GST I-9301 User Manual

30303029 Issue 4.03
Features
Electronically addressed. The address can be
modified in field.
intelligently.
Insulation technology for input signal, good
anti-interference ability.
Cable checking. Plug-in structure.
Description
With a microprocessor, I-9301 Addressable Single I/O Module can communicate with fire alarm control panel (FACP), check power cut, control output and LED.
The module closes the output relay and illuminates the LED when receiving start command from fire alarm control panel.
Connection and Wiring
Terminals on the module are shown as Fig. 1.
9
10
15
16
8
7
2
1
D1
D2
Z1
Z2
V+ G
COM1
NO1 NC1
GST-LD-8301/I-9301
Mounting Hole
Mounting Hole
Mounting Direction
Fig. 1
Z1,Z2:Connecting with loop of FACP, polarity-insensitive. D1, D2: Polarity-insensitive 24VDC power line. V+,G:24VDC output terminals, supplying output contact with +24V output signal . There is 24V output at V+ and G no matter whether the module is started or not. NC1, COM1, NO1: Normally closed or normally open output terminals.
Recommended Wiring
1.5mm
2
or above fire cable for 24VDC power line,
1.0mm
2
or above fire cable for other terminals, subject
to local codes.
Installation
The module is simply plugged onto the base after corresponding terminals are connected.
Conduit
Electric Box
Module
Conduit
B-9310 Back Box
Module
Fig. 2 Fig. 3 If the cable conduit is inside the wall, the base is
installed onto the electric box (Fig. 2). If the cable conduit is on the surface of the wall, the B-9310 Back Box is available.
Note the upward arrow for mounting direction (Fig.1).
Application
The module is designed to connect with the devices controlled by fire alarm control panel, including smoke exhauster, fan blower, and fire valve.
Address can be set through P-9910B programmer in field, refer to P-9910B Hand Held Programmer Installation and Operation Manual for specific operation.
Mode of checking feedback signal can be set through P-9910B programmer. After unlocking the programmer, press Function and then number “4”, i nput “13” or “40”. “13” means checking the feedback signal at any time, “40” means checking feedback signal only in started state. Press Program, if P appears on the screen, the setting is successful. The module can directly drive a smoke exhauster or fire valve (electrical tripping device). System composition is shown in Fig. 4.
The Intelligent Solution
I-9301
Addressable Single I/O Module
548h/02
30303029 Issue 4.03
Fig. 4 System composition for volt-free output contact controlling field device is shown in Fig. 5.
Fig. 5
Note: Don’t connect the module’s contact to the AC control loop directly, preventing the strong AC interference signal from damaging the module or controlled device.
The module is not used for gas extinguishing devices.
Specification
Operating Voltage Loop: 24V
Power: 24VDC Quiescent Current Loop1mA Power≤2mA Action Current Loop≤3mA Power≤15mA Output Capacity
Output contact capacity is 24VDC/5A
Voltage output capacity is 24VDC/1A
Output Control Mode Relay normally open/normally closed
volt-free output Addressing Electronically addressed Addressing Range Occupying one address, selectable
within 1242. LED Red, flashes when polling, illuminates in
action. Ingress Protection Rating
IP30
Operating Temperature
0+49
Relative Humidity 93%, non condensing Material and Color of Enclosure
ABS, White (RAL 9010)
Dimension (L×W×H)
120mm×80mm×39mm
Weight About 194g (with base)
Accessories and Tools
Model Name Remark
P-9910B Hand Held
Programmer
Supplied separately
B-9310 Back Box
Supplied separately
Limited Warranty
GST warrants that the product will be free from defects
in design, materials and workmanship during the warranty period. This warranty shall not apply to any product that is found to have been improperly installed or used in any way not in accordance with the instructions supplied with the product. Anybody, including the agents, distributors or employees, is not in the position to amend the contents of this warranty. Please contact your local distributor for products not covered by this warranty.
GST China Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004 Tel: +86 (0) 335 8502528 Fax: +86 (0) 335 8508942
sales@gst.com.cn www.gst.com.cn
GST UK Global System Technology PLC
Lion Court, Staunton Harold Hall, Melbourne Road, Ashby de la Zouch, Leicestershire, England LE65 1RT Tel: +44 1283 225 478 Fax: +44 1283 220 690
info@gst.uk.com www.gst.uk.com
GST Dubai Global System Technology PLC
PO Box 17998 Unit ZA04 JEBEL ALI Free Zone, Dubai, UAE Tel: +971 (0) 4 8833050 Fax: +971 (0) 4 8833053
info@gst.uk.com www.gst.uk.com
This document is subject to change without notice. Please contact GST for more information or questions.
Z2
Z1
GND
+24V
Electrical Tripping Device
COM1
Z1
G
D1
V+
D2
NO1
Z2
I-9301
Z2
NO1
D2
V+
D1
G
Z1
COM1
Controlled Device
+24V GND
Z1 Z2
Control Input
I-9301