GST-NRP00/GST-NRP00-HU/GST-NRP00-PT
Network Repeater Panel Installation and Operation Manual
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
Do not attempt to install, service, or operate this unit until this manual is read and
understood.
This equipment must be installed in accordance with these instructions and the
appropriate national, regional and local regulations specific to the country and
location of the installation. Consult with the appropriate Authority Having
Jurisdiction (AHJ) for confirmation of the requirements.
It shall only be installed and serviced by trained specialist.
Disconnect all sources of power before servicing.
Page 1
GST-NRP00/GST-NRP00-HU/GST-NRP00-PT
Network Repeater Panel Installation and Operation Manual
Chapter 1 Product Introduction
GST-NRP00/GST-NRP00-HU/GST-NRP00-PT Network Repeater Panel is simple
installation, operation, and easy maintenance. It is used in fire alarm system with the
following features:
1The LCD can display 8 lines in total and 18 characters each line, assisting the 15
LEDs to display important information.
2The memory does not lose data even if power supply is accidentally removed.
3RS485 interface enables networking.
Page 2
GST-NRP00/GST-NRP00-HU/GST-NRP00-PT
Network Repeater Panel Installation and Operation Manual
Chapter 2 Technical Specifications
2.1 Electrical Specifications
Voltage: 20VDC27VDC
Current is less than 350mA normally and less than 500mA in fire condition.
Standby power consumption does not exceed 9W and maximum power
consumption does not exceed 13W.
2.2 Communication Loop Parameters
2 channels of RS485 interface.
Transmission media: twisted pair.
Communication distance: less than 1200m.
2.3 Dimensions
The dimensions of the repeater panel is 390mm×270mm×100mm (L x H x W) as shown
in Fig. 2-1.
390
100
75
Fig. 2-1
Page 3
GST-NRP00/GST-NRP00-HU/GST-NRP00-PT
Network Repeater Panel Installation and Operation Manual
Chapter 3 Structure
3.1 Appearance and Internal Structure
The network repeater panel is flush mounted. Its appearance and internal structure are
shown in Fig. 3-1 and 3-2.
1
3
2
4
Fig. 3-1
1 Clock 2 LCD 3 Indicators4 Keypad
Fig. 3-2
1 Main board2 Switch board3 LCD4 Network board 5 Speaker
6 DC-DC Power supply 7 Terminal board
3.1.1Description of LEDs
FIRE: Red. It illuminates when the repeater panel receives a fire alarm message
from fire alarm control panels (FACP) in network. After fire condition is removed,
the fire status can only be cleared by pressing RESET key, and this LED goes out
simultaneously.
COMMON FAULT: Yellow. It illuminates when it receives fault messages from
FACPs innetwork or when there is fault with itself. It goes out automatically after
Page 4
GST-NRP00/GST-NRP00-HU/GST-NRP00-PT
Network Repeater Panel Installation and Operation Manual
the fault condition is removed.
DISABLE: Yellow. It illuminates when the repeater panel receives, from FACPs in
network, disabled messages of connected devices, FP.E. output or SOUNDER
CIRCUIT OUTPUT. It goes out when such status is canceled.
SYSTEM FAULT: Yellow. It illuminates if the program encounters a dead halt. After
the system is rebooted, only by pressing RESET, can system fault be cleared, and
this LED goes out.
PRE-ALARM: Red. It illuminates if there is pre-alarm message.
POWER ON: Green. It illuminates when system power is normal.
POWER FAULT: Yellow. It illuminates when the repeater panel receives message
of fault with FACPs in network. After the fault is cleared, it will go out.
F.P.E. FLT/DISABLE: Yellow. It flashes when the repeater panel receives message
of fault with F.P.E. output and illuminates steadily after the F.P.E. is disabled. It
goes out after the fault and disabled conditions are cleared.
SOUNDER FLT: Yellow. It illuminates when the repeater panel receives message of
fault with the SOUNDER CIRCUIT OUTPUT of FACPs in network. It goes out
automatically after the fault is cleared.
SOUNDER DISABLE: Yellow. It illuminates steadily after the SOUNDER CIRCUIT
OUTPUT of FACPs in network is disabled. It goes out automatically after the
disabled condition is cleared.
TEST MODE: Yellow. It illuminates when the repeater panel is under commission.
SILENCE: Yellow. It illuminate after SILENCE key is pressed, and goes out when
RESET key or EVAC key is pressed.
EVAC: Red. It illuminates after EVAC key is pressed and goes out when RESET or
SILENCE key is pressed.
3.1.2Description of Keys
SYSTEM: System set-up key (manager password required), used for setting
system time, modifying operator password and manager password, setting network
system, and system initialization.
TEST: Self-test key (operator password required). Pressing this key in normal
standby state can self-test the audible and visual indication.
MODE: Mode setting key (operator password required). Pressing this key can set
the LCD contrast, message display modes, manually start device and manually
stop device.
TAB: For switching different type of messages in display screen; for moving the
cursor under input screen.
RESET: Resetting the repeater panel or FACPs in network (operator password
required).
BROWSE:Browsing network information.
Page 5
GST-NRP00/GST-NRP00-HU/GST-NRP00-PT
Network Repeater Panel Installation and Operation Manual
LOG: Viewing history record.
MUTE: Pressing this key can silence the sound of FACPs and GST-NRP01
repeater panels in network.
VIEW FAULT: If the repeater panel is not displaying fault messages, pressing this
key can view fault messages.
LOCK: Locking the keypad when it is unlocked.
,: Scrolling among more than one piece of displayed messages.
ESC: Canceling or quitting the operating menu. If it’s pressed while the repeater
panel is displaying messages, it will resume to display messages of the highest
level.
VIEW DISABLE: If the screen is not displaying disabled messages, pressing this
key can view the disabled messages.
ENTER: Confirming inputs to be valid. In normal standby state, pressing it can
toggle the clock display between month/day mode and hour/minute mode.
SILENCE Pressing it can silence the sounders and close the output of alarm
bell.
EVAC: Pressing this key can start all sounders and bells in the system to evacuate
people.
3.2 Configuration
3.2.1Default Configuration
A standard repeater panel consists of main board, power converter module and display
and operation part.
Main board
Main board is the core of the repeater panel, which contains CPU and interfaces to
other main parts.
Power converter module
The power converter module is used for converting the power supply from 24VDC
to 5VDC.
Display and operation part
This part is used to indicate and display different status of the system, and enables
relative operations through keypad (browsing, setting and etc).
3.2.2Optional Components
Network Card (P-9940AP-9960AP-9960)
The network card is used for connecting GST series FACPs into network. Refer to
Appendix 1 for wiring.
Page 6
GST-NRP00/GST-NRP00-HU/GST-NRP00-PT
Network Repeater Panel Installation and Operation Manual
Chapter 4 Installation
4.1 Configuration Inspection
Before installation, check the following items:
Engineering Configuration
Check the configuration according to packing list. The main items to be examined are:
installation and operation manual, keys to the repeater panel, etc.
Internal Configurations and Interconnections
All internal parts have been connected (including optional units ordered) before the
repeater panel leaves the factory. Therefore, you can mainly check the connection
among parts, including the connection between main board and power converter board,
switch board and network board, the connection of power converter board, network
board and terminal board, and of speaker and main board etc. Please refer to Appendix
1 for the internal connection diagram.
4.2 Installing the Cabinet
Dimension of the cabinet is shown in Fig. 4-1.
Ambient conditions for installation of the repeater panel:
Temperature: 040
Relative humidity: 95, non-condensing
360
300
330
Fig. 4-1
100
75
4.3 Start-up Check
After installation, apply power to it as shown in Fig. 4-2. Turn on the power supply and
check if the repeater panel can self-test. The procedures are as follows.
Check if the digital displays showing time are illuminated one by one.
Check if the LCD showing system messages such as fire alarm is illuminated.
Check iftheLEDs showing the state of system can be illuminated one by one.