Features
Electronically addressed. Built-in microprocessor stores 14 history data. Drift compensation to suit environment changing
extensively.
Combined smoke and heat algorithm greatly
improves detector performance.
Self-diagnostic. Removable innovative sensing chamber, easy for
maintenance.
Reporting dirt fault for contaminated chamber. Remote indicator output available. Designed to comply with EN 54-5/EN 54-7
standards.
Description
I-9101 Intelligent Combination Heat/Photoelectric Smoke Detector integrates photoelectric detection and fixed temperature and rate of rise detection technology by combining smoke sensor and heat sensor in mechanism and circuitry structure. Just because of the combination of smoke detection and heat detection, I-9101 detector not only overcomes the disadvantage that detectors using common infrared scattering technology are insensitive to black smoke with small particles, but also can pick up fire with obvious rise of temperature such as alcohol flame, thus extending its application range.
Connection and Cabling
Fig. 1 shows the detector bottom and Fig. 2 the base.
100mm
C
25mm
5mm
03mm
45mm~75mm
Mounting Hole
Z
-
0
3
D
Fig.1 Fig.2
There are four terminals with numbers on the base.
1&3: Loop connection (non-polarized) 2: Positive terminal of remote indicator
4: Negative terminal of remote indicator
Recommended Cabling
1.0 mm2 or above fire cable for detector loop, laid out through metal conduit or flame-retardant conduit. Subject to local codes.
Installation
A fixed installation direction is ensured by the location elements on the detector and the base. Fix the base with two tapping screws, and then align mark C on the detector with A on the base, rotate the detector to align mark C with mark B (Refer to Fig. 1 and 2 for the position of the marks), the detector will be fitted to the base. Mounting of the detector is shown in Fig. 3.
Conduit
Detector
Base
Back Box
Fig.3
Application
The detector can be electronically addressed by a programmer. Please refer to P-9910B Hand Held Programmer Installation and Operation Manual for details.
The Intelligent Solution
I-9101 Intelligent Combination
Heat/Photoelectric Smoke Detector
30307848 Issue 1.01
Specification
Operating Voltage
loop 24V (16V~28V)
Standby Current
0.8mA Alarm Current
5.0mA
Indicator
Red. Flashes in normal, and illuminates in alarm
Remote Indicator Output
Directly connecting with indicator (built-in 5.1kΩ resistor, maximum output current is 5.0mA). Quiet in normal condition. Illuminates steadily in alarm.
Alarm Temperature
58 Class
A2R
Rate of Response
3/min
Programming Method
Electronically programming Code Range
one address within 1242.
Wiring
Non-polarized 2-core for loop. Polarized 2-core for remote indicator.
Ingress Protection Rating
IP22 Environment Temperature
-10℃~+50
Relative Humidity
95%, non condensing
Material of Enclosure
ABS
Dimensions
Diameter: 100mm Height: 56mm(base)
Mounting Hole Distance
45mm75mm Weight
About 120g
Maintenance
The detector should be installed just before
commission and kept well before installation. Corresponding measures should be taken for dust-proof, damp-proof and corrosion-proof.
Dust covers are an effective way to limit the entry
of dust into smoke detector sensing chambers. Therefore, the dust cover should not be removed until the building starts to be used.
Clean the detector at least once 1 year to ensure
normal operation of the system.
If unwanted alarms are often found of the detector
on site, the sensing chamber should be cleaned. Power must be removed from the detector before cleaning.
Before cleaning the detector, notify the proper
authorities that the system is undergoing maintenance and will be temporarily out of service. Disable the zone or system undergoing maintenance to avoid any unwanted alarms.
The detector should be tested again after cleaning
and re-installing. Notify the proper authorities when the system is back in service.
Fire simulation test should be done to the detector
at least once 6 months.
Accessories and Tools
Model
Name
Remark
P-9910B
Hand held programmer
Order separately DZ-03
Base
Order separately
Limited Warranty
GST warrants that the product will be free of charge
for repairing or replacing from defects in design, materials and workmanship during the warranty period. This warranty doesnt cover any product that is found to have been improperly installed or used in any way not in accordance with the instructions supplied with the product. Anybody, including the agents, distributors or employees, is not in the position to amend the contents of this warranty. Please contact your local distributor for products not covered by this warranty.
GST TURKEY
Turkish Distributor:- Alfa Elektronik Yapi Donanimlari LTD STI, Gersan Sanayi Sitesi 2308, Sokak No. 87, 06770 Ergazi, Ankara-Turkey www.alfamax.com.tr
GST CHINA Global System Technology PLC
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004 Tel: +86 (0) 335 8502528
GST UK Global System Technology PLC
Lion Court, Melbourne Road, Leicestershire, LE651RT, United Kingdom Tel: +44 1283 225 478 Fax: +44 1283 220 690 info@gst.uk.com www.gst.uk.com
This document is subject to change without notice. Please contact GST for more information or questions.
Loading...