Gtec ZS110 User Manual

USER MANUAL
On-Line UPS
Model ZS110
6000VA-10000VA
Uninterruptible Power Supply System
1
2
Contents
1Brief introduction.................................................................1-5
1.1 System and model description....................................................1
1.2 Description of commonly used symbols....................................2
1.3 Appearance...............................................................................2-4
1.4 Product specification and performance......................................5
2. Safety Instruction...................................................................6
3. Installation........................................................................7-14
3.1 Unpacking and inspection...........................................................7
3.2 Input and output power wiring and protective earth ground
installation..............................................................................7-9
3.3 Operating procedure for connecting the long backup time
model UPS with the external battery..................................9-10
3.4 Parallel operation.................................................................10-13
4. Operation and Operating mode.......................................14-20
4.1 Operation..............................................................................14-15
4.2 Operating mode....................................................................15-20
5. Battery maintenance.............................................................21
6. Notes for battery disposal and battery replacement..............22
7. Troubleshooting..............................................................23-24
Appendix 1 Description of Display panel.............................25-26
Appendix2 Indicator and alarm..........................................27-28
8. Chapter Operation (LCD model) ....................................29-39
8.1 Operation Display Panel...............................................................29
8.2 Operation Mode.......................................................................30-34
8.3 Operating Instructions.............................................................34-35
8.4 Checking UPS function.................................................................36
8.5 Troubleshooting.......................................................................37-39
3
1. Brief introduction
1.1 System and model description
The On-Line-Series is an uninterruptible power supply incorporating double-converter technology. It provides perfect protection specifically for strict load. The double-converter principle eliminates all mains power disturbances. A rectifier converts the alternating current from the socket outlet to direct current. This direct current charges the batteries and powers the inverter. In the event of power failure, the maintenance-free batteries power the inverter. Thus the inverter generates a sine wave AC power, which permanently supplies the loads.
Designed with the proven on-line, double conversion architecture, this series of UPS offers the greatest degree of availability in power protection and provides continuous high-quality AC power to connect strict load, especially for the basic equipments in some areas as: finance, communication, government, traffic, manufacture, education and so on.
This manual is applicable to the following models:
Type Model Input Battery
6KVA 6K Single phase + N inbuilt
Standard
10KVA 10K Single phase + N inbuilt
6KVAS 6KS Single phase + N External battery bank 10KVAS 10KS Single phase + N External battery bank 10KVAS 3C10KS Three-phase + N + PE External battery bank 12KVAS 3C12KS Three-phase + N + PE External battery bank 15KVAS 3C15KS Three-phase + N + PE External battery bank
Long
back up
time
20KVAS 3C20KS Three-phase + N + PE External battery bank
4
1.2 Description of commonly used symbols
The following symbols will be used in this manual and may appear during the course of your practical applications. Therefore, all users should be familiar with them and understand their meanings.
1.3 Appearance
BACK VIEW of 6K
Notation and Explanation
Notation
Explanation Notation
Explanation
Alert you to pay special
attention
Protective ground
Caution of high voltage
Alarm silence
Turn on the UPS
Overload indication
Turn off the UPS
Battery check
Idle or shut down the UPS
Recyclable
Alternating current source (AC)
Do not dispose with
ordinary trash
Direct current source (DC)
Battery
5
BACK VIEW of 6K-KS
BACK VIEW of 10K
6
BACK VIEW of 10K-KS
BACK VIEW of 3C10K-KS3C12K-KS3C15K-KS3C20K-KS
7
1.4 Product specification and performance
General specification
Inputfull load
Output
Power Rating Model
Frequency
(Hz)
Voltage Current Voltage Current
Dimensions
(W*L*H)mm
Weight
(kg)
6KVA/4.8KW 6K 50/60 (176-276)VAC 31max 220V/230V 27A
260X560X717 68
6KVA/4.8KW 6KS 50/60 (176-276)VAC 31max 220V/230V 27A
260x533x501 17.5
10KVA/8KW 10K 50/60 (176-276)VAC 50max 220V/230V 45A
260X560X717 70
10KVA/8KW 10KS 50/60 (176-276)VAC 50max 220V/230V 45A
260x533x501 19.5
10KVA/8KW 3C10KS 50/60 (304-478)VAC 50max 220V/230V 45A
260X560X717
12KVA/9.6KW
3C12KS 50/60 (304-478)VAC 60 max 220V/230V 54A
260X560X717
15KVA/12KW 3C15KS 50/60 (304-478)VAC 75 max 220V/230V 68A
260X560X717
20KVA/15KW 3C20KS 50/60 (304-478)VAC 100 max 220V/230V 91A
260X560X717
Electrical performance
INPUT
Model Voltage Frequency Power Factor
6K(S)/S10K(S)
Single-phase220VAC
230VAC
50/60Hz±5%
adjustable
>0.99(Full load)
3C10KS/3C12KS/3C15KS
/3C20KS
Three-phase380VAC/220 VAC380VAC/230VAC
50/60Hz±5%
adjustable
>0.95(Full load)
Output
Voltage
regulation
Power
factor
Frequency tolerance Distortion Overload capacity
Current
crest ratio
±1% 0.8lag
Synchronized
46-
54Hz in Line mode
(AC mode) ±1% of
normal frequency in
Battery mode
THD<2%
Full load
(Linear load)
105%-
125%load transfers
to bypass mode after 1
minutes >130% load
transfers to bypass mode
after 30second
3:1
maximum
Operating environment
Temperature Humidity Altitude Storage temperature
0°-40° <95% <1000m 0°-40°
Note: If the UPS is installed or used in a place where the altitude is above
than 1000m, the output power must be decrease in use, please refer to the following:
Altitude(M)
1000 1500 2000 2500 3000 3500 4000 4500 5000
Load 100% 95% 91% 86% 82% 78% 74% 70% 67%
8
2. Safety Instruction
Even if the interruptible Power System (UPS) is not connected to utility power, the output socket of the UPS may still present 220V/230V output voltage.
If it is necessary to replace the external battery cord or power cord, please purchase the original material from the service center or distributor of our company so as to avoid overheat or spark resulting in fire due to insufficient capacity.
Do not let battery or batteries get close to any heating source and do not incinerate battery or batteries, they may explode.
Do not open or mutilate the battery or batteries, released electrolyte is highly poisonous and harmful to the skin and eyes.
Do not short the positive and negative of battery electrode. Otherwise, it may cause electric shock or fire.
To avoid the risk of being shocked, please do not attempt to open the case of the UPS.
A battery can present a risk of electric shock and high short circuit
current.
Do not plug household appliance such as hair dryers to UPS.
9
3. Installation
3.1 Unpacking and inspection
1) Unpack the packaging and check the package contents. The shipping package contains:
A UPS
A user manual
A communication cable
2) Inspect the appearance of the UPS to see if there is any damage during transportation. Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or lacking of some parts.
3.2 Input and output power wiring and protective earth ground
installation
3.2.1. Notes for installation
1) The UPS must be installed in a location with good ventilation, far away from water, inflammable gas and corrosive agents.
2) The UPS should not be tilted. The air inlet port at the lower part of the front panel and the fan outlet port on the rear panel should not be blocked so as to ensure good ventilation (Allow at least 0.5m of space on each side).
3) In case if the UPS is unpacked, installed and used at very low temperatures, condensation of water drops may appear. It is necessary to wait until the UPS is fully dried inside out before proceeding to installation and use. Otherwise, there may be a risk of electric shock.
3.2.2. Installation
Installation and wiring must be performed in accordance with the local electric code and the following instructions by professional personnel. For safety, please cut off the mains power breaker before installation. The battery breaker also needs to be cut off if it is a long backup time model.
1) Open the terminal block cover located on the rear panel of the UPS (please refer to the appearance diagram).
2) For 6K (S) UPS, it is recommended to select the UL1015 10AWG (6mm2) wire or other insulated wire which complies with AWG Standard for the UPS input and output wirings.
10
3) For 10K (S)/3C10KS UPS, it is recommended to select the UL1015 8AWG (10mm2) wire or other insulated wire which complies with AWG Standard for the UPS input and output wirings.
4) For 3C12KS/3C15KS/3C20KS UPS, it is recommended to select the UL1015 6AWG (25mm2) wire or other insulated wire which complies with AWG Standard for the UPS input and output wirings.
Note: Do not use the wall receptacle as the input power source for the
UPS, as its rated current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed. (Please refer to section 1.4)
5) Connect the input and output wires to the corresponding input and output terminals according to the following diagram.
Note: you must make sure that the input and output wires and the input and
output terminals are connected tightly.
6) The protective earth ground wire refers to the wire connection between the equipment which consumes electro-equipment and the ground wire. The wire diameter of protective earth ground wire should be at least as above mentioned for each model and green wire or green wire with yellow ribbon wire is used.
7) After having completed the installation, make sure the wiring is correct.
8) Please install the leak current protective breaker at the output power distribution panel of the UPS if necessary.
9) To connect the load with the UPS, please turn off all the loads first, then perform the connection and finally turn on the loads one by one.
10) No matter the UPS is connected to the utility power or not, the output of the UPS may have electricity. The parts inside the unit may still have hazardous voltage after turning off the UPS. To make the UPS have no output, power off the UPS, and then disconnect the utility power supply.
11) Suggest charging the batteries for 8 hours before use. After connection, turn the input breaker in the “ON” position, the UPS will charge the batteries automatically. You can also use the UPS immediately without charging the batteries first, but the backup time may be less than the standard value.
11
12) If it is necessary to connect the inductance load such as a monitor or a laser printer to the UPS, the start-up power should be used for calculating the capacity of the UPS, as its start-up power consumption is too big when it is started.
Input and Output Terminal Block wiring diagram of 6KS)、10K(S)
Input and Output Terminal Block wiring diagram of
3C10KS/3C12KS/3C15KS/3C20KS
3.3 Operating procedure for connecting the long backup time model UPS with the external battery
3.3.1. The nominal DC voltage of external battery pack is 192VDC. Each
battery pack consists of 16 pieces of 12V”maintenance-free” batteries in series. To achieve longer backup time, it is possible to connect multi-battery packs, but the principle of “same voltage, same type” should be strictly followed.
3.3.2.For 6KS/10KS/3C10KS/3C12KS/3C15KS/3C20KS,The procedure of
installing battery bank should be complied with strictly. Otherwise you may encounter the hazardous of electric shock.
12
1) A DC breaker must be connected between the battery pack and the
UPS. The capacity of breaker must be not less than the data specified in the general specification as follow.
Model 6K 6KS 10K 10KS 3C10KS 3C12KS 3C15KS 3C20KS
Battery
voltage
192VDC 192VDC 192VDC 192VDC
240VDC 240VDC 240VDC 240VDC
Battery
current
34A max 34A max 56A max 56A max
46A max. 56A max. 70A max. 102A max.
Note: 240VDC battery voltage can be choose for 6K(S)/10K(S).
2) Set the battery pack breaker in “OFF” position and connect the 16 pieces of batteries in series.
3.3.3. To complete the connection by plugging the connector of the external battery cable into the external battery socket of the UPS. Do not attempt to connect any loads to the UPS now. You should connect the input power wire to the right position first. And then set the breaker of the battery pack in the “ON” position. After that set the input breaker in the “ON” position. The UPS begins to charge the battery packs at the time.
3.4 Parallel operation
3.4.1. Brief introduction of the redundancy
N+X is currently the most reliable power supply structure. N represents the minimum UPS number that the total load needs; X represents the redundant UPS number, i.e. the fault UPS number that the system can handle simultaneously. The bigger the X is, the higher reliability of the power system is. For occasions where reliability is highly required, N+X is the optimal mode. As long as the UPS is equipped with parallel cables, up to 3 of them can be connected in parallel to realize output power sharing and power redundancy.
3.4.2. Parallel installation
1) Users need to opt a standard 25-pin communication cable, which should have 25 cores, corresponding stitches and shield, as the UPS parallel cable. The length of the parallel cable is appropriate to be less than 3 m.
2) Strictly follow the stand-alone wiring requirement to perform the input wiring of each UPS.
13
3) Connect the output wires of each UPS to an output breaker panel first, and then connect the wiring to the load via the breaker panel.
4) The parallel UPS must be equipped with battery individually.
5) Please refer the figure followed to see the wiring of parallel operation. The capacity of the breaker must be not less than the specification as follow.
Model No. Capacity of breaker
6K(S) 40A/250VAC
10K(S)/3C10KS 60A/250VAC
3C15KS/3C20KS 100A/250VAC
*The requirement of the output wiring is as follows:
When the distance between the UPSs in parallel and the breaker panel is less than 20 meters, the difference between the wires of input & output of the UPSs is required to be less than 20%;
When the distance between the UPSs in parallel and the breaker panel is greater than 20 meters, the difference between the wires of input & output of the UPSs is required to be less than 10%.
3.4.3. Operation and maintenance
1) To perform the general operation, follow the stand-alone operating
requirement;
2) Start up: The units transfer to INV mode simultaneously as they start up sequentially in utility power mode; Shutdown: the units shut down sequentially in INV mode. When the last one completes the shutdown action, each unit will shut down the inverter simultaneously and transfer to bypass mode.
3) To perform the maintenance, follow the stand-alone requirement.
14
15
16
4. Operation and Operating mode
It is easy to operate the equipment, with no previous training. You just need to read through this manual and operate according to the instructions in it. The meaning of the LED indicators, please refer to the appendix 1 “Display panel”.
4.1 Operation
4.1.1. Turn on the UPS with utility power supplied
1) After you make sure that the power supply connection is correct, set the input breaker in the “ON” position first. At this time the fan rotates and the UPS supplies power to the load via the bypass. The UPS operates in Bypass mode.
2) To power on the UPS by simply pressing the “ON” button continuously for more than 1 second.
3) When being powered on, the UPS will perform self-diagnosis, with the load/battery level LEDs turned on and then off one after another in ascending order. A few seconds later, the INV LED is turned on, the UPS is already running in Utility Power mode. If the utility power is abnormal, the UPS will operate in battery mode without output interruption of the UPS.
4.1.2. Turn on the UPS with no utility power supplied
1) Press the “ON” button continuously for more than 1 second to power on the UPS. For long back up time model (“L” model), please make sure that the battery breaker is in “ON” position.
2) During the course of starting up, the UPS has the same action as if it is connected to utility power except that the utility power LED is not turned on and the battery LED is turned on instead.
4.1.3. Turn off the UPS with utility power supplied
1) Press the “OFF” button continuously for more than 1 second to turn off the inverter of the UPS immediately.
2) When being powered off, the UPS will perform self-diagnosis, the Load/Battery level LEDs will be turned on and then off one after another in ascending order, then the INV LED will be turned off and Bypass
17
LED will be turned on. The UPS is working in Bypass mode.
3) Upon completion of the above to turn it off, output of electric current of the UPS is still present. In order to cut off the output from the UPS, simply cut off the utility power supply and the UPS will perform self-diagnosis, finally not any display is shown on the display panel and no voltage output is available from the UPS output.
4.1.4. Turn off the UPS with no utility power supplied
1) Press the “OFF” button continuously for more than 1 second to power off the UPS.
2) When being powered off, the UPS will perform self-diagnosis, the
Load/Battery level LEDs will be turned on and then off one after another in ascending order. Finally not any display is shown on the display panel and no voltage is available from the UPS output.
Suggestions: Please turn off the connected loads before turning on the UPS and turn on the loads one by one after the UPS is working in INV mode. Turn off all of the connected loads before turning off the UPS.
4.2 Operating mode
4.2.1. Normal power mode
In the normal mode, the display on the front panel is shown in the following diagram. The utility power indicator and the Inverter indicator are turn on. The load/battery capacity indicator will be turned on in accordance with the load capacity connected.
1. If the utility power indicator blinks, it indicates that there are problems with reversed polarity (L, N) of site wiring or disconnect with ground that may result in shock hazard. UPS is still working in normal mode. If the battery indicator is turn on at the same time, it shows that the voltage or frequency of the utility power is out of the normal input range of the UPS. The UPS works in battery mode.
18
Figure 4-1 Normal Mode
2. If output overloaded, the load level indicators will be turned on and alarm will beep every second. You should get rid of some unnecessary loads one by one to decrease the loads connected to the UPS less than 95% capacity of the UPS.
3. If the battery indicator blinks, it indicates that no battery is connected to the UPS or battery voltage is too low. You should check if battery is properly connected to the UPS, and press function button more than 5 seconds to start the battery self-diagnosis. If the connection between battery and UPS is confirmed without any problem, it may be due to the defect or aging of the battery, please refer to the “troubleshooting” in chapter 7 to solve the problem accordingly.
Note:Connection to the power generator should be made according to the
following steps:
l Activate the power generator and wait until the operation is stable
before connecting the output of the power generator to the UPS (be sure that the UPS is in idle mode). Then, turn on the UPS according to the startup procedure. After the UPS is turned on, the loads are connected one by one.
l It recommended that the capacity of the AC generator chosen should
double that of the UPS.
4.2.2 Battery mode
In battery mode the display on the front panel is shown in the following diagram. The battery indicator and the inverter indicator are turn on. If the
19
utility power indicator blinks at the same time, it shows that the utility power is abnormal. The load/battery capacity indicators will be turn on in accordance with the battery capacity. Please note that the load/battery capacity indicator in normal mode will indicate the battery capacity in battery mode.
1. When the ups is running in battery mode, the alarm will beep every 4 seconds. If the “Function” key is pressed for more than 5 seconds, the alarm will not beep (silence function). Press the “Function” key more than 5 seconds again to resume the alarm function.
Figure 4-2 Battery Mode
2. When the battery capacity decreases, the number of load/battery capacity indicators turned on will decrease. If the battery voltage drops to the pre-alarm level (capable of maintaining the backup time for more than 2 minutes), the alarm will beep every second to remind the user of insufficient battery capacity.
4.2.3 Bypass mode
When operating in bypass mode set up through UPSilon software, the display on the front panel is show in the following diagram. The utility power indicator and the bypass indicator are turn on. The load/battery capacity indicator will be turned on in accordance with the load capacity connected.
1. If the utility power indicator blinks, it shows that the voltage or frequency of the utility power is out of the input range of the UPS or there are problems with reversed polarity (L/N) of site wiring or
20
disconnect to the ground for protection.
2. When operating in bypass mode, the UPS beeps every 2 minutes, If the “Function” key is pressed for more than 5 seconds, the alarm will not beepsilence function. Press the “Function” key more than 5 seconds again to resume the alarm function.
Notes: When operating in bypass mode, the backup function of the UPS is not available and the power used by the load is directly from the utility power via internal EMI filter.
Figure 4-3 Bypass Mode
4.2.4. Abnormality mode
In case the fault LED is turned on when the UPS is in use, it shows that the UPS is operating in abnormal mode. Please refer to the troubleshooting in section 7 for details.
4.2.5. Backup time for the standard model
The backup time of the long backup time model is dependent on the external battery pack capacity and the load level as well as other factors. The backup time of standard model may vary from different models and load level. Please refer to the following:
21
4.2.6. Internet Communication
This series is equipped with an intelligent slot for Web power (optional accessory) or other optional card to achieve remote management of the UPS. Please contact your local distributor for further information.
4.2.7. Description of communication interface
1) The standard RS232 port is applicable to communicate with computer. Description and pin assignment of RS232 Baud rate: 2400bps Data bit: 8 bit Ending bit: 1bit Parity bit: None DB-9 pin assignment:
RS232 Interface
22
Pin number Function description I/O
3 Rxd Input 2 Txd Output 5 GND Ground
2) User enables to monitor and manage the UPS through installed the
AS400 card (optional). PIN1: UPS failure (normally open, active close) PIN2: summary alarm PIN3: ground PIN4: Remote shutdown PIN5: Common PIN6: Bypass active (relay close) PIN7: Battery low PIN8: UPS On (relay close) PIN9: Utility Power failure (normally open, active close)
AS400 Interface
23
5. Battery maintenance
This series UPS only requires minimal maintenance. The battery used for standard models is valve regulated sealed lead-acid maintenance free battery. These models require minimal repairs. The only requirement is to charge the UPS regularly in order to maximize the expected life of the battery. When being connected to the utility power, whether the UPS is turned on or not, the UPS keeps charging the batteries and also offers the protective function of overcharging and over discharging.
The UPS should be charged once every 4 to 6 months if it has not been used for a long time. In the regions of hot climates, the battery should be charged and discharged every 2 months. The standard charging time should be at least 12 hours.
Under normal conditions, the battery life lasts 3 to 5 years. In case if the
battery is found not in good condition, earlier replacement should be made. Battery replace event should be performed by qualified personnel.
Replace batteries with the same number and same type of batteries.
Keep the ambient temperature between 15 and 25
Do not replace the battery individually. All the batteries should be
replaced at the same time following the instructions of the battery supplier.
Normally, the batteries should be charged and discharged once every 4 to 6 months. Charging should begin after the UPS shuts down automatically in the course of discharging, the standard charging time for the standard UPS should be at least 12 hours. Discharge the battery with the load more than 50%.
24
6. Notes for battery disposal and battery replacement
1) Before disposing batteries, remove conductive articles such as necklace, wrist watches and rings.
2) If it is necessary to replace any connection cables, please purchase the original materials from the authorized distributors or service centers, so as to avoid overheat or spark resulting in fire due to insufficient capacity.
3) Do not dispose of batteries or battery packs in a fire, they may explode.
4) Do not open or mutilate batteries, released electrolyte is highly poisonous and harmful to the skin and eyes.
5) Do not short the positive and negative electrodes of the battery, otherwise, it may result in electric shock or fire.
6) Make sure that there is no voltage before touching the batteries. The battery circuit is not isolated from the input potential circuit. There may be hazardous voltage between the battery terminals and the ground.
7) Even though the input breaker is disconnected, the components inside the UPS are still connected with the batteries, and there are potential hazardous voltages. Therefore, before any maintenance and repairs work is carried out, switch off the breaker of the battery pack or disconnect the jumper wire of connecting between the batteries.
8) Batteries contain hazardous voltage and current. Battery maintenance such as the battery replacement must be carried out by qualified personnel who are knowledgeable about batteries. No other persons should handle the batteries.
25
7.Troubleshooting
Problem Possible cause Solution
The 1# Fault LED
and the 6 #LED are
turned on, the buzzer
beeps continuously
The UPS shutdown due to internal overheat
Make sure the UPS is not
overloaded; the air vents are not
blocked and the ambient
temperature is not too high. Wait
for 10 minutes for the UPS to cool
down before turning on again. If
failed, please contact the distributor
or service center.
The 1# Fault LED
and the 2# and5 #
LED are turned on,
and the buzzer beeps
continuously
The UPS output
is Short circuited.
Turn off the UPS. Remove all the
loads. Ensure that the load is not failed or the UPS has no internal
faults before turning it on again. If
failed, please contact the
distributor or service center.
The 1# Fault LED
and the 4# LED are
turned on, the UPS
beeps continuously
The UPS shuts
down due to its
internal fault.
Please contact the distributor or
service center.
The 1# Fault LED
and the 5# LED are
turned on, the UPS
beeps continuously
The UPS shuts down due to its
internal fault.
Please contact the distributor or
service center.
The utility power
LED flashes
The voltage or
frequency of the
utility power is
out of the input
range of the
UPS.
The UPS is running in battery
mode. To save your data and close
the application program. Make
sure the utility power is within the
input voltage or frequency range
permitted by the UPS.
The 1# Fault LED
and the 2# LED are
turned on, the UPS
beeps continuously
The UPS is overloaded or the load equipment is
faulty
Check the loads and remove all no critical equipment. Recalculate the load power and reduce the number
of loads connected to the UPS.
Check that the loads are not failed.
The 1# Fault LED
and the battery LED
are turned on, the
buzzer beeps every
second
The charger of
the UPS is
defective.
Please contact the distributor or
service center.
26
7.Troubleshooting
Problem Possible cause Solution
Battery LED flashes Battery low
Check the battery. If the
battery is damaged, replace
the battery immediately and
ensure that the battery breaker
is in “ON” position.
The utility power is
normal, but the UPS
can not turn in line
mode
AC input breaker in
“OFF” position
Set the input breaker in “ON”
position
Battery not yet been
fully charged
Keep UPS connected to utility
power persistently for more
than 10 hours to recharge the
batteries again.
UPS overloaded
Check the loads and remove
the non-critical equipment.
Battery discharging
time diminishes
Battery aged
Replace the batteries. Please
contact the distributor to
obtain the parts and
replacement service.
The “ON” button is
pressed too briefly
Press the “ON” button for
more than 1 second.
The UPS is not
connected to the
battery or the battery
pack voltage is too low.
Check the battery or recharge
the battery.
The UPS cannot
power on after
pressing the “ON”
button
UPS internal fault
Please connect the distributor
or service center.
When you contact the service center, please provide the following information:
Model No. and the serial No. of the UPS;
The date when the problem arose;
Complete description of the problem, including the LED display, alarm
warning, power condition and load capacity. If your UPS is a long backup time model, you may also provide the battery information.
27
Appendix 1 Description of Display panel
1. ON button: Pressing the ON/OFF button more than 1 second, the UPS system is turned on.
2. OFF button: By pressing this button more than 1 second turns off the UPS system whenever the UPS run under the normal mode/battery mode.
3. Function button The Function button provides the following functions:
1) Battery self- diagnosis: When the UPS ran in normal mode, pressing this button more than 5 seconds (buzzer beeps twice) can start the battery self-diagnosis.
2) Silence function in battery/bypass mode In battery/bypass mode, when the buzzer beeps, pressing and holding the function button for more than 5 seconds (buzzer beeps one times) can silence the buzzer. Press the button for more than 5 seconds (buzzer beeps twice) again to resume the alarm function.
Note: The alarm silencing function of the Function button is valid only in
battery mode, and invalid for any other UPS alarm.
4. LED indicators The LEDs contains Fault indicator, Load/battery capacity indicator, Bypass indicator, utility power indicator, Inverter indicator, Battery indicator.
28
Appendix 1 Description of Display panel
Table Appendix 1 Description of indicators
No. Color Indicator Description
1# Red Fault indicator
When the indicator on, it shows that
the UPS in abnormal condition. 2# Orange Load/battery capacity indicator 3# Green Load/battery capacity indicator 4# Green Load/battery capacity indicator 5# Green Load/battery capacity indicator
6# Green Load/battery capacity indicator
Show the capacity of load/battery:
1.Indicate the percentage of the load capacity in normal mode and bypass mode
2. Indicate the battery capacity level in battery mode.
7# Orange Bypass indicator
When the indicator on, it shows that
the loading current is supplied from the
utility power directly
8# Green Utility power indicator
When the indicator on, it shows that
the utility power is normal.
9# Green Inverter indicator
When the indicator on, it shows that
the load current is supplied from utility
power or battery via the inverter.
10#
Orange
Battery indicator
When the indicator on, it shows that
the load current is supplied from
battery via the inverter.
29
Appendix2 Indicator and alarm
LED indicators
No.
Operating status
1# 2# 3# 4# 5# 6# 7# 8# 9# 10
#
Audible alarm
1 0%--25%Load
● ●
none
2 26%--50% Load
● ●
● ●
none
3 51%--75% Load
● ●
● ●
none
4
76%--100%
Load
● ● ●
● ●
none
5
Normal
mode
101%--105%
Load
● ● ●
● ●
none
6
0~20%
battery capacity
Beep once
every sec
7
21%~40%
battery capacity
Beep once
every 4 sec.
8
41%~60%
battery capacity
Beep once
every 4 sec.
9
61%~80%
battery capacity
● ●
Beep once
every 4 sec.
10
Battery
mode
81%~100%
battery capacity
● ● ●
Beep once
every 4 sec.
11 Bypass mode
↑ ↑ ↑ ↑
● ● ●
Beep once
every 2 min.
12
Overloaded in Normal
mode
● ● ●
● ●
Beep twice
every sec
13
Overloaded in bypass
mode
● ● ● ● ●
Beep twice
every sec
14 Utility power abnormal
↑ ↑ ↑ ↑
none
15 Bypass mode abnormal
↑ ↑ ↑
none
16
Overload in Battery mode,
pre-alarm
↑ ↑
↑ ↑
↑ ● ●
Beep twice
every sec
17 Overload fault
● ● ↑
Sustained
beep
18
Overheating fault
● ●
↑ ↑
Sustained
beep
19 Inverter fault
● ●
Sustained
beep
20 Output short circuit
● ● ● ↑
Sustained
beep
30
LED indicators
No.
Operating status
1# 2# 3# 4# 5# 6# 7# 8# 9# 10
#
Audible alarm
21
BUS voltage fault
Sustained
beep
22 Charger or battery fault
● ↑ ↑
Beep once
every sec
23 Fan failure
● ● ●
↑ ↑
Beep once
every sec
24 Parallel fault
● ● ●
↑ ↑
Sustained
beep
25 ID repetition
● ●
Sustained
beep
27
BAT voltage low
↑ ↑
↑ ↑ ↑ ↑ ↑ ↑
Beep once
every sec
28
Over Charger
Sustained
beep
29
Reversed polarity (L, N) of
input wiring or
disconnected with ground.
↑ ↑ ↑ ● ↑
Beep once
every sec
30
BAT fault
Sustained
beep
31
EPO mode
↑ ↑
↑ ↑ ↑ ↑
Beep once
every sec
32
Bus short
Sustained
beep
33 Negtive power fault
● ● ● ● ↑ ↑
Sustained
beep
34
React Power Fault
● ● ● ● ↑ ↑
Sustained
beep
35
Power Fault
● ● ● ● ● ↑
Sustained
beep
36
Inv Rly Stick Fault
● ● ● ↑ ↑
Sustained
beep
37
Inv Rly Open Fault
● ● ● ↑ ↑
Sustained
beep
38
Line SCR Fault
● ● ↑ ↑
Sustained
beep
39 Line In Fuse Open Fault
● ●
● ↑ ↑
Sustained
beep
LED indictor description: O n :Flash :Depending on other conditions
31
8 Chapter Operation (LCD model)
8.1 Operation Display Panel
1. ON button: Pressing the ON button more than 1 second (buzzer beeps once), the UPS system is turned on.
2. OFF button: By pressing this button more than 1 second (buzzer beeps once) turns off the UPS system whenever the UPS run under the normal mode/battery mode.
3. Function button The Function button provides the following functions: a) Battery self- diagnosis: When the UPS ran in normal mode, pressing this
button more than 5 seconds (buzzer beeps twice) can start the battery self-diagnosis.
b) Silence function in battery/bypass mode
In battery/bypass mode, when the buzzer beeps, pressing and holding the function button for more than 5 seconds (buzzer beeps two times) can silence the buzzer. Press the button for more than 5 seconds (buzzer beeps twice) again to resume the alarm function
c) LCD display screen switch
Pressing the function button for more than 1 seconds (buzzer beeps once) to switch LCD display screen
4. LED indicators The LED indicators contains Fault indicator, Bypass indicator, utility power indicator, Inverter indicator, Battery indicator. The definition of each indicator is the same as LED panel (refer to table Appendix 1).
32
8.2 Operation Mode
UPS Operation Mode contains normal mode, battery mode and bypass mode. Under the three modes, the page showing output voltage and output frequency is the main display page. If users need more information about UPS, Pressing the function button can initiate display screen switch. If the current page is not the main page, UPS will auto switch back the main page after 30 seconds. In order to extend the LCD usage life, the backlight will turn off after 1 minute without any switch operation. At this point, Users just need to touch any button briefly, the backlight will be turn on.
8.2.1 Normal mode When operating in the normal mode, the display of main page on the front
panel is shown as the figure 8-2. The utility power indicator and the Inverter indicator are turn on. Load information area shows load value, and the battery level area indicates dynamically when the battery is not full charged (the battery level icons lit one after another circularly). When the battery is full charged, all the level icons are turn on.
1) If the utility power indicator blinks, it indicates that there are problems with reversed polarity (L, N) of site wiring or disconnect with ground. UPS is still working in normal mode. If the battery indicator is turn on at the same time, it shows that the voltage or frequency of the utility power is out of the normal input range of the UPS. The UPS works in battery mode.
Figure 8-2 Normal Mode
33
2) If load is more than 105 percent, the buzzer beeps twice every second, meanwhile, the warning icon blinks every second too, reminding that you have been overloaded. You should get rid of some unnecessary loads one by one to decrease the loads until the alarm clear
3) If the battery indicator blinks, it indicates that no battery is connected to the UPS or battery voltage is too low. You should check if battery is properly connected to the UPS, and press function button more than 5 seconds to start the battery self-diagnosis. If the connection between battery and UPS is confirmed without any problem, it may be due to the defect or aging of the battery, please refer to the “troubleshooting” in chapter 7 to solve the problem accordingly.
4) The other four display pages are load percent page, actual load page, input information page and the maximum temperature page.
Note:Connection to the power generator should be made according to the
following steps:
l Activate the power generator and wait until the operation is stable
before connecting the output of the power generator to the UPS (be sure that the UPS is in idle mode). Then, turn on the UPS according to the startup procedure. After the UPS is turned on, the loads are connected one by one.
l It recommended that the capacity of the AC generator chosen should
double that of the UPS.
8.2.2 Battery Mode
When operating in the normal mode, the display of main page on the front panel is shown as the figure 8-3. The battery indicator and the Inverter indicator are turn on. If the utility power indicator blinks at the same time, it shows that the utility power is abnormal. Load information area shows load value, and bat level area shows current battery capacity.
1) When the UPS is running in battery mode, the alarm will beep every 4
seconds. If the “Function” key is pressed for more than 5 seconds, the alarm will not beep silence function). Press the “Function” key more than 5 seconds again to resume the alarm function.
34
Figure 8-3 Battery Mode
2) When the battery capacity decreases, the number of load/battery capacity indicators turned on will decrease. If the battery voltage drops to the pre-alarm level (capable of maintaining the backup time for more than 2 minutes), the alarm will beep every second to remind the user of insufficient battery capacity.
3) The other four display pages are load percent page, actual load page, battery information page and the maximum temperature page.
8.2.3 Bypass Mode
When operating in bypass mode set up through UPSilon software, the display on the front panel is shown as the figure 8-4, the utility power indicator and the bypass indicator are turn on. The load/battery capacity indicator will be turned on in accordance with the load capacity connected. Load information area shows load value, and the battery level area indicates dynamically when the battery is not full charged (the battery level icons lit one after another circularly). When the battery is full charged, all the level icons are turn on.
1) When operating in bypass mode, the UPS beeps every 2 minutes. If the
“Function” key is pressed for more than 5 seconds, the alarm will not beep (silence function). Press the “Function” key more than 5 seconds again to resume the alarm function.
2) If the utility power indicator blinks, it shows that the voltage or
frequency of the utility power is out of the input range of the UPS or there are problems with reversed polarity (L/N) of site wiring or disconnect to the ground for protection.
35
3) The other four display pages are load percent page, actual load page, input information page and the maximum temperature page.
Notes: When operating in bypass mode, the backup function of the UPS is
not available and the power used by the load is directly from the utility power via internal EMI filter.
Figure 8-4 Bypass Mode
8.2.4 LCD indication of UPS alarm status and faults
In the event of an UPS fault, UPS enters fault operation mode, at this point, the fault icon turn on consistently, the buzzer beeps continuously and the data information area shows current fault code (refer to table 8.5-1), the display on the front panel is shown as the figure8-5.
Figure 8-5 Fault display
36
When a warning occurred, the fault icon blinks every second, and users can switch to the alarm display page shown as the figure 8-6 to check the warning code.
Figure 8-6 Alarm display
8.3 Operating Instructions
8.3.1 UPS ON/OFF Operation
Note: The battery is fully charged before delivery. However, storage and
transportation will inevitably cause some charge loss. Therefore, it is advisable to charge the battery for 10 hours before using it, so as to ensure adequate battery autonomy.
1. Turning on the UPS The operation of turning on the UPS contains: turning on with utility power and turning on without utility power.
1) Turning on with utility power: Connect the mains input to the UPS, press the ON button more than one second, UPS start to turn on. At this point, the LCD begins to conduct self-diagnosis (all the LCD indicators are turn on about 4 seconds). Seconds later, the UPS will begin to operate in Normal mode; meanwhile, the utility power indicator, inverter indicators will turn on. If the utility power is abnormal, the UPS will work in battery mode.
2) Turning on without utility power: With no mains input feed to the UPS, press the ON button more than one second, ups start to turn on, At this point, the LCD begins to conduct self-diagnosis (all the LCD indicators are turn on about 4 seconds). Seconds later, the battery indicator, inverter indicators will be turn on to
37
indicate that the UPS is working in battery mode.
2. Powering down the UPS The operation of powering down the UPS contains: turning off ups in normal mode, turning off ups in battery mode
1) Completely power down the UPS from Normal mode Hold and press the OFF button persistently for more than 1 second to power off the UPS. If it bas been set up to work in bypass mode by software, the bypass indicator will be turn on to indicate that the UPS is working in bypass mode. In order to cut off the output from the UPS, simply cut off the utility power supply. LCD begins to conduct self-diagnosis (all the LCD indicators are turn on about 4 seconds), seconds later, not any display is shown on the front panel and no output is available from the UPS outlets, system completely power down.
2) Completely power down the UPS from Battery mode Press the “OFF” button persistently for more than 1 second to power off the UPS. When being powered off, the LCD will start self-diagnosis (all the LCD indicators are turn on about 4 seconds), seconds later, not any display is shown on the front panel and no voltage output is available from the UPS outlets, system completely power down.
8.3.2 Conducting Battery self-diagnosis
In UPS operation, users can manually initiate battery self-diagnosis to check the battery conditions. There are two methods to initiate the battery self-diagnosis:
1. Through the function button In normal mode, press and hold the function for more than 5 seconds until the buzzer beeps twice. At this point the indicators (LED7~10) will blink cyclically, indicating the UPS has worked in battery mode and the battery self-diagnosis has started. The battery self-diagnosis will last for 5 seconds default. In the event of a battery fault during battery self-diagnosis, the UPS will transfer to normal mode automatically.
2. Through the monitor software Users can also initiate battery self-diagnosis through the background monitoring software.
38
8. 4Checking UPS function
Every time when conducting field maintenance, please check the regular function of the UPS, including:
1. Check the operation status of the UPS If the main voltage is within the specifications, the UPS should operate in normal mode; if the main voltage is abnormal, the UPS should operate in battery mode. In both cases, there should be no fault indication.
2. Check the transfer between the UPS operation modes Disconnect the main input to simulate a mains failure, the UPS should transfer to battery mode and operate normally; then recover the mains input, the UPS should transfer to normal mode and operate normally
3. Check the LED indicators of the UPS During the check processes stated above, check that the LED indication of the UPS agrees with the UPS operation mode.
39
8 Chapter Operation (LCD model)
8.5 Troubleshooting
In the event of an UPS fault, shoot the trouble according to Table8.5-1. If the fault still persists, please contact our customer service center.
Faults
Fault/
Warning
code
Fault icon Alarm
Possible
cause
Solution
F01
on
constantly
Beep
continuously
Internal
fault.
Please contact the distributor
or Service center
F02
on
constantly
Beep
continuously
Internal
fault.
Please contact the distributor
or Service center
F03
on
constantly
Beep
continuously
Internal
fault.
Please contact the distributor
or Service center
F05
on
constantly
Beep
continuously
Internal
fault.
Please contact the distributor
or Service center
F06
on
constantly
Beep
continuously
Internal
fault.
Please contact the distributor
or Service center
F07
on
constantly
Beep
continuously
Internal
fault.
Please contact the distributor
or Service center
F08
on
constantly
Beep
continuously
Internal
fault.
Please contact the distributor
or Service center
F10
on
constantly
Beep
continuously
The UPS output is
short
circuited
Turn off the UPS. Remove
all loads. Ensure that the loads are not failed or the UPS has no internal short before turn on it again. If
failed, please contact the
distributor or service center
F17
on
constantly
Beep
continuously
Internal
fault.
Please contact the distributor
or Service center
F21
on
constantly
Beep
continuously
Internal
fault.
Please contact the distributor
or Service center
F25
on
constantly
Beep
continuously
Internal
fault.
Please contact the distributor
or Service center
F26
on
constantly
Beep
continuously
Internal
fault.
Please contact the distributor
or Service center
F29
on
constantly
Beep
continuously
Internal
fault.
Please contact the distributor
or Service center
F32
on
constantly
Beep
continuously
parallel line
loss
Please check parallel line
connect or not.
40
8 Chapter Operation (LCD model)
Faults
Fault/
Warning
code
Fault icon Alarm
Possible
cause
Solution
F34
on
constantly
Beep
continuously
Internal
fault.
Please contact the
distributor or Service center
F35
on
constantly
Beep
continuously
Internal
fault.
Please contact the
distributor or Service center
F36
on
constantly
Beep
continuously
Internal
fault.
Please contact the
distributor or Service center
F42
on
constantly
Beep
continuously
Internal
fault.
Please contact the
distributor or Service center
F57
on
constantly
Beep
continuously
Battery fault
Please contact the
distributor or Service center
A04
Blink once
every
second
No beep Line fail
Please check line voltage
A05
Blink once
every
second
No beep
ground line
unconnected
Please check ground line
connect or not.
A07
Blink once
every
second
Beep once
every two
minutes
reversed
polarity
(L,N) of site
wiring
Please check the polarity of
the neutral wiring and the
line wiring
A08
Blink once
every
second
No beep By pass fail Please check line voltage
A10
Blink once
every
second
Beep once
every
second
Batteries
unconnected
Please check battery line
connect or not.
A11
Blink once
every
second
Beep once
every
second
Battery
voltage low
The UPS output will be cut
off, please switch to the
backup power.
A12
Blink once
every
second
Beep
continuously
Battery
overcharging
Please contact the
distributor or Service center
A14
Blink once
every
second
Beep twice
every
second
Overload
pre-warning
Reduce the member of
loads connected to the UPS.
41
Faults
Fault/
Warning
code
Fault icon Alarm
Possible
cause
Solution
A15
Blink once
every
second
Beep
continuously
Overload
fault
Reduce the member of
loads connected to the
UPS.
A16
Blink once
every
second
Beep once
every
second
Fan failure
Ensure that the fan is not
locked
A18
Blink once
every
second
Beep
continuously
Charger fail
Please contact the
distributor or Service
center
A20
Blink once
every
second
No beep
Start UPS
fail
Please check the battery
cables connect or not.
A33
Blink once
every
second
No beep
Parallel mode
fault
Please contact the
distributor or Service
center
A34
Blink once
every
second
No beep Eeprom fault
Please contact the
distributor or Service
center
A35
Blink once
every
second
Beep
continuously
ID repetition
Please contact the
distributor or Service
center
A53
Blink once
every
second
Beep
continuously
Unrecognized
UPS model
Please contact the
distributor or Service
center
A61
Blink once
every
second
Beep
continuously
Slave PSDR
fault
Please contact the
distributor or Service
center
Table 8.5-1 UPS troubleshooting of LCD panel indicator
When you contact the service center, please provide the following information:
Model No and Serial No of the UPS.
The date when the problem arose.
Complete description of the problem, including the panel display, alarm
warning, and power condition and the load capacity. If the UPS is a long backup time model, you may also provide the battery information.
Loading...