GSW POWER VENTED GAS FIRED WATER HEATER Installation And Operating Instructions Manual

POWER VENTED GAS FIRED WATER HEATER
WARNING:
Improper installation, adjustment, altera­tion, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional infor­mation, consult a qualified installer, ser­vice agency, or the gas utility.
INSTALLATION AND
OPERATING INSTRUCTIONS
Read these instructions thoroughly before starting
FOR YOUR SAFETY
• Installation and service must be per­formed by a qualified installer, service agency or the gas utility.
WARNING:
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, per­sonal injury or death.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
CSA 4.1a-2009
PART No. 324089-000 Rev. 00 (12-07)
TABLE OF CONTENTS
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
User Responsibilities 3 Qualified Installer Or Service Agency 3
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Safety Warning (Flammable Vapours) 4 Safety Warning (Scalding) 4 Safety Warning (Carbon Monoxide) 4 Relief Valve Requirements (T&P) 5 Flooding/Freezing/Fire Damage 5
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Unpacking the Water Heater 5 Location Requirements 5 In Earthquake Zones Closet Installations Floor Surfaces Clearances and Accessibility 6 Gas Supply 6 Gas Supply Pressure Gas Leak Testing Gas Operating Pressures Air Requirements 7 Appliances In Enclosures 7 Typical Installation 8 Replacement Parts And Deliming Products 9 Water Piping - Mixing Valve Usage 10 Mixing Valves Exhaust Venting 11 High Ambient Temperature Installations 11 Important Notes and Warnings Venting Terminations and Sizing Rodent Screens Calculating Equivalent Feet Venting Instructions Blower Exhaust Direction 15 Blower Assembly Installation 15 Vent Pipe Connection to Blower Condensate 17 Water Supply 17 Piping Installation Filling the Water Heater Closed System/Thermal Expansion Temperature and Pressure (T&P) Relief Valve 18 The Temperature and Pressure Relief Valve: The Discharge Line/Relief Drain Tube: Temperature-Pressure Relief Valve and Pipe
Insulation
Electrical Supply 19
SAFETY LOCKOUTS . . . . . . . . . . . . . . . . . . . . . . . .21
High Limit Controls 21 Thermostat/Water Temperature Blower Exhaust Gas Limit Switch Blower Air Pressure Switch 21 Flammable Vapour Sensor 21 Resettable Lockout 21 Water Heater Operation 21 Installation Checklist 22
OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . .23
Temperature Regulation 23 Mixing Valves 23 Lighting Instructions 24 Operating The Temperature Control System 25 Gas Control Valve/Thermostat
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Burner Flames 26 Operational Conditions 26 Condensation Water Heater Sounds Smoke/Odour Anode Rod/Water Odour “Air” In Hot-water Faucets
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Draining and Flushing 27 Routine Preventative Maintenance
(Homeowner/User) 27 Gas Control 27 Temperature and Pressure Relief Valve 27 Burner Operation and Inspection 28 Burner Cleaning Housekeeping 28 Anode Rod Inspection 28 To Remove the Anode Rod To Install the Anode Rod Venting System and Blower 30
COMBO HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
System Requirements 31 Installation 31
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . .32
ECO Reset 34 Ignition State and Timing 34 System Error Codes Honeywell Troubleshooting Chart -
User Control
REFERENCE PARTS . . . . . . . . . . . . . . . . . . . . . . . .36
Reference Parts Listing 36
LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . .38
RETAIN THESE INSTRUCTIONS IN A SAFE LOCATION FOR FUTURE REFERENCE
– 2 –
Your safety and the safety of others is very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING”.
DANGER
You can be killed or seriously injured if you don’t immediately follow instructions.
WARNING
You can be killed or seriously injured if you don’t follow instructions.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
INTRODUCTION
Thank you for purchasing a Flammable Vapour Ignition Resistant Power Vented Water Heater. This water heater is
designed to reduce the risk of fl ammable vapour related fi res by shutting the burner down before fl ammable vapours get into the water heater combustion chamber. This is achieved by the means of the fl ammable vapour sensor. Properly installed and maintained, it will provide years of trouble free service. This gas-fi red water heater has been developed to produce potable hot water for normal residential demands and may also be used in combination with space heating applications.
User Responsibilities
This manual has been prepared to acquaint you with the installation, operation and maintenance of your gas fi red water heater and provide important safety information in these areas. It is your responsibility to ensure that your water heater is properly installed and cared for.
FAILURE TO FOLLOW THE INSTRUCTIONS IN THIS MANUAL MAY RESULT IN SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE. THOROUGHLY READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE YOU ATTEMPT TO INSTALL, OPERATE OR MAINTAIN THIS HEATER.
Installation and service requires trade knowledge in the areas of plumbing, electricity, venting, air supply and gas supply. Only a qualifi ed service technician shall install or service this water heater.
Service to the Power Vent System should only be performed by a qualifi ed service technician.
The manufacturer of this water heater will not assume any liability for any property damage, personal injury or death resulting from improper sizing, installation or failure to comply with these instructions.
Qualified Installer Or Service Agency
Installation and service of this water heater requires ability equivalent to that of a Qualifi ed Agency in the fi eld involved. Installation skills such as plumbing, air supply, venting, gas supply and electrical supply are required in addition to electrical testing skills when performing service.
Do not discard this manual. You or future users of this water heater will need it for reference.
– 3 –
SAFETY
Safety Warning (Scalding)
DANGER
This water heater is design-certifi ed by CSA International as a Category III, water heater that takes its combustion and dilution air either from the installation area or from air ducted to the unit from the outside. In addition to the installation instructions found in this manual, the water heater must be installed in accordance with provincial codes and the latest edition of "Natural Gas and Propane Installation Code" CSA-B149.1.
Hot water produced by this appliance can cause severe burns due to scalding. The hazard is increased for young children, the aged or the disabled when water temperatures exceed 52°C (125°F). Use tempering valves, also known as mixing valves, in the hot-water system to reduce the risk of scalding at point-of-use such as lavatories, sinks and bathing facilities (see Figures 11 & 12). Such precautions must be followed when this heater is operated in combination with dishwashing or space heating applications.
Safety Warning (Flammable Vapours)
Safety Warning (Carbon Monoxide)
WARNING
FLAMMABLES
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death
Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance. Storage of or use of gasoline or other flammable vapours or liquids in the vicinity of this or any other appliance can result in serious injury or death.
There is a risk of property damage, personal injury or death from the by-products of combustion (e.g., fl ue gases), in using fuel-burning appliances such as water heaters. Areas that may not be suitable for water heater installation include those where fl ammable liquids, gasoline, solvents, adhesives etc. are stored. Also not suitable are areas where engine­driven equipment is stored, operated or repaired. Flammable vapour products should not be stored or used near the water heater or air intake. Due to the nature of air movement, ammable vapours can be carried some distance from the point of storage. Although the safety system is designed to reduce the risk of fl ammable vapour related fi res, the gas- red water heater igniter or burner fl ame can ignite these vapours causing a fl ashback, fi re or explosion, which may result in severe property damage, serious personal injury or death. If fl ammable liquids or vapours have spilled or leaked in the area of the water heater, leave the area immediately and call the fi re department from a neighbor's home. Do not attempt to clean the spill until all ignition sources have been extinguished.
– 4 –
Flammable Vapours
As with all fuel burning equipment, this heater requires an adequate supply of air for combustion. An insuffi cient air supply can result in poor combustion or the re-circulation of the fl ue gases. Such a condition may cause soot build- up and present a fi re hazard. Flow reversal of fl ue gases may cause an increase of carbon monoxide inside of the dwelling that could result in serious bodily harm or death from asphyxiation.
MAKE SURE THE FLOW OF COMBUSTION AIR IS NOT RESTRICTED.
WARNING
Breathing Hazard - Carbon Monoxide Gas
• Install vent system in accordance with codes.
• Do not operate water heater if flood damaged.
• For operation above 10,100’ (3,079 m), a high altitude orifice must be installed.
• Do not operate if soot buildup is present.
• Do not obstruct water heater air intake with insulating jacket.
• Do not obstruct blower air intake.
• Do not place chemical vapor emitting products near water heater.
• Gas and carbon monoxide detectors are available.
• No vent damper installation is compatible with this power vented water heater.
Breathing carbon monoxide can cause brain damage or death.
Always read and understand instruction manual.
Relief Valve Requirements (T&P)
All water heaters must be fi tted with a proper temperature and pressure relief valve. These valves must be certifi ed as meeting the requirements of the "Standard For Relief Valves For Hot Water Supply Systems, ANSI Z21.22/CSA 4.4".
Flooding/Freezing/Fire Damage
If this water heater has been exposed to ooding, freezing, re or any unusual condition, do not put it into operation until
it has been inspected and approved by a qualifi ed service technician. THESE CONDITIONS CAN RESULT IN UNSEEN
INTERNAL DAMAGE.
CAUTION
Hydrogen gas can be produced in a hot water system served by this heater that has not been used for a long pe­riod of time (generally two (2) weeks or more). Hydrogen
gas is extremely fl ammable and can ignite when ex- posed to a spark or fl ame. To reduce the risk of injury un-
der these conditions, it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected to the hot water system. Use caution in opening faucets. If hydrogen is present, there will probably be an unusual sound such as air escaping through the pipe as the water begins to ow. There should be no smoking or open fl ame near the faucet at the time it is open.
Location Requirements
IMPORTANT:
This water heater must be installed strictly in accordance with the instructions enclosed, and all applicable electrical, fuel and building codes. It is possible that connections to the water heater, or the water heater itself, may develop leaks. It is therefore strongly recommended that the wa­ter heater be installed so that any leakage of the tank or related water piping is directed to an adequate drain in such a manner that it cannot damage the building, fur­niture, fl oor covering, adjacent areas, lower fl oors of the structure or other property subject to water damage. This is particularly important if the water heater is installed in a multi-story building, on fi nished fl ooring or carpeted sur- faces. THE MANUFACTURER WILL NOT ASSUME ANY LIABILITY for damage caused by water leaking from the water heater, pressure relief valve, or related fi ttings. Se- lect a location as centralized within the piping system as possible. In any location selected, it is recommended that a suitable drain pan be installed under the water heater. This pan must limit the water level to a MAXIMUM depth of 45mm (1 3/4 in.) and have a diameter that is a minimum of 50mm (2 in.) greater than the diameter of the water heater. Suitable piping shall connect the drain pan to a properly operating fl oor drain. When used with a fuel-fi red heater, this drain pan must not restrict combustion air fl ow.
INSTALLATION Unpacking the Water Heater
Important: Do not remove any permanent instructions, labels, or the data label from outside of the water heater or on the inside of panels.
Remove exterior packaging and place installation com-
ponents aside. Inspect all parts for damage prior to installation and start-
up. Completely read all instructions before attempting to
assemble and install this product. Read the “Safety” section of this manual first and then
entire manual carefully. If you don’t follow safety rules, the water heater will not operate properly. It could cause DEATH, SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE. This manual contains instruc­tions for installation, operation, and maintenance of the gas-fired water heater. It also contains warnings throughout the manual that you must read and be aware of. All warnings and instructions are essential to proper operation of the water heater and your safety. Since we cannot put everything on the first few pages, READ ENTIRE MANUAL BEFORE ATTEMPTING TO INSTALL OR OPERATE THE WATER HEATER. After installation, dispose of packaging material in the
proper manner.
45mm max
(1 3/4 in.)
AT LEAST 50mm (2 in.) GREATER
THAN THE DIAMETER OF THE
WATER HEATER.
PIPE TO
ADEQUATE
DRAIN
Figure 1
The water heater must be installed indoors in an area not subject to freezing temperatures and in a vertical position on a level surface. Water heaters located in unconditioned spaces (e.g., attics, basements etc.) may require insulation of the water piping, drain piping and venting to protect against condensation. The power vented series of water heaters are designed to vent the products of combustion horizontally through the wall or vertically through the roof. The blower expels the products of combustion by means of certifi ed plastic piping to the outdoors without the need for a conventional chimney.
– 5 –
Select a location as centralized within the piping system as possible. The heater should be located in an area where leakage of the tank or connections will not result in damage to the area adjacent to the water heater or to lower fl oors of the structure (see "IMPORTANT" notice on the previous page). Before installing this water heater, consideration and planning must be given to the following details:
Proximity to walls and other objects (see "Clearance and Accessibility").
Access to gas supply (see "Gas Supply").
Routing and support of the vent piping and termination (see "Venting").
Position of water supply and placement of water piping and floor drain (see "Water Supply").
In Earthquake Zones
The water heater must be braced, anchored, or strapped to avoid moving during an earthquake. Contact local utilities for code requirements in your area.
MANUAL GAS
SHUT-OFF
GAS
CONTROL/
THERMOSTAT
GROUND-
JOINT UNION
76mm (3 in.)
DRIP LEG
Figure 3
Closet Installations
The water heater may be installed in a closet with a door that is connected to a bedroom or bathroom providing the units are installed and vented per the manufacturer's instructions.
Floor Surfaces
If installing over carpeting, the carpeting must be protected by a metal or wood panel beneath the water heater. The protective panel must extend beyond the full width and depth of the water heater by at least 76mm (3 in.) in each direction or if in an alcove or closet installation, the entire fl oor must be covered by the panel.
Clearances and Accessibility
ALCOVES
AIR INTAKE *
BACK
SENSOR *
FRONT 600mm
(24 in.) MIN.
FOR SERVICE
* DO NOT BLOCK AIR INTAKE OR SENSOR ACCESS. ENSURE ADEQUATE
CLEARANCE FOR AIR SUPPLY
TOP TO
CEILING
SIDES
SIDES
CLOSETS
The minimum clearances between the heater and com-
bustible materials are: Top 200mm (8 in.) Front 100mm (4 in.) Rear and Sides 0mm (0 in.) Note: These requirements are also listed on the data plate located on the front of the water heater.
The water heater is certified for installation on a combus-
tible floor.
Figure 2 may be used as a reference guide to locate the specifi c clearance locations. A minimum of 600mm (24 in.) of front clearance and 100mm (4 in.) on each side should be provided for inspection and service.
Gas Supply
DANGER
Explosion Hazard
Install a gas supply shut-off valve.
Do not connect a natural gas water heater to
a L.P. gas supply.
Do not connect a L.P. gas water heater to a natural gas supply
Failure to follow these instructions can result in death, an explosion or carbon monoxide poisoning.
Figure 2
– 6 –
Read the data plate to be sure the water heater is made for the type of gas you will be using in your home. This
information will be found on the data plate located above the gas control valve. If the information does not agree with the type of gas available, do not install or attempt to start.
Note: An odourant is added by the gas supplier to the gas used by this water heater. This odourant may fade over an extended period of time. Do not depend upon this odourant as an indication of leaking gas.
This gas piping must be installed in accordance with all provincial requirements and the latest edition of "Natural Gas and Propane Installation Code" CSA-B149.1.
Use properly sized gas piping and to ensure full gas input and a properly sized gas supply regulator to ensure adequate gas supply pressure. The supply piping and regulator must be large enough to satisfy the requirements of all appliances connected to the gas service and when all appliances are operating simultaneously. Undersize piping and insuffi cient pressure can restrict the gas fl ow causing the water heater to perform poorly. Improperly sized piping may pose a safety hazard.
Note: When installing gas piping, apply sealing compounds approved for use with natural and propane gas.
Install a readily accessible manual shut-off valve in the
1. gas supply line as required "Natural Gas and Propane Installation Code" CSA-B149.1. The owner/operator must be shown the location of this valve and be given instructions on how to use it to shut off the gas to the heater. Install a drip leg (if not already incorporated as part of
2. the water heater) as shown. The drip leg must be no less than 76mm (3 in.) long for the accumulation of dirt, foreign material, and water droplets. Install a ground joint union, or other approved gas dis-
3. connect, between the gas control/thermostat and the manual shut-off valve. This is to allow easy removal of the gas control/thermostat. Turn the gas supply on and check for leaks. Use a chlo-
4. ride-free soap and water solution (bubbles forming indi­cate a leak) or other approved method.
Gas Supply Pressure
Important: The gas supply pressure must not exceed the maximum supply pressure as stated on the water heater's data plate.
Gas Leak Testing
Important: This water heater and its gas connection must be leak tested before placing the appliance in operation.
If the code requires the gas lines to be tested at a pres­sure exceeding 14 in. w.c. (3.5 kPa), the water heater and its manual shut-off valve must be disconnected from the gas supply piping system and the line capped.
If the gas lines are to be tested at a pressure less than 14 in. w.c. (3.5 kPa), the water heater must be isolated from the gas supply piping system by closing its manual shut-off valve.
WARNING
Exposure to a higher gas supply pressure may cause damage to the control, resulting in explosion or fi re. Consult your local gas supplier and gas authorities. DO NOT PUT INTO SERVICE IF OVER-PRESSURIZATION HAS OCCURRED.
Gas Operating Pressures
The gas supply pressure and burner manifold pressure is listed on the data plate located on the front of the heater above the gas control/thermostat. Ensure the gas supply pressure to the water heater and the burner manifold pressure are properly adjusted while all appliances are in operation. Refer to Figure 35 for Honeywell Gas Control/Thermostat Details.
Rated Manifold
Pressure. in.
w.c. (kPa)
10 (2.48) 9.2 (2.28) 10.2 (2.53)
4 (0.99) 3.6 (0.89) 4.4 (1.09)
U.L. and CSA recognized fuel gas and Carbon Monoxide (CO) detectors are recommended in all applications and should be installed using the manufacturer's instructions and local codes, rules or regulations.
Air Requirements
A gas water heater cannot operate properly without the correct amount of air for combustion. Do not install in a confi ned area such as a closet, unless you provide adequate air supply. Never obstruct the fl ow of dilution/ventilation air. If you have any doubts or questions at all, call your gas supplier. Failure to provide the proper amounts of air can result in a fi re or explosion and cause death, serious bodily injury, or property damage. The combustion and dilution air inlets are shown in Figure 5.
Important: Air must not come from a corrosive atmosphere. Any failure due to corrosive elements in the atmosphere is excluded from warranty coverage. Installations in or for certain places including, but not limited to, those listed below may require outdoor air for combustion and dilution to reduce the risk of chemical exposure. In these cases it is probably necessary to install a Power Direct Vent (PDV) water heater:
Beauty shops, Photo processing labs
Buildings with indoor pools
Water heaters installed in some laundry, hobby or craft
rooms Water heaters installed near chemical storage areas
In some cases, isolation of the water heater from corrosive environments may be required.
Min. Manifold
Pressure. in.
w.c. (kPa)
Max. Manifold
Pressure. in.
w.c. (kPa)
– 7 –
Appliances In Enclosures
If the water heater is installed in an enclosure ensure an air supply is provided as required by the current edition of CSA­B149.1, the Natural Gas and Propane Installation Code.
Typical Installation
1. Vent Termination Elbow with
Rodent Screen
2. *Vent Pipe
3. *Vent Pipe Coupling (if required)
4. *Vent Pipe Elbow (long radius)
5. Limit Switch (see Figure 9)
6. T&P Valve
7. Diptube
8. Baffle Assembly
9. * Discharge Pipe
10. Gas Control Valve/Thermostat
(Honeywell)
11. Gas Valve Electronic Control
Module And Cover (Honeywell)
12. Drain Valve
13. Outer Gas Door
14. Manifold Door Assembly (behind
outer door) (see Figures 6 & 7)
15. *Floor Drain
16. *Metal Drain Pan
17. Flammable Vapour Sensor (under
cover) (see Figure 8)
18. **Combo Heating System Return Inlet (Optional)
19. Air Inlet Snorkel
20. **Combo Heating System Supply Outlet (Optional)
21. Blower with Power Cord (see Figure 9)
22. Air Switch (inside box) (see Figure
9)
23. Junction Box (see Figure 9)
24. Junction Box Cover (see Figure 6)
25. Air Tubing (see Figure 9)
26. Rubber Coupling
27. Gear Clamp
28. Flue Collector
29. Hot-Water Outlet Nipple
30. Anode (under cap)
31. Cold-Water Inlet Nipple
32. Flexible Manifold Tube (see Figures 6 & 7)
33. Viewport (see Figures 6 & 7)
34. Flame Sensor Rod (see Figures 6 & 7)
35. Gas Orifice (see Figures 6 & 7)
36. Sheet Metal Burner (see Figures 6 & 7)
37. Gas Manifold (see Figures 6 & 7)
38. Hot-Surface Igniter (see Figures 6 & 7)
39. Manifold Door Gasket (see Figures 6 & 7)
40. Manifold Door (see Figures 6 & 7)
41. Two Piece Grommet With Clip (see Figures 6 & 7)
42. *Inlet Water Shut-off Valve
43. *Gas Supply*
44. *Main Manual Gas Shut-off Valve
45. *Ground Joint Union (gas connec­tion)
46. *Sediment Trap/Dirt Leg
47. *Union (water connection)
48. Rating Plate
49. ***Control Harness
50. *Thermal Expansion Tank (required for all closed systems)
1
2
3
4
27
42
26
21
21
48
6
20
7
9
10
11
8
50
47
21
31
Dilution
Air Inlets
Combustion
Air Inlets
29
47
28
29
30
18
43
44
19
12
45
46
49
17
16
Front View Rear View
Figure 4 Figure 5
– 8 –
15
13
14
Natural gas and Propane main burner with igniter assembly for 40k to 50k Btu/hr models
22
25
26
34
32
33
Figure 6
Natural gas and Propane main burner with igniter assembly for 60k to 75k Btu/hr models
32 34
35
35
23
27
24
36
37
5
38
39
4041
Figure 9
Vacuum relief valve install per local codes (not supplied with heater).
Figure 10
33
Figure 7
41
40
39
36
37
38
* Items not supplied with the water heater ** The side recirculation loop connections may not be used
as the primary water inlet and outlet connections. For your convenience, plugs are installed in these fittings at the factory. Remove these plugs if needed for your specific installation. Otherwise (as with all connections) check for leaks while filling the tank with water and after completing the installation.
*** Caution: harness has 120 VAC present during opera-
tion.
Replacement Parts And Deliming Products
Replacement parts and recommended delimer may be ordered through authorized servicers or distributors. When ordering parts, provide complete model and serial numbers (see rating plate), quantity and name of part desired. Standard hardware items may be purchased locally.
17
Figure 8
– 9 –
Water Piping - Mixing Valve Usage
MIXING VALVE
SUGGESTED PlPING ARRANGEMENT FOR
TOP CONNECTIONS
CERTAIN
MODELS ARE EQUIPPED WITH SIDE PLUMBING
CONNECTIONS FOR
SPACE HEATING.
THE HOT AND
COLD FITTING
ASSEMBLlES
(PART #9001262)
CAN BE ORDERED
THROUGH AN
AUTHORIZED
DEALER
GAS
SUPPLY
DRAIN VALV E
* NOTE: THE T&P VALVE CAN BE PIPED DIRECTLY TO THE DRAIN
TEMPERED
POTABLE WATER
Figure 11
This appliance has been design certifi ed as complying with CSA Standard for water heaters and certain models with side plumbing connections are considered suitable for Water (Potable) Heating and Space Heating. The water heater should not be subjected to excessive water pressure fl uctuations and should not be subjected to an operating pressure greater than 80 psi. If this occurs, a pressure-reducing valve with a bypass should be installed in the cold-water inlet line. This should be placed on the supply to the entire house in order to maintain equal hot and cold water pressure.
SHUT-OFF
VALV E
COLD-WATER
INLET
TEMERATURE­PRESSURE RELIEF VALVE
DISCHARGE PIPE (DO NOT CAP OR PLUG)
TO SUITABLE DRAIN
150mm (6”) MAX. AIR GAP*
METAL DRAlN PAN
MIXING VALVE
SUGGESTED PlPING
ARRANGEMENT FOR
TOP CONNECTIONS
NON-TEMPERED
WATER SUPPLY
GAS
SUPPLY
DRAIN VALV E
* NOTE: THE T&P VALVE CAN BE PIPED DIRECTLY TO THE DRAIN
TEMPERED
POTABLE WATER
SHUT-OFF
VALV E
COLD-WATER
INLET
NON-TEMPERED
WATER RETURN
TEMERATURE­PRESSURE RELIEF VALVE
DISCHARGE PIPE (DO NOT CAP OR PLUG)
TO SUITABLE DRAIN
150mm (6”) MAX. AIR GAP*
METAL DRAlN PAN
Figure 12
Mixing Valves
Water heaters are intended to produce hot water. Water heated to a temperature which satisfi es space heating, clothes washing, dish washing, and other sanitizing needs can scald and cause permanent injury upon contact. Short repeated heating cycles caused by small hot-water uses can cause temperatures at the point of use to exceed the water heater’s temperature setting by up to 11C° (20F°). Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infi rm and the physically/mentally disabled. Table 3 shows the approximate time-to-burn relationship for normal adult skin. National plumbing code requirements limit the temperatures of certain fi xtures in the home. Local codes may have additional requirements. In addition to these requirements, if anyone using hot water in your home fi ts into one of these groups, then you must take special precautions. In addition to using the lowest possible temperature setting that satisfi es your hot water needs, a means such as a Mixing Valve, should be used at the hot water taps used by these people or at the water heater. Mixing valves are available at plumbing supply or hardware stores. Consult a Qualifi ed Installer or Service Agency. Follow mixing valve manufacturer’s instructions for installation of the valves (see Figures 11 & 12). Before changing the factory setting on the thermostat, read the “Temperature Regulation” section in this manual.
– 10 –
Exhaust Venting
This heater is designed to exhaust the products of combustion (fl ue gases) to the outdoors using a sealed piping system. Table 1 lists the allowable vent materials and sizing information. Figure 16 shows the general venting layout while Figures 17-19 show various end termination details and clearances. Connection of the venting piping to the blower is shown in Figures 21-25.
Correct installation of the venting system is essential to the safe and effi cient operation of this water heater. Vent piping must be installed in accordance with all applicable national and provincial codes. All installations shall meet the requirements as stated in the latest edition of the "Natural Gas and Propane Installation Codes" CSA-B149-1.
PREFERRED PRACTICESNOT RECOMMENDED
STREET ELBOW NORMAL ELBOW
150mm
(6 in.) min.
BACK TO BACK ELBOWS
PREFERRED PRACTICE
90° SHORT SWEEP ELBOW
(MORE RESTRICTIVE)
Figure 13
Note: The information provided in Figure 13 is intended as a
guideline for good vent installation practices only and is not intended to restrict venting options beyond those restrictions established by the latest edition of the "Natural Gas and Propane Installation Codes" CSA-B149-1 or any applicable local and provincial codes.
90° LONG SWEEP ELBOW
(LESS RESTRICTIVE)
High Ambient Temperature Installations
This heater requires room air to lower the fl ue gas temperatures before the gases pass through the vent system. The dilution air inlets are located on the rear of the blower assembly (see Figures 5 & 21). As the room temperature rises, the ability to lower the fl ue gases lessens so special attention to the choice of venting material is required. Establishing the ambient temperatures where the heater and the venting is installed is very important, especially in regions with warmer climates or any region that experiences hot summers. Ambient conditions hotter than 43°C (110°F) require that the venting material be either CPVC or polypropylene. Areas that can experience high ambient environments include closets, alcoves, areas under staircases, attics especially in metal roofed buildings, areas with restricted air movement, rooms with large solar gains, metal sheds, industrial or commercial enterprises and venting systems exposed to direct sunlight. For high temperature environments, obtain high limit switch upgrade Kit # 9008306015 and use the higher rated vent piping.
Important Notes and Warnings
This heater is certified to be installed using Schedule
40 PVC or CPVC or polypropylene plastic vent material. All jurisdictions require that this material is approved to ULC S636. Only use approved material. All venting mate­rial and components must be joined with the approved primer/cleaner and solvent cement. Do not common vent this heater with any other appli-
ance. During operation the plastic piping will expand as it heats
up and contract as it cools down. This is normal for this type of venting. Rigidly fastening the vent piping can cause undue stress that may result in the cracking or fracturing the vent piping material. A fracture of the vent­ing pipe may pose a serious safety hazard. To prevent stressing of the vent system, all hangers and supports must allow the vent piping freedom to move. Use long sweep elbows wherever possible. Closely-
coupled elbows and short radius elbows can reduce the venting capacity. All power vented water heaters generate a certain
amount of operational noise. In order to minimize noise transmission to the support structure, it is recommended to use isolation pads between the pipe hangers and the vent pipe. Most power vent installations develop some condensa-
tion in the vent piping. When using long runs of venting or when the venting passes through cold or unheated areas, considerable amounts of condensate from the flue gases can develop. Provision must be made for the con­densate to drain freely from the system or to be collected in a condensate trap(s) that can be drained. Damage or fracture of the vent piping may occur if the condensate is allowed to collect and freeze. Pooling of condensate can restrict airflow and can cause nuisance failures of the system.
11
Venting Terminations and Sizing
Refer to Figure 16 and Table 1 for vent pipe materials and
sizing. Examples of the vent terminations are shown in Figures 17 and 18. If the installation requires a vent riser, suitable drainage must be provided to ensure condensa­tion does not accumulate. Termination through a roof is shown Figure 19. 40, 50 and 60-gallon heaters with rated inputs of 50k
Btu/hr or less are supplied with a 2” termination elbow, a plastic “rodent screen” and a wire mesh "rodent screen" (see Figure 14). 50 and 75-gallon heaters with rated inputs of 60k Btu/hr
or more are supplied with a 3” termination elbow, a plastic “rodent screen” and a wire mesh "rodent screen" (see Figure 15).
Rodent Screens
A vent termination screen is required to keep foreign objects, rodents and small birds from entering the venting system. These screens have been sized to ensure maximum energy effi ciency of the vent system based on the “equivalent length” of the vent piping. CHOOSE ONLY the ONE SCREEN THAT MATCHES YOUR VENTING CONFIGURATION (see Figures 14 & 15). How to determine the “equivalent length” is shown in Figure 16 and in Table 1. This will allow for easy removal for inspection and cleaning.
For heaters with rated inputs of 50k Btu/hr or less see Figure 14.
For heaters with rated inputs of 60k Btu/hr or more see Figure 15.
For heaters with rated inputs of 50k Btu/hr or less:
with 2 in. venting (short) with 2 in. venting (long)
VENT LENGTH LESS THAN OR EQUAL TO 20 EQUIVALENT FT.
(6.1 METRES) USE THIS SCREEN
(SUPPLIED).
VENT LENGTH GREATER THAN
20 EQUIVALENT FT.
(6.1 METRES) USE THIS SCREEN
(SUPPLIED).
with 3 in. venting with 4 in. venting
For heaters with rated inputs of 60k Btu/hr or more:
with 3 in. venting (short) with 3 in. venting (long)
VENT LENGTH LESS THAN OR EQUAL TO 20 EQUIVALENT FT.
(6.1 METRES) USE THIS SCREEN
(SUPPLIED).
VENT LENGTH GREATER THAN
20 EQUIVALENT FT.
(6.1 METRES) USE THIS SCREEN
(SUPPLIED).
with 4 in. venting
VENT LENGTH GREATER THAN
50 EQUIVALENT FT.
(15.2 METRES) USE THIS SCREEN
(FIELD SUPPLIED).
VENT LENGTH GREATER THAN
125 EQUIVALENT FT.
(38.1 METRES) USE THIS SCREEN
(ORDER KIT # 9008310015).
Figure 14
– 12 –
VENT LENGTH GREATER THAN
125 EQUIVALENT FT.
(38.1 METRES) USE THIS SCREEN
(FIELD SUPPLIED).
Figure 15
Loading...
+ 27 hidden pages