GST I-9308 User Manual

Page 1
9
10
15
16
8
7
2
1
Z1
Z2
D1
D2
L-
L+
Mounting Hole
Mounting Hole
Mounting Direction
65mm
Conduit
B-9310 Back Box
Conduit
ModuleModule
Back Box
I-9308
Addressable Sounder Circuit Module
Features
Photoelectric insulation technology for loop and power,
good ability of anti-interference.
Address can be programmed through a programmer or
Microprocessor monitors running, checks the short,
broken circuit of output, monitors power supply and transmits the information to the FACP.
Four working modes. Plug-in structure.
Description
I-9308 Addressable Sound Circuit Module (the module) is used to drive C-9402 Conventional Base Mount Sounder (C-9402), C-9403 Conventional Sounder Strobe (C-9403), C-9404 Conventional Sounder (C-9404), generating pre-alarm sound, fire alarm and continuous alarm sound. The module is addressable, and four working modes can be set through hand held programmer, with cable-checking.
If the cable conduit is inside the wall, the base is installed onto the Back Box (Fig. 2). If the cable conduit is on the surface of the wall, a B-9310 Back Box is available (Fig. 3).
Connection and Cabling
Fig. 1 shows terminals of the module.
Fig. 1
Connection description: D1, D2: 24VDC power, non-polarized Z1, Z2: Connecting with loop of FACP, non-polarized L+, L-: Polarized output, refer to Fig. 6 and Fig. 7 for connection with different sounders.
Recommended Cabling
1.0mm2 or above fire cable should be for Z1, Z2. Fire cable, whose cross section should meet with power capacity of connected devices, is for 24VDC power line; 1.5mm2 or above fire cable for others, subject to local codes.
Installation
The module is simply plugged onto the base after corresponding terminals are connected.
30303456 Issue 4.04
Fig.2 Fig.3 Note the arrow upward for mounting direction (Fig. 1).
Operation
Programming
The module can be programmed in field through a programmer. When the module occupies two addresses, the low address can be programmed and can increase 1 automatically to become the high address. Refer to P-9910B
Hand Held Programmer Installation and Operation Manual
for specific operations.
Setting Working Mode
In power-on state, press Function and enter number 4, will show on the last digit. Input the alarm mode parameter, press Program, “P will be shown on the screen, meaning the corresponding mode has been set. The module is defaulted mode I (1). Working mode (I, II, III, IV) can be set in field referring to the corresponding parameters (1, 2, 3, 4). Program the module before installation, use proper mode according to the field conditions.
Page 2
Mode
Used Address
Controlled devices
Type of Alarm Signal
Mode I
One
C-9403 C-9404
Continuous alarm signal
Mode II
Two
C-9402
Low address: pre-alarm signal High address: Fire alarm signal
Mode III
One
C-9402
Fire alarm signal
Mode IV
Two Low address: pre-alarm signal High address: continuous alarm signal
C-9402
3
1
1
C-9402
Z1 Z2
L+
I-9308
L-
D2
D1
24VDC
2
4
6
5
3
2
4
6
5
Fire Alarm Control Panel
4.7kΩ Resistor
D
D
L-
Z2
D2
I-9308
D1
Z1
L+
2
K
2
Z
S
1
K
Z
1
1
D
2
G
K
Z
2
2
S
K
1
1
Z
2
D
G
1
24VDC
4.7kΩ Resistor
C-9403/C-9404 C-9403/C-9404
Fire Alarm Control Panel
Operating Voltage
Loop: Loop 24V (16V~28V) Power: 24VDC (20VDC~28VDC)
Standby Current
Loop ≤1.5mA Power 10mA
Action Current
Loop ≤4mA Power 500mA
Output Control Mode
Pulse
Alarm Mode
Mode, Mode , Mode , Mode . Different addresses.
Programming Method
Electronically addressed with 1 242, occupies one or two addresses.
Indicators
Fault LED: yellow, illuminates when the circuit is short, broken or power cut. Action LED: red, flashes when polling, and illuminates on receiving start signal.
Ingress Protection Rating
IP30
Operating Temperature
-10℃~+50 Relative Humidity
95%, non-condensing
Material and Color of Enclosure
ABS, white (RAL 9016)
Dimension (L×W×H)
120mm×80mm×43mm (with base)
Weight
About 195g (with base)
Model
Name
Remark
P-9910B
Hand Held Programmer
Order separately B-9310
Back Box
Order separately
500ms
1000ms
420ms 280ms
This Data Sheet is subject to change without notice. Please contact GST for more information or questions.
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532
service.gst@fs.utc.com www.gst.com.cn
Pulse durations of pre-alarm and fire alarm are shown in Fig.4 and Fig. 5.
Fig. 4
Fig. 5
Specification
Applications
Accessories and Tools
The module can connect with C-9402 directly. It can generate pre-alarm signal or fire alarm signal when there is fire information. The system connection is shown in Fig. 6.
Limited Warranty
Fig. 6
The module can connect with C-9403, C-9404 directly. It can generate continuous alarm signal when there is fire information. The system connection is shown in Fig. 7.
Fig. 7
30303456 Issue 4.04
GST warrants that the product will be free of charge for repairing or removing from defects in design, materials and workmanship during the warranty period. This warranty shall not apply to any product that is found to have been improperly installed or used in any way not in accordance with the instructions supplied with the product. Anybody, including the agents, distributors or employees, is not in the position to amend the contents of this warranty. Please contact your local distributor for products not covered by this warranty.