Guardian 4721, 4722, 4723, 4724, 4725 Repair Manual

...
Models: 4721, 4722, 4723, 4724, 4725, 4726
1.5L HOME STANDBY GENERATORS
www.guardiangenerators.com
DIAGNOSTIC REPAIR MANUAL
Page ii
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become famil­iar with the Owner’s Manual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
Generac cannot anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique that Generac does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique utilized does not render the generator unsafe.
Despite the safe design of this generator, operating this equipment imprudently, neglecting its main­tenance or being careless can cause possible injury or death. Permit only responsible and capable persons to install, operate or maintain this equipment.
Potentially lethal voltages are generated by these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near running genera­tors.
!
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe opera­tion be copied and posted in potential hazard areas. Safety should be stressed to all opera­tors and potential operators of this equipment.
!
Important Safety Notice
Proper service and repair is important to the safe, economical and reliable operation of all standby electric power systems. The troubleshooting, testing and servicing procedures recom­mended by Generac and described in this manual are effective methods of performing such operations. Some of these operations or procedures may require the use of specialized equip­ment. Such equipment should be used when and as recommended.
It is important to note that this manual contains various DANGER, CAUTION, and NOTE blocks. These should be read carefully in order to minimize the risk of personal injury or to prevent improper methods or practices from being used. Use of improper or unauthorized practices may damage equipment or render it unsafe. The DANGER, CAUTION and NOTE blocks are not exhaustive. Generac could not possibly know, evaluate and advise the service trade of all con­ceivable ways in which operations described in this manual might be accomplished or of the possible hazardous consequences of each way. Consequently, Generac has not taken any such broad evaluation. Accordingly, anyone who uses any troubleshooting, testing or service proce­dure that is not recommended by Generac must first satisfy himself that neither his safety nor the equipment's safety will be jeopardized by the procedure or the method he selects.
!
DANGER
Page iii
GENERAL HAZARDS
• For safety reasons, Generac recommends that this equipment be installed, serviced and repaired by an authorized service dealer or other competent, qualified electrician or installation technician who is familiar with applicable codes, standards and regulations. The operator also must comply with all such codes, standards and regulations.
• Installation, operation, servicing and repair of this (and related) equipment must always comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed, operated and serviced in accor­dance with the manufacturer’s instructions and recommendations. Following installation, do nothing that might render the unit unsafe or in noncompliance with the aforementioned codes, standards, laws and regulations.
• The engine exhaust fumes contain carbon monoxide gas, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. For that reason, ade­quate ventilation must be provided. Exhaust gases must be piped safely away from any building or enclosure that houses the generator to an area where people, animals, etc., will not be harmed. This exhaust system must be installed properly, in strict compliance with applicable codes and standards.
• Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and ventilating air is critical to prevent buildup of explosive gases and to ensure correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator.
• Keep the area around the generator clean and uncluttered. Remove any materials that could become hazardous.
• When working on this equipment, remain alert at all times. Never work on the equipment when physi­cally or mentally fatigued.
• Inspect the generator regularly, and promptly repair or replace all worn, damaged or defective parts using only factory-approved parts.
• Before performing any maintenance on the generator, disconnect its battery cables to prevent acciden­tal start-up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
ELE
CTRICAL HAZARDS
• All generators covered by this manual produce dangerous electrical voltages and can cause fatal electri­cal shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as well as the standby generator. Avoid contact with bare wires, terminals, connections, etc., on the generator as well as the transfer switch, if applicable. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• If people must stand on metal or concrete while installing, operating, servicing, adjusting or repairing this equipment, place insulative mats over a dry wooden platform. Work on the equipment only while standing on such insulative mats.
!!
Page iv
• The National Electrical Code (NEC), Article 250 requires the frame and external electrically conductive parts of the generator to be connected to an approved earth ground and/or grounding rods. This grounding will help prevent dangerous electrical shock that might be caused by a ground fault condi­tion in the generator set or by static electricity. Never disconnect the ground wire.
• Wire gauge sizes of electrical wiring, cables and cord sets must be adequate to handle the maximum electrical current (ampacity) to which they will be subjected.
• Before installing or servicing this (and related) equipment, make sure that all power voltage supplies are positively turned off at their source. Failure to do so will result in hazardous and possibly fatal electrical shock.
• Connecting this unit to an electrical system normally supplied by an electric utility shall be by means of a transfer switch so as to isolate the generator electric system from the electric utility distribution sys­tem when the generator is operating. Failure to isolate the two electric system power sources from each other by such means will result in damage to the generator and may also result in injury or death to utility power workers due to backfeed of electrical energy.
• Generators installed with an automatic transfer switch will crank and start automatically when NOR­MAL (UTILITY) source voltage is removed or is below an acceptable preset level. To prevent such auto­matic start-up and possible injury to personnel, disable the generator’s automatic start circuit (battery cables, etc.) before working on or around the unit. Then, place a “Do Not Operate” tag on the generator control panel and on the transfer switch.
• In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in elec­tric shock, or may get caught in moving components causing injury.
FIRE HAZARDS
• Keep a fire extinguisher near the generator at all times. Do NOT use any carbon tetra-chloride type extinguisher. Its fumes are toxic, and the liquid can deteriorate wiring insulation. Keep the extinguisher properly charged and be familiar with its use. If there are any questions pertaining to fire extinguish­ers, consult the local fire department.
EXPLOSION HAZARDS
• Properly ventilate any room or building housing the generator to prevent build-up of explosive gas.
• Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no com­bustible materials are left in the generator compartment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
• Generac generator sets may operate using one of several types of fuels. All fuel types are potentially FLAMMABLE and/or EXPLOSIVE and should be handled with care. Comply with all laws regulating the storage and handling of fuels. Inspect the unit’s fuel system frequently and correct any leaks imme­diately. Fuel supply lines must be properly installed, purged and leak tested according to applicable fuel-gas codes before placing this equipment into service.
• Diesel fuels are highly FLAMMABLE. Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Natural gas is lighter than air, and LP gas is heavier than air; install leak detectors accordingly.
Page 1
PART TITLE PAGE
SPECIFICATIONS 2
1 General Information 3
2 Prepackaged Liquid Cooled AC Generators 19 3 V-Type Prepackaged Transfer Switches 39
4 DC Control- Units with Liquid-Cooled Engine 57
5 Operational Tests and Adjustments 95
6 Electrical Data 101
TABLE OF CONTENTS
1.5 LITER PREPACKAGED HOME STANDBY
GENERATORS
DIAGNOSTIC
REPAIR MANUAL
Page 2
GENERATOR SPECIFICATIONS
Phase ............................................................ Single
Rated Max. Cont. AC Power Output (kW) ......... 15*
Rated Voltage (volts) ................................. 120/240
No. of Rotor Poles - 15 kW ................................... 2
No. of Rotor Poles - 20/25 kW .............................. 4
Driven Speed of Rotor - 15 kW ....................... 1800
Driven Speed of Rotor - 20/25 kW .................. 3600
Rotor Excitation System .. Direct excited brush type
Rotor/Stator Insulation ................................ Class F
* Rated power of generator is subject to and limited
by such factors as ambient temperature, altitude, engine condition, and other factors. Engine power will decrease about 3% for each 1000 feet above 600 feet and will decrease an additional 1.65% for each 10°F above 77°F. Maximum output power of the generator is limited by maximum engine power.
ENGINE SPECIFICATIONS
Make .........................................................Mitsubishi
Displacement.............................................92 inches
(1.5 liters)
Cylinder Arrangement .................................4, in-line
Valve Arrangement...........................Overhead Cam
Firing Order ...................................................1-3-4-2
Number of Main Bearings .......................................5
Compression Ratio ..........................................9 to 1
No. of Teeth on Flywheel....................................104
Ignition Timing
at 1800 rpm..................................35 degrees BTDC
Spark Plug Gap..............................0.020-0.025 inch
Recommended Spark Plugs
Champion .................................................RN11YC4
Oil Pressure ...............................................30-50 psi
Crankcase Oil Capacity ...3.0 U.S. quarts (2.8 liters)
Recommended Engine Oil ...................SAE 15W-40
Type of Cooling SystemPressurized, closed recovery
Cooling Fan ..........................................Pusher Type
Cooling System Capacity ..2 U.S. gallons (7.6 liters)
Recommended Coolant........Use a 50-50 mixture of
ethylene glycol base.
FUEL CONSUMPTION
25 kW Models
Using Natural Gas .................... 441 cu. ft. per hour
Using LP Gas.......... 175 cubic ft. (4.8 gal.) per hour
20 kW Models
Using Natural Gas .................... 359 cu. ft. per hour
Using LP Gas ......... 143 cubic ft. (4.0 gal.) per hour
15 kW Models
Using Natural Gas .................... 277 cu. ft. per hour
Using LP Gas .......... 110 cubic ft.(3.1 gal.) per hour
NOTE: Fuel consumption is given at rated maxi­mum continuous power output when using natural gas rated at 1000 Btu per cubic foot and LP gas rated 2520 Btu per cubic foot. Actual fuel con-
sumption obtained may vary depending on such variables as applied load, ambient temperature, engine conditions and other environmental factors.
Fuel pressure for a natural gas set up should be five inches to 14 inches of water column (0.18 to 0.5 psi) at all load ranges.
Fuel pressure for an LP vapor set up should be 11 inches to 14 inches of water column (0.4 to 0.5 psi) at all load ranges.
ENGINE OIL RECOMMENDATIONS
The unit has been filled with 15W-40 engine oil at the factory. Use a high-quality detergent oil classified “For Service SJ or latest available.” Detergent oils keep
the engine cleaner and reduce carbon deposits. Use oil having the following SAE viscosity rating, based on the ambient temperature range anticipated before the next oil change:
NOTE: Synthetic oil is highly recommended when the generator will be operating in ambient temper­atures which regularly exceed 90° F and/or fall below 30° F.
ANY ATTEMPT TO CRANK OR START THE ENGINE BEFORE IT HAS BEEN PROPERLY SERVICED WITH THE RECOMMENDED OIL MAY RESULT IN AN ENGINE FAILURE.
COOLANT RECOMMENDATIONS
Use a mixture of half low silicate ethylene glycol base anti-freeze and deionized water. Cooling system capacity is about 8 U.S. quarts (7.6 liters). Use only deionized water and only low silicate anti-freeze. If desired, add a high quality rust inhibitor to the recom­mended coolant mixture. When adding coolant, always add the recommended 50-50 mixture.
DO NOT USE ANY CHROMATE BASE RUST INHIBITOR WITH ETHYLENE GLYCOL BASE ANTI-FREEZE OR CHROMIUMHYDROXIDE (“GREEN SLIME”) FORMS AND WILL CAUSE OVERHEATING. ENGINES THAT HAVE BEEN OPERATED WITH A CHROMATE BASE RUST INHIBITOR MUST BE CHEMICALLY CLEANED BEFORE ADDING ETHYLENE GLYCOL BASE ANTI-FREEZE. USING ANY HIGH SILICATE ANTI-FREEZE BOOSTERS OR ADDITIVES WILL ALSO CAUSE OVERHEATING. IT IS ALSO REC­OMMENDED THAT ANY SOLUBLE OIL INHIBITOR IS NOT USED FOR THIS EQUIPMENT.
!
!
SPECIFICATIONS
Temperature Oil Grade (Recommended)
Above 80° F (27° C) SAE 30W or 15W-40
32° to 80° F (-1° to 27° C) SAE 20W-20 or 15W-40
Below 32° F (0° C) SAE 10W or 15W-40
Page 3
PART TITLE PAGE
1.1 Generator Identification 4
1.2 Prepackaged Installation Basics 6
1.3 Preparation Before Use 9
1.4 Testing, Cleaning and Drying 10
1.5 Engine-Generator Protective Devices 13
1.6 Operating Instructions 15
1.7 Automatic Operating Parameters 17
TABLE OF CONTENTS
1.5 LITER PREPACKAGED HOME STANDBY
GENERATORS
PART 1
GENERAL
INFORMATION
PART 1
GENERAL INFORMATION
SECTION 1.1
GENERATOR IDENTIFICATION
Page 4
STARTER
DATA PLATE
FUSE
FAULT
15-A
INDICATOR
HOURMETER
AGC
AUTO
SET EXERCISE TIME
OFF
ON
MANUAL
CONTROL PANEL
HOURMETER
15 AMP FUSE
FAULT INDICATOR
SET EXERCISE SWITCH
AUTO-OFF-MANUAL SWITCH
ALTERNATOR
DISTRIBUTOR
CIRCUIT BREAKER
CARBURETOR
MUFFLER
RADIATOR
ENGINE
FUEL REGULATOR
BATTERY
PART 1
GENERAL INFORMATION
SECTION 1.1
GENERATOR IDENTIFICATION
INTRODUCTION
This Diagnostic Repair Manual has been prepared especially for the purpose of familiarizing service per­sonnel with the testing, troubleshooting and repair of prepackaged home standby generator systems. Every effort has been expended to ensure that infor­mation and instructions in the manual are both accu­rate and current. However, the manufacturer reserves the right to change, after or otherwise improve the product at any time without prior notification.
The manual has been divided into several PARTS. Each PART has been divided into SECTIONS. Each SECTION consists of two or more SUBSECTIONS.
It is not the manufacturers intent to provide detailed disassembly and reassembly instructions in this man­ual. It is the manufacturers intent to (a) provide the service technician with an understanding of how the various assemblies and systems work, (b) assist the technician in finding the cause of malfunctions, and (c) effect the expeditious repair of the equipment.
UNITS WITH LIQUID COOLED ENGINE
A typical prepackaged generator with liquid cooled engine is shown on Page 4 at front of this manual.
A DATA PLATE, affixed to the unit, contains impor­tant information pertaining to the unit, including its Model Number, Serial Number, kW rating, rated rpm, rated voltage, etc. The information from this data plate may be required when requesting information, ordering parts, etc.
Figure 1. A Typical Data Plate
Page 5
INTRODUCTION
Information in this section is provided so that the ser­vice technician will have a basic knowledge of instal­lation requirements for prepackaged home standby systems. Problems that arise are often related to poor or unauthorized installation practices.
A typical prepackaged home standby electric system is shown in Figure 1, below. Installation of such a sys­tem includes the following:
• Selecting a Location
• Mounting of the generator.
• Grounding the generator.
• Providing a fuel supply.
• Mounting the transfer switch.
• Connecting power source and load lines.
• Connecting system control wiring.
• Post installation tests and adjustments.
SELECTING A LOCATION
Install the generator set as close as possible to the electrical load distribution panel(s) that will be powered by the unit, ensuring that there is proper ventilation for cooling air and exhaust gases. This will reduce wiring and conduit lengths. Wiring and conduit not only add to the cost of the installation, but excessively long wiring runs can result in a voltage drop.
MOUNTING THE GENERATOR
Mount the generator set to a concrete slab. The slab should extend past the generator and to a distance of at least twelve (12) inches on all sides. The unit can be retained to the concrete slab with masonry anchor bolts.
GROUNDING THE GENERATOR
The National Electric Code requires that the frame and external electrically conductive parts of the gen­erator be property connected to an approved earth ground. Local electrical codes may also require prop­er grounding of the unit. For that purpose, a ground­ing lug is attached to the unit. Grounding may be accomplished by attaching a stranded copper wire of the proper size to the generator’s grounding lug and to an earth-driven copper or brass grounding-rod (electrode). Consult with a local electrician for ground­ing requirements in your area.
THE FUEL SUPPLY
Units with liquid cooled engines are shipped from the factory to run on natural gas (Figure 2). Units that will use LP (propane) gas fuel (Figure 3) must be convert­ed in the field per instructions located in the Installation Manual.
LP (propane) gas is usually supplied as a liquid in pressure tanks. Liquid cooled units require a "vapor withdrawal" type of fuel supply system when LP (propane) gas is used. The vapor withdrawal system utilizes the gaseous fuel vapors that form at the top of the supply tank.
The pressure at which LP gas is delivered to the gen­erator’s fuel solenoid valve may vary considerably, depending on ambient temperatures. In cold weather, supply pressures may drop to "zero". In warm weath­er, extremely high gas pressures may be encoun­tered. A primary/secondary supply regulator is required to maintain correct gas supply pressure to the generator demand regulator.
Minimum recommended gaseous fuel pressure at the inlet side of the generator’s fuel solenoid valve is
Figure 1. Typical Prepackaged Installation
PART 1
Page 6
GENERAL INFORMATION
SECTION 1.2
PREPACKAGED INSTALLATION BASICS
GENERAL INFORMATION
SECTION 1.2
PREPACKAGED INSTALLATION BASICS
PART 1
Page 7
11 inches water column for LP gas (6.38 ounces per square inch), and 5 inches water column for natural gas (2.89 ounces per square inch). The maximum recommended pressure is 14 inches water column (8.09 ounces per square inch). A primary regulator may be required to ensure that proper fuel supply pressures are maintained.
DANGER: LP AND NATURAL GAS ARE BOTH HIGHLY EXPLOSIVE. GASEOUS FUEL LINES MUST BE PROPERLY PURGED AND TESTED FOR LEAKS BEFORE THIS EQUIP­MENT IS PLACED INTO SERVICE AND PERI­ODICALLY THEREAFTER. PROCEDURES USED IN GASEOUS FUEL LEAKAGE TESTS MUST COMPLY STRICTLY WITH APPLICA-
BLE FUEL GAS CODES. DO NOT USE FLAME OR ANY SOURCE OF HEAT TO TEST FOR GAS LEAKS. NO GAS LEAKAGE IS PERMITTED. LP GAS IS HEAVIER THAN AIR AND TENDS TO SETTLE IN LOW AREAS. NATURAL GAS IS LIGHTER THAN AIR AND TENDS TO SETTLE IN HIGH PLACES. EVEN THE SLIGHTEST SPARK CAN IGNITE THESE FUELS AND CAUSE AN EXPLOSION.
Use of a flexible length of hose between the genera­tor fuel line connection and rigid fuel lines is required. This will help prevent line breakage that might be caused by vibration or if the generator shifts or set­tles. The flexible fuel line must be approved for use with gaseous fuels.
!
Figure 3. Typical LP Gas Fuel System (Liquid Cooled Units)
Figure 2. Typical Natural Gas Fuel System (Liquid Cooled Units)
5-14 INCHES WATER COLUMN OPTIMUM
APPROVED FLEX LINE (CAUTION! — KEEP FLEX FUEL LINE STRAIGHT)
NATURAL GAS PRIMARY REGULATOR
GAS CARBURETOR
GENERATOR DEMAND REGULATOR
LP PRIMARY/SECONDARY SUPPLY REGULATOR
VAPOR
LIQUID
GENERATOR BASE
MANUAL SHUTOFF VALVE
APPROVED FLEX LINE (CAUTION! — KEEP FLEX FUEL LINE STRAIGHT)
11-14 INCHES WATER COLUMN OPTIMUM
GENERATOR BASE
GAS CARBURETOR
GENERATOR DEMAND REGULATOR
MANUAL SHUTOFF VALVE
THE TRANSFER SWITCH
A transfer switch is required by electrical code, to pre­vent electrical feedback between the utility and stand­by power sources, and to transfer electrical loads from one power supply to another safely.
PREPACKAGED TRANSFER SWITCHES: Instructions and information on prepackaged transfer
switches may be found in Part 3 of this manual.
POWER SOURCE AND LOAD LINES
The utility power supply lines, the standby (generator) supply lines, and electrical load lines must all be con­nected to the proper terminal lugs in the transfer switch. The following rules apply:
In 1-phase systems with a 2-pole transfer switch, con­nect the two "Utility" source hot lines to transfer switch Terminal Lugs N1 and N2. Connect the "Standby" source hot lines (E1, E2) to transfer switch Terminal Lugs E1 and E2. Connect the load lines from transfer switch Terminal Lugs T1/T2 to the elec­trical load circuit. Connect "Utility", "Standby" and "Load" neutral lines to the neutral block in the transfer switch.
SYSTEM CONTROL INTERCONNECTIONS
Prepackaged home standby generators are equipped with a terminal board identified with the following ter-
minals: (a) utility 1, (b) utility 2, (c) load 1, (d) load 2, (e) 23, and (f) 194. Prepackaged transfer switches house an identically marked terminal board. Suitable, approved wiring must be interconnected between identically numbered terminals in the generator and transfer switch. When these six terminals are properly interconnected, dropout of utility source voltage below a preset value will result in automatic generator start­up and transfer of electrical loads to the "Standby" source. On restoration of utility source voltage above a preset value will result in retransfer back to that source and generator shutdown. System control wiring must be routed through its own separate conduit.
A control board, mounted on the standby generator set, provides a "7-day exercise" feature. This feature allows the standby generator to start and run once every 7 days, on a day and at a time of day selected. The timer clock that controls this automatic exercise of the unit must be powered by voltage from the transfer switch Load 1/Load 2 terminals. If the exer­cise function is to be made available, connect suitable wiring from the ATS transfer switch load terminal lugs, to the "Load 1/Load 2" terminals in the generator.
The control board in the generator also provides a battery "trickle charge" circuit. This circuit, when pow­ered by utility source voltage, will deliver a charging voltage to the battery during non-operating periods to keep the battery charged. To use the trickle charge feature, connect suitable wiring to the generator’s "Utility 1/Utility 2" terminals and to the appropriate ter­minals in the "ATS" transfer switch.
PART 1
Page 8
GENERAL INFORMATION
SECTION 1.2
PREPACKAGED INSTALLATION BASICS
Figure 4. Prepackaged Interconnection Diagram
TRANSFER
SWITCH
UTILITY 1
REMOTE TEST
SWITCH (OPTIONAL)
- OPEN SWITCH TO TEST -
SWITCH TYPE, SPST
ELECTRICAL RATINGS,
2A @ 250Vac MIN.
LOAD 1
LOAD 2
UTILITY 2
22 UTILITY SUPPLY WITH SERVICE DISCONNECT
NEUTRAL
N1 N2
23
194
E1 E2
T1 T2
CUSTOMER
LOAD
LUG
NOTE:
POWER LEADS AND TRANSFER SWITCH LEADS MUST BE RUN IN TWO DIFFERENT CONDUITS.
NEUTRAL
CONNECTION
CB1
AC GENERATOR
CONTROL PANEL
33
11
44
UTILITY 1 (N1)
UTILITY 2 (N2) LOAD 1 (T1)
LOAD 2 (T2)
23
194
GENERAL INFORMATION
SECTION 1.3
PREPARATION BEFORE USE
PART 1
Page 9
GENERAL
The installer must ensure that the home standby gen­erator has been properly installed. The system must be inspected carefully following installation. All applic­able codes, standards and regulations pertaining to such installations must be strictly complied with. In addition, regulations established by the Occupational Safety and Health Administration (OSHA) must be complied with.
Prior to initial startup of the unit, the installer must ensure that the engine-generator has been properly prepared for use. This includes the following:
• An adequate supply of the correct fuel must be available for generator operation.
• The engine must be properly serviced with the rec­ommended oil.
• The engine cooling system must be properly ser­viced with the recommended coolant.
FUEL REQUIREMENTS
Liquid cooled engine units are shipped from the facto­ry to run on natural gas. The installer must ensure that the correct fuel supply system has been installed and is compatible with engine-generator require­ments. Read "The Fuel Supply" in Section 1.3 careful­ly.
ALL UNITS:
• When natural gas is used as a fuel, it should be rated at least 1000 BTU’s per cubic foot.
• When LP (propane) gas is used as a fuel, it should be rated at 2520 BTU’s per cubic foot.
ENGINE OIL RECOMMENDATIONS
For prepackaged generators with liquid cooled engine, use a high quality detergent oil that meets or exceeds API Service SC, SD, SE or SF. Detergent oils keep the engine cleaner and reduce carbon deposits. Use oil having the following SAE viscosity rating, based on the anticipated ambient temperature range before the next oil change:
Engine crankcase oil capacities for the 1.5 Liter engine covered in this manual can be found in the specifications section at the beginning of the book.
RECOMMENDED ENGINE COOLANT
Use a mixture of 50 percent soft water and 50 percent ethylene glycol base anti-freeze in the engine cooling system. Use only SOFT WATER and LOW SILICATE anti-freeze. If so equipped, a coolant recovery bottle must also be properly serviced with the recommend­ed 50-50 mixture. When adding coolant to the radiator or to the coolant recovery bottle, use only the recom­mended mixture.
If desired, a high quality rust inhibitor may be added to the recommended coolant mixture.
CAUTION: Do NOT use any chromate base rust inhibitor with ethylene glycol base anti­freeze, or the formation of chromium hydrox­ide (called "green slime") may result and cause overheating of the engine. The use of high silicate antifreeze boosters or additives may also cause overheating. In addition, use of any soluble oil type rust Inhibitor Is NOT recommended.
!
AMBIENT TEMPERATURE RANGE RECOMMENDED OIL
Above 80° F (27° C) SAE 30W or 15W-40
32° to 80° F (-1° to 27° C) SAE 20W-20 or 15W-40
Below 32° F (0° C) SAE 10W or 15W-40
VISUAL INSPECTION
When it becomes necessary to test or troubleshoot a generator, it is a good practice to complete a thor­ough visual inspection. Remove the access covers and look closely for any obvious problems. Look for the following:
• Burned or broken wires, broken wire connectors, damaged mounting brackets, etc.
• Loose or frayed wiring insulation, loose or dirty con­nections.
• Check that all wiring is well clear of rotating parts.
• Verify that the Generator properly connected for the correct rated voltage. This is especially important on new installations. See Section 1.2, "AC Connection Systems".
• Look for foreign objects, loose nuts, bolts and other fasteners.
• Clean the area around the Generator. Clear away paper, leaves, snow, and other objects that might blow against the generator and obstruct its air openings.
MEASURING VOLTAGES
When troubleshooting and testing the generator set, the technician will be required to measure both AC and DC voltages. Measurement of voltage requires that the user be thoroughly familiar with the meter being used for such tests. Consult the instruction manual for the meter being used.
When measuring voltage, it is best to connect the meter test leads to the terminals being tested while the generator is shut down or while power to those terminals is turned off.
DANGER: POWER VOLTAGES GENERATED BY THIS EQUIPMENT ARE EXTREMELY HIGH AND DANGEROUS. USE EXTREME CARE WHEN MEASURING POWER VOLTAGES SUCH AS GENERATOR AC OUTPUT VOLT­AGE. CONTACT WITH LIVE TERMINALS AND CONDUCTORS MAY RESULT IN HARMFUL AND POSSIBLY LETHAL ELECTRICAL SHOCK. DO NOT ATTEMPT TO READ POWER VOLTAGES WHILE STANDING ON WET OR DAMP GROUND, OR WHILE HANDS OR FEET ARE WET. STAY WELL CLEAR OF HIGH VOLTAGE POWER TERMINALS. CON­NECT METER TEST LEADS TO TERMINALS
AND LEADS WHILE THE GENERATOR IS SHUT DOWN OR WHEN THE POWER SUP­PLY TO SUCH LEADS AND TERMINALS IS TURNED OFF. THE USE OF INSULATIVE RUBBER MATS IS RECOMMENDED. TAKE POWER VOLTAGE READINGS ONLY WHILE STANDING ON SUCH INSULATIVE MATS.
MEASURING CURRENT
Alternating current (AC) can be measured with a clamp-on ammeter. Most clamp-on ammeters will not measure direct current (DC). Load current readings should never exceed the generator’s data plate rating for continuous operation. However, momentary surges in load current may be encountered when starting electric motors.
On 1-phase generators, the data plate generally lists rated line-to-line and line-to-neutral current.
MEASURING RESISTANCE
The resistance (in ohms) of generator stator and rotor windings can be measured using an ohmmeter or an accurate volt-ohm-milliammeter (VOM).
The resistance of some windings is extremely low. Some readings are so low that a meter capable of reading in the "milliohms" range would be required. Many meters will simply read CONTINUITY. However, a standard volt-ohm-milliammeter (VOM) may be used to test for continuity, or for a shorted or grounded condition.
INSULATION RESISTANCE
The insulation resistance of stator and rotor windings is a measurement of the integrity of the insulating materials that separate the electrical windings from the generator’s steel core. This resistance can degrade over time or due to such contaminants as dust, dirt, oil, grease and especially moisture. In most cases, failures of stator and rotor windings is due to a breakdown in the insulation. And, in many cases, a low insulation resistance is caused by mois­ture that collects while the generator is shut down. When problems are caused by moisture buildup on the windings, they can usually be corrected by dry­ing the windings. Cleaning and drying the windings can usually eliminate dirt and moisture built up in the generator windings.
!
PART 1
GENERAL INFORMATION
SECTION 1.4
TESTING, CLEANING AND DRYING
Page 10
GENERAL INFORMATION
SECTION 1.4
TESTING, CLEANING AND DRYING
PART 1
Page 11
MEGGERS: The normal resistance of generator winding insulation
is on the order of millions of ohms. This high resis­tance can be measured with a device called a "meg­ger". The megger is a megohm meter ("meg" stands for million) and a power supply. The power supply voltage varies between megger models and is selec­table on some models. The most common power sup­ply voltage is 500 volts. Use of power supplies greater than 500 volts are not recommended on prepackaged generators.
CAUTION: Before attempting to measure Insulation resistance, first disconnect and Isolate all leads of the winding to be tested. Electronic components, diodes, surge pro­tectors, relays, voltage regulators, etc., can be destroyed if subjected to high megger voltages.
HI-POT TESTER: A "Hi-Pot" tester is shown in Figure 1. The model
shown is only one of many that are commercially available. The tester shown is equipped with a volt­age selector switch that permits the power supply voltage to be selected. It also mounts a breakdown lamp that will illuminate to indicate an insulation breakdown during the test.
Figure 1. One Type of Hi-Pot Tester
STATOR INSULATION TESTS
GENERAL: Units with liquid cooled engine and 1 -phase stator
windings are equipped with (a) dual stator AC power windings, and (b) an excitation or DPE winding. These units are not equipped with a battery charge winding. Stator winding insulation tests consist of (a) testing all windings to ground, (b) testing between iso­lated windings, and (c) testing between parallel wind­ings. Figure 3 represents the various stator AC output leads on 1 -phase units with liquid-cooled engine.
TEST ALL WINDINGS TO GROUND:
1.Disconnect and isolate Stator Leads 11, 22, 33, 44, 2 and 6.
2.Connect terminal ends of all stator leads together. Make sure all wire terminal ends are completely isolated from frame ground.
3.Connect the red test probe of the Hi-Pot tester to the terminal ends of all stator leads. Connect the black tester probe to a clean frame ground on the stator can. Then, proceed as follows:
a.Turn the Hi- Pot tester switch OFF b.Plug the tester cord into a 120 volts AC wall
socket and set its voltage selector switch to "500 volts".
c.Turn the tester switch ON and observe the
breakdown lamp. After one (1) second, turn the tester switch OFF.
If the breakdown lamp turned on during the one (1) second test, clean and dry the stator. Then, repeat the test. If breakdown lamp comes on during the sec­ond test, replace the stator assembly.
Figure 3. Stator Winding Leads (Liquid Cooled Units)
TEST BETWEEN ISOLATED WINDINGS:
1.Connect the red test probe to stator lead 2, the black probe to stator lead 11.
2.Set the tester switch to "500 volts".
3.Turn the tester switch ON and check that the pilot lamp is lighted.
4.Wait one (1) second while observing the tester breakdown lamp. DO NOT EXCEED ONE SEC­OND. After one (1) second, turn the tester switch OFF.
5.Connect the red test probe to stator lead 2, the black probe to stator lead 33. Then, repeat Steps 2, 3 and 4.
!
11
22
33
44
6
2
If the breakdown lamp turned on during any one (1) second test, the stator should be cleaned and dried. After cleaning and drying, repeat the test. If the break­down lamp turns on during the second test, replace the stator assembly.
TEST BETWEEN PARALLEL WINDINGS: 1 Set the tester’s voltage switch to "500 volts".
2.Connect the red tester probe to stator lead 11, the black probe to stator lead 33.
3.Turn the tester switch ON and check that the pilot lamp is on.
4.Waft one (1) second while observing the break­down lamp. Then, turn the tester switch OFF.
If the breakdown lamp came on during the one (1) second test, clean and dry the stator. Then, repeat the test. If breakdown lamp comes on during second test, replace the stator assembly.
TESTING ROTOR INSULATION
Before attempting to test rotor insulation, either the brush leads must be completely removed from the brushes or the brush holders must be completely removed. The rotor must be completely isolated from other components before starting the test.
1.Connect the red tester lead to the positive (+) slip ring (nearest the rotor bearing).
2.Connect the black tester probe to a clean frame ground, such as a clean metal part of the rotor.
3.Turn the tester switch OFF.
4.Plug the tester into a 120 volts AC wall socket and set the voltage switch to "500 volts".
5.Turn the tester switch ON and make sure the pilot light has turned on.
6.Observe the breakdown lamp, then turn the tester switch OFF. DO NOT APPLY VOLTAGE LONGER THAN ONE (1) SECOND.
If the breakdown lamp came on during the one (1) second test, cleaning and drying of the rotor may be necessary. After cleaning and drying, repeat the insu­lation breakdown test. If breakdown lamp comes on during the second test, replace the rotor assembly.
Figure 6. Testing Rotor Insulation
CLEANING THE GENERATOR
Caked or greasy dirt may be loosened with a soft brush or a damp cloth. A vacuum system may be used to clean up loosened dirt. Dust and dirt may also be removed using dry, low-pressure air (25 psi maxi­mum).
CAUTION: Do not use sprayed water to clean the generator. Some of the water will be retained on generator windings and termi­nals, and may cause very serious problems.
DRYING THE GENERATOR
To dry a generator, proceed as follows:
1.Open the generator main circuit breaker. NO ELEC­TRICAL LOADS MUST BE APPLIED TO THE GENERATOR WHILE DRYING.
2.Disconnect all wires No. 4 from the voltage regula­tor.
3.Provide an external source to blow warm, dry air through the generator interior (around the rotor and stator windings. DO NOT EXCEED 185° F. (85° C.).
4.Start the generator and let it run for 2 or 3 hours.
5.Shut the generator down and repeat the stator and rotor insulation resistance tests.
!
PART 1
Page 12
GENERAL INFORMATION
SECTION 1.4
TESTING, CLEANING AND DRYING
RED TEST LEAD
BLACK TEST LEAD
GENERAL INFORMATION
SECTION 1.5
ENGINE-GENERATOR PROTECTIVE DEVICES
PART 1
Page 13
GENERAL
Standby electric power generators will often run unat­tended for long periods of time. Such operating para­meters as (a) engine oil pressure, (b) engine temper­ature, (c) engine operating speed, and (d) engine cranking and startup are not monitored by an operator during automatic operation. Because engine opera­tion will not be monitored, the use of engine protective safety devices is required to prevent engine damage in the event of a problem.
Prepackaged generator engines mount several engine protective devices. These devices work in conjunction with a control circuit board, to protect the engine
against such operating faults as (a) low engine oil pressure, (b) high temperature, (c) overspeed, and (d) overcrank. On occurrence of any one or more of those operating faults, control board action will effect an engine shutdown.
LOW OIL PRESSURE SHUTDOWN: See Figure 1. Prepackaged generators with liquid
cooled engine are equipped with an oil pressure switch having a closing pressure of about 10 psi. Should oil pressure drop below that value, an auto­matic engine shutdown will occur. Circuit operation is similar to that of air-cooled units.
Figure 1. Protective Devices on Liquid Cooled Engine
LOW COOLANT LEVEL SWITCH
HIGH COOLANT
TEMPERATURE
SWITCH
OVERCRANK AND OVERSPEED
SHUTDOWN ARE CONTROLLED
BY THE CIRCUIT BOARD
LOW OIL
PRESSURE
SWITCH
PART 1
Page 14
GENERAL INFORMATION
SECTION 1.5
ENGINE-GENERATOR PROTECTIVE DEVICES
HIGH COOLANT TEMPERATURE SHUTDOWN: The engine is equipped with a coolant temperature
switch. Should engine coolant temperature exceed approximately 284° F. (140° C.), the engine will be shut down automatically by control board action.
LOW COOLANT LEVEL SENSOR: It is possible that engine coolant level might drop low
enough so that the high temperature switch is no longer immersed in the liquid coolant. If this happens engine temperatures could increase rapidly but the temperature switch would not sense the high temper­ature condition and the engine would continue to run. To prevent this occurrence, a low coolant level sensor is provided. The sensor is immersed in cooling sys­tem liquid. If coolant level drops below the level of the low coolant level sensor, the device will complete a Wire 85 circuit to ground. Engine shutdown will occur.
OVERSPEED SHUTDOWN: The control board on liquid cooled units receives AC
frequency (rpm) signals directly from the stator AC power windings, via sensing leads S15 and S16. Should AC frequency exceed approximately 72 Hz, circuit board action will initiate an automatic engine shutdown.
NOTE: For units rated 1800 rpm, 72 Hz is equal to 2160 rpm.
NOTE: The control board also uses the sensing lead signals (S15, S16) (a) to terminate cranking at about 50% of rated frequency, and (b) as an “engine running” signal. The circuit board will not initiate transfer of electrical loads to the "Standby" source until sensing voltage and fre­quency is greater than 50 % of the unit’s rated values.
OVERCRANK SHUTDOWN: Automatic engine cranking and startup normally
occurs when the control board senses that utility source voltage has dropped below approximately 60 percent of its nominal rated voltage and remains at that low level longer than six (6) seconds. At the end of six (6) seconds, control board action will energize a crank relay and a run relay (both relays are on the control board). On closure of the crank relay contacts, control board action will deliver 12 volts DC to a con­trol contactor (CC). The control contactor will ener­gize and battery power will be delivered across its closed contacts to the starter motor (SM). The engine will then crank.
During a manual startup (AUTO-OFF-MANUAL switch at "Manual"), action is the same as during an automatic start, except that cranking will begin imme­diately when the switch is set to "Manual".
Control board action (during both a manual and an automatic start) will hold the crank relay energized for about 7-9 seconds. The relay will then de-energize for about 7-9 seconds, and then energize again. In this manner, the engine will be cranked for 7-9 seconds, will rest for 7-9 seconds, and will crank again, and so on until the engine starts.
If the engine has not started after approximately 90 sec­onds of these crank-rest cycles, cranking will automati­cally terminate and shutdown will occur. The control board uses AC signals from the stator battery charge windings as an indication that the engine has started.
Page 15
CONTROL PANEL
GENERAL: See Figure 1 (Page 16). A typical prepackaged control
panel on units with liquid cooled engine includes: (a) an auto-off-manual switch, (b) a fault indicator lamp, (c) a 15 amp fuse, and (d) a set exercise switch.
AUTO-OFF-MANUAL SWITCH: Use this switch to (a) select fully automatic operation,
(b) to crank and start the engine manually, and (c) to shut the unit down or to prevent automatic startup.
1. AUTO position:
a.Select AUTO for fully automatic operation. b.When AUTO is selected, circuit board will moni-
tor utility power source voltage.
c. Should utility voltage drop below a preset level
and remain at such a low level for a preset time, circuit board action will initiate engine cranking and startup.
d.Following engine startup, circuit board action
will initiate transfer of electrical loads to the “Standby” source side.
e.On restoration of utility source voltage above a
preset level, circuit board action will initiate retransfer back to the “Utility Source” side.
f. Following retransfer, circuit board will shut the
engine down and will then continue to monitor utility source voltage.
2. OFF Position:
a.Set the switch to OFF to stop an operating
engine.
b.To prevent an automatic startup from occurring,
set the switch to OFF.
3. MANUAL Position:
a.Set switch to MANUAL to crank and start unit
manually.
b.Engine will crank cyclically and start (same as
automatic startup, but without transfer). The unit will transfer if utility voltage is not available.
DANGER: WHEN THE GENERATOR IS INSTALLED IN CONJUNCTION WITH AN AUTOMATIC TRANSFER SWITCH, ENGINE CRANKING AND STARTUP CAN OCCUR AT ANY TIME WITHOUT WARNING (PROVIDING THE AUTO-OFF-MANUAL SWITCH IS SET TO AUTO). TO PREVENT AUTOMATIC STARTUP AND POSSIBLE INJURY THAT MIGHT BE CAUSED BY SUCH STARTUP, ALWAYS SET THE AUTO-OFF-MANUAL SWITCH TO ITS OFF POSITION BEFORE WORKING ON OR AROUND THIS EQUIPMENT.
FAULT INDICATOR LAMP: The fault indicator lamp will turn on in the event that
any one or more of the following engine fault condi­tions should occur: (a) low oil pressure, (b) high coolant temperature, (c) low coolant level, (d) over­speed, and (e) overcrank.
15 AMP FUSE: This fuse protects the DC control system, including
the control board, against overload. If the fuse has blown, engine cranking and running will not be possi­ble. Should fuse replacement become necessary, use only an identical 15 amp replacement fuse.
THE SET EXERCISE SWITCH: Use this switch to select the time and day for system
exercise.
TO SELECT AUTOMATIC OPERATION
The following procedure applies to those installations in which the prepackaged home standby generator is installed in conjunction with a prepackaged transfer switch. Prepackaged transfer switches do not have an intelligence circuit of their own. Instead, automatic operation on prepackaged transfer switch and gener­ator combinations is controlled by a control circuit board housed in the generator.
To select automatic operation when a prepackaged transfer switch is installed along with a prepackaged home standby generator, proceed as follows:
1. Check that the prepackaged transfer switch main con­tacts are at their “Utility” position, i.e., the load is connect­ed to the utility power supply. If necessary, manually actu­ate the switch main contacts to their “Utility” source side. See Part 3 of this manual for instructions.
2. Check that utility source voltage is available to transfer switch Terminal Lugs N1 and N2 (2-pole, 1-phase transfer switches).
3.Set the generator’s AUTO-OFF-MANUAL switch to its AUTO position.
4. Actuate the generator’s main line circuit breaker to its ON or “Closed” position. With the preceding Steps 1 through 4 completed, a dropout in utility supply voltage below a preset level will result in automatic generator cranking and start-up. Following startup, the prepackaged transfer switch will be actuated to its “Standby” source side, i.e., loads powered by the standby generator.
MANUAL TRANSFER TO “STANDBY” AND
MANUAL STARTUP
To transfer electrical loads to the "Standby" (genera­tor) source and start the generator manually, proceed
!
GENERAL INFORMATION
SECTION 1.6
OPERATING INSTRUCTIONS
PART 1
PART 1
Page 16
GENERAL INFORMATION
SECTION 1.6
OPERATING INSTRUCTIONS
as follows:
1.On the generator panel, set the AUTO-OFF-MANU­AL switch to OFF.
2.On the generator, set the main line circuit breaker to it’s OFF or "Open" position.
3.Turn OFF the utility power supply to the transfer switch, using whatever means provided (such as a utility-source line circuit breaker).
4.Manually actuate the transfer switch main contacts to their “Standby” position, i.e., loads connected to the “Standby” power source side.
5.On the generator panel, set the AUTO-OFF-MANU­AL switch to MANUAL. The engine should crank and start.
6.Let the engine warm up and stabilize for a minute or two at no-load.
7.Set the generator’s main line circuit breaker to its ON or "Closed" position. The generator now powers the electrical loads.
MANUAL SHUTDOWN AND RETRANSFER
BACK TO "UTILITY"
To shut the generator down and retransfer electrical loads back to the "Utility" position, proceed as follows:
1.Set the generator’s main line circuit breaker to its OFF or "Open" position.
2.Let the generator run at no-load for a few minutes, to cool.
3.Set the generator’s AUTO-OFF-MANUAL switch to OFF. Wait for the engine to come to a complete stop.
4.Turn OFF the “Utility” power supply to the transfer switch using whatever means provided (such as a “Utility” source main line circuit breaker)
5.Manually actuate the prepackaged transfer switch to its “Utility” power source side, i.e., “Load” con­nected to the “Utility” source.
6.Turn ON the “Utility” power supply to the transfer switch, using whatever means provided.
7.Set the generator’s AUTO-OFF-MANUAL switch to AUTO.
THE SET EXERCISE TIME SWITCH
The prepackaged home standby generator will start and exercise once every seven (7) days, on a day and at a time of day selected by the owner or opera­tor. The set exercise time switch is provided to select the day and time of day for system exercise.
See Part 5, Section 5.2 ("The 7-Day Exercise Cycle") for instructions on how to set exercise time.
DANGER: THE GENERATOR WILL CRANK AND START WHEN THE SET EXERCISE TIME SWITCH IS SET TO "ON". DO NOT ACTUATE THE SWITCH TO "ON" UNTIL AFTER YOU HAVE READ THE INSTRUC­TIONS IN SECTION 1.6.
!
Figure 1. Control Panel
HOURMETER
AUTO
OFF
MANUAL
FUSE
15-A AGC
FAULT
INDICATOR
SET EXERCISE TIME
ON
Page 17
GENERAL INFORMATION
SECTION 1.7
AUTOMATIC OPERATING PARAMETERS
PART 1
INTRODUCTION
When the prepackaged generator is installed in con­junction with a prepackaged transfer switch, either manual or automatic operation is possible. Manual transfer and engine startup, as well as manual shut­down and retransfer are covered in section 1.7. Selection of fully automatic operation is also dis­cussed in that section. This section will provide a step-by-step description of the sequence of events that will occur during automatic operation of the sys­tem.
AUTOMATIC OPERATING SEQUENCES
PHASE 1 - UTILITY VOLTAGE AVAILABLE: With utility source voltage available to the transfer
switch, that source voltage is sensed by a control board in the generator panel and the circuit board takes no action.
Electrical loads are powered by the "Utility" source and the AUTO-OFF-MANUAL switch is set to AUTO.
PHASE 2 - UTILITY VOLTAGE DROPOUT: If a dropout in utility source voltage should occur
below about 60 percent of the nominal utility source voltage, a 12 second timer on the control board will start timing. This timer is required to prevent false generator starts that might be caused by transient util­ity voltage dips.
PHASE 3 - ENGINE CRANKING: When the control board’s 12 second timer has fin-
ished timing and if utility source voltage is still below 60 percent of the nominal source voltage, control board action will energize a crank relay and a run relay. Both of these relays are mounted on the control board.
Control board action will hold the crank relay ener­gized for about 7-9 seconds. The relay will then be de-energized for about 7-9 seconds, energized again for 7-9 seconds, and so on. When the crank relay energizes the engine will crank, when it is de-ener­gized, engine cranking will stop. This cyclic action of crank/rest, crank/rest, etc., will continue until either (a) the engine starts, or (b) until ninety (90) seconds have elapsed.
If the engine has not started within ninety (90) sec­onds, cranking will terminate and shutdown will occur. On liquid cooled engine units, a fault indicator lamp (LED) on the generator panel will illuminate.
If the engine starts, cranking will terminate when gener­ator AC output frequency reaches approximately 30 Hz.
PHASE 4 - ENGINE STARTUP AND RUNNING: The control board senses that the engine is running
by receiving a voltage/frequency signal from the gen­erator stator windings.
When generator AC frequency reaches approximately 30 Hz, an engine warm-up timer on the control board turns on. That timer will run for about fifteen (15) sec­onds. At the same time, an engine minimum run timer will turn on.
The engine warm-up timer lets the engine warm-up and stabilize before transfer to the "Standby" source can occur.
The engine minimum run timer prevents a cold engine from being shut down, as might happen if utility source power is restored very quickly. The minimum run timer will run for about 10-12 minutes. That means the engine must run for 10-12 minutes before it can be shut down automatically.
NOTE: The engine can be shut down manually at any time, by setting the AUTO-OFF-MANUAL switch to OFF.
PHASE 5 - TRANSFER TO “STANDBY”: When the control board’s engine warm-up timer has
timed out, control board action completes a transfer relay circuit to ground. The transfer relay is housed in the prepackaged transfer switch enclosure.
The transfer relay energizes and transfer of loads to the “Standby” power source occurs. Loads are now powered by standby generator AC output.
PHASE 6 - “UTILITY” POWER RESTORED: When utility source voltage is restored above about
80 percent of the nominal supply voltage, a fifteen (15) second timer on the control board starts timing. If utility voltage remains sufficiently high at the end of fifteen (15) seconds, a “retransfer time delay” will start timing and will time for about six (6) seconds.
PHASE 7 - RETRANSFER BACK TO “UTILITY”: When the retransfer time delay has finished timing,
control board action will open a circuit to a transfer relay (housed in the transfer switch). The transfer relay will then de-energize and retransfer back to the “Utility” source will occur. Loads are now powered by “Utility” source power. On retransfer, an “engine cool­down timer” starts timing and will run for about one (1) minute.
PHASE 8 - GENERATOR SHUTDOWN: When the engine cool-down timer has finished timing,
and if the minimum run timer has timed out, engine shutdown will occur.
PART 1
GENERAL INFORMATION
SECTION 1.7
AUTOMATIC OPERATING PARAMETERS
Page 18
AUTOMATIC OPERATING SEQUENCES CHART
SEQ. CONDITION ACTION SENSOR, TIMER OR OTHER
1 “Utility” source voltage is No action Voltage Dropout Sensor on control
available. circuit board.
2 “Utility” voltage dropout below A 6-second timer on control Voltage Dropout Sensor and 6
60% of rated voltage occurs. board turns on. second timer on control board.
3 “Utility” voltage is still below 6-second timer runs for 6 Voltage Dropout Sensor and 6
60% of rated voltage. seconds, then stops. second timer.
4 “Utility” voltage is still low after Control board action energizes a Control board crank and run
6 seconds. crank relay and a run relay. The relays.
engine cranks for 7-9 seconds, rests for 7-9 seconds, and so on until engine starts. See NOTE 1.
5 “Utility” voltage still low and Control board’s “engine warmup Engine Warmup Timer (15 seconds)
the engine has started. timer” and “engine minimum run Minimum Run Timer (13 minutes)
timer” both turn on.
6 Engine running and “engine Control board action energizes a Control board transfer relay circuit
warmup timer” times out. transfer relay in transfer switch Transfer switch transfer relay.
and transfer to “Standby” occurs.
7 Engine running and load is No further action Control board’s “voltage pickup
powered by “Standby” power. sensor” continues to seek an
acceptable “Utility voltage.
8 “Utility” source voltage is Control board’s “voltage pickup Voltage Pickup Sensor (80%)
restored above 80% of rated sensor” reacts and a “return to Return to Utility Timer (10 seconds) source voltage. utility timer” turns on.
9 “Utility voltage still high after 6 “Return to utility timer” times out Return to Utility Timer
seconds.
10 “Utility” voltage still high. Control board action opens the Control board transfer relay circuit
transfer relay circuit to ground. Transfer switch transfer relay. Transfer relay de-energizes and retransfer to “Utility” occurs.
11 Engine still running, loads are Control board’s “engine cooldown control board’s Engine Cooldown
powered by “Utility” source. timer” starts running. Timer (1 minute)
12 After 1 minute, “engine cooldown Engine Cooldown Timer
timer” stops and control board’s control board Run Relay. run relay de-energizes. Engine shuts down.
13 Engine is shut down, loads are No action. Voltage Dropout Sensor on control
powered by “Utility” source. circuit board. Return to Sequence 1.
Note1: In Sequence 4, if engine has not started in 90 seconds cranking will end and shutdown will occur.
Page 19
PART TITLE PAGE
2.1 Description and Major Components 20
2.2 AC Output Operational Analysis 24
2.3 AC Output Troubleshooting Flow Charts 26
Problem 1 - Generator Produces ZeroVoltage or
ResidualVoltage 26
Problem 2 - Generator Produces
LowVoltage at No-Load 28
Problem 3 - Generator Produces High
Voltage at No-Load 28
Problem 4 -Voltage and Frequency Drop
ExcessivelyWhen Loads Are Applied 29
2.4 AC Output Diagnostic Tests 30
TABLE OF CONTENTS
1.5 LITER PREPACKAGED HOME STANDBY
GENERATORS
PART 2
PREPACKAGED
LIQUID-COOLED
AC GENERATORS
TEST DESCRIPTION ......................................PAGE
1 Check Main Circuit Breaker ................................ 30
2 Check AC Output Voltage .................................. 31
3 Test Excitation Circuit Breaker .......................... 31
4 Test Thermal Protector ...................................... 32
5 Fixed Excitation Test/Rotor
Amp Draw Test .................................................. 32
6 Wire Continuity .................................................. 33
7 Check Field Boost .............................................. 33
8 Testing the Ststor with a VOM ............................ 34
9 Resistance Check of Rotor Circuit .................... 35
TEST DESCRIPTION ......................................PAGE
10 Check Brushes
and Slip Rings .................................................... 35
11 Test Rotor Assembly .......................................... 35
12 Check AC Output Frequency ............................ 36
13 Check and Adjust Governor Board
and Stepper Motor .............................................. 36
14 Check and Adjust
Voltage Regulator .............................................. 38
15 Check Voltage and Frequency Under Load ...... 38
16 Check for Overload Condition ............................ 38
17 Check Engine Condition .................................... 38
INTRODUCTION
This section covers the major components of the AC generator proper, i.e., those generator assemblies that provide for the production of AC electrical power.
The single bearing rotor (revolving field) is driven by a
1.5 liter, liquid cooled gas engine. The rotor is cou­pled to the engine flywheel, by means of a flexible coupling and a fan and ring gear assembly, so the engine crankshaft and rotor operate at the same speed.
Major components of the AC generator are shown in Figure 1 on the next page. These components are (a) a flexible coupling, (b) fan and ring gear, (c) rotor, (d) blower housing, (e) stator assembly, (f) rear bearing carrier, and (g) a rear bearing carrier cover.
BLOWER HOUSING
The blower housing is bolted to the engine and sup­ports the engine end of the AC generator. It houses the fan and ring gear assembly. A cutout area on one side of the housing allows a blower air outlet screen to be mounted.
FLEXIBLE DISK
A flexible disk bolts to the engine flywheel and to the fan and ring gear assembly. The disk maintains prop­er alignment between the engine and generator parts.
FAN AND RING GEAR ASSEMBLY
The fan and ring gear assembly are retained to the flexible disk which, in turn, is retained to the engine flywheel. The fan draws cooling air into the generator interior through slots in a rear bearing carrier cover, then expels the heated air outward through a screen on the blower housing. The ring gear teeth mate with teeth on a starter motor pinion gear, when the engine is cranked.
ROTOR ASSEMBLY
The rotor assembly on units rated 1800 rpm is a 4­pole type, having two north magnetic poles and two south magnetic poles.
The rear end of the rotor is bolted and keyed to the fan and ring gear. A ball bearing has been pressed onto the rotor’s front shaft, which is retained, in a machined bore in the rear bearing carrier.
A positive (+) and a negative (-) slip ring is provided on the rotor shaft that retains the ball bearing. Brushes will ride on these slip rings.
The combination of slip rings and brushes allow rotor excitation current to be transmitted from stationary components into the rotating rotor windings. The posi­tive (+) slip ring is the one nearest the rotor bearing.
REAR BEARING CARRIER
The rear bearing carrier supports the front of the gen­erator. Mounting feet at the carrier bottom permit the carrier to be bolted to the generator’s mounting base. A machined bore, in the center of the carrier, accepts the rotor bearing. Bosses allow for the retention of brush holders. Long stator bolts pass through holes in the carrier’s outer periphery, to sandwich and retain the stator can between the carrier and the blower housing. A rear bearing carrier gasket helps prevent dust from entering the bearing area.
STATOR ASSEMBLY
The stator can is sandwiched between the blower housing and the rear bearing carrier, and retained in that position by four (4) stator bolts.
A notched cutout has been provided in the rear bear­ing carrier end of the stator can. A rubber grommet has been placed into that notch, for protection of the stator leads that are brought out of the stator.
REAR BEARING CARRIER PLATE
This plate is retained to the rear bearing carrier by four (4) capscrews, lockwashers and flatwashers. The plate provides slotted air inlet openings for the pas­sage of cooling and ventilating air into the generator.
BRUSH HOLDERS AND BRUSHES
Brushes are retained in a brush holder which is retained to drilled and threaded bosses on the rear bearing carrier. In most cases, two brush holders are used having two brushes per holder. Brush holders are precisely positioned so that one of the two brush­es slides on a positive (+) slip ring, the other on a negative (-) slip ring. The positive (+) brush and slip ring are nearest the rotor bearing. The positive (+) side of the DC excitation circuit (Wire No. 4, red) con­nects to the positive (+) brush; the negative (-) or grounded side (Wire No. 0) to the negative (-) brush. Brushes and brush holders are illustrated in Figure 2, on Page 22.
PART 2
Page 20
PREPACKAGED LIQUID
COOLED AC GENERATORS
SECTION 2.1
DESCRIPTION AND MAJOR COMPONENTS
PREPACKAGED LIQUID
COOLED AC GENERATORS
SECTION 2.1
DESCRIPTION AND MAJOR COMPONENTS
PART 2
Page 21
S
OR
er
g
OR
OUSING
SK
S
R
E
e
t
Figure 1. Generator Major Components
ROT
FLEXIBLE DI
TAT
REAR BEARING CARRIE
BRUSH HOLDERS AND BRUSHE
To Blow
Housin
REAR BEARING CARRIER PLAT
To Engin
rankshaf
BLOWER H
Figure 2. Brush Holders and Brushes
THE EXCITATION CIRCUIT
AC output from the stator excitation (DPE) winding is delivered to the voltage regulator, via a thermal pro­tector (TP), Wire No. 2, an excitation circuit breaker (CB1), Wire No. 162, and Wire No. 6. This is “unregu­lated” excitation current.
Figure 3. Schematic - Excitation Circuit
THERMAL PROTECTOR: This normally closed thermal switch protects the stator
windings against excessively high internal tempera­tures. The switch is physically imbedded in the stator windings and electrically connected in series with the DPE winding AC output to the regulator. If internal sta­tor temperatures exceed a safe value, the switch con­tacts will open and the DPE output to the voltage regu­lator will be terminated. Without excitation current flow to the rotor, generator AC output voltage will drop to a value commensurate with rotor residual magnetism.
The thermal protector is self-resetting. That is, when internal stator temperatures drop to a safe value, its contacts will re-close and normal DPE output to the regulator will resume.
Wire No. 5 is a thermal protector “bypass” lead. If the thermal switch has failed in its open position, it can be bypassed. The Wire No. 5 bypass lead is brought out of the stator and has a wire nut on its end.
Figure 4. The Thermal Protector
EXCITATION CIRCUIT BREAKER: This circuit breaker protects the regulator against high
voltage surges. If the breaker has tripped open, loss of excitation current will occur. Stator power winding AC output voltage will then drop to a value commen­surate with residual magnetism in the rotor. The breaker is self-resetting.
Figure 5. Excitation Circuit Breaker
VOLTAGE REGULATOR: See Figure 6. Unregulated AC output from the stator
DPE winding is delivered to the voltage regulator, via Wires No. 6 and 162. Stator power winding AC volt­age and frequency signals are delivered to the regula­tor, via “sensing” Wires No. S15 and S16. The regula­tor rectifies the DPE output and, based on the sensing lead signals, regulates the DC current output. An LED (light emitting diode) is incorporated on the regulator. This red light senses the “sensing” (S15/S16) input.
62
CK
CK
D
D
PART 2
Page 22
PREPACKAGED LIQUID
COOLED AC GENERATORS
SECTION 2.1
DESCRIPTION AND MAJOR COMPONENTS
+ -
BLA
BLA
H WITH RED LEA
RE
DPE - STATOR EXCITATION WINDING
CB2 - EXCITATION CIRCUIT BREAKER
VR - VOLTAGE REGULATOR
TP - THERMAL PROTECTOR
6
DPE TP
WIRE
5
NUT
(BYPASS)
2
CB2
6
162
162
6
VR
1
PREPACKAGED LIQUID
COOLED AC GENERATORS
SECTION 2.1
DESCRIPTION AND MAJOR COMPONENTS
PART 2
Page 23
Figure 6. Prepackaged Voltage Regulator
If the red LED goes “out”, sensing signals to the regu­lator have been lost. The following rules apply:
• Loss of sensing can be caused by an “open” circuit condition in sensing leads S15 and S16. These sensing leads also operate the generator’s panel mounted AC frequency meter. Thus, if the red LED is out, it may be assumed that an open circuit exists in the sensing circuit.
• Loss of sensing to the regulator will usually result in a “full field” condition and resultant high voltage out­put from stator AC power winding. The maximum voltage that regulator action can deliver is limited by a “clamming” action on the part of the regulator.
• A complete open circuit condition in the stator AC power windings will cause loss of sensing voltage and frequency. However, this will result in a zero voltage output from the stator windings.
Based on the “sensing” signals, the regulator delivers direct current (DC) to the rotor, via Wire No. 4 and the positive (+) brush and slip ring. This regulated current flows through the rotor and to frame ground, via the negative (-) slip ring and brush and Wire No. 1. The following apply:
• The concentration of magnetic flux lines around the rotor will be proportional to the regulated excitation current flow through the rotor plus any residual magnetism.
• An increase in excitation current flow through the rotor windings will increase the concentration of “magnetic flux” lines around the rotor which, in turn, will increase the AC voltage induced into the stator AC power windings.
FIELD BOOST
See Figure 7. The prepackaged system provides a “field boost” feature. Field boost, in effect, “flashes the field” whenever the engine is cranking to ensure an early “pickup voltage” in the stator windings.
A field boost diode and a field boost resistor are installed in a printed circuit board. Field boost DC out­put to the rotor is reduced to approximately 9-10 volts by the field boost resistor.
Manual and automatic cranking is initiated by PCB board action, when that board energizes a crank relay (K1). When the relay is energized, battery voltage is delivered across its closed contacts and to the rotor, via a field boost resistor, field boost diode, and Wire No. 4. Notice that field boost current flow is available only while the engine is cranking.
Figure 7. The Field Boost Circuit
(from Schematic Drawing #0F5244)
0
6
4
4
S16
S15
162
1
AR
RED
4
1
4
0
4
VR
4
0
2
17A
7D119
5
PCB
16
10 12
E 4
3
14
15
13
1
B
ROTOR RESIDUAL MAGNETISM
The generator revolving field (rotor) may be consid­ered to be a permanent magnet. Some ‘residual” magnetism is always present in the rotor. This resid­ual magnetism is sufficient to induce a voltage into the stator AC power windings that is approximately 2­12 volts AC.
FIELD BOOST
FIELD BOOST CIRCUIT: When the engine is cranking, direct current flow is
delivered from a circuit board to the generator rotor windings, via Wire 4.
The field boost system is shown schematically in Figure 2. Manual and automatic engine cranking is initiated by circuit board action, when that circuit board energizes a crank relay. Battery voltage is then delivered to field boost Wire 4 (and to the rotor), via a field boost resistor and diode. The crank relay, field boost resistor and diode are all located on the circuit board.
Notice that field boost current is available only while the crank relay is energized, i.e., while the engine is cranking.
Field boost voltage is reduced from that of battery voltage by the resistor action and, when read with a DC voltmeter, will be approximately 9 or 10 volts DC.
Figure 7. The Field Boost Circuit
(from Schematic Drawing #0F5244)
Figure 1. Operating Diagram of AC Generator
PART 2
Page 24
PREPACKAGED LIQUID
COOLED AC GENERATORS
SECTION 2.2
OPERATIONAL ANALYSIS
1
AR
RED
4
1
4
0
4
VR
4
0
2
13
1
B
17A
7D119
5
PCB
16
10 12
E 4
3
14
15
PREPACKAGED LIQUID
COOLED AC GENERATORS
SECTION 2.2
OPERATIONAL ANALYSIS
PART 2
Page 25
OPERATION
STARTUP: When the engine is started, residual plus field boost
magnetism from the rotor induces a voltage into the stator AC power windings and the stator excitation or DPE windings. In an “on-speed” condition, residual plus field boost magnetism are capable of creating approximately one-half the unit’s rated voltage.
ON-SPEED OPERATION: As the engine accelerates, the voltage that is induced
into the stator windings increases rapidly, due to the increasing speed at which the rotor operates.
FIELD EXCITATION: An AC voltage is induced into the stator excitation
(DPE) windings. The DPE winding circuit is completed to the voltage regulator, via Wire 2, excitation circuit breaker, Wire 162, and Wire 6. Unregulated alternat­ing current can flow from the winding to the regulator.
The voltage regulator “senses” AC power winding output voltage and frequency via stator Wires S15 and S16.
The regulator changes the AC from the excitation winding to DC. In addition, based on the Wires S15 and S16 sensing signals, it regulates the flow of direct current to the rotor.
The rectified and regulated current flow from the reg­ulator is delivered to the rotor windings, via Wire 4, and the positive brush and slip ring. This excitation current flows through the rotor windings and is direct­ed to ground through the negative (-) slip ring and brush, and Wire 1.
The greater the current flow through the rotor wind­ings, the more concentrated the lines of flux around the rotor become.
The more concentrated the lines of flux around the rotor that cut across the stationary stator windings, the greater the voltage that is induced into the stator windings.
Initially, the AC power winding voltage sensed by the regulator is low. The regulator reacts by increasing the flow of excitation current to the rotor until voltage increases to a desired level. The regulator then main­tains the desired voltage. For example, if voltage exceeds the desired level, the regulator will decrease the flow of excitation current. Conversely, if voltage drops below the desired level, the regulator responds by increasing the flow of excitation current.
AC POWER WINDING OUTPUT: A regulated voltage is induced into the stator AC
power windings. When electrical loads are connected across the AC power windings to complete the circuit, current can flow in the circuit. The regulated AC power winding output voltage will be in direct propor­tion to the AC frequency. For example, on units rated 120/240 volts at 60 Hz, the regulator will try to main­tain 240 volts (line-to-line) at 60 Hz. This type of regu­lation system provides greatly improved motor start­ing capability over other types of systems.
Use the “Flow Charts” in conjunction with the detailed instructions in Section 2.4. Test numbers used in the flow charts correspond to the numbered tests in Section 2.4.
The first step in using the flow charts is to correctly identify the problem. Once that has been done, locate the problem on the following pages. For best results, perform all tests in the exact sequence shown in the flow charts.
PART 2
Page 26
PREPACKAGED LIQUID
COOLED AC GENERATORS
SECTION 2.3
TROUBLESHOOTING FLOW CHARTS
Problem 1 - Generator Produces Zero Voltage or Residual Voltage
TEST 1 - CHECK
MAIN CIRCUIT
BREAKER
RESET TO
“ON”
OR REPLACE
IF BAD
A
PERFORM FIXED
TEST 3 - TEST
EXCITATION
CIRCUIT BREAKER
TEST 5 -
EXCITATION /
ROTOR AMP
DRAW
G
D
B
C
GOOD -PROCEED
BAD -PROCEED, REPLACE AFTER TESTS
CONCLUDE
TEST 4 - TEST
THERMAL
PROTECTOR
RE-TEST
REPAIR
OR REPLACE
FUSES
CHECK
VOM
FUSES
TEST 6 - WIRE
CONTINUITY
GOOD
TEST 7 -
FIELD BOOST
BAD
GOOD
REPLACE
VOLTAGE
REGULATOR
BAD
REPAIR
OR
REPLACE
THEN
RETEST
TEST 8 -TEST
S TATO R
BAD
REPAIR
OR
REPLACE
GOOD
PERFORM STATOR
INSULATION
RESISTANCE TEST
BAD
TEST 9 -
CHECK ROTOR
CIRCUIT
REPAIR
OR
REPLACE
BAD
BAD
GOOD
BAD
BAD
PERFORM ROTOR
RESISTANCE TEST
TEST 10 -
CHECK BRUSHES & SLIP RINGS
GOOD
TEST 11 -
TEST ROTOR
ASSEMBLY
GOOD
INSULATION
Loading...
+ 85 hidden pages