 13 - No Battery Charge ...................100
Problem 14 - Unit Starts and Transfer Occurs
When Utility Power is Available ........101
Page 2
Problem 15 - Generator Starts
Immediately in Auto - No Transfer to
Standby. Utility Voltage is Present .....101
Problem 16 - 15 Amp Fuse (F1) Blown ..........102
Problem 17 - Generator Will Not Exercise .....102
Problem 18 - No Low Speed Exercise ...........102
4.4 Diagnostic Tests ............................................ 103
Introduction .................................................. 103
Test 41 - Check Position Of
AUTO-OFF-MANUAL Switch ........... 103
Test 42 - Try A Manual Start ......................... 103
Test 43 - Test AUTO-OFF-MANUAL Switch . 103
Test 44 - Check Wire 15/15A/15B/239/0
Voltage ..............................................104
Test 45 - Check 15 Amp Fuse ........................105
Test 46 - Check Battery .................................105
Test 47 - Check Wire 56 Voltage ...................106
Test 48 - Test Starter Contactor Relay
(V-twin Only) ......................................106
Test 49 - Test Starter Contactor .....................106
Test 50 - Test Starter Motor ............................107
Test 51 - Check Fuel Supply
And Pressure.....................................109
Test 52 - Check Circuit Board
Wire 14 Output ..................................110
Test 53 - Check Fuel Solenoid .......................111
Test 54 - Check Choke Solenoid
(V-twins Units Only) ...........................112
Test 55 - Check For Ignition Spark .................113
Test 56 - Check Spark Plugs ..........................114
Test 57 - Check Engine / Cylinder Leak Down
Test / Compression Test114
Test 58 - Check Shutdown Wire .....................115
Test 59 - Check And Adjust
Ignition Magnetos ..............................116
Test 60 - Check Oil Pressure Switch
And Wire 86 .......................................117
Test 61 - Check High Oil
Temperature Switch ...........................118
Test 62 - Check And Adjust Valves ................119
Test 63 - Check Fuel Regulator
(7 Kw Natural Gas Units Only) ..........117
Test 64 - Check Battery Charge Output .........120
Test 65 - Check Transformer (TX)
Voltage Output ...................................118
Test 66 - Check AC Voltage At
Battery Charger .................................121
Test 67 - Check Battery Charge
Relay (BCR) ......................................122
Test 68 - Check Battery Charge
Winding Harness ...............................122
Test 69 - Check Battery Charger Wiring .......123
Test 70 - Check Wire 18 Continuity ................123
Test 71 - Check N1 And N2 Voltage ...............123
Test 72 - Check Utility Sensing Voltage
At The Circuit Board ..........................124
Test 73 - Test Set Exercise Switch .................124
Test 75 - Check Battery Voltage Circuit ..........124
Test 76 - Check Cranking And
Running Circuits ................................124
Test 77 - Test Exercise Function ....................126
Test 78 - Check Dip Switch Settings ..............126
Test 79 - Check Idle Control Transformer
(V-twin Units Only) .............................126
Test 80 - Check LC1 & LC2 Wiring ................126
Test 81 - Check Idle Control Transformer
Primary Wiring ...................................127
PART 5 - OPERATIONAL TESTS......................... 129
5.1 System Functional Tests ................................ 130
Introduction ....................................................130
Manual Transfer Switch Operation .................130
Electrical Checks ...........................................130
Generator Tests Under Load ..........................131
Checking Automatic Operation ......................132
Setting The Exercise Timer ............................132
PART 6 - DISASSEMBLY ..................................... 133
6.1 Major Disassembly ........................................ 134
Major Disassembly .........................................134
Front Engine Access. .....................................136
Torque Requirements
(Unless Otherwise Specified) ............136
PART 7 - ELECTRICAL DATA .............................. 137
Drawing 0F7820 Wiring Diagram, 7kWHSB
Models 005240 & 005280 ................................... 138
Drawing 0F7821 Wiring Schematic, 7kWHSB
Models 005240 & 005280 ................................... 140
Drawing 0F7822 Wiring Diagram, 10, 13 & 16 kW HSB Models 005241 & 005281 Models 005242 & 005282 Models 005243 & 005283
Models 005244 & 005284 ................................... 142
Drawing 0F7823 Schematic, 10, 13 & 16 kW HSB Models 005241 & 005281 Models 005242 & 005282 Models 005243 & 005283
Models 005244 & 005284 ................................... 144
Drawing 0F9070 Wiring Diagram, Transfer Switch
8 Circuit/16 Circuit ............................................... 146
Drawing 0F9775 Wiring Diagram, Schematic
8 Circuit/16 Circuit ............................................... 147
Page 3
SPECIFICATIONS
GENERATOR
Model
005240 & 005280 005241 & 005281 005242 & 005282
Rated Max. Continuous Power Capacity (Watts*) 6,000 NG/7,000 LP 9,000 NG/10,000 LP 13,000 NG/13,000 LP 15,000 NG/16,000 LP
Rated Voltage 120/240 120/240 120/240 120/240
Rated Max. Continuous Load Current (Amps)
120 Volts** 50.0 NG/58.3 LP 75.0 NG/83.3 LP 108.3 NG/108.3 LP 125 NG/133.3 LP
240 Volts 25.0 NG/29.2 LP 37.5 NG/41.7 LP 54.1 NG/54.1 LP 52.5 NG/66.6 LP
Main Line Circuit Breaker 30 Amp 45 Amp 55 Amp 65 Amp
Circuits***
50A, 240V - - - 1
40A, 240V - - 1 1
30A, 240V 1 1 1 -
20A, 240V - 1 - 1
20A, 120V 1 3 3 5
15A, 120V 5 3 5 5
Phase 1 1 1 1
Number of Rotor Poles 2 2 2 2
Rated AC Frequency 60 Hz 60 Hz 60 Hz 60 Hz
Power Factor 1 1 1 1
Recommended Air Filter Part # 0C8127 Part # 0E9581 Part # 0C8127 Part # 0C8127
Battery Requirement Group 26
12 Volts and
350 Cold-cranking
Amperes Minimum
Group 26
12 Volts and
525 Cold-cranking
Amperes Minimum
Group 26
12 Volts and
525 Cold-cranking
Amperes Minimum
Battery Warming Blanket 0F6148DSRV
Weight (Unit Only) 336 Pounds 375 Pounds 425.5 Pounds 445 & 414 Pounds
Enclosure Steel/Aluminum
Normal Operating Range -20°F (-28.8°C) to 104°F (40°C)
005243 & 005283
005244 & 005284
Group 26
12 Volts and
525 Cold-cranking
Amperes Minimum
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.Maximum power
decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60° F) ambient temperature.
** Load current values shown for 120 volts are maximum TOTAL values for two separate circuits.The maximum current in each circuit must not exceed the value stated for 240 volts.
*** Circuits to be moved from main panel to transfer switch load center must be protected by same size breaker. For example, a 15 amp circuit in main panel must be a 15 amp circuit in
transfer switch.
STATOR WINDING RESISTANCE VALUES / ROTOR RESISTANCE
Power Winding: Across 11 & 22 0.223-0.259 ohms 0.144 ohms 0.115 ohms 0.080 ohms
Power Winding: Across 33 & 44 0.223-0.259 ohms 0.144 ohms 0.115 ohms 0.080 ohms
Excitation Winding: Across2&6 1.528-1.769 ohms 1.238 ohms 1.256 ohms 1.092 ohms
Battery Charge Winding: Across 66 & 77 0.146-0.169 ohms 0.158 ohms 0.164 ohms 0.130 ohms
Rotor Resistance 11.88-13.76 ohms 11.8 ohms 12.6 ohms 22.0 ohms
Page 4
005240, 005280
(6/7 kW)
005241, 005281
(9/10 kW)
005242, 005282
(13/13 kW)
005243, 005283 005244, 005284
(15/16 kW)
ENGINE
SPECIFICATIONS
Model 005240 & 005280 005241 & 005281 005242 & 005282
005243 & 005283
005244 & 005284
Type of Engine GH-410 GT-530 GT-990 GT-990
Number of Cylinders 1 2 2 2
Rated Horsepower 14.5 @ 3,600 rpm 18 @ 3,600 rpm 30 @ 3,600 rpm 30 @ 3,600 rpm
Displacement 410cc 530cc 992cc 992cc
Cylinder Block
Aluminum w/Cast Iron
Sleeve
Aluminum w/Cast Iron
Sleeve
Aluminum w/Cast Iron
Sleeve
Aluminum w/Cast Iron
Sleeve
Valve Arrangement Overhead Valves Overhead Valves Overhead Valves Overhead Valves
Ignition System Solid-state w/Magneto Solid-state w/Magneto Solid-state w/Magneto Solid-state w/Magneto
Recommended Spark Plug RC14YC BPR6HS RC12YC RC12YC
Spark Plug Gap 0.76 mm (0.030 inch) 0.76 mm (0.030 inch) 1.02 mm (0.040 inch) 1.02 mm (0.040 inch)
Compression Ratio 8.6:1 9.5:1 9.5:1 9.5:1
Starter 12 VDC 12 VDC 12 VDC 12 VDC
Oil Capacity Including Filter Approx. 1.5 Qts Approx. 1.7 Qts Approx. 1.7 Qts Approx. 1.7 Qts
Recommended Oil Filter Part # 070185B Par t # 070185B Part # 070185B Part # 070185B
Recommended Air Filter Part # 0C8127 Part # 0E9581 Part # 0C8127 Part # 0C8127
Operating RPM 3,600 3,600 3,600 3,600
FUEL CONSUMPTION
Model # Natural Gas* LP Vapor**
1/2 Load Full Load 1/2 Load Full Load
005240, 005280 (6/7 kW) 66 119 0.82/30 1.47/54
005241, 005281 (9/10 kW) 102 156 1.25/46 1.93/70
005242, 005282 (13/13 kW) 156 220 1.55/57 2.18/80
005243, 005283 (15/16 kW) 005244, 005284 (15/16 kW)
* Natural gas is in cubic feet per hour.
**LP is in gallons per hour/cubic feet per hour.
Values given are approximate.
173 245 1.59/59 2.51/92
Page 5
SPECIFICATIONS
MOUNTING DIMENSIONS
Page 6
MOUNTING DIMENSIONS
SPECIFICATIONS
Page 7
SPECIFICATIONS
MAJOR FEATURES
7 kW, Single Cylinder GH-410 Engine
Exhaust Enclosure
Composite Base
Oil Dipstick
Data Decal
Air Filter Cover
Battery CompartmentOil Filter
Control Panel
Fuel Inlet (Back)
Fuel Regulator
Exhaust Enclosure
Composite Base
10 kW, V-twin GT-530 Engine
Control
Oil Dipstick
Data Decal
Battery CompartmentOil Filter
Panel
Air Filter
Fuel Inlet (Back)
Fuel Regulator
13 kW and 16 kW, V-twin GT-990 Engine
Air Filter Cover
Oil Dipstick
Exhaust Enclosure
Composite Base
Data Decal
Control Panel
Fuel Inlet (Back)
Fuel Regulator
Battery CompartmentOil Filter
Page 8
PART 1
GENERAL
INFORMATION
Air-cooled, Prepackaged
Automatic Standby Generators
TABLE OF CONTENTS
PART TITLE PAGE
1.1 Generator Identification 10
1.2 Prepackaged Installation
Basics
1.3 Preparation Before Use 14
1.4 Testing, Cleaning and Drying 16
1.5 Engine-Generator Protective
Devices
1.6 Operating Instructions 25
1.7 Automatic Operating
Parameters
11
23
28
1.1 Generator Identification
1.2 Prepackaged Installation Basics ..................... 11
Introduction ......................................................11
Selecting A Location ........................................11
Grounding The Generator ................................11
The Fuel Supply ...............................................11
The Transfer Switch / Load Center ...................11
Power Source And Load Lines .........................13
System Control Interconnections .....................13
1.3 Preparation Before Use ................................... 14
General ............................................................14
Fuel Requirements...........................................14
Fuel Consumption ............................................14
Reconfiguring The Fuel System .......................14
Engine Oil Recommendations .........................16
1.4 Testing, Cleaning and Drying........................... 16
Meters ............................................................17
The VOM ..........................................................17
Measuring AC Voltage .....................................17
Measuring DC Voltage .....................................17
Measuring AC Frequency ................................17
Measuring Current ...........................................18
Measuring Resistance .....................................18
Electrical Units .................................................19
Ohm's Law .......................................................19
................................... 10
Visual Inspection ..............................................20
Insulation Resistance .......................................20
The Megohmmeter...........................................20
Stator Insulation Resistance Test .....................21
Rotor Insulation Resistance Test ......................22
Cleaning The Generator...................................22
Drying The Generator ......................................22
1.5 Engine-Generator Protective Devices ............. 23
General ............................................................23
Low Battery ......................................................23
Low Oil Pressure Shutdown .............................23
High Temperature Switch .................................23
Overspeed Shutdown ......................................23
RPM Sensor Failure .........................................23
Overcrank Shutdown .......................................24
1.6 Operating Instructions ..................................... 25
Control Panel ...................................................25
To Select Automatic Operation ........................26
Manual Transfer To “Standby” And
Manual Startup ....................................26
Manual Shutdown And Retransfer
Back To “Utility” ....................................27
1.7 Automatic Operating Parameters .................... 28
Introduction ......................................................28
Automatic Operating Sequences .....................28
Page 9
SECTION 1.1
GENERATOR IDENTIFICATION
INTRODUCTION
This Diagnostic Repair Manual has been prepared especially for the purpose of familiarizing service per­sonnel with the testing, troubleshooting and repair of air-cooled, prepackaged automatic standby genera­tors. Every effort has been expended to ensure that information and instructions in the manual are both accurate and current. However, Generac reserves the right to change, alter or otherwise improve the product at any time without prior notification.
The manual has been divided into seven PARTS. Each PART has been divided into SECTIONS. Each SECTION consists of two or more SUBSECTIONS.
It is not our intent to provide detailed disassembly and reassemble instructions in this manual. It is our intent to (a) provide the service technician with an under standing of how the various assemblies and systems work, (b) assist the technician in finding the cause of malfunctions, and (c) effect the expeditious repair of the equipment.
ITEM NUMBER: Many home standby generators are manufactured
to the unique specifications of the buyer. The Model Number identifies the specific generator set and its unique design specifications.
PART 1
Item #
Serial
Volts
Amps
Watts
-
1 PH, 60 HZ, RPM 3600
MAX OPERATING AMBIENT
FOR STANDBY SERVICE
0055555
1234567
120/240 AC
108.3/108.3
13000
CLASS F INSULATION
TEMP - 120F/49C
GENERAL INFORMATION
NEUTRAL FLOATING
MAX LOAD UNBALANCED - 50%
GENERAC POWER SYSTEMS
WAUKESHA, WI MADE IN U.S.A.
SERIAL NUMBER: Used for warranty tracking purposes.
Figure 1. A Typical Data Plate
Page 10
GENERAL INFORMATION
PART 1
SECTION 1.2
PREPACKAGED INSTALLATION BASICS
INTRODUCTION
Information in this section is provided so that the ser­vice technician will have a basic knowledge of instal­lation requirements for prepackaged home standby systems. Problems that arise are often related to poor or unauthorized installation practices.
A typical prepackaged home standby electric system is shown in Figure 1 (next page). Installation of such a system includes the following:
• Selecting a Location
• Grounding the generator.
• Providing a fuel supply.
• Mounting the load center.
• Connecting power source and load lines.
• Connecting system control wiring.
• Post installation tests and adjustments.
SELECTING A LOCATION
Install the generator set as close as possible to the electrical load distribution panel(s) that will be pow­ered by the unit, ensuring that there is proper ventila­tion for cooling air and exhaust gases. This will reduce wiring and conduit lengths. Wiring and conduit not only add to the cost of the installation, but excessively long wiring runs can result in a voltage drop.
Control system interconnections non-prepackaged generator consist of N1 and N2, and leads 23 and
194. Control system interconnection leads must be run in a conduit that is separate from the AC power leads. Recommended wire gauge size depends on the length of the wire:
Max. Cable Length Recommended Wire Size
460 feet (140m) No. 18 AWG.
461 to 730 feet (223m) No. 16 AWG.
731 to 1,160 feet (354m) No. 14 AWG.
1,161 to 1850 feet (565m) No. 12 AWG.
GROUNDING THE GENERATOR
The National Electric Code requires that the frame and external electrically conductive parts of the gen­erator be property connected to an approved earth ground. Local electrical codes may also require prop­er grounding of the unit. For that purpose, a ground­ing lug is attached to the unit. Grounding may be accomplished by attaching a stranded copper wire of the proper size to the generator grounding lug and to an earth-driven copper or brass grounding-rod (elec­trode). Consult with a local electrician for grounding requirements in your area.
THE FUEL SUPPLY
Prepackaged units with air-cooled engines were oper­ated, tested and adjusted at the factory using natural gas as a fuel. These air-cooled engine units can be converted to use LP (propane) gas by making a few adjustments for best operation and power.
LP (propane) gas is usually supplied as a liquid in pressure tanks. Both the air-cooled and the liquid cooled units require a “vapor withdrawal” type of fuel supply system when LP (propane) gas is used. The vapor withdrawal system utilizes the gaseous fuel vapors that form at the top of the supply tank.
The pressure at which LP gas is delivered to the generator fuel solenoid valve may vary considerably, depending on ambient temperatures. In cold weather, supply pressures may drop to “zero”. In warm weath er, extremely high gas pressures may be encountered. A primary regulator is required to maintain correct gas supply pressures.
Current recommended gaseous fuel pressure at the inlet side of the generator fuel solenoid valve is as follows:
LP NG
Minimum water column 10 inches 5 inches
Maximum water column 12 inches 7 inches
A primary regulator is required to ensure that proper fuel supply pressures are maintained.
DANGER: LP AND NATURAL GAS ARE BOTH
Use of a flexible length of hose between the genera­tor fuel line connection and rigid fuel lines is required. This will help prevent line breakage that might be caused by vibration or if the generator shifts or settles. The flexible fuel line must be approved for use with gaseous fuels.
Flexible fuel line should be kept as straight as possi ble between connections. The bend radius for flexible fuel line is nine (9) inches. Exceeding the bend radius can cause the fittings to crack.
HIGHLY EXPLOSIVE. GASEOUS FUEL LINES MUST BE PROPERLY PURGED AND TESTED FOR LEAKS BEFORE THIS EQUIPMENT IS PLACED INTO SERVICE AND PERIODICALLY THEREAFTER. PROCEDURES USED IN GASEOUS FUEL LEAKAGETESTS MUST COMPLY STRICTLY WITH APPLICABLE FUEL GAS CODES. DO NOT USE FLAME OR ANY SOURCE OF HEAT TO TEST FOR GAS LEAKS. NO GAS LEAKAGE IS PERMITTED. LP GAS IS HEAVIER THAN AIR AND TENDS TO SETTLE IN LOW AREAS. NATURAL GAS IS LIGHTER THAN AIR AND TENDS TO SETTLE IN HIGH PLACES. EVEN THE SLIGHTEST SPARK CAN IGNITE THESE FUELS AND CAUSE AN EXPLOSION.
THE TRANSFER SWITCH / LOAD CENTER
A transfer switch is required by electrical code, to pre­vent electrical feedback between the utility and stand­by power sources, and to transfer electrical loads from one power supply to another safely.
PREPACKAGED TRANSFER SWITCHES: Instructions and information on prepackaged transfer
switches may be found in Part 3 of this manual.
Page 11
-
-
SECTION 1.2
PREPACKAGED INSTALLATION BASICS
BAR
NEUTRAL
100A OR 200A
HOUSE MAIN
SERVICE
GROUND
PANEL BOARD
TRANSFER SWITCH)
GENERAC UL LISTED
(8, 10, 12 OR 16 CIRCUIT
PART 1
CONNECTION OF GENERATOR
TO EXTERNAL CONNECTION PANEL
GENERAL INFORMATION
TO HOUSE BRANCH
CIRCUITS SPLICED
USING WIRE NUTS
GROUND
CIRCUITS
EMERGENCY
STUD
NEUTRAL
40A OR 70A 2-POLE
CIRCUIT BREAKER
194N1 N2 23
2 POLE
EARTH
GENERATOR OUTPUT CIRCUIT BREAKER
SPIKE
CONNECTION BOX
4 PIN
EXTERNAL CUSTOMER
CONNECTOR
Page 12
Figure 1. Typical Prepackaged Installation
GENERATOR GROUND
(LOCATED ON THE REAR OF UNIT)
GENERAL INFORMATION
PART 1
SECTION 1.2
PREPACKAGED INSTALLATION BASICS
POWER SOURCE AND LOAD LINES
The utility power supply lines, the standby (genera­tor) supply lines, and electrical load lines must all be connected to the proper terminal lugs in the transfer switch. The following rules apply: In 1-phase systems with a 2-pole transfer switch, connect the two utility source hot lines to Transfer Switch Terminal Lugs N1 and N2. Connect the standby source hot lines (E1, E2) to Transfer Switch Terminal Lugs E1 and E2. Connect the load lines from Transfer Switch Terminal Lugs T1 and T2 to the electrical load circuit. Connect UTILITY, STANDBY and LOAD neutral lines to the neutral block in the transfer switch.
SYSTEM CONTROL INTERCONNECTIONS
Prepackaged home standby generators are equipped with a terminal board identified with the following ter­minals: (a) UTILITY 1, (b) UTILITY 2, (c) 23, and (d)
194. Prepackaged load centers house an identically marked terminal board. When these four terminals are properly interconnected, dropout of utility source voltage below a preset value will result in automatic generator startup and transfer of electrical loads to the “Standby” source. On restoration of utility source voltage above a preset value will result in retransfer back to that source and generator shutdown.
5-7" WC REGULATOR TO HOUSEHOLD
GAS METER CAPABLE
OF PROVIDING FUEL
SAFETY
SHUT OFF
VALV E
0000001
Figure 2. Proper Fuel Installation
FLOW OF:
119,000 (6/7KW) 156,000 (9/10KW) 220,000 (13kW) 245,000 (15/16KW)
+HOUSEHOLD APPLIANCES
(BASED ON 1000 BTU/CU FT)
BTU/HOUR
}
GAS MAIN
2-5 PSI
Page 13
SECTION 1.3
PREPARATION BEFORE USE
PART 1
GENERAL INFORMATION
GENERAL
The installer must ensure that the home standby gen­erator has been properly installed. The system must be inspected carefully following installation. All appli­cable codes, standards and regulations pertaining to such installations must be strictly complied with. In addition, regulations established by the Occupational Safety and Health Administration (OSHA) must be complied with.
Prior to initial startup of the unit, the installer must ensure that the engine-generator has been properly prepared for use. This includes the following:
• An adequate supply of the correct fuel must be available for generator operation.
• The engine must be properly serviced with the rec ommended oil.
FUEL REQUIREMENTS
With LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed above the liquid fuel in the storage tank.
The engine has been fitted with a fuel carburetion system that meets the specifications of the 1997 California Air Resources Board for tamper-proof dual fuel systems. The unit will run on natural gas or LP gas, but it has been factory set to run on natural gas. Should the primary fuel need to be changed to LP gas, the fuel system needs to be reconfigured. See the Reconfiguring the Fuel System section for instruc tions on reconfiguration of the fuel system.
Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is 5 inches to 7 inches water column (0.18 to 0.25 psi); and for liq uid propane, 10 inches to 12 inches of water column (0.36 to 0.43 psi).
NOTE: All pipe sizing, construction and layout must comply with NFPA 54 for natural gas applica tions and NFPA 58 for liquid propane applications. Once the generator is installed, verify that the fuel pressure NEVER drops below four (4) inches water column for natural gas or 10 inches water column for liquid propane.
Prior to installation of the generator, the installer should consult local fuel suppliers or the fire marshal to check codes and regulations for proper installation. Local codes will mandate correct routing of gaseous fuel line piping around gardens, shrubs and other landscaping to prevent any damage.
Special considerations should be given when install ing the unit where local conditions include flood­ing, tornados, hurricanes, earthquakes and unstable ground for the flexibility and strength of piping and their connections.
Use an approved pipe sealant or joint compound on all threaded fitting.
All installed gaseous fuel piping must be purged and leak tested prior to initial start-up in accordance with local codes, standards and regulations.
FUEL CONSUMPTION
The fuel consumption rates are listed in the SPECIFICATIONS section at the front of this manual.
BTU FLOW REQUIREMENTS - NATURAL GAS: BTU flow required for each unit based on 1000 BTU
per cubic foot. 6/7 kW — 119,000 BTU/Hour
9/10 kW — 156,000 BTU/Hour
-
13 kW — 220,000 BTU/Hour 15/16 kW — 245,000 BTU/Hour
DANGER
Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even
the slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is per­mitted. Natural gas, which is lighter than air, tends to collect in high areas. LP gas is heavi-
-
-
-
-
er than air and tends to settle in low areas.
NOTE: A minimum of one approved manual shut­off valve must be installed in the gaseous fuel supply line. The valve must be easily accessible. Local codes determine the proper location.
RECONFIGURING THE FUEL SYSTEM
7 KW, 410CC ENGINE: To reconfigure the fuel system from NG to LP, follow
these steps (Figure 1):
NOTE: The primary regulator for the propane sup ply is NOT INCLUDED with the generator. A fuel pressure of 10 to 12 inches of water column (0.36 to 0.43 psi) to the fuel inlet of the generator must be supplied.
1. Turn off the main gas supply (if connected).
2. Open the roof and remove the door.
3. Remove the battery (if installed).
4. Disconnect Wire 0 and Wire 14 from the gas solenoid on top of the demand regulator.
5. Remove the carburetor fuel hose from the outlet port of the demand regulator.
6. Remove the demand regulator by removing the fastener that retains the regulator mounting bracket.
-
Page 14
GENERAL INFORMATION
FUEL SELECTION LEVER -
“IN” POSITION FOR NATURAL GAS
FUEL SELECTION LEVER -
“OUT” POSITION FOR LIQUID PROPANE (VAPOR) FUEL
PART 1
SECTION 1.3
PREPARATION BEFORE USE
7. Remove the square headed steel pipe plug from out­let port #1 and the brass hose barb fitting from outlet port #2.
8. Refit the brass hose barb fitting to outlet port #1 and the square headed steel pipe plug to outlet port #2.
PIPE
HOSE & PLUG SWITCHED SIDES
LP FUEL SYSTEM
PRESSURE TAP
FUEL HOSE
BRASS HOSE FITTING
OUTLET PORT
FUEL JET
FUEL HOSE
BRASS HOSE
FITTING
ADJUSTMENT
SCREW
PLUG
NG FUEL SYSTEM
12.Check for gas leakage at the pipe plug, hose connection and fittings.
10, 13 AND 16 KW, V-TWIN ENGINES: To reconfigure the fuel system from NG to LP, follow
these steps:
NOTE: The primary regulator for the propane sup ply is NOT INCLUDED with the generator. A fuel pressure of 10 to 12 inches of water column (0.36 to 0.43 psi) to the fuel inlet of the generator must be supplied.
-
3/4” HOLE
NOTE: Use an approved pipe sealant or joint com pound on all threaded fittings to reduce the pos­sibility of leakage.
9. Reverse procedure Steps 1-6 to reinstall demand regulator.
10.Take the plastic plug supplied in the poly-bag with the generator and press it into the 3/4” hole on the bottom of the air cleaner base (Figure 2).
11.Reverse the procedure to convert back to natural gas.
Figure 1. Demand Regulator
Figure 2. Demand Regulator
AIR CLEANER
Figure 3. 10 kW, GT-530 (Inlet Hose Slid Back)
-
Figure 4. 10 kW, GT-530 (Inlet Hose Slid Back)
1. Open the roof.
2. For 10 kW units: Loosen clamp and slide back the
air inlet hose.
• Slide fuel selector on carburetor out towards the back of the enclosure (Figures 3 and 4).
• Return the inlet hose and tighten clamp securely. For 13 and 16 kW units: remove the air cleaner
cover.
Page 15
SECTION 1.3
PREPARATION BEFORE USE
PART 1
GENERAL INFORMATION
• Slide the selector lever out towards the back of the enclosure (Figures 5 and 6).
• Return the air cleaner cover and tighten the two thumb screws.
3. Close the roof.
4. Reverse the procedure to convert back to natural gas.
FUEL SELECTION LEVER -
“IN” POSITION FOR NATURAL GAS
Figure 5. 13/16 kW, GT-990 (Airbox Cover Removed)
ENGINE OIL RECOMMENDATIONS
The primary recommended oil for units with air­cooled, single cylinder or V-Twin engines is synthetic oil. Synthetic oil provides easier starts in cold weather and maximum engine protection in hot weather. Use high quality detergent oil that meets or exceeds API (American Petroleum Institute) Service class SG, SH, or SJ requirements for gasoline engines. The follow­ing chart lists recommended viscosity ranges for the lowest anticipated ambient temperatures.
Engine crankcase oil capacities for the engines cov ered in this manual can be found in the specifications section at the beginning of the book.
Lowest Anticipated Ambient Temperature
Above 60° F (16° C) Use SAE 30 oil
20° to 59° F (-7° to 15° C) Use SAE 10W-30 oil
Below 20° F (-7° C) SAE 5W-20/5W-30
For all seasons Use SAE 5W-30 Synthetic oil
Oil Grade (Recommended)
-
FUEL SELECTION LEVER -
“OUT” POSITION FOR LIQUID PROPANE (VAPOR) FUEL
Figure 6. 13/16 kW, GT-990 (Airbox Cover Removed)
Page 16
GENERAL INFORMATION
PART 1
SECTION 1.4
TESTING, CLEANING AND DRYING
METERS
Devices used to measure electrical properties are called meters. Meters are available that allow one to measure (a) AC voltage, (b) DC voltage, (c) AC frequency, and (d) resistance In ohms. The following apply:
• To measure AC voltage, use an AC voltmeter.
• To measure DC voltage, use a DC voltmeter.
• Use a frequency meter to measure AC frequency In “Hertz” or “cycles per second”.
• Use an ohmmeter to read circuit resistance, in “ohms”.
THE VOM
A meter that will permit both voltage and resistance to be read is the “volt-ohm-milliammeter” or “VOM”.
Some VOMs are of the “analog” type (not shown). These meters display the value being measured by physically deflecting a needle across a graduated scale. The scale used must be Interpreted by the user.
“Digital” VOM's (Figure 1) are also available and are generally very accurate. Digital meters display the measured values directly by converting the values to numbers.
NOTE: Standard AC voltmeters react to the AVERAGE value of alternating current. When working with AC, the effective value is used. For that reason a different scale is used on an AC voltmeter. The scale is marked with the effective or “rms” value even though the meter actually reacts to the average value. That is why the AC voltmeter will give an Incorrect reading if used to measure direct current (DC).
MEASURING AC VOLTAGE
An accurate AC voltmeter or a VOM may be used to read the generator's AC output voltage. The following apply:
1. Always read the generator's AC output voltage only at the unit's rated operating speed and AC frequency.
2. The generator's Voltage Regulator can be adjusted for correct output voltage only while the unit is operating at its correct rated speed and frequency.
3. Only an AC voltmeter may be used to measure AC voltage. DO NOT USE A DC VOLTMETER FOR THIS PURPOSE.
DANGER!: GENERATORS PRODUCE HIGH
AND DANGEROUS VOLTAGES. CONTACT WITH HIGH VOLTAGE TERMINALS WILL RESULT IN DANGEROUS AND POSSIBLY LETHAL ELECTRICAL SHOCK.
MEASURING DC VOLTAGE
A DC voltmeter or a VOM may be used to measure DC voltages. Always observe the following rules:
1. Always observe correct DC polarity.
a. Some VOM's may be equipped with a polar-
ity switch.
b. On meters that do not have a polarity switch,
DC polarity must be reversed by reversing the test leads.
2. Before reading a DC voltage, always set the meter to a higher voltage scale than the anticipated reading. If in doubt, start at the highest scale and adjust the scale downward until correct readings are obtained.
Figure 1. Digital VOM
3. The design of some meters is based on the “current flow” theory while others are based on the “electron flow” theory.
a. The “current flow” theory assumes that
direct current flows from the positive (+) to the negative (-).
b. The “electron flow” theory assumes that cur-
rent flows from negative (-) to positive (+).
NOTE: When testing generators, the “current flow” theory is applied. That is, current is assumed to flow from positive (+) to negative (-).
MEASURING AC FREQUENCY
The generator's AC output frequency is proportional to Rotor speed. Generators equipped with a 2-pole Rotor must operate at 3600 rpm to supply a frequency of 60 Hertz. Units with 4-pole Rotor must run at 1800 rpm to deliver 60 Hertz.
Page 17
SECTION 1.4
TESTING, CLEANING AND DRYING
PART 1
GENERAL INFORMATION
Correct engine and Rotor speed is maintained by an engine speed governor. For models rated 60 Hertz, the governor is generally set to maintain a no-load fre­quency of about 62 Hertz with a corresponding output voltage of about 124 volts AC line-to-neutral. Engine speed and frequency at no-load are set slightly high to prevent excessive rpm and frequency droop under heavy electrical loading.
MEASURING CURRENT
CLAMP-ON: To read the current flow, in AMPERES, a clamp-on
ammeter may be used. This type of meter indicates current flow through a conductor by measuring the strength of the magnetic field around that conductor. The meter consists essentially of a current trans­former with a split core and a rectifier type instrument connected to the secondary. The primary of the cur­rent transformer is the conductor through which the current to be measured flows. The split core allows the Instrument to be clamped around the conductor without disconnecting it.
Current flowing through a conductor may be mea sured safely and easily. A line-splitter can be used to measure current in a cord without separating the conductors.
NOTE: If the physical size of the conductor or ammeter capacity does not permit all lines to be measured simultaneously, measure current flow in each individual line. Then, add the Individual readings.
IN-LINE: Alternatively, to read the current flow in AMPERES,
an in-line ammeter may be used. Most Digital Volt Ohm Meters (VOM) will have the capability to mea­sure amperes.
This usually requires the positive meter test lead to be connected to the correct amperes plug, and the meter to be set to the amperes position. Once the meter is properly set up to measure amperes the circuit being measured must be physically broken. The meter will be in-line or in series with the component being mea sured.
In Figure 4 the control wire to a relay has been removed. The meter is used to connect and supply voltage to the relay to energize it and measure the amperes going to it.
-
1.00 A
-
Figure 2. Clamp-On Ammeter
BATTERY
+-
Figure 4. A VOM as an In-line meter
RELAY
MEASURING RESISTANCE
The volt-ohm-milliammeter may be used to measure the resistance in a circuit. Resistance values can be very valuable when testing coils or windings, such as the Stator and Rotor windings.
When testing Stator windings, keep in mind that the resistance of these windings is very low. Some meters are not capable of reading such a low resistance and will simply read CONTINUITY.
If proper procedures are used, the following condi tions can be detected using a VOM:
• A “short-to-ground” condition in any Stator or Rotor winding.
• Shorting together of any two parallel Stator wind ings.
• Shorting together of any two isolated Stator wind ings.
• An open condition in any Stator or Rotor winding.
-
-
-
Figure 3. A Line-Splitter
Page 18
GENERAL INFORMATION
PART 1
SECTION 1.4
TESTING, CLEANING AND DRYING
Component testing may require a specific resis­tance value or a test for INFINITY or CONTINUITY. Infinity is an OPEN condition between two electrical points, which would read as no resistance on a VOM. Continuity is a closed condition between two electrical points, which would be indicated as very low resis­tance or “ZERO” on a VOM.
ELECTRICAL UNITS
AMPERE: The rate of electron flow in a circuit is represented
by the AMPERE. The ampere is the number of elec­trons flowing past a given point at a given time. One AMPERE is equal to just slightly more than six thou­sand million billion electrons per second.
With alternating current (AC), the electrons flow first in one direction, then reverse and move in the oppo site direction. They will repeat this cycle at regular intervals. A wave diagram, called a “sine wave” shows that current goes from zero to maximum positive value, then reverses and goes from zero to maximum negative value. Two reversals of current flow is called a cycle. The number of cycles per second is called frequency and is usually stated in “Hertz”.
VOLT: The VOLT is the unit used to measure electrical
PRESSURE, or the difference in electrical potential that causes electrons to flow. Very few electrons will flow when voltage is weak. More electrons will flow as voltage becomes stronger. VOLTAGE may be consid­ered to be a state of unbalance and current flow as an attempt to regain balance. One volt is the amount of EMF that will cause a current of 1 ampere to flow through 1 ohm of resistance.
OHM: The OHM is the unit of RESISTANCE. In every circuit
there is a natural resistance or opposition to the flow of electrons. When an EMF is applied to a complete circuit, the electrons are forced to flow in a single direction rather than their free or orbiting pattern. The resistance of a conductor depends on (a) its physical makeup, (b) its cross-sectional area, (c) its length, and (d) its temperature. As the conductor's tempera­ture increases, its resistance increases in direct pro­portion. One (1) ohm of resistance will permit one (1) ampere of current to flow when one (1) volt of electro­motive force (EMF) is applied.
OHM'S LAW
A definite and exact relationship exists between VOLTS, OHMS and AMPERES. The value of one can be calculated when the value of the other two are
-
known. Ohm's Law states that in any circuit the current will increase when voltage increases but resistance remains the same, and current will decrease when resistance Increases and voltage remains the same.
VOLTS
(E)
AMPS
(I)
OHMS
(R)
Conductor of a Circuit
OHM - Unit measuring resistance
-
AMPERE - Unit measuring rate of
Figure 5. Electrical Units
current flow (number of electrons past a given point)
VOLT - Unit measuring force or
difference in potential causing current flow
or opposition to flow
+
Figure 6. Ohm's Law
If AMPERES is unknown while VOLTS and OHMS are known, use the following formula:
=
AMPERES
VOLTS
OHMS
VOLTS
Page 19
AMPERES =
If VOLTS is unknown while AMPERES and OHMS are known, use the following formula:
VOLTS = AMPERES x OHMS
If OHMS is unknown but VOLTS and AMPERES are known, use the following:
OHMS
SECTION 1.4
TESTING, CLEANING AND DRYING
PART 1
GENERAL INFORMATION
VISUAL INSPECTION
When it becomes necessary to test or troubleshoot a generator, it is a good practice to complete a thorough visual inspection. Remove the access covers and look closely for any obvious problems. Look for the follow­ing:
• Burned or broken wires, broken wire connectors,
MINIMUM INSULATION RESISTANCE = (in “Megohms”)
damaged mounting brackets, etc.
• Loose or frayed wiring insulation, loose or dirty con nections.
• Check that all wiring is well clear of rotating parts.
• Verify that the Generator properly connected for the correct rated voltage. This is especially important on new installations. See Section 1.2, “AC Connection Systems”.
• Look for foreign objects, loose nuts, bolts and other fasteners.
• Clean the area around the Generator. Clear away paper, leaves, snow, and other objects that might blow against the generator and obstruct its air openings.
GENERATOR RATED VOLTS
__________________________
1000
+1
INSULATION RESISTANCE
Use a megger power setting of 500 volts. Connect one megger test lead to the junction of all stator leads, the other test lead to frame ground on the sta­tor can. Read the number of megohms on the meter.
The MINIMUM acceptable megger reading for stators may be calculated using the following formula:
EXAMPLE: Generator is rated at 120 volts AC. Divide “120” by “1000” to obtain “0.12”. Then add “1” to obtain “1.12” megohms. Minimum Insulation resistance for a 120 VAC stator is 1.12 megohms.
If the stator insulation resistance is less than the cal culated minimum resistance, clean and dry the stator. Then, repeat the test. If resistance is still low, replace the stator.
­Use the Megger to test for shorts between isolated windings as outlined “Stator Insulation Tests”.
Also test between parallel windings. See “Test Between Windings” on next page.
TESTING ROTOR INSULATION: Apply a voltage of 500 volts across the rotor posi-
tive (+) slip ring (nearest the rotor bearing), and a clean frame ground (i.e. the rotor shaft). DO NOT EXCEED 500 VOLTS AND DO NOT APPLY VOLTAGE LONGER THAN 1 SECOND. FOLLOW THE MEGGER MANUFACTURER’S INSTRUCTIONS CAREFULLY.
ROTOR MINIMUM INSULATION RESISTANCE:
1.5 megohms
-
The insulation resistance of stator and rotor windings is a measurement of the integrity of the insulating materials that separate the electrical windings from the generator steel core. This resistance can degrade over time or due to such contaminants as dust, dirt, oil, grease and especially moisture. In most cases, failures of stator and rotor windings is due to a break­down in the insulation. And, in many cases, a low insu­lation resistance is caused by moisture that collects while the generator is shut down. When problems are caused by moisture buildup on the windings, they can usually be corrected by drying the windings. Cleaning and drying the windings can usually eliminate dirt and moisture built up in the generator windings.
THE MEGOHMMETER
GENERAL: A megohmmeter, often called a “megger”, consists of
a meter calibrated in megohms and a power supply. Use a power supply of 500 volts when testing stators or rotors. DO NOT APPLY VOLTAGE LONGER THAN ONE (1) SECOND.
TESTING STATOR INSULATION: All parts that might be damaged by the high meg-
ger voltages must be disconnected before testing. Isolate all stator leads (Figure 8) and connect all of the stator leads together. FOLLOW THE MEGGER MANUFACTURER’S INSTRUCTIONS CAREFULLY.
Page 20
CAUTION: Before attempting to measure
HI-POT TESTER: A “Hi-Pot” tester is shown in Figure 7. The model
shown is only one of many that are commercially available. The tester shown is equipped with a voltage
Insulation resistance, first disconnect and Isolate all leads of the winding to be tested. Electronic components, diodes, surge protec­tors, relays, voltage regulators, etc., can be destroyed if subjected to high megger volt­ages.
Figure 7. One Type of Hi-Pot Tester
GENERAL INFORMATION
PART 1
SECTION 1.4
TESTING, CLEANING AND DRYING
selector switch that permits the power supply voltage to be selected. It also mounts a breakdown lamp that will illuminate to indicate an insulation breakdown dur­ing the test.
STATOR INSULATION RESISTANCE TEST
GENERAL: Units with air-cooled engines are equipped with (a)
dual stator AC power windings, (b) an excitation or DPE winding, and (c) a battery charge winding. Insulation tests of the stator consist of (a) testing all windings to ground, (b) testing between isolated wind­ings, and (c) testing between parallel windings. Figure 8 is a pictorial representation of the various stator leads on units with air-cooled engine.
TESTING ALL STATOR WINDINGS TO GROUND:
1. Disconnect stator output leads 11 and 44 from the gen­erator main line circuit breaker.
2. Remove stator output leads 22 and 33 from the neutral connection and separate the two leads.
3. Disconnect C2 Connector from the side of the control panel. The C2 Connector is the closest to the back panel (see Figure 9, Section 6.1).
c.Turn the tester switch ON and observe the
breakdown lamp on tester. DO NOT APPLY VOLTAGE LONGER THAN 1 SECOND. After one (1) second, turn the tester switch OFF.
If the breakdown lamp comes on during the one-sec ond test, the stator should be cleaned and dried. After cleaning and drying, repeat the insulation test. If, after cleaning and drying, the stator fails the second test, the stator assembly should be replaced.
6. Now proceed to the C2 Connector. Each winding will be individually tested for a short to ground. Insert a large paper clip (or similar item) into the C2 Connector at the following pin locations:
Pin
Location
1 77 Battery Charge
2 66 Battery Charge
3 22 Sense Lead Power
4 11 Sense Lead Power
5 6 Excitation
6 2 Excitation
7 0 Ground
8 4 Positive to Brush
Wire
Number
Winding
-
2
6
11P
11S
22P
22S
33
44
66
77
Figure 8. Stator Winding Leads
4. Connect the terminal ends of Wires 11, 22, 33 and 44 together. Make sure the wire ends are not touching any part of the generator frame or any terminal.
5. Connect the red test probe of the Hi-Pot tester to the joined terminal ends of stator leads 11, 22, 33 and 44. Connect the black tester lead to a clean frame ground on the stator can. With tester leads connected in this manner, proceed as follows:
a.Turn the Hi-Pot tester switch OFF. b.Plug the tester cord into a 120 volt AC wall
socket and set its voltage selector switch to “1500 volts”.
Next refer to Steps 5a through 5c of the Hi-Pot proce­dure.
Example: Insert paper clip into Pin 1, Hi-Pot from Pin 1 (Wire 77) to ground. Proceed to Pin 2, Pin 3, etc. through Pin 8.
5
6
7
8
Figure 9. C2 Connector Pin Location Numbers
(Female Side)
TEST BETWEEN WINDINGS:
1 2
3
4
1. Insert a large paper clip into Pin Location 1 (Wire 77). Connect the red tester probe to the paper clip. Connect the black tester probe to Stator Lead 11. Refer to Steps 5a through 5c of “TESTING ALL STATOR WINDINGS TO GROUND” on previous page.
2. Repeat Step 1 at Pin Location 5 (Wire 6) and Stator Lead 11.
3. Connect the red test probe to Stator Lead 33. Connect the black test probe to Stator Lead 11. Refer to Steps 5a through 5c of “TESTING ALL STATOR WINDINGS TO GROUND” on previous page.
Page 21
SECTION 1.4
TESTING, CLEANING AND DRYING
4. Insert a large paper clip into Pin Location No. 1 (Wire
77). Connect the red tester probe to the paper clip. Connect the black tester probe to Stator Lead 33. Refer to Steps 5a through 5c of “TESTING ALL STATOR WINDINGS TO GROUND” on the previous page.
5. Repeat Step 4 at Pin Location 3 (Wire 6) and Stator Lead 33.
For the following Step (7) an additional large paper clip (or similar item) will be needed:
7. Insert a large paper clip into Pin Location 1 (Wire 77). Connect the red tester probe to the paper clip. Insert the additional large paper clip into Pin Location 5 (Wire 6). Connect the black tester probe to this paper clip. Refer to Steps 5a through 5c of “TESTING ALL STATOR WINDINGS TO GROUND” on the previous page.
PART 1
POSITIVE (+) TEST LEAD
Figure 10. Testing Rotor Insulation
GENERAL INFORMATION
ROTOR INSULATION RESISTANCE TEST
Before attempting to test rotor insulation, the brush holder must be completely removed. The rotor must be completely isolated from other components before starting the test. Attach all leads of all stator windings to ground.
1. Connect the red tester lead to the positive (+) slip ring (nearest the rotor bearing).
2. Connect the black tester probe to a clean frame ground, such as a clean metal part of the rotor shaft.
3. Turn the tester switch OFF.
4. Plug the tester into a 120 volts AC wall socket and set the voltage switch to “1500 volts”.
5. Turn the tester switch “On” and make sure the pilot light has turned on.
6. Observe the breakdown lamp, then turn the tester switch OFF. DO NOT APPLY VOLTAGE LONGER THAN ONE (1) SECOND.
If the breakdown lamp came on during the one (1) second test, cleaning and drying of the rotor may be necessary. After cleaning and drying, repeat the insu­lation breakdown test. If breakdown lamp comes on during the second test, replace the rotor assembly.
CLEANING THE GENERATOR
Caked or greasy dirt may be loosened with a soft brush or a damp cloth. A vacuum system may be used to clean up loosened dirt. Dust and dirt may also be removed using dry, low-pressure air (25 psi maximum).
CAUTION: Do not use sprayed water to clean
the generator. Some of the water will be
retained on generator windings and terminals, and may cause very serious problems.
DRYING THE GENERATOR
To dry a generator, proceed as follows:
1. Open the generator main circuit breaker. NO ELECTRICAL LOADS MUST BE APPLIED TO THE GENERATOR WHILE DRYING.
2. Disconnect all Wires 4 from the voltage regulator.
3. Provide an external source to blow warm, dry air through the generator interior (around the rotor and stator wind­ings. DO NOT EXCEED 185° F. (85° C.).
4. Start the generator and let it run for 2 or 3 hours.
5. Shut the generator down and repeat the stator and rotor insulation resistance tests.
Page 22
GENERAL INFORMATION
LOW OIL SWITCH HIGH TEMP SWITCH
PART 1
SECTION 1.5
ENGINE-GENERATOR PROTECTIVE DEVICES
GENERAL
Standby electric power generators will often run unattended for long periods of time. Such operating parameters as (a) battery voltage, (b) engine oil pres­sure, (c) engine temperature, (d) engine operating speed, and (e) engine cranking and startup are not monitored by an operator during automatic operation. Because engine operation will not be monitored, the use of engine protective safety devices is required to prevent engine damage in the event of a problem.
Prepackaged generator engines mount several engine protective devices. These devices work in conjunction with a circuit board, to protect the engine against such operating faults as (a) low battery, (b) low engine oil pressure, (c) high temperature, (d) overspeed, and (e) overcrank. On occurrence of any one or more of those operating faults, circuit board action will effect an engine shutdown.
LOW BATTERY
The microprocessor will continually monitor the bat­tery voltage and turn on the Low Battery LED if the battery voltage falls below 11.0 volts for one (1) min­ute. No other action is taken on a low battery condi­tion. Low battery voltage is a non-latching alarm which will automatically clear if the battery voltage rises above 11.0 volts. Battery voltage is NOT moni­tored during the crank cycle.
OVERSPEED SHUTDOWN
During engine cranking and operation, the circuit board receives AC voltage and frequency signals from the ignition magneto, via Wire 18. Should the speed exceed approximately 72 Hz (4320 rpm), circuit board action will de-energize a “run relay” (mounted on the circuit board). The relay’s contacts will open, to termi­nate engine ignition and close a fuel shutoff solenoid. The engine will then shut down. This feature protects the engine-generator against damaging overspeeds.
NOTE: The circuit board also uses rpm sensing to terminate engine cranking.
RPM SENSOR FAILURE
During cranking, if the board does not see a valid RPM signal within three (3) seconds, it will shut down and latch out on RPM sensor loss.
During running, if the RPM signal is lost for one full second the board will shut down the engine, wait 15 seconds, then re-crank the engine.
• If an RPM signal is not detected within the first three (3) seconds of cranking, the control board will shut the engine down and latch out on RPM sensor loss.
• If the RPM signal is detected the engine will start and run normally. If the RPM signal is subsequently lost again, the control board will try one more re­crank attempt before latching out and flashing the overspeed LED.
LOW OIL PRESSURE SHUTDOWN
See Figure 1. An oil pressure switch is mounted on the engine oil filter adapter. This switch has normally closed contacts that are held open by engine oil pres­sure during cranking and startup. Should oil pressure drop below approximately 8 psi, the switch contacts will close. On closure of the switch contacts, a Wire 86 circuit from the circuit board will be connected to ground. Circuit board action will then de-energize a “run relay” (on the circuit board). The run relay’s nor­mally open contacts will then open and a 12 volts DC power supply to a Wire 14 circuit will then be terminat­ed. This will result in closure of a fuel shutoff solenoid and loss of engine ignition.
HIGH TEMPERATURE SWITCH
This switch’s contacts (Figure 1) close if the tempera­ture should exceed approximately 140° C (284° F), initiating an engine shutdown. The generator will auto­matically restart and the LED on the generator control panel will reset once the temperature has returned to a safe operating level.
Figure 1. Engine Protective Switches on an
Air-Cooled Engine
Page 23
SECTION 1.5
ENGINE-GENERATOR PROTECTIVE DEVICES
OVERCRANK SHUTDOWN
This feature prevents the generator from damaging itself when it continually attempts to start and another problem, such as no fuel supply, prevents it from start­ing. The unit will crank and rest for a preset time limit. Then, it will stop cranking, and the LED on the gen­erator control panel will light indicating an overcrank failure. The AUTO/OFF/MANUAL switch will need to be set to OFF and then back to AUTO to reset the generator control board.
NOTE: If the fault is not repaired, the overcrank feature will continue to activate.
APPROXIMATE CRANK CYCLE TIMES:
7 KW UNITS: 15 seconds ON
7 seconds OFF 7 seconds ON 7 seconds OFF 7 seconds ON 7 seconds OFF 7 seconds ON 7 seconds OFF 7 seconds ON 7 seconds OFF 7 seconds ON
If the unit fails to start, the overcrank alarm LED will be illuminated.
PART 1
GENERAL INFORMATION
10 KW, 13 KW AND 16 KW UNITS: 16 seconds ON
7 seconds OFF 16 seconds ON 7 seconds OFF 7 seconds ON 7 seconds OFF 7 seconds ON 7 seconds OFF 7 seconds ON 7 seconds OFF
If the unit fails to start, the overcrank alarm LED will be illuminated.
Page 24
GENERAL INFORMATION
PART 1
SECTION 1.6
OPERATING INSTRUCTIONS
CONTROL PANEL
GENERAL: See Figure 1 for control panel configurations.
CONTROL AND INFORMATION CENTER
SYSTEM SET
LOW BATTERY
OFF
AUTO. MAN.
SYSTEM FUSE
15A
ASSY: 0F8418/0F8419
SET
EXERCISE
TIME
Figure 1. Control Panel
AUTO-OFF-MANUAL SWITCH: Use this switch to (a) select fully automatic operation,
(b) to crank and start the engine manually, and (c) to shut the unit down or to prevent automatic startup.
1. AUTO position:
a.Select AUTO for fully automatic operation. b.When AUTO is selected, circuit board will moni-
tor utility power source voltage.
c. Should utility voltage drop below a preset level
and remain at such a low level for a preset time, circuit board action will initiate engine cranking and startup.
d.Following engine startup, circuit board action
will initiate transfer of electrical loads to the “Standby” source side.
e.On restoration of utility source voltage above
a preset level, circuit board action will initiate retransfer back to the “Utility Source” side.
f. Following retransfer, circuit board will shut the
engine down and will then continue to monitor utility source voltage.
2. OFF Position:
a.Set the switch to OFF to stop an operating
engine.
b.To prevent an automatic startup from occurring,
set the switch to OFF.
3. MANUAL Position:
a.Set switch to MANUAL to crank and start unit
manually.
b.Engine will crank cyclically and start (same as
automatic startup, but without transfer). The unit will transfer if utility voltage is not available.
DANGER: WHEN THE GENERATOR IS
INSTALLED IN CONJUNCTION WITH AN
AUTOMATIC TRANSFER SWITCH, ENGINE CRANKING AND STARTUP CAN OCCUR AT
LOW OIL
HIGH TEMP
OVER SPEED NO RPM SENSE IF FLASHING
OVER CRANK
FLASHING GREEN LED= NO UTILITY SENSE 5 FLASHING RED LEDS= EXERCISER NOT SET
ANY TIME WITHOUT WARNING (PROVIDING THE AUTO-OFF-MANUAL SWITCH IS SET TO AUTO). TO PREVENT AUTOMATIC STARTUP AND POSSIBLE INJURY THAT MIGHT BE CAUSED BY SUCH STARTUP, ALWAYS SET THE AUTO-OFF-MANUAL SWITCH TO ITS OFF POSITION BEFORE WORKING ON OR AROUND THIS EQUIPMENT.
15 AMP FUSE: This fuse protects the DC control circuit (including the
circuit board) against overload. If the fuse element has melted open due to an overload, engine cranking or running will not be possible. Should fuse replace­ment become necessary, use only an identical 15 amp replacement fuse.
THE SET EXERCISE SWITCH: This generator is equipped with an exercise timer.
Once it is set, the generator will start and exercise once every seven days, on the day of the week and at the time of day the following sequence is completed. During this exercise period, the unit runs for approxi­mately 12 minutes and then shuts down. Transfer of loads to the generator output does not occur during the exercise cycle unless utility power is lost.
A switch on the control panel (see Figure 1) per mits selection of the day and time for the system to exercise. At the chosen time, perform the following sequence to select the desired day and time of day the system will exercise. Remember seasonal time changes affect the exercise time settings.
1. Verify that the AUTO/OFF/MANUAL switch is set to
AUTO.
2. Press and hold the "Set Exercise Time" switch for sev-
eral seconds, then release. All the red LED's will flash for approximately 10 seconds and then stop.
3. Once the red LED's stop flashing, the generator will start
and run for approximately 12 minutes and then shut down. The exerciser is now set to run at this time of day each week.
Example: If the "Set Exercise Time" switch is pressed
on Saturday afternoon at 2:00 p.m., the generator will start and exercise for approximately 12 minutes every Saturday at 2:00 p.m..
NOTE: The exerciser will only work in the AUTO mode and will not work unless this procedure is performed. The exerciser will need to be reset every time the 12 volt battery is disconnected and then reconnected, and when the 15A fuse is removed.
The 16 kW unit has a low speed exercise option. Dip switch 1 on the control board is factory set to OFF. This allows the engine to run at a slower speed during weekly exercise periods for quieter operation. If this Dip switch is set to ON, the generator will exercise at it's normal speed.
-
Page 25
SECTION 1.6
OPERATING INSTRUCTIONS
PART 1
GENERAL INFORMATION
This DIP switch position is only read at board power up. If the DIP switch position is changed, power to the board must be cycled for the micro controller to recog­nize the new DIP switch position.
Low speed exercise will be handled as follows:
1. The standard start sequence will be initiated.
2. The unit will run at 2,400 RPM.
3. If utility is lost during exercise, the controller will do the following:
• Wait 10 seconds for utility to return.
• If utility returns within 10 seconds, continue to exer
cise at 2,400 RPM.
• If utility is still lost after 10 seconds, run the engine
up to 3600 RPM and transfer the load. At this time the controller will exit the exercise routine and assume full automatic operation.
PROTECTION SYSTEMS: Unlike an automobile engine, the generator may have
to run for long periods of time with no operator pres­ent to monitor engine conditions. For that reason, the engine is equipped with the following systems that protect it against potentially damaging conditions:
• Low Battery
• Low Oil Pressure Sensor
• High Temperature Sensor
• Overcrank
• Overspeed
• No RPM Sense
There are LED readouts on the control panel to notify you that one of these faults has occurred. There is also a “System Set” LED that is lit when all of the fol lowing conditions are true:
1. The AUTO-OFF-MANUAL switch is set to the AUTO position.
2. The NOT IN AUTO dip switch is set to the OFF position on the control board.
3. No alarms are present.
To select automatic operation when a prepackaged transfer switch is installed along with a prepackaged home standby generator, proceed as follows:
1. Check that the prepackaged transfer switch main con­tacts are at their UTILITY position, i.e., the load is connected to the power supply. If necessary, manu­ally actuate the switch main contacts to their UTILITY source side. See Part 5 of this manual, as appropriate, for instructions.
2. Check that utility source voltage is available to transfer
-
switch terminal lugs N1 and N2 (2-pole, 1-phase trans­fer switches).
3. Set the generator AUTO-OFF-MANUAL switch to its AUTO position.
4. Actuate the generator main line circuit breaker to its “On” or “Closed” position. With the preceding Steps 1 through 4 completed, a dropout in utility supply voltage below a preset level will result in automatic generator cranking and start-up. Following startup, the prepackaged transfer switch will be actuated to its “Standby” source side, i.e., loads powered by the standby generator.
MANUAL TRANSFER TO “STANDBY” AND
MANUAL STARTUP
To transfer electrical loads to the “Standby” (genera­tor) source and start the generator manually, proceed as follows:
1. On the generator panel, set the AUTO-OFF-MANUAL
-
switch to OFF.
2. On the generator, set the main line circuit breaker to it’s OFF or “Open” position.
3. Turn OFF the power supply to the transfer switch, using whatever means provided (such as a utility source line circuit breaker).
TO SELECT AUTOMATIC OPERATION
The following procedure applies only to those installa­tions in which the air-cooled, prepackaged automatic standby generator is installed in conjunction with a prepackaged transfer switch. Prepackaged transfer switches do not have an intelligence circuit of their own. Automatic operation on prepackaged transfer switch and generator combinations is controlled by circuit board action.
Page 26
4. Manually actuate the transfer switch main contacts to their “Standby” position, i.e., loads connected to the “Standby” power source side.
NOTE: For instructions on manual operation of prepackaged transfer switches, see Part 5.
5. On the generator panel, set the AUTO-OFF-MANUAL switch to MANUAL. The engine should crank and start.
6. Let the engine warm up and stabilize for a minute or two at no-load.
7. Set the generator main line circuit breaker to its “On” or “Closed” position. The generator now powers the electri­cal loads.
GENERAL INFORMATION
PART 1
MANUAL SHUTDOWN AND RETRANSFER
BACK TO “UTILITY”
To shut the generator down and retransfer electrical loads back to the UTILITY position, proceed as fol­lows:
1. Set the generator main line circuit breaker to its OFF or “Open” position.
2. Let the generator run at no-load for a few minutes, to cool.
3. Set the generator AUTO-OFF-MANUAL switch to OFF. Wait for the engine to come to a complete stop.
4. Turn off the utility power supply to the transfer switch using whatever means provided (such as a utility source main line circuit breaker)
5. Manually actuate the prepackaged transfer switch to its UTILITY source side, i.e., load connected to the utility source.
6. Turn on the utility power supply to the transfer switch, using whatever means provided.
SECTION 1.6
OPERATING INSTRUCTIONS
7. Set the generator AUTO-OFF-MANUAL switch to AUTO.
Page 27
SECTION 1.7
AUTOMATIC OPERATING PARAMETERS
PART 1
GENERAL INFORMATION
INTRODUCTION
When the prepackaged generator is installed in conjunction with a prepackaged transfer switch, either manual or automatic operation is possible. Manual transfer and engine startup, as well as manual shutdown and retransfer are covered in Section 1.6. Selection of fully automatic operation is also discussed in that section. This section will provide a step-by-step description of the sequence of events that will occur during automatic operation of the system.
AUTOMATIC OPERATING SEQUENCES
The generator’s control panel houses a control logic circuit board. This board constantly monitors util­ity power source voltage. Should that voltage drop below a preset level, circuit board action will signal the engine to crank and start. After the engine starts, the circuit board signals the transfer switch to activate and connect load circuits to the standby power supply (load terminal lugs T1/T2 connect to terminal lugs E1/ E2). Refer to the Electrical Data section.
The generator must run at 50 Hz or greater for the transfer output to be activated. Once activated, it will remain active even if the frequency dips below 50 Hz.
Upon restoration of utility source voltage above a preset level, generator circuit board action signals the transfer switch to transfer loads back to that power supply. After retransfer, the engine is signalled to shut down.
The actual sequence of operation is controlled by sensors and timers on a control logic circuit board, as follows:
A. Utility Voltage Dropout Sensor
• This sensor monitors utility source voltage.
• If utility source voltage drops below about 65 percent of the nominal supply voltage, the sensor energizes a 10 second timer.
• Once the timer has expired, the engine will crank and start if utility is still low.
B. Engine Warm-up Time Delay
• This mechanism lets the engine warm up for about five (5) seconds before the load is transferred to the standby source.
C. Standby Voltage Sensor
• This sensor monitors generator AC output voltage. When the voltage has reached 50 percent of the nominal rated voltage, transfer to standby can occur.
D. Utility Voltage Pickup Sensor
• This sensor monitors utility power supply voltage. When that voltage is restored above 75 percent of the nominal source voltage, a retransfer time delay starts timing.
E. Retransfer Time Delay
• This timer runs for about 15 seconds.
• At end of a 15-second delay, circuit board action de­energizes transfer relay in the transfer switch if utility is still present.
• Retransfer to utility power source then occurs.
F. Engine Cool-down Timer
Page 28
• When the load is transferred back to utility power source, the engine cool-down timer starts timing.
• The timer will run for about one minute, and the gen erator will then shut down.
-
Loading...
+ 121 hidden pages