GST C-9401, I –9401 Installation And Operation Manual

I –9401 Addressable Sounder Strobe
Installation and Operation Manual
(Issue 3.02, August 2012)
I-9401 Addressable Sounder Strobe C-9401 Sounder Strobe Installation and Operation Manual
CONTENTS
I General .................................................................................................................... 1
II Features ................................................................................................................... 1
III Technical Specifications........................................................................................... 1
IV Structure and Operation Principle ........................................................................... 2
V Mounting and Wiring ................................................................................................ 2
VI Testing ..................................................................................................................... 4
VII Applications ............................................................................................................. 4
I-9401 Addressable Sounder Strobe C-9401 Sounder Strobe Installation and Operation Manual
Page 1
I General
Sounder Strobe is a kind of optical and visual alarm device used to warn people in field when fire occurs. GST produces two types of sounder strobe, addressable (I-9401) and conventional (C-9401). Addressable sounder strobe can be started directly by fire alarm controller. It can be electronically programmed and modified by P-9910 Hand Held Programmer in field. Conventional sounder strobe can give optical and visual alarm when powered by DC24V, and can be connected to fire alarm controller through an addressable linkage control module. When it is not started, wire checking can be done by loading reverse voltage and connecting terminal resistor at the end of the circuit.
II Features
1. Red plexiglass panel, several strong red LED as light source, striking, long-life and low consumption.
2. Fire alarm sound over 85dB, easy to catch attention.
3. Circuit part and base box are plugged together, reliable contact convenient for engineering;
Addressable:
4. Peripheral control terminals to startup the sounder strobe directly by passive normally open contact (e.g. manual call point), unaffected by power-cut of signal bus.
5. Signal bus and power bus non-polarized, easy for connection.
6. Function of checking power-cut, sending fault information to the controller.
7. Electronic programming of address code that can be modified on site.
Conventional:
8. DC24V two-wire, polarized, easy for wire checking (connecting terminal resistor when checking, the resistance value can be deiced by connecting devices).
III Technical Specifications
1. Operating Voltage (power bus terminal only for conventional):
Signal Bus Voltage: 24V Range Allowed: 16V28V; Power Bus Voltage: DC24V Range Allowed: DC20VDC28V
2. Operating Current (power alarming current only for conventional):
Power Standby Current10mA; Power Alarming Current160mA; Loop Standby Current0.8mA; Loop Starting Current6.0mA.
3. Flashing Frequency: 20180 times every minute when alarming;
4. Alarm Voice85dB(Due front 3m horizontal (A weighted))
5. Wiring: