GSS HDTV 1000 MPTS Assembly Instructions Manual

Grundig SAT SystEms
A
CLASS
KLASSE
Head-End HDTV Converter to IP
DVB-S2 to MPTS
HDTV 1000 MPTS
A
KLASSE
CLASS
GSS Grundig SAT Systems GmbH Beuthener Strasse 43
English
Assembly Instructions
D-90471 Nuremberg
Phone: +49 (0) 911 / 703 8877 Fax: +49 (0) 911 / 703 9210 E-mail: info@gss.de Internet: http://www.gss.de
Contents
1 Safety regulations and notes .....................................................................................4
2 General information .................................................................................................5
2.1 Packing contents ..........................................................................................5
2.2 Meaning of the symbols used ........................................................................5
2.3 Technical data .............................................................................................5
2.4 Description .................................................................................................6
2.4.1 Input signal path “INROUTE” ..............................................................7
2.4.1.1 Menu setting “A+ASI=1 B+ASI=2”.......................................7
2.4.1.2 Menu setting “A+B+ASI=1 ASI=2”.......................................7
2.4.2 Output signal path “OUTROUTE” ........................................................8
2.4.2.1 Menu setting “ASI => ASI” ....................................................8
2.4.2.2 Menu setting “1=>ASI ASI=>MA” .......................................8
2.4.2.3 Menu setting “2=>ASI ASI=>MB” ........................................9
2.4.3 General ...........................................................................................9
2.5 Software query ..........................................................................................10
2.6 How the TPS module works .........................................................................10
3 Assembly ...............................................................................................................11
3.1 Installing the cassette ..................................................................................11
3.2 EMC regulations ........................................................................................11
3.3 Cassette overview ......................................................................................12
3.4 Connecting the cassette ..............................................................................13
3.5 Retrofitting a CA module ............................................................................13
4 The control panel at a glance ..................................................................................14
4.1 Menu items ...............................................................................................14
4.2 Control panel ............................................................................................14
5 Programming .........................................................................................................15
5.1
Programming procedure
5.1.1 Channel strips “A” (without CA module) and “B” .................................15
5.1.2 Channel strip “A” with CA module ....................................................18
5.2 Programming the cassette ..........................................................................19
Selecting the cassette, displaying the software version ....................................19
Setting the Ethernet parameters ...................................................................20
Setting the IP address of the cassette ............................................................20
Setting the address range ...........................................................................21
Setting the address of the gateway ..............................................................22
Setting the UDP port ...................................................................................22
Selecting the input signal path .....................................................................23
Selecting the output signal path ...................................................................23
Setting the ASI transfer rate .........................................................................24
Setting the ASI options ...............................................................................25
Selecting the channel strip ..........................................................................26
Switching the IP address off or on ................................................................26
Selecting the transmission protocol ...............................................................26
..............................................................................15
- 2 -
Setting the port number ..............................................................................26
Defining the quantity of data packets ...........................................................27
Setting the forward error correction .............................................................27
Setting the transmission channel ..................................................................27
Setting the output IP address .......................................................................29
Setting the LNB oscillator frequency .............................................................29
Setting the input symbol rate .......................................................................30
Setting the DVB mode ................................................................................30
Setting the input frequency ..........................................................................31
Testing the signal to noise ratio ....................................................................32
Setting the station filter ...............................................................................33
Displaying the output data rate ....................................................................37
Network Information Table (NIT) ..................................................................37
Network/operator identification ..................................................................38
Deleting a PID ...........................................................................................39
Renaming a PID .........................................................................................39
Saving settings ..........................................................................................40
5.2.1 Operation with a CA module ............................................................41
Setting the operating voltage for the CA module .................................41
Setting the PID monitoring ................................................................41
Configuring the CA module ..............................................................42
Decoding services ...........................................................................43
6 Final procedures .....................................................................................................45
- 3 -
1 Safety regulations and notes
• Assembly, installation and servicing should be carried out by authorised electricians.
• Switch off the operating voltage of the system before beginning with as­sembly or service work or pull out the mains plug.
• Do not perform installation and service work during thunderstorms.
• Install the system so it will not be able to vibrate…
- in a dust-free, dry environment
- in such a manner that it is protected from moisture, fumes, splashing water and dampness
- somewhere protected from direct sunlight
- not within the immediate vicinity of heat sources
- in an ambient temperature of -20 °C to +50 °C.
• Ensure that the head-end station is adequately ventilated. Do not cover
the ventilation slots.
• Beware of short circuits
• No liability is accepted for any damage caused by faulty connections or
inappropriate handling.
• Observe the relevant standards, regulations and guidelines on the instal-
lation and operation of antenna systems.
• Earth the SAT receiver in accordance with DIN EN 50083-1 / 60728-11
and VDE 0855 (earthing, equipotential bonding rail).
Test the software versions of the head-end station and the cassette and
update them if necessary. The current software versions can be found at ”www.gss.de”.
• For further information please read the assembly instructions for the
head-end station used.
Take action to prevent static discharge when working on the device.
Electronic devices should never be disposed of in the household rubbish. In
accordance with directive 2002/96/EC of the European Parliament and the European Council from January 27, 2003 which addresses old elec­tronic and electrical devices, such devices must be disposed of at a desig­nated collection facility. At the end of its service life, please take your device to one of these public collection facilities for proper disposal.
- 4 -
2 General information
2.1 Packing contents
1 Cassette HDTV 1000 MPTS 2 HF cables 1 CD (assembly instructions) 1 Brief assembly instructions
2.2 Meaning of the symbols used
Important note
—> General note
• Performing works
2.3 Technical data
The devices meet the following EU directives:
2006/95/EC, 2004/108/EC
The product fulfils the guidelines and standards for CE labelling.
HF input
Frequency range: 925 … 2150 MHz Level range: 60 dBµV … 80 dBµV Return loss: > 8 dB Impedance: 75 Ω DVB-S modes: QPSK 1/2 , 2/3 , 3/4 , 5/6 , 7/8 DVB-S2 modes: QPSK 1/2 , 3/5 , 2/3 , 3/4 , 4/5 , 5/6 , 8/9 , 9/ 8PSK
3
/5 , 2/3 , 3/4 , 5/6 , 8/9 , 9/
10
Symbol rate DVB-S: QPSK: 2 … 45 MSymb/s Symbol rate DVB-S2: QPSK: 10 … 30 MSymb/s 8PSK: 10 … 31 MSymb/s
LAN interface
Standard: 100-BASE-T Data rate: 80 MBit Protocols: UDP (User Data Protocol), RTP (Real-Time Transport Protocol)
- 5 -
10
ASI interfaces
Standard: DIN EN 50083-9 Format: MPEG ISO IEC 13818-1 User data rate: 2 … 90 Mbit/s Impedance: 75 Ω Level (input / output): 800 mV
± 10%
PP
Return loss (input): > 17 dB (5 … 270 MHz)
Connections
SAT inputs: 2 F sockets LAN: 1 RJ 45 socket ASI input: 1 BNC socket, 75 Ω ASI output: 1 BNC socket, 75 Ω Connection strip (10-pin): for supply voltages and control circuits RS 232 socket: serial interface for software update Conditional access: 1 (several channels can be decoded)
2.4 Description
The cassette is a
DVB-S2 / MPTS
converter which combines modulated services (programmes) in accordance with the DVB-S-/DVB-S2 standard and transport streams supplied via the ASI interface in the TPS module. The transport streams are emitted, equipped with IP addresses via the LAN interface. Principle signal path:
IP address: Port: Service 1
Service 2
Channel strip "A"
Channel strip "B"
Service 3 212.40.90 : 1234
Service 4
Service …
Service A
Service B 212.40.91 : 1234
Service C
Service …
For operating the cassette in a LAN network it can be assigned its own IP ad­dress. The cassette has two SAT inputs and one LAN interface. Additionally is equipped with one ASI input and one ASI output (ASI – Asynchronous Serial Interface according to DIN EN 50083-9)
- 6 -
The transport stream fed via the ASI socket can be inserted into the transport streams of the receiving stages via the TPS module. The signal path is set in the menu items input signal path
INROUTE” and output signal path ”OUTROUTE
2.4.1 Input signal path “INROUTE”
2.4.1.1 Menu setting “A+ASI=1 B+ASI=2”
The transport streams of the receiving stage of channel strip ”A” “TS A” and of the ASI input “TS ASI” generate the transport stream 1. The transport streams of the receiving stage of channel strip ”B” “TS B” and of the ASI input “TS ASI” generate the transport stream 2.
CA module
SAT IF
input ”A“
Receiving stage
Empfangsteil
channel strip "A"
"A"
TS A
TPS
Transport stream 1
.
ASI input
SAT IF
input ”B“
Receiving stage
channel strip "B"
TS ASI
TS B
TPS
Transport stream 2
2.4.1.2 Menu setting “A+B+ASI=1 ASI=2”
The transport streams of the receiving stages of channel strips ”A” “TS A”, B” “TS B” and of the ASI input “TS ASI” generate the transport stream 1. “TS ASI
SAT IF
input ”A“
SAT IF
input ”B“
ASI input
transport stream fed via the ASI input generates the transport stream 2.
CA module
Receiving stage
Empfangsteil
channel strip "A"
"A"
Receiving stage
channel strip "B"
TS A
TS B
TS ASI
TPS
Transport stream 1
Transport stream 2
The
- 7 -
2.4.2 Output signal path “OUTROUTE”
2.4.2.1 Menu setting “ASI => ASI”
The transport streams 1 (channel strip “A”) and 2 (channel strip “B”) equipped with IP addresses are provided at the LAN interface. The transport stream from the ASI input “TS ASI” is made available via the ASI output.
Transport stream 1
Transport stream 2
ASI input ASI output
TS ASI
Channel strip "A"
”OUT-IP”
Channel strip "B"
”OUT-IP”
LAN interface
2.4.2.2 Menu setting “1=>ASI ASI=>MA”
The transport stream 1 is made available via the ASI output. The transport stream 2 (channel strip ”B”) and the transport stream fed via the ASI input (channel strip ”A”, ”MA”) are provided at the LAN interface equipped with IP addresses.
Transport stream 1
ASI input
Transport stream 2
Channel strip "A"
”OUT-IP”
Channel strip "B"
”OUT-IP”
ASI output
LAN interface
- 8 -
2.4.2.3 Menu setting “2=>ASI ASI=>MB”
Transport stream 1 (channel strip ”A”) and the transport stream fed via the ASI input (channel strip ”B”, ”MB”) are provided at the LAN interface equipped with IP addresses. The transport stream 2 is made available via the ASI output.
Transport stream 1
ASI input
Transport stream 2
Channel strip "A"
”OUT-IP”
Channel strip "B"
”OUT-IP”
LAN interface
ASI output
2.4.3 General
The cassette is equipped with two channel strips (“A” and “B”).
The channel strips consist of the digital SAT tuners and the digital signal processing levels. In the head-end station display, the channel strips of the cassette are indicated with “
Bx …A
” or “
Bx …B
”. The channel strip “A” can decode encoded services via a corresponding CA module. The cassette is controlled with the head-end station control unit. Two LEDs provide an indication of the quality of the SAT IF input signal with their colour. The quality of the received transport stream can also be shown in the display (“
C/N
” menu). The LEDs for the LAN interface show whether a network connection exists and whether a data transfer is in progress. The integrated TPS module (Transport Stream Processing) processes the data from the demodulated transport streams. When the head-end station is switched on, the two-line LC display shows the software version of the control unit. To operate this cassette the software version of the control unit must be “V 40” or higher. You can find the current operating software for the control unit and the cassette, the software “BE-Flash” required for updating and the current as- sembly instructions on the website “www.gss.de”. The cassette is designed for use in the following head-end stations: – STC 1200 – STC 316 – STR 19-8 – PST 19-1
- 9 -
2.5 Software query Control unit
If necessary, you can activate the indication of the software version of the con­trol unit manually:
• Press any two keys on the control unit of the head-end station simultaneously until the display goes dark and the software version, e.g. “V 40” appears.
Cassette
After activating the cassette the software version of the cassette is displayed (s. page 19).
2.6 How the TPS module works
After decoding QPSK- or 8PSK-modulated signals, the demodulated trans­port stream can be accessed via the integrated TPS module. This transport stream, also called data stream, contains several services with the appropriate data components (video, audio, data and service information), which can be changed using the TPS module. In the station filter services can be deleted. This reduces the output data rate. Additionally services of the different transport streams can be assembled to a new transport stream. The transport stream contains data in the form of tables which the receivers evaluate and require for convenient use. The TPS module can adjust the “Net­work Information Table” (NIT) to accommodate the new service data. The “NIT” contains data which is required by the set-top boxes for the automatic search feature. Some network operators transmit an operator ID in the transport stream (e.g. visAvision). By changing the CAT the operator ID can be adjusted to the de­mands.
- 10 -
3 Assembly
A
CLASS
KLASSE
3.1 Installing the cassette
– Ensure the head-end station is mounted so it will not be able to vibrate.
Avoid, for example, mounting the head-end station onto a lift shaft or any other wall or floor construction that vibrates in a similar way.
– Before installing or changing a cassette unplug the power cable from the
mains power socket.
• Remove the fastening screws
1 of an unoccupied slot from the bracket of the
head-end station.
• Insert the cassette in this slot and push it into the housing.
• Align the cassette and apply slight pressure to connect it to the connections of the board and the HF bus bar.
• Fasten the cassette with the screws 1.
1
0°
.$66(77(
.$66(77(
.$66(77(
.$66(77(
.$66(77(
.$66(77(
.$66(77(
.$66(77(
.$66(77(
.$66(77(
.$66(77(
.$66(77(
+<%5,'9(567b5.(5
ACHTUNG!
Vor dem Kassettenwechsel
MESSAUSGANG
unbedingt
denNetzstecker ziehen.
–20 dBμV
CAUTION!
AUSGANG
Before
changing cassettes remove
max. 106 dBμV
mains plug.
*UXQGLJ6$76yVWePV
1
3.2 EMC regulations To comply with the current EMC regulations, it is necessary to connect the
lines leading in and out of the head-end station using cable terminals.
When mounting the cassette in a head-end station which is installed in a
19” cabinet, make sure the connections leading in and out for the 19” cabi­net are made using cable terminals.
The attenuation of shielding of the connection lines for ASI and antenna
A
KLASSE
CLASS
must meet the requirements for “Class A”.
- 11 -
• Insert the required number of cable terminals in the openings provided in the head-end station or in the 19" cabinet.
—> Cable terminals are not included in the scope of delivery.
3.3 Cassette overview
Tighten the nuts on the cable terminals until the teeth on the lock washer have penetrated the exterior coating and a good connection is made between the housing and cable terminals.
5678 9 ! @2143 0 #
1 Status LED 2 SAT IF input 3 Status LED 4 SAT IF input
of channel strip “B”
of channel strip “B”
of channel strip “A”
of channel strip “A”
5 Status LED of the LAN interface (yellow LED – data transfer) 6
LAN socket
7 Status LED of the LAN interface (green LED – network connection) 8 ASI input 9 ASI output 0 Type label ! Slot for a CA module @ D-SUB socket “RS 232“ The operating software of the cassette can be updated via the 9-pin D-SUB
socket “RS 232” using a PC or notebook and the software “BE-Flash”.
You can find the current operating software on the website “www.gss.de”.
# MAC address
- 12 -
3.4 Connecting the cassette
4
• Connect the SAT IF input cables to the SAT IF inputs
2
(channel strip “B”) (fig. chap. 3.3).
• Connect the LAN socket 6.
• Connect the ASI input 8 and the ASI output 9 to the peripheral ASI devices.
3.5 Retrofitting a CA module
The cassette is equipped with a common interface. It allows you to connect a CA module for various encryption systems and service providers. Encoded serv­ices can only be decoded with a CA module suitable for the encoding system and the corresponding smart card. The smart card contains all the information for authorisation, decoding and subscription.
(channel strip “A”) and
– When working with the CA module, please read the corresponding op-
Check with the distributor or manufacturer of the CA module to be used to ensure that it is suitable for decoding several services.
– The hardware and software of this cassette have been thoroughly pre-
pared and tested. Any changes made by service providers to the data structures in the service data might impair or even prevent this function.
erating manual from the respective provider.
• Insert the smart card 1 into the CA module 2 so that the chip 3 on the smart card faces the thicker side (top) of the CA module.
• Insert the CA module into the guide rails of the CA slot 4 with the top side of the CA module facing the top side of the cassette.
• Push the CA module without canting into the guide rails of the CA slot 4 and contact it to the common interface.
4
2 3 1
- 13 -
4 The control panel at a glance
4.1 Menu items
Program the
cassette
using the buttons on the control unit of the head-end station. The two-line display of the control unit then shows the menus. The parameters and functions to be set are underlined.
Use the key to select the following main menu items:
– Ethernet parameters – Input signal path – Output signal path
BE–Remote V 40
please wait . . .
– Channel strip – IP address, transmission protocol, port number – Number of data packets, forward error correction, transmission channel – Output IP address – LNB oscillator frequency – Input symbol rate – Input frequency – Station filter – CA module (if available) – Output data rate – Network Information Table (NIT) –
Network/operator identification – Deleting a PID – Renaming a PID
4.2 Control panel
The key pad on the head-end station is used to scroll through the menus:
scrolls forward through the menus.
/
select parameters in the menus.
set values, initiate actions.
selects sub-menus.
AUDIO
M
scrolls backward through the menus.
saves all entries.
- 14 -
5 Programming
BE–Remote
please wait …
V 40
Box 4
V 10
DVBS2-MPTS
– – –
1
………
………
………
5
………
………
………
+
t > 10 s
Bx 4
A+B+ASI=1
INROUTE
ASI=2
Bx 4
stat =>
ETHERNET
Options
stat / DHCP
A
Bx 4
192.168. 0. 1
IP-GATEWAY
Bx 4
255.255.255. 0
IP-MASK
Å
Ï
/
Bx 4
192.168. 0.128
IP-ADDR
Å
Ï
/
Å
Ï
/
Bx 4
60000
UDP-PORT
Å
Ï
/
Å
0 … 65535
A+ASI=1 B+ASI=2 / A+B+ASI=1 ASI=2
Ein / On
5.1
Programming procedure
5.1.1 Channel strips “A” (without CA module) and “B”
Box
Box
page 17
- 15 -
Bx 4
Line A <=
LINE
=> Line B
B
Bx 4
1=>ASI
OUTROUTE
ASI=>MA
Bx 4
108000 KBits
ASI RATE
188 / 204 positive / negativ continuous / burst
Bx 4
188 pos. cont.
ASI OPTION
Å
Ï
/
Å
Ï
/
Bx 4A
on UDP
MODE/PORT
1234
ASI=>ASI 1=>ASI ASI=>MA 2=>ASI ASI=>MB
Bx 4A
7 off
PKTS / FEC
Å
Ï
/
on / off UDP / RTP, 0 … 65535
Å
Ï
/
off / 10/9 … 20/19 Annex A / Annex B
1 … 7
Bx 4A
227. 40. 50. 60
OUT-IP
Å
Ï
/
Bx 4A
27500
SYMBOL
DVB-S
Bx 4A
11836 -1.8
FREQ
CN 12
Å
Ï
/
Å
Ï
/
Bx 4A
10600 MHz
LNB
Bx 4A
12.0 dB
C/N
(+ 9.6) OK
Anzeige: Signalqualität
Display: Signal quality
Å
Ï
/
Å
Ï
/
10600 / 9750
27500 / 22000
DVB-S / QPSK… / 8PSK… / DTV…
Line A Line B
Å
Ï
/
page 14
page 17
- 16 -
Bx 4A
Filter
PROGRAM
off
Services entfernen / hinzufügen
Removing / activating services
nächster Service (Programm)
next service (station)
Å
Ï
/
A
M
B
Bx 4A
off
NIT
=> Make
Bx 4A
PID 0x0000
DROP
off
Bx 4A
0xDE00
CAT-ID
off
Å
Ï
/
Bx 4A
0x0000 –> 0000
REMAP
off
Å
Ï
/
on / off
Å
Ï
/
on / off
Å
Ï
/
Å
Ï
/
on / off
Å
Ï
/
on / off
Å
Ï
/
Services entfernen / hinzufügen
Removing / activating services
nächster Service
next service
Å
Ï
/
Services entfernen / hinzufügen
Removing / activating services
nächster Service
next service
Å
Ï
/
01/07Bx 4A TV +
Das Erste
Bx 4A
Filter
PROGRAM
on
01/09Bx 4B TV +
ZDF
…/…ASI … +
………
Å
Bx 4A
72956 kbps
DATARATE
C
D
Kanalzug ”A” mit CA-Modul
Channel strip ”A” with CA module
ohne CA-Modul
without CA module
Kanalzug ”B”
Channel strip ”B”
page 18
- 17 -
page 16
page 15
5.1.2 Channel strip “A” with CA module
C
page 17
Bx 4A
Supply
Bx 4A
PID Check
Bx 4A
M
Bx 4A 01/03
Information *)
*) Die angezeigte Information ist abhängig vom verwendeten CA-Modul.
The information displayed is dependent on the CA module used.
MENU
Menu <=
CA
5.0 V
CA
on
CA
=> Edit
Ï
D
Å
page 17
3.3 V / 5.0 V
on / off
Bx 4A TV X
. . . .
S
Bx 4A
Menu <=
04/09
CA
=> Edit
X / 0
X – entschlüsselt
decrypted
0 – verschlüsselt
encrypted
Ï
Å
/
nächster Service
next service
- 18 -
5.2 Programming the cassette
BE–Remote
please wait …
V 40
t > 10 s
Ein / On
Box 4
V 10
DVBS2-MPTS
– – –
1
+
A
—> Pressing the
button for longer than 2 seconds cancels the pro­gramming procedure. This takes you back to the program item “Selecting the cassette” from any menu. Any entries that have not been saved are reset to the previous settings.
M
—> Entries in the menus can be saved by pressing the
key. You are taken
back to the “Selecting the cassette” menu item.
—>
Using the
AUDIO
button previous menus can be activated.
• Switch on the head-end station —> The display shows the software version (e.g. V 40) —> The processor reads the
cassettes
‘ data
(approx. 10 seconds).
Selecting the cassette, displaying the software version
Box
Box 5
• Select the
cassette
you want to program (e.g. Box 4) by
repeatedly pressing the button if necessary.
—> The display shows e.g. the menu
Box 4” stands for
DVBS2-MPTS
” type of cassette
Box 4 DVBS2-MPTS“
slot
4
V 10” software version of the cassette
- 19 -
:
• Press the button.
Bx 4
stat =>
ETHERNET
Options
stat / DHCP
Bx 4
192.168. 0.128
IP-ADDR
Å
Ï
/
Å
4
/
—> The “Setting the Ethernet parameters” – “ETHERNET”
menu is activated.
Setting the Ethernet parameters
In this menu you specify whether the Ethernet parameters for the
prospectively intended control of
the cassette are entered automatically by a connected server (“DHCP”), or whether you want to enter them manually (“stat”). To assign the cas­sette uniquely, each IPTV cassette must be allocated its own IP address.
Bx
192.16. 0.12
IP-ADDR
• Press the buttons to select manual setting (”stat”) or
automatic setting (”DHCP”) of the Ethernet parameters.
• Press the
—> The “Setting the IP address of the cassette”
▶ button to activate the setting options
(”Options”)
– menu
.
IP-ADDR” is activated.
Setting the IP address of the cassette
If you choose to enter the Ethernet parameters manually, set the IP address of the cassette in this menu. If “DHCP” is selected, the “IP-ADDR”, “IP-MASK” and “IP-GATEWAY” sub-menus display the parameters that were assigned auto­matically by a connected server. If a server is not connected, “ 0. 0. 0. 0*” appears in the corresponding menu. The star “ * ” in the display means that the data is provided by a DHCP server.
- 20 -
Bx 4
stat =>
ETHERNET
Options
stat / DHCP
Bx 4
192.168. 0.128
IP-ADDR
Å
Ï
/
Å
4
s
T
stat / DHC
P
Bx 4
255.255.255. 0
IP-MASK
Å
Ï
/
Bx
tat =>
THERNE
Options
• Use the
buttons to place the cursor under the digit
/
of the IP address displayed to be set and use to set the IP address wished.
• Press the
—> The “Setting the address range”
button.
– “IP-MASK” menu is
activated.
Setting the address range
In this menu you define the address range for the cassettes connected to the LAN network.
• Use the
buttons to place the cursor under the digit
/
of the IP address displayed to be set and use to set the IP address wished.
• Press the
—> The “Setting the address of the gateway”
button.
IP-GATEWAY” menu is activated.
- 21 -
Setting the address of the gateway
Bx 4
192.168. 0. 1
IP-GATEWAY
Å
Ï
/
Bx 4
60000
UDP-PORT
Å
Ï
/
0 … 65535
The address of a gateway (server) can be set in this menu. If no gateway is used you can skip this setting.
• Use the
buttons to place the cursor under the digit
/
of the IP address displayed to be set and use to set the IP address wished.
• Press the
—> The “Setting the UDP port”
button.
– “UDP-PORT” menu is
activated.
Setting the UDP port
The UDP port setting is required if the cassette needs to be reached externally to make the setting, such as from another input frequency. This setting is intended for future functions and can be skipped for this cassette.
• Use the
buttons to place the cursor under the digit
/
of the port number displayed to be set and use to set the port number wished (”0” … ”65535”).
• Press the
button.
—> The “Selecting the input signal path” – “INROUTE”
menu is activated.
- 22 -
Selecting the input signal path
Bx 4
A+B+ASI=1
INROUTE
ASI=2
A+ASI=1 B+ASI=2 / A+B+ASI=1 ASI=2
Bx 4
1=>ASI
OUTROUTE
ASI=>MA
Bx 4
108000 KBits
ASI RATE
Å
Ï
/
ASI=>ASI 1=>ASI ASI=>MA 2=>ASI ASI=>MB
4
E
/
In this menu you define the signal path of the input transport streams.
Menu setting “A+ASI=1 B+ASI=2” (s. chap. 2.4.1.1, page 7).
Menu setting “A+B+ASI=1 ASI=2” (s. chap. 2.4.1.2, page 7).
• Use the
buttons to select the signal path wished.
• Press the button.
—> The “Selecting the output signal path” – “OUTROUTE”
menu is activated.
Selecting the output signal path
In this menu you define the signal path of the output transport streams.
Menu setting “ASI=>ASI” (s. chap. 2.4.2.1, page 8).
Menu setting “1=>ASI ASI=>MA (s. chap. 2.4.2.2, page 8).
Menu setting “2=>ASI ASI=>MB (s. chap. 2.4.2.3, page 9).
Bx
10
ASI RAT
00 KBits
- 23 -
• Use the buttons to select the signal path wished.
Bx 4
1=>ASI
OUTROUTE
ASI=>MA
Bx 4
108000 KBits
ASI RATE
Å
Ï
/
ASI=>ASI 1=>ASI ASI=>MA 2=>ASI ASI=>MB
4
E
A
A
2
• If you do not want to do ASI settings, press the
button.
—> The “Selecting the channel strip” – “LINE” menu is
activated
(page 26).
• Press the button.
—> The “Setting the ASI transfer rate” – “ASI RATE” menu
is activated.
Setting the ASI transfer rate
In this menu you set the transfer rate for the ASI component connected. For this setting please take the required information from the documentation (technical data) of the ASI component to be connected.
ASI=>ASI 1=>ASI ASI=>M
=>ASI ASI=>MB
Bx
1=>ASI
OUTROUT
ASI=>M
• Use the
buttons to place the cursor under the digits
/
to be set for the transfer rate then use the buttons to set the transfer rate wished.
• Press the button.
—> The “Setting the ASI options”
– “ASI OPTION” menu is
activated.
- 24 -
Setting the ASI options
188 / 204 positive / negativ continuous / burst
Bx 4
188 pos. cont.
ASI OPTION
Å
Ï
/
2=>ASI ASI=>MB
In this menu you define the size of the data packets, their polarity and the type of transmission. For this setting please take the required information from the documentation (technical data) of the ASI component to be connected.
• Press the
buttons to set the size of the data packets
(“188” or “204” bits).
• If the polarity of the data to be transmitted has to be
changed, press the
buttons to place the cursor un-
/
der “pos.” (positive – standard) and using the but- tons set to “neg.” (negative).
• To change the type of transmission press the
/
buttons to position the cursor under “cont.” (continuous – standard) and using the set to “burst”.
—> Setting “cont.” The data packets of the user data are collected to a
great data packet in the transport stream. —> Seting “burst” The data packets of the user data are spaced out
evenly in the transport stream.
• Press the button. —> The “Selecting the channel strip” – “LINE” menu is
activated.
- 25 -
Selecting the channel strip
Bx 4
Line A <=
LINE
=> Line B
B
Line A Line B
Å
Ï
/
Bx 4A
on UDP
MODE/PORT
1234
Å
Ï
/
on / off UDP / RTP, 0 … 65535
• By pressing
channel strip “B” (“Line B”) by pressing the ▶ button
select channel strip “A” (“Line A”) or select
.
—> The “Switching the IP address off or on, selecting the
transmission protocol, setting the port number” –
MODE / PORT
” menu is activated.
Switching the IP address off or on Selecting the transmission protocol Setting the port number
In this menu you can switch off or on the output IP address of the channel strip, and define the transmission protocol and the port number.
Switching the IP address off or on
• Press the
buttons to switch ”
IP address of the channel strip.
- 26 -
off” or “on
” the output
Selecting the transmission protocol
• Press the ▶ button to position the cursor under ”UDP” or
RTP”.
• Using the buttons to select the transmission protocol
wished:
UDP” – The User Datagram Protocol is for the connec-
tionless transmission of data to a certain applica­tion. The port number of the service is also sent which the data should obtain.
RTP” – The Real-time Transport Protocol is for continu-
ously transmitting multimedia data streams in an IP network. Unlike UDP, the header is transmitted which makes the data transmission more robust.
Setting the port number
• Press the
number e.g. ” 1234”.
• Use the
digit of the port number displayed to be set.
• Using the buttons set the port number wished.
• Press the button. —> The “Defining the quantity of data packets, setting
the forward error correction, setting the transmission channel” – “PKTS / FEC” menu is activated.
button to position the cursor under the port
buttons to position the cursor under the
/
Defining the quantity of data packets Setting the forward error correction Setting the transmission channel
In this menu you set the quantity of the data packets to be transmitted, the forward error correction FEC and the trans­mission channel. If the forward error correction is used the data to be transmitted is encoded in a redundant way so that the addressee can correct transmission errors.
- 27 -
Defining the quantity of data packets
Bx 4A
7 off
PKTS / FEC
Å
Ï
/
off / 10/9 … 20/19 Annex A / Annex B
1 … 7
Bx 4A
7 10/09
PKTS / FEC
AnnexB
• Using the buttons define the quantity of MPEG data
packets in one IP data packet (”1” … ”7”).
Setting the forward error correction
• Press the ▶ button to position the cursor under ”off” . —> In position ”off” the forward error correction (FEC) is
switched off.
• Using the buttons set the value of the FEC wished
(”off, 10/9” … ”20/19”).
Setting the transmission channel
• Press the ▶ button to position the cursor under ”Annex…”.
• Use the buttons to set the transmission channel
wished (”AnnexA” / ”AnnexB”).
• Press the button. —> The “Setting the output IP address” – “OUT-IP” menu
is activated.
- 28 -
Setting the output IP address
Bx 4A
227. 40. 50. 60
OUT-IP
Å
Ï
/
Å
Ï
/
Bx 4A
10600 MHz
LNB
10600 / 9750
In this menu you set the output IP address for the channel strip selected. This IP address the services wished are allocated in the station filter.
Allocate different IP addresses to the channel strips.
• Press the
buttons to position the cursor under the
/
digit of the IP address to be set.
• Using the buttons set the IP address wished
.
• Press the button. —> The “Setting the LNB oscillator frequency” – “
LNB
menu is activated.
Setting the LNB oscillator frequency
Set the oscillator frequency of the LNB used in this menu.
• Using the button the oscillator frequencies ”10600
or ”9750“ can be selected directly.
• To set another LNB oscillator frequency use the
but-
/
tons to place the cursor under the digit of the LNB oscillator frequency displayed to be set.
• Press to enter the respective digit of the oscillator
frequency of the LNB used.
• Repeat the procedure by the quantity of the digits to be
set.
- 29 -
• Press the button.
Bx 4A
27500
SYMBOL
DVB-S
Å
Ï
/
Å
Ï
/
27500 / 22000
DVB-S / QPSK… / 8PSK… / DTV…
—> The “Setting the input symbol rate, setting the DVB
mode” – “SYMBOL” menu is activated.
Setting the input symbol rate Setting the DVB mode
The symbol rates of the satellite transponders can be found in the current channel table of the satellite operator, in various satellite magazines and in the Internet. The cassette recognizes the transmitted DVB mode and switches over between the normal QPSK mode (DVB-S) and the DVB-S2 mode. Receiving stations with DVB-S2 mode, we suggest to preset the DVB mode to shorten the time for searching stations.
Setting the input symbol rate
• Using the
button the symbol rates 27500“ or
22000“ can be selected directly.
• To set other symbol rates use the
buttons to position
/
the cursor under the digit of the symbol rate displayed to be set.
• Press
to enter the respective digit of the symbol rate
needed.
• Repeat the procedure by the quantity of the digits to be set.
Setting the DVB mode
• Use the
set the required DVB-S2-mode with the
button to place the cursor under “DVB-S” and
buttons.
• Press the button. —> The “Setting the input frequency” – “FREQ” menu is
activated.
- 30 -
Setting the input frequency
Bx 4A
11836 -1.8
FREQ
CN 12
Å
Ï
/
Bx 4A
12.0 dB
C/N
(+ 9.6) OK
Anzeige: Signalqualität
Display: Signal quality
If three dots “ “ appear in the second line of the display, the cassette is in the “station search” mode. Please wait until the process has finished. Once the HF receiver has synchronised to the input signal, any offset to the target frequency is displayed in MHz, e.g. “– 1.8”. If a question mark “?” appears in the second line of the dis­play, there is no input signal present. Check the configuration of the antenna system and head-end station as well as the preceding settings of the cassette.
• Use the
buttons to position the cursor under the
/
digit of the frequency displayed to be set.
• Press
to set the appropriate digit of the input fre-
quency wished.
• Set the frequency offset shown in the display
to less than 1 MHz the
buttons.
by varying the input frequency
(e.g. “– 1.8”)
using
—> The ”CN 12” display e.g. indicates the signal to noise
ratio of the signal received.
• Press the button. —> The “Testing the signal to noise ratio” – “C/N” menu is activated.
- 31 -
Testing the signal to noise ratio
In this menu you can estimate the quality of the input signal.
C/N
(+ 9.6) OK
Bx 4A
12.0 dB
  
1 Current signal to noise ratio 2 This value shows the difference between the quality
of the input signal and the threshold of the tuner at this type of modulation.
At a value lower than “5” picture dropouts can occur.
3 If “OK” is shown, the signal to noise ratio is ok.
If a value < 5 is shown under 2 the display changes
from “OK” to “??”. In this case test the input signal.
—> In addition to the indicator in the display, there is a
status LED which indicates the quality of the received transport stream (level and C/N).
—> If the LED lights yellow the SAT IF input level and the
signal to noise ratio must be tested.
Status LED Channel strip "A"
LED indicator Indication
Green Signal quality is good
Yellow
Red No signal
Signal quality is insufficient
Status LED Channel strip "B"
• Press the button
- 32 -
to return to the main menu.
If the input signal path “A+B+ASI=1 ASI=2” is selected the station filter of channel strip “B” is used in the channel strip “A”. Therefore perform the settings for channel strip “B” according to the pages 29 … 31 (LNB oscillator frequency, input symbol rate, input frequency) before activating the “Set­ting the station filter” – “PROGRAM” menu. If the input signal path “A+ASI=1 B+ASI=2” is selected the channel strips can be programmed one after the other.
• Press the
button.
—> The “Setting the station filter” – “PROGRAM” menu is
activated.
Setting the station filter
The default setting for the station filter is “off”. In this menu you define the services received to be transmitted. If services are activated the output data rate increases. If the station filter is switched off (factory default) all services of the transport stream passes the station filter. As soon as the station filter is activated services can be added to the transport stream selectively.
The figure of the menu below is dependent on the setting of the “Selecting the input signal path” ”INROUTE” menu (page 23). The programming procedure shown below corresponds to the setting ”A+B+ASI = 1 ASI = 2”. With this setting the transport stream of channel strip “B” is routed to the transport stream of channel strip “A” and there­fore cannot be set in channel strip “B”. Programming channel strip “B” the transport stream coming from the ASI input can be processed only.
- 33 -
”INROUTE” menu settingA+B+ASI=1 ASI=2”.
Bx 4A
Filter
PROGRAM
off
Services entfernen / hi
Removing / activating
nächster Service (Prog
next service (station)
Å
Ï
/
on / off
Å
Ï
/
Services entfernen / hi
Removing / activating
nächster Service
next service
Å
Ï
/
Services entfernen / hi
Removing / activating
nächster Service
next service
Å
Ï
/
01/07Bx 4A TV +
Das Erste
Bx 4A
Filter
PROGRAM
on
01/09Bx 4B TV +
ZDF
…/…ASI … +
………
Å
Bx 4B
Filter
PROGRAM
off
Å
…/…ASI … –
………
Å
Ï
/
on / off
Bx 4B
Filter
PROGRAM
on
Channel strip “A
Channel strip ”B”
Press the
—> All services from the channel strip will be read, and
then displayed with name and type of the service.
button.
—> If no services is found, the following error message
will appear in the display: “FILTER no Service”.
In this case, check the configuration of the antenna
- 34 -
system and head-end station, as well as the previ­ously adjusted settings for the cassette and the com­ponents connected to the ASI input.
—> The display shows e.g.:
Das Erste
Bx 4A TV + 01/07
Meaning of the indicators in the example:
Bx 4A – Slot 4, channel strip “A” “TV” – ”Television” (type of service) “ + ” – “
01/07” – The 1st of 7 services is being displayed .
Das Erste
Further possible terms displayed:
The currently
selected
” – Name of the service
service is activated.
“RA” ”Radio” (type of service) For radio stations, the
screen of the connected TV
or test receiver is darkened.
“ – ” “ * The star means that the
The currently selected service is
service
coded. To enable the
service
, the CA module and
switched off.
selected is en-
the appropriate smart card of the provider are required.
—> If a service number (e.g. “131”) appears instead of
TV” or “RA”, this indicates that an unnamed
service
or an undefined transport stream is being received.
• Use the
order, then use
buttons to call up the
/
to activate (indicated by “ + ”) or to
service
s in sequential
remove them (“ – ”).
—> Pressing the button all services can be acti-
vated or deactivated.
Press the button.
• Set the station filters of channel strip “B” and “ASI” in the
same way as channel strip “A”.
To save changes and to activate the station filter press the
button.
- 35 -
—>
Bx 4A
Filter
PROGRAM
off
Å
01/07Bx 4A TV +
Das Erste
Å
Ï
/
…/…ASI … –
………
Å
Ï
/
on / off
PROGRAM
on
Bx 4A
Filter
The filter is activated. The display shows “PROGRAM Filter on”. —> If
services
are activated the corresponding PIDs (au­dio, video, text) are inserted into the transport stream and the PAT and SDT tables are updated.
Test the status of the individual services:
• If the filter is switched on, press the
button. In this mode you can test the settings of the station filter again or change them if necessary.
• In the “PROGRAM Filter on” menu the station filter switched on can be switched “off” using the buttons if necessary.
”INROUTE” menu settingA+ASI = 1 B+ASI = 2”. Channel strip “A
• Set the channel strip “A” or “B”.
—> The setting of the channel strips “A” and “B” is identi-
cal and follows the description above.
- 36 -
• Press the button.
> The “Displaying the output data rate”
– “DATARATE” menu is activated when the channel strips “A” without a
CA module installed
and “B” are programmed.
Programming the channel strip “A” with a CA module
installed the “Setting the operating voltage for the CA module” – “CA Supply” menu is activated (s. page 41).
Displaying the output data rate
In this menu the current data rate is displayed.
ohne CA-Modul
without CA module
Kanalzug ”B”
Channel strip ”B”
Bx 4A
72956 kbps
Bx 4A
off
C
D
DATARATE
• Press the
Kanalzug ”A” mit CA-Modul
Channel strip ”A” with CA module
button.
—> The “Network Information Table” – “NIT” menu is ac-
tivated.
Network Information Table (NIT)
This menu has no function at this cassette. Therefore it can be skipped.
NIT
=> Make
• Press the
button.
—> The “Network/operator identification” – “CAT-ID”
menu is activated.
- 37 -
Network/operator identification
In this menu, you can change the network/operator identi­fication (CAT-ID – Conditional Access Table - Identification), for example of the visAvision transponder (Eutelsat 8° West).
Ï
Bx 4A
Å
/
0xDE00
CAT-ID
off
Ï
Å
/
on / off
CAT is not to be changed.
• Press the
button.
—> The “Deleting a PID” – “DROP” menu is activated
(page 39).
CAT is to be changed.
The network operator e.g. requires that you set the operator ID of the visAvision transponder to “2”.
Use the
buttons to position the cursor under the digit
/
to be set.
• Use
to change
the operator ID from “0xDE00” to
0xDE02”.
• Use the ▶ button to position the cursor under “off,” then use to activate the new CAT “on”.
—> The menu display switches to “modified”. —> If you try to change the network/operator identifica-
tion (operator ID) of a transponder which cannot be modified, “not modified” appears in the display.
• Press the button.
—> The “Deleting a PID” – “DROP” menu is activated.
- 38 -
Deleting a PID
In this menu a PID of the transport stream can be deleted.
Å
/
Bx 4A
PID 0x0000
Ï
DROP
Ï
off
• Use the
Å
/
on / off
buttons to place the cursor under the re-
/
spective digit of the hexadecimal number of the PID to be deleted (“0x0000”) and set the hexadecimal number using
.
• Use
▶ to set the cursor to “
using the
buttons.
off
” and switch to “on”
(delete)
• Press the button.
—> The “Renaming a PID” – “REMAP” menu is activated.
Renaming a PID
In this menu you can allocate a new address to a PID retain­ing the complete data content.
Å
/
Bx 4A
0x0000 –> 0000
Ï
M
REMAP
off
Ï
Å
/
on / off
B
A
• Use the
buttons to place the cursor under the re-
/
spective digit of the hexadecimal number of the PID to be changed (“0x0000”) and set the hexadecimal number us­ing .
• Use the
buttons to place the cursor under the re-
/
spective digit of the hexadecimal number of the new PID (“–> 0000”).
• Set the hexadecimal number using .
• Use ▶ to set the cursor to “off” and switch to “on” (re- name) using the buttons.
- 39 -
Saving settings
• Press the
M
button. —> The settings are saved. —> You will be returned to the menu item “Selecting the
cassette” via connection A (page 19).
—> If functions of the TPS module are activated, their sta-
tus is shown in the second line of the display: “M” – Station filter is switched on.C” – Network/operator identification CAT is activated.
—> By pressing the
button, you will be returned to the menu item “Selecting the channel strip” via connection B without
saving the programmed data
(page 26).
—> If necessary set channel strip “B”.
- 40 -
5.2.1 Operation with a CA module
In order for this function of the CA module to be possible, services capable of being decoded by the CA module you are using and your smart card must be selected in the “Set­ting the station filter” – “PROGRAM” menu (page 33). Where both encrypted and unencrypted services are transmit­ted, short-term picture loss may occur when switching between encrypted and unencrypted services.
Setting the operating voltage for the CA module
In this menu the operating voltage for the CA module can be set.
C
Bx 4A
Supply
• Use the
CA
5.0 V
3.3 V / 5.0 V
buttons to set the operating voltage for the
CA module (”3.3 V“ / ”5.0 V“).
• Press the button. —>
The “Setting the PID monitoring” – “CA”
menu
is acti-
vated.
Setting the PID monitoring
The factory default of the PID monitoring is switched on. If particular PIDs are not decrypted the CI module is reset. Additionally dropouts may occur if several services are de­crypted. To prevent this the PID monitoring can be switched off.
Bx 4A
PID Check
CA
on
on / off
- 41 -
• Use the buttons to switch “off” or “on” the PID moni-
Bx 4A
Menu <=
CA
=> Edit
*) Die angezeigte Information ist abhängig vom verwendeten CA-Modul.
The information displayed is dependent on the CA module used.
Bx 4A 01/03
Information *)
MENU
Bx 4A TV X
. . . .
04/09
S
X – entschlüsselt
decrypted
0 – verschlüsselt
encrypted
X / 0
nächster Service
next service
Å
Ï
M
Å
Ï
/
X . . . 4
/
X
üsse
d
üsse
d
X
e
ce
/
toring.
• Press the button. —>
The “Configuring the CA module” – “CA” menu is acti­vated.
Configuring the CA module
The menu varies according to which CA module you are using. For this reason, please refer to the operating manual of your particular CA module. The relevant information is shown in the display of the head-end station. This may ap­pear as a fixed display or as scrolling text according to dis­play capabilities.
/ 0
Bx 4A TV
09
ntschl
ecrypte
0 – verschl
ncrypte
lt
lt
• Press the ◀
ächster Servic
next servi
—>
By pressing the button you can skip the “Con­figuring the CA module” – “CA” menu and activate the “Displaying the output data rate” – “DATARATE” menu (page 37).
—> The display shows e.g.: Bx 4A 01/03 MENU Information
button to activate the menu of the CA module.
- 42 -
Meaning of the indicators:
Bx 4A
Menu <=
CA
=> Edit
*) Die angezeigte Information ist abhängig vom verwendeten CA-Modul.
The information displayed is
Bx 4A 01/03
Information *)
MENU
Bx 4A TV X
. . . .
04/09
S
X – entschlüsselt
decrypted
0 – verschlüsselt
encrypted
X / 0
nächster Service
next service
Å
Ï
M
Å
Ï
/
3
)
Bx 4A – Slot 4, channel strip “A”
01/03
– The first of three menu items is activated.
MENU
– The menu of the CA module is activated.
For the explanation of further details please use the operat­ing instructions of the CA module used.
• Use the buttons to activate the menu desired.
• Press the ▶ button to activate the menu.
• Use the buttons to select the function desired.
• To set the CA module use the
and buttons.
/
• All settings are saved by pressing the M button. —> You will be returned to the “Configuring the CA module” – “CA” menu item.
—>
By pressing the button you can cancel the settings in the menu of the CA module and are returned to the “Configuring the CA module” – “CA” menu.
• Press the ▶ button. —> The “Decoding services” – “Edit” menu is activated.
Bx 4A 0/0
Information *
ENU
Decoding services
In this menu you select the services wished from the encoded transport stream, which are to be decoded.
—> The display shows e.g.:
. . . .
- 43 -
Bx 4A TV X 04/09
Meaning of the indicators in the example:
D
Bx 4A
Menu <=
CA
=> Edit
Bx 4A – Slot 4, channel strip “A” “TV” – ”Television” (type of service) “X”
The currently
selected
service is decrypted. “
04/09” – The 4th of 9 services is being displayed.
. . . .
– Name of the service
Further possible terms displayed:
“RA” – ”Radio” (type of service) “0
• Use the
order which are to be decoded, then use
The currently selected service is encrypted.
buttons to call up the services in sequential
/
to decrypt
(“X”) or not to decrypt them (“0”).
Save changes and activate the filter:
Press the button.
—> The filter is activated. The display shows the “Configuring the CA module” – “CA” menu.
• Press the button. —> The
“Displaying the output data rate” – “DATARATE”
menu
is activated
- 44 -
(page 37)
.
6 Final procedures
After installing the head-end station, upgrading accessories or installing
cassettes it is necessary to tighten all cable connections, cable terminals and cover screws in order to maintain compliance with current EMC regula­tions securely.
• Securely tighten the cable bolted connections using an appropriate open­ended spanner.
• Mount the front cover (s. assembly instructions of the head-end station).
- 45 -
Service:
Phone: +49 (0) 911 / 703 2221 Fax: +49 (0) 911 / 703 2326 Email: service@gss.de
Alterations reserved. Technical data E. & O.E. © by GSS GmbH 04092009
Loading...