30309533 Issue 1.04
Features
Strong environmental adaptability due to drift
compensation.
Self-diagnostic.
Reed switch testing.
Removable innovative sensing chamber, easy for
maintenance.
Dirty chamber checking.
Fire LED allows 360°viewing
Remote indicator output available.
Polling LED can be set to close.
2 levels smoke sensitivities programmable, level 1
complies with EN 54-7. Heat part complies with EN
54-5.
Description
DI-9101E Intelligent Combination Heat Photoelectric
Smoke Detector integrates photoelectric detection and
fixed temperature and rate of rise detection technology
by combining smoke sensor and semi-conductor heat
sensor in mechanism and circuitry structure. Just
because of the combination of smoke detection and heat
detection, it not only overcomes the disadvantage that
detectors using common infrared scattering technology
are insensitive to black smoke with small particles, but
also can pick up fire with obvious rise of temperature
such as alcohol flame, thus extending its application
range.
Connection and Cabling
Fig. 1 shows the detector bottom and Fig. 2 DB-01 base.
Fig. 1 Fig. 2
There are four terminals with numbers on the base.
1&3: Loop connection (polarity-insensitive)
2: Positive terminal of remote indicator
4: Negative terminal of remote indicator
Recommended Cabling
1.0mm2 or above fire cable is recommended, laid
through metal or flame-retardant conduit, but subject to
local codes. Different color cables for remote indicator
are used to avoid wiring mistake.
Installation
A fixed installation direction is ensured by the location
elements on the detector and the base. Fix the base with
two tapping screws, and then align mark A on the
detector with B on the base, rotate the detector to align
mark A with mark C (Refer to Fig. 1 and 2 for the position
of the marks), the detector will be fitted to the base.
Fig. 3 shows the installation of the detector.
51.5mm
Electrical Box
Conduit
Base
Detector
Fig. 3
Application
The detector can be addressed in field by using P-9910B
programmer. Please refer to P-9910B Hand Held
Programmer Installation and Operation Manual for
details.
In power-on state, input unlocking password and press
Clear to unlock. Press Function, then press “3”, the
screen shows “-” at the last digit.
Input corresponding sensitivity or parameter and press
Program, the screen will show a “P”, the corresponding
sensitivity or parameter is programmed. Press Clear to
clear the "P". Input locking password and press Clear to
return.
Rate of rise and level 1 is defaulted.
Parameters set using programmer
Input Parameter
of a Detector
Read Sensitivity Level: in power-on state, pressing Test,
the screen displays address of the detector. Pressing
“Up”, display sensitivity level, device type and initial
sensitivity in turns.
Testing
Before testing, please ensure that the detector has
been installed correctly and powered up. After 10
seconds, testing begins.
1) The detector must be tested after installation and
periodical maintenance.
2) Testing method
a) Reed Switch Testing
Magnetic test zone is shown in Fig. 4. Put the
magnet of commission tool close to that of the
detector and hold on for a few seconds until the
detector generates alarm.
DI-9101E Intelligent Combination
Heat Photoelectric Smoke Detector
0832-CPR-F0339
GST-0507-01
14
![](/html/39/397b/397bb20472f7c9416fee65db93f33ba93bcc7ce78f2cbee4414a4522c4e90632/bg2.png)
Fig. 4
b) Smoke test
Taking a smoldering cotton rope close to the
detector, blow the smoke into the detector until the
detector generates alarm.
c) Temperature test
Approach a heater (such as a hair drier) to the
thermistor of the detector until it alarms.
3) After testing, reset the detector. Notify the proper
authorities that the system is back to normal
operation.
If a detector fails in testing, clean it by the steps in
Maintenance, and retest it. If it still fails, return it for
repair.
Maintenance
The detector should be installed just before
commissioning and kept well before installation,
taken corresponding measures for dust-proof,
damp-proof and corrosion-proof.
The dust-proof cover should not be removed until
the project is plunged into usage. Otherwise it may
not report alarm properly.
Clean the detectors regularly, at least once a year
to ensure normal operation of the system.
If unwanted alarms are often found of the detector
on site, the sensing chamber should be cleaned.
Power must be removed from the detector before
cleaning.
Steps for chamber cleaning:
a) Open the top cover of detector, and draw out
the sensing chamber by slightly lifting its two
sides using a straight screwdriver, as shown in
Fig. 5.
Fig. 5
b) Clean the internal of the chamber by alcohol
cotton swab with tweezers or using clean water
and brush. Make sure not to leave any fiber in
the chamber.
c) Put back the chamber and the top cover.
Before cleaning, notify the proper authorities that
the system is under maintenance and will
temporarily be out of service. Disable the automatic
controls relating to the zone or system under
maintenance to avoid unwanted actions.
The detector should be tested after re-installed to
ensure normal operation.
Fire simulation test should be done to the detector at
least every 6 months.
Specification
≤1.8mA (without remote indicator)
≤ 3.8mA (with remote indicator)
Red. Flashes in polling, and
illuminates in alarm
Polarized output. Directly connect
to remote indicator (built in 10k
resistor in series, output current is
2mA); Flash in alarming and do
not illuminate in normal.
Electronically programming
Non-polarized 2-core for loop.
Polarized 2-core for remote
indicator.
Setting of sensitivity
and range
The sensitivity can be set by
programmer with two levels: Level
1(default), level 2.
Ingress Protection
Rating
Diameter: 100mm
Height: 54.5mm (with base)
WEEE Information
2012/19/EU (WEEE directive): Products marked
with this symbol cannot be disposed of as unsorted
municipal waste in the European Union. For proper
recycling, return this product to your local supplier
upon the purchase of equivalent new equipment, or
dispose of it at designated collection points.
Limited Warranty
GST warrants that the product will be free of charge for repairing
or replacing from defects in design, materials and workmanship
during the warranty period. This warranty does not cover any
product that is found to have been improperly installed or used
in any way not in accordance with the instructions supplied with
the product. Anybody, including the agents, distributors or
employees, is not in the position to amend the contents of this
warranty. Please contact your local distributor for products not
covered by this warranty.
This document is subject to change without notice. Please contact GST for more information or questions.
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532 service.gst@fs.utc.com www.gst.com.cn