Changing SIDs/PIDs "manually" (only in "Multiplex mode manual") .. 46
7 Final procedures ..............................................................................................48
- 3 - PADA 5100
1 safetyregulationsandnotes
• Assembly, installation and servicing should be carried out by authorised
electricians.
• Switch off the operating voltage of the system before beginning with assembly or service work or pull out the mains plug.
• Do not perform installation and service work during thunderstorms.
• Install the system so it will not be able to vibrate…
- in a dust-free, dry environment
- in such a manner that it is protected from moisture, fumes, splashing wa-
ter and dampness
- somewhere protected from direct sunlight
- not within the immediate vicinity of heat sources
- in an ambient temperature of 0 °C to +50 °C. In case of the formation of
condensation wait until the system is completely dried.
• Ensure that the head-end station is adequately ventilated. Do not cover the
ventilation slots.
• Beware of short circuits
• No liability is accepted for any damage caused by faulty connections or
inappropriate handling.
• Observe the relevant standards, regulations and guidelines on the installation and operation of antenna systems.
• The standards EN/DIN EN 50083 resp. IEC/EN/DIN EN 60728 must be
observed.
• For further information please read the assembly instructions for the headend station used.
• Test the software versions of the head-end station and the cassette and
update them if necessary. The current software versions can be found at
"www.mygss.eu".
Take action to prevent static discharge when working on the device!
Electronic devices should never be disposed of in the household rubbish. In
accordance with directive 2002/96/EC of the European Parliament and the
European Council from January 27, 2003 which addresses old electronic and
electrical devices, such devices must be disposed of at a designated collection
facility. At the end of its service life, please take your device to one of these
public collection facilities for proper disposal.
- 4 - PADA 5100
2 generalinformation
2.1 PaCk ingCo ntents
1 Cassette PADA 5100
1 LAN cable
6 BNC cable
1 Brief assembly instructions
1 Messprotokoll
2.2 mea ningoft hesy mbolsu s ed
Important note
—> General note
• Performing works
- 5 - PADA 5100
2.3 teChn iC aldata
The devices meet the following EU directives:
2011/65/EU, 2014/30/EU, 2014/35/EU
The product fulfils the guidelines and standards for CE labelling (page 49).
Unless otherwise noted all values are specified as "typical".
The cassette is a 5 to 1 multiplexer. It converts 5 ASI/SPTS/MPTS input channels
into one ASI/MPTS output channel.
Each input transport stream can be fed in
selectively via each one ASI input or the LAN interface (five input IP addresses).
The fed in transport streams can be edited individually and will be combined
into one transport stream in the TPS module.
This transport stream is emitted at the ASI output or the LAN interface (one
output IP address).
Principle signal path:
LAN1: 227.40.50.1
ASI input 1
LAN 2: 227.40.50.2
ASI input 2
LAN 3: 227.40.50.3
ASI input 3
LAN 4: 227.40.50.4
ASI input 4
LAN 5: 227.40.50.5
ASI input 5
TPS
LAN 6: 227.40.50.6
ASI output
For operating the cassette in a LAN network it can be assigned its own hardware
IP address.
—> Two IP address ranges are used:"Hardware" IP addresses (menu ETHERNET), which are used to
connect the cassettes in the network (e.g. 192.168.0.x).
"IPTV" IP addresses (menus OUT-IP, IP-INPUT), which are used to
send and receive the IPTV channels (multicast range 224.5.0.0 …
231.255.255.255e.g. 227.40.50.x).
The LEDs for the LAN interface show whether a network connection exists and
whether a data transfer is in progress.
The cassette is controlled with the head-end station control unit.
When the head-end station is switched on, the two-line LC display shows the
software version of the control unit.
- 7 - PADA 5100
To operate this cassette the software version of the control unit must be "V 45"
or higher. You can find the current operating software for the control unit and
the cassette, the software "BE-Flash" and the current assembly instructions on
the website "www.mygss.eu".
The cassette is intended for use in the
PROFI-LINE
head-end stations.
Five LEDs (page 11 6, 8, 0, @, $) indicate by their colour whether an
input signal is present:
LED colourIndication
GreenSignal present
Redno Signal
2.5 so f t ware q uery
Control unitIf necessary, you can activate the indication of the software version of the
control unit manually:
• Press any two keys on the control unit of the head-end station simultaneously
until the display goes dark and the software version, e.g. "V 45" appears.
CassetteAfter activating the cassette the software version of the cassette is displayed
(see page 16).
- 8 - PADA 5100
3 assembly
3.1 installi ngtheC assette
– Ensure the head-end station is mounted so it will not be able to vibrate.
Avoid, for example, mounting the head-end station onto a lift shaft or any
other wall or floor construction that vibrates in a similar way.
– Before installing or changing a cassette unplug the power cable from the
mains power socket.
• Remove the fastening screws 1 of an unoccupied slot from the bracket of
the head-end station.
• Insert the cassette in this slot and push it into the housing.
• Align the cassette and apply slight pressure to connect it to the connections
of the board and the HF bus bar.
• Fasten the cassette with the screws 1.
1
1
- 9 - PADA 5100
3.2 emC regul ations
To comply with the current EMC regulations, it is necessary to connect the lines
leading in and out of the head-end station using cable terminals.
When mounting the cassette in a head-end station which is installed in a 19"
cabinet, make sure the connections leading in and out for the 19" cabinet are
made using cable terminals.
The attenuation of shielding of the connection lines for ASI and antenna must
KLASSE
CLASS
meet the requirements for "Class A".
• Insert the required number of cable terminals in the openings provided in
the head-end station or in the 19" cabinet.
Tighten the nuts on the cable terminals until the teeth on the lock washer have
penetrated the exterior coating and a good connection is made between the housing and cable terminals.
- 10 - PADA 5100
3.3 Ca ssetteoverv iew
2
3
4
5 ASI input 5
6 Status LED ASI input 5
7 ASI input 4
8 Status LED ASI input 4
9 ASI input 3
0 Status LED ASI input 3
! ASI input 2
@ Status LED ASI input 2
# ASI input 1
^
1 Status LED of the LAN interface (data transfer)
LAN socket
Status LED of the LAN interface (network connection)
%
$
#
@
!
0
9
8
7
6
5
ASI output
$ Status LED ASI input 1
% D-SUB socket "RS 232"
^ Type label + MAC address (at the frame)
4
3
2
1
—> The operating software of the cassette can be updated via the 9-pin
D-SUB socket "RS 232" using a PC or notebook and the software
"BE-Flash". You can find the current operating software on the website "www.mygss.eu".
3.4 Co n n eCtin gtheC assette
• Connect the LAN socket 2.
• Connect the ASI inputs 5, 7, 9, !, # and the ASI output 4 to the
peripheral ASI devices.
- 11 - PADA 5100
4 theControlPanelataglanCe
4.1 menui tems
Programme the
cassette
using the buttons on the control unit of the head-end
station. The two-line display of the control unit then shows the menus.
The parameters and functions to be set are underlined.
Use the key to select the following main menu items:
– Output parameter
– Input parameter
– Transport stream and ORGNET-ID
– NIT
– Refresh tables
– Displaying the data rate
– LAN check
– Factory reset
4.2 Co ntrol Pa n e l
The key pad on the head-end station is used to scroll through the menus:
scrolls forward through the menus.
select parameters in the menus.
set values, initiate actions.
selects sub-menus.
scrolls backward through the menus.
saves all entries.
- 12 - PADA 5100
5 Programming
BE–Remote
please wait …
V 45
Box 4
V 4
TS-MUX
0.128 – – –
Box1
………
……
……
Bx1A
C5-12,S3-24
TWIN-SAT
C07
Böx4
C5-12,S3-24
TWIN-SAT
C07
Box5
………
……
……
+
t > 10 s
Bx 4
stat =>
ETHERNET
Options
stat / DHCP
A
Bx 4
192.168. 0 . 1
IP-GATEWAY
Bx 4
255.255.255. 0
IP-MASK
▶
◀
/
Bx 4
192.168. 0.128
IP-ADDR
▶
◀
/
▶
◀
/
Bx 4
60000
UDP-PORT
▶
◀
/
B
▶
0 … 65535
transparent
fixed
Ein / On
Bx 4MUX-MOD E
manual
Bx 4
0xxx
SID-OFFSET
nur bei Auswahl "16 Bit"
only with selection "16 Bit"
nur bei Auswahl "fixed"
only with selection "fixed"
16 Bit default
8 Bit US
Bx 4
16 Bit
SID-NORM
default
Bedienhinweise
"blättert" Menüs vorwärts.
"blättert" Menüs rückwärts.
wählen die Eingabeposition
wählt Untermenü
stellen Werte ein,.
speichert alle Eingaben.
1zeigt die Eingabeposition
Operating Hints
scrolls forward through the menu.
scrolls backward through the menu.
select the enter position.
selects a submenu.
set values and triggers actions.
saves all entries.