Grundfos UPS 26-150, UPS 43-100, UPS 50-60 Installation And Operating Instructions Manual

Grundfos UP XL
3191277
Maintenance-free circulators with insulating shell (if equipped)
Installation and operating instructions
GRUNDFOS INSTRUCTIONS
Conforms to UL STD 514C Certified to CSA STD C22.2 No. 18.2
English (US)
Note
Caution
English (US) Installation and operating instructions
Original installation and operating instructions.
CONTENTS
1. Symbols used in this document
2. Limited warranty
3. Safety warning
3.1 Read this booklet
3.2 Electrical work
4. Pre-installation checklist
4.1 Confirm you have the correct pump
4.2 Check the condition of the pump
4.3 Verify electrical requirements
4.4 Pumped liquid requirements
5. Installation procedures
5.1 Piping considerations
5.2 Changing the terminal box position
5.3 Electrical connection
5.4 Insulating shells (if equipped)
6. Starting the pump
6.1 Vent the piping system
6.2 Speed selection
7. Fault finding
7.1 Fault finding chart
7.2 Preliminary checks
7.3 Current measurement
7.4 Insulation resistance (lead-to-ground)
7.5 Winding resistance (line-to-line)
7.6 Resistance tables
8. Replacing components
8.1 Removing the pump head
8.2 Fitting the pump head
8.3 Replacing the terminal box or capacitor
9. Additional technical data
10. Disposal
Page
10
10 10
11
11 12 12 13 13 13
14
14 15
16
17 17

1. Symbols used in this document

Warning If these safety instructions are not
observed, it may result in personal
2 3 4
4 4
4
4 4 5 5
6
6 7 8 9
injury.
Warning If these instructions are not
observed, it may lead to electric shock with consequent risk of serious personal injury or death.
Warning The surface of the product may be
so hot that it may cause burns or personal injury.
Notes or instructions that make the job easier and ensure safe operation.
If these safety instructions are not observed, it may result in malfunction or damage to the equipment.
Warning Prior to installation, read these
installation and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice.
2

2. Limited warranty

Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only to be free of defects in material and workmanship for a period of 36 months from date of manufacture. Grundfos' liability under this warranty shall be limited to repairing or replacing at Grundfos' option, without charge, F.O.B. Grundfos' factory or authorized service station, any product of Grundfos' manufacture. Grundfos will not be liable for any costs of removal, installation, transportation, or any other charges which may arise in connection with a warranty claim.
Products which are sold but not manufactured by Grundfos are subject to the warranty provided by the manufacturer of said products and not by Grundfos' warranty. Grundfos will not be liable for damage or wear to products caused by abnormal operating conditions, accident, abuse, misuse, unauthorized alteration or repair, or if the product was not installed in accordance with Grundfos' printed installation and operating instructions.
To obtain service under this warranty, the defective product must be returned to the distributor or dealer of Grundfos' products from which it was purchased together with proof of purchase and installation date, failure date, and supporting installation data. Unless otherwise provided, the distributor or dealer will contact Grundfos or an authorized service station for instructions. Any defective product to be returned to Grundfos or a service station must be sent freight prepaid; documentation supporting the warranty claim and/or a Return Material Authorization must be included if so instructed.
GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSSES, OR EXPENSES ARISING FROM INSTALLATION, USE, OR ANY OTHER CAUSES. THERE ARE NO EXPRESS OR IMPLIED WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH EXTEND BEYOND THOSE WARRANTIES DESCRIBED OR REFERRED TO ABOVE.
Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages and some jurisdictions do not allow limit actions on how long implied warranties may last. Therefore, the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from jurisdiction to jurisdiction.
English (US)
3
English (US)

3. Safety warning

4. Pre-installation checklist

3.1 Read this booklet

This booklet is designed to help a certified installer to install, begin operation of, and troubleshoot the Grundfos Small UP and UPS pumps.
Following the instructions will ensure safe, trouble-free operation.
This booklet should be left with the owner of the pump for future reference and information regarding its operation. Should the owner experience any problems with the pump, a certified professional should be contacted.

3.2 Electrical work

All electrical work should be performed by a qualified electrician in accordance with the latest edition of the National Electrical Code, local codes and regulations.
Warning A faulty motor or wiring can cause
electrical shock that could be fatal, whether touched directly or conducted through standing water. For this reason, proper grounding of the pump to the power supply's grounding terminal is required for safe installation and operation.
In all installations, the above-ground metal plumbing should be connected to the power supply ground as described in the National Electrical Code. All wiring must comply with the National Electrical Code, state, and local regulations.

4.1 Confirm you have the correct pump

• Read the pump nameplate to ensure it is the one you ordered.
• Compare the pump's nameplate data and its performance curve (for head, gpm, etc.) with the application in which you plan to install it.
• Will the pump do what you expect it to do?

4.1.1 Pump to system type recommendations

Open systems (i.e. potable water): Stainless steel or bronze volute (pump housing) only.
Closed systems (i.e. airless, non-potable water): Cast iron, stainless steel, or bronze volute (pump housing).
Other considerations regarding Grundfos small UP and UPS pumps:
• These pumps are intended for indoor use only.
• If installed outdoors the pump must be protected by an appropriate, well ventilated, water-tight enclosure to keep out moisture and dirt.
• Minimum ambient temperatures must be no lower than 33 °F ( 1 ° C ).
• For ambient and fluid temperature see sections 4.4 Pumped liquid requirements and 9. Additional technical data.

4.2 Check the condition of the pump

The pump's shipping carton is specially designed around the pump during production to prevent damage.
As a precaution, it should remain in the carton until you are ready to install it. At that point, look at the pump and examine it for any damage that may have occurred during shipping.
Examine any other parts of the shipment as well for any visible damage. Once the pump has been removed from the box, care should be taken NOT to drop or mishandle the pump.
Box contents:
• one pump
• two gaskets (flanged units only)
• one Installation and Operation Instruction (I&O).
4

4.3 Verify electrical requirements

Note
Caution
Verify the electrical supply to be certain the voltage, phase and frequency match that of the pump motor. The proper operating voltage and other electrical information can be found on the pump nameplate.
This pump's motor is designed to run on ± 10 % of the nameplate-rated voltage.

4.4 Pumped liquid requirements

Warning The Grundfos Small UP/UPS pump
is intended for use with water only. The pump must not be used for the transfer of flammable liquids such as diesel oil, gasoline, and similar liquids.
The pump is not for pool or marine use.
The pump can be used to circulate:
• Potable hot water.
• Water containing glycol for hydronic heating (see section 9. Additional technical data for additional limitations).
• Cooling water.
In domestic hot-water systems it is advisable to use stainless steel pump housing versions of this pump.
All pump types (stainless, bronze or cast iron pump housing) should not be used in water with a degree of hardness lower than 14 grains per gallon of hardness.
Fluids should be clean and should not contain solid particles, fibers, or mineral oils.
If the pump is installed in a heating system, the water should meet the requirements of accepted standards on water quality in heating systems.
The fluid should not contain solid particles, fibers, or mineral oils.
The pump is lubricated and cooled by the liquid being pumped. Therefore, the pumped liquid must always be allowed to circulate through the pump.
Extended periods without circulation will cause premature wear to the bearings and excessive motor heat.
The pumped liquid must meet the temperature requirements listed in the following charts.
Fluid must never be allowed to freeze during non-operational periods.
Open systems
(domestic, potable hot water)
Fluid Ambient
Min. 36 °F (2 °C) 33 °F (1 °C) Max. < 149 °F (65 °C) 100 °F (38 °C)
In domestic hot-water systems, it is recommended to keep the liquid temperature below 149 °F (65 °C) to eliminate the risk of lime precipitation.
(non-potable heating or cooling airless
Min. All
Max.
Max. 50 % glycol at 15 °F (-9.5 °C) liquid
(Hydraulic performance change can be expected.)
Closed systems
fluid)
Pump
models
UPS 26-150
UPS 43-100
UPS 50-60
Water and glycol mix
Liquid Ambient
36 °F
(2 °C)
230 °F
(110 °C)
230 °F
(110 °C)
212 °F
(100 °C)
33 °F
(1 °C)
100 °F
(38 °C)
100 °F
(38 °C)
100 °F
(38 °C)
English (US)
5
English (US)

5. Installation procedures

Warning Never make any connections in the
pump terminal box unless the electrical supply has been switched off.
The pump should not be connected to the electrical system until it has been properly installed in the piping system.
Warning Risk of electrical shock - this pump
has not been investigated for use in swimming pool or marine areas.

5.1 Piping considerations

When making piping connections, be sure to follow the piping manufacturer's recommendations and all code requirements for piping material.
Thoroughly clean and flush all dirt and sediment from the system before attempting to install the pump.

5.1.1 Location in the piping line

The pump should never be located at the lowest point of the piping system (where dirt and sediment collect), nor should it be located at the highest point of the piping system (where air accumulates).
Warning The pump must be positioned so
that someone cannot accidentally come into contact with the hot surfaces of the pump.
When installing the pump into the piping system, Grundfos recommends that pressure gauges be installed in the inlet and discharge flanges or pipes. This will allow the pump and system performance to be checked.
Do not block the pipe plugs in the pump housing flanges by locating the terminal box over these plugs.

5.1.2 Mounting positions

The arrows on the pump housing indicate the direction of water flow. The pump may be installed in vertical or horizontal piping, but the motor shaft must always remain horizontal, as shown in fig. 1.
Fig. 1 Installation positions

5.1.3 Terminal box positions

At the bottom of the stator, closest to the pump housing, there are three drain holes to allow condensed water to escape. The drain holes shall not be blocked for any reason and one drain hole must always point downward.
There is not a drain hole directly below the terminal box; therefore the terminal box must be positioned in one of the positions shown in fig. 1 or fig. 2.
TM04 5646 3609
6
Loading...
+ 14 hidden pages