GST C-9402 User Manual

30306067 Issue 1.02
Features
Used as the base of detectors or as the sounder.
Description
Connection and Cabling
Fig. 1 shows terminals of the sounder.
A
B
Mounting Hole
Fig. 1
Refer to Application for connection.
Recommended Cabling
1.0mm2 or above fire cable, subject to local codes.
Installation
Warning: Before installing the sounder, disconnect the power from loop and verify that all the bases are securely installed and that the cabling is correct on each base.
1 Before installation, first check the enclosure without scrapes and distortion, the labels should be complete. 2 Mounting of the sounder is shown in Fig. 2.
Back Cover
Base
Sounder
Top Cover or Detector
Back Box
Fig.2
3 Fix the sounder to the back box with screws. 4 Align the orientation mark of the top cover to mark A (refer to Fig.1), rotate the sounder to align the mark with mark B, the top cover is installed. If it's used as detector base, take down the top cover and install the detector on it in the same method as mounting the top cover.
Application
The sounder can be used as a base to install intelligent heat or smoke detectors to combine detection and alarm. It can also be used as a sounder.
The audible control part of the sounder has two wires. Used as the sounder, it needs separate wiring to connect with detectors. The sounder can be directly connected to I-9308 module, which occupies two consecutive address points. When there is fire alarm message, it activates low address to give pre-alarm sound, activates high address to give fire alarm sound. System wiring is shown in Fig. 3.
Sounder
Sounder
24VDC
Fire Alarm Control Panel
4
6
3
5
4
6
5
2
3
2
I-9308
D2D1
Z1
L+
1
1
L-
Z2
Ω
Resistor
Fig. 3
"5" of the sounder connects to "L+" of I-9308 module. "6" of the sounder connects to "L-" of I-9308 module.
The "5" and "6" of the last sounder in the system should be connected with a 4.7kΩ terminal resistor. The sounder can also be used as detector base to mount different detectors, which can both detect fire and give audible alarm signal to realize combined function. Remove the top cover and mount the intelligent or conventional detector.
C-9402
Conventional Base Mount Sounder
30306067 Issue 1.02
When mounting intelligent detector on the sounder, first wire according to Fig. 3, then refer to Fig.4.
Intelligent Detector
3
1
1
Fire Alarm Control Panel
Intelligent Detector
Z1
Z2
L+
I-9308
L-
D2
D1
2
4
6
5
3
2
4
6
5
24VDC
Fig. 4
"1" and "3" of the sounder connect to loop, polarity-insensitive. "2" and "4" don't connect to any wire, but are used to fix the detector accessorily.
When mounting conventional detectors on the sounder, I-9319 Intelligent Zone Monitor Unit should be added to the system and a P-9907 Active End of Line Unit connected to the end of the loop. First wire according to Fig. 3, then refer to Fig. 5.
Conventional Detector
3
1
1
Fire Alarm Control Panel
Conventional Detector
Z1
Z2
L+
I-9308
L-
D2
D1
24VDC
2
4
6
5
3
2
4
6
5
I-9319
Z1
O-
Z2
O+
3
Diode
Diode
P-9907 Active End of Line Unit
Fig. 5
"1" of the sounder connects to "O+" of the zone monitor unit.
"3" of the sounder connects to "O-" of the zone monitor unit.
An 1N5819 diode (please note polarity) should be connected between 1 and 2 of the sounder.
"2" of the sounder connects to "1" of the next equipment as anode of output power.
"2" and "3" of the last sounder connect to end of line unit. "4" of the sounder doesn't connect to any wire, but is used to fix the detector accessorily
Specification
Operating Voltage
24VDC
Alarm Current
15mA
Sound Level
85dB (1m horizontally ahead (A weighted))
Type of Alarm Signal
Pre-alarm: Intermittent (0.5s on 1s off) Fire Alarm: Continuous
(0.4s on 0.3s off)
Ingress Protection Rating
IP31
Operating Temperature
-10℃~+50 Relative Humidity
95%, non condensing
Material and Color of Enclosure
ABS, white (RAL 9016)
Dimension
Diameter: 120mm Height: 38.8mm(without top
cover)
Weight
About 130g
Accessories and Tools
Model
Name
Remark
I-9308
Addressable Sounder Circuit Module
Order separately
Top cover
Order separately
Limited Warranty
GST warrants that the product will be free of charge
for repairing or replacing from defects in design, materials and workmanship during the warranty period. This warranty shall not apply to any product that is found to have been improperly installed or used in any way not in accordance with the instructions supplied with the product. Anybody, including the agents, distributors or employees, is not in the position to amend the contents of this warranty. Please contact your local distributor for products not covered by this warranty.
This Data Sheet is subject to change without notice. Please contact GST for more information or questions.
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532
service.gst@fs.utc.com www.gst.com.cn
Loading...