GSW 5065 User Manual

PART NO. 63940 REV. B (06-09)
WARNING:
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, per­sonal injury or death.
WARNING:
Improper installation, adjustment, alter­ation, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional infor­mation, consult a qualified installer, serv­ice agency, or the gas utility.
FOR YOUR SAFETY
• Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance.
• Installation and service must be per­formed by a qualified installer, service agency or the gas utility.
Do not try to light any appliance.
Do not touch any electrical switch; do
not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
WHAT TO DO IF YOU SMELL GAS
FLAMMABLE VAPOUR IGNITION RESISTANT
POWER VENTED WATER HEATER
INSTALLATION AND OPERATING INSTRUCTIONS
Read and understand these instructions thoroughly before starting.
This page intentionally left blank. May be used for notes or to record other installation information.
– 2 –
TABLE OF CONTENTS
I) Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Consumer Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
II) Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Code Requirements For Installations In Canada . . . . . . . . . . . . . . . . . . . .
Code Requirements For Installations In The United States . . . . . . . . . . . .
Safety Warning (Flammable Vapours) . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Warning (Scalding) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Warning (Carbon Monoxide) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Relief Valve Requirements (T&P). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
III) Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Unpacking The Water Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Drain Pan Requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Location Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clearances And Accessibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Air Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Water Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Checklist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IV) Lighting & Operating Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
V) Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
First Lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Control/Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flammable Vapour Sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Temperature Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Water Heater Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sequence Of Operation (Robertshaw 2000WDER). . . . . . . . . . . . . . . . . .
Burner Flames . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Emergency Shut Down. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operational Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Water Heater Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Smoke/Odour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Anode Rod/Water Odour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VI) Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Draining And Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Routine Preventative Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Temperature And Pressure Relief Valve . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VII) Combination Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Read Before Proceeding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VIII) Troubleshooting Guide (Robertshaw 2000WDER). . . . . . . . . . . . . . . 27
IX) Parts Reference Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
RETAIN THESE INSTRUCTIONS IN A SAFE LOCATION FOR FUTURE REFERENCE
– 3 –
Thank you for purchasing a Flammable Vapour Ignition Resistant Power Vented Water Heater. This water heater
is designed to reduce the risk of flammable vapour related fires by shutting the burner down before flammable vapours get into the water heater combustion chamber. This is achieved by the means of the flammable vapour sensor. Properly installed and maintained, it will provide years of trouble free service. This gas-fired water heater has been developed to produce potable hot water for normal residential demands and may also be used in combination with space heating applica­tions. Any deviation from these applications could affect your warranty.
Consumer Responsibilities
This manual has been prepared to acquaint you with the installation, operation and maintenance of your gas fired water heater and provide important safety information in these areas. It is your responsibility to ensure that your water heater is properly installed and cared for.
FAILURE TO FOLLOW THE INSTRUCTIONS IN THIS MANUAL MAY RESULT IN SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE. THOROUGHLY READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE YOU ATTEMPT TO INSTALL, OPERATE OR MAINTAIN THIS HEATER.
Installation and service requires trade knowledge in the areas of plumbing, electricity, venting, air supply and gas supply. If you lack these skills or have difficulty understand­ing these instructions, you should not proceed. Enlist the
help of a qualified service technician to install this water heater.
Examples of qualified service technicians include those trained in the plumbing and heating industry, local gas utili­ty personnel or an authorized service person.
Service to the Power Vent System should only be per­formed by a qualified service technician.
The manufacturer and seller of this water heater will not assume any liability for any property damage, personal injury or death resulting from improper sizing, installation or failure to comply with these instructions.
The warranty on this water heater is in effect only when the water heater is installed and operated in accordance with these instructions. A data plate identifying your water heater can be found above the gas control/thermostat. When refer­ring to your water heater, always have the information listed on the data plate readily available.
Protect your warranty: Regularly service your water heater as directed in the "Maintenance" section of this man­ual. Retain your original receipt as proof of purchase.
Do not discard this manual. You or future users of this water heater will need it for reference.
Your safety and the safety of others is very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING”.
DANGER
WARNING
You can be killed or seriously injured if you don’t immediately follow instructions.
You can be killed or seriously injured if you don’t follow instructions.
I) INTRODUCTION
The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of potential exposure to such substances. WARNING: This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm. This appliance can cause low-level exposure to some of the substances listed, including formalde­hyde, carbon monoxide, and soot.
– 4 –
This water heater is design-certified by CSA International as a Category I, non-direct vented water heater which takes its combustion air either from the installation area or from air ducted to the unit from the outside.
In addition to the installation instructions found in this man­ual, the water heater must be installed in accordance with all local and provincial or state codes or, in the absence of such, with the latest editions of the following specifications.
For Installations in Canada:
“Natural Gas and Propane Installation Code” CAN/CSA­B149.1 and “Canadian Electrical Code (CAN/CSA C22.1), Part I” available from:
Canadian Standards Association, 5060 Spectrum Way, Mississauga, Ontario, Canada L4W 5N6
For Installations in the United States:
“National Fuel Gas Code” ANSI Z223.1 (NFPA 54) and “National Electrical Code” (NFPA 70)” available from:
American National Standards Institute, 25 West 43rd Street, New York, NY 10036 Massachusetts code requires this water heater to be installed in accordance with Massachusetts Plumbing and Fuel Gas Code 248 CMR Section 2.00 and 5.00.
Check your phone listings for the local authorities having jurisdiction over your installation.
Safety Warning (Flammable Vapours)
There is a risk of property damage, personal injury or death from the by-products of combustion (e.g., flue gases), in using fuel-burning appliances such as water heaters. Areas that may not be suitable for water heater installation include those where flammable liquids, gasoline, solvents, adhe­sives etc. are stored, or where engine-driven equipment or vehicles are stored, operated or repaired. These, and simi-
lar products, should not be stored or used near the water heater or air intake. Due to the nature of air movement, flammable vapours can be carried some distance from the point of storage. The gas-fired water heater igniter or burn­er flame can ignite these vapours causing a flashback, fire or explosion, which may result in severe property damage, serious personal injury or death. If flammable liquids or vapours have spilled or leaked in the area of the water heater, leave the area immediately and call the fire depart­ment from a neighbor’s home. Do not attempt to clean the spill until all ignition sources have been extinguished.
Safety Warning (Scalding)
Hot water produced by this appliance can cause severe burns due to scalding. The hazard is increased for young children, the aged or the disabled when water temperatures exceed 52°C (125°F). Use tempering valves, also known as mixing valves, in the hot water system to reduce the risk of scalding at point-of-use such as lavatories, sinks and bathing facilities. Such precautions must be followed when this heater is operated in combination with dishwashing or space heating applications.
Safety Warning (Carbon Monoxide)
As with all fuel burning equipment, this heater requires an adequate supply of air for combustion and ventilation. An insufficient air supply can result in poor combustion or the re-circulation of the flue gases. Such a condition can cause soot build-up and present a fire hazard. Flow reversal of flue gases can cause an increase of carbon monoxide inside of the dwelling that could result in serious bodily harm or death from asphyxiation.
MAKE SURE THE FLOW OF COMBUSTION AND VENTI­LATION AIR IS NOT RESTRICTED.
WARNING
Flammable Vapours
FLAMMABLES
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death
Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance. Storage of or use of gasoline or other flammable vapours or liquids in the vicinity of this or any other appliance can result in serious injury or death.
DANGER
DANGER
Carbon Monoxide Warning
• Follow all vent system requirements by the local authorities having jurisdiction over your installation.
• Failure to do so can result in death, explo­sion or carbon monoxide poisoning.
II) SAFETY
– 5 –
Relief Valve Requirements (T&P)
All water heaters must be fitted with a proper temperature and pressure relief valve. These valves must be certified as meeting the requirements of the “Standard For Relief
Valves For Hot Water Supply Systems, ANSI Z21.22/CSA 4.4”.
If this water heater has been exposed to flooding, freezing, fire or any unusual condition, do not put it into operation until it has been inspected and approved by a qualified service technician.
THESE CONDITIONS CAN RESULT IN UNSEEN INTER­NAL DAMAGE and are not subject to warranty coverage.
Unpacking the Water Heater
Important: Do not remove any permanent instructions, labels, or the data label from outside of the water heater or on the inside of panels.
Remove exterior packaging and place installation com­ponents aside.
Inspect all parts for damage prior to installation and start-up.
Completely read all instructions before attempting to assemble and install this product.
If you observe damage to the water heater or any of its components, DO NOT ASSEMBLE OR INSTALL IT OR MAKE ANY ATTEMPT TO FIX THE DAMAGED PART(S). Contact the place of purchase for further instructions.
After installation, dispose of packaging material in the proper manner.
Location Requirements
The water heater must be installed indoors in an area not subject to freezing temperatures and in a vertical position on a level surface. Water heaters located in unconditioned spaces (e.g., attics, basements etc.) may require insulation of the water piping, drain piping and venting to protect against condensation. The power vented series of water heaters are designed to vent the products of combustion horizontally through the wall or vertically through the roof. The blower expels the products of combustion by means of plastic piping to the outdoors without the need for a con­ventional chimney. Select a location as centralized within the piping system as possible. The heater should be located in an area where leakage of the tank or connections will not result in damage
IMPORTANT:
This water heater must be installed strictly in accordance with the instructions enclosed, and local electrical, fuel and building codes. It is possible that connections to the water heater, or the water heater itself, may develop leaks. IT IS THEREFORE IMPERATIVE that the water heater be installed so that any leakage of the tank or relat­ed water piping is directed to an adequate drain in such a manner that it cannot damage the building, furniture, floor covering, adjacent areas, lower floors of the structure or other property subject to water damage. This is particular­ly important if the water heater is installed in a multi-story building, on finished flooring or carpeted surfaces. GSW WILL NOT ASSUME ANY LIABILITY for damage caused by water leaking from the water heater, pressure relief valve, or related fittings. Select a location as centralized within the piping system as possible. In any location selected, it is recommended that a suitable drain pan be installed under the water heater. This pan must limit the water level to a MAXIMUM depth of 45mm (1 3/4 in.) and have a diameter that is a minimum of 50mm (2 in.) greater than the diameter of the water heater. Suitable piping shall connect the drain pan to a properly operating floor drain. When used with a fuel-fired heater, this drain pan must not restrict combustion air flow.
WARNING
Excessive Weight Hazard Use two or more people to move and install water heater. Failure to do so can result in back or other injury.
III) INSTALLATION
CAUTION
Hydrogen gas can be produced in a hot water system served by this heater that has not been used for a long period of time (generally two (2) weeks or more).
Hydrogen gas is extremely flammable and can ignite when exposed to a spark or flame. To reduce the risk of
injury under these conditions, it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance con­nected to the hot water system. Use caution in opening faucets. If hydrogen is present, there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow. There should be no smoking or open flame near the faucet at the time it is open.
45mm MAX
(1 3/4 in.)
AT LEAST 50mm (2 in.)
GREATER THAN THE DIAMETER
OF THE WATER HEATER.
PIPE TO
ADEQUATE
DRAIN
Figure 1 Drain Pan Installation
– 6 –
to the area adjacent to the water heater or to lower floors of the structure (see “IMPORTANT” notice on the previous page). Before installing this water heater, consideration and planning must be given to the following details:
Proximity to walls and other objects (see “Clearance and
Accessibility”).
Access to gas supply (see “Gas Supply”).
Routing and support of the vent piping and termination
(see “Venting”).
Position of water supply and placement of water piping
and floor drain (see “Water Supply”).
In Earthquake Zones Note: The water heater must be braced, anchored, or
strapped to avoid moving during an earthquake. Contact local utilities for code requirements in your area.
Note: The water heater may be installed in a closet with a door off a bedroom or bathroom providing the units are installed and vented per the manufacturer’s instructions.
Important: If installing over carpeting, the carpeting must be protected by a metal or wood panel beneath the water heater. The protective panel must extend beyond the full width and depth of the water heater by at least 76mm (3 in.) in each direction or if in an alcove or closet installation, the entire floor must be covered by the panel.
Clearances and Accessibility
The minimum clearances between the heater and com­bustible materials are:
Top . . . . . . . . . . . . . 200mm (8 in.)
Front . . . . . . . . . . . 100mm (4 in.)
Rear and Sides . . . 25mm (1 in.)
Note: These requirements are also listed on the data plate located on the front of the water heater.
The water heater is certified for installation on a com­bustible floor.
Figure 2 may be used as a reference guide to locate the specific clearance locations. A minimum of 600mm (24 in.) of front clearance and 100mm (4 in.) on each side should be provided for inspection and service.
Gas Supply
Read the data plate to be sure the water heater is made for the type of gas you will be using in your home. This
information will be found on the data plate located above the gas control valve. If the information does not agree with the type of gas available, do not install or attempt to start. Call your dealer.
Note: An odourant is added by the gas supplier to the gas used by this water heater. This odourant may fade over an extended period of time. Do not depend upon this odourant as an indication of leaking gas.
FRONT 600mm (24 in.) MIN. FOR SERVICE
BACK
AIR INTAKE *
SENSOR *
SIDES
SIDES
VENT
TOP TO CEILING
* DO NOT BLOCK AIR INTAKE OR SENSOR ACCESS. ENSURE ADEQUATE
CLEARANCE FOR AIR SUPPLY
Figure 2 Minimum Clearance Locations
DANGER
Explosion Hazard
• Use a new CSA approved gas supply line.
• Install a gas supply shut-off valve.
• Do not connect a natural gas water heater to a L.P. gas supply.
• Do not connect a L.P. gas water heater to a natural gas supply
• Failure to follow these instructions can result in death, an explosion or carbon monoxide poisoning.
Figure 3 Gas Piping
DRIP LEG
MANUAL
GAS
SHUT-OFF
GAS
CONTROL/
THERMOSTAT
76mm (3 in.)
GROUND-
JOINT UNION
– 7 –
This gas piping must be installed in accordance with all local and provincial or state codes or, in the absence of such, the latest edition of “Natural Gas and Propane Installation
Code” CAN/CSA-B149.1 (Canada), or “National Fuel Gas Code” ANSI Z223.1 (NFPA 54) (U.S.A.).
Note: When installing gas piping, apply sealing compounds
approved for use with natural and propane gas.
1. Install a readily accessible manual shut-off valve in the gas supply line as recommended by the local utility. The owner/operator must be shown the location of this valve and be given instructions on how to use it to shut off the gas to the heater.
2. Install a drip leg (if not already incorporated as part of the water heater) as shown. The drip leg must be no less than 76mm (3 in.) long for the accumulation of dirt, foreign material, and water droplets.
3. Install a ground joint union between the gas control /thermostat and the manual shut-off valve. This is to allow easy removal of the gas control/thermostat.
4. Turn the gas supply on and check for leaks. Use a chlo­ride-free soap and water solution (bubbles forming indi­cate a leak) or other approved method.
Gas Pressure
Important: The gas supply pressure must not exceed the maximum supply pressure as stated on the water heater’s data plate.
Gas Leak Testing
Important: This water heater and its gas connection must be leak tested before placing the appliance in operation.
If the code requires the gas lines to be tested at a pres­sure exceeding 14 in. w.c. (3.5 kPa), the water heater and its manual shut-off valve must be disconnected from the gas supply piping system and the line capped.
If the gas lines are to be tested at a pressure less than 14 in. w.c. (3.5 kPa), the water heater must be isolated from the gas supply piping system by closing its manu­al shut-off valve.
U.L. recognized fuel gas and (CO) detectors are recom­mended in all applications and should be installed using the manufacturer’s instructions and local codes, rules, or regu­lations.
Note: Air may be present in the gas lines and could prevent the burner from lighting on initial start-up. The gas lines should be purged of air by a qualified service technician after installation of the gas piping system.
WARNING
Exposure to a higher gas supply pressure may cause damage to the control, resulting in explosion or fire. Consult your local gas supplier and gas authorities. DO NOT PUT INTO SERVICE IF OVER-PRESSURIZATION HAS OCCURRED.
– 8 –
Air Requirements
Important: Air for combustion and ventilation must not come from a corrosive atmosphere. Any failure due to cor­rosive elements in the atmosphere is excluded from war­ranty coverage. Installations in or for certain places including, but not limited to, those listed below will require outdoor air for combustion due to chemical exposure:
Beauty shops Photo processing labs Buildings with indoor pools Water heaters installed in laundry, hobby or craft rooms Water heaters installed near chemical storage areas
In such circumstances, outdoor combustion air may reduce, but will not eliminate the presence of corrosive chemicals in the air. Combustion air must be free of acid-forming chemi­cals such as sulfur, fluorine and chlorine. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresheners, paint and varnish removers, refrig­erants and many other commercial and household prod­ucts. When burned, vapours from these products form high­ly corrosive acid compounds. These products should not be stored or used near the water heater or air inlet. The area in which the heater is located is classified as either “an unconfined sp
ace
” or “a confined sp
ace
.”
An unconfined sp
ace
is defined as a space having a vol­ume not less than 50 cubic feet per 1000 BTU/hour (4.8 cubic metres per kilowatt) of combined input rating of all appliances using the space. Adjacent open rooms may be included as part of the unconfined space, provided there are no closeable doors between these rooms. An exam­ple of this is an open basement. A confined sp
ace is one smaller than described above.
For buildings using tight construction (newer and renovated structures), the air supply shall be introduced from the out­doors, regardless of whether the space is confined or unconfined.
Confined Space Air Requirements for Canadian Installations
Refer to Figure 4 (a), or (b), and Table 1 for proper sizing and location of combustion air ducts and openings. CHECK LOCAL CODES. a). Two permanent openings shall be provided connecting
the confined space (e.g., closet, small room) with the unconfined space. Each opening shall have a free area of one square inch per 1,000 BTU/hour input (22 cm²/kW) of all appliances in the confined space. The top opening shall be located as close to the ceiling as prac­tical but never lower than the top of the heater. (see Figure 4 (a)). The bottom opening shall be located nei­ther more than 450mm (18 in.), nor less than 150mm (6 in.), above floor level.
b). When using a single air supply, the duct shall terminate
within 300mm (12 in.) above and within 600mm (24 in.) horizontally of the burner level
of the appliance having the largest input. For example: GSW’s water heaters’ burners are 150mm (6 in.) from the floor, plus 300mm (12 in.) equals 450mm (18 in.) as shown in Figure 4 (b). All exterior vent openings are to be at least 300mm (12 in.) above the ground and clear of snow levels.
CONFINED
SPACE
PERMANENT OPENINGS
EQUIPMENT LOCATED IN CONFINED SPACES;
ALL AIR FROM INSIDE THE BUILDING.
(a)
UNCONFINED SPACE
BASEMENT INSTALLATION, EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM OUTDOORS
(b)
CONFINED
SPACE
GRADE
COMBINATION COMBUSTION/
VENTILATION
AIR DUCT
300mm (12 in.) (MIN)
450mm (18 in.)
600mm (24 in.)
Figure 4 Combustion Air Supply Openings And Ducts
(Can.)
BTU / h (kW / hr)
cm2in.2mm in. mm in.
25,000 8 45 7 76 3 100 4 50,000 15 45 7 76 3 100 4 75,000 23 70 11 100 4 125 5 100,000 30 90 14 100 4 125 5 125,000 37 120 18 125 5 150 6 150,000 45 140 22 125 5 150 6
Acceptable Round
Duct Size Diameter
Combined Input of
All Appliances in
Confined Space*
Required
Free Area
A**
B***
Table 1 Air Supply Sizing (Can.)
* All appliances refers to, and includes, those appliances
using the same air source (e.g. water heater, furnace, boiler, clothes dryer etc.).
** Maximum allowable length of ductwork listed in column
A is 6.1 equivalent metres (20 ft.).
*** Maximum allowable length of ductwork listed in column
B is 15.2 equivalent metres (50 ft.).