New equipment manufactured by seller or service supplied by
seller is warranted to be free from defects and workmanship
under normal use and service for a minimum of twenty-four (24)
months from date of installation, thirty (30) months from date of
shipment, unless otherwise stated in product warranty guide
(available upon request). In the case of spare or replacement
parts manufactured by seller, the warranty period shall be for a
period of twelve months from shipment.
Sellers obligation under this warranty is limited to repairing or
replacing, at its option, any part found to its satisfaction to be so
defective, provided that such part is, upon request, returned to
seller’s factory from which it was shipped, transportation prepaid.
Parts replaced under warranty shall be warranted for twelve
months from the date of the repair, not to exceed the original
warranty period. This warranty does not cover parts damaged by
decomposition from chemical action or wear caused by abrasive
materials, nor does it cover damage resulting from misuse,
accident, neglect, or from improper operation, maintenance,
installation, modification, or adjustment. This warranty does not
cover parts repaired outside seller’s factory without prior written
approval. Seller makes no warranty as to starting equipment,
electrical apparatus or other material not of its manufacture. If
purchaser or others repair, replace, or adjust equipment or parts
without sellers prior written approval, seller is relieved of any
further obligation to purchaser under this paragraph with respect
to such equipment or parts, unless such repair, replacement, or
adjustment was made after seller failed to satisfy within a
reasonable amount of time seller’s obligations under this
paragraph. Sellers liability for breach of these warranties (or for
breach of any other warranties found by a court of competent
jurisdiction to have been given by seller) shall be limited to: (A)
accepting return of such equipment EXW plant of manufacture
and (B) refunding any amount paid thereon by purchaser (less
depreciation at the rate of 15 % per year if purchaser has used
equipment for more than thirty [30] days), and cancelling any
balance still owing on the equipment or (C) in the case of service,
at the sellers option, redoing the service, or refunding the
purchase order amount of the service or portion thereof upon
which such liability is based. These warranties are expressly in
lieu of any other warranties, express or implied, and seller
specifically disclaims any implied warranty of merchantability or
fitness for a particular purpose, and in lieu of any other obligation
or liability on the part of the seller whether a claim is based upon
negligence, breach of warranty, or any other theory or cause of
action. In no event shall seller be liable for any consequential,
incidental, indirect, special or punitive damages of any kind. For
purposes of this paragraph, the equipment warranted shall not
include equipment, parts, and work not manufactured or
performed by seller. With respect to such equipment, parts, or
work, seller’s only obligation shall be to assign to purchaser the
warranties provided to seller by the manufacturer or supplier
providing such equipment, parts or work. No equipment furnished
by seller shall be deemed to be defective by reason of normal
wear and tear, failure to resist erosive or corrosive action of any
fluid or gas, purchaser’s failure to properly store, install, operate,
or maintain the equipment in accordance wtih good industry
practices or specific recommendations of seller, including, but not
limited to seller’s installation and operation manuals, or
purchaser’s failure to provide complete and accurate information
to seller concerning the operational application of the equipment.
2. General information
These installation and operating instructions are a supplement to
the installation and operating instructions for the corresponding
standard pumps LCS and VLS. For instructions not mentioned
specifically in this manual, see the installation and operating
instructions for the standard pump.
2.1 Hazard statements
The symbols and hazard statements below may appear in
Grundfos installation and operating instructions, safety
instructions and service instructions.
DANGER
Indicates a hazardous situation which, if not avoided,
will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate personal injury.
The hazard statements are structured in the following way:
SIGNAL WORD
Description of hazard
Consequence of ignoring the warning.
- Action to avoid the hazard.
English (US)
3
English (US)
2.2 Notes
The symbols and notes below may appear in Grundfos
installation and operating instructions, safety instructions and
service instructions.
Observe these instructions for explosion-proof
products.
A blue or grey circle with a white graphical symbol
indicates that an action must be taken.
A red or grey circle with a diagonal bar, possibly with
a black graphical symbol, indicates that an action
must not be taken or must be stopped.
If these instructions are not observed, it may result in
malfunction or damage to the equipment.
Tips and advice that make the work easier.
2.3 Abbreviations and definitions
AIAnalog input.
ALAlarm, out of range at lower limit.
AOAnalog output.
AUAlarm, out of range at upper limit.
CIMCommunication interface module.
The ability to draw current into the terminal and
guide it towards GND in the internal circuitry.
The ability to push current out of the terminal
and into an external load which must return it
to GND.
Grundfos Digital Sensor.
Factory-fitted sensor in some Grundfos pumps.
Ground fault circuit interrupter.
(USA and Canada).
Low voltage with the risk of electric shock if the
terminals are touched.
Open collector:
Configurable open-collector output.
Protective extra-low voltage.
A voltage that cannot exceed ELV under
normal conditions and under single-fault
conditions, except earth (ground) faults in
other circuits.
Safety extra-low voltage.
A voltage that cannot exceed ELV under
normal conditions and under single-fault
conditions, including earth (ground) faults in
other circuits.
4
3. Receiving the product
D
4.1.2 Mounting
3.1 Transporting the product
WARNING
Falling objects
Death or serious personal injury
- Secure the product during transportation to prevent
it from tilting or falling down.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes when moving the product.
• Motors from 3 to 5 Hp (2.2 to 5.5 kW): Do not stack more than
two motors in their original packaging.
• Motors from 7.5 to 15 Hp (5.5 to 11 kW): Do not stack the
motors.
3.2 Inspecting the product
Before you install the product, do the following:
1. Check that the product is as ordered.
2. Check that no visible parts have been damaged.
3. If parts are damaged or missing, contact your local Grundfos
sales company.
4. Installing the product
4.1 Mechanical installation
4.1.1 Handling the product
Observe local regulations setting limits for manual lifting or
handling. The motor weight is stated on the nameplate.
CAUTION
Back injury
Minor or moderate personal injury
- Use lifting equipment.
CAUTION
Crushing of feet
Minor or moderate personal injury
- Secure the product to a solid foundation by bolts
through the holes in the flange or the base plate.
In order to maintain the UL mark, additional
requirements apply to the equipment. See Appendix,
page 66.
4.1.3 Cable entries
See the size of the cable entries in section 10.6 Other technical
data.
4.1.4 Cable glands
The number and size of cable glands delivered with the pump
depends on the motor size. See section 10.6 Other technical
data.
4.1.5 Ensuring motor cooling
Leave at least 2 in. (50 mm) between the end of the fan cover and
a wall or other fixed objects. See fig. 1.
Fig. 1 Minimum distance (D) from the motor to a wall or other
fixed objects
English (US)
TM05 5236 3512
CAUTION
Crushing of feet
Minor or moderate personal injury
- Wear safety shoes and attach lifting equipment to
the motor eyebolts when handling the product.
Do not lift the product by the terminal box.
5
English (US)
B3B14B5
4.1.6 Outdoor installation
The enclosure class of MLE motor is a NEMA 3 rating. If you
install the motor outdoors, provide the motor with a suitable cover
and open the drain holes to avoid condensation on the electronic
components. See figs 2 and 3.
When fitting a cover to the motor, observe the
guideline in section 4.1.5 Ensuring motor cooling.
The cover must be sufficiently large to ensure that the motor is
not exposed to direct sunlight, rain or snow. Grundfos does not
supply covers. We therefore recommend that you have a cover
built for the specific application. In areas with high humidity, we
recommend that you enable the built-in standstill heating
function. See section 7.21 "Standstill heating".
Fig. 2 Examples of covers (not supplied by Grundfos)
In order to maintain the UL mark, additional
requirements apply to the equipment. See Appendix,
page 66.
4.1.7 Drain holes
When the motor is installed in moist surroundings or areas with
high humidity, the bottom drain hole must be open. The enclosure
class of the motor will then be lower. This helps prevent
condensation in the motor as the motor becomes self-venting,
and it allows water and humid air to escape.
The motor has a plugged drain hole on the drive side. You can
turn the flange 90 ° to both sides or 180 °.
Fig. 3 Drain holes
4.2 Electrical installation
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor and to the
signal relays. Wait at least 5 minutes before you
make any connections in the terminal box. Make
sure that the power supply cannot be accidentally
switched on.
DANGER
Electric shock
Death or serious personal injury
- Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
If the power supply cable is damaged, it must be replaced by the
manufacturer, the manufacturer's service partner or a similarly
qualified person.
The user or the installer is responsible for the installation of
TM05 3496 3512
correct grounding and protection according to local regulations.
All operations must be carried out by a qualified electrician.
4.2.1 Protection against electric shock, indirect contact
WARNING
Electric shock
- Death or serious personal injury
- Connect the motor to a protective ground and
provide protection against indirect contact in
accordance with local regulations.
Protective-ground conductors must always have a yellow/green
(PE) or yellow/green/blue (PEN) color marking.
Protection against power supply voltage transients
The motor is protected against power supply voltage transients in
accordance with EN 61800-3.
Motor protection
The motor requires no external motor protection. The motor
incorporates thermal protection against slow overloading and
blocking.
TM02 9037 1604
6
4.2.2 Cable requirements
RCD, type B
Cable cross-section
DANGER
Electric shock
Death or serious personal injury
- Always comply with local regulations as to cable
cross-sections.
Single-phase supply
Conductor type
Solid
Stranded0.5 - 2.530-12
Three-phase supply
Conductor
material
Copper
Cross section
2
[mm
][AWG]
0.5 - 2.528-12
Single-phase supply voltage
• 1 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
If you want to supply the motor through an IT
network, make sure that you have a suitable motor
variant. If you are in doubt, contact Grundfos.
The wires in the motor terminal box must be as short as possible.
Excepted from this is the separated ground conductor which must
be so long that it is the last one to be disconnected in case the
cable is inadvertently pulled out of the cable entry.
For maximum backup fuse, see section 10.3.1 Supply voltage.
English (US)
Conductor type
Solid
Stranded0.5 - 1018-8
Conductors
Typ e
Stranded or solid copper conductors.
Temperature rating
Temperature rating for conductor insulation: 140 °F (60 °C).
Temperature rating for outer cable sheath: 167 °F (75 °C).
4.2.3 Power supply
Conductor
material
Copper
Cross section
2
][AWG]
[mm
0.5 - 1018-8
DANGER
Electric shock
- Death or serious personal injury
- Use the recommended fuse size. See section
10.3.1 Supply voltage.
TM05 4034 1912TM05 3494 1512
Fig. 4 Example of a power supply-connected motor with
power supply switch, backup fuse and additional
protection
Fig. 5 Power supply connection, single-phase motors
7
English (US)
L1
L2
L3
L2
L1
L3
PE
RCD, type B
Three-phase supply voltage
• 3 x 440-480 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
The wires in the motor terminal box must be as short as possible.
Excepted from this is the separated ground conductor which must
be so long that it is the last one to be disconnected in case the
cable is inadvertently pulled out of the cable entry.
In order to avoid loose connections, make sure that you have
pressed home the terminal block for L1, L2 and L3 in its socket
when you connect the supply cable.
For maximum backup fuse, see section 10.4.1 Supply voltage.
4.2.4 Additional protection
DANGER
Electric shock
Death or serious personal injury
- Only use residual-current circuit breakers (ELCB,
GFCI, RCD) of type B.
The residual-current circuit breaker must be marked with the
following symbol:
If you want to supply the motor through an IT
network, make sure that you have a suitable motor
variant. If you are in doubt, contact Grundfos.
Corner grounding is not allowed for supply voltages
above 3 x 480 V, 50/60 Hz.
Fig. 6 Example of a power supply-connected motor with
power supply switch, backup fuses and additional
protection
Fig. 7 Power supply connection, three-phase motors
The total leakage current of all the electrical equipment in the
installation must be taken into account. You find the leakage
current of the motor in sections 10.3.2 Leakage current and
10.4.2 Leakage current (AC).
This product can cause a direct current in the protective ground
conductor.
Overvoltage and undervoltage protection
Overvoltage and undervoltage may occur in case of unstable
power supply or a faulty installation. The motor is stopped if the
voltage falls outside the permissible voltage range. The motor
restarts automatically when the voltage is again within the
permissible voltage range. Therefore, no additional protection
relay is required.
The motor is protected against transients from the
TM05 3942 1812TM05 3495 1512
power supply according to EN 61800-3. In areas with
high lightning intensity, we recommend external
lightning protection.
Overload protection
If the upper load limit is exceeded, the motor automatically
compensates for this by reducing the speed and stops if the
overload condition persists.
The motor remains stopped for a set period. After this period, the
motor automatically attempts to restart. The overload protection
prevents damage to the motor. Consequently, no additional motor
protection is required.
Overtemperature protection
The electronic unit has a built-in temperature sensor as an
additional protection. When the temperature rises above a certain
level, the motor automatically compensates for this by reducing
the speed and stops if the temperature keeps rising. The motor
remains stopped for a set period. After this period, the motor
automatically attempts to restart.
Protection against phase unbalance
Three-phase motors must be connected to a power supply with a
quality corresponding to IEC 60146-1-1, class C, to ensure
correct motor operation at phase unbalance. This also ensures
long life of the components.
8
4.2.5 Connection terminals
The descriptions and terminal overviews in this section apply to
both single- and three-phase motors.
For maximum torques, see section Torques, page 64.
Connection terminals, LCSE and VLSE
LCSE and VLSE pumps have a number of inputs and outputs
enabling the pumps to be used in advanced applications where
many inputs and outputs are required.
The pumps have these connections:
• three analog inputs
• one analog output
• two dedicated digital inputs
• two configurable digital inputs or open-collector outputs
• Grundfos Digital Sensor input and output
• two Pt100/1000 inputs
• two LiqTec sensor inputs
• two signal relay outputs
• GENIbus connection.
See fig. 8.
Digital input 1 is factory-set to be start-stop input
where open circuit results in stop. A jumper has been
factory-fitted between terminals 2 and 6. Remove the
jumper if digital input 1 is to be used as external
start-stop or any other external function.
English (US)
DANGER
Electric shock
Death or serious personal injury
- Make sure that the wires to be connected to the
connection groups below are separated from each
other by reinforced insulation in their entire
lengths.
• Inputs and outputs
All inputs and outputs are internally separated from the power
supply-conducting parts by reinforced insulation and galvanically
separated from other circuits. All control terminals are supplied by
protective extra-low voltage (PELV), thus ensuring protection
against electric shock.
• Start-stop: (Digital input 1) = Terminals 2 and 6
• External analog signal input: (Analog input 2) = Terminals 7
and 23
• GENIbus Terminals A, Y and B
• Signal relay outputs
– Signal relay 1:
LIVE:
You can connect supply voltages up to 250 VAC.
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
– Signal relay 2:
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
• Power supply (terminals N, PE, L or L1, L2, L3, PE).
* If you use an external supply source, there must be a
connection to GND.
Fig. 8 Connection terminals, LCSE and VLSE pumps
10
21LiqTec sensor input 1
20GND
22LiqTec sensor input 2
LiqTec sensor input
(white conductor)
Ground (brown and black
conductors)
LiqTec sensor input
(blue conductor)
Digital input/output,
10DI3/OC1
configurable.
Open collector: Max. 24 V
resistive or inductive.
Analog input:
4AI1
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2DI1Digital input, configurable
5+5 V
Supply to potentiometer and
sensor
6GNDGround
TM05 3509 3512
AGENIbus, AGENIbus, A (+)
YGENIbus, YGENIbus, GND
BGENIbus, BGENIbus, B (-)
3GNDGround
15+24 VSupply
8+24 VSupply
26+5 V
Supply to potentiometer and
sensor
23GNDGround
25GDS TX
Grundfos Digital Sensor
output
24GDS RXGrundfos Digital Sensor input
Analog input:
7AI2
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
Digital input 1 is factory-set to be start-stop input
where open circuit results in stop. A jumper has been
factory-fitted between terminals 2 and 6. Remove the
jumper if digital input 1 is to be used as external
start-stop or any other external function.
DANGER
Electric shock
Death or serious personal injury
- Make sure that the wires to be connected to the
connection groups below are separated from each
other by reinforced insulation in their entire
lengths.
• Inputs and outputs
All inputs and outputs are internally separated from the power
supply-conducting parts by reinforced insulation and galvanically
separated from other circuits. All control terminals are supplied by
protective extra-low voltage (PELV), thus ensuring protection
against electric shock.
• Start-stop: (Digital input 1) = Terminals 2 and 6
• External analog signal input: (Analog input 2) = Terminals 7
and 23
GENIbus Terminals A, Y and B
• Signal relay outputs
– Signal relay 1:
LIVE:
You can connect supply voltages up to 250 VAC to the
output.
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
– Signal relay 2:
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
• Power supply (terminals N, PE, L or L1, L2, L3, PE).
English (US)
11
English (US)
3
15
8
26
23
25
24
7
B
Y
6
5
2
4
10
A
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
NC
C2
NO
NC
C1
NO
+24 V*
+
+
+24 V*/5 V*
+24 V*
+24 V*
OC
DI
GND
TerminalTypeFunction
NC
C1Common
NO
Normally closed
contact
Normally open
contact
Signal relay 1
(LIVE or PELV)
* If you use an external supply source, there must be a
connection to GND.
Fig. 9 Connection terminals, optional for LCSE and VLSE
pumps
NC
C2Common
NO
Normally closed
contact
Normally open
contact
Signal relay 2
(PELV only)
Digital input/output,
10DI3/OC1
configurable.
Open collector: Max. 24 V
resistive or inductive.
Analog input:
4AI1
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2DI1Digital input, configurable
5+5 V
Supply to potentiometer and
sensor
6GNDGround
AGENIbus, AGENIbus, A (+)
YGENIbus, YGENIbus, GND
BGENIbus, BGENIbus, B (-)
3GNDGround
15+24 VSupply
8+24 VSupply
26+5 V
Supply to potentiometer and
sensor
23GNDGround
TM05 3510 3512
25GDS TX
24GDS RX
Grundfos Digital Sensor
output
Grundfos Digital Sensor
input
Analog input:
7AI2
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
12
4.2.6 Signal cables
A
Y
B
A
Y
B
1
2
3
1
2
3
Motor
A
Y
B
A
Y
B
1
2
1
2
Motor
• Use screened cables with a cross-sectional area of minimum
28 AWG and maximum 16 AWG for the external on/off switch,
digital inputs, setpoint and sensor signals.
• Connect the screens of the cables to the frame at both ends
with good connection. The screens must be as close as
possible to the terminals. See fig. 10.
Fig. 10 Stripped cable with screen and wire connections
• Always tighten screws for frame connections whether a cable
is fitted or not.
• The wires in the motor terminal box must be as short as
possible.
Connection of E+pump to Danfoss pressure sensor MBS3000
The blue wire of the pressure sensor is connected to the #4
terminal of the E-pump. The brown wire of the pressure sensor is
connected to the #8 terminal of the E-pump.
See section 4.2.6 Signal cables for additional details.
4.2.7 Bus connection cable
New installations
For the bus connection, use a screened 3-core cable with a
cross-sectional area of minimum 28 AWG and maximum 16 AWG.
If the motor is connected to a unit with a cable clamp which is
identical to the one on the motor, connect the screen to this cable
clamp.
If the unit has no cable clamp leave the screen unconnected at
this end. See fig. 11.
TM02 1325 4402 TM05 1533 2911
Fig. 11 Connection with screened 3-core cable
Replacing a motor
• If a 2-core cable is used in the installation, connect it as shown
in fig. 12.
Fig. 12 Connection with screened 2-core cable
English (US)
TM05 3973 1812TM02 8842 0904
• If a screened 3-core cable is used in the installation, follow the
instructions in section New installations.
13
English (US)
A
B
B
C
D
A
A
A
B
A
4.3 Installing a communication interface module
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor and to the
signal relays. Wait at least 5 minutes before
starting any work on the motor. Make sure that the
power supply cannot be accidentally switched on.
Always use an antistatic service kit when handling
electronic components. This prevents static electricity
from damaging the components.
When unprotected, place the component on the
antistatic cloth.
3. Remove the securing screw (fig. 16, A).
TM06 4082 1515TM06 4083 1515TM06 4195 1615
Fig. 16 Removing the securing screw
4. Fit the CIM module by aligning it with the three plastic holders
(fig. 17, A) and the connecting plug (fig. 17, B). Press home
the module using your fingers.
Fig. 13 Antistatic service kit
1. Loosen the four screws (fig. 14, A) and remove the terminal
box cover (fig. 14, B).
Fig. 14 Removing the terminal box cover
2. Remove the CIM cover (fig. 15, A) by pressing the locking tab
(fig. 15, B) and lifting the end of the cover (fig. 15, C). Then lift
the cover off the hooks (fig. 15, D).
TM06 4462 2315TM06 4081 1515TM06 4084 1515
Fig. 17 Fitting the CIM module
5. Fit and tighten securing screw (fig. 16, A) to 1.3 Nm.
6. Make the electrical connections to the CIM module as
described in the instructions delivered with the module.
7. Connect the cable screens of the bus cables to ground via
one of the ground clamps (fig. 18, A).
Fig. 18 Connecting the cable screens to ground
Fig. 15 Removing the CIM cover
14
8. Route the wires for the CIM module. See the example in fig.
FCC
19.
Fig. 19 Example of wire routing
9. Fit the CIM cover.
10. If the CIM module is supplied with an FCC label, then place
this on the terminal box. See fig. 20.
4.4 Changing the position of the control panel
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply to the motor and to the
signal relays. Wait at least 5 minutes before
starting any work on the motor. Make sure that the
power supply cannot be accidentally switched on.
You can turn the control panel 180 °. Follow the instructions
below.
1. Loosen the four screws (TX25) of the terminal box cover.
TM06 4085 1515TM05 7028 0413
Fig. 21 Loosening the screws
2. Remove the terminal box cover.
English (US)
TM05 5351 3612TM05 5352 3612TM05 5353 3612
Fig. 20 FCC label
11. Fit the terminal box cover (fig. 14, B) and cross-tighten the
four mounting screws (fig. 14, A) to 6 Nm.
Make sure that the terminal box cover is aligned with
the control panel. See section 4.4 Changing the
position of the control panel.
Fig. 22 Removing the terminal box cover
3. Press and hold in the two locking tabs (fig. 23, A) while gently
lifting the plastic cover (fig. 23, B).
Fig. 23 Lifting the plastic cover
15
English (US)
4. Turn the plastic cover 180 °.
Do not twist the cable more than 90 °.
Fig. 24 Turning the plastic cover
5. Position the plastic cover correctly on the four rubber pins (fig.
25, C). Make sure that the locking tabs (fig. 25, A) are placed
correctly.
Fig. 25 Positioning the plastic cover
6. Fit the terminal box cover, and make sure that it is also turned
180 ° so that the buttons on the control panel are aligned with
the buttons on the plastic cover.
7. Tighten the four screws (TX25) with 5 Nm.
Fig. 26 Fitting the terminal box cover
5. Product introduction
5.1 Product description
Grundfos E-pumps are fitted with frequency-controlled
permanent-magnet motors for single-phase or three-phase power
supply connection.
5.1.1 Pumps without factory-fitted sensor
The pumps have a built-in PI controller and can be set for an
external sensor enabling the control of the following parameters:
• constant pressure
• constant differential pressure
• constant temperature
• constant differential temperature
TM05 5354 3612TM05 5355 3612TM05 5356 3612
• constant flow rate
• constant level
• constant curve
• constant other value.
The pumps have been factory-set to constant-curve control
mode. You can change the control mode with R100 or Grundfos
GO.
5.1.2 Pumps with factory-fitted pressure sensor
The pumps have a built-in PI controller and are set for a pressure
sensor enabling the control of the outlet pressure.
The pumps have been factory-set to constant-pressure control
mode. The pumps are typically used to keep a constant pressure
in variable-demand systems.
5.1.3 Settings
The description of settings applies both to pumps without
factory-fitted sensor and to pumps with a factory-fitted pressure
sensor.
Setpoint
You can set the desired setpoint in three ways:
• on the pump control panel
• via an input for external setpoint signal
• with the Grundfos wireless R100 remote control or Grundfos
GO.
Other settings
Make all other settings with R100 or Grundfos GO.
You can read important parameters, such as the actual value of
the control parameter and power consumption, via R100 or
Grundfos GO.
If special or customized settings are required, use Grundfos PC
Tool. Contact your local Grundfos company for more information.
16
5.1.4 Radio communication
Env.Type :
Serial no :
SFCL:
PF:
PBFMHMIEff
n max:
CIMWgt
:
DE
:
kg
NDE
:
T
amb
:
:
FAA
V
~
P.C.
:
Made in Hungary
OUTPUT
VARIANT
INPUT
TEFC
Type
:
P.N.
:
U
in
:
I
1/1
:
f
in
HpHzP2
I
SF Amp:
rpm
:::
:
::
:
Xxxxxxxxxxx
E.P. Motor
DK - 8850 Bjerringbro, Denmark
Env.T
yyp
p
:
S
a
o
:
SF
C
:
P
:
Effn W
g
g
t
:
DE
:
k
g
g
NDE:T
amb
:
:
FAAVP
.C.
:
PU
TTE
C
T
yp
yp
e
:
P.N.
:
U
n
:
I
1/1
:
finHzP
I
S
p
p
:
:
PB
FM
HMICIM
VARIANT
Hp
rpm
::
:
:
PB
:
HMI
:
C
:
H
prpm
Env.Type :
Serial no :
SFCL:
PF:
PBFMHMIEff
n max:
CIMWgt
:
DE
:
kg
NDE
:
T
amb
:
:
FAA
V
~
P.C.
:
Made in Hungary
OUTPUT
VARIANT
INPUT
TEFC
Type
:
P.N.
:
U
in
:
I
1/1
:
f
in
HpHzP2
I
SF Amp:
rpm
:::
:
::
:
Xxxxxxxxxxx
E.P. Motor
DK - 8850 Bjerringbro, Denmark
Env.T
yyp
p
:
S
a
l
n
o
:
SF
C
:
P
:
Eff
n
W
g
g
t
:DE:
k
g
g
NDE
:
T
amb
:
:
FAAVP
.C.
:
PU
TTE
C
T
yp
yp
e
:
P.N.
:
U
n
:
I
1/1
:
f
n
HzP
I
S
p
p
:
:
PBFM
HMI
CIM
VARIANT
Hp
rpm
:
:
::
PB
:
C
:
H
prpm
FM
:
This product incorporates a radio module for remote control
which is a class 1 device and which you can use anywhere in the
EU without restrictions.
For use in USA and Canada, see page 66.
Some variants of the product and products sold in China and
Korea have no radio module.
This product can communicate with Grundfos GO and other
products of the same type via the built-in radio module.
In some cases, an external antenna may be required. Only
Grundfos-approved external antennas may be connected to this
product, and only by a Grundfos-approved installer.
5.1.5 Battery
A Li-ion battery is fitted in LCSE and VLSE pumps. The Li-ion
battery complies with the Battery Directive (2006/66/EC). The
battery does not contain mercury, lead and cadmium.
5.2 Identification
5.2.1 Identification of functional module
You can identify the fitted module in one of the following ways:
Grundfos GO
You can identify the functional module in the "Fitted modules"
menu under "Status".
Pump display
For pumps fitted with the advanced control panel, you can identify
the functional module in the "Module type" menu under "Status".
Motor nameplate
You can identify the fitted module on the motor nameplate. See
fig. 27.
5.2.2 Identification of control panel
You can identify the fitted module in one of the following ways:
Grundfos GO
You can identify the control panel in the "Fitted modules" menu
under "Status".
Pump display
For pumps fitted with the advanced control panel, you can identify
the control panel in the "Module type" menu under "Status".
Motor nameplate
You can identify the fitted control panel on the motor nameplate.
See fig. 28.
IN
i
eri
e
F
i
L
F Am
F
IM
Fig. 28 Identification of control panel
VariantDescription
HMI 300Advanced control panel
English (US)
TM06 4013 1415
5.3 Bus signal
IN
i
eri
e
F
L
F Am
F
IM
Fig. 27 Identification of functional module
VariantDescription
FM 300Advanced functional module
The pump supports serial communication via an RS-485 input.
The communication is carried out according to the Grundfos
GENIbus protocol and enables connection to other pumps as well
as a building management system or another external control
system.
Via a bus signal, you can remote-set pump operating parameters,
such as setpoint and operating mode. At the same time, the pump
can, via the bus, provide status information about important
parameters, such as actual value of control parameter, input
power and fault indications.
Contact Grundfos for further information.
TM06 1889 3314
If you use a bus signal, the number of settings
available via R100 or Grundfos GO are reduced.
17
English (US)
A
5.4 Grundfos Eye
The operating condition of the pump is indicated by Grundfos Eye
on the control panel. See fig. 29, A.
Fig. 29 Grundfos Eye
Grundfos EyeIndicationDescription
No lights are on.
The two opposite green indicator lights are rotating in
the direction of rotation of the pump when seen from
the non-drive end.
The two opposite green indicator lights are
permanently on.
One yellow indicator light is rotating in the direction
of rotation of the pump when seen from the non-drive
end.
One yellow indicator light is permanently on.
The two opposite red indicator lights flash
simultaneously.
The green indicator light in the middle flashes quickly
four times.
TM05 5993 4312
The power is off.
The pump is not running.
The power is on.
The pump is running.
The power is on.
The pump is not running.
Warning.
The pump is running.
Warning.
The pump is stopped.
Alarm.
The pump is stopped.
This is a feedback signal which the pump gives in
order to ensure identification of itself.
The green indicator light in the middle flashes
continuously.
Grundfos GO or another pump is trying to
communicate with the pump. Press on the
pump control panel to allow communication.
The green indicator light in the middle is permanently
on.
Remote control with Grundfos GO via radio.
The pump is communicating with Grundfos GO via
radio connection.
The green indicator light in the middle flashes quickly
while Grundfos Go is exchanging data with the
pump. It takes a few seconds.
Remote control with Grundfos GO via infrared
light.
The pump is receiving data from Grundfos GO via
infrared communication.
18
5.5 Signal relays
NCNO
C
NCNOCNCNOCNCNOCNCNO
C
C
NO NCCNO NCCNO NC
NCNOCNCNO
C
C
NO NCCNO NC
NCNOCNCNOCNCNO
C
NCNOCNCNO
C
C
NO NC
NCNOCNCNO
C
C
NO NCCNO NCCNO NCCNO NC
C
NO NCCNO NC
NCNO
C
NCNO
C
C
NO NC
NCNOCNCNO
C
C
NO NC
NCNO
C
C
NO NC
C
NO NCCNO NC
NCNO
C
C
NO NC
NCNO
C
C
NO NCCNO NC
NCNO
C
C
NO NC
NCNO
C
NCNOCNCNOCNCNO
C
C
NO NC
NCNO
C
C
NO NC
NCNO
C
C
NO NC
NCNOCNCNO
C
The pump has two outputs for potential-free signals via two
internal relays.
You can set the signal outputs to "Operation", "Pump running",
"Ready", "Alarm" and "Warning".
The functions of the two signal relays appear from the table
below:
English (US)
DescriptionGrundfos Eye
The power is off.
Off
The pump runs in
"Normal" mode.
Green, rotating
The pump runs in
"Manual" mode.
Green, rotating
The pump is in
operating mode
"Stop".
Green, steady
Warning, but the
pump is running.
Yellow, rotating
Warning, but the
pump runs in "Manual"
mode.
Yellow, rotating
Warning, but the
pump was stopped via
a "Stop" command.
Yellow, steady
Alarm, but the pump is
running.
Red, rotating
Contact position of signal relays when activated
"Operation"
"Pump
running"
"Ready""Alarm""Warning"
"Operating
mode"
-
"Normal",
"Min." or
"Max."
"Manual"
"Stop"
"Normal",
"Min." or
"Max."
"Manual"
"Stop"
"Normal",
"Min." or
"Max."
Alarm, but the pump
runs in "Manual"
mode.
The pump is stopped
due to an alarm.
The pump is stopped
due to "Low-flow stop
function".
"Manual"
Red, rotating
"Stop"
Red, flashing
"Normal"
Green, steady
19
English (US)
1
2
3
4
5
6
6. User interfaces
WARNING
Hot surface
Death or serious personal injury
- Only touch the buttons on the display as the
product may be very hot.
You can make the pump settings by means of the following user
interfaces:
Control panels
• Advanced control panel.
See section 6.1 Advanced control panel.
Remote controls
• Grundfos GO.
See section 6.2 Grundfos GO.
• Grundfos R100 remote control.
See section 6.3 R100 remote control.
If the power supply to the pump is switched off, the settings are
stored.
6.1 Advanced control panel
The pumps can be fitted with the advanced control panel as an
option.
Fig. 30 Advanced control panel
Pos. Symbol Description
1
2-Graphical color display.
3It goes one step back.
4
TM05 4849 1013
5
Grundfos Eye
This shows the operating status of the pump.
For further information, see section 4.4 Changing
the position of the control panel.
With these buttons you can navigate between
main menus, displays and digits.
When you change the menu, the display always
shows the top display of the new menu.
With these buttons you can navigate between
submenus.
They change value settings.
Note: If you have disabled the possibility to make
settings with the "Enable/disable settings"
function, then you can enable it again temporarily
by pressing these buttons simultaneously for at
least 5 seconds. See section 7.29 "Buttons on
product" ("Enable/disable settings").
It saves changed values, resets alarms and
expands the value field.
It enables radio communication with Grundfos
GO and other products of the same type.
When you try to establish radio communication
between the pump and Grundfos GO or another
pump, the green indicator light in Grundfos Eye
flashes. A note also appears in the pump display
stating that a wireless device wants to connect to
the pump. Press on the pump control panel to
allow radio communication with Grundfos GO and
other products of the same type.
This makes the pump ready for operation/starts
and stops the pump.
Start:
If you press the button when the pump is
stopped, the pump only starts if no other
functions with higher priority have been enabled.
See section 8. Description of settings.
Stop:
If you press the button when the pump is running,
the pump is always stopped. When you stop the
pump via this button, the
icon appears in the
bottom of the display.
6This button goes to the "Home" menu.
20
6.1.1 Home display
Fig. 31 Example of "Home" display
Pos.SymbolDescription
"Home"
This menu shows up to four user-defined
parameters. You can select parameters
1
2-
3-
4-
5
6
7
8
9
6.1.2 Startup guide
The pump incorporates a startup guide which is started at the first
startup. See section 7.37 "Run start-up guide". After the startup
guide, the main menus appear in the display.
shown as shortcut icon , and when
pressing you go directly to the
"Settings" display for the selected
parameter.
"Status"
This menu shows the status of the pump
and system as well as warnings and
alarms.
"Settings"
This menu gives access to all setting
parameters. You can make detailed
settings of the pump in this menu.
See section 7. Description of functions.
"Assist"
This menu enables assisted pump setup,
provides a short description of the control
modes and offers fault advice.
See section 7.40 "Assist".
This symbol indicates that the pump has
been stopped via the
This symbol indicates that the pump is
functioning as master pump in a multipump
system.
This symbol indicates that the pump is
functioning as a slave pump in a multipump
system.
This symbol indicates that the pump is
operating in a multipump system. See
section 7.44 "Multi-pump setup" ("Setup of
multi-pump system").
This symbol indicates that the possibility to
make settings has been disabled for
protective reasons. See section
7.29 "Buttons on product" ("Enable/disable
settings").
button.
English (US)
TM06 8915 0417
21
Loading...
+ 49 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.