![](/html/e6/e690/e690c23b9a30fc2496907ea39b2be9cd62381330d8e2d14c83042165c199b8c3/bg1.png)
30307848 Issue 1.01
Features
Electronically addressed.
Built-in microprocessor stores 14 history data.
Drift compensation to suit environment changing
extensively.
Combined smoke and heat algorithm greatly
improves detector performance.
Self-diagnostic.
Removable innovative sensing chamber, easy for
maintenance.
Reporting dirt fault for contaminated chamber.
Remote indicator output available.
Designed to comply with EN 54-5/EN 54-7
standards.
Description
I-9101 Intelligent Combination Heat/Photoelectric
Smoke Detector integrates photoelectric detection and
fixed temperature and rate of rise detection technology
by combining smoke sensor and heat sensor in
mechanism and circuitry structure. Just because of the
combination of smoke detection and heat detection,
I-9101 detector not only overcomes the disadvantage
that detectors using common infrared scattering
technology are insensitive to black smoke with small
particles, but also can pick up fire with obvious rise of
temperature such as alcohol flame, thus extending its
application range.
Connection and Cabling
Fig. 1 shows the detector bottom and Fig. 2 the base.
25mm
5mm
03mm
45mm~75mm
Mounting
Hole
Z
-
0
3
D
Fig.1 Fig.2
There are four terminals with numbers on the base.
1&3: Loop connection (non-polarized)
2: Positive terminal of remote indicator
4: Negative terminal of remote indicator
Recommended Cabling
1.0 mm2 or above fire cable for detector loop, laid out
through metal conduit or flame-retardant conduit.
Subject to local codes.
Installation
A fixed installation direction is ensured by the location
elements on the detector and the base. Fix the base
with two tapping screws, and then align mark C on the
detector with A on the base, rotate the detector to align
mark C with mark B (Refer to Fig. 1 and 2 for the
position of the marks), the detector will be fitted to the
base.
Mounting of the detector is shown in Fig. 3.
Conduit
Detector
Base
Back Box
Fig.3
Application
The detector can be electronically addressed by a
programmer. Please refer to P-9910B Hand Held
Programmer Installation and Operation Manual for
details.
I-9101 Intelligent Combination
Heat/Photoelectric Smoke Detector
![](/html/e6/e690/e690c23b9a30fc2496907ea39b2be9cd62381330d8e2d14c83042165c199b8c3/bg2.png)
30307848 Issue 1.01
Specification
Red. Flashes in normal, and
illuminates in alarm
Directly connecting with indicator
(built-in 5.1kΩ resistor, maximum
output current is 5.0mA). Quiet in
normal condition. Illuminates
steadily in alarm.
Electronically programming
Code Range
one address within 1~242.
Non-polarized 2-core for loop.
Polarized 2-core for remote
indicator.
Ingress
Protection
Rating
IP22
Environment
Temperature
Diameter: 100mm
Height: 56mm(base)
Maintenance
The detector should be installed just before
commission and kept well before installation.
Corresponding measures should be taken for
dust-proof, damp-proof and corrosion-proof.
Dust covers are an effective way to limit the entry
of dust into smoke detector sensing chambers.
Therefore, the dust cover should not be removed
until the building starts to be used.
Clean the detector at least once 1 year to ensure
normal operation of the system.
If unwanted alarms are often found of the detector
on site, the sensing chamber should be cleaned.
Power must be removed from the detector before
cleaning.
Before cleaning the detector, notify the proper
authorities that the system is undergoing
maintenance and will be temporarily out of service.
Disable the zone or system undergoing
maintenance to avoid any unwanted alarms.
The detector should be tested again after cleaning
and re-installing. Notify the proper authorities
when the system is back in service.
Fire simulation test should be done to the detector
at least once 6 months.
Accessories and Tools
Limited Warranty
GST warrants that the product will be free of charge
for repairing or replacing from defects in design,
materials and workmanship during the warranty period.
This warranty doesn’t cover any product that is found
to have been improperly installed or used in any way
not in accordance with the instructions supplied with
the product. Anybody, including the agents,
distributors or employees, is not in the position to
amend the contents of this warranty. Please contact
your local distributor for products not covered by this
warranty.
GST TURKEY
Turkish Distributor:- Alfa Elektronik
Yapi Donanimlari LTD STI, Gersan
Sanayi Sitesi 2308, Sokak No. 87,
06770 Ergazi, Ankara-Turkey
www.alfamax.com.tr
GST CHINA
Global System Technology PLC
No. 80, Changjiang East Road,
QETDZ, Qinhuangdao, Hebei,
P. R. China 066004
Tel: +86 (0) 335 8502528
GST UK
Global System Technology PLC
Lion Court, Melbourne Road,
Leicestershire, LE651RT,
United Kingdom
Tel: +44 1283 225 478
Fax: +44 1283 220 690
info@gst.uk.com
www.gst.uk.com
This document is subject to change without notice. Please contact GST for more information or questions.