GST C-9102 Installation And Operation Manual

C-9102 (UL) Conventional
Photoelectric Smoke Detector
Installation and Operation Manual
(Issue 1.04, July 2012)
C-9102 (UL) Conventional Photoelectric Smoke Detector Installation and Operation Manual
CONTENTS
I General ................................................................................................................ 1
II Features ............................................................................................................... 1
III Technical Specifications ....................................................................................... 1
IV Structure and Operation Principle ........................................................................ 2
V Mounting and Wiring ............................................................................................ 2
VI Testing .................................................................................................................. 4
VII Troubleshooting ................................................................................................... 5
VIII Maintenance ......................................................................................................... 6
IX Cautions ............................................................................................................... 6
X Quality Warranty .................................................................................................. 7
C-9102 (UL) Conventional Photoelectric Smoke Detector Installation and Operation Manual
Page 1
I General
C-9102 (UL) Conventional Photoelectric Smoke Detector (hereinafter called the detector) is a non-addressable detector, applicable to hotels, restaurants, office buildings, teaching buildings, banks, warehouses, libraries, computer rooms and switch rooms, etc. It can be connected with compatible fire alarm control panel (FACP) through a 4.7kΩ terminal resistor to detect fire.
II Features
The detector adopts the latest scattering technology and excellent photoelectric components, improving the reliability, stability and conformity of the sensor. With special optical sensing chamber, it has high ability of insect-proof, dust-proof, and interference-proof of external rays. With novel structure and attractive appearance, the detector has stable and reliable performance and high damp-proof ability.
III Technical Specifications
1. Operating Voltage: 12VDC28VDC
2. Operating Current: Standby Current:60μA Alarm Current: 10mAI30mA
(Note: The alarm current depends on the current limit of the FACP. It’s not
allowed to power the detector directly by 24VDC. Otherwise the detector will be blown as a result of without current limiting resistor.)
3. Alarm Reset: Instantaneous Cut-out (5s MAX, 2.5VDC MAX)
4. Initiating Time:10s
5. Sensitivity:1.23%/ft2.02%/ft
6. Maximum Ripple Voltage: 4V(peak-to-peak value)
7. Alarm Confirming LED: Red, not lit when in normal operation, constantly lit when
alarming.
8. Monitoring Area: When space height is 6m12m, the monitoring area of a detector
is 80m2 for normal protection area; When space height is less than 6m, it is 60 m2.
9. Wiring: Connecting with the power cable by polarized two-wire.
10. Operating Environment: Temperature: 0℃~37.8 (UL268) Relative Humidity:95%, non-condensing
11. Dimension: Diameter: 100mm Height: 42mm (without base)
Diameter: 105mm Height: 56mm (with base)
12. Ingress Protection: IP22
13. Material and Color of Enclosure: ABS, ivory white
14. Weight: About 120g
15. Matching Parts: DZ-03 Base
16. Standard Applied: UL268