GST DI-9204 Installation Manual

30306358 Issue 1.01
Features
Electronically addressed. The address can be
Alarming by pressing. Reset by a special key. Plug-in structure. Designed to comply with EN 54-11.
Description
Connecting to the loop of GST fire alarm system, DI-9204 Digital Manual Call Point (the MCP) is suitable for public places. When there is fire, pressing the glass on the MCP can send the alarm signal to fire alarm control panel. After receiving the signal, the control panel will show address information of the MCP and generate alarm sound.
Connection and Cabling
Terminals on the MCP base are shown as Fig. 1.
Z1Z2Z1Z2
60mm
Fig. 1 Z1, Z2: Connecting to the loop of control panel, polarity-insensitive.
Recommended Cabling
0.5mm
2
or above fire cable, subject to local codes.
Installation
The conduit can be surface mounted or flush mounted.
Surface mounting: First install the back box onto the wall using 4 screws, and then install the base onto the back box. Connect cables to corresponding terminals as described above. Hook the juts of the MCP body to the base, and then press the part below the glass to combine them completely. Fig. 2 shows surface mounting.
Flush mounting: Install the base into the back box. Then combine the
enclosure and base the same as surface mounting. Fig. 3 shows flush mounting.
Base
Back
Box
MCP Body
Fig. 2
Base
Back box
MCP Body
Fig. 3
Application
The MCP should be programmed using P-9910B programmer. Please refer to P-9910B Hand Held Programmer Installation and Operation Manual. Terminal Z1 and Z2 of MCP base can directly connect to the loop of control panel. After correct connection, the control panel should be able to register the MCP. Usage of the key
Vertically insert the key into the key-hole, then push it with force and turn it clockwise. Turn the key back and pull it out when the glass is rebounded.
The Intelligent Solution
DI-9204
Digital Manual Call Point
30306358 Issue 1.01
Compatible Equipment This MCP can be used together with control panels such as GST100, GST200, GST5000 and GST9000.
Specification
Operating Voltage Loop 24V (16V~28V) Standby Current ≤0.6mA Alarm Current ≤1.8mA
Indicator
Red. Flashes once three seconds. Illuminates after
alarming. Type of Initiating Part
Reusable
Initiating Mode Pressing the glass manually Resuming Mode
Manually resumed by a
special key Programming Mode
Electronically addressed Code Range One address within 1~242
Wiring Two-wire, polarity-insensitive Class Type A, indoor use Ingress Protection
Rating
IP43 Ambient
Temperature
-10℃~+55
Relative Humidity 95%, non condensing Material of Enclosure
ABS
Dimension (L×W×H)
87.1mm×87.1mm×58mm
(with back box)
87.1mm×87.1mm×23mm
(without back box) Mounting Hole Distance
60mm
Weight
About 160g (with back box)
About 107g (without back
box)
Accessories and Tools
Model Name Remark P-9910B Hand Held
Programmer
Order separately
Limited Warranty
GST warrants that the product will be free of charge
for repairing or replacing from defects in design, materials and workmanship during the warranty period. This warranty doesn’t cover any product that is found to have been improperly installed or used in any wa y not in accordance with the instructions supplied with the product. Anybody, including the agents, distributors or employees, is not in the position to amend the contents of this warranty. Please contact your local distributor for products not covered by this warranty.