GS Chromalox 4081, Chromalox 4082 Installation & Operation Manual

Page 1
Installation & Operation Manual
4081/4082 Graphical Profile
Controller & Recorder
PK532-1 0037-75562 March 2016
A
Page 2
B
Page 3
Copyright © February 2016, Chromalox, all rights re­served. No part of this publication may be reproduced, transmitted, transcribed or stored in a retrieval system, or translated into any language in any form by any means without the written permission of Chromalox.
Copies of this manual are available in electronic for­mat on the Chromalox web site (www.chromalox.com) Printed versions are available from Chromalox or its representatives.
Note: It is strongly recommended that applications in­corporate a high or low limit protective device, which will shut down the equipment at a preset process con­dition in order to prevent possible damage to property or products.
The Safety Alert Symbol: is found throughout these in­stallation instructions to identify potential hazards that can result in personal injury. The seriousness of the po­tential risk is identified by one of these three words:
DANGER – will result in serious injury or death.
WARNING – could result in serious injury or death.
CAUTION – may result in minor or moderate injury.
Note: It is strongly recommended that applications incorporate a high or low limit protective device, which will shut down the equipment at a pre-set process condition in order to prevent possible dam­age to property or products.
Warranty and Returns Statement
These products are sold by Chromalox under the war­ranties set forth in the following paragraphs. Such war­ranties are extended only with respect to a purchase of these products, as new merchandise, directly from Chromalox or from a Chromalox distributor, repre­sentative or reseller and are extended only to the first buyer thereof who purchases them other than for the purpose of resale.
Warranty
These products are warranted to be free from function­al defects in material and workmanship at the time the products leave Chromalox factory and to conform at that time to the specifications set forth in the relevant C instruction manuals sheet or sheets, for such products for a period of three years.
THERE ARE NO EXPRESSED OR IMPLIED WAR­RANTIES, WHICH EXTEND BEYOND THE WARRAN­TIES HEREIN AND ABOVE SET FORTH. CHROMAL­OX MAKES NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE PRODUCTS.
THE INTERNATIONAL HAZARD SYMBOL IS IN­SCRIBED ADJACENT TO THE REAR CONNEC­TION TERMINALS. IT IS IMPORTANT TO READ THIS MANUAL BEFORE INSTALLING OR COM­MISSIONING THE UNIT.
THIS SYMBOL MEANS THE EQUIPMENT IS PROTECTED THROUGHOUT BY DOUBLE INSU­LATION.
WARNING: PRODUCTS COVERED BY THIS MAN­UAL ARE SUITABLE FOR INDOOR USE, INSTAL­LATION CATEGORY II, POLLUTION CATEGORY 2 ENVIRONMENTS.
Limitations
Chromalox shall not be liable for any incidental damag­es, consequential damages, special damages, or any other damages, costs or expenses excepting only the cost or expense of repair or replacement as described above. Products must be installed and maintained in accordance with Chromalox instructions. There is no warranty against damage to the product resulting from corrosion. Users are responsible for the suitability of the products to their application.
For a valid warranty claim, the product must be re­turned carriage paid to the supplier within the war­ranty period. The product must be properly packaged to avoid damage from Electrostatic Discharge or other forms of harm during transit.
This user guide covers all versions of the Chromal­ox 4081/4082 Controller & Recorder.
i
Page 4
Table of Contents
Contents Page Number
Warranty and Returns Statement ......................................................................................................................... i
1 Introduction ..................................................................................................................................................... 1
2 Installation ....................................................................................................................................................... 1
Unpacking ......................................................................................................................................................... 1
Installation ......................................................................................................................................................... 2
Panel-Mounting ................................................................................................................................................ 2
Cleaning ............................................................................................................................................................ 2
3 Field Upgrade Options .................................................................................................................................... 3
Plug-Modules and Upgradeable Functions ...................................................................................................... 3
Preparing to Install or Remove Plug-in Modules .............................................................................................. 4
Removing/Replacing Option Modules .............................................................................................................. 4
Replacing the Instrument in its Housing ........................................................................................................... 5
Auto Detection of Plug-in Modules ................................................................................................................... 5
Data Recorder Board ........................................................................................................................................ 5
Profiler Enabling ................................................................................................................................................ 5
4 Electrical Installation ...................................................................................................................................... 6
Avoiding EMC Problems ................................................................................................................................... 6
Cable Isolation & Protection ........................................................................................................................ 6
Noise Suppression at Source ...................................................................................................................... 6
Sensor Placement (Thermocouple or RTD) ...................................................................................................... 7
Thermocouple Wire Identification ..................................................................................................................... 7
Thermocouple Wire Color CHART ............................................................................................................... 7
Pre-wiring – Cautions, Warnings & Information ............................................................................................... 8
Connections and Wiring ................................................................................................................................... 9
Central Terminal Connections ...................................................................................................................... 9
Outer Terminal Connections ...................................................................................................................... 10
Power Connections ................................................................................................................................... 10
Universal Input 1 Connections ................................................................................................................... 11
Universal / Auxiliary Input 2 Connections .................................................................................................. 12
Base Option 1 ............................................................................................................................................ 13
Base Option 2 ............................................................................................................................................ 13
Plug-in Module Slot 1 Connections ........................................................................................................... 13
Plug-in module slot 2 Connections............................................................................................................ 14
Plug-in Slot 3 Connections ........................................................................................................................ 15
Plug-in Slot A Connections ........................................................................................................................ 16
Option C Connections ............................................................................................................................... 17
5 Powering Up .................................................................................................................................................. 18
Powering Up Procedure .................................................................................................................................. 18
Front Panel Overview ...................................................................................................................................... 18
Display ............................................................................................................................................................ 18
LED Functions ................................................................................................................................................. 19
Keypad Functions & Navigation ...................................................................................................................... 19
ii
Page 5
Contents Page Number
6 Messages & Error Indications ...................................................................................................................... 20
Plug-in Module Problems ............................................................................................................................... 20
Sensor Break Detection ................................................................................................................................. 20
Un-Calibrated Input Detection ........................................................................................................................ 20
PV Over-range or Under-range Indication ...................................................................................................... 20
Auxiliary Input Over-range or Under-range Indication ................................................................................... 20
Cascade-Open ................................................................................................................................................ 20
Profile Not Valid .............................................................................................................................................. 20
USB Data Transfer Failure message ............................................................................................................... 20
Getting Help .................................................................................................................................................... 20
7 Application Setup .......................................................................................................................................... 21
Pre-Commissioning Considerations ............................................................................................................... 21
8 Operation and Configuration Menus ........................................................................................................... 23
Operation Mode .............................................................................................................................................. 23
Navigating and Adjusting Values in Operator Mode .................................................................................. 23
OPERATION MODE SCREEN SEQUENCE ............................................................................................... 24
Main Menu ...................................................................................................................................................... 29
Entry into the Main Menu ........................................................................................................................... 29
Unlock Codes ........................................................................................................................................... 29
Main Menu Options ............................................................................................................................. 29
Setup Wizard .................................................................................................................................................. 30
Manual entry to the Setup Wizard ............................................................................................................. 30
Setup Wizard Screens .......................................................................................................................... 30
Supervisor Mode ............................................................................................................................................. 30
Entry into Supervisor Mode ...................................................................................................................... 30
Supervisor Mode Screens ................................................................................................................... 31
Configuration Menu ........................................................................................................................................ 31
Entry into the Configuration Menu .................................................................................................................. 31
Configuration Menu Screens: ................................................................................................................... 31
Input Configuration Sub-Menu Screens .................................................................................................... 35
Control Configuration Sub-Menu Screens ................................................................................................ 36
Outputs Configuration Sub-Menu Screens ............................................................................................... 42
Alarm Configuration Sub-Menu Screens ................................................................................................... 43
Communications Configuration Sub-Menu Screens ................................................................................. 44
Data Recorder Configuration Sub-Menu Screens ..................................................................................... 44
Clock Configuration Sub-Menu Screens ................................................................................................... 46
Display Configuration Sub-Menu Screens ................................................................................................ 46
Lock Code Configuration Sub-Menu Screen............................................................................................. 47
Reset To Defaults Sub-Menu Screen ......................................................................................................... 47
The USB Menu ............................................................................................................................................... 47
Entry into the USB Menu ........................................................................................................................... 47
USB Menu Screens .............................................................................................................................. 48
Recorder Control Menu ................................................................................................................................. 49
Entry into the Recorder Control Menu ....................................................................................................... 49
Recorder Menu Screens ...................................................................................................................... 49
Profiler Setup Menu ....................................................................................................................................... 50
Entry into the Profiler Setup Menu ............................................................................................................ 50
Profiler Setup Menu Screens .......................................................................................................... 50
Profiler Control Menu ...................................................................................................................................... 51
Profiler Control Menu Screens ................................................................................................................... 53
iii
Page 6
Contents Page Number
Service & Product Information Mode .............................................................................................................. 54
Entry into Service & Product Information Mode ....................................................................................... 54
Service & Product Information Screens: ............................................................................................. 54
Automatic Tuning Menu .................................................................................................................................. 55
Entry into the Automatic Tuning Menu ...................................................................................................... 55
Automatic Tuning Menu Screens ......................................................................................................... 55
Lost Lock Codes ............................................................................................................................................. 56
9 Input Calibration & Multi-point Scaling ....................................................................................................... 57
User Calibration .............................................................................................................................................. 57
Calibration Reminder ................................................................................................................................ 57
Single Point Calibration ............................................................................................................................. 57
Two Point Calibration ................................................................................................................................ 58
Multi-point Scaling ..................................................................................................................................... 58
Base Calibration Adjustment .......................................................................................................................... 58
Required Equipment ................................................................................................................................. 59
Performing a Calibration Check ................................................................................................................ 59
Recalibration Procedure ........................................................................................................................... 59
Input Calibration Phases ..................................................................................................................... 59
10 Digital Inputs ................................................................................................................................................ 60
Digital Signal Type ........................................................................................................................................... 60
Inverting Digital Inputs .............................................................................................................................. 60
Soft Digital Inputs ........................................................................................................................................... 60
Digital Input Functions .................................................................................................................................... 60
11 Cascade Control ........................................................................................................................................... 62
Normal Cascade Operation ........................................................................................................................... 62
Cascade-Open ................................................................................................................................................ 62
Manual Mode ................................................................................................................................................. 62
Cascade Tuning .............................................................................................................................................. 63
12 Ratio Control ................................................................................................................................................ 64
13 Redundant Input ........................................................................................................................................... 64
14 Valve Motor Drive / 3-Point Stepping Control ........................................................................................... 66
Pro-EC44 2-Loop Graphical Profile Controller & Recorder ............................................................................ 66
Special Wiring Considerations for Valve Motor Control ................................................................................. 66
Position Feedback .......................................................................................................................................... 66
Valve Limiting ............................................................................................................................................. 66
15 Setpoint Sources ........................................................................................................................................... 67
Loop 1 Setpoint Sources ............................................................................................................................... 67
Loop 1 Profile Setpoint ............................................................................................................................. 67
Loop 2 Setpoint Sources ................................................................................................................................ 67
Loop 2 Profile Setpoint ............................................................................................................................. 67
16 Profiler ............................................................................................................................................................ 68
Profile Components ....................................................................................................................................... 68
Profile Header & Segment Information ...................................................................................................... 68
Profile Starting & Standard Segments ....................................................................................................... 68
Two Loop Profiles ..................................................................................................................................... 69
iv
Page 7
Contents Page Number
Loop-back Segments ............................................................................................................................... 70
Profile Running / Holding vs. Hold Segments ................................................................................................ 70
The Auto-Hold Feature ................................................................................................................................... 70
Auto Hold Examples ................................................................................................................................. 70
Profile Cycles & Repeat Sequences .............................................................................................................. 71
Power/Signal Lost Recovery Actions.............................................................................................................. 72
Profile End Actions .......................................................................................................................................... 73
Profile Abort Actions ...................................................................................................................................... 73
17 USB Interface ................................................................................................................................................ 74
Using the USB Port ........................................................................................................................................ 74
USB Memory Stick Folders & Files ........................................................................................................... 74
18 Data Recorder ............................................................................................................................................... 75
Recordable Values ......................................................................................................................................... 75
Recorder Control and Status ..................................................................................................................... 75
Uploading Data .......................................................................................................................................... 75
Additional Features & Benefits from the Recorder ......................................................................................... 75
19 Controller Tuning ........................................................................................................................................... 76
PID Sets & Gain Scheduling ........................................................................................................................... 76
Automatic Tuning ............................................................................................................................................ 76
Manually Tuning .............................................................................................................................................. 78
Tuning Control Loops - PID with Primary Output only ............................................................................... 78
Tuning Control Loops - PID with Primary & Secondary Outputs ............................................................... 78
Valve, Damper & Speed Controller Tuning ................................................................................................. 79
Fine Tuning ................................................................................................................................................ 81
20 Serial Communications ................................................................................................................................ 83
Supported Protocols ....................................................................................................................................... 83
RS485 Configuration.................................................................................................................................. 83
Ethernet Configuration ............................................................................................................................... 83
Supported Modbus Functions ........................................................................................................................ 84
Function Descriptions ................................................................................................................................ 84
Exception Responses ................................................................................................................................ 86
Modbus Parameters ....................................................................................................................................... 86
Data Formats ............................................................................................................................................. 86
Parameter Register Address Listings ............................................................................................................. 87
Calibration Reminder Parameters .............................................................................................................. 87
Universal Process Input 1 Parameters....................................................................................................... 88
Universal Process Input 2 Parameters....................................................................................................... 92
Digital Input Setup Parameters .................................................................................................................. 97
Plug-in Module Slot A Parameters .......................................................................................................... 112
Plug-in Module Slot 1 Parameters ........................................................................................................... 114
Plug-in Module Slot 2 Parameters .......................................................................................................... 116
Plug-in Module Slot 3 Parameters .......................................................................................................... 119
Output 4 Parameters ............................................................................................................................... 122
Output 5 Parameters ............................................................................................................................... 124
Linear Output 6 Parameters ..................................................................................................................... 126
Linear Output 7 Parameters ..................................................................................................................... 127
Loop 1 Setpoint Parameters ................................................................................................................... 128
Loop 2 Setpoint Parameters .................................................................................................................... 129
Aux A Input Parameters ........................................................................................................................... 130
v
Page 8
Contents Page Number
Loop 1 Control Parameters...................................................................................................................... 131
Loop 2 Control Parameters...................................................................................................................... 137
Alarm Parameters .................................................................................................................................... 143
Recorder & Clock Parameters ................................................................................................................. 151
Display & Security .................................................................................................................................... 157
Instrument Data Parameters .................................................................................................................... 164
Profiler Control & Status Parameters ....................................................................................................... 166
Profile Setup via Modbus ......................................................................................................................... 169
21 Glossary ....................................................................................................................................................... 186
22 PC Software ................................................................................................................................................. 208
Using the PC Software ................................................................................................................................ 208
Instrument Simulation ................................................................................................................................... 209
Configuring the Connection .......................................................................................................................... 210
Instrument Configuration .............................................................................................................................. 212
Main Parameter Adjustment .................................................................................................................... 212
Extending Functionality via Software ....................................................................................................... 213
Profile Creation and Editing .......................................................................................................................... 214
Data Recorder Trend Upload & Analysis ....................................................................................................... 216
23 Specifications ............................................................................................................................................. 217
Universal Process Inputs .............................................................................................................................. 217
General Input 1 and 2 Specifications ....................................................................................................... 217
Thermocouple Input ................................................................................................................................. 217
Resistance Temperature Detector (RTD) Input ........................................................................................ 218
DC Linear Input ........................................................................................................................................ 218
Input Functions ........................................................................................................................................ 219
Auxiliary Input ............................................................................................................................................... 219
Digital Inputs ................................................................................................................................................. 220
Output Specifications .................................................................................................................................. 221
Communications .......................................................................................................................................... 223
Control Loop(s) ............................................................................................................................................. 224
Alarms ........................................................................................................................................................... 225
Profiler Option ............................................................................................................................................... 225
Data Recorder Option ................................................................................................................................... 226
Display .......................................................................................................................................................... 226
Operating Conditions ................................................................................................................................... 226
Conformance Norms .................................................................................................................................... 226
Dimensions ................................................................................................................................................... 226
24 Chromalox 4801/4082 Product Coding ..................................................................................................... 227
vi
Page 9
1 Introduction
This product is a 1/4 DIN size (96 x 96mm front) micro­processor based graphical process controller, featuring a 160 x 80 pixel, monochrome LCD with dual color (red/ green) backlight. It operates from 100-240V at 50/60 Hz or 24V-48V AC/DC, depending on the model pur­chased. It can measure and control up to two process variables from a variety of sources such as tempera­ture, pressure, flow and level. Primary and secondary control outputs are possible for each loop.
Optional features include a second process input, USB interface, remote setpoint inputs RS485 or Ethernet communications, profile control and data recording. Control options include cascade, ratio and 3-point stepping valve control. Automatic tuning or 5 stage gain-scheduling are also available.
The USB Interface option allows uploading or down­loading instrument configuration settings to/from a USB memory stick, for easy configuration of multiple instruments or transfer to/from the PC configuration software. If the data recorder or profiler options are fit­ted, recordings and profile information can be trans­ferred via the memory stick.
The data recorder option allows the user to make re­cordings of the processes over time. Recordings can be transferred to a memory stick using the USB inter­face or downloaded via one of the communications op­tions.
The Profiler option allows the user to predefine up 255 segments, shared amongst up to 64 Setpoint Profiles. These control the setpoint levels for the control loop(s)
over time, increasing, decreasing or holding their val­ues as required. When combined with the real-time clock (part of the Data Recorder option) the profiling capabilities are expanded to allow automatic program start at a defined time and day.
Inputs are user configurable for thermocouple and RTD probes, as well as linear process signal types such as mVDC, VDC or mADC. Two-point calibration or multi­point scaling can compensate for errors or non-linear signals. Output options include single or dual relays, single or dual SSR drivers, triacs or linear mA/V DC. These can be used for process control, alarms/events or retransmission of the process variable or setpoint to external devices. Transmitter power supply options can provide an unregulated 24V DC (22mA) auxiliary output voltage, or a 0 to 10VDC stabilized excitation for external signal transmitters.
Up to 7 alarms can be defined as process high or low, deviation (active above or below controller setpoint), band (active both above and below setpoint), rate of input change, control loop, PID power or signal break types. Alarm status can be indicated by lighting an LED, changing the display backlight color or viewing the active alarm status screen. These alarms can be linked to any suitable output.
Configuration for basic applications is possible using the easy Setup Wizard run automatically at first power­up or manually later. Access to the full range of param­eters is via a simple menu driven front panel interface, or the PC based configuration software.
2 Installation
ELECTRIC SHOCK/FIRE HAZARD. Read and understand all instructions before ine installa­tion, servicing or operating controller. Failure to do so could result in personal injury or death and/or equipment or property damage.
Unpacking
1. Remove the product from its packing. Retain the
packing for future use, in case it is necessary to transport the instrument to a different site or to re­turn it to the supplier for servicing.
2. The instrument is supplied with a panel gasket and
push-fit mounting clamp. A multi-page concise manual is supplied with the instrument, in one or more languages. Examine the delivered items for damage or defects. If any are found, contact your supplier immediately.
Installation
ELECTRIC SHOCK/FIRE HAZARD. Installation should be only performed by technically com­petent personnel. It is the responsibility of the installing engineer to ensure that the config­uration is safe. Local Regulations regarding electrical installation & safety must be ob­served (e.g. US National Electrical Code (NEC) or Canadian Electrical Code). Failute to follow these instructions could result in personal in­jury or death or equipment/property damage.
1
Page 10
Figure 1. Main Dimensions
Gasket
Mounting Panel
Panel-Mounting
The mounting panel must be rigid and may be up to
6.0mm (0.25 inches) thick. The cut-out size is:
92mm x 92mm (+0.5mm / -0.0mm).
Instruments may be mounted side-by-side in a mul­tiple installation, but instrument to panel moisture and dust sealing will be compromised. Allow a 20mm gap above, below and behind the instrument for ventilation. The cut-out width (for n instruments) is:
(96n - 4) mm or (3.78n - 0.16) inches
If panel sealing must be maintained, mount each in­strument into an individual cut-out with 10mm or more clearance between the edges of the holes.
Note: The mounting clamp tongues may engage the ratchets either on the sides or the top/bottom faces of the Instrument housing. When installing several Instruments side-by-side in one cut-out, use the ratchets on the top/bottom faces.
Ensure the inside of the panel remains within the instrument operating temperature and that there is adequate airflow to prevent overheating.
Note: For an effective IP66 seal against dust and moisture, ensure gasket is well compressed against the panel, with the 4 tongues located in the same ratchet slot.
Do not remove the panel gasket, as this may result in inadequate clamping and sealing of the instrument to the panel.
Once the instrument is installed in its mounting panel, it may be subsequently removed from its housing if nec­essary, as described in the Fitting and Removing Plug­in Modules section.
Cleaning
Clean the front panel by washing with warm soapy water and dry immediately. If the USB option is fitted, close the USB port cover before cleaning.
Clamp
Ratchets
Instrument
Housing
Figure 2. Panel-Mounting
2
1. Insert instrument into the panel cut-out.
2. Hold front bezel firmly
(without pressing on the display area), and re-fit mounting clamp. Push the clamp forward, using a tool if necessary, until gasket compresses and instrument is held firmly
in position.
Page 11
3 Field Upgrade Options
Plug-Modules and Upgradeable Functions
Plug-Modules can be either pre-installed at the time of manufacture, or retrofitted in the field to expand the capabilities of the controller. Contact your supplier to purchase these items. Part numbers and circuit board identification numbers for the plug-in modules and ac­cessories are shown in below:
Table 1. Options and Accessories
Plastic pegs prevent fitting of older non-rein­forced single relay modules (Board Identifica­tion Numbers 637/01 and 638/01). Fitting the older relay modules reduces the isolation rat­ing to Basic 240V Isolation and is therefore not recommended. Remove this peg when fitting Dual Relay Modules.
PAR T
NUMBER DESCRIPTION
OPTION SLOT (OUTPUT) 1
0149-50043
0149-50044
0149-50077
0149-50047
OPTION SLOT (OUTPUT) 2 OR 3
0149-50050
0149-50049
0149-50051
0149-50052
0149-50070
0149-50053
OPTION SLOT A
0149-50056
0149-50057
0149-50055
0149-50058
ACCESSORIES
0149-50063
0149-50092
0149-50086
0149-50088
Single Relay Output for option slot (Output) 1 716/01
Single SSR Driver Output for option slot (Output) 1 716/02
Triac Output for option slot (Output) 1
Linear mA / Voltage Output module for option slot (Output) 1
Single Relay Output for option slot (Output) 2 or 3
Dual Relay Output for option slot (Output) 2 or 3
Single SSR Driver Output for option slot (Output) 2 or 3
Dual SSR Driver Output for option slot (Output) 2 or 3
Triac module Output for slot (Output) 2 or 3
24VDC Transmitter Power Supply for option slot (Output) 2 or 3
Digital Input for plug-in module slot A
Basic Auxiliary Input for plug-in module slot A
RS485 Serial Communications for plug-in module slot A
Ethernet Communications for plug-in module slot A
Profiler Enable Key-code
ChromaloxPro Configuration Software Only (60 & 80 Series)
Univ S/W Converter & PC Cable 20/40/50/60/80 Series
Cable Only – 40/50/80 Series to Universal Adaptor
BOARD IDENTIFICATION
NUMBER
716/01
716/02
716/03
639/01
717/01
644/01
717/02
644/02
647/01
642/01
641/02
653/01
680/01
707/01
3
Page 12
Board Positions
Board Mounting
l Latch (x1)
Board
100
Main Board Connectors
Note: All dual relay modules have reinforced isola­tion.
Struts (x4)
Front Panel Remova
Plug-in Module A
Plug-in Module 3
Power Supply
2nd Universal Input & Base Option 2 Board
1st Universal Input & Base Option 1 Board
Plug-in Module 1
Plug-in Module 2
USB/Digital Input C Option Board
Figure 3. Rear View (uncased) & Board Positions
Preparing to Install or Remove Options
Modules
POWER SUPPLY
BOARD
Transformer
Color Code
-240V (Yellow)
24-48V(Blue)
Display Board
Connections
1st UNIVERSAL
INPUT / BASE
OPTION 1
BOARD
Module Slot 3
Connector PL4B
Module Slot A Connectors PL5, & PL6
Module Slot 1 Connectors PL7 & PL8
PC Configurator
Socket SK1
Module Slot 2 Connector PL4A
Figure 4. Main Board Connectors
This product is designed to allow the user to recon­figure some hardware options in the field by changing the plug-in modules in slots 1, 2, 3, & A located on the power supply and 1st universal input boards. The main boards (display/CPU, power supply, inputs 1 & 2 and digital input/USB) are factory fitted, but may be removed while reconfiguring the plug-in modules. Take care when re-fitting these boards. Observe the power supply board transformer color, and case labelling to check the supply voltage, otherwise irreparable dam­age may occur.
ELECTRIC SHOCK HAZARD. Disconnect all power before installing or servicing controller. Failure to do so could result in personal injury or property damage.
1. Grip the edges of the front panel (there is a finger grip on each edge) and pull it forwards approxi­mately 10mm, until the Front Panel Removal Latch prevents further movement. The purpose of the latch is to prevent removal of the instrument without the use of a tool.
2. The Front Panel Removal Latch must be pushed down to allow removal of the instrument. Using a tool (e.g. screwdriver or pen tip), press down it down through the front central ventilation hole. This will release the instrument from the case.
3. The internal boards can now be accessed. Take note of the orientation of the instrument and boards for subsequent replacement into the housing. The positions of the boards, their mountings and the Front Panel Removal Latch are shown above.
Replacement of boards must be carried out by a technically competent technician. If the Pow­er Supply board does not match the labelling, users may apply incorrect voltage resulting in irreparable damage.
Removing/Replacing Option Modules
1. To remove or replace Plug-in Modules 1, 2, 3 or A it
is necessary to detach the power supply and input boards from the front panel by lifting first the upper and then lower mounting struts.
2. Remove or fit the modules to the connectors on the power supply and input boards. The location of the connectors is shown below. Plastic pegs prevent fitting of older nonreinforced single relay modules – Remove the peg to fit dual relay modules
3. Assemble the Power Supply and Input boards to­gether. Tongues on each option module locate into slots cut into the main boards, opposite each of the connectors. Hold the Power and Input boards to­gether and relocate them back on their mounting struts.
4
Page 13
4. Push the boards forward to ensure correct connec­tion to the front Display/CPU board and re-check the installation of the Option C and/or 2nd Input / Base Option 2 boards if present.
Check for correct orientation of the modules and that all pins are located correctly.
Replacing the Instrument in its Housing
Data Recorder Board
If installed, the Data Recorder memory and Real Time Clock (RTC) components are located on a plug-in daughter board attached to the front Display/CPU board.
Servicing of the Data Recorder/RTC circuit and replacement of the lithium battery should only be carried out by a technically competent tech­nician.
ELECTRIC SHOCK HAZARD. Disconnect all power before installing or servicing controller. Failure to do so could result in personal injury or property damage.
With the required option modules correctly located into their respective positions the instrument can be replaced into its housing as follows:
1. Hold the Power Supply and Input boards together.
2. Align the boards with the guides in the housing.
3. Slowly and firmly, push the instrument into position
in its case.
Ensure that the instrument is correctly ori­entated. A mechanical stop will operate if an attempt is made to insert the instrument in the wrong orientation, this stop MUST NOT be over-ridden.
Auto Detection of Plug-in Modules
The instrument automatically detects which plug-in modules have been fitted into each slot. The menus and screens change to reflect the options compatible with the hardware. The modules fitted can be viewed in the product information menu, as detailed in the Prod­uct & Service Information Mode section of this manual.
Profiler Enabling
If you purchased a controller with the Profiler option installed, these features will be enabled during manu­facture.
Controllers supplied without the Profiler option in­stalled can be upgraded in the field by purchasing a licence code number from your supplier. A unique code must be purchased to enable profiling on each control­ler that requires it.
Entering the Profiler Enable Code
Hold down the and keys during the power-up “splash screen”.
Using the or keys, enter the 16-character li­cence code in the displayed screen.
Press to move on to the next character. Press to move back to the previous character.
Press after entering the final character.
To confirm if profiling is installed in your instrument, check the Controller Feature Information in Product & Service Information Mode.
5
Page 14
4 Electrical Installation
ELECTRIC SHOCK/FIRE HAZARD. Installation should be only performed by technically com­petent personnel. It is the responsibility of the installing engineer to ensure that the configu­ration is safe. Local Regulations regarding elec­trical installation & safety must be observed (e.g. US National Electrical Code (NEC) or Ca­nadian Electrical Code). Failure to follow these instructions could result in personal injury or
death and/or equipment / property damage.
Avoiding EMC Problems
This controller has passed EMC compliance tests to EN61326. There should be no difficulty achieving this level of compliance in use, but it should be borne in mind that the wiring of the installation can significantly reduce the efficiency of instrumentation immunity due to the ease with which high frequency RF can enter via unprotected cables.
The following general recommendations can reduce the possibility of EMC problems.
1. If the instrument is being installed in existing equip­ment, wiring in the area should be checked to en­sure that good wiring practices have been followed.
2. The controller should be mounted in a properly earthed metal cabinet. All round metal shielding is important, so the cabinet door may require a con­ductive sealing strip.
3. It is good practice to ensure that the AC neutral is at or near ground (earth) potential. A proper neutral will help ensure maximum performance from the instru­ment.
4. Consider using a separate isolation transformer to feed only the instrumentation. A transformer can protect instruments from noise found on the AC power supply.
tween them. If wires MUST cross each other, ensure they do so at 90 degrees to minimize interference.
Keep signal cables as short as possible. If an earthed thermocouple is used or if the sensor has a screened cable, it should be earthed at one point only, preferably at the sensor location or cabinet entry point, by means of a metal gland. Ideally all analogue and digital signals should be shielded like this, but for unscreened cables, large diameter ferrite sleeves at the cabinet entry point are an effective method of reducing RF interference. Looping cables through the ferrite sleeves a number of times improves the efficiency of the filtering. For mains input cables the fitting a suitable mains filter can pro­vide good results.
Noise Suppression at Source
If possible, eliminate mechanical contact relays and replace with solid-state relays. Noise-generating de­vices such as Ignition transformers, arc welders, mo­tor drives, relays and solenoids should be mounted in a separate enclosure. If this is not possible, separate them from the instrumentation, by the largest distance possible.
Many manufacturers of relays, contactors etc supply ‘surge suppressors’ to reduce noise at its source. For those devices that do not have surge suppressors sup­plied, Resistance-Capacitance (RC) networks and/or Metal Oxide Varistors (MOV) may be added.
Inductive coils: MOVs are recommended for transient suppression in inductive coils. Connect as close as possible, in parallel to the coil. Additional protection may be provided by adding an RC network across the MOV.
Cable Isolation & Protection
Four voltage levels of input and output wiring may be used with the unit:
1. Analog inputs or outputs (for example thermocou­ple, RTD, VDC, mVDC or mADC)
2. Relays & Triac outputs
3. Digital Inputs & SSR Driver outputs
4. AC power
The only wires that should run together are those of the same category.
If any wires need to run parallel with any from another category, maintain a minimum space of 150mm be-
Figure 5. Transient Suppression
with Inductive Coils
Contacts: Arcing may occur across contacts when
they open and close. This results in electrical noise as well as damage to the contacts. Connecting a properly sized RC network can eliminate this arc.
For circuits up to 3 amps, a combination of a 47 ohm resistor and 0.1 microfarad capacitor (1000 volts) is recommended. For circuits from 3 to 5 amps, connect two of these in parallel.
6
Page 15
Figure 6. Contact Noise Suppression
Sensor Placement (Thermocouple or RTD)
If a temperature probe is to be subjected to corrosive or abrasive conditions, it must be protected by an ap­propriate thermowell.
Probes must be positioned to reflect the true process temperature:
1. In a liquid media - the most agitated area
2. In air - the best circulated area
The placement of probes into pipe work some distance from the heating vessel leads to trans­port delay, which results in poor control.
For a two wire RTD, a wire link should be used in place of the third wire (see the wiring section for details). Two wire RTDs should only be used with lead lengths less than 3 metres.
Use of three wire RTDs is strongly recommended to reduce errors do to lead resistance.
Thermocouple Wire Identification
The different thermocouple types are identified by their wires color, and where possible, the outer insulation as well. There are several standards in use throughout the world, but most regions now use the International IEC584-3 standard.
The table below shows the wire and sheath colors used for most common thermocouple types. The format used in this table is:
+ Wire
Sheath
- Wire
Type
J +*
T +
K +
-*
N +
B +
R & S +
Table 2. Thermocouple Extension Wire Colors
International
IEC584-3
Black
-
White Red Blue Black Blue
Brown
-
White Red Blue Blue Brown
Green
White Red Blue Purple Green
Pink
-
White Red Blue
Grey
-
White Red Grey
Orange
-
White Red Blue Green White
Black
Brown
Green
Pink
Grey
Orange
USA ANSI
MC 96.1
White
Black
Blue
Blue
Yellow
Yellow
Orange
Orange
Grey
Grey
Black
Green
British
BS1843
Yellow
Black
White
Blue
Brown
Red
Orange
Orange
White
Green
French
NFC 42-324
Yellow
Black
Yellow
Blue
Yellow
Yellow
Yellow
Green
German
DIN 43710
Red
Blue
Red
Brown
Red
Green
Red
Grey
Red
White
C (W5)
*Wire is magnetic. a magnet can be used to assist with correctly identifying the type and polarity of the conductors
+
-
White
White
Red
7
Page 16
Pre-Wiring: Cautions, Warnings & Information
Installation should be only performed by tech­nically competent personnel. It is the respon­sibility of the installing engineer to ensure that the configuration is safe. Local Regulations regarding electrical installation & safety must be observed (e.g. US National Electrical Code (NEC) or Canadian Electrical Code).
ELECTRIC SHOCK/FIRE HAZARD. THIS EQUIP­MENT IS DESIGNED FOR INSTALLATION IN AN ENCLOSURE THAT PROVIDES ADEQUATE PRO­TECTION AGAINST ELECTRIC SHOCK. THE ISOLATION SWITCH SHOULD BE LOCATED IN CLOSE PROXIMITY TO THE UNIT, IN EASY REACH OF THE OPERATOR AND APPROPRI­ATELY MARKED. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PERSON­AL INJURY OR DEATH AND/OR EQUIPMENT / PROPERTY DAMAGE.
This symbol means the equipment is protected throughout by double insu­lation. All external circuits connected must provide double insulation. Fail­ure to comply with the installation in­structions may impact the protection provided by the unit.
ELECTRIC SHOCK/FIRE HAZARD. TO AVOID ELECTRICAL SHOCK, AC POWER WIRING MUST NOT BE CONNECTED TO THE SOURCE DISTRI­BUTION PANEL UNTIL ALL WIRING PROCE­DURES ARE COMPLETED. CHECK THE INFOR­MATION LABEL ON THE CASE TO DETERMINE THE CORRECT VOLTAGE BEFORE CONNECT­ING TO A LIVE SUPPLY. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PER­SONAL INJURY OR DEATH AND/OR EQUIPMENT / PROPERTY DAMAGE.
8
Page 17
OPTION
OPTION
Connections and Wiring
Central Terminal Connections
Note: The wiring diagram below shows all possible combinations to the main connections (numbered 1 to 24) in the centre of the case rear. The actual con­nections required depends upon the features and modules fitted.
ELECTRIC SHOCK/FIRE HAZARD. CHECK THE INFORMATION LABEL ON THE CASE TO DE­TERMINE THE CORRECT VOLTAGE BEFORE CONNECTING TO A LIVE SUPPLY. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RE­SULT IN PERSONAL INJURY OR DEATH AND/OR EQUIPMENT / PROPERTY DAMAGE.
OPTION
Figure 7. Central Terminals 1 to 24
OPTION
9
Page 18
Outer Terminal Connections
Note: The wiring diagram below shows the Cen­tral Terminals (numbered 25 to 42) at the sides of the case rear. Connections for the 2nd Input, Base Option 2 and Digital Input C are shown. The actual connections required depends upon the features and modules fitted.
Figure 8. Outer Terminals 25 to 42
Power Connections
ELECTRIC SHOCK/FIRE HAZARD. CHECK THE INFORMATION LABEL ON THE CASE TO DE­TERMINE THE CORRECT VOLTAGE BEFORE CONNECTING TO A LIVE SUPPLY. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RE­SULT IN PERSONAL INJURY OR DEATH AND/OR EQUIPMENT / PROPERTY DAMAGE.
ELECTRIC SHOCK/FIRE HAZARD. THIS EQUIP­MENT IS DESIGNED FOR INSTALLATION IN AN ENCLOSURE THAT PROVIDES ADEQUATE PRO­TECTION AGAINST ELECTRIC SHOCK. THE ISOLATION SWITCH SHOULD BE LOCATED IN CLOSE PROXIMITY TO THE UNIT, IN EASY REACH OF THE OPERATOR AND APPROPRI­ATELY MARKED. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PERSON­AL INJURY OR DEATH AND/OR EQUIPMENT / PROPERTY DAMAGE.
Power Connections - Mains Powered Instruments
Mains powered instruments operate from a 100 to 240V (±10%) 50/60Hz supply. Power consumption is 20VA. Connect the line and neutral as illustrated via a UL listed fuse type: 250V AC 1Amp anti-surge and a two-pole IEC60947-1 & IEC60947-3 compliant isola­tion switch / circuit breaker located within easy reach of the operator and appropriately marked. If relays switch mains voltage this should be separate from the instruments mains supply.
Figure 9. Mains Power Connections
10
Page 19
Power Connections - 24/48V AC/DC Powered Instruments
24/48V AD/DC powered instruments will operate from a 20 to 48V AC or 22 to 55V DC supply. AC power con­sumption is 15VA max, DC power consumption is 12 watts max. Connection should be via a UL listed fuse type: 65v dc 350mAamp anti-surge and a two-pole IEC60947-1 & IEC60947-3 compliant isolation switch / circuit breaker located within easy reach of the opera­tor and appropriately marked.
Figure 10. 24/48V AC/DC Power
Connections
Universal Input 1 Connections – PT100 / NI120 (RTD) input
The inputs supports two types of RTD. PT100 (plati­num sensor, 100Ω at 0°C). For three wire RTDs, con­nect the resistive leg and the common legs of the RTD as illustrated. For a two wire RTD a wire link should be fitted across terminals 2 & 3 (in place of the third wire). Two wire RTDs should only be used when the leads are less than 3 metres long. Avoid cable joints.
Universal Input 1 Connections
Universal Input 1 is present on all models. This input is normally used for the measured variable signal from a process to be controlled. It can be connected to ther­mocouples; resistance temperature detectors; ana­logue mA; mV or V DC signals. The input settings are in the Input 1 Configuration sub-menu. Connections for the various types are shown below. Ensure that the sig­nal is correctly connected, paying particular attention to the polarity.
Universal Input 1 Connections ­Thermocouple (T/C)
Supported thermocouple types & ranges are listed in the input specifications section on page 245. Only use the correct thermocouple wire or compensating cable from the sensor to the instrument terminals avoiding joints in the cable if possible. Where joints are made, special thermocouple connectors must be used. Fail­ure to use the correct wire type and connectors will lead to inaccurate readings. Ensure correct polarity of the wires by cross-referencing the colors with the ther­mocouple reference table.
Figure 12. Input 1 - RTD Connections
Four wire RTDs can be used, provided that the fourth wire is left unconnected. This wire should be cut short or tied back so that it cannot contact any of the termi­nals on the rear of the instrument.
Universal Input 1 Connections - Linear Volt, mV or mA input
The input supports the following linear/analogue sig­nals: 0 to 50mV; 10 to 50mV; 0 to 5V; 1 to 5V; 0 to 10V; 2 to 10V; 0 to 20mV; 4 to 20mA from any suit­able source. Voltage & millivolt signals are connected to terminals 2 & 3, milliamp signals are connected to 1 & 3. Carefully observe the position & polarity of the connections.
Figure 11.
Input 1 - Thermocouple Connections
Figure 13. Input 1 - DC Volt, mV & mA Connections
11
Page 20
Universal / Auxiliary Input 2 Connections
An Auxiliary Input 2 option is fitted to some models. This can connect to a potentiometer; analogue mA; mV or V DC signal for a remote setpoint input signal, or for flow/valve position feedback information. Alternatively, a second Universal Input 2 option may be fitted. In ad­dition to the remote setpoint input signal or feedback information possible with the auxiliary input, the 2nd Universal Input can be used as a second process con­trol loop for two control loops, or used in conjunction with input one in more complex single control loops. Universal Input 2 can be connected to thermocouples; resistance temperature detectors; potentiometers; an­alogue mA; mV or V DC signals.
The settings are in the Input 2 Configuration sub-menu. Connections for the various types are shown below. Ensure that the signal is correctly connected, paying particular attention to the polarity.
Universal Input 2 Connections ­Thermocouple (T/C)
The optional 2nd universal input, supports various thermocouple types. Supported types & ranges are listed in the input specifications section on page 245. Only use the correct thermocouple wire or compensat­ing cable from the sensor to the instrument terminals avoiding joints in the cable if possible. Where joints are made, special thermocouple connectors must be used. Failure to use the correct wire type and connectors will lead to inaccurate readings. Ensure correct polarity of the wires by cross-referencing the colors with a ther­mocouple reference table.
Figure 15. Input 2 - RTD Connections
Four wire RTDs can be used, provided that the fourth wire is left unconnected. This wire should be cut short or tied back so that it cannot contact any of the termi­nals on the rear of the instrument.
Universal / Auxiliary Input 2 Connections ­Linear Volt, mV or mA input
The optional auxiliary or 2nd universal input supports the following linear/analogue signals: 0 to 50mV; 10 to 50mV; 0 to 5V; 1 to 5V; 0 to 10V; 2 to 10V; 0 to 20mV; 4 to 20mA from any suitable source. Voltage & milli­volt signals are connected to terminals 2 & 3, milliamp signals are connected to 1 & 3. Carefully observe the polarity of the connections.
Figure 14. Input 2 - Thermocouple Connections
Universal Input 2 Connections – PT100 / NI120 (RTD) Input
The optional 2nd universal input, supports two types of RTD. PT100 (platinum sensor, 100Ω at 0°C). For three wire RTDs, connect the resistive leg and the common legs of the RTD as illustrated. For a two wire RTD a wire link should be fitted across terminals 35 & 36 (in place of the third wire). Two wire RTDs should only be used when the leads are less than 3 metres long. If possible, avoid cable joints.
Figure 16. Input 2 - DC Volt, mV & mA Connections
Universal / Auxiliary Input 2 Connections – Potentiometer
The optional auxiliary or 2nd universal input, the termi­nals detailed below can be used to connect a feedback potentiometer. Minimum potentiometer resistance is 100Ω.
Figure 17. Input 2 - Potentiometer Connections
12
Page 21
Base Option 1
Base Option 1 provides one or two factory fitted out­puts. A relay designated as Output 4 is fitted on all models, and an optional linear mA/V DC designated as Output 6. Base options cannot be added after manu­facture. The functions of outputs 4 & 6 are set in the Output Configuration sub-menu. Connect as illustrated below.
Base Option 1 Relay Output 4
Present on all instruments, Output 4 is a SPST relay, rated at 2 amps at 240 VAC resistive. If it is used to switch mains voltages, the supply should be separate from the instrument supply and should be correctly
switched and fused.
Figure 20. Relay Output 5 Connections
Base Option 2 Linear Output 7
Part of base option 2, Output 7 is an optional linear mV/V DC analogue output. The type & range are se­lectable from 0 to 5, 0 to 10, 2 to 10V & 0 to 20 or 4 to 20mA.
Figure 21. Linear Output 7 Connections
Figure 18. Relay Output 4 Connections
Base Option 1 Linear Output 6
Part of base option 1, Output 6 is an optional linear mV/V DC analogue output. The type & range are se­lectable from 0 to 5, 0 to 10, 2 to 10V & 0 to 20 or 4 to
20mA.
Figure 19. Linear Output 6 Connections
Base Option 2
Base Option 2 provides one or two factory fitted out­puts. An optional relay designated as Output 5, and an optional linear mA/V DC designated as Output 7. Base options cannot be added after manufacture. The func­tions of outputs 5 & 7 are set in the Output Configura­tion sub-menu. Connect as illustrated below.
Plug-in Module Slot 1 Connections
A selection of plug-in modules are available for Mod­ule Slot 1. They can be fitted during manufacture, or purchased and fitted later by the user. Modules in slot 1 are designated Output 1. They are not interchange­able with those in slot 2 or 3. Their function is set in the Output Configuration sub-menu. Connect as illustrated below.
Plug-in Module Slot 1 – Single Relay Out­put Module
If fitted with a single relay output module, connect as shown. The relay contacts are SPDT and rated at 2 amps resistive, 240 VAC. If it is used to switch mains voltages, the supply should be separate from the in­strument supply and should be correctly switched and fused.
Base Option 2 Relay Output 5
Part of base option 2, Output 5 is a SPST relay, rated at 2 amps at 240 VAC resistive. If it is used to switch mains voltages, the supply should be separate from the instrument supply and should be correctly switched and fused.
Figure 22.
Plug-in Module Slot 1 – Single Relay Module
Plug-in Module Slot 1 – Single SSR Driver Output Module
If fitted with a single SSR Driver output module, con­nect as shown. The 10V DC pulse signal (load resis­tance 500 ohms) is isolated from all inputs/outputs except other SSR drivers.
13
Page 22
Figure 23.
Plug-in Module Slot 1 – Single SSR Driver Module
Plug-in Module Slot 1 - Triac Output Module
If fitted with a triac output module, connect as shown. This output is rated at 0.01 to 1 amp @ 280V AC 50/60Hz. Isolated from all other inputs and outputs. A snubber should be fitted across inductive loads to en­sure reliable switch off of the Triac.
Figure 24. Plug-in Module Slot 1 - Triac Module
Plug-in Module Slot 1 - Linear Voltage or mADC Output module
If fitted with a DC linear output module, connect as shown. Output type & range are selectable from 0 to 5, 0 to 10, 2 to 10V & 0 to 20 or 4 to 20mA. Isolated from all other inputs and outputs.
Plug-in Module Slot 2 – Single Relay Out­put Module
If fitted with a single relay output module, connect as shown. The relay contacts are SPDT and rated at 2 amps resistive, 240 VAC. If it is used to switch mains voltages, the supply should be separate from the in­strument supply and should be correctly switched and fused.
Figure 26.
Plug-in Module Slot 2 – Single Relay Module
Plug-in Module Slot 2 - Dual Relay Output Module
If fitted with a dual relay output module, connect as shown. This module has two independent SPST relays for outputs 2A and 2B, with a shared common terminal. The contacts are rated at 2 amp resistive 240 VAC. If used to switch mains voltages, the supply should be separate from the instruments mains supply and the contacts should be correctly switched and fused.
Figure 25. Plug-in Module Slot
1 - Linear Voltage & mADC Module
Plug-In Module Slot 2 Connections
A selection of plug-in modules are available for Module Slot 2. They are interchangeable with slot 3, but not slot 1.They can be fitted during manufacture, or pur­chased and fitted later by the user. Modules in slot 2 are designated Output 2, and for dual modules Output 2A and 2B. Their functions are set in the Output Con­figuration sub-menu. Connect as illustrated below.
Figure 27.
Plug-in Module Slot 2 - Dual Relay Module
Plug-in Module Slot 2 – Single SSR Driver Output Module
If fitted with a single SSR Driver output module, con­nect as shown. The 10V DC pulse signal (load resis­tance 500 ohms) is isolated from all inputs/outputs except other SSR drivers.
14
Page 23
Figure 28.
Plug-in Module Slot 2 – Single SSR Driver Module
Figure 31. Plug-in Module Slot 2 -
Transmitter Power Supply Module
Plug-in Module Slot 2 – Dual SSR Driver Output Module
If fitted with a dual SSR Driver output module, the two solid-state relay driver outputs are designated as Out­put 2A and 2B. The outputs are 10V DC pulse signals, (load resistance 500 ohms). They are isolated from all inputs/output except other SSR driver outputs. Con­nect as shown making note of the shared positive common terminal.
Figure 29.
Plug-in Module Slot 2 – Dual SSR Driver Module
Plug-in Module Slot 2 ­Triac Output Module
If fitted with a Triac output module, connect as shown. This output is rated at 0.01 to 1 amp @ 280V AC 50/60Hz. Isolated from all other inputs and outputs. A snubber should be fitted across inductive loads to en­sure reliable switch off of the Triac.
Figure 30. Plug-in Module Slot 2 - Triac Module
Plug-in Slot 3 Connections
A selection of plug-in modules are available for Module Slot 3. They are interchangeable with slot 2, but not slot 1.They can be fitted during manufacture, or pur­chased and fitted later by the user. Modules in slot 3 are designated Output 3, and for dual modules Output 3A and 3B. Their functions are set in the Output Con­figuration sub-menu. Connect as illustrated below.
Plug-in Module Slot 3 – Single Relay Output Module
If fitted with a single relay output module, connect as shown. The relay contacts are SPDT and rated at 2 amps resistive, 240 VAC. If it is used to switch mains voltages, the supply should be separate from the in­strument supply and should be correctly switched and fused.
Figure 32.
Plug-in Module Slot 3 – Single Relay Module
Plug-in Module Slot 3 - Dual Relay Output Module
If fitted with a dual relay output module, connect as shown. This module has two independent SPST relays for outputs 3A and 3B, with a shared common terminal. The contacts are rated at 2 amp resistive 240 VAC. If used to switch mains voltages, the supply should be separate from the instruments mains supply and the contacts should be correctly switched and fused.
Plug-in Module Slot 2 ­Transmitter Power Supply Module
If fitted with a transmitter power supply module (Tx­PSU), connect as shown. The output is a 24V nominal (unregulated, 19 to 28V DC), supply at 22mA max. Only one TxPSU is supported, do not fit in slot 2 if one is already fitted in slot 3.
Figure 33
Plug-in Module Slot 3 - Dual Relay Module
15
Page 24
Plug-in Module Slot 3 – Single SSR Driver Output Module
If fitted with a single SSR Driver output module, con­nect as shown. The 10V DC pulse signal (load resis­tance 500 ohms) is isolated from all inputs/outputs except other SSR drivers.
Figure 34
Plug-in Module Slot 3 – Single SSR Driver Module
Plug-in Module Slot 3 – Dual SSR Driver Output Module
If fitted with a dual SSR Driver output module, the two solid-state relay driver outputs are designated as Out­put 3A and 3B. The outputs are 10V DC pulse signals, (load resistance 500 ohms). They are isolated from all inputs/output except other SSR driver outputs. Con­nect as shown making note of the shared positive common terminal.
Plug-in Module Slot 3 - Transmitter Power Supply Module
If fitted with a transmitter power supply module (Tx­PSU), connect as shown. The output is a 24V nominal (unregulated, 19 to 28V DC), supply at 22mA max. Only one TxPSU is supported, do not fit in slot 3 if one is already fitted in slot 2.
Figure 37. Plug-in Module Slot 3 -
Transmitter Power Supply Module
Plug-in Slot A Connections
A selection of plug-in modules are available for Mod­ule Slot A. They can be fitted during manufacture, or purchased and fitted later by the user. Depending on their functions, they are setup Input or Communica­tions configuration sub-menus. Connect as illustrated below.
Figure 35.
Plug-in Module Slot 3 – Dual SSR Driver Module
Plug-in Module Slot 3 ­Triac Output Module
If fitted with a Triac output module, connect as shown. This output is rated at 0.01 to 1 amp @ 280V AC 50/60Hz. Isolated from all other inputs and outputs. A snubber should be fitted across inductive loads to en­sure reliable switch off of the Triac.
Figure 36. Plug-in Module Slot 3 - Triac Module
Plug-in Module Slot A – Basic Auxiliary Input Module
If fitted with a basic auxiliary mA/V DC analogue input module, connect as shown. Isolated from all inputs/ outputs. Consider using the 2nd auxiliary input (if avail­able) instead, as this has additional features and leaves plug-in module slot A free for other modules.
Figure 38. Plug-in Module Slot A –
Basic Auxiliary Input Module
Plug-in Module Slot A ­Ethernet Communications Module
If fitted with the Ethernet communication module, the communications protocol available is Modbus TCP. Isolated from all inputs/outputs. If necessary, cut out the removable panel to access the RJ45 connector through the top of the case. No rear connections are required.
16
Page 25
Plug-in Module Slot A ­RS485 Serial Communications Module
If fitted with the RS485 serial communication module, the protocol used is Modbus RTU. Isolated from all inputs/outputs. Carefully observe the polarity of the A (Rx/Tx +ve) and B (Rx/Tx -ve) connections.
Figure 39. Plug-in Module Slot A –
RS485 Serial Communications Module
External computing devices connected to the communications port should comply with the standard, UL 60950.
Plug-in Module Slot A – Single Digital In­put Module
If a digital input module is fitted, it provides a fully iso­lated input that is held high via a pull-up resistor. The input can be connected to either to voltage free con­tacts (e.g. from a switch), or a TTL compatible signal. Logic High = Open contacts (>5000Ω) or 2 to 24VDC signal. Logic Low = Closed contacts (<50Ω) or -0.6 to +0.8VDC signal.. Connect as shown.
Option C Connections – Multiple Digital Input Module
If the Multiple Digital Input option is fitted, the connec­tions are as illustrated. The 8 opto-isolated inputs each have a positive input terminal and share a common negative terminal. The inputs are held high with internal pull-up resistors, so may be connected to either volt­age free contacts (e.g. from a switch), or TTL compat­ible signals: Logic High = Open contacts (>5000Ω) or 2 to 24VDC signal. Logic Low = Closed contacts (<50Ω) or -0.6 to +0.8VDC signal.
Figure 40. Plug-in Module Slot A –
Digital Input A Module
Option C Connections
Option C offers a factory fitted multiple digital input op­tion. The board also accommodates the USB port if that is option is fitted. The USB port does not have connections on the rear terminal, it is accessed via the front panel.
Figure 14. Input 2 - Thermocouple Connections
Special Wiring Considerations for Valve Motor Control
Valve Motor Drive (VMD) controllers require two identi­cal outputs to be assigned to position the valve. One to open and one to close the valve. These outputs can be two single relays, two triacs, two SSR drivers or one dual relay, but it is recommended to use two single re­lays (SPDT change-over contacts), and to interlock the relay wiring as shown. This prevents both motor wind­ings from being driven at the same time, even under fault conditions.
Switching actuators directly connected to the valve motor must only be used up to half of their rated volt­age (see CAUTION below). The internal relay and triac outputs are rated at 240VAC, so the maximum motor voltage when using them in this way is therefore 120V unless interposing relays are used. Interposing relays or other devices used to control the valve must them­selves be rated for twice the motor supply voltage.
17
Page 26
Open Valve
e
“OPEN” RELAY
N/O
C
N/C
“CLOSE” RELAY
2 x 120V = 240V
120V
N/C C N/O
N/C C N/O
120VAC SUPPLY
Winding
Valve Common
Close Valv Winding
Figure 42. Interlocking of Valve Motor Drive Relays
5 Powering Up
Ensure safe wiring practices have been followed. When powering up for the first time, disconnect the output connections. The instrument must be powered from a supply according to the wiring label on the side of the unit. The supply will be either 100 to 240V AC, or 24/48V AC/DC powered. Check carefully the supply voltage and connections before applying power
ELECTRIC SHOCK/FIRE HAZARD. The windings of a valve motor effectively form an autotrans­former. This has a voltage doubling effect when power is applied to either the Open or Close terminal, causing twice the supplied voltage at the other terminal. For this reason, switching devices directly connected to the valve mo­tor must only be used up to half of their rated voltage. The maximum motor voltage when us­ing the internal relays/triacs is therefore 120V unless interposing relays are used. Interpos­ing relays or other devices used to control the valve must themselves be rated for twice the motor supply voltage. Failure to follow these instructions could result in personal injury or equipment damage.
Powering Up Procedure
At power up, a self-test procedure is automatically started, during which a splash screen is displayed and the LED indicators are lit. At the first power up from new, a Setup Wizard runs to assist configuration of ba­sic applications (refer to the Setup Wizard section on page 43). At all other times, the instrument returns to the normal operation mode once the self-test proce­dure is complete.
Front Panel Overview
The illustration below shows an instrument fitted with the optional USB socket located to the right of the four keypad buttons. Clean the front panel by washing with warm soapy water and dry immediately. If the USB op­tion is fitted, close the port cover before cleaning.
Display
The instrument has a 160 x 80 pixel monochrome graphical display with dual color (red/green) backlight. The main display typically shows the process variables, setpoints, power / deviation bar graphs or graphical trends during normal operation. There are recorder and profile status screen. The top line of the display has labels for the 4 LED indicators. If desired, the back­light color can be changed to indicate the presence of an active alarm or latched output. Refer to the Display Configuration section.
Figure 43. A Typical Front Panel
18
Page 27
LED Functions
There are four red LEDs that by default indicate the status of the primary & secondary outputs, automatic tuning and alarm status. The top line of the graphical display has four labels for LED indicators. The function of these LEDs and their display labels can be changed using the PC configuration software. The information in this manual assumes standard functions for these
LEDs.
Button Function
Moves backward to the previous parameter or screen in the current mode. Holding this key down for more than 1 second skips immediately to the previous screen accepting ALL values as shown.
CAUTION: If editing a parameter, ensure that the current (highlighted) parameter val­ue is correct before pressing the key as this action will update the instrument to the value displayed.
In menus and configuration choice screens, this key moves to the next item on the list.
Editable values can be decreased by pressing this key. Holding the key down speeds up the change.
In Trend views this key moves the Cursor Line back through the stored data points
In menus and configuration choice screens, this key moves to the previous item on the list.
Editable values can be increased by pressing this key. Holding the key down speeds up the change.
In Trend views this key moves the Cursor Line forward through the stored data points
Moves forward to the next parameter or screen in the current mode. Holding this key down for more than 1 second skips immediately to the next screen accepting ALL values as shown.
CAUTION: If editing a parameter, ensure that the current (highlighted) parameter val­ue is correct before pressing the key as this action will update the instrument to the value displayed.
Keypad Functions & Navigation
Each instrument has four keypad switches, which are used to navigate through the user menus and adjust the parameter values. In configuration screens, a con­text sensitive scrolling help text is displayed that guides the user about the function of the keys.
Pressing the key while holding down the key causes the instrument to move up one menu level. From Operation Mode and in most menus, this will result in entry to the Main Menu.
From sub-menus, it is necessary to carry out this sequence more than once to reach the main menu.
CAUTION: If editing a parameter, ensure that the current (highlighted) parameter val­ue is correct before pressing the key as this action will update the instrument to the value displayed.
19
Page 28
6 Messages and Error Indicators
Plug-in Module Problems
If an invalid or unknown module is detected in one of the plug-in module slots during the power-up self-test, the message “Fault Found, Press , for details” is shown. This is followed by “Replace faulty module in Module Slot n, Press ,” (where n is the faulty slot location). The Service Contact information is displayed next showing details of who to contact if a fault persists
Replace the module in slot “n”. If this does not solve the problem, return the instrument for investigation.
Do not continue using the product until the the error is resolved.
Sensor Break Detection
Whenever a problem is detected with a process vari­able or auxiliary input connection, the displayed value for that input is replaced with the word “OPEN”; except in Ratio control where an open input 1 or 2 is shown as “x1-Open” or “x2-Open”. See Redundant Input to protect critical processes from sensor faults.
This may be the result of a failed sensor, a broken con­nection or an input circuit fault.
In this condition, the control outputs go to the pre-set power value (see Control Configuration.)
Correct the signal/wiring problem to continue normal operation.
Un-Calibrated Input Detection
The instrument is fully calibrated during manufacture. If a fault occurs and calibration data is lost, the process input displays are replaced with the word “ERROR” and error is shown instead of “Calibrated” for effected inputs in Service & Product Information mode.
In this condition, the control outputs go to the pre-set power value (see Control Configuration).
Perform a full base calibration of the input be­fore continuing normal operation. If the problem persists, return the instrument for servicing.
PV Over-Range or Under-Range Indication
If a measured process input value is more than 5% above than the Scaled Input Upper Limit, its value is replace by the word “HIGH” to indicate that it is out of range.
If a measured process input value is more than 5% below than the Scaled Input Lower Limit, its value is replaced by the word “LOW” to indicate that it is out of range.
Auxiliary Input Over-range or Under-range Indication
If the auxiliary Remote Setpoint input is more than 5% above than the Auxiliary Input Upper Limit, its value is replaced by the word “HIGH” to indicate that it is out of range.
If the auxiliary Remote Setpoint input is more than 5% below than the Auxiliary Input Lower Limit, its value is replace by the word “LOW” to indicate that it is out of range.
Cascade-Open
“Cascade Open” is shown on the main screen if the internal link has be severed between cascaded master and slave control loops. This mode should only be used for diagnostics and slave tuning. Close the cascade for proper operation. Refer to the Cascade Control section for more information.
Profile Not Valid
If the user attempts to run a profile that would take the setpoint beyond the current setpoint limits, the profile will not run and the message “Profile Not Valid” is dis­played at the bottom of the profile status screen.
USB Data Transfer Failure message
If the instrument cannot successfully write to the USB memory stick, the message “Data Transfer Failure” will be displayed. Check that there is adequate disk space on the memory stick, then retry.
If the instrument cannot successfully read data from the USB memory stick, the message “Data Transfer Failure” will also appear. Check that this operation would not cause the maximum number of profiles and/ or segments to be exceeded then retry.
Getting Help
First Level Support
If the errors persist or other problems are encountered, refer your supplier for first level support. This includes help with configuration, tuning, servicing and replace­ment modules.
Second Level Support
If your supplier is unable to assist or cannot be con­tacted, check the Service & Product Information screen on the main menu for details of who to contact.
Third Level Support
If further assistance is required, contact the nearest company from those listed on the back page of this manual.
Servicing
If you need to return your instrument for servicing, contact your supplier or check the Service & Product Information screen on the main menu for instructions for its return.
20
Page 29
7 Application Setup
Before beginning configuration, consider how the con­troller will be used in your application. For instance, how many control loops are needed, is cascade or ratio control required, will the unit control a valve motor, do you need setpoint profiling etc. Consideration should also be given to the output types, alarms and tuning method.
This section is intended to help with this process, guid­ing you through the major configuration settings. Addi­tional information can be found in the relevant sections of this manual, including the glossary, configuration menus, and dedicated sections for major features. These are listed in the table of contents.
Pre-Commissioning Considerations
An easy Setup Wizard is available for basic applica­tions where the most commonly required parameters are present for adjustment in turn. The wizard has a sub-set of the full configuration menu options. For
Loop 1 / Master
Process Type*
(only if 2nd
input fitted)
One Loop*
Input 2 Con­figuration | Input 2 Usage = Not Used
Two Loops*
Input 2 Configu­ration | Input 2 Usage = Stan­dard
+Feedback*
Input 2 Configu­ration | Input 2 Usage = Feed­back
Redundant*
Input 2 Configu­ration | Input 2 Usage = Feed­back
Standard PID Control Select = Control Standard
Valve Motor Drive Control Select = VMD (TPSC) Control
Standard PID Control Select = Control Standard
Valve Motor Drive Control Select = VMD (TPSC) Control
Valve Motor Drive Control Select = VMD (TPSC) Control
Standard PID Control Select = Control Standard
Valve Motor Drive Control Select = VMD (TPSC) Control
Control Configuration: Control Select
Control
Configuration:
Control Type
Primary Only Control Type = Single
Primary/Secondary Control Type = Dual
Primary Only Control Type = Single
Primary/Secondary Control Type = Dual
Primary Only Control Type = Single
Primary / Secondary Control Type = Dual
more complex applications where the wizard is not sufficient, consideration must be given to the following fundamental questions:
If fitted, how will the 2nd input be used?
• One loop only (if the 2nd input not fitted or not used in this application)
• Two independent control loops
• Valve feedback for loop 1
• A “redundant” backup for the 1st input
• Cascaded with the first control loop
• A reference input for ratio control
How will the instrument physically control the process?
• Primary only or primary & secondary control out­puts
• Direct valve motor drive outputs
The table below shows the main input and control con­figuration settings for these application types (see con­figuration menus).
Loop 2 / Slave
Control Configuration: Control Select
Standard PID Control Select = Control Standard
Valve Motor Drive Control Select = VMD (TPSC) Control
Primary Only Control Type = Single
Primary / Secondary Control Type = Dual
Control
Configuration:
Control Type
21
Page 30
Loop 1 / Master
Loop 2 / Slave
Process Type*
(only if 2nd
input fitted)
Cascade*
Input 2 Configu­ration | Input 2 Usage
= Standard
AND
Loop 1 / Master Configuration | Control Mode = Cascade
Ratio*
Input 2 Configu­ration | Input 2 Usage
= Standard
AND
Loop 1 / Master Configuration | Control Mode = Ratio
Control Configuration: Control Select
Standard PID Control Select = Control Standard
Valve Motor Drive Control Select = VMD (TPSC) Control
Control
Configuration:
Control Type
Control Configuration: Control Select
Standard PID Control Select = Control Standard
Valve Motor Drive Control Select = VMD (TPSC) Control
Control
Configuration:
Control Type
Primary Only Control Type = Single
Primary / Secondary Control Type = Dual
Which outputs will be used for control, and are alarms or event outputs needed?
• Output configuration
• Alarms & Profile Events
What are the sources for the setpoints?
• Local setpoint(s) only, or a remote setpoint input
• Profile Control
Is Input re-configuration required?
• Analogue input calibration & scaling
• Digital input functions
Which other features are to be used?
• Data Recorder.
• Serial Communications.
• USB Interface.
Once you have an understanding of your application and how the controller will be used, continue on to the configuration and use section below.
CAUTION: Configuration & commissioning must be completed before proceeding to Operation Mode. It is the responsibility of the installing engineer to ensure that the configuration is safe.
22
Page 31
8 Operation and Configuration Menus
This section contains information on all of the control­ler’s modes and the configuration menus.
Operation Mode
This is the mode used during normal operation of the instrument. It can be accessed from the Main Menu, and is the usual mode entered at power-up. The avail­able displays are dependent upon the features/options fitted and the way in which it has been configured.
The Base screen is the usual screen displayed during operation. It provides “at a glance” information about the process. The Profile Status screen shows similar information when using profiles.
Subsequent screens allow the display and selection/ adjustment* of the setpoints. From display configura­tion, a selection of other parameter screens can be made available for operator selection/adjustment*. These include: profile control; cascade open/close; auto/manual control; setpoint ramp rate; setpoint source; control enable; clear latched outputs; data re­cording & status trend views. Optional operator mode screens are marked in the screen lists. Some screens will persist until the user navigates away, others will ‘time-out’ back to the base screen.
* If required, all Operation Mode parameters can be made read only. Otherwise parameters such as set­points can be adjusted within their configured limits.
Set all Configuration parameters as required before starting normal operations. It is the re­sponsibility of the installing engineer to ensure that the configuration is safe for the intended application.
Navigating and Adjusting Values in Opera­tor Mode
Press to move forward or to move backwards through the available screens.
When a displayed value can be adjusted, use to change its value.
The next/previous screen follows the last parameter. If
no further changes are needed, hold down for >1sec to skip straight to the next/previous screen accepting ALL values shown.
In Trend Views, pressing or moves the cursor line back and forward through the last 240 data points.
or
or
ELECTRIC SHOCK/FIRE HAZARD. DURING NORMAL USE, THE USER MUST NOT REMOVE THE CONTROLLER FROM ITS HOUSING OR HAVE UNRESTRICTED ACCESS TO THE REAR TERMINALS, AS THIS WOULD PROVIDE PO­TENTIAL CONTACT WITH HAZARDOUS LIVE PARTS. FAILURE TO FOLLOW THESE INSTRUC­TIONS COULD RESULT IN PERSONAL INJURY OR DEATH AND/OR EQUIPMENT / PROPERTY DAMAGE.
23
Page 32
OPERATION MODE SCREEN SEQUENCE
(scaled ±5% of input span)
±100% primary & secondary)
* = in loop 1 & 2 screen area
Master
All possible screens are listed below. The sequence shown depends on the configuration and status. E.g. set­tings for “Loop 2” only apply if 2nd input is fitted and configured for 2-loop control. *Some screens are only shown if set to do so in Display Configuration.
After 2 minutes without key activity, the most screens revert to the Base Operating Screen. Screens marked do not revert automatically. They remain displayed until the user navigates away.
Calibration Check Due Warning
If a Calibration Reminder is set and the due date has passed this will be shown at every power up, and repeated once per day. Press to acknowledge and continue using the instrument temporarily without recalibration.
Change the due date or disable the reminder to cancel the warning. This feature is only possible if the recorder is fitted. It is enabled in Input Configuration
Single Control Loop: Normal Operation
LED Indicators
LED Function Labels
Process Variable Value
Effective Actual Setpoint
Value
Engineering Units
Control Deviation Graph
Two Control Loops: Normal Operation
Power Graph (0-100% primary,
LED Indicators
LED Function Labels
Process Variable* & Actual
Setpoint Values*
Indicators for Alarm and Remote Setpoint active*
Loop Description*
Control Deviation 5% of span) & Power Graphs* Engineering Units*
2-LOOP OPERATION
Default LED indicator functions are PRI, SEC, TUNE & ALARM - the functions and their labels can be altered only with the PC configuration software. In valve motor drive mode, the power bar-graph is replaced by valve Open / Stop / Close unless the 2nd input is used for position feedback, where it shows 0 to 100% valve position. In manual mode the effective setpoint is replaced by the %Manual Power and the label “MAN”. In manual mode with valve motor drive the setpoint is replaced by valve Open / Stop / Close. If control is disabled the effective setpoint value is replaced by “OFF”.
Cascade Control: Normal Operation
LED Indicators
LED Function Labels
Master Process Value
Cascade Status
Setpoint (Slave SP if
Slave Process Value
Cascade Open)
Control Deviation (±5% of span) & Power Graphs
24
Page 33
OPERATION MODE SCREEN SEQUENCE
Ratio
RATIO CONTROL
Progres
d
1-LOOP PROFILE STATUS
Default LED indicator functions are PRI, SEC, TUNE & ALARM - the functions and their labels can be altered only with the PC configuration software. Cascade Status shows “Cascade” when cascade is operating normally and “Cascade Open” when the master / slave link has been disconnected. Master & Slave Process Values. In valve motor drive mode, the power bar-graph is replaced by valve Open / Stop / Close. In manual mode the slave setpoint is replaced by the %Manual Power and the label “MAN”. In manual mode with valve motor drive the slave setpoint is replaced by valve Open / Stop / Close. If control is disabled the effective master setpoint value is replaced by “OFF”.
Radio Control: Normal Operation
LED Indicators
LED Function Labels
Relative Process Value
& Setpoint Labels
Relative Setpoint
Control Deviation (±5% of span) & Power Graphs
Default LED indicator functions are PRI, SEC, TUNE & ALARM - the functions and their labels can be altered only with the PC configuration software. In manual mode the ratio setpoint value is replaced by the %Manual Power and the label “MAN”. If control is disabled the effective setpoint value is replaced by “OFF”.
Operator Profile Control
Allows the operator to control the defined profiles. If a profile is running, the choices are: Do Nothing; Abort Profile (end immediately); Jump to Next Segment; Hold Profile or Release Hold. If no profile is running, the choices are: Do Nothing; Run Profile; End Profile Control (returns to standard control­ler operation) or Select Profile. *only shown if set to do so in Display Configuration.
Single Control Loop: Profiler Status
LED Indicators
LED Function Labels
Process Value & Setpoint
Engineering Units
Profile Name & Progress
Segment No, Type &
s(or Delayed Start
Time)
Default LED indicator functions are as shown in the initial base screen. In manual mode the effective setpoint is replaced by the %Manual Power and the label “MAN”. In manual mode with valve motor drive the setpoint is replaced by valve Open / Stop / Close. If control is disabled the effective setpoint value is replaced by “OFF”.
Note: If power is lost when a profile is running and recovery is set to continue, the bar-graph re-starts from the beginning but the overall time remains correct.
25
Profile Status Indicator:
Run,
Held,
Stoppe
Page 34
OPERATION MODE SCREEN SEQUENCE
* = in loop
Two Control Loops: Profiler Status
LED Indicators
LED Function Labels Engineering Units*
Profile Status Indicators*:
Run, Held,
Stopped
Process Variable Values & Setpoints*
Loop Descriptions*
Profile Name & Progress
1 & 2 screen area
Default LED indicator functions are as shown in the initial base screen. In manual mode the effective setpoints are replaced by the %Manual Power and the label “MAN”. In manual mode with valve motor drive the setpoints are replaced by valve Open / Stop / Close.
Note: If power is lost when a profile is running and recovery is set to continue, the bar-graph re-starts from the beginning but the overall time remains correct.
Event Status
Cascade Mode
Auto/Manual Control Se­lection – Loop 1 (or Cas­cade Slave)
Setpoint Value Display & Adjustment – Loop 1
Lists all configured profile events with their current status (Active or Inactive) – Shown only when the instrument is in profiler mode.
Allows the user to open the cascade, breaking the master-slave link for commis­sioning & tuning.
CAUTION: Return to Cascade-CLOSE when finished!
*only shown if set to do so in Display Configuration.
Switches loop 1 (or the cascade slave loop) between automatic and manual control modes. Switching between these modes uses “Bumpless Transfer”. *only shown if set to do so in Display Configuration.
When using standard PID control, Manual mode replaces the Setpoint display with a -100 to 100% power output level value, labelled “Man”. The
used to adjust the manual power value.
When using VMD control, Manual mode replaces the Setpoint display with the valve movement status (Opening, Closing or Stopped), labelled “Man”. The key opens the valve and the key closes the valve.
If Manual control is selected when in Cascade mode, the slave loops % power value shown. This is the power output fed directly to the control actuator (e.g. power to the heater elements).
CAUTION: Manual mode overrides the automatic control loop. It also
ignores any output power limits, valve open/close limits and the con­trol enable/disable setting. The operator is responsible for maintain­ing the process within safe limits.
Note: If power is lost when a profile is running and recovery is set to continue, the bar-graph re-starts from the beginning but the overall time remains correct.
View and adjust the main and alternate setpoints for loop 1 (or the master loop in cascade mode). The setpoints can be set to any value within the setpoint limits set in Control Configuration. View and adjust local (internal) setpoints for the loop. The currently selected setpoint is marked as “active”. If the alternate setpoint is remote it cannot be adjusted from the keypad.
2-LOOP PROFILE STATUS
Segment No. Type & Progress (or Delayed Start Time)
or keys are
26
Page 35
OPERATION MODE SCREEN SEQUENCE
Setpoint Ramp Rate – Loop 1
Select Active Setpoint – Loop 1
Control Enable – Loop 1
Auto/Manual Control Selection – Loop 2
The setpoint ramp rate adjustment for loop 1. Adjustable between 0.1 and 9999.0 display units per hour. When set to “OFF”, setpoint changes will step immediately to the new value - *only shown if set to do so in Display.
Note: If power is lost when a profile is running and recovery is set to continue, the bar-graph re-starts from the beginning but the overall time remains correct.
Select if the main or alternate setpoint is to be the “active” setpoint for loop 1 (or the master loop in cascade mode). *only shown if set to do so in Display.
Enables or disables loop 1 control outputs. When disabled, the primary and sec­ondary control outputs of loop 1 are set to zero 0% (unless manual mode has been selected) and the setpoint value is replaced by “OFF”. *only shown if set to do so in Display.
CAUTION: The instrument cannot control the process when disabled.
Switches loop 2 between automatic and manual control modes. Switching between these modes uses “Bumpless Transfer”. *only shown if set to do so in Display Con­figuration. When using standard PID control, Manual mode replaces the Setpoint
display with a -100 to 100% power output level value, labelled “Man”. The
keys are used to adjust the manual power value.
When using VMD control, Manual mode replaces the Setpoint display with the valve movement status (Opening, Closing or Stopped), labelled “Man”. The the valve and the key closes the valve.
CAUTION: Manual mode overrides the automatic control loop. It also
ignores any output power limits, valve open/close limits and the control enable/disable setting. The operator is responsible for maintaining the process within safe limits.
key opens
or
Setpoint Value Display & Adjustment – Loop 2
Setpoint Ramp Rate – Loop 2
Select Active Setpoint – Loop 2
Control Enable – Loop 2
Alarm Status
In manual mode a running profile will hold if it is controlling the setpoint of loop 2, until automatic control is reselected.
View and adjust the main and alternate setpoints for loop 2. The setpoints can be set to any value within the setpoint limits set in Control Configuration. View and ad­just local (internal) setpoints for the loop. The currently selected setpoint is marked as “active”. If the alternate setpoint is remote it cannot be adjusted from the keypad.
The setpoint ramp rate adjustment for loop 2. Adjustable between 0.1 and 9999.0 display units per hour. When set to “OFF”, setpoint changes will step immediately to the new value - *only shown if set to do so in Display.
If the setpoint ramp feature is used, it disables pre-tune completely, and if self­tune is used, it will only calculate new terms after the ramp has completed and the setpoint is constant.
Select if the main or alternate setpoint is to be the “active” setpoint for loop 2 (or the master loop in cascade mode). *only shown if set to do so in Display
Enables or disables loop 2 control outputs. When disabled, the primary and sec­ondary control outputs of loop 2 are set to zero 0% (unless manual mode has been selected) and the setpoint value is replaced by “OFF”.
*only shown if set to do so in Display Configuration.
CAUTION: The instrument cannot control the process when disabled.
Lists the status of the alarms. Shown if any of the 7 alarms is active. The titles
“Alarm n” can be replaced with the PC configuration software to a user defined 8 character name for each alarm.
27
Page 36
OPERATION MODE SCREEN SEQUENCE
Manual Record Digital Input Profile Record Alarm Record
Active Alarm(s)
Trend Upper Scale Value
Loop No,
TREND VIEW
Clear Latched Outputs
Recorder Memory Full Warning
Manual Recording Trigger
Recorder Status Information
Hold down or for 3 seconds to clear the selected latched output – An output will only reset if the condition that caused it to latch on is no-longer present. *only shown if set to do so in Display Configuration.
Indicates that the Data Recorder memory is full and that recording has either stopped or is overwriting older data if in FIFO recording mode.
Set the manual recording trigger on or off. *only shown if set to do so in Display Configuration.
Note: Setting the manual trigger to off may not stop the recording. Data record­ing will still take place if another recording trigger is active.
Shows the recording status (“Stopped” or “Recording”); icons for any active re­cording triggers; the recording mode (FIFO or Record Until Memory Is Used); the approximate recording time remaining* and a memory usage bar-graph. In FIFO mode, the time remaining is replaced with “FIFO” when full. *If the status of alarms is
recorded, extra samples are taken when the alarms change state reducing the avail­able recording time. Take this into account when determining if there is sufficient memory available.
Icons for Active Recored Triggers
Trend Views: One per COntrol Loop
Process Variable Trend
Setpoint Trend (dotted) Trend Lower Scale Value
& Time Markers
(10 samples per marker)
Cursor Line
PV Value At Cursor Line
Sample Interval (or time at cursor line)
Trend views can be shown of each loop. They are auto-scaling graphs with alarm indication and other process information. The trend can be set to show the process variable only; the process variable & setpoint (dotted line), or the minimum and maximum value of the process variable measured since the last sample. Any active alarm(s) are indicated above the graph. Graph types and data sample intervals 1 sec to 30 mins) are set in Display Configuration. Trend scale values adjust automatically to visible data (between 2 to 100% of the input span).
120 data points are visible. Pressing or moves the cursor line back through the graph to examine up to 240 data points. The process variable value of that data point is shown to the right of the cursor line and the sample rate value is replaced by the time represented by the cursor position.
*only shown if set to do so in Display Configuration.
Note: Trend data is not retained at power down or if the sample interval is changed.
28
Page 37
OPERATION MODE SCREEN SEQUENCE
Custom Display Screens
You can copy up to 50 configuration menu parameters into normal operation mode using the PC software. These extended operator mode screens appear at the end of the normal sequence. If the parameter is normally displayed on screen with another parameter, both parameters will appear.
Note: In this mode screens are not pass-code protected, they can be freely adjust. It is possible to make operation mode “read only”, including any custom screens from Display Configuration.
Main Menu
This menu is used to access the various features and configuration settings. The available menus are depen­dent upon the features and options fitted and how it has been configured.
Entry into the Main Menu
Holding down and pressing from Operation Mode and most other screens will cause the unit to enter the Main Menu. Each time this key press sequence is made, the instrument moves to the next menu level above. Sub-menu levels will require this sequence to be pressed more than once in order to reach the Main Menu.
Navigating the Main Menu
Once in the Main Menu, press or to select the required option
Press Scrolling “Help Text” is shown at the bottom of the
screens to aid navigation.
to enter the chosen menu.
Unlock Codes
To prevent unauthorized entry, most menus require a pass-code (1 to 9999) to gain entry. These menus are indicated by the symbol and changed from the Lock Code Configuration sub­menu of Configuration Mode. The factory default un­lock code is 10 for all modes but for security, these should be changed to new values. If the Configuration Mode lock code is lost, refer to Lost Lock Codes.
. The codes can be viewed
Operation Mode
Setup Wizard
Supervisor Mode
Configuration Menu
Automatic Tuning
USB Menu
Recorder Control
Profile Setup
Profile Control
Service & Product Information
OPERATION MODE SCREEN SEQUENCE
The normal operation screens, displaying the process and setpoint values; se­lection/adjustment of the setpoints; auto/manual control; alarm/event status; trend views; data recorder and profile information.
An easy, step-by-step parameter setup for simple applications.
If configured from the PC software, a sub-set of up to 50 Configuration screens can be accessed.
Accesses the sub-menus for Inputs; Control Loops; Outputs; Alarms; Com­munications; Recorder; Clock; Display and Lock Codes. There is an option to Reset to Defaults wiping all user settings from the instrument.
Selection of Pre-tune, Self-tune and Auto Pre-tune for the control loops.
Uploading/downloading instrument configuration, profile information and data recordings.
Manually starting, stopping and deleting recordings
Selection of profiles. Running, holding or aborting the selected profile
Selection of profiles. Running, holding or aborting the selected profile
Contact information for service/support, followed by instrument information, including features and plug-in modules installed, serial number, firmware ver­sion etc.
29
Page 38
Setup Wizard
An easy Setup Wizard runs automatically at first ever power-up. Follow the Wizard to setup parameters re­quired for basic applications. The parameters covered by the Setup Wizard are marked with a w in the fol­lowing sections covering the configuration mode sub­menus. Once completed, the Setup Wizard exits to Operation Mode.
The Wizard can be run again at any time from the Main Menu. An option to reset all parameters to default (rec­ommended) is offered when manually running the wiz­ard.
Resetting defaults all parameters, not just those covered by the quick setup wizard. For more complex applications the user may have to reconfigure other Configuration Menu set­tings before using the instrument.
Experts or users with more complex applications can select the parameters they wish to setup directly from the Configuration Menus bypassing the Wizard.
Manual entry to the Setup Wizard
To select the Setup Wizard from the Main Menu.
Hold down
Press or to select Setup Wizard.
Note: With the exception of the first ever power-up, entry into this mode is security-protected by the Setup Wizard Lock Code. Refer to the Lock Code Configuration sub-menu.
Press to enter the Setup Wizard.
and press to enter the Main Menu.
Navigating in the Setup Wizard
Press to move forward, or to move backwards through the screens.
Press or to change the value as required.
Holding down immediately to the next/previous screen accepting ALL values as shown.
Hold down and press to return to the Main Menu
Scrolling “Help Text” is shown at the bottom of the screens to aid navigation.
or for more than 1 second skips
SETUP WIZARD SCREENS
Setup Wizard Unlocking
Key Screens from Configuration Menu (those marked w)
Setup Wizard Completed
Enter correct code number to access Setup Wizard.
w
Factory Default value is 10.
Press
w
screen prompts to alter the values.
w
Confirms completion of the Setup Wizard. Exits to Operation Mode.
to select each major configuration parameter in turn. Follow on-
Supervisor Mode
This mode is only available if it has been configured from the PC software. Its purpose is to allow selected operators access to a lock-code protected sub-set of the configuration parameters, without providing them with the higher level configuration menu unlock code.
The PC software can copy up to 50 parameters from configuration menus for inclusion in the supervisor mode screen sequence. If the parameter is normally displayed on screen with another parameter, both pa­rameters will appear. It is not possible to configure su­pervisor mode screens without using the software.
Entry into Supervisor Mode
Adjustments to these parameters should only be performed by personnel competent and au­thorized to do so.
Supervisor Mode is entered from the Main Menu
Hold down
Press or to select Supervisor Mode
and press to enter the Main Menu.
Note: Entry into this mode is security-protected by the Supervisor Mode Lock Code. Refer to the Lock Code Configuration sub-menu.
30
Page 39
Press to enter the Supervisor Mode.
Navigating in the Supervisor Mode
Press to move forward, or to move backwards through the screens.
Press or to change the value as required.
SUPERVISOR MODE SCREENS
Supervisor Mode Unlocking
Supervisor Mode Screens
If Supervisor Mode is configured, enter correct code number to continue. Factory Default value is 10.
Press to alter the values.
to select each selected parameter in turn. Follow on-screen prompts
The next/previous screen follows the last parameter. If
no further changes are required, hold down or >1sec to skip straight to next/previous screen accept­ing ALL values shown..
Hold down and press to return to the Main Menu
Scrolling “Help Text” is shown at the bottom of the screens to aid navigation.
Configuration Menu
This menu can be used as an alternative to the more limited Setup Wizard when the instrument is config­ured for the first time in more complex applications, or when further changes are required to the instruments settings. The configuration menu contains a number of sub-menus that allow access to all of the available parameters. The correct settings must be made be­fore attempting to use the instrument in an application. Screens marked w are also shown in the Setup Wizard.
Entry into the Configuration Menu
Adjustments to these parameters should only be performed by personnel competent and au­thorized to do so.
Configuration is entered from the Main Menu
Hold down and press to enter the Main Menu.
Press or to select Configuration Menu
Note: Entry into this mode is security-protected by the Configuration Menu Lock Code. Refer to the Unlock Code section for more details.
Configuration contains sub-menus to set-up the In­puts; Control; Outputs; Alarms; Communications; Re­corder; Clock; Display and Lock Codes.
There is also an option to reset the instrument to its factory default settings.
The Input and Control sub-menus contain further sub­menus with configuration and
calibration settings for each process input; control loops 1 & 2 and the digital inputs. Only parameters that are applicable to the hardware and options fitted will be displayed.
From the Configuration Menu, press or to se­lect the required sub-menu.
Press to enter the sub-menu.
If required, press or to select the next level sub-
menu, then press to enter.
Hold down menu level.
Scrolling “Help Text” is shown at the bottom of the screens to aid navigation.
and press to return to next higher
Press to enter the Configuration Menu.
Navigating the Configuration Menu
CONFIGURATION MENU SCREENS
Configuration Mode Unlocking
Configuration Options
Enter correct code number to access Configuration Mode. Factory Default value is 10.
Select the required Configuration Sub-Menu Option from: Inputs; Control; Outputs; Alarm; Communications; Recorder; Clock; Display; Lock Code or Reset To Defaults.
31
Page 40
CONFIGURATION MENU SCREENS
Input 1 Setup - Sub-menu to setup Input 1. Press + to return to Input Menu
Input Type
Engineering Units
Decimal Point Position
Scaled Input Lower Limit
Scaled Input Upper Limit
Multi-Point Scaling Enable
Scaling Point n
Display Value n
CJC Enable/Disable
Input Filter Time
Select from various Thermocouple, RTD and Linear mA, mV or VDC inputs. -
w
see specifications section for available input types.
Note: Recheck the units and decimal point settings if you change the input type.
Select display units from: °C; °F; °K; bar; %; %RH; pH; psi or none. Tempera-
w
ture sensor inputs are limited to °C; °F
Sets the maximum display resolution to 0; 1; 2 or 3 decimal places. Numbers >99.999 never display more than 2 dec places, >999.99 never display more
w
than 1 dec place and >99999 always display without a decimal place. Tem­perature inputs are limited to 0 or 1 decimal place.
For temperature inputs, upper & lower limits set the usable span. The minimum span = 100 units, maximum span = range limits for the sensor type selected.
For DC linear inputs, the limits define the values shown (-9999 to 9999.9) when input is at minimum and maximum values. Min span = 100 units.
Enables or disables multi-point scaling. This allows up to 15 point input linear­ization for DC signals - not possible with temperature sensor inputs
If multi-point scaling is enabled, up to 15 breakpoints* can scale input vs. dis­played values between the scaled input limits. Each breakpoint has a % value for the input signal, and the value to display when the input is at that value. *A Scaling Point set to 100% input ends the scaling sequence.
Enables/disables internal thermocouple Cold Junction Compensation. If dis­abled, external compensation will be required for thermocouples. The default value is Enabled.
Removes unwanted signal noise. Adjustable from 0.1 to 100.0 seconds or OFF (default = 2s). Use the smallest value that gives acceptable results.
Caution: Large values slow the response to changes in the process.
Input 1 Calibration - Sub-menu to calibrate Input 1. Press
Calibration Type
Calibration Offset
Calibration Low Value
Calibration Low Offset
Calibration High Value
Calibration High Offset
Input 2 Setup - Sub-menu to calibrate Input 2. Press
Select the calibration type from base; single or 2-point calibration. Select sin­gle to apply a calibration offset across the entire measured range. Use 2-point to enter calibration offsets at both low and high points of the usable range – refer to User Calibration details.
Caution: The default is Base Calibration. For single or 2-point cali-
bration, the user must enter values to adjust the displayed value to match a known standard or accurate external reading.
The single point calibration offset. Limited by the input span, +Ve values add to, –Ve values subtract from, the measured input across entire range.
The displayed value for the 1st (low) adjustment of 2-point calibration. Choose a value close to the lowest level used in the application.
The adjustment value for the 1st (low) point when using 2-point calibration. +Ve values add to, –Ve values subtract from measured input at this point.
The displayed value for the 2nd (high) adjustment of 2 point calibration. Choose a value close to the highest level used in the application.
The adjustment value for the 2nd (high) point when using 2-point calibration. +Ve values add to, –Ve values subtract from measured input at this point.
+
+
to return to Input Menu
to return to Input Menu
32
Page 41
Input 2 Usage
Input Type
Engineering Units
Decimal Point Position
Scaled Input Lower Limit
Scaled Input Upper Limit
Multi-Point Scaling Enable
Scaling Point n
Display Value n
CJC Enable/Disable
Input Filter Time
Set Valve Lower Position
Set Valve Upper Position
CONFIGURATION MENU SCREENS
Input 2 can be used as a standard process input for a second control loop (including its use as part of a cascade), a redundant input or a feedback signal
w
input from a valve or flow meter. Redundant or Feedback disables the input as an independent control loop.
w
If input 2 is selected as a standard process input, select from various Thermo­couple, RTD and Linear mA, mV or VDC inputs. - see specifications section on page 245, for available input types. If input 2 is selected as feedback possible types are limited to Linear mA, mV, VDC or Potentiometer. Redundant inputs automatically assume the same input type as input 1.
Note: Recheck the units and decimal point settings if you change the input type.
Select display units from: °C; °F; °K; bar; %; %RH; pH; psi or none. Tempera-
w
ture sensor inputs are limited to °C; °F
Sets the maximum display resolution to 0; 1; 2 or 3 decimal places. Numbers >99.999 never display more than 2 dec places, >999.99 never display more
w
than 1 dec place and >99999 always display without a decimal place. Tem­perature inputs are limited to 0 or 1 decimal place.
For temperature inputs, upper & lower limits set the usable span. The mini­mum span = 100 units, maximum span = range limits for the sensor type selected - see specs on page 245. For DC linear inputs, the limits define the values shown (-9999 to 9999.9) when input is at minimum and maximum val­ues. Min span = 100 units.
Enables or disables multi-point scaling. This allows up to 15 point input linear­ization for DC signals - not possible with temperature sensor inputs
If multi-point scaling is enabled, up to 15 breakpoints* can scale input vs. dis­played values between the scaled input limits. Each breakpoint has a % value for the input signal, and the value to display when the input is at that value. *A Scaling Point set to 100% input ends the scaling sequence.
Enables/disables internal thermocouple Cold Junction Compensation. If dis­abled, external compensation will be required for thermocouples. The default value is Enabled.
Removes unwanted signal noise. Adjustable from 0.1 to 100.0 seconds or OFF (default = 2s). Use the smallest value that gives acceptable results.
Caution: Large values slow the response to changes in the process.
If input 2 is selected as feedback indication, this stores the feedback value equal to the minimum valve travel. The procedure below moves the valve to the fully closed position to find the feedback value:
Press
Press until the valve is closed to its limit of its travel.
Press and simultaneously to store the feedback level.
If input 2 is selected as feedback indication, this stores the feedback value equal to the maximum valve travel. The procedure below moves the valve to the fully open position to find the feedback value:
Press
Press U until the valve is opened to its limit of its travel.
Press and simultaneously to store the feedback level.
and simultaneously to begin feedback limit adjustment.
and simultaneously to begin feedback limit adjustment.
Input 2 Calibration - Sub-menu to calibrate Input 2. Press
33
+
to return to Input Menu
Page 42
Calibration Type
Calibration Offset
Calibration Low Value
Calibration Low Offset
Calibration High Value
Calibration High Offset
CONFIGURATION MENU SCREENS
If input 2 is selected as a standard process input, the user can select the cali­bration type from base; single or 2-point calibration. Select single to apply a calibration offset across the entire measured range. Use 2-point to enter cali­bration offsets at both low and high points of the usable range – refer to the User Calibration details.
Caution: The default is Base Calibration. For single or 2-point cali-
bration, the user must enter values to adjust the displayed value to match a known standard or accurate external reading.
The single point calibration offset. Limited by the input span, +Ve values add to, –Ve values subtract from measured input across the range.
The displayed value for the 1st (low) adjustment of 2-point calibration. Choose a value close to the lowest level used in the application.
The adjustment value for the 1st (low) point when using 2-point calibration. +Ve values add to, –Ve values subtract from measured input at this point.
The displayed value for the 2nd (high) adjustment of 2 point calibration. Choose a value close to the highest level used in the application.
The adjustment value for the 2nd (high) point when using 2-point calibration. +Ve values add to, –Ve values subtract from measured input at this point.
Calibration Reminder - Calibration reminder Sub-menu. Press
Calibration Reminder Enable/Disable
Calibration Reminder Date
Auxiliary Input A Setup - Sub-menu to setup auxiliary A input. Press
Auxiliary Input A Type
Aux A Input Lower Limit
Aux A Input Upper Limit
Auxiliary Input A Offset
Enables/disables the Calibration Reminder shown at start-up (and daily there­after), if the due date has passed - Recorder version only
Sets the due date for Calibration Reminder - Recorder version only.
Enables/disables the Calibration Reminder shown at start-up (and daily there­after), if the due date has passed - Recorder version only
These scale values relate to when auxiliary input A is at the range minimum & maximum values. They are adjustable between ±0.001 & ±10000. When auxiliary input A provides a remote setpoint, the scaled input becomes the ef­fective setpoint (although always constrained within setpoint limits).
Caution: Take care to scale correctly especially if being used as
the remote setpoint source for both loops.
An offset applied to the scaled auxiliary input A value. Adjustable, from +/-
0.001 to 20000 units or OFF, with. +Ve values add, –Ve values subtracted. Useful in multi-zone setpoint slave applications. Default = OFF.
+
to return to Input Menu
to return to Input Menu
+
34
Page 43
CONFIGURATION MENU SCREENS
Digital Input Setup - Sub-menu to setup the Digital Inputs. Press + to return to Input Menu
Digital Input Status
Tick Digital Inputs To Invert
Profile Selection Type
Choose Profile Selection
Configure Digital Inputs
Soft Digital Input n Digital Input Logic
Soft Digital Input n Alarm-Event
Digital Input n Function
A diagnostic status (
c = OFF, R = ON, Ø = not available) for digital inputs A;
C1 to C8 and “Soft “digital inputs S1 to S4. If used for profile selection, it also shows bit pattern type (binary or BCD) and selected profile number
Select digitals input with R to invert their operation (making them appear OFF when their actual state is ON). Inputs shown as Ø are not available.
Select the bit pattern to be used for profile selection. Binary or BCD (Binary Coded Decimal). Select None if profile selection not is required.
For profiler versions, the Multi-Digital Input option can be used to select the profile to run with a standard binary bit pattern or binary coded decimal from BCD switches. C1 is the least significant bit (LSB) of the bit pattern. Profiles are numbered from 0 to 63. Use the table to choose inputs C1 to Cn for the number of profiles to select:
C1 C1 to C2 C1 to C3 C1 to C4 C1 to C5 C1 to C6 C1 to C7
Binary 0 to 1 0 to 3 0 to 7 0 to 15 0 to 31 0 to 63
BCD 0 to 1 0 to 3 0 to 7 0 to 9 0 to 19 0 to 39 0 to 63
Any inputs chosen for profile selection are not available for other uses.
– refer to Digital Inputs
Select any available digital input or soft digital input to be configured for use. The current status of each is shown as Assigned or Unused.
Set up a “Soft” digital input n that is the result of the Boolean AND selections of physical inputs, globally OR’d with the OR selections.
Press
or to select R / deselect c the options. Inputs shown as Ø are
not available – refer to Digital Inputs
Further set up of “Soft” digital input n that adds the Boolean OR of Alarms & Events to the physical digital inputs already selected.
Press
or to select R / deselect c the options. Inputs shown as Ø are
not available – refer to Digital Inputs
Select the function to be operated from digital input n. – The possible func­tions are:
Loop 1 or 2 Setpoint Select; Loop 1 or 2 Auto/Manual Select; Loop 1 or 2 Con­trol Select; Loop 1 or 2 Pre-Tune Select; Loop 1 or 2 Self-Tune Select
Clear All Latched Outputs; Output n Clear Latch; Output n Forcing On or Off; Profile Run/Hold; Profile Hold Segment Release; Profile Abort; Data Recorder Trigger or Key n Mimic (replicating pressing
or ).
35
Page 44
CONTROL CONFIGURATION SUB-MENU SCREENS
Control Loop 1 - Sub-menu to setup Control Loop 1. Press + to return to Input Menu These settings apply to the master loop if the controller has been setup for cascade control.
Control Mode
Cascade Mode
Profile Selection Type
Control Select
Control Enable/Disable
Auto/Manual Control Selection
Control Type
Primary Control Action
Control Status
Power Output Levels
Gain Schedule PID Set in Use
Select the fundamental application type, from: Standard; Cascade or Ratio. Refer to the Application Setup section.
Note: Choosing Cascade or Ratio disables the use of the 2nd input as a fully independent control loop.
Opens or closes the cascade link. Cascade-Open breaks the master-slave connection. This allows slave loop to be tuned & adjusted independently.
Caution: Return to Cascade when finished!
Select the bit pattern to be used for profile selection. Binary or BCD (Binary Coded Decimal). Select None if profile selection not is required.
Select from Control Standard or Control VMD (TPSC).
Use Control VMD to directly drive the windings of a motorized valve. This uses a 3-point stepping algorithm giving “open” and “close” outputs.
Use Standard for all other applications (including solenoid valves or modulat­ing valves with positioning circuitry requiring mA or VDC signals).
Used to temporarily disable the control outputs. Select control Enabled (nor­mal) or Disabled – when disabled, control output(s) for this loop are turned off (unless manual mode has been selected), and the setpoint value is replaced by “OFF”.
Caution: The instrument is not able to control the process when
control is disabled and the Output Power Limits are ignored.
Switches the control loop between Automatic and Manual Control. The opera­tor monitors and alters power to correctly control the process (0 to 100% or
-100 to +100% for dual control).
Caution: Manual mode overrides the automatic control loop. It
also ignores any output power limits, valve open/close limits and the control enable/disable setting. The operator is responsible for maintaining the process within safe limits.
Select Single Control for primary control only (e.g. heating only or cooling only) or Dual for primary and secondary control outputs (e.g. heating and cooling) ­Dual is not possible with Ratio or VMD Control.
Set the primary control output for Reverse or Direct Action. Reverse action ap­plies additional primary power as the process falls further below setpoint (e.g. heating applications).
Direct action applies additional primary power as the process rises higher above setpoint (e.g. cooling applications).
In dual control, secondary output action is opposite to primary action.
A “read-only” diagnostic status display of the current loop 1 process variable and effective setpoint values to assist with manual tuning.
A “read-only” diagnostic status display of the current loop 1 primary and sec­ondary % output power levels to assist with manual tuning – Not shown with
VMD Control. Does not apply if control is disabled or in manual mode.
A “read-only” diagnostic status display showing the PID set in use. The set used may vary based on the current setpoint or process variable value. – Only
shown if Gain Scheduling is in use.
36
Page 45
PID Set Selection
Set n – Primary Pb
Set n – Secondary Pb
Set n – Integral
Set n – Derivative
Set n – Overlap
Set n – On/Off Diff
Set n - Breakpoint
Manual Reset (Bias)
Anti Wind-Up Limit
Ratio SFAC
Ratio NO
Primary Cycle Time
Secondary Cycle Time
CONTROL CONFIGURATION SUB-MENU SCREENS
Choose to use one of five PID Sets; or choose Gain Schedule on SP or PV. – This selects a fixed PID set to be “Active”; or automatically switch sets based
changes in SP or PV values.
The primary proportional band for PID Set n (n = up to 5). Set as On-Off con­trol, or a proportional band from 1 to 9999 display units – Only the set(s) in use
are shown.
The secondary proportional band for PID Set n (n = up to 5) if dual control is used. Set as On-Off control, or a proportional band from 1 to 9999 display units – Only the set(s) in use are shown.
The integral time value (Automatic Reset) for PID Set n (n = up to 5). Adjustable from 1s to 99min 59s or OFF – Only the set(s) in use shown.
The derivative time value (Rate) for PID Set n (n = up to 5). Adjustable from 1s to 99 min 59s or OFF – Only the set(s) in use are shown.
The overlap (+ve) or deadband (-ve) between primary & secondary propor­tional bands for PID Set n (n = up to 5). In display units - limited to 20% of the combined primary & secondary prop band width.
The on-off control hysteresis (deadband) for PID Set n (n = up to 5). Adjustable from 1 to 300 display units, centred about the setpoint – Only the set(s) in use
are shown.
The SP or PV value where the PID Set n (n = up to 5) if gain scheduling is used. Set 1 is used from Scaled Input Lower Limit to the Set 2 Breakpoint, then Set 2 used to the Set 3 Breakpoint etc. If a breakpoint is set to OFF subsequent PID sets are not used. The final PID set runs to the Scaled Input Upper Limit.
The Manual Reset value to bias the control working point within the propor­tional band(s). Adjustable from 0 to 100% for single control or 100 to +100% for dual control. Typically set to 80% of typical power needed for setpoint, but lower values can help inhibit start-up overshoot.
Adjusts the value at which the “reset wind-up inhibit” is applied. Above this power level further integral action is suspended. Adjustable from 10 to 100% of PID power. Lower values inhibit overshoot.
Caution: If set too low control deviation can occur (the process set-
tles, but is offset above or below the setpoint). It this is observed, increase the value until the deviation error is removed.
The nominal ratio scaling factor used for Stoichiometric Ratio Control in burn­er fuel/air control applications. Adjustable from 0.010 to 99.999. – refer to the Ratio Control section.
A constant between 0.0 & 9999.0, added to the x1 (input 1) value in Stoichio­metric Ratio Control mode to allow for atomizing air when calculating the pro­cess value. The total air flow is therefore x1 + NO
The primary power cycle time. Adjustable from 0.5 to 512 seconds. Applied for time proportioned primary relay, SSR driver or triac control outputs – Not used
for VMD Control modes.
The secondary power cycle time when dual control is used. Adjustable from
0.5 to 512 seconds. Applied for time proportioned primary relay, SSR driver or triac control outputs – Not used for VMD Control modes.
37
Page 46
CONTROL CONFIGURATION SUB-MENU SCREENS
Primary Power Lower Limit
Primary Power Upper Limit
Secondary Power Lower Limit
Secondary Power Upper Limit
Sensor Break Pre-set Power Output
Motor Travel Time
Minimum Motor On Time
Valve Open Limit
Valve Close Limit
Valve Sensor Break Action
The minimum primary output power limit. The control algorithm will not allow the power output fall below this level. Adjustable from 0 to 90% but is always at least 10% below the primary power upper limit.
Caution: The instrument will not be able to control the process
correctly if the lower limit is above the level required to maintain setpoint.
The maximum primary output power limit. The control algorithm will not allow the power output rise above this level. Adjustable from 10 to 100% but is al­ways at least 10% above the primary power lower limit.
Caution: The instrument will not be able to control the process
correctly if the upper limit is below the level required to maintain setpoint.
The minimum secondary output power limit. The control algorithm will not allow the power output fall below this level. Adjustable from 0 to 90% but is always at least 10% below the secondary power upper limit.
Caution: The instrument will not be able to control the process
correctly if the lower limit is above the level required to maintain setpoint.
The maximum secondary output power limit. The control algorithm will not al­low the power output rise above this level. Adjustable from 10 to 100% but is always at least 10% above the secondary power lower limit.
Caution: The instrument will not be able to control the process
correctly if the upper limit is below the level required to maintain setpoint.
Set the power level to be applied if the process input signal or an active remote setpoint input is lost. Adjustable from 0 to 100% for single control or -100 to +100% for dual control. The default value is OFF (0% power). Does not apply if control is disabled or in manual mode.
Caution: Ensure the value set will maintain safe process condi-
tions.
The motor travel time (valve movement time from fully open to fully closed in mm:ss). Adjustable from 5s to 5 mins - In VMD Control Mode only.
The minimum drive effort (in seconds) to begin moving the motorized valve in VMD Control Mode. Adjustable from 0.02 to 1/10 of the Motor Travel Time
The maximum position the controller will attempt to drive the valve to in VMD Control Mode. Adjustable from the valve close limit+1% to 100.0% (fully open)
- Only possible if the 2nd input is used for valve feedback.
The minimum position the controller will attempt to drive the valve to in VMD Control Mode. Adjustable from 0.0% (fully closed) to the valve open limit-1%
- Only possible if the 2nd input is used for valve feedback.
The direction to drive the valve if the process input signal or an active remote setpoint input is lost. The default action is to drive the valve closed. – Applies
to VMD Control Mode only. Does not apply if control is disabled or in manual mode.
Caution: Set to safe values for the process!
38
Page 47
CONTROL CONFIGURATION SUB-MENU SCREENS
Setpoint Lower Limit
Setpoint Upper Limit
Setpoint Ramp Rate
Main Setpoint Source
Alternate Setpoint Source
Main Setpoint Value
Alternate Setpoint Value
Select Active Setpoint
Main Setpoint Offset
Alternate Setpoint Offset
The minimum allowable setpoint value. Adjustable within the scaled input lim­its, but cannot be above the setpoint upper limit. Applies to local, remote and profile setpoints.
Caution: Set to safe values for the process. Operators can adjust
local setpoints to any value between the limits set.
The maximum allowable setpoint value. Adjustable within the scaled input lim­its, but cannot be below the setpoint lower limit. Applies to local, remote and profile setpoints.
Caution: Set to safe values for the process. Operators can adjust
local setpoints to any value between the limits set.
Setpoint Ramp Rate value, adjustable from 1 to 9999 display units per hour, or OFF. The ramp is applied at power-up (from current PV to SP) and whenever the setpoint value or source is changed. If set to OFF, the setpoint steps im­mediately to the new setpoint value.
Select the source of the main setpoint. This can only be a “Local” setpoint set from the keypad, or Not used.
Select the source of the alternate setpoint. This can be a “Local” setpoint, not used, or an analogue remote setpoint (RSP) signal applied to input 2 or auxil­iary input A – depending on available hardware.
Sets the current value of the main setpoint between the setpoint upper and lower limits.
Sets the current value of the alternate setpoint between the setpoint upper and lower limits – is read-only if alternate setpoint source is RSP.
Select if the main or alternate setpoint is to be the current “active” setpoint for this loop.
An offset that can be added to the main setpoint (+ve values) or subtracted from it (-ve values) when the instrument is a comms slave in a multi-zone ap­plication. This changes the effective setpoint used for control.
Caution: It should be set to zero if an offset is not required.
An offset that can be added to the alternate setpoint (+ve values) or subtracted from it (-ve values) when the instrument is a comms slave in a multi-zone ap­plication. This changes the effective setpoint used for control.
Caution: It should be set to zero if an offset is not required.
Control Loop 2 - Sub-menu to setup Control Loop 1. Press + to return to Input Menu These settings apply to the slave loop if the controller has been setup for cascade control.
Control Select
Control Enable/Disable
Select from Control Standard or Control VMD (TPSC).
Use Control VMD to directly drive the windings of a motorized valve. This uses a 3-point stepping algorithm giving “open” and “close” outputs.
Use Standard for all other applications (including solenoid valves or modulat­ing valves with positioning circuitry requiring mA or VDC signals).
Used to temporarily disable the control outputs. Select control Enabled (nor­mal) or Disabled – when disabled, control output(s) for this loop are turned off (unless manual mode has been selected) and the setpoint value is replaced by “OFF”.
Caution: The instrument is not able to control the process when
control is disabled and the Output Power Limits are ignored.
39
Page 48
Auto/Manual Control Selection
Control Type
Primary Control Action
Control Status
Power Output Levels
Gain Schedule PID Set in use
PID Set Selection
Set n – Primary Pb
Set n – Secondary Pb
Set n – Integral
Set n – Derivative
Set n – Overlap
Set n - Breakpoint
Manual Reset (Bias)
Anti Wind-Up Limit
Switches the control loop between Automatic and Manual Control.
Caution: Manual mode overrides the automatic control loop. It
also ignores any output power limits, valve open/close limits and the control enable/disable setting. The operator is responsible for maintaining the process within safe limits.
Select Single Control for primary control only (e.g. heating only or cooling only) or Dual for primary and secondary control outputs (e.g. heating and cooling) - Dual is not possible with Ratio or VMD Control.
Set the primary control output for Reverse or Direct Action. Reverse action applies additional primary power as the process falls further below setpoint (e.g. heating applications). Direct action applies additional primary power as the process rises higher above setpoint (e.g. cooling applications). In dual control, secondary output action is opposite to primary action.
A “read-only” diagnostic status display of the current loop 2 process vari­able and effective setpoint values to assist with manual tuning.
A “read-only” diagnostic status display of the current loop 2 primary and secondary % output power levels to assist with manual tuning – Not shown with VMD Control. Does not apply if control is disabled or in manual mode.
A “read-only” diagnostic status display showing the PID set in use. The set use may vary based on the current setpoint or process variable value. – Only
shown if Gain Scheduling is in use.
Choose to use one of five PID Sets; or choose Gain Schedule on SP or PV. – This selects a fixed PID set to be “Active”; or automatically switch sets
based changes in SP or PV values.
The primary proportional band for PID Set n (n = up to 5). Set as On-Off control, or a proportional band from 1 to 9999 display units – Only the set(s)
in use are shown.
The secondary proportional band for PID Set n (n = up to 5) if dual control is used. Set as On-Off control, or a proportional band from 1 to 9999 display units – Only the set(s) in use are shown.
The integral time value (Automatic Reset) for PID Set n (n = up to 5). Adjust­able from 1s to 99min 59s or OFF – Only the set(s) in use are shown.
The derivative time value (Rate) for PID Set n (n = up to 5). Adjustable from 1s to 99 min 59s or OFF – Only the set(s) in use are shown.
The overlap (+ve) or deadband (-ve) between primary & secondary propor­tional bands for PID Set n (n = up to 5). In display units - limited to 20% of the combined primary & secondary prop band width.
The SP or PV value where the PID Set n (n = up to 5) if gain scheduling is used. Set 1 is used from Scaled Input Lower Limit to the Set 2 Breakpoint, then Set 2 used to the Set 3 Breakpoint etc. If a breakpoint is set to OFF subsequent PID sets are not used. The final PID set runs to the Scaled Input Upper Limit.
The Manual Reset value to bias the control working point within the propor­tional band(s). Adjustable from 0 to 100% for single control or 100 to +100% for dual control. Typically set to 80% of typical power needed for setpoint, but lower values can help inhibit start-up overshoot.
Adjusts the value at which the “reset wind-up inhibit” is applied. Above this power level further integral action is suspended. Adjustable from 10 to 100% of PID power. Lower values inhibit overshoot.
Caution: If set too low control deviation can occur (the process
settles, but is offset above or below the setpoint). It this is ob­served, increase the value until the deviation error is removed.
40
Page 49
Primary Cycle Time
Secondary Cycle Time
Primary Power Lower Limit
Primary Power Upper Limit
Secondary Power Lower Limit
Secondary Power Upper Limit
Sensor Break Pre-set Power Output
Motor Travel Time
Minimum Motor On Time
Slave SP Scale Min
Slave SP Scale Max
Valve Sensor Break Action
The primary power cycle time. Adjustable from 0.5 to 512 seconds. Applied for time proportioned primary relay, SSR driver or triac control outputs – Not used for VMD Control modes.
The secondary power cycle time when dual control is used. Adjustable from
0.5 to 512 seconds. Applied for time proportioned primary relay, SSR driver or triac control outputs – Not used for VMD Control modes.
The minimum primary output power limit. The control algorithm will not al­low the power output fall below this level. Adjustable from 0 to 90% but is always at least 10% below the primary power upper limit.
Caution: The instrument will not be able to control the process
correctly if the lower limit is above the level required to maintain setpoint.
The maximum primary output power limit. The control algorithm will not al­low the power output rise above this level. Adjustable from 10 to 100% but is always at least 10% above the primary power lower limit.
Caution: The instrument will not be able to control the process
correctly if the upper limit is above the level required to maintain setpoint.
The minimum secondary output power limit. The control algorithm will not allow the power output fall below this level. Adjustable from 0 to 90% but is always at least 10% below the primary power upper limit.
Caution: The instrument will not be able to control the process
correctly if the lower limit is above the level required to maintain setpoint.
The maximum secondary output power limit. The control algorithm will not allow the power output rise above this level. Adjustable from 10 to 100% but is always at least 10% above the primary power lower limit.
Caution: The instrument will not be able to control the process
correctly if the upper limit is above the level required to maintain setpoint.
Set the power level to be applied if the process input signal or an active remote setpoint input is lost. Adjustable from 0 to 100% for single control or
-100 to +100% for dual control. The default value is OFF (0% power). Does
not apply if control is disabled or in manual mode.
Caution: Ensure the value set will maintain safe process condi-
tions.
The motor travel time (valve movement time from fully open to fully closed in mm:ss). Adjustable from 5s to 5 mins - In VMD Control Mode only.
The minimum drive effort (in seconds) to begin moving the motorized valve in VMD Control Mode. Adjustable from 0.02 to 1/10 of the Motor Travel Time.
The effective cascade slave setpoint value equating to 0% power demand from the master controller - Limited by the slave input scaling.
Caution: Set to safe values for the process!
The effective cascade slave setpoint value equating to 100% power demand from the master controller - Limited by the slave input scaling.
Caution: Set to safe values for the process!
The direction to drive the valve if the process input signal or an active remote setpoint input is lost. The default action is to drive the valve closed. –
Applies to VMD Control Mode only. Does not apply if control is disabled or in manual mode.
Caution: Set to safe values for the process!
41
Page 50
Setpoint Lower Limit
Setpoint Upper Limit
Setpoint Ramp Rate
Main Setpoint Source
Alternate Setpoint Source
Main Setpoint Value
Alternate Setpoint Value
Select Active Setpoint
Main Setpoint Offset
Alternate Setpoint Offset
The minimum allowable setpoint value. Adjustable within the scaled input limits, but cannot be above the setpoint upper limit. Applies to local, remote and profile setpoints.
Caution: Set to safe values for the process. Operators can adjust
local setpoints to any value between the limits set.
The maximum allowable setpoint value. Adjustable within the scaled input limits, but cannot be below the setpoint lower limit. Applies to local, remote and profile setpoints.
Caution: Set to safe values for the process. Operators can adjust
local setpoints to any value between the limits set.
Setpoint Ramp Rate value, adjustable from 1 to 9999 display units per hour, or OFF. The ramp is applied at power-up (from current PV to SP) and whenever the setpoint value or source is changed. If set to OFF, the setpoint steps immediately to the new setpoint value.
Select the source of the main setpoint. This can only be a “Local” setpoint set from the keypad, or Not used.
Select the source of the alternate setpoint. This can be a “Local” setpoint, not used, or an analogue remote setpoint signal applied to input 2 or auxil­iary input A – depending on available hardware.
Sets the current value of the main setpoint between the setpoint upper and lower limits.
Sets the current value of the alternate setpoint between the setpoint upper and lower limits.
Select if the main or alternate setpoint is to be the “active” setpoint for this loop.
An offset that can be added to the main setpoint (+ve values) or subtracted from it (-ve values) when the instrument is a comms slave in a multi-zone ap­plication. This changes the effective setpoint used for control.
Caution: It should be set to zero if an offset is not required.
An offset that can be added to the alternate setpoint (+ve values) or sub­tracted from it (-ve values) when the instrument is a comms slave in a multi­zone application. This changes the effective setpoint used for control.
Caution: It should be set to zero if an offset is not required.
OUTPUTS CONFIGURATION SUB-MENU SCREENS
Output n Configuration - Up to 9 outputs listed. Any already used show as “Assigned” but can be changed.
If “Digital” is shown, the output is driven directly via a digital input (see input configuration). Relevant screen sequences repeat for outputs fitted. Press
Linear Output n Type
Adjustable 0-10V Transmitter PSU n
Output n Usage
OPn OR Selection
Set the desired type for any linear outputs fitted. From: 0-5, 0-10, 1-5, 2-10V
w
& 0-20, 4-20mA or 0-10VDC adjustable transmitter PSU.
Sets the voltage required if linear output n type is 0-10VDC adjustable trans-
w
mitter PSU.
Sets the use for the output. From: Loop 1 or 2 Primary / Secondary Power; Logical OR or AND of Alarms & Profile Events (direct or reverse acting); Re-
w
transmission (of loop 1 or 2 effective setpoint, Input 1 or 2 process values). Choices offered are appropriate for the output type fitted (e.g. only linear out­puts can retransmit).
When an output usage is set for logical OR alarms & profile events, this selects the alarms or events to be OR’d. Press
w
Alarms 1 to 7; Events 1 to 5; PR (Profile running); PE (Profile Ended). Direct outputs turn on, & reverse outputs turn off according to the selected logical OR combination.
+ to return to Configuration Menu
or to select R or deselect c
42
Page 51
OUTPUTS CONFIGURATION SUB-MENU SCREENS
OPn AND Selection
Output n Latch Enable
Output n Lower Retransmit Limit
Output n Upper Retransmit Limit
When an output usage is set for logical AND alarms & profile events, this se­lects the alarms or events to be AND’d. Press
c
w
Alarms 1 to 7; Events 1 to 5; PR (Profile running); PE (Profile Ended). Direct outputs turn on, & reverse outputs turn off according to the selected logical AND combination.
If enabled, an output will remain latched ON even if the condition that caused it to be on is no-longer present, and remains latched even if the instrument is powered off-on. The output latch must be reset to turn it off.
w
Note: An output cannot reset if the condition that caused it to turn on is still present.
The displayed value at which the retransmission output reaches its minimum level (e.g the display value when a 4 to 20mA retransmission output is at 4mA). Adjustable from -9999 to 9999.9. The output is at its minimum below this value. Above this value, it rises linearly in line with the displayed value to reach its maximum at the Upper Retransmit Limit display value.
w
The displayed value at which a retransmission output will be at its maximum level (e.g. the display value when a 4 to 20mA retransmission output is at 20mA). Adjustable from -9999 to 9999.9. The output is at its maximum above this display value. Below this value, it falls linearly in line with the displayed value to reach its minimum at the Lower Retransmit Limit display value.
or to select R or deselect
ALARM CONFIGURATION SUB-MENU SCREENS
Alarm n Configuration - 7 alarms listed with any already used shown as “Assigned”. Relevant screen se-
quences repeat for each alarm (n = 1 to 7). Press
+ to return to Configuration Menu
Alarm n Type
Alarm n Source
Alarm n Value
Alarm n Hysteresis
Alarm n Minimum Duration
Alarm n Inhibit
Sets the function of alarm n from: Unused; Process High; Process Low; PV-SP Deviation; Band; Control Loop; Rate Of Signal Change per minute; Input Sig-
w
nal Break; % of Recorder Memory Used, Control Power High, Control Power Low.
The signal source of Alarm n from: Input 1, Input 2 & Auxiliary Input A; Control Loop 1; Control Loop 2; Loop 1 Primary or Secondary Power; Loop 2 Primary
w
or Secondary Power – auxiliary input A is only possible if fitted and the alarm type can only be input signal break.
The Alarm n activation point – The value is limited by the scaled input limits for Process High; Process Low; PV-SP Deviation (+ve above, -ve below setpoint), Band (above or below setpoint) type alarms. Rate of Signal Change is a rate of 0.0 to 99999 (rate in units per minute). Memory used, Control Power High, Control Power Low are 0.0 to 100.0% – not required for Control Loop or Input
w
Signal Break alarm types.
The deadband on the “safe” side of alarm n, through which signal must pass before alarm deactivates - not for Rate of Change, Control Loop, Input Break
or Percentage of Memory used alarms.
The minimum time that alarm n must be passed its threshold before activating (deactivation is not affected by this parameter). Adjustable from 0.0 to 9999.0 secs. – not used for signal break, memory or loop alarms.
w
Caution: If the duration is less than the time set, the alarm will not
become active.
If the inhibit is enabled, it prevents the initial alarm activation if the alarm con-
w
dition is true at power up. Activation only occurs once the alarm condition has passed and then reoccurred
43
Page 52
Control n Loop Alarm
Manual Record Digital Input Profile Record Alarm Record
Type
Control n Loop Alarm Time
COMMUNICATIONS CONFIGURATION SUB-MENU SCREENS
No Communications Warning
Modbus Parity
Modbus Data Rate
Master Mode, or Slave Address
Target Register In Slave
Master Mode Format
Serial Communications Write Enable
ALARM CONFIGURATION SUB-MENU SCREENS
Sets the loop alarm time source, from: Manual Loop Alarm Time (as set in the loop alarm n time screen) or Automatic (twice the integral time constant set-
w
ting). If configured, a Loop Alarm activates if no response is seen in loop n after this time following the saturation of its power output. – Only seen if an alarm is
set for control loop type.
The time (max 99:59 mm:ss) for loop n to begin responding after PID power
w
output reaches saturation, if a manual loop alarm type is configured.
If Communications Configuration menu is entered without a communications module fitted.
The setting for Modbus comms parity bit checking, from: Odd; Even or None. Set the same parity for all devices on the network – Only seen if RS485 or
Ethernet communications option is fitted.
The setting for the Modbus comms data speed. From: 4800; 9600; 19200; 38400; 57600 or 115200 bps. Set the same speed for all devices on the net­work – Only seen if RS485 or Ethernet communications option is fitted.
Slave address (1 to 255), or multi-zone Setpoint Master Mode – Only seen if
RS485 or Ethernet communications option is fitted, but Master mode is not available over Ethernet.
Target memory register for the setpoint value in attached slave controllers. All slaves must have the same setpoint register address as set here - Appears
only if unit is in Master mode.
The data format required by the attached setpoint slaves. From: Integer; inte­ger with 1 decimal place or float - Appears only if unit is in Master mode.
Enables/disables writing via RS485 or Ethernet communications. When dis­abled, parameters can be read, but attempts to change their values over com­ms are blocked.
DATA RECORDER CONFIGURATION SUB-MENU SCREENS:
No Recorder Warning
Recording In Progress Warning
Pause (Override Trigger)
Recorder Status Information
If the Recorder Configuration menu is entered on an instrument without this option fitted.
A warning if recording when attempting to enter recorder configuration.
Access to the configuration is denied unless the recording is paused.
Select No to continue recording or Yes to enter recorder configuration.
Note: Recording is paused until recorder configuration is completed. It restarts automatically on exit from this menu.
Current information about the data recorder feature, including if a recording is in progress (Recording or Stopped); the recording mode (FIFO or Record Until Memory Is Used); a % memory use bar-graph and the estimated available time remaining based on the data selected and memory left. If the alarm status is recorded and is likely to change often, take this into account when determin­ing if there is sufficient memory available. Icons are displayed for active recording triggers. If any trigger is active, the selected data will be recorded.
44
Page 53
DATA RECORDER CONFIGURATION SUB-MENU SCREENS:
Recorder Mode
Recording Sample Interval
Choose Record Until Memory Used (stops recording when full) or Continuous FIFO (First In - First Out).
Caution: A FIFO recording will overwrite previous recordings in
memory, starting with the oldest data first. Download the previous data before selecting this option.
Recording of the selected data will happen once every sample interval. From every: 1; 2; 5; 10; 15; 30 Seconds, or 1; 2; 5; 10; 15; 30 Minutes.
- The recording interval does not affect Trend View sample rates.
Note: Shorter intervals reduce the possible recording duration.
Recorder Auto Trigger
Trigger on Alarms
Loop 1 Values to Record
Loop 2 Values to Record
Other Values to Record
Activities to Record
Automatic recording triggers. From: None; On Alarm; During Profile and Alarm or Profile. Data is recorded if any trigger is active (including a digital input or manual recording start).
Any combination of alarms 1 to 7 can be set to trigger a recording (TRG) or not (OFF). If any alarm set to TRG becomes active, the alarm recording trigger activates.
Note: 10 samples at 1s intervals are stored and added to the recording prior to and after the data that is stored at the normal sample rate while the alarm is on.
Any combination of loop 1 values can be recorded from: Process Variable; Maximum or Minimum PV (since the previous sample was taken); Setpoint; Primary Power, Secondary Power. Set to Record (REC) or not (OFF).
Note: Recording more parameters reduces the possible recording duration.
Any combination of loop 2 values can be recorded from: Process Variable; Maximum or Minimum PV (since the previous sample was taken); Setpoint; Primary Power, Secondary Power. Set to Record (REC) or not (OFF).
Note: Recording more parameters reduces the possible recording duration.
If required, select to record the value of auxiliary input A.
Multiple process events can be recorded from: Alarm n Status (n = 1 to 7) or Unit turned Off/On.
Profiler Events to Record
Note: If an alarm changes state an extra sample is recorded using extra memory. The remaining recording time is reduced accordingly.
The Profiler Event n Status can be recorded (n = 1 to 5).
Note: If a profile event changes state an extra sample is recorded using extra memory. The remaining recording time is reduced accordingly.
45
Page 54
Date Format
Set Date
Set Time
Note: Clock settings cannot be changed when the data recorder is active.
DISPLAY CONFIGURATION SUB-MENU SCREENS
Language
Enable Custom Display Mode
Read Only Operation Mode?
Display Color
Invert Display
Display Contrast
Loop 1 Trend Sample Interval
Loop 1 Trend View Mode
Loop 2 Trend Sample Interval
Loop 2 Trend View Mode
Operator Visibility
CLOCK CONFIGURATION SUB-MENU SCREENS
The format used for all displayed dates: dd/mm/yyyy (Day / Month / Year) or
w
mm/dd/yyyy (Month / Day / Year). – Recorder versions only.
Set the internal clock Date – Entered in the format defined by Date Format
w
screen. – Recorder versions only.
Set the internal clock Time. - In hh:mm:ss (Hours : Minutes : Seconds) format.
w
– Recorder versions only.
Select English or the alternate local language. The alternate language is se­lected at time of order, but can be changed later using the PC software.
Enables/disables the Custom Operation Mode, if configured. The screens seen in this mode are configured using the PC configuration software.
Allows Operation Mode to be Read/Write or Read-Only where screens can be seen but the values cannot be changed.
From: Red only; Green only; Red to Green on Alarm or Green to Red on Alarm; Red to Green if Output Latched or Green to Red if Output Latched.
Standard or Inverted display image.
Screen contrast (10 and 100) to improve clarity. 100 = maximum contrast.
The Interval between the displayed values on the loop 1 trend graph. From: Every 1; 2; 5; 10; 15; 30 Seconds, or 1; 2; 5; 10; 15; 30 Minutes. -
Independent from the loop 2 trend graph and data recorder sample rates.
The data to display on the loop 1 trend graph. From: Process Value only, PV (solid) & SP (dotted) at sample time, or the Max & Min PV between samples (candle-stick graph). Alarm active indication is always shown at the top of
graph.
The Interval between the displayed values on the loop 2 trend graph. From: Every 1; 2; 5; 10; 15; 30 Seconds, or 1; 2; 5; 10; 15; 30 Minutes. - Independent
from the loop 1 trend graph and data recorder sample rates.
The data to display on the loop 1 trend graph. From: Process Value only, PV (solid) & SP (dotted) at sample time, or the Max & Min PV between samples (candle-stick graph). Alarm active indication is always shown at the top of
graph.
Extra parameters can be made visible/adjustable in Operation Mode from: Profile Control; Recorder Start/Stop; Recorder Status; Loop 1 & 2 Setpoint Select; Loop 1 & 2 Auto/Manual Select; Loop 1 & 2 Control Select; Loop 1 & 2 Trend View; Loop 1 & 2 Setpoint Ramp Rate.
See Operator Mode lists.
46
Page 55
Lock Code Configuration
Reset To Defaults
LOCK CODE CONFIGURATION SUB-MENU SCREEN
Set Lock Codes (passwords) for the following configuration and control menus: Setup Wizard; Configuration Mode; Tuning Menu; Supervisor Mode; USB Menu; Recorder Menu, Profiler Setup and Profiler Menu. Independently adjustable from 1-9999 or OFF.
Note: The factory default value is 10 for all lock codes. For security, users are recommended to change these codes.
RESET TO DEFAULTS SUB-MENU SCREEN
The user can set all parameters back to their factory default values before preparing the instrument for installation in a new application.
Caution: The user must reconfigure all of the required settings be-
fore using the instrument.
The USB Menu
A notification is shown if a USB memory stick is in­serted or removed from the USB port. The USB Menu will automatically be offered after insertion. The USB menu can also be accessed from the Main Menu.Entry into the Configuration Menu.
Entry into the USB Menu
Do not remove the memory stick from the USB port whilst a Data Transfer to or from the USB stick is in progress. Data loss or corruption may result.
The USB Menu is entered from the Main Menu
Hold down
Press or to select USB Menu
Note: Entry into this mode is security-protected by the USB Menu Lock Code. Refer to the Lock Code Configuration sub-menu.
and press to enter the Main Menu.
Navigating the USB Menu
Press to move forward, or to move backwards through the screens.
Press or to change the value as required.
The next/previous screen follows the last parameter. If
no further changes are required, hold down or >1sec to skip straight to next/previous screen accept­ing ALL values shown.
Hold down and press to return to the Main Menu
Note: During Data Transfer, normal operation car­ries on in the background, but operator access to other screens is not possible. The transfer of a full memory can take up to 20 minutes. Only begin a transfer when you are certain that access (e.g. set­point changes) will not be required.
Scrolling “Help Text” is shown at the bottom of the screens to aid navigation.
Press to enter the Configuration Menu.
47
Page 56
USB Mode Unlocking
Read/Write To USB Device
USB MENU SCREENS
Enter correct code number to access the USB Menu.
Factory Default value is 10.
Select the required action from: Read Configuration File; Write Configuration File; Write Recorder Log File. Read Profile Files; Write Profile Files.
Note: “Writing” is downloading from the Instrument to the USB stick. “Reading” is uploading from the USB stick to the Instrument.
Select Profile To Write
Enter A File Name
Enter A Folder Name
Write
Writing Profile, Configuration or Log
Transfer Successful
Transfer Failure
Select File
Reading Profile or Configuration File
Read
Transfer Successful
Transfer Failure
If writing a profile to the USB memory stick, choose a profile to write from the list provided.
Enter an 8-character file name if writing configurations or profiles. A file ex­tension is automatically added to the end of file name (bct for configurations or pfl for profiles).
Caution: Existing files with the same name will be over-written.
Recorder logs can contain multiple files. The user enters an 8-character folder name for these logs. See the Data Recorder section
Note: To prevent existing recordings being over-written, an error message is shown if the folder name entered already exists.
An animated screen is shown the files are being written.
Caution: Do not disconnect USB device until completed! Data loss
or corruption may result.
Confirmation that the data transfer to the USB stick completed correctly.
Press
For write failures, check for adequate disk space on the USB stick.
Select the Configuration or Profile file to transfer from the USB stick. Cau-
tion: Configuration reads overwrite ALL of the instruments exist-
ing settings with new values.
An animated screen is shown while files are being read. Caution: Do not remove the memory stick whist this operation is in progress. Data corruption may result.
Confirmation that the data transfer from the USB stick completed correctly.
Press
For read failures, check the maximum number of profiles and/or segments is not being exceeded.
to continue
to continue.
48
Page 57
Recorder Control Menu
Manual Record Digital Input Profile Record Alarm Record
This menu allows the user to manually start a recording or to delete previous recordings. Refer to the Recorder Configuration sub-menu in Configuration Mode for in­formation about how to setup the data to be recorded and the recording interval and the Data Recorder Op­tion section on page 97 for general information about the recorder feature.
Entry into the Recorder Control Menu
The Recorder Control Menu is entered from the Main Menu
Hold down and press to enter the Main Menu.
Navigating the Recorder Control Menu
Press to move forward, or to move backwards through parameters & screens.
Holding down immediately to the next/previous screen accepting ALL values as shown.
Press or to select or change the value as re­quired.
The next/previous screen follows the last parameter. If
no further changes are required, hold down or >1sec to skip straight to next/previous screen accept­ing ALL values shown.
or for more than 1 second skips
Press or to select Recorder Control Menu
Note: Entry into this mode is security-protected by the Recorder Control Menu Lock Code. Refer to the Lock Code Configuration sub-menu.
Press
Recorder Mode Unlocking
Recording in Progress Warning
Start/Stop Data Recording
to enter the Recorder Control Menu.
RECORDER MENU SCREENS:
Enter correct code number to access the Data Recorder Menu.
Factory Default value is 10.
Shown if a recording is in progress when the recorder control menu is entered.
Turn on or off the manual recording trigger.
Note: Recording continues if another record trigger is active (e.g. on alarm/profile or via a digital input). Access is restricted to this screen only until recording stops (remove all active triggers).
Hold down
Scrolling “Help Text” is shown at the bottom of the screens to aid navigation.
and press to return to the Main Menu
Recorder Status Information
Clear Recordings
Current information about the data recorder feature, including if a recording is in progress (Recording or Stopped); the recording mode (FIFO or Record Until Memory Is Used); a % memory use bar-graph and the estimated available time remaining based on the data selected and memory left. If the alarm status is
recorded and is likely to change often, take this into account when determining if there is sufficient memory available.
Icons are displayed for active recording triggers. If any are active, the selected data will be recorded.
Clears the recorder memory. Download any recorded data before use.
Caution: This permanently deletes All recorded data.
49
Page 58
Profiler Setup Menu
Screens marked must be completed for a valid profile to be created. Refer to the Profiler section on page 87 for more details about the profiler.
will not time-out automatically. They
Entry into the Profiler Setup Menu
The Profiler Setup Menu is entered from the Main Menu
Hold down and press to enter the Main Menu. Press or to select the Profiler Setup Menu
Note: Entry into this mode is security-protected by the profiler setup menu lock code. Refer to the Lock Code Configuration sub-menu.
Navigating the Profiler Setup Menu
Press to move forward, or to move backwards through parameters & screens.
Press or to select or change the value as re­quired.
Holding down immediately to the next/previous screen accepting ALL values as shown.
Hold down and press to return to the Main Menu
Scrolling “Help Text” is shown at the bottom of the screens to aid navigation.
or for more than 1 second skips
Press
Profiler Setup Menu Unlocking
Profile Setup Options
General Profile Configuration
to enter the Profiler Setup Menu.
Enable Edit While Running
Timer Start Function
General
PROFILER SETUP MENU SCREENS
Enter correct code number to access Profiler Setup Menu. Factory Default value is 10.
Select the required profile setup sub-menu option from: General Configura­tion; Create a Profile; Edit a Profile Header; Edit a Profile Segment; Insert a Segment; Delete a Segment; Delete a Profile or Delete ALL Profiles.
Sub-menu with global settings affecting all profiles. Press Press return to Profile Setup Menu
Enables or disables the ability to edit profiles whist a profile is running.
Caution: Edits made to the current or next segment of the running
profile will take effect until after the profile is restarted.
Enable or disable automatic starting of profiles. When enabled, delayed starts are possible, or if the selected profile has a day & time trigger it waits until the time set before starting.
Note: If the Timer Start Function is disabled, profiles can only be manually started, and with immediate effect even if they have a delay or day & time trigger defined.
& to
Create A Profile
Sub-menu to create a new profile. A header is created first, followed by the segments – see below.
Caution: It is not possible to exit from this sub-menu until profile
creation is fully complete. Do not turn off the power during pro­file creation or editing. When the profile creation/editing is com­plete the instrument returns automatically to the profile setup main menu.
Note: A warning is displayed if the maximum number of 64 profiles or 255 segments is exceeded.
50
Page 59
PROFILER SETUP MENU SCREENS
Profile Header: Settings that apply to the chosen profile as a whole.
Enter Profile Name
Set the Number of Loops
Give each profile a unique descriptive name of up to 16 characters. The name is shown in the profile status screen and in profile selection lists.
Select if a profile controls the setpoint of first loop only or both control loops. This screen is “read only” when editing a profile. The number cannot be changed once the profile has been created.
Note: the segment type and time settings are common to both loops. Some segment types are not available with 2-loop profiling
Profile Starting Point
Profile Start Trigger
Profile Start Time
Profile Start Day(s)
Profile Header Details
Profile Start Delay Time
Profile Recovery Method
Profile Recovery Time
Profile Abort Action
Profile Cycles
Profile Segments: Settings that apply to individual profile segments
Segment Number
Segment Type
Profile Segment Details
The setpoint value used at the beginning of the first segment. From: Current Setpoint or Current Process Variable. The setpoint starts from the measured PV(s) or effective setpoint(s) of the process as it begins running.
From: None (profile start is not delayed); After Delay or Day and Time.
- Day and Time possible on the recorder version only.
Note: If the Timer Start Function is disabled, profiles can only be manually started, and with immediate effect even if they have a delay or day & time trigger defined.
If Day and Time is the Profile Start Trigger, this is the time (hh:mm:ss) when the profile will begin if it is selected to run.
If Day and Time is the Profile Start Trigger, this is the Day(s) when the profile should run. From: Mon; Tue; Wed; Thu; Fri; Sat; Sun; Mon-Fri; Mon-Sat; Sat­Sun or All.
If After Delay is the Profile Start Trigger, this is the delay time of up to 99:59 (hh:mm) before a profile begins after a start request has been given.
The power-on action if profile was running at power-down (e.g. after a power cut), or following correction of a signal break. From: Control outputs off; Re­start profile from the beginning; Maintain last profile setpoint; Use controller setpoint; Continue profile from where it was when power failed..
The Recovery Method is ignored (the profile continues from where power failed), if power off for less than this time. Max 99:59 (hh:mm).
- Recorder version only.
The action taken after profile has been forced to stop early. From: Control outputs off; Maintain last profile setpoint or Use controller setpoint.
The number of times the program should run each time it is started. From 1 to 9999 or Infinite.
Shows the number of the profile segment being created. The maximum num­ber of profiles across all profiles is 255.
Set the segment type from: Ramp Time (time to reach target SP); Ramp Rate (rate of change towards target SP – Single loop profiles only); Step (jump to target SP), Dwell (keep current SP); Hold (hold profile until released); Loop (back to previous segment); Join (to another profile); End or Repeat Sequence Then End (repeat a sequence of joined profiles).
Note: Segment Ramp Rate is not available if the profile controls two loops. A Join, End or Repeat Sequence Then End isthe last segment in the pro­file. Repeat Sequence Then End is always the last profile in a sequence.
51
Page 60
Loop 1 Target Setpoint.
Loop 2 Target Setpoint.
Segment Ramp Time
Segment Ramp Rate
Segment Dwell Time
Number of Loops
Back to Segment Number
PROFILER SETUP MENU SCREENS
The setpoint value to be reached control loop 1 by the end of this segment, if the type is Ramp Time, Ramp Rate or Step.
If the profile is controlling 2 loops, this is the setpoint value to be reached control loop 2 by the end of the segment, if the type is Ramp Time or Step.
The time (hh:mm:ss) to reach the segment target setpoint if the segment type is Ramp Time.
The rate of change towards the Segment Target Setpoint if segment type is Ramp Rate. The rate can be from 0.001 to 9999.9 display units per hour.
The time (hh:mm:ss) to maintain the current setpoint if the segment type is Dwell.
If the segment type is Loop, enter the number of times to repeat the loop back, before continuing forward to the next segment.
If the segment type is Loop, enter the segment to loop back to.
Note: Two Loop-backs cannot be set to cross each other.
Loop 1 Auto-Hold Type
Loop 1 Auto-Hold Band Value
Loop 2 Auto-Hold Type
Profile Segment Details
Loop 2 Auto-Hold Band Value
Segment Hold Release Type
Hold Release Time
Times To Repeat Sequence
Segment End Type
Select Profile to Join
The auto-hold type for this segment to ensure loop 1 tracks the setpoint. From: None (no auto-hold); Above Setpoint (hold if too high only); Below Set­point (hold if too low only) or Band (hold if too high or low).
The distance loop 1 can be from setpoint. Beyond this the profile is held for the selected Auto-Hold Type.
Note: For Two-Loop Profiles, either loop can cause the profile to hold. The profile continues only when both loops are within their Auto-Hold Bands.
The auto-hold type for this segment to ensure loop 2 tracks the setpoint. From: None (no auto-hold); Above Setpoint (hold if too high only); Below Set­point (hold if too low only) or Band (hold if too high or low).
The distance loop 2 can be from setpoint. Beyond this the profile is held for the selected Auto-Hold Type.
Note: For Two-Loop Profiles, either loop can cause the profile to hold. The profile continues only when both loops are within their Auto-Hold Bands.
A hold segment can either be released by an Operator/Digital input or be set to wait until a specified Time of Day - Recorder version only.
The time of day (hh:mm:ss) when a Hold Segment will release if the Release Type is Time Of Day. The profile is held by the hold segment and only re­leased at the next occurrence of the time of day set.
The number of times the entire sequence of profiles should run. – if the last segment is Repeat Sequence Then End.
The action taken after the profile ends normally. From: Control Outputs Off; Maintain Last Profile Setpoint or Use Controller Setpoint.
Choose a profile to join to from the list provided – if the final segment type is Join. The selected profile will start immediately the current profile ends.
52
Page 61
Event n
Profile Segment Details
Edit A Profile Header
Edit A Profile Segment
PROFILER SETUP MENU SCREENS
Select the events to be active during this segment. n = 1 to 5. Note: For end segments, the events selected to be active stay on until the instrument exits from profiler mode or a new profile runs.
Note: For end segments, the events selected to be active stay on until the instrument exits from profiler mode or a new profile runs.
Choose the profile to be edited from the list of names provided, then alter any values as required – The profile header details are as shown in “Create A
Profile” above.
Choose the profile, then the segment to be edited from the lists provided. Alter any values as required – The profile segment details are as shown in
“Create A Profile” above.
Note: The last segment type can only be set to Join, End or Repeat Se­quence Then End. Use Insert or Delete to change the end position.
Insert A Segment
Delete A Segment
Delete A Profile
Delete All Profiles
Profiler Control Menu
Profiler Control Menu Unlocking
Profile Control
Select Profile
Choose the profile, then the new segment’s position from the lists provided – Enter the new segment values as required – The profile segment details are as
shown in “Create A Profile” above.
Note: The new segment type cannot be set to Join, End or Repeat Se­quence Then End. Use Delete to change the end position.
Choose the profile, then the segment to be deleted from the lists provided. End, Join or Repeat segments cannot be deleted.
Choose the profile to be deleted from the list of names is provided. The user is prompted confirm the deletion.
If selected, the user is prompted to confirm that the profiles should be de­leted.
Caution: This deletes all profiles from memory!
PROFILER CONTROL MENU SCREENS
Enter correct code number to access Profiler Control Menu.
Factory Default value is 10.
If a profile is running, from: Do Nothing; Abort Profile (end immediately); or Jump to Next Profile Segment; Hold Profile or Release Hold. If profile not running, from: Do Nothing; Run Profile; End Profile Control (return to normal controller operation) or Select Profile.
Selects a profile. If Run Profile was chosen in the previous screen, the profile starts (after a delay if one is enabled). Otherwise the profile is selected, but waits for a run instruction (e.g. via digital input or timer).
Note: Selection is “read only” if profile selection is via a digital input. Otherwise choose from the list of profile names provided.
53
Page 62
Service & Product Information Mode
This is read only information about the instrument, its modules and enabled features. It has contact informa­tion to tell the user where they can obtain service, sales or technical support for the product. Normally this is the manufacturer or suppliers’ details. Using the PC software, the user can enter their own contact informa­tion. There are 7 lines of text - each up to 25 characters in length.
Entry into Service & Product Information Mode
The Service & Product Information Mode is entered from the Main Menu
Hold down and press to enter the Main Menu.
Press or to select the Service & Product Infor­mation Mode.
Navigating Product Information Mode
Press to move forward or to move backwards through the displayed information.
Hold down
Scrolling “Help Text” is shown at the bottom of the screens to aid navigation.
and press to return to the Main Menu
Press Mode.
Plug-in Module Information
Base Options
Optional Features
Firmware Information
Product Revision Level
Serial Number
Date of Manufacture
Input 1 Calibration Status
Input 2 Calibration Status
Calibration Check Due Date
For Service Contact
to enter the Service & Product Information
SERVICE & PRODUCT INFORMATION SCREENS:
Lists the type plug-in modules types in Slots 1, 2, 3 or A
Lists factory fitted base options, from: 2nd Universal/Aux input; Output 4 & 5 Relay; Output 6 & 7 Linear mA/V DC.
Lists which other optional features are fitted/enabled, from: Profiler; USB Port; Data Recorder and 8 Digital Inputs.
The type and version of firmware installed in the instrument.
Software and Hardware update status.
The instrument serial number.
The instrument Date of Manufacture (date format is dd/mm/yyyy).
The base calibration status for each signal type on input 1.
Caution: Re-calibrate input 1 for mVDC, VDC, mADC, RTD or Ther-
mocouple CJC if they do not say “Calibrated”
The base calibration status for each signal type on optional input 2.
Caution: Re-calibrate input 2 for mVDC, VDC, mADC, RTD or Ther-
mocouple CJC if they do not say “Calibrated”
The date re-calibration is due. – only shown if the Calibration Reminder is enabled in the Input Configuration menu.
Contact information for service, sales or technical support.
54
Page 63
Automatic Tuning Menu
The automatic tune menu is used to engage pre-tune and/or self-tune to assist setting up proportional bands and the integral and derivative time values used by the control loops.
Pre-tune can be used to set PID parameters approxi­mately. Self-tune may then be used to optimize the tun­ing if required. See the Tuning section on page 99 for more information. Pre-tune can be set to run automati­cally after every power-up by enabling Auto Pre-Tune.
Entry into the Automatic Tuning Menu
The Automatic Tuning Menu is entered from the Main Menu
Hold down and press to enter the Main Menu.
Press or to select the Automatic Tuning Menu.
Press R to enter the Automatic Tuning Menu.
AUTOMATIC TUNING MENU SCREENS
Automatic Tuning Mode Unlocking
Control loop 1 or 2
Cascade Mode
Enter correct code number to access the Automatic Tuning Menu. Factory Default value is 10.
Select which control loop you want to tune –if unit has 2 control loops.
To pre-tune a cascade slave, select open-cascade.
Note: When slave tuning is completed, repeat choosing open-cascade to tune the master.
Navigating the Automatic Tuning Menu
Press to move forward or to move backwards through the selections.
Press or to change values or engage and disen­gage the tuning as required.
Hold down
Scrolling “Help Text” is shown at the bottom of the screens to aid navigation.
and press to return to the Main Menu
Pre-Tune Method
Pre-Tune Value
Pre-Tune Save Location
Run Pre-Tune on Set n Now?
Pre-Tune Status
Engage Self-Tune
Self-Tune Status
From: Pre-Tune Standard or Pre-Tune at Value. Standard Pre-Tune tests the process response half-way from the activation point to the setpoint. Pre-Tune at Valve allows the user to specify where the test occurs.
Sets the value at which the process is tested for Pre-Tune at Valve. Caution: Consider possible over-shoot!
Store the pre-tune result to one of 5 PID sets. The new PID terms can be stored to any set, without changing the “active set” from control configura­tion.
Turns pre-tune on/off for the chosen PID Set. If configured, the TUNE LED
w
indicator flashes whilst pre-tune is operating - *see below.
Note: Pre-tune is disabled in on-off control mode; if the PV is less than 5% of span from setpoint; during Profiles; if the setpoint is ramping or if the selected control loop has been disabled.
Shows the current pre-tune status: Running or Stopped. If an attempt to run pre-tune failed, the reason is shown.
Turns self-tune on/off for the active PID Set. If configured, the TUNE LED indicator is continuously on whilst self-tune is operating
Note: Self-Tune disabled if control is On-Off or disabled. If engaged dur­ing setpoint ramping, profile ramps or pre-tuning it is suspended until the ramp or pre-tune is completed.
Shows current self-tune status: Running or Stopped. If an attempt to run self­tune failed, the reason is shown.
55
Page 64
AUTOMATIC TUNING MENU SCREENS
Auto Pre-Tune At Power Up
*TUNE indication is the default function of LED 3 but the user may have altered the LED functions or the labels using the PC Configuration Software. If LED 3 is used as a TUNE indicator, it flashes while pre-tune is operating, and is continuously on whilst self-tune is operating. If both pre-tune and self-tune are engaged the TUNE indicator will flash until pre-tune is finished, and is then continuously on.
Enables/disables automatic pre-tune. When enabled, this attempts to tune the active PID set at every power-up (see Run Pre-Tune Now above).
Note: Auto Pre-tune applies standard pre-tune engagement rules at pow­er-up. It is disabled in on-off control mode; if the PV is less than 5% of span from setpoint; during Profiles; if the setpoint is ramping or if the selected control loop has been disabled.
Note: Pre-tune will flash the LED instead of turn­ing it on, but flashing will be obscured if the LED had been configured to be used in conjunction with other functions and one of these is on.
Lost Lock Codes
All menu lock codes can be viewed or changed from configuration mode. In the event that the configuration mode lock code is forgotten, the instrument can be forced into Lock Code Configuration from power-up, where the codes can be checked or set to new values.
Forcing Lock Code Configuration
Power down the instrument.
Re-apply the power and hold down than 5 seconds as the start-up splash screen appears. The Lock Code Configuration menu is displayed.
Press to move forward or to move backwards through the screen elements.
Make note of the codes or press or to change their values if required.
Hold down and press to return to the Main Menu
Scrolling “Help Text” is shown at the bottom of the screens to aid navigation.
and for more
56
Page 65
9 Input Calibration & Multi-point Scaling
User Calibration
The process inputs can be adjusted to remove sensor errors or to match the characteristics of the attached process. For each loop, independent use of base (un­adjusted), single point offset or two point calibration strategies are possible, as is the use of multi-point scaling for the displayed values of linear inputs. These parameters are in the Input 1 & 2 calibration sub-menus of Input Configuration Sub-Menu Screens.
Incorrect use of Calibration & Scaling can make the displayed value very different from the actual process variable. There is no front panel indication of when these parameters are in use.
Note: These methods do not alter the internal in­strument calibration. Simply choose Base Calibra­tion to restore normal measured values. Re-calibration of the internal base values is possi­ble, but should only be attempted by qualified per­sonnel as it overwrites the factory calibration – see Base Calibration Adjustment below if you think this may be required.
Re-calibration of the internal base values is possible, but should only be attempted by qualified personnel as it overwrites the factory calibration – see Base Calibra­tion Adjustment below if you think this may be required.
Calibration Reminder
If the Data Recorder feature is fitted, a calibration re­minder can be set for a future date. From this date a daily reminder is shown (and shown at every start-up), until a new date has been set. This is useful in applica­tions that require a regular check of the measured ac­curacy – see Input Configuration Sub-Menu Screens.
Single Point Calibration
This is a ‘zero offset’ applied to the process variable across the entire span. Positive values are added to the reading, negative values are subtracted. It can be used if the error is constant across the range, or the user is only interested in a single critical value. To use, se­lect Single Point Calibration from the input calibration menu, and simply enter a value equal, but opposite to the observed error to correct the reading.
Single Point
‘Offset Calibration’
value
New Displayed
Value
Original
Displayed
Value
Figure 44. Single Point Calibration
This example shows a positive offset value. For exam­ple: If the process displays 27.8 when it should read 30, The error is -2.2 so an applied offset of +2.2 would change the displayed value to 30.
The same offset is applied to all values, so at 100.0 the new displayed value would be 102.2.
57
Page 66
Two Point Calibration
This method is used where an error is not constant across the range. Separate offsets are applied at two points in the range to eliminate both “zero” and “span” errors. To use:
1. Measure and record the error at a low point in the process.
2. Measure and record the error at a high point in the process.
3. Go to the first two point input calibration screen.
a. Enter the desired low point value as the Calibra-
tion Low PV value.
b. Enter an equal, but opposite value to the ob-
served error as the Calibration Low Offset to cor­rect the error at the low point.
4. Go to the second two point input calibration screen.
a. Enter the desired high point as the Calibration
High PV value.
b. Enter an equal, but opposite value to the ob-
served error as the Calibration High Offset to correct the error at the high point.
Calibration
High Offset
Original Displayed
New Displayed
Calibration
Low Offset
Figure 45. Two Point Calibration
This example shows a positive Low Offset and a nega­tive High Offset. For example: If the process displays a low end error where +0.5 displays as 0.0, an offset of +0.5 corrects the value to +0.5
A high end value of 100.0 with a -1.7 offset would read
98.3.
There is a linear relationship between these two cali­bration points.
Value
Value
Calibration Low
Process Value
Calibration High
Process Value
Multi-point Scaling
If an input is connected to a linear input signal (mA, mV or VDC), multi-point scaling can be enabled. This al­lows the linearization of a non-linear signal. – see Input
Configuration Sub-Menu Screens.
The Scale Input Upper & Lower Limits define the values shown when the input is at its minimum and maximum values. Up to 15 breakpoints can scale the input vs. displayed value between these limits. It is advisable to concentrate the break points in the area of the range with the most non-linearity, or an area of particular im­portance to the application.
To Scale
Upper Limit
New
Linearized
Displayed
Values
Non-linear signal
Scale Lower
Limit
Scaling Point 1
Scaling Points 2, 3 & 4
Figure 46. Multi-point Scaling
Set the scale limits, and then enter the 1st scaling point (this is a % of the scaled input span, and the desired display value to be shown at that input value. Next set the 2nd point and display value, followed by the 3rd etc. Continue unit all breakpoints are used or you have reached 100% of the input span. A breakpoint set at 100% ends the sequence.
Base Calibration Adjustment
Calibration of each input type is carried out during manufacture. This can be verified in the Service and Product Info screens.
Re-calibration of the internal base values is possible, but should only be attempted by qualified personnel as it overwrites the factory calibration. For most appli­cations, base re-calibration is not required during the lifetime of the instrument.
Choose values as near as possible to the bot­tom and top of your usable span to achieve maximum calibration accuracy. The effect of any error can grow at values beyond the cho­sen calibration points.
ELECTRIC SHOCK/FIRE HAZARD. BASE CALI­BRATION SHOULD ONLY BE PERFORMED IF ERRORS HAVE BEEN ENCOUNTERED. REFER TO CALIBRATION CHECK BELOW. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RE­SULT IN PERSONAL INJURY OR DEATH AND/OR EQUIPMENT / PROPERTY DAMAGE.
58
Page 67
ELECTRIC SHOCK/FIRE HAZARD. Any calibra­tion adjustment must only be performed by personnel who are technically competent and authorized to do so. Failure to follow these instructions could result in personal injury or equipment damage.
The equipment used must be in a known good state of calibration.
Required Equipment
To verify the accuracy of the instrument or to carry out recalibration, a suitable calibration signal source is re­quired for each input type as listed below. Accuracy must be better than ±0.05% of reading:
1. DC linear inputs: 0 to 50mV, 0 to 10VDC and 0 to 20mADC.
2. Thermocouple inputs - complete with 0ºC reference facility, appropriate thermocouple functions and compensating lead wire.
3. RTD inputs: decade resistance box with connec­tions for three-wire input.
Performing a Calibration Check
1. Setup input 1 for the input signal type to be checked.
2. Power up the instrument and correctly connect the
signal source. Leave powered up for at least five minutes for RTD and DC linear inputs, and at least 30 minutes for thermocouple inputs.
3. After the appropriate delay for stabilisation, check the calibration at a number of cardinal points by ap­plying the appropriate input signal. The observed readings should be within the tolerances stated in the specifications.
4. Test the other signal types as above if required.
5. Repeat the process for input 2 if fitted.
Recalibration Procedure
For each process input, recalibration is carried out in six phases as shown in the table below; each phase corresponds to a basic input type.
INPUT CALIBRATION PHASES
Type Signal (<0.05% error) Cable Type
Millivolt Voltage Milliamps (pt 1) Milliamps (pt 2) RTD Thermocouple
1. For optimum accuracy, leave the instrument power-up
for >30 minutes to warm up before beginning the cali­bration, and then toggle the power off/on to restart the instrument.
2. During the power-up “splash screen”, press and
together until the Input 1 Calibration Status screen
is displayed.
3. Correctly connect the 1st phase signal (50mV), then
press to select the first phase
4. Press + to initiate the calibration.
5. During calibration the message “50mV DC Input Cali-
brating” will display for a few seconds. This should be followed by the “Calibration Successful” confirmation.
6. If the input is misconnected or an incorrect signal is ap­plied, the calibration will be aborted and the values will not be altered. The display will show “Failed: Signal Too Small!” or “Failed: Signal Too Large!”. Correct the problem and repeat that phase before continuing.
50 mVDC Copper Wire 2 3 6 7
10 VDC Copper Wire 2 3 6 7
0 mADC Copper Wire 3 1 7 5
20 mADC Copper Wire 3 1 7 5
200 ohm Copper 3-Wires 1 2 & 3 5 6 & 7
0ºC K type source K Thermocouple Wire 2 3 6 7
Note: The 50 mV calibration phase MUST always be
calibrated before calibration of the thermocouple input.
Input 1 Terminals Input 2 Terminals
+ - + -
7. Press to select the next calibration phase.
8. Repeat this process for each input type until all the
phases are calibrated. For each phase, ensure that the correct input is applied, using the appropriate connec­tions.
9. If the instrument has 2 process inputs, when the first input sequence completes, the Input 2 Calibration Sta­tus screen is displayed. Repeat the procedure from 3 above for this input.
10. Once calibration is complete, recorder versions will ask for a Calibration Reminder Date. If required, this can be changed to the date of your next calibration check. Ensure that Calibration Reminders are enabled in Input Configuration to receive a reminder.
11. Press + to exit to the main menu.
Note: The Calibration Mode automatically exits if there is no button activity for two minutes.
59
Page 68
Slot A, C1 to C8 & Soft digital input status
C1-C3 = 011 = 6)
Highlighted Input
10 Digital Inputs
Digital inputs are driven to one of two states (active or inactive) by an applied voltage signal or a contact opening/closing.
A total of 9 physical digital inputs are possible on this instrument. A multiple digital input can be installed at time of purchase, and a single plug-in module can be fitted in option slot A.
Digital Signal Type
The digital inputs can be connected to volt-free con­tacts, or to a voltage signal (compatible with TTL). They can often be used in parallel with equivalent menu se­lections, where either can change function status.
Some inputs are level sensitive, while others are edge sensitive requiring a High to Low or Low to High transi­tion to change functions status. Pre-Tune is always off at power-up (except if auto pre-tune is enabled), but other edge sensitive functions retain their power off status at power on. See the tables below for details.
Open contacts (>5000Ώ) or 2 to 24VDC signal = Logic High (logic low if inverted). Closed contacts (<50Ώ) or
-0.6 to +0.8VDC signal = Logic Low (logic high if in­verted).
highlighted input and to skip to next screen accepting the values shown.
to un-invert o. Hold down
Soft Digital Inputs
In addition to the physical digital inputs, four “soft” dig­ital inputs are available. They are used to select func­tions in the same way as the physical inputs.
The response time is 0.25 seconds. Signals applied for less than this time may not register and the function might not change state.
A diagnostic screen assists commissioning and fault finding by showing the current signal state for all digital inputs.
Active, Ø = Unavailable)
(
=
Profile select bit format (BCD or Binary)
Profile selected (example shown:
Inverting Digital Inputs
Digital inputs can be inverted to reverse their action making an “on” input behave as off. Step thorough
each input using the key. Press to invert R the
The four soft digital inputs can be configured by com­bining physical inputs, alarms & events using Boolean logic. Input AND selections are then globally OR’d with the input OR selections, the alarms & the events. By using the invert inputs function, NAND & NOR equiva­lents can be created.
Digital Input Functions
Some or all of inputs C1 to C7 can be used for profile selection. If used in this way they cannot be used for any other functions. Soft inputs and any physical digital inputs not allocated for profile selection can be used to change the instrument status. Each input can only perform a single function. The possible functions are listed in the next table.
60
Page 69
Single Functions
Digital inputs can often work in parallel with equivalent menus, where either can change function status.
In the table below, = Level Sensitive: Where a High or low signal sets the function status. High-Low or Low-High transition changes the function status. Pre-Tune is always off at power on (except if auto pre-tune is in use), and profile recovery is as configured, but others functions retain their power off status when the power returns.
Function Logic High* Logic Low*
Loop 1 Control Select Enabled Disabled Loop 2 Control Select Enabled Disabled Loop 1 Auto/Manual Select Automatic Manual Loop 2 Auto/Manual Select Automatic Manual
Loop 1 Setpoint Select Main SP Alternate SP Loop 2 Setpoint Select Main SP Alternate SP Loop 1 Pre-Tune Select Stop Run Loop 2 Pre-Tune Select Stop Run Loop 1 Self-Tune Select Stop Run Loop 2 Self-Tune Select Stop Run Profile Run/Hold Hold Run Profile Hold Segment Release No Action Release Profile Abort No Action Abort
Data Recorder Trigger Not Active Active
Output n Forcing Off/Open On/Closed
Clear All Latched Outputs No Action Reset
Output n Clear Latch No Action Reset
Key n Mimic (for L D U R) No Action Key Pressed
= Edge Sensitive:
Sensitivity / Functions’
Power On State
/ Retained / Retained / Retained / Retained
/ Retained / Retained
/ OFF
/ OFF / Retained / Retained
/ As configured
/ Retained
/ As Digital Input
/ As Digital Input
/ As Digital Input
/ As Digital Input
/ As Digital Input
/ As Digital Input
Profile Selection via Digital Inputs
For instruments with the profiler option, the multi-digital input option can be used to select the profile to run using either a standard binary bit pattern, or binary coded decimal from BCD switches. Profile selection inputs are all level sensitive ( ), with a high/open signal equating to a binary 1 (assuming non-inverted), and a low/closed signal equating to a binary 0 (assuming non-inverted).
Profiles are numbered 0 to 63. Select inputs C1 to Cn for the required number of profiles, from the table:
C1 C1 to C2 C1 to C3 C1 to C4 C1 to C5 C1 to C6 C1 to C7
Binary
BCD
C6 to C1 C5 to C1 C4 to C1 C3 to C1 C2 to C1 C1
000000 to 111111
(0 to 63)
A single BCD switch can be used to select profiles 0 to 9 using C1 to C4, with a bit pattern identical to standard binary. For larger numbers, a double BCD switch arrangement is needed. A separate binary pattern is applied to C5 to C7 for the “tens” digit (10 = 001, 20 = 010, 30 = 011 etc). Any number combination higher than 63 is invalid.
Multiples of Ten (0x to 6x) Multiples of One (x0 to x9)
C7 to C1 C6 to C1 C5 to C1 C4 to C1 C3 to C1 C2 to C1 C1
000 to 110
(0x to 6x)
0 to 1 0 to 3 0 to 7 0 to 15 0 to 31 0 to 63 0 to 1 0 to 3 0 to 7 0 to 9 0 to 19 0 to 39 0 to 63
Using Binary to Select Profile Numbers
Selection of profiles is via a simple binary bit pattern. C1 is the least significant bit (LSB).
00000 to 11111
(0 to 31)
00 to 11
(0x to 3x)
(0x to 1x)
0000 to 1111
(0 to 15)
Using BCD to Select Profile Numbers
0 to 1
0000 to 1001
(x0 to x9)
000 to 111
(0 to 7)
000 to 111
(x0 to x7)
00 to 11
(0 to 3)
00 to 11
(x0 to x3)
0 to 1
(0 to 1)
0 to 1
(x0 to x1)
61
Page 70
250°C
Setpoint
11 Cascade Control
Applications with long time lags (e.g. with two or more capacities such as heated jackets) can be difficult to control with a single control loop. The solution is to split the process into two or more cascaded loops consist­ing of a Master and Slave(s) acting on a common ac­tuator. Ideally, the slave loop’s natural response time should be at least 5 times faster than the master.
The master controller measures the process tempera­ture and compares it to the desired product setpoint. Its correcting variable (0 to 100% PID output) becomes the slave’s effective setpoint (scaled to suit the pro­cess). This setpoint is compared to the slave’s process input, and the controlling actuator is adjusted accord­ingly.
Note: Cascade control is only available on models fitted with the 2nd control loop. The master loop uses input 1; and the slave loop uses input 2.
Example Cascade Application
In this example the controlling actuator is a heater, indirectly heating the product via an oil jacket. The maximum input to the slave represents 300ºC, thus restricting the jacket temperature. At start-up the mas­ter compares the product temperature (ambient) to its setpoint (250ºC) and gives 100%. This sets the maxi­mum slave setpoint (300ºC), which is compared to the oil temperature (ambient) and the slave requests maxi­mum heater output.
As the oil temperature rises towards the slave setpoint, its output falls. Gradually, the product temperature will also begin rising, at a rate dependant on the transfer rate/lag between the oil jacket and the product. Eventu­ally this causes the master’s PID output to decrease, reducing the slave setpoint. The oil temperature is re­duced towards the new slave setpoint. This continues until the system becomes balanced. The result is quick­er, smoother control with the ability to cope with chang­es in the load. Overshoot is minimized and the jacket temperature is kept within acceptable tolerances.
Normal Cascade Operation
During operation, the master and slave are coupled to­gether and. “Cascade” is displayed. The master pro­cess value and setpoint are most relevant to the user. The master setpoint is directly adjustable. The process value of the slave controller is displayed for information only.
Cascade-Open
The cascade can be disconnected (via digital inputs or menu selection), switching from normal operation to di­rect control of the slave. “Cascade-Open” is displayed. Opening the cascade is “Bumpless”. The current cas­cade value is used as the initial slave setpoint (dis­played as “SlaveSP”). The process is then controlled and adjusted solely by the slave controller using this setpoint. Switching back to Cascade is also bumpless.
Master
MASTER
IP1
PRODUCT
OIL JACKET
HEATER
0-100%
OP SP
Output
MASTER SENSOR
Figure 47. Cascade Example
0-300°C
Slave SP
SLAVE SENSOR
SLAVE
IP2
ELECTRIC SHOCK/FIRE HAZARD. The master process value is not under control when the cascade is open, but will be affected by the
OP SP
slave process. The operator is responsible for maintaining safe conditions. Failure to follow these instructions could result in personal in­jury or equipment damage.
Manual Mode
The controller can be put into manual mode (via digital inputs or menu selection), switching from normal op­eration to direct control of the slave loop’s correcting variable. Manual power is adjusted from 0% or -100 to 100%. “MAN” is displayed.
ELECTRIC SHOCK/FIRE HAZARD. Manual mode disables the cascade loop. It also ignores any output power limits, valve open/close limits and the control enable/disable setting. The op­erator is responsible for maintaining the pro­cess within safe limits. Failure to follow these instructions could result in personal injury or equipment damage.
62
Page 71
Cascade Tuning
The user can tune the slave and master loops manu­ally, or use the pre-tune feature (see Controller Tuning).
In either case the slave control loop must first be opti­mized on its own, followed by the master loop in com­bination with the previously tuned slave.
To automatically pre-tune a cascade:
1. Go to the Automatic Tuning menu
2. Select “Cascade-Open” from the pre-tune menu to
tune the PID set(s) on the slave.
3. After the slave has successfully tuned, pre-tune the master/slave combination by selecting “Cascade­Closed” from the pre-tune menu.
Note: The cascade remains open until you pre-tune the master or manually select Cascade-Closed.
To manually tune a cascade:
1. Select Cascade-Open from the Cascade Control menu, breaking the link between the master and slave loops.
2. Set the slave controller setpoint manually to the ap­propriate value for your application.
3. Tune the slave for relatively fast control (‘proportion­al only’ is often sufficient).
4. Select Cascade-Closed from the Cascade Control menu to link the master and slave loops, then tune the master/slave combination.
63
Page 72
Fuel
12 Ratio Control
A ratio control loop is used where the quantity of one of the material is to be controlled in proportion to the measured quantity of a second material. The controller mixes the materials at the desired ratio by adjusting the flow of input 1. The flow of input 2 may be controlled separately, but is not controlled by the ratio control loop itself.
The process value used by the controller is therefore determined by the ratio of the two inputs rather than a single measured variable.
Note: Ratio control is available on models with the 2nd Auxiliary Input, or two loop models. The feature and information displayed is optimized for control of burner fuel/air, but can be used in other flow ratio applications.
Stoichiometric Combustion
Below is an example of stoichiometric combustion ra­tio control. For optimum combustion the fuel-air ratio is set so that there are no flammable residues in the waste gas.
Burner
Air
Air Valve
fected by this control loop. Atomizing air is fed in with the fuel oil at a constant rate ‘NO’. This must be con­sidered when calculating the correct fuel/air mix. Total airflow is x1 + NO. The stoichiometric factor, SFac is entered to match the desired ratio. E.g for 10 parts total airflow to one part fuel, SFac would be 10.
The setpoint (entered as a relative value such as 1.00) is multiplied by SFac when calculating the control de­viation. E.g. with a setpoint of 1.00 and SFac of 10 the controller attempts to make the physical ratio 10. With a setpoint of 1.03 it would attempt to make the ratio
10.3 for 3% excess air.
The instantaneous (controlled) process value is calcu­lated from the physical ratio, divided by SFac. Like the setpoint, this is displayed as relative value.
E.g. if SFac is 10, with 59.5m3/h airflow measured at x1, 0.5m3/h atomising air applied at NO and 6m3/h fuel is measured at x2, the instantaneous process value would be:
x1 + NO
x2 * SFac
=
59.5 + 0.5
6 * 10
=
1.00
If fuel flow remained at 6m3/h and the setpoint was adjusted to 1.05 (5% excess air), the controller would increase the x1 air flow to 62.5m3/h.
x1 + NO
x2 * SFac
=
62.5 + 0.5
6 * 10
=
1.05
Atomization Air
NO
Figure 48. Ratio Control Example
It is normal in this application to display the process value and setpoint as relative values rather than the physical ratio or absolute values. A scaling factor is set such that the displayed value will be 1.00 at the correct stoichiometric ratio for the application.
Inputs 1 and 2 are configured and scaled to match the attached flow meters. In this example a 4 to 20mA sig­nal at x1 represents 0 to 1000m3/h of airflow controlled by a valve. The second 4 to 20mA signal at x2 repre­sents 0 to 100m3/h of fuel oil. The fuel flow is not af-
Typical Ration display with Setpoint at 1.05
64
Page 73
13 Redundant Input
If the 2nd universal input is fitted, the second input can be configured as a redundant input for the main pro­cess input. This increases process security by protect­ing against the possible loss of valuable product result­ing from sensor failure.
A second sensor is connected to input 2 so that if the main sensor fails, the instrument automatically switch­es to this backup or “redundant” sensor. In this con­dition, if input 1 has a signal break alarm configured it will activate, but any other process input or control status alarms seamlessly switch to the 2nd input. The 2nd input continues to be used until the signal to input 1 is restored.
Note: The user may not even be aware of a sen­sor fault, so it is strongly recommended that signal break alarms are configured for both inputs to pro­vide a notification if problems occur.
The redundant sensor must be of the same type, and be correctly located in the application ready to take over if needed. If the redundant input option is select­ed, the 2nd input cannot be used for other functions.
Note: If both signals are lost at the same time, the PV value display is replaced with “OPEN” and the normal sensor break actions occur.
65
Page 74
14 Valve Motor Drive / 3-Point Stepping Control
When directly controlling the motor of a modulating valve or damper, set the Control Mode to VMD in con­figuration mode to enable the 3-point stepping Valve Motor Drive control algorithm.
The term “3-point stepping” is used because there are 3 output states, open valve, close valve or stopped (no action). Switched outputs move the valve further open, or further closed when a control deviation error is de­tected. If the error is reduced to zero, no further output is required until the load conditions change.
VMD mode doesn’t allow on-off control (the minimum proportional band equates to 0.5% of the scaled input span) and usually requires PI control, where the deriva­tive parameter is set to OFF.
Note: Some modulating valves have positioning cir­cuitry to adjust the valve position. These require a DC linear mA or voltage output and use the standard control algorithm (Set Control Mode to Standard).
Special Wiring Considerations for Valve Motor Control
Valve motor drive mode must have two identical out­puts assigned to position the valve. One to open and one to close the valve. These outputs can be two single relays, two triacs, two SSR drivers or one dual relay, but it is recommended to use two single relays (SPDT change-over contacts), and to interlock the wiring as shown. This prevents both motor windings from being driven at the same time, even under fault conditions.
Open Valve
“OPEN” RELAY
N/O
C
N/C
“CLOSE” RELAY
2 x 120V = 240V
120V
N/C C N/O
N/C C N/O
120VAC SUPPLY
ELECTRIC SHOCK/FIRE HAZARD. of a valve motor effectively form an autotrans­former. This has a voltage doubling effect when power is applied to either the Open or Close ter­minal, causing twice the supplied voltage at the other terminal. For this reason, switching devices directly connected to the valve motor must only be used up to half of their rated voltage. The max-
Winding
Valve Common
Close Valve Winding
The windings
imum motor voltage when using the internal re­lays/triacs is therefore 120 V unless interposing relays are used. Interposing relays or other devic­es used to control the valve must themselves be rated for twice the motor supply voltage. Failure to follow these instructions could result in per­sonal injury or equipment damage.
Switching actuators directly connected to the valve motor must only be used up to half of their rated volt­age. The internal relay and triac outputs in this instru­ment are rated at 240VAC Therefore, the maximum mo­tor voltage when using them is therefore 120V unless interposing relays are used. Interposing relays or other devices used to control the valve must themselves be rated for twice the motor supply voltage.
Position Feedback
In VMD mode this instrument uses a boundless (open­loop) 3-point stepping algorithm. It does not require any kind of position feedback in order to correctly con­trol the process and can therefore avoids problems as­sociated with faulty feedback signals.
However, where valve feedback is available it can still be displayed in a bar-graph as a percentage open (0 to 100%). Position feedback is usually provided by means of a potentiometer mechanically linked to the valve. The output of a related flow meter can also be used to indicate the relative valve position. Flow meters typically have linear 0-20/4-20mA or 0-5/0-10V signals. To display the position/flow signal the 2nd input is must be configured for this purpose.
The input is adjusted and scaled to show 0 to 100% representing valve fully closed to fully open, or a flow rate equating to fully closed to fully open. The valve position scaling parameters are set in the Input Con­figuration sub menus.
Valve Limiting
When valve position/flow indication is in use, the signal can be used by the controller to limit the valve move­ment. Upper and/or lower limits can be set beyond which it will not attempt to drive the valve. The valve open and close limits are set in the Control Configura­tion sub menu.
These limits must be used with care. They are effectively control power limits. Do not set val­ues that prevent proper control of the process!
66
Page 75
15 Setpoint Sources
The setpoint is the target value at which the instrument attempts to maintain the process variable. Each loop can have a Main “local” setpoint set from the keypad and an Alternate setpoint.
Loop 1 Setpoint Sources
Loop 1 can have a Main “local” setpoint set from the keypad and an Alternate setpoint. The alternate set­point source can be either another local Setpoint or a remote setpoint (RSP), set by a mA or V DC signal ap­plied to the 2nd input or to auxiliary input A. The control loop can only use one setpoint source at a time for each loop. This is called the “Active Setpoint”. If the profiler option is fitted this provides the setpoint when the profiler is in use, replacing both main an alternate setpoints.
Main/alternate setpoint selection can be made via a digital input; from the Control Configuration menu or if enabled in the Display Configuration sub-menu, an operator screen can be used to select the setpoint. The chosen setpoint selection method can be used to per­manently select one of the setpoints, or allow switching between them.
Refer to the Control Configuration Sub-Menu Screens on page 50 for setpoint settings.
Loop 1 Profile Setpoint
When in profile control mode, the selected profile al­ways provides the active setpoint source for loop 1. Once profile control mode is exited, the selected main or alternate setpoint for loop 1 becomes active again.
Loop 2 Setpoint Sources
Loop 2 can have a Main “local” setpoint set from the keypad and an Alternate setpoint. The alternate set­point source can be either another local Setpoint” or a remote setpoint (RSP), set by a mA or V DC signal applied to auxiliary input A. The control loop can only use one setpoint source at a time for each loop. This is called the “Active Setpoint”. If the profiler option is fitted this provides the setpoint, replacing both main an alternate setpoints, when 2-loop profiling is in use.
Main/alternate setpoint selection can be made via a digital input; from the Control Configuration menu or if enabled in the Display Configuration sub-menu, an operator screen can be used to select the setpoint. The chosen setpoint selection method can be used to per­manently select one of the setpoints, or allow switching between them.
Refer to the Control Configuration Sub-Menu Screens for setpoint settings.
Loop 2 Profile Setpoint
If the selected profile was configured to control the setpoint of both loops, it will provide the active set­point source. Once profile control mode is exited, the selected main or alternate setpoint for loop 2 becomes active again.
67
Page 76
16 Profiler
This section covers the Profiler (or setpoint program­mer) option. To confirm if profiling is enabled on your controller, refer to the Service & Product Info menu.
Introduction
The Profiler feature allows the user to store up to 255 profile segments, shared between a maximum of 64 Profiles. Each profile controls the value of the setpoint over time; increasing, decreasing or holding their val­ues as required. The profile can control both setpoints if the 2nd control loop is fitted.
Profiler options and screens are added to the Main Menu and Operation Mode.
Profiler Enabling
Controllers supplied without the Profiler option in­stalled can be upgraded by purchasing a licence code number. Refer to the Field Upgrade information.
To obtain the correct code you must tell your supplier the instrument serial number – this can be found in the Service & Product Info menu.
To enter the licence code, hold down the + keys during the power-up splash screen. Enter the 16-character licence code in the displayed screen and
press .
Profile Components
General profile configuration settings apply to all pro­files. They enable or disable “profile editing while run­ning”, and automatic starting of the selected profile if it has been configured with a delay or day & time start trigger.
If delay or day & time start triggers are disabled, pro­files can only be manually started, and this is with im­mediate effect even if they have a delay or day & time trigger defined. If delay or day & time start triggers are enabled, delayed starts are possible, and if the select­ed profile has a day & time trigger it will wait until the time set and before starting.
Note: Even if profile editing is enabled, changes to the current and next segment or a running pro­file will not take effect until the profile is next run. Changes to other segments will take effect imme­diately.
more segments. The header information is unique for each profile, it contains the profile’s name; if it controls just one or both loops; how it should start & stop; the abort & power-loss recovery actions; and how many times it should be repeated.
Note: Profile Header information is only stored to memory as the Segment creation sequence begins. No profile is created if you exit before this point. Segment information is stored as each segment is created, but the profile remains invalid until an end or join segment is defined.
Segment information is stored as each segment is cre­ated, but the profile remains invalid until an end or join segment is defined.
Segments can be ramps, dwells, steps or special seg­ments such as holds, ends, joins or loop-backs.
If the instrument also has the data recorder option, its real time clock (RTC) expands the profiling capabilities by adding Day & Time profile start options, releasing of hold segments at a specific time of day and chang­ing the power fail recovery option to one based on the length of time the power has been off. These features are explained below and in the Profiler Setup and Pro­file Control menus.
Profile Starting & Standard Segments
The example profile below explains the standard seg­ment types required to make a simple profile or profile sequence. A Start Trigger is the instruction to begin the selected profile. This can be from the profile control menu, a digital input signal, via a serial communica­tions command or if enabled in the display configu­ration, the profile can be controlled from an operator screen.
Following a Start Trigger, profiles can start immedi- ately, after a delay, or using the Day & Time start timer (Day & Time start available on with the Recorder option only). Following the start trigger, the remaining delay time or the start day & time are shown in the profile status bar-graph until the profile begins running.
Note: Profiles outside current setpoint limits will not run, A “profile not valid” error shows if you attempt to run a profile under these circumstances.
Profile Header & Segment Information
Each profile has its own header information plus 1 or
68
Page 77
PROFILE 1 PROFILE 9
Seg. 1 Target SP
Ramp
Timer or Delay Dwell
Join (Profile 1to Profile 9)
(Time/Rate)
Starting Setpoint
Start
Trigger
Figure 49. Profile Starting and Standard Segment Types
Ramps and Step Segments have target setpoint that they will reach as they finish. If a segment is a Ramp­Time type, the slope needed to reach the target set­point in the defined time will change depending on the starting setpoint value. For a Ramp-Rate segment, the slope is defined by the segments Ramp Rate, so the time to reach the target setpoint will change instead. This is of particular significance for the first segment, since the starting value of the process may not be known in advance.
Note: When using the instrument as a two loop pro­filer Ramp-Rate type segments are not available. Calculate the time from the starting value to the target setpoint and use Ramp-Time instead.
Step
End
The example below shows how two loop profiling works in practice. Auto-Hold settings and target set­points are independent for each loop, but the segment types and time settings are the same.
A Dwell (often called a “soak”) holds the previous setpoint value for the specified dwell time. Step segments jump straight to the new target setpoint value. An End segment ends the profile or profile sequence. If the last segment is a Join, the “join target” profile will begin running.
Note: If the join target has been deleted the profile sequence will abort and the last profiles abort ac­tion will apply.
Two Loop Profiles
If the instrument is configured to control two control loops, the setpoint of both loops can be maintained when profiling. Both setpoints are synchronized to a common segment time-base, but have independent target setpoints for each of the segments.
Note: When using the instrument as a two loop pro­filer Ramp-Rate type segments are not available. Calculate the time from the starting value to the target setpoint and use Ramp-Time instead.
Seg. u & v shows a ramp and a dwell with the shared time base The ramp direction can be different (Seg. w), and although one loop cannot ramp while the other dwells, a “dwell” is achieved by a ramp with its final setpoint value at the same value as the previous seg­ment (Seg. x). Similarly, if only one loop is to Step to a new value, make the other “step” to its existing set­point value. If you later change the previous setpoint, you may have to change both segments.
The Loop-back feature takes both loops back to the same defined earlier segment.
Note: Auto-Hold settings are independent for each loop. Either loop can cause the profile to auto-hold, holding both loops at the current setpoint value. The profile continues only when both loops are back within their hold bands.
69
Page 78
Loop-Back Segments
Loop
Continue Triggers
Hold Segments
End
Hold Start
Hold Stop
Run
Held if Auto-Hold set to Above Setpoint or Band
Dwell Segment
Setpoint
Hold Band
Process Variable
Held if Auto-Hold set to Below Setpoint or Band
A Loop-back segment goes back to a specified seg­ment in the current profile. This action is repeated for the required number of times (1 to 9999) before the profile continues onwards. More than one Loop Seg­ment can be used in a profile, but they cannot cross.
-back target segment
x 500
Loop Segment
End
Example: Runs segments 1 to 5, then
repeats segments 3 to 5 again 500 times, before continuing on to segments 7
Figure 50. Loop-back Segments
Profile Running / Holding vs. Hold Segments
A Hold Segment is a pre-planned hold programmed into the profile. It maintains the value of the previous segment and the profile does not continue until a Con- tinue Trigger occurs. This can be via a key-press, se­rial communications, a digital input signal or after wait­ing until a pre-set time of day (time of day is available with the recorder option only).
The Auto-Hold Feature
There are independent auto-hold settings for each seg­ment of each loop controlled by the profile. When uti­lized, auto-hold ensures that the profile and the actual processes remain synchronized. If the process does not closely match the setpoints (within the defined Hold Bands), the profile will be held until it returns within bounds. When Auto-Hold becomes active, the profile status is shown as “Held”.
Note: The segment time is increased by the time that the process is out of bounds, extending the to­tal profile run time.
Auto-hold can be configured to hold the profile if the process goes beyond the hold band Above the Set-
point only, Below the Setpoint only or it can be set to Band (either side of the setpoint).
Note: For two-loop profiles, either loop can cause the profile to hold. The entire profile (i.e. both loops) will be held if either process is outside of its auto­hold band. It continues only when both loops are back within their auto-hold bands.
Figure 51. Run/Hold & Hold Segments
A Hold condition during a segment maintains the cur­rent profile setpoint value(s). Once the hold condition is stopped the Ramp or Dwell continues. The user can request that the profile holds, or it can be instigated automatically.
Note: A running segment will hold if the operator or a digital input instructs it to. It can also hold due to “auto-hold”, if one of the profile control loops is disabled, if a cascade is set to “open” or if manual control is selected.
Auto Hold Examples
Figure 52. Auto-Hold on a Dwell Segment
During a Dwell, the dwell time is increased by the time that the process is outside of the hold band in the se­lected direction(s). This ensures the process was at the desired level for the required amount of time.
70
Page 79
Auto Hold on Ramps
Held if Auto-Hold set to Above Setpoint or Band
Held if Auto-Hold set to Below Setpoint or Band
PROFILE 4PROFILE 31 PROFILE 7
This sequence is repeated ten times.
During a Ramp segment, the ramp is held at the cur­rent setpoint value while the process is outside of the hold band in the selected direction(s). The time taken to complete the ramp is increased by the time taken by the Auto-Hold.
Process Variable
Ramp Setpoint (without Auto-Hold)
Hold Band
Ramp Setpoint (with Auto-Hold)
Figure 53. Auto-Hold On A Ramp Segment
Profile 4
Cycles = 1
Cycles = 3
Profile 31
Profile Cycles & Repeat Sequences
A profile can be configured to run itself from 1 to 9999 times or continuously using the Profile Cycles setting. A profile ending with Repeat then End will run the en­tire sequence of profiles again from 1 to 9999 times before ending.
Profile 7
Cycles = 1
(Profile 4 to Profile 31)
Join
Repeat Sequence = 10
Example: Runs profile 4 once, profile 31 three times & profile 7 once.
Figure 54. Profile Cycles & Repeats
Repeat Then End
(times to repeat = 10)
Join (Profile 31 to Profile 7)
71
Page 80
Power/Signal Lost Recovery Actions
Power off or input lost
Power / input returns
If the power is cut or the input signal is lost while a pro­file is running, the instrument will use the defined Pro­file Recovery Method once the signal / power returns. The profile recovery method is set in the profile header.
The possible profile recovery options are explained be­low.
Run (Start-on SP)
Off Time
Note: Recorder versions always use option E (Con­tinue profile) if the “off time” is less than the Profile Recovery Time setting. If the “off time” is longer, the defined Profile Recovery Method is used.
Note: With option E, after the power returns profile bar graph resets and shows the remaining/elapsed time for the profile only since re-starting.
Planned Profile
Controller SP
= Control Off
Possible Recovery Methods:
A
End the profile and maintain the setpoint value(s) from the time the power failed.
B End the profile and use Controller Setpoint value (s).
See
note
above
End the profile with the Control outputs off - setpoint value replaced by “OFF”.
C D Restart the profileagain from the beginning. E Continue profile from the point it had reached when the power failed
Figure 55. End, Abort and Recovery Actions
72
Page 81
Profile End Actions
Possible Profile End Actions:
A
At profile end, maintain the Final Setpoint value(s) of the last segment.
B At profile end, exit Profiler Mode and use
the Controller Setpoint value(s).
C At profile end, remain in Profiler Mode
with the Control outputs off.
Controller SP
Run (Start-on SP)
Normal Profile End
= Control Off
Last Profile SP
Controller SP
g
with the Control outputs off.
Once a running profile ends, that profiles’ Segment End Type defines the action taken by the instrument. If a sequence of profiles are joined together, the End Segment Type of the last profile in the sequence will be carried out when it completes. The end segment type is set in the final profile segment data.
The possible profile end actions are explained below.
Profile Abort Actions
If a running profile is forced to end early, the Profile Abort Action defines action taken by the instrument. The profile abort action is set in the profile header.
If a profile sequence is forced to end early, the profile abort action of the current segment will be used.
The possible abort options are explained below.
Run (Start-on SP)
Profile Aborted
Controller SP
Last Profile SP
Figure 56. Profile End Action
Note: When using two loop profiles, the end-action applies to both loops, but each ends with its own individual setpoint in line with the method chosen.
Controller SP
= Control Off
Possible Profile Abort Actions:
A
Abort the profile and maintain the value of the setpoint at the time of the abort.
B Abort the profile and exit Profiler Mode usin
the Controller Setpoint value.
C Abort the profile and remain in Profiler Mode
Figure 57. Profile Abort Action
Note: When using two loop profiles, the abort-ac­tion applies to both loops, but each ends with its own individual setpoint in line with the method cho­sen.
73
Page 82
17 USB Interface
The features in this section are available on models fit­ted with the optional USB Interface.
Using the USB Port
The USB Interface can be used to upload or download instrument settings to or from a USB memory stick (FAT32 formatted). Easy configuration of multiple in­struments is achieved by copying from one instrument to another, or by transferring data from the PC configu­ration software. If the Data Recorder or Profiler options are fitted, recordings and profile information can also be transferred via USB memory stick. Refer also to the USB menu.
USB Memory Stick Folders & Files
When a USB stick is inserted, the instrument looks for, and if necessary creates the DEVICE, CONFIG, PRO- FILE and RECORDER folders. Files must be located in these folders in order to be used by the instrument. When preparing to upload files from your PC, ensure that you save them to the correct folder on the memory stick.
If the file name already exists, data will be overwritten.
Note: To speed up the disk operation, keep the number of files in these folders to a minimum.
The first recorder log file is named 001-0001.csv. A new file is created with the first 3 digits incremented (e.g. 002-0001.csv; 003-0001.csv etc) each time the data being recorded is changed. The last 4 digits in­crement (e.g. 001-0002.csv; 001-0003.csv etc) if the file size reaches 65535 lines, if a recording is stopped then re-started or if there is a period of >10s without an alarm when recording from an alarm trigger.
Do not remove the memory stick during data transfer. Data corruption may result.
During data transfer, normal operations carry on in the background, but operator access is denied. Transfer of full memory can take up to 20 minutes. Only begin a transfer when access to the instrument (e.g. setpoint changes) will not be required.
DEVICE – This folder must be located in the Root of the USB memory stick
CONFIG – Configuration files (*.bct)
PROFILE – Profile program files (*.pfl)
RECORDER – Recorder log folders/files The
user is asked for a new recorder sub-folder name before transferring recorder data to USB. The instrument stores the log files (*.csv) in this folder.
74
Page 83
Manual
Input
18 Data Recorder
The optional Data Recorder allows the recording of pro­cess conditions to memory over time. It operates inde­pendently from the Trend Views. The recorder includes 1Mb of flash memory to store data when powered down and a real time clock (RTC) with a battery backup.
Servicing of the Data Recorder/RTC circuit and replacement of the internal lithium battery should be carried out by only a trained technician.
Recordable Values
A selection of values can be recorded for each control loop, from: Process Variable; Maximum or Minimum Process Values (since the previous sample); Setpoints; Primary Power, Secondary Power or Auxiliary Input values. Additionally the status of Alarms and Profiler Events can be recorded, as can when the unit is turned On/Off. See the Recorder Configuration sub-menu.
Sampling rates between 1 second and 30 minutes are possible, with the data either recorded until all memory is used, or with a continuous “First In/First Out” buffer overwriting the oldest data when full.
The recording capacity is dependent on sample rate and number of values recorded. For example: Two ana­logue values will recorded for 21 days at 30s intervals. More values or faster sample rates reduce the duration proportionally.
Note: If recorded, each alarm/event change forces an extra sample to be recorded, reducing the remaining recording time available. If these are likely to change often, take this into account when determining if there is sufficient memory available.
Recorder Control and Status
Options for starting/stopping recordings include Manually (from the recorder menu or a screen added to operation mode); a Digital Input; during a Running Profile; or Record on Alarm. See the Recorder Configuration sub-menu.
The recorder control menu allows the manual trigger to be started or stopped, as well as deleting recorded data from memory.
A status screen is shown with current information about the recorder, including if a recording is in progress (Re­cording or Stopped); the recording mode (FIFO or Record Until Memory Is Used); a % memory use bar-graph and the estimated available time remaining based on the data selected and memory used.
Recorder status and manual record trigger control can optionally be added to Operation Mode. This is enabled or disabled in the Display Configuration sub-menu.
Note: The recorder control screens allow the manual trigger to be started or stopped, but recording will continue as long as any trigger that has been config­ured is active.
Uploading Data
Recordings can be transferred to a memory stick using the USB Port. They can also be uploaded directly to the PC software via the configuration port or RS485/Ethernet communications if fitted.
The data is stored in Comma Separated format (.csv) which can be opened and analysed with the optional PC software or opened directly into a spreadsheet. Many third party software programs can also import data in the .csv format.
The file contains a header identifying the source instru­ments serial number, the date of the file upload and de­scriptions of the data columns.
The data columns seen depends on the data selected to record, but will always include the date and time of each sample. The date format follows the instrument date for­mat selection. Date(en) is dd/mm/yyyy, and Date (us) is mm/dd/yyyy.
Note: Analysis with the PC software is limited to 8 ana­logue channels, so only the first 8 will be displayed. The number of recorded alarms & events is not limited.
Additional Features & Benefits from the Recorder
The real time clock (RTC) included with the data recorder also expands the profiling capabilities (see Profiler) and allows a “calibration due” reminder to be shown at a specified date (see the Input Configuration sub-menu).
Record
These icons are displayed for each active recording trigger.
Digital
Profile Record
Alarm
Record
75
Page 84
PID Set 1
PID Set 2
PID Set 3
PID Set 4
PID Set 5
PV or SP
Scale Upper Limit
Scale Lower Limit
Breakpoints
19 Controller Tuning
PID Sets & Gain Scheduling
Up to 5 sets of PID tuning terms can be entered for each control loop, allowing the instrument to be pre-set for differing conditions. Each set has individual values for the following parameters: Primary Proportional Band; Secondary Proportional Band; On-Off Differential; Inte­gral Time; Derivative time; Overlap/Deadband. The pa­rameter values can be entered in the control configura­tion sub menu (page 50), but also see Automatic Tuning below for automatic tuning of the PID sets.
The PID sets might be configured for different applica­tions, or to allow for differing process or load conditions that might occur in a single application. In this case one set at a time would be selected as the “Active PID” set for that loop.
Alternatively, if the process conditions change signifi­cantly during use (e.g. if it is partially exothermic as the temperature rises) Gain Scheduling can be employed.
Gain scheduling ‘bumplessly’ switches PID sets auto­matically at successively higher setpoint or process val­ues, giving optimal control across a wide range of pro­cess conditions. This is explained in the diagram below.
PID set 1 is used from the scaled input lower limit until the “breakpoint” for set 2 is passed and that set be­comes active.
Set 2 is then used until the breakpoint for Set 3 is reached etc.
If any breakpoint is set to OFF, the subsequent PID sets are not used.
The final set continues from the last breakpoint to the scaled input upper limit.
Gain Scheduling breakpoints can be selected to switch PID sets with a change in the current setpoint value, or the current process value.
Note: ON/OFF control is possible with the individual PID sets but cannot be used with gain scheduling. On/ off control is replaced with the default proportional band if gain scheduling is turned on.
If the a change to the scale lower or upper limits forces any of the breakpoints out of bounds, all breakpoints will be turned off and the instruments uses the default PID set 1.
Automatic Tuning
To automatically optimize the controllers tuning terms for the process, you can use Pre-Tune, Self-Tune or Auto Pre-Tune independently for each control loop.
Note: Automatic tuning will not engage if either pro­portional band is set to On/Off control. Also, pre-tune (including an auto pre-tune attempt) will not engage if the setpoint is ramping, if a profile is running, or if the Process Variable is <5% of span from setpoint.
Pre-Tune
Pre-tune performs a single disturbance of the normal start-up pattern so that a good approximation of the ideal PID values can be made prior reaching setpoint. It automatically stops running when the test is complete. The user chooses which PID set the new tuning terms will be applied to, but this selection does not change the selected “active PID set”. This allows tuning of any PID set for future use before return to control with the current PID set.In VMD mode, derivative is not applied by pre-tune, and the controller is optimized for PI con­trol. In standard control mode, PI & D are all calculated, which may not suit all processes.
There are two pre-tune modes with different process test points. The first is “Standard Pre-Tune” which tests the process response half-way from the activation point (the process value when pre-tune began running) to the current setpoint. The second type is “Pre-Tune at Value” which allows the user to specify the exact point at which the process test will occur.
ELECTRIC SHOCK/FIRE HAZARD. Consider possible process over-shoot when selecting the value to tune at. If there is a risk of damage to the product or equipment select a safe value. Failure to follow these instructions could result in personal injury or equipment damage.
76
Page 85
During pre-tune, the controller outputs full primary
Pr
Setpoint (SP)
Temperature
Setpoint 1
Setpoint Change
Load Disturbance
Time
Setpoint 2
Start-up
power until the process reaches the specified test point. Power is then removed (full secondary power ap­plied for dual control), causing an oscillation which the
Process Variable (PV)
Initial PV
e-Tune
engaged
+100% Power (HEAT output)
here
pre-tune algorithm uses to calculate the proportional band(s), integral and derivative time. The pre-tune pro­cess is shown below.
Oscillation Peak
Pre-Tune Value set or
Test Point specified, or
for “standard” pre-
for Std Pre-Tune =
SP – Initial PV
2
tune
Control Power
-100% Power (Cool output)
Figure 58. Pre-Tune Operation
Pre-tune is selected from the automatic tuning menu. It will not engage if either primary or secondary outputs on a controller are set for On-Off control, during set­point/profile ramping or if the process variable is less than 5% of the input span from the setpoint.
Note: To pre-tune a cascade, first select “Cascade­Open” to tune the PID set(s) on the slave. After the slave has successfully tuned, remember to pre-tune the master/slave combination (this time select “Cas­cade-Closed”). The cascade remains open until you do this.
Auto Pre-Tune
As a single-shot operation, pre-tune will automatically disengage once complete, but can be configured to run at every power up using the auto pre-tune function. If auto pre-tune is selected, a Standard Pre-tune will attempt to run at every power up, applying new tun­ing terms to the current Active PID set. Auto pre-tune will not be able to test the process if at the time the controller is powered up, either primary or secondary outputs are set for On-Off control, during setpoint/pro­file ramping or if the process variable is less than 5% of the input span from the setpoint. Auto pre-tune is not possible with cascade control mode.
Self-Tune
If engaged, self-tune uses a pattern recognition algo­rithm to continuously monitor and adjust for control deviation. It optimizes the tuning by applying new PID terms to the current Active PID set while the control­ler is operating. In VMD control mode, derivative is not applied by self-tune, and the controller is optimized for PI control.
Figure 59. Self-Tune Operation
77
Page 86
The diagram shows a typical application involving a process start up, setpoint change and load distur­bance. In each case, self-tune observes one complete oscillation before calculating new terms. Successive deviations cause the values to be recalculated con­verging towards optimal control. When the controller is switched off, these terms are stored and used as starting values at switch on. The stored values may not always be ideal, if for instance the controller is new or the application has changed. In this case the user can use pre-tune to establish new initial values for self-tune to fine-tune.
Use of continuous self-tuning is not always appropri­ate. For example frequent artificial load disturbances, such as where an oven door is often left open for ex­tended periods, might lead to calculation errors. In standard control mode, PI & D are all calculated, which may not suit all processes. Self-Tune cannot be en­gaged if the instrument is set for on-off control or with cascade control mode.
Process Variable
Time
P = Peak-to-Peak variation of first cycle
T = Time period of oscillation (minutes)
Primary Proportional Band = P
Integral Time = T (minutes)
Dervitive Time = T/6
Figure 60. Manually Tuning -
PID with Primary Output
Manually Tuning
Tuning Control Loops - PID with Primary Output only
This technique balances the need to reach setpoint quickly, with the desire to limit setpoint overshoot at start-up or during process changes. It determines val­ues for the primary proportional band and the integral and derivative time constants that allow the controller to give acceptable results in most applications that use a single control device.
This technique is suitable only for processes that are not harmed by large fluctuations in the process variable.
1. Check that the scaled input limits and the setpoint limits are set to safe and appropriate levels for your process. Adjust if required.
2. Set the setpoint to the normal operating value for the process (or to a lower value if an overshoot be­yond this value might cause damage).
3. Select On-Off control (i.e. set the primary propor­tional band to zero).
4. Switch on the process. The process variable will rise above and then oscillate about the setpoint. Record the peak-to-peak variation (P) of the first cycle (i.e. the difference between the highest value of the first overshoot and the lowest value of the first under­shoot), and the time period of the oscillation (T) in minutes. See the diagram below.
5. Calculate the PID control parameters (primary pro­portional band, integral time and derivative time) us­ing the formulas shown.
6. Repeat steps 1-5 for the second control loop if re- quired.
Tuning Control Loops - PID with Primary & Secondary Outputs
This tuning technique balances the need to reach set­point quickly, with the desire to limit setpoint overshoot at start-up and during process changes. It determines values for the primary & secondary proportional bands, and the integral and derivative time constants that al­low the controller to give acceptable results in most applications using dual control (e.g. Heat & Cool).
These techniques are suitable only for pro­cesses that are not harmed by large fluctua­tions in the process variable.
Method 1 – For Simple Processes
Use this method if the process is simple/easily con­trolled and the relative power available from the prima­ry and secondary actuators is approximately symmetri­cal (e.g. if the maximum heating and cooling power is equal)
1. Tune the controller using only the Primary Control output as described in steps 1 to 5 of Manually Tun­ing - PID with Primary Output, above.
2. Set the Secondary Proportional Band to the same value as the Primary Proportional Band and monitor the operation of the controller in dual control mode.
3. If there is a tendency to oscillate as the control pass­es into the Secondary Proportional Band, increase its value. If the process appears to be over-damped (slow to respond) in the region of the secondary proportional band, decrease its value.
78
Page 87
4. When the PID tuning values have been determined,
Process Variable
Time
if there is a disturbance to the process variable as control passes from one proportional band to the other, set the Overlap/Deadband parameter to a positive value to introduce some overlap. Adjust this value by trial and error until satisfactory results are obtained.
Method 2 – For Asymmetrical Processes
Use this method if the relative power available from the primary and secondary actuators is not symmetri­cal (e.g. if the maximum cooling power is less than the maximum heating power)
1. Check that the scaled input limits and the setpoint limits of the loop in question are set to safe and ap­propriate levels for your process. Adjust if required.
2. Set the setpoint to the normal operating value for the process (or to a lower value if overshoots be­yond this value might cause damage).
3. Select On-Off control by setting the primary pro­portional band to zero (the secondary proportional band will automatically be set on-off control when you do this).
4. Switch on the process. The process variable will os­cillate about the setpoint. Record the peak-to-peak variation (V) of the oscillation (i.e. the difference be­tween the on-going overshoot and undershoot), the time period of the oscillation (T) in minutes and the maximum rate of rise (dP) and fall (dS) as the oscil­lation continues.
V = On-going Peak-to-Peak variation
T = Time period of oscillation (minutes)
dS = Maximum rate of rise
dP = Maximum rate of fall
R = Ratio dS/dP
Primary Proportional Band = Pb.P = V/R
Secondary proportional band = R x Pb.P
Integral Time = T minutes
Derivative Time = T/6
5. Calculate and enter the PID control parameters (pri-
mary proportional band, integral time and derivative time) using the formulas shown, and observe the process.
6. If symmetrical oscillation occurs, increase the pro­portional bands together, maintaining the same ra­tio. If the asymmetrical oscillation occurs, adjust the ratio between the bands until it becomes symmetri­cal, then increase the bands together, maintaining the new ratio.
7. When the PID tuning values have been determined, if there is a disturbance to the process variable as control passes from one proportional band to the other, set the Overlap/Deadband parameter to a small positive value to introduce some overlap. Ad­just this value by trial and error to find the minimum value that gives satisfactory results.
Valve, Damper & Speed Controller Tuning
This tuning method is used when controlling devices such as dampers, modulating valves or motor speed controllers. It applies equally to modulating valves with their own valve positioning circuitry, or in VMD mode where the instrument directly controls the valve motor– see Valve Motor Drive / 3-Point Stepping Control. It de- termines values for the primary proportional band, and integral time constant. The derivative time is normally set to OFF. This type of PI Control minimizes valve/mo­tor wear whilst giving optimal process control.
In VMD modem the Motor Travel Time and Minimum On Time must be correctly set to match the valve spec­ifications before attempting to tune the controller.
This technique is suitable only for processes that are not harmed by large fluctuations in the process variable.
1. Set the setpoint to the normal operating process value (or to a lower value if overshoot beyond this value is likely to cause damage).
2. Set the Primary Proportional Band a value approxi­mately equal to 0.5% of the input span for the loop to be tuned. (Span is the difference between the scaled input limits).
3. Set the Integral & Derivative time constants both to OFF.
4. Switch on the process. The process variable should oscillate about the setpoint.
5. Follow the instructions in the diagram below. At each stage, allow sufficient settling time before moving on to the next stage. P.Pb is the Primary Proportional Band, Int.T is the Integral Time Con­stant.
79
Page 88
START
Apply power to
the load
Process Variable
Does the
PV continuously
oscillate?
No
Note the time
interval T
Multiply
a
P.Pb
setting by 1.5
& Set
Int.T
= T
Tb
Time
Yes
Are the
Oscillations
decaying to
Yes
zero?
No
Note the period
a
Multiply
P.Pb
of the decaying
oscillations (T
b
)
setting by 1.5
Multiply P.Pb
setting by 1.5 &
Set
Int.T =
Tb
2
Process Variable
END
The controller is now tuned. Fine-tuning may be required
to optimize the controllers’
response
Ta
Time
This method can also be used to tune PID loops. Set Derivative to approx. Ta / 4
Figure 61. Manually Tuning – PI Control
80
Page 89
Fine Tuning
Proportional Cycle Times
Too Long: Oscillation period = cycle time.
Proportional Bands
Too Wide:
Integral Time
Too Long: Slow warm up and response
Small adjustments can be made to correct minor con­trol problems. These examples assume reverse acting control (e.g. heating). Adjust accordingly for direct ac­tion. If they do not help solve the problem, re-tune the controller as detailed on the preceding sections.
Note: When fine tuning the settings, only adjust one parameter at a time, and allow enough time for the process to settle into its new state each time you change a value.
Cycle Times
A separate cycle time adjustment parameter is provid­ed for the Primary and Secondary control when using time-proportioning control outputs.
If the process oscillates at the same frequency as the cycle time, it indicates it may be too long for the pro­cess. Decrease the cycle time and re-check the period of oscillation, if it has changed to match the new cycle time this confirms that the time is too long.
If the control actuators will accept it, continue reducing the cycle time until the process stabilizes, or no further improvement is seem. Recommended times. Relays
10 seconds. SSR Driver 1 second.
Proportional Bands
Increase the width of the proportional bands if the pro­cess overshoots or oscillates excessively. Decrease the width of the proportional band if the process re­sponds slowly or fails to reach setpoint.
Too Narrow: Process Oscillates
Ideal: Stable Process
Note: Adjusting the cycle time affects the controllers operation; a shorter cycle time gives more accurate control, but mechanical control actuators such as re­lays will have a reduced life span.
Slow warm up and response
Integral Time Constant
To find the optimum integral time, decrease its value until the process becomes unstable, then increase it a little at a time, until stability has is restored. Induce a load disturbance or make a setpoint change to verify that the process stabilizes. If not increase the value some more and re-test. If the response is too slow, de­crease the integral time, but avoid instability.
Too Short: Overshoots and oscillates
81
Page 90
Derivative Time Constant
Derivative Time
Too Short
disturbance
response under-corrects
Anti Wind -up
Too Smal
setpoint before
above/below setpoint
Manual Reset
Too High
Too Low: Slow to setpoint
Initially set the derivative to between 1/4th and 1/10th of the Integral time value. Increase the derivative time if the process overshoots/undershoots. Increase it a little at a time, but if the process becomes unstable, decrease it until the oscillation stops. Induce a load disturbance or make a setpoint change to verify that the process stabilizes. If not decrease the value some more and re-test.
l: Overshoots
settling
Process Disturbance
Too Long: Oscillates and over corrects
when process disturbed
Process Disturbance
: Slow warm up and
Note: When controlling a modulating valve, it is usually recommended that derivative is set to OFF to avoid excessive valve activity. Derivative can cause process instability in these processes.
Anti Wind-up
If after fully optimising the tuning, there is an overshoot of the setpoint at start-up or in response to large set­point changes, the reset wind-up inhibit point can be reduced to suspend integral action until the process is closer to setpoint. If set too low control deviation can occur (the process settles, but is offset above or below the setpoint). It this is observed, increase the value until the deviation error is removed.
Too Short: Slow to setpoint or offset
Manual Reset
For proportional only control, after making all other adjustments, if a positive control deviation error exists (process is offset above the setpoint) reduce the man­ual reset until the error is eliminated. If there is a nega­tive error (process is offset below the setpoint) increase manual reset until the error is eliminated.
For PID or PI control, typically set manual reset to ap­proximately 80% of power needed to maintain set­point, but lower values can be used to inhibit start-up overshoot if required.
: Overshoots setpoint at start-up
82
Page 91
MODBUS
20 Serial Communications
Supported Protocols
Communication with a Modbus RTU or Modbus TCP master device is possible if the appropriate commu­nications module is fitted in option slot A. An RS485 Module is required for Modbus RTU. An Ethernet Mod­ule is required for Modbus TCP. The instrument can also act as “setpoint master” over RS485 for multi-zone applications. In this mode the unit continuously sends its setpoint value using Modbus broadcast messages. Master mode is not available with Ethernet module.
To protect the EEPROM from excessive write opera­tions, the 6 most recent parameter write requests are held in standard RAM. All data is written to EEPROM at power-down or if another parameter is changed. Avoid continuously changing more than 6 parameters.
All models also have a configuration socket for bench setup via the PC configuration software prior to in­stallation. An RS232 to TTL lead (available from your supplier) is required in order to use this socket. A front mounted USB port is available on some models; this can also be used to configure the instrument or to transfer recorder or profile files via a USB memory stick.
RS485 Configuration
The RS485 address, bit rate and character format are configured via the front panel from the Comms Con­figuration sub-menu or by using the PC Configurator software.
Data rate: 4800, 9600, 19200, 38400, 57600 or 115200 bps
Parity: None (default), Even, Odd
Character format: Always 8 bits per character.
Device Address: See below.
Ethernet Configuration
For Modbus TCP communications (Modbus over Eth­ernet), the Ethernet IP address can either be assigned by a Dynamic Host Configuration Protocol (DHCP), BootP or AutoIP server on the network, or manually as­signed using the IP address allocation software tool. Refer to the PC Software section of this manual on page 235 for more information about setting the IP ad­dress. The supported data rates 10/100BASE-T (10 or 100 Mbps) are automatically detected.
Link Layer
A query (data request or command) is transmitted from the Modbus Master to the Modbus Slave. The slave instrument assembles the reply to the master. This in­strument is normally a slave device. It can only act as a master when being use as setpoint master controller to broadcast its setpoint to other controllers in a multi­zone application.
SLAVE
MASTER
QUERY
RESPONSE
INSTRUMENT
RS485 Device Addressing
The instrument must be assigned a unique device ad­dress in the range 1 to 255. This address is used to rec­ognize Modbus queries intended for this instrument. With the exception of globally addressed broadcast messages, the instrument ignores Modbus queries that do not match the address that has been assigned to it.
The instrument will accept broadcast messages (global queries) using device address 0 no matter what device address is assigned to it. No response messages are returned for globally addressed queries.
Figure 62. Modbus Link Layer
A message for either a QUERY or RESPONSE is made up of an inter-message gap followed by a sequence of data characters. The inter-message gap is at least
3.5 data character times - the transmitter must not
start transmission until 3 character times have elapsed since reception of the last character in a message, and must release the transmission line within 3 character times of the last character in a message.
Note:Three character times is approximately 0.25ms at 115200 bps, 0.51ms at 57600 bps, 0.75ms at 38400 bps, 1.5ms at 19200 bps, 3ms at 9600 bps and 6ms at 4800bps.
83
Page 92
Data is encoded for each character as binary data, transmitted LSB first.
For a QUERY the address field contains the address of the slave destination. The slave address is given to­gether with the Function and Data fields by the Appli­cation layer. The CRC is generated from the address, function and data characters.
For a RESPONSE the address field contains the ad­dress of the responding slave. The Function and Data fields are generated by the slave application. The CRC is generated from the address, function and data char­acters.
The standard MODBUS RTU CRC-16 calculation em­ploying the polynomial 216+215+22+1 is used.
Supported Modbus Functions
The following Modbus function types are supported by this instrument:
Function
Code
03 / 04 Read
06 Write Single
Modbus
Meaning Description
Read current binary Holding/Input registers
value of specified num-
ber of parameters at
given address. Up to 64
parameters can be ac-
cessed with one query.
Writes two bytes to a Register
specified word address.
Inter-
message
Gap
Address 1 Character
Function 1
Character
Data n
Characters
CRC
Check 2
Characters
08 Diagnostics Used for loopback test
16
(0x10 hex)
23
(0x17 hex) Read/Write
Function Descriptions
The following is interpreted from the Modbus protocol description obtainable from www.modbus.org. Refer to that document if clarification is required. In the func­tion descriptions below, the preceding device address
value is assumed, as is the correctly formed two-byte CRC value at the end of the QUERY and RESPONSE frames.
Function 03 / 04 - Read Holding/Input Registers
Reads current binary value of data at the specified word addresses.
QUERY: Function 03 / 04 - Read Holding/Input Registers
Func
Code
03/04 LO LO HI LO
Address of
First Word
Number of
Words
Write Multiple Registers
Multiple Registers
only.
Writes up to 253 bytes
of data to the specified
address range.
Reads and Writes
253 bytes of data to
the specified address
ranges.
QUERY: Function 03 / 04 - Read Holding/Input Registers
Func
Code
Bty
Code 1st Word Etc. Last Word
03/04 XX HI LO g HI LO
Note: In the response the “Number of Bytes” indicates the number of data bytes read from the instrument. E.g. if 5 words are read, the count will be 10 (0xA hex). The maximum number of words that can be read is
64. If a parameter does not exist at one of the addresses read, a value of 0000h is returned for that word.
84
Page 93
Function 06 - Write Single Register
Reads current binary value of data at the specified word addresses.
QUERY: Function 06 - Write Single Register
Func
Code
QUERY: Function 06 - Write Single Register
Func
Code
Note: The Response normally returns the same data as the query.
Address of
Word
06 HI LO HI LO
Address of
Word
06 HI LO HI LO
Value to
Write
Value
Written
Function 08 - Loopback Diagnostic Test
QUERY: Function 08 - Loopback Diagnostic Test
Func
Code
Diagnostic
Code Value
08 00 00 HI LO
QUERY: Function 08 - Loopback Diagnostic Test
Func
Code
08 00 00 HI LO
Note: The Response normally returns the same data as the loopback query. Other diagnostic codes are not supported.
Sub
Function Value
Function 16 - Write Multiple Registers (0x10 Hex)
QUERY: Function 16 - Write Multiple Registers (0x10 Hex)
Func
Code
10 HI LO HI LO XX HI LO g HI LO
QUERY: Function 16 - Write Multiple Registers (0x10 Hex)
Func
Code 1st Word Last Word
10 HI LO HI LO
1st Write
Address
Number of
Words
Byte
Count 1st Word etc Last Word
Note: The maximum number of data bytes that can be written in one message is 253 bytes.
85
Page 94
Function 23 Hex - Read / Write Multiple Registers (0x17 hex)
Reads and writes the requested number of consecutive words (two-bytes) starting at the specified addresses.
QUERY: Function 23 Hex - Read / Write Multiple Registers (0x17 hex)
Func
Code
17 HI LO HI LO HI LO HI LO XX HI LO g HI LO
QUERY: Function 23 Hex - Read / Write Multiple Registers (0x17 hex)
Func
Code
17 XX HI LO
Note: The maximum number of data bytes that can be read and written in one message is 253 bytes.
1st Read
Address
Byte
Count 1st Word etc Last Word
Number of
Words
1st Write
Address
g
HI LO
Number of
Write Words
Byte
Count
1st Word etc Last Word
Values to Write
Exception Responses
If a QUERY is sent without a communication error, but the instrument cannot interpret it, an Exception RESPONSE is returned. The exception response consists of a modified version of the original function code and an exception code that explains what was wrong with the message. Possible exception responses and their reasons are:
Exception
Function Code
The original function code with its most significant bit (MSB) set.
This offsets it by 0x80, so for example 0x06 becomes 0x86.
Note: In the case of multiple exception codes for a single query, the Exception code returned is the one corresponding to the first parameter in error.
Code
00 Unused None
01 Illegal
02 Illegal Data
03 Illegal Data
Modbus Parameters
The register addresses for the Modbus parameters are detailed in the tables below. The Access column indi­cates if a parameter is read only (RO) or if it can also be written to (R/W). Communications writes will not be implemented if the Writing Via Serial Comms param­eter in the Communications Configuration sub-menu is set to Disabled.
Data Formats
Data can be accessed in three formats: Integer Only (decimal places are not included), Integer with 1 Deci­mal Place (only the first decimal place value is includ-
Modbus Meaning Description
Function number is out of range.
Function
Write functions: Parameter number is out of range
Address
Value
or not supported. (for write functions only). Read Functions: Start parameter does not exist or the end parameter greater than 65536.
Attempt to write invalid data / required action not executed.
ed) or an IEEE / Motorola (big endian) Floating Point Number. Where possible use floating point numbers especially if the values have more than one decimal place.
Note: Read only parameters will return an excep­tion if an attempt is made to write values to them. Some parameters that do not apply for a particu­lar configuration will still accept read / writes (e.g. attempting to scale a linear output which has not been fitted).
86
Page 95
Parameter Register Address Listings
Calculating Parameter Register Addresses
Integer Only Integer +1 Floating Point
Register Address Calculation (hex) Address Address + 0x4000 Address x 2 + 0x8000
(dec) Address Address + 16384 Address x 2 + 32768
Address Example:
(For Loop 1 Process Variable)
Data Value Returned: If actual Value = 23.9 decimal
(hex) 0x0407 0x4407 0x880E
(dec) 1031 17415 34830
(hex) 0x00, 0x17 0x00, 0xEF 0x41, 0xBF, 0x33, 0x33
(dec) 23 239 23.9 as floating decimal
The register address offset calculations are shown above.
For your convenience, the parameter tables on the fol­lowing pages show each parameter’s Modbus register address as a decimal and hexadecimal number for all three formats. The tables also show if the parameter has read-only (RO) or read-write (RW) access.
Analog parameter values and their limits are expressed as decimals.
Bit parameters list the bit positions and their meaning (bit 0 = LSB). Only bits that have a function are listed, unused bits are omitted.
Calibration Reminder Parameters
Parameter Name & Register Address
Integer Int +1 Float Access Values & Description
Calibration Reminder Enable Value Calibration Reminder Status
Dec 1048 17432 34864
Hex 0418 4418 8830
Calibration Reminder Date Value Calibration Reminder Status
Dec n/a n/a 34866
Hex n/a n/a 8832
RW
RW
0 Disabled
1 Enabled
This can be entered only as a floating point number.
When converted to binary the least significant 19 bits represents
the date in this format:
www DDDDD MMMM YYYYYYY
YYYYYYY = YEAR
MMMM = MONTH
DDDDD = DAY OF MONTH (1-31 but must be valid)
www = Day of the week The day of week portion
is calculated from the date (Read Only).
Example with date set to 31/07/2012
Day (31) = 11111
Month (7) = 0111
Year (12) = 0001100
Bits 17 and higher are ignored when writing so 11111 0111 0001100 (64396 decimal) is just one of many possible numbers
to write as 31/07/2012, and when reading the date back, the number returned is
10 11111 0111 0001100 (195468 decimal) because bits 17-19
are 010 (to represent “Tuesday”).
87
Page 96
Universal Process Input 1 Parameters
Parameter Name & Register Address
Integer Int +1 Float Access Values Description
Universal Process Input 1 Type Value Calibration Reminder Status
Dec 1024 17408 34816
Hex 0400 4400 8800
Input 1 Engineering Units Value Engineering Units For Display
Dec 1025 17409 34818
Hex 0401 4401 8802
Input 1 Maximum Display Decimal Places Value Maximum Number of Decimal Places In Display
Dec 1026 17410 34820
Hex 0402 4402 8804
RW
RW
RW
0 2 4 6
8 10 12 14 16 18 20 22 24 26 28 29 30 31 32 33 34 35 36
0
1
2
3
4
5
6
7
8
0
1
2
3
B Type Thermocouple C Type Thermocouple D Type Thermocouple E Type Thermocouple J Type Thermocouple K Type Thermocouple L Type Thermocouple N Type Thermocouple R Type Thermocouple S Type Thermocouple T Type Thermocouple PtRh 20%: 40% Thermocouple PT100 RTD NI120 RTD 0 to 20mA DC 4 to 20mA DC 0 to 50mV DC 10 to 50mV DC 0 to 5V DC 1 to 5V DC 0 to 10V DC 2 to 10V DC Potentiometer
= None = °C (Default for Europe) = °F (Default for USA) = °K = Bar = pH = % = %RH = PSI
= None (e.g. 1234) = One (e.g. 123.4) = Two (e.g. 12.34) = Three (e.g. 1.234)
Input 1 Scaled Input Lower Limit Scaling Value Low Limit
Dec 1027 17411 34822
Hex 0403 4403 8806
Input 1 Scaled Input Upper Limit Scaling Value High Limit
Dec 1028 17412 34824
Hex 0404 4404 8808
Input 1 Process Variable Offset Single Point Calibration PV Offset
Dec 1029 17413 34826
Hex 0405 4405 880A
RW
RW
RW
Valid between input 1 range maximum and minimum
(see Specifications section for input details)
Valid between input 1 range maximum and minimum
(see Specifications section for input details)
Used for Single Point Calibration of input 1 Valid
between the scaled input lower & upper limits
88
Page 97
Input 1 Filter Time Constant Input 1 Process Input Filter Time
Dec 1030 17414 34828
Hex 0406 4406 880C
RW
Valid between 0.0 and 512.0
Input 1 Process Variable Process Input 1 Value
Dec 1031 17415 34830
Hex 0407 4407 880E
RO
The current input 1 process value
Input 1 Signal /Sensor Break Flag Value Process Input Break Status
Dec 1032 17416 34832
Hex 0408 4408 8810
RO
0
Inactive
1
Active (break detected)
Input 1 Signal Under Range Flag Value Process Input Under Range Status
Dec 1033 17417 34834
Hex 0409 4409 8812
RO
0
Inactive
1
Active (under-range detected)
Input 1 Signal Over Range Flag Value Process Input Over Range Status
Dec 1034 17418 34836
Hex 040A 440A 8814
RO
0
Inactive
1
Active (over-range detected)
Input 1 Cold Junction Compensation Value CJC Status
Dec 1035 17419 34838
Hex 040B 440B 8816
RW
0
Disabled
1
Enabled (default)
Input 1 Multi-Point Scaling Enable Value Multi-Point Scaling Status
Dec 1053 17437 34874
Hex 041D 441D 883A
RW
0
Disabled
1
Enabled (valid only if the input type is linear)
Input 1 Scale Point 1 Multi-Point Scaling Point 1
Dec 1054 17438 34876
RW
Percentage of the scaled input where multi-point scaling value 1 is applied. 0.1 to 100.0% *set to 100% ends scaling sequence at that point.Hex 041E 441E 883C
Input 1 Display Point 1 Multi-Point Scaling Display Value For Point 1
Dec 1055 17439 34878
Hex 041F 441F 883E
RW
Value to display at multi-point scaling point. 1 Valid between the scaled input lower & upper limits.
Input 1 Scale Point 2 Multi-Point Scaling Point 2
Dec 1056 17440 34880
RW
Percentage of the scaled input where multi-point scaling value 2 is applied. 0.1 to 100.0% *set to 100% ends scaling sequence at that pointHex 0420 4420 8840
Input 1 Display Point 2 Multi-Point Scaling Display Value For Point 2
Dec 1057 17441 34882
Hex 0421 4421 8842
RW
Value to display at multi-point scaling point 2. Valid between the scaled input lower & upper limits.
Input 1 Scale Point 3 Multi-Point Scaling Point 3
Dec 1058 17442 34884
RW
Percentage of the scaled input where multi-point scaling value 3 is applied. 0.1 to 100.0% *set to 100% ends scaling sequence at that pointHex 0422 4422 8844
Input 1 Display Point 3 Multi-Point Scaling Display Value For Point 3
Dec 1059 17443 34886
Hex 0423 4423 8846
RW
Value to display at multi-point scaling point 3. Valid between the scaled input lower & upper limits.
89
Page 98
Input 1 Scale Point 4 Multi-Point Scaling Point 4
Dec 1060 17444 34888
RW
Percentage of the scaled input where multi-point scaling value 4 is applied. 0.1 to 100.0% *set to 100% ends scaling sequence at that point.Hex 0424 4424 8848
Input 1 Display Point 4 Multi-Point Scaling Display Value For Point 4
Dec 1061 17445 34890
Hex 0425 4425 884A
RW
Value to display at multi-point scaling point 4. Valid between the scaled input lower & upper limits.
Input 1 Scale Point 5 Multi-Point Scaling Point 5
Dec 1062 17446 34892
RW
Percentage of the scaled input where multi-point scaling value 5 is applied. 0.1 to 100.0% *set to 100% ends scaling sequence at that point.Hex 0426 4426 884C
Input 1 Display Point 5 Multi-Point Scaling Display Value For Point 5
Dec 1063 17447 34894
Hex 0427 4427 884E
RW
Value to display at multi-point scaling point 5. Valid between the scaled input lower & upper limits.
Input 1 Scale Point 6 Multi-Point Scaling Point 6
Dec 1064 17448 34896
RW
Percentage of the scaled input where multi-point scaling value 6 is applied. 0.1 to 100.0% *set to 100% ends scaling sequence at that point.Hex 0428 4428 8850
Input 1 Display Point 6 Multi-Point Scaling Display Value For Point 6
Dec 1065 17449 34898
Hex 0429 4429 8852
RW
Value to display at multi-point scaling point 6. Valid between the scaled input lower & upper limits.
Input 1 Scale Point 7 Multi-Point Scaling Point 7
Dec 1066 17450 34900
RW
Percentage of the scaled input where multi-point scaling value 7 is applied. 0.1 to 100.0% *set to 100% ends scaling sequence at that point.Hex 042A 442A 8854
Input 1 Display Point 7 Multi-Point Scaling Display Value For Point 7
Dec 1067 17451 34902
Hex 042B 442B 8856
RW
Value to display at multi-point scaling point 7. Valid between the scaled input lower & upper limits.
Input 1 Scale Point 8 Multi-Point Scaling Point 8
Dec 1068 17452 34904
RW
Percentage of the scaled input where multi-point scaling value 8 is applied. 0.1 to 100.0% *set to 100% ends scaling sequence at that point.Hex 042C 442C 8858
Input 1 Display Point 8 Multi-Point Scaling Display Value For Point 8
Dec 1069 17453 34906
Hex 042D 442D 885A
RW
Value to display at multi-point scaling point 8. Valid between the scaled input lower & upper limits.
Input 1 Scale Point 9 Multi-Point Scaling Point 9
Dec 1070 17454 34908
RW
Percentage of the scaled input where multi-point scaling value 9 is applied. 0.1 to 100.0% *set to 100% ends scaling sequence at that point.Hex 042E 442E 885C
Input 1 Display Point 9 Multi-Point Scaling Display Value For Point 9
Dec 1071 17455 34910
Hex 042F 442F 885E
RW
Value to display at multi-point scaling point 9. Valid between the scaled input lower & upper limits.
90
Page 99
Input 1 Scale Point 10 Multi-Point Scaling Point 10
Dec 1072 17456 34912
RW
Percentage of the scaled input where multi-point scaling value 10 is applied. 0.1 to 100.0% *set to 100% ends scaling se­quence at that point.Hex 0430 4430 8860
Input 1 Display Point 10 Multi-Point Scaling Display Value For Point 10
Dec 1073 17457 34914
Hex 0431 4431 8862
RW
Value to display at multi-point scaling point 10. Valid between the scaled input lower & upper limits.
Input 1 Scale Point 11 Multi-Point Scaling Point 11
Dec 1074 17458 34916
RW
Percentage of the scaled input where multi-point scaling value 11 is applied. 0.1 to 100.0% *set to 100% ends scaling se­quence at that point.Hex 0432 4432 8864
Input 1 Display Point 11 Multi-Point Scaling Display Value For Point 11
Dec 1075 17459 34918
Hex 0433 4433 8866
RW
Value to display at multi-point scaling point 11. Valid between the scaled input lower & upper limits.
Input 1 Scale Point 12 Multi-Point Scaling Point 12
Dec 1076 17460 34920
RW
Percentage of the scaled input where multi-point scaling value 12 is applied. 0.1 to 100.0% *set to 100% ends scaling se­quence at that point.Hex 0434 4434 8868
Input 1 Display Point 12 Multi-Point Scaling Display Value For Point 12
Dec 1077 17461 34922
Hex 0435 4435 886A
RW
Value to display at multi-point scaling point 12. Valid between the scaled input lower & upper limits.
Input 1 Scale Point 13 Multi-Point Scaling Point 13
Dec 1078 17462 34924
RW
Percentage of the scaled input where multi-point scaling value 13 is applied. 0.1 to 100.0% *set to 100% ends scaling se­quence at that point.Hex 0436 4436 886C
Input 1 Display Point 13 Multi-Point Scaling Display Value For Point 13
Dec 1079 17462 34926
Hex 0437 4437 886E
RW
Value to display at multi-point scaling point 13. Valid between the scaled input lower & upper limits.
Input 1 Scale Point 14 Multi-Point Scaling Point 14
Dec 1080 17464 34928
RW
Percentage of the scaled input where multi-point scaling value 14 is applied. 0.1 to 100.0% *set to 100% ends scaling se­quence at that point.Hex 0438 4438 8870
Input 1 Display Point 14 Multi-Point Scaling Display Value For Point 14
Dec 1081 17465 34930
Hex 0439 4439 8872
RW
Value to display at multi-point scaling point 14. Valid between the scaled input lower & upper limits.
Input 1 Scale Point 15 Multi-Point Scaling Point 15
Dec 1082 17466 34932
RW
Percentage of the scaled input where multi-point scaling value 15 is applied. 0.1 to 100.0% *set to 100% ends scaling se­quence at that point.Hex 043A 443A 8874
Input 1 Display Point 15 Multi-Point Scaling Display Value For Point 15
Dec 1083 17467 34934
Hex 043B 443B 8876
RW
Value to display at multi-point scaling point 15. Valid between the scaled input lower & upper limits.
91
Page 100
User Calibration Type Value Calibration Type
Dec 1085 17469 34938
Hex 043D 443D 887A
User Calibration Point - Low Value Two Point Calibration Low Point
Dec 1086 17470 34940
Hex 043E 443E 887C
User Calibration Point - Low Offset Two Point Calibration Low Offset Value
Dec 1087 17471 34942
Hex 043F 443F 887E
User Calibration Point - High Value Two Point Calibration High Point
Dec 1088 17472 34944
Hex 0440 4440 8880
User Calibration Point - High Offset Two Point Calibration High Offset Value
Dec 1089 17473 34946
Hex 0441 4441 8882
RW
RW
RW
RW
RW
0
None (input 1 base calibration used)
1
Single Point Calibration
2
Two Point Calibration
The input value at which the Low Offset will be applied. Valid between input 1 scaled input lower & upper limits.
The Low Offset value applied to the reading at the Low Calibra­tion Point 0.0 to 100.0%.
The input value at which the High Offset will be applied Valid between input 1 scaled input lower & upper limits.
The High Offset value applied to the reading at the High Calibra­tion Point 0.0 to 100.0%.
Universal Process Input 2 Parameters
Parameter Name & Register Address
Integer Int +1 Float Access Values & Description
Universal Input 2 Usage Value Process Input Type
Dec 1166 17550 35100
Hex 048E 448E 891C
Universal Process Input 2 Type Value Process Input Type
Dec 1100 17484 34968
Hex 044C 444C 8898
RW
RW
0 Standard
1 Feedback signal for Input 1
2 Redundant Sensor
(backup for Input 1 Thermocouple or RTD)
3 Not Used (or Indication only)
0 B Type Thermocouple
2 C Type Thermocouple
4 D Type Thermocouple
6 E Type Thermocouple
8 J Type Thermocouple
10 K Type Thermocouple
12 L Type Thermocouple
14 N Type Thermocouple
16 R Type Thermocouple
18 S Type Thermocouple
20 T Type Thermocouple
22 PtRh 20%: 40% Thermocouple
24 PT100 RTD
26 NI120 RTD
28 0 to 20mA DC
29 4 to 20mA DC
92
Loading...